134 As of: 06/2004 - Subject to change without prior notice
High Pressure Centrifugal PumpsProduct Overview
High Pressure Centrifugal Pumps Product Overview
Wilo-Economy MHI Duty chart
• Non self-priming pumps for:– Water supply and pressure boosting– Commerce and industry,– Cooling water circuits,– Washing and sprinkling systems
Wilo-Multivert MVIS Duty chart
• Non self-priming pumps for:– Water supply and pressure boosting
systems
Wilo-Multivert MVI Duty chart
• Non self-priming pumps for:– Water supply and pressure boosting– Fire extinguishing systems– Boiler feed systems– Industrial circulation systems– Process technology– Cooling water circuits– Washing and sprinkling systems
60
50
40
30
20
10
00 2 3 4 5 6 7 8 10 20
H[m
]
Q[m /h]3
Wilo-Economy-MHI50 Hz
MHI200
MHI1600
MHI400
MHI800
100
80
60
40
20
00 2 4 6 8 10
Wilo-Multivert-MVIS50 Hz
MVIS200
MVIS800
MVIS400
Q[m3/h]
H[m
]
200
160
120
80
40
0
MVI100
MVI200
MVI400
MVI800
MVI
Wilo-Multivert MVI 50 Hz
0 1 2 3 4 5 6 7 8 10 15
H[m
]
1600-6
Q[m3/h]
200
160
120
80
40
0
MVI5200
MVI3200
MVI1600
Wilo-Multivert MVI 50 Hz
4 5 6 7 8 10 20 30
H[m
]
Q[m3/h]
135Vesion: 06/2004 - Subject to technical modifications
High Pressure Centrifugal PumpsProduct Advantages
High
pre
ssur
e ce
ntrif
ugal
pum
ps
Product Advantages
Wilo-Economy MHI
• All parts in contact with the fluid medium in stainless steel 1.4301 (AISI 304)• Compact construction• All relevant components are KTW and WRAS approved
Wilo-Multivert MVIS
• Low noise (up to 20 dB [A] quieter than conventional pumps)• All parts in contact with the fluid medium are corrosion proof
• Glandless pump technology• All relevant components are KTW and WRAS approved
Wilo-Multivert MVI
• All parts in contact with the fluid medium are corrosion proof
• Drive via IEC standard motors• All relevant components are KTW and WRAS approved• All parts in contact with the fluid medium in stainless steel1.4301 (AISI 304),
with the exception of MVI 16.. to 52..: Pump base EN-GJL-250, cataphoresis coated.Other materials optional.
138 As of: 06/2004 - Subject to change without prior notice
High Pressure Centrifugal PumpsEquipment/Function
• = available, – = not available
Equipment/Function Wilo-
EconomyMHI
Wilo-Multivert
MVIS
Wilo-Multivert
MVI
Wilo-Economy
MHIE
Wilo-Multivert
MVISE
Wilo-Multivert
MVIE
Hydraulic data
Monobloc stainless steel pump • – – • – –
Inline stainless steel pump – • • – • •
Glandless pump – • – – • –
Self-venting – – – – • –
Mechanical seal (seals in both directions of rotation) • – • • – •
Hydraulic in 1.4301 • • 1.. to 16..-6 • • 2.. to 16..-6
Hydraulic in 1.4301Pump base in EN-GJL-250 – – 16.. to 52.. – – 16.. to 52..
Threaded connection • – – • – –
Oval flange, Round flange – • • – • •
Victaulic connections – – • – – •
Motor
3-phase-DIN motor – – • – – •
DM (3-phase motor) • • • • • •
EM (AC motor) • – • • – •
Integrated frequency converter – – –
•(Only DM ver-
sion, controlla-ble from
26 to 65 Hz)
•(Water cooled, adapted, con-tinuously con-trollable from20 to 50 Hz)
•(Controllable
from26 to 65 Hz)
Integrated frequency converter(Manual speed control in conjunction with control by remote signal 0...10 V / 4...20 mA M1/M3 or Automatic operation p = const. M2)
– – –•
(Only EM ver-sion)
–•
(Only EM ver-sion)
Integrated thermal motor protection•
(Only EM ver-sion)
– – • • •
Low water level protection – – – • • •
4-pole (n = 1,450 rpm) – – Optional – – –
Equipment/Scope of delivery
Oval mating flange Rp 1 up to Rp 11/2 – ••
(Only on ver-sion PN 16)
–•
(Only on ver-sion PN 16)
•
(Only on ver-sion PN 16)
Installation and operating manual • • • • • •
Options
Hydraulic in 1.4404 2.. to 8.. – 2.. to 16..-6 2.. to 4.. – 2.. to 16..-6
Hydraulic in 1.4404Pump base in EN-GJL-250 – – 16.. to 52.. – – 16.. to 52..
Other mechanical seals • – • • – •
Other standard motors – – • – – –
Other seal materials • – • • – •
139Vesion: 06/2004 - Subject to technical modifications
High Pressure Centrifugal PumpsTechnical Data
High
pre
ssur
e ce
ntrif
ugal
pum
ps
• = available, – = not available
Note on inlet pressure:The max. inlet pressure is calculated from the max. operating pressure of the systemminus the max. delivery head of the pump at Q = 0.
Note on materials:1.4301 satisfies AISI 304, 1.4404 satisfies AISI 316L.
Wilo-EconomyMHI
Wilo-Multivert MVIS
Wilo-Multivert MVI
Technical Data2.. 4.. 8.. 16.. 2.. 4.. 8.. 1.. 2.. 4.. 8.. 16..-6 16.. 32.. 52..
Approved fluidsDrinking, heating, process water • • •
Condensate • – •
Water-glycol mixture(Up to 40% Vol. glycol / from 10% Vol.glycol per-formance verification required)
• • •
Other fluid media(Without abrasive or fibrous particles, so long as they are non-aggressive to the respective pump materi-als.)
• • •
Power (at 50 Hz operation)
Flow, max. [m3/h] 5 8 12 25 4.5 8 14 3 5 8 14 25 25 50 70
Max. delivery head [m] 70 70 60 47 114 108 70 240 230 210 230 130 240 220 180
Fluid temperature [°C] -15 to +110 -10 to +50 -15 to +120
Ambient temperature [°C] 40 40 40
Operating pressure [bar] 10 16 16/25
Inlet pressure [bar] 6 6 10
Nominal speed [rpm] 2,950 2,800 2,950
MotorMains connection 1~ [V/Hz](Permissible voltage tolerance ± 10%)
230/50 or 220/60 –/– 230/50 or 220/60 (up to 1.5 kW)
Mains connection 3~ [V/Hz](Permissible voltage tolerance ± 10%)
230/50 or 220/60 400/50 Y or 380/60 Y
230/50 400/50 Y
230/50 or 220/60 (up to 4.0 kW)400/50 Y or 380/60 Y (from 4.0 kW)
Insulation class F F F
Radio interference level EN 61800-3 N EN 61800-3
Protection class IP 54 IP 44 IP 55
Pipe Connections
Nominal diameter, pipe connection [Rp] 1 1 11/4 11/2 1 11/4 11/2 – – – – – – – –
Flange connection in PN16/PN25 [DN] – – – – – – – 25 25 32 40 50 50 65 80
Victaulic-connections – – – – – – – • • • • • – – –
MaterialsImpellers 1.4301/1.4404 1.4301 1.4301/1.4404 (MVI 16-6 only in 1.4301)
Stage chambers 1.4301/1.4404 1.4301 1.4301/1.4404 (MVI 16-6 only in 1.4301)
Pump housing 1.4301/1.4404 1.4301 1.4301/1.4404 EN-GJL-250/1.4404
Shaft 1.4404 1.4122 1.4301/1.4404 1.4057/1.4404
Seal EPDM (EP 851)/Viton
EPDM (EP 851)
EPDM (EP 851)/Viton
EPDM (EP 851)/Viton
Housing cover 1.4301/1.4404 – 1.4301/1.4404
Housing base – 1.4301 1.4301/1.4404 –
Mechanical seal B-Carbon/Tungsten car-bide – B-Carbon/Tungsten carbide
SiC/carbon
Pressure casing 1.4301/1.4404 1.4301 1.4301/1.4404
Bearing Tungsten carbideCarbon, synthetic
resinimpregnated
Tungsten carbide
Pump base Aluminium EN-GJL-250 EN-GJL-250 –
Pump base (In contact with the flow medium) – – – EN-GJL-250/1.4408
141Vesion: 06/2004 - Subject to technical modifications
High Pressure Centrifugal PumpsTechnical Data
Fluid Adaptability Chart
High
pre
ssur
e ce
ntrif
ugal
pum
ps
Code:• Resistant
– Not resistant
Note:Viton in combination with water is only resistant up to 90 °C max.
List of fluid media resistance characteristics of pumps in the Wilo-Multivert MVI/MVIE series 2.. up to 16-6 and Wilo-Economy MHI/MHIE series 2.. up to16..
This list is not necessarily complete. Data on the application limits of different pump materials when handling any of the listed fluids have been conscientiously prepared to the best available knowledge. However, the information must be regarded only as a non-binding guide to these characteristics. Guarantee claims of any kind must not be derived on the basis of this information.In practice it is unlikely that only the pure substances listed here will be contained in the pumped media. Even small additions of other matter can decisively influence or change the chemical aggression of a basic substance. Detrimental effects can also be attributed to incrustations, condensate or temperature changes. In many cases only practical experience can provide adequate evidence of the suit-ability of a particular material.
We therefore request that sufficient attention be given to the rele-vant footnotes and other remarks that are appended to the informa-tion.
Questions related to the chemical and other resistance of the Wilo-Multivert MVI/MVIE-Series 16../32../52.. should be directed to your respective Wilo sales office or representative.RemarksIn addition to this list of resistance characteristics, the properties of the flow medium, such as density, solidification point, viscosity, etc., as well as Ex-protection requirements, should be given separate and additional consideration.The limits of applicability of the pumps, based on pressure and tem-perature, must also be observed.
Fluid Adaptability ChartVol.-%
max.Temp. °C
max.1.4301 (AISI 304) 1.4404 (AISI 316 L)
Pumped fluid EPDM Viton EPDM Viton
Alkaline cleaner • – • –
Alcohol, see Ethanol • – • –
Aluminium sulphate 10% 25° – – – •
Ammonia water (A.hydroxide) 100% 80° • – • –
Ammonium chloride (Salmiac) 15% 60° – – • –
Ammonium hydrogen carbonate 10% 40° • – • –
Ammonium sulphate 20% 50° – – • –
Antifrogen (KW-Basis) 40% 70° • • • •
Cider 60° – – • –
Petrol (Ex-protection required) 25° – • – •
Benzoic acid 10% 100° – – – •
Boric acid Unsaturated solution 60° – – – •
Brandy < 40% Alc. 60° • – • –
Butanol 60° • – • –
Buttermilk – – – –
Calcium acetate Unsaturated solution 100° – – • –
Calcium hydroxide 10% 80° – – – •
Calcium nitrate 10% 30° • – • –
Deionic (fully desalinated water) 50° – – • –
Diesel oil (Light, extra light)
(Ex-protection required)80° – • – •
Iron phosphate – – – –
Iron-II-sulphate – – – –
Iron-III-sulphate – – – –
Oil 80° – • – •
Peanut oil – • – •
Vinegar (Wine vinegar) 10% 60° – – • –
142 As of: 06/2004 - Subject to change without prior notice
High Pressure Centrifugal PumpsTechnical Data
Fluid Adaptability Chart
Acetic acid anhydride 25° – – • –
Ethanol (Acetanol, Alcohol)
(Ex-protection required)60° • – • –
Ethylene glycol/Diethylene glycol 40 % 70° • • • •
Fixer 25° – – – •
Fruit juice 60° – – – •
Tannic acid Unsaturated solution Boiling point – – • –
Glycerine • – • –
Glycol – – – – – –
Glycol-water 40 % 70° • • • •
Uric acid – – • –
Heating oil (Light) (Ex-protection required)
– • – •
Hexane 40° – • – •
Hydraulic oil – • – •
Isopropanol (Ex-protection required) • – • –
Potassium carbonate Unsaturated solution 100° • – • –
Potassium hydrogen carbonate 10 % 60° • – • –
Potassium hydrate 10 % 60° • – • –
Potassium nitrate – – – –
Potassium permanganate Unsaturated solution 80° – – • –
Potassium sulphate Unsaturated solution 60° – – • –
Milk of lime (Calcium hydroxide) 10 % 80° – – – •
Kerosine (Ex-protection required) 25° – • – •
Copper sulphate Unsaturated solution 60° – – – •
Lubricant coolant 80° – • – •
Linseed oil 60° – • – •
Linseed oil + 3 % H2S04 60° – – – •
Liqueur 60° – – – •
Magnesium sulphate Unsaturated solution
< Boiling temper-ature – – – –
Maize oil 100° – • – •
Maleic acid 50 % 60° – – – •
Methanol (Ex-protection required) 60° • – • –
Methyl alcohol: Methanol(Ex-protection required)
60° • – • –
Lactic acid Unsaturated solution 25° – – – •
Mineral oil, see oil
Miscella 60° – • – •
Sodium carbonate 10 % 60° • – • –
Sodium hydroxide 25 % 20° • – • –
Sodium hydroxide 10 % 80° • – • –
Sodium nitrate Unsaturated solution 80° • – • –
Sodium phosphate 5 % 110° • – • –
Fluid Adaptability ChartVol.-%
max.Temp. °C
max.1.4301 (AISI 304) 1.4404 (AISI 316 L)
Pumped fluid EPDM Viton EPDM Viton
143Vesion: 06/2004 - Subject to technical modifications
High Pressure Centrifugal PumpsTechnical Data
Fluid Adaptability Chart
High
pre
ssur
e ce
ntrif
ugal
pum
ps
Sodium sulphate – – – –
Carbonate lye
Fruit pulp (containingSO 2) Boiling tempera-ture – – – •
Oil:
– Heating oil (Ex-protection required) 120° – • – •
– Maize oil 100° – • – •
– Mineral oil 80° – • – •
– Rapeseed oil 100° – • – •
– Castor oil 100° – • – •
– Lubricating oil – • – •
– Cutting oil – • – •
– Soybean oil 100° – • – •
– Oil of turpentine 60° – • – •
– Turbine oil (Not SDF oils) 100° – • – •
Oil-water-mixture 10% 250° – • – •
Oxalic acid – – – –
Paraffin(s) – • – •
Kerosene (Ex-protection required) – • – •
Phosphoric acid 10 % 85° – – – •
Polyglycols 90° – • – •
Polyethylene glycols 40 % 70° • • • •
2-Propanol 60° • – • –
Pulps, see fruit pulps
Rapeseed oil 100° – • – •
Ricine 100° – • – •
Salicylic acid Unsaturated solution 25° – – • –
Ammonia solution (Ammonium hydrox-
ide)100 % 80° • – •
Sulphuric acid 5 % 25° – – – •
Sulphuric acid 2.50 % 60° – – – •
Sulfurous acid (Saturated) 20° – – – •
Safety refrigerants
(e.g. Freon, Frigen. etc., free of water)– – – –
Silicone oil 100° – • – •
Cooking oil 100° – • – •
Terpentine (Oil) 60° – • – •
Trisodium phosphate 10 % Boiling tempera-ture • – • –
Toluene – – – –
Wash liquid alc. (Bottle rinsing) 10 % 80° • – • –
Wash liquid alc. (Metal degreasing) 10 % 80° – • – •
Water, with the following characteristics:pH < 6.5; Chloride < 150 mg/l pH > 6.5; Chloride < 300 mg/l
– Swimming pool water (No colloids) 35° • – • –
– Deionic 50° – – • –
– Distilled water 50° – – • –
Fluid Adaptability ChartVol.-%
max.Temp. °C
max.1.4301 (AISI 304) 1.4404 (AISI 316 L)
Pumped fluid EPDM Viton EPDM Viton
144 As of: 06/2004 - Subject to change without prior notice
High Pressure Centrifugal PumpsTechnical Data
Fluid Adaptability Chart
– Decarbonated water – – • –
– Soft water – – • –
– Fire services water • – • –
– Heating water • – • –
– Boiler water (dH < 11.5) • – • –
– Boiler feed-water, fully demineralised – – • –
– Condensate (pH < 4.5) – – • –
– Tap water • – • –
– Pure water • – • –
– Ultrapure water (Electronics, etc.) – – • –
– Feed water, see boiler water
and boiler feed-water
– Rinsing water • – • –
– Semi-desalinated water, see
decarbonated water
– Fully desalinated water, see Deionic
– Soft water, see decarbonated water
Other water:
– Boiler feed-water, partly desalinated • – • –
– Cooling and chilled water • – • –
– Untreated water
(Suspended solids < 10 ppm)• – • –
– Drinking water • – • –
Wine, (white, red) – – • –
Wine acid Unsaturated solution 60° – – – •
Citric acid 5 % 25° – – • –
Sugar juice (Solution)
susp. s < 20 ppm– – • –
Fluid Adaptability ChartVol.-%
max.Temp. °C
max.1.4301 (AISI 304) 1.4404 (AISI 316 L)
Pumped fluid EPDM Viton EPDM Viton
146 As of: 06/2004 - Subject to change without prior notice
High Pressure Centrifugal PumpsTechnical Data
Options Chart
• = Standard version, – = not available and not obtainable
Options Chart MVI1/2/4/8/16-6
MVI16/32/52
MVIS MVIE2/4/8/16-6
MVIE16/32/52
MVISE
MaterialPump base EN_GJL-250 with cataphoresis coating Hydraulic in 1.4301/1.4404 (AISI 304/316L) – • • – • •
Parts in contact with the fluid medium in 1.4301 (AISI 304) • – • • • •
Parts in contact with the fluid medium in 1.4404 (AISI 316L) • • – • • –
SealsEPDM • • • • • •
Viton • • • • • •
Hydraulic connectionThreaded connection – – – – – –
Oval flange • – • • – •
Round flange • • – • • –
Victaulic fast coupling • – • • – •
Motor versionsIndividual motors Optional Optional – – – –
1~230 V, 50 Hz•
(up to P2 = 1.5 kW)
– –•
(only version 2../4..)
– –
3~230 V, 50 HzOptional
(up to P2= 4 kW for 230/400 V;from P2= 5.5 kW only 400 V )
• – – –
3~400 V, 50 Hz – – • – – •
3~500 V, 50 Hz Optional Optional – – – –
1~110 V, 60 Hz Optional Optional – – – –
1~220 V, 60 Hz Optional Optional – – – –
3~380 V, 60 Hz Optional Optional – – – –
3~400 V, 60 Hz Optional Optional – – – –
3~440 V, 60 Hz Optional Optional – – – –
3~460 V, 60 Hz Optional Optional – – – –
3~480 V, 60 Hz Optional Optional – – – –
3~380 V up to 440 V and 50 Hz up to 60 Hz – – – • • –
IP 44 – – • – – •
IP 54 – – – • • –
IP 55 • • – – – –
Ex-protected motors Optional Optional – – – –
Motors with resistors (PTC) Optional Optional – • • Optional
Motors with UL certification Optional Optional Optional – – Optional
Motors with CSA certification Optional Optional Optional – – Optional
Thermal motor protectionOptional
(up to2=1.5 kW inclusive)
– – – – –
Speed controllable via remote FU • • • – – –
Integrated frequency converter – – – • • •
Paint finishIndividual paint finishes Optional Optional Optional Optional Optional Optional
Mechanical sealsTungsten carbide/carbon • • • • • •
Tungsten carbide/Tungsten carbide Optional Optional Optional Optional Optional Optional
SiC/SiC Optional Optional Optional Optional Optional Optional
Drinking water compatibilityKTW • • • • • •
WRAS • • • • • •
153Vesion: 06/2004 - Subject to technical modifications
High Pressure Centrifugal PumpsWilo-Multivert MVI
Pump Curves
High
pre
ssur
e ce
ntrif
ugal
pum
ps
Wilo-Multivert MVI 102 up to MVI 124 Wilo-Multivert MVI 202 up to MVI 220Wilo-Multivert MVIPump Curves
Pump curves in accordance with ISO 9906, Class 2 Pump curves in accordance with ISO 9906, Class 2
Wilo-Multivert MVI 402 up to MVI 419 Wilo-Multivert MVI 802 up to MVI 819
Pump curves in accordance with ISO 9906, Class 2 Pump curves in accordance with ISO 9906, Class 2
Wilo-Multivert-MVI 102-12450 Hz
m3/h
m3/h
m3/h
l/s
P
0 0,25 0,5 1,25
2,5
2
1,5
1
0,5
0
240
220
200
180
160
140
120
100
80
60
40
20
0
5040302010
0
1086420
124
110
123
NPSH
Q
0 0,5 1 1,5 2 2,5Q
0 0,5 1 1,5 2 2,5Q
0 0,5 1 1,5 2 2,5
121
118
116
112
106107108109
114
104105
102
123124
121
118116114112110
102103104105106
109
107108
H[m
]N
PSH
[m]
P 2[kW
]
P[%]
103
Wilo-Multivert-MVI 202-22050 Hz
0 0,5 1 1,5
3,5
3
2,5
2
1,5
1
0,5
0
240
220
200
180
160
140
120
100
80
60
40
20
0
6
4
2
0
60
40
20
0
220
208207
NPSH
Q
0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5
p
Q
0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 Q
0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5
217
214
212
210
206205204
202203
217
220
214
212210208
206
204203
205
207
202
NPS
H [m
]H
[m]
P 2[kW
]
[l/s]
[m3/h]
[m3/h]
[m3/h]
p[%
]
Wilo-Multivert-MVI 402-41950 Hz
[l/s]
p[%
]
NPS
H [m
]H
[m]
P 2[kW
]
[m3/h]
[m3/h]
[m3/h]
0 0,5 1 1,5 2
4
3,5
3
2,5
2
1,5
1
0,5
0
220
200
180
160
140
120
100
80
60
40
20
0
6
4
2
0
60
40
20
0
419
408407
Q
Q
0 1 2 3 4 5 6 7 8
417
414
412
410
406405
403
417419
414412
408
0 1 2 3 4 5 6 7 8
0 1 2 3 4 5 6 7 8
402
404
Q
410
402403404405
407406
NPSH
p
Wilo-Multivert-MVI 802-81950 Hz
0 1 2 3 4
8
7
6
5
4
3
2
1
0
240
220
200
180
160
140
120
100
80
60
40
20
0
76543210
70605040302010
0
819
807
Q
Q
Q
0 2 4 6 8 10 12 14
817
814
812811
806805804
802803
0 2 4 6 8 10 12 14
810
808
0 2 4 6 8 10 12 14
819817
814812
810808807
811
806805
802
804803
NPSH
p
[l/s]
p[%
]
NPS
H [m
]H
[m]
P 2[kW
]
[m3/h]
[m3/h]
[m3/h]
154 As of: 06/2004 - Subject to change without prior notice
High Pressure Centrifugal PumpsWilo-Multivert MVI
Pump Curves, Terminal Diagram
Pump curves in accordance with ISO 9906, Class 2
Wilo-Multivert MVI 1602-6 up to MVI 1611-6
Terminal diagram
Pump Curves, Terminal Diagram
Wilo-Multivert-MVI 1602/6-1611/650 Hz
0 1,0 2,0 3,0 4,0 5,0 6,0 7,0
8
7
6
5
4
3
2
1
0
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
706050403020100
706050403020100
NPSH
H[m
]
Q
Q
NP
SH
[m]
Q
P2
[kW
]
0 5 10 15 20 25
1610/6
1609/6
1608/6
1607/6
1606/6
1605/6
1604/6
1603/6
1602/6
ηp
1611/61610/61609/61608/61607/61606/61605/61604/61603/61602/6
1611/6
[l/s]
[m3/h]
0 5 10 15 20 25
0 5 10 15 20 25
ηp
[%]
[m3/h]
[m3/h]
4 kW
5,5 kW
W 2
U1
U2
V1
L 0
W 2
U1
U2
V1
L 0
W 2
W 1V1U1
V2U2
L 3L 2L 1
3~400 V
3~400 V
3~230 V
1~230 V
1~230 V
W 2
W 1V1U1
V2U2
L 3L 2L 1
W 2
W 1V1U1
V2U2
Y ? -
155Vesion: 06/2004 - Subject to technical modifications
High Pressure Centrifugal PumpsWilo-Multivert MVI
Motor Data
High
pre
ssur
e ce
ntrif
ugal
pum
ps
Motor DataMotor Data
Nominal power P2 Nominal current IN
1~230 V, 50 Hz 3~230 V, 50 Hz 3~400 V, 50 Hz
[kW] [A]
MVI 102 0.37 2.7 1.6 0.93
MVI 103 0.37 2.7 1.6 0.93
MVI 104 0.55 3.6 2.28 1.32
MVI 105 0.55 3.6 2.28 1.32
MVI 106 0.75 4.85 2.94 1.7
MVI 107 0.75 4.85 2.94 1.7
MVI 108 0.75 4.85 2.94 1.7
MVI 109 1.1 6.6 4.15 2.4
MVI 110 1.1 6.6 4.15 2.4
MVI 112 1.1 6.6 4.15 2.4
MVI 114 1.5 9.1 5.5 3.2
MVI 116 1.85 – 6.75 3.9
MVI 118 1.85 – 6.75 3.9
MVI 121 2.2 – 7.8 4.5
MVI 123 2.2 – 7.8 4.5
MVI 124 3.0 – 10.4 6.0
MVI 202 0.37 2.6 1.6 0.95
MVI 203 0.55 3.5 2.3 1.35
MVI 204 0.75 4.9 2.9 1.7
MVI 205 0.75 4.9 2.9 1.7
MVI 206 1.1 6.6 4.2 2.4
MVI 207 1.1 6.6 4.2 2.4
MVI 208 1.5 9.1 5.5 3.2
MVI 210 1.5 9.1 5.5 3.2
MVI 212 1.85 – 7.0 4.0
MVI 214 2.2 – 7.6 4.4
MVI 217 3.0 – 10.9 6.3
MVI 220 3.7 – 13.5 7.8
MVI 402 0.55 3.5 2.3 1.35
MVI 403 0.75 4.9 2.9 1.7
MVI 404 1.1 6.6 4.2 2.4
MVI 405 1.1 6.6 4.2 2.4
MVI 406 1.5 9.1 5.5 3.2
MVI 407 1.5 9.1 5.5 3.2
MVI 408 1.85 – 7.0 4.0
MVI 410 2.2 – 7.6 4.4
MVI 412 3.0 – 10.9 6.3
MVI 414 3.0 – 10.9 6.3
MVI 417 3.7 – 13.5 7.8
MVI 419 4.0 – 14.5 8.4
MVI 802 0.75 4.8 2.9 1.7
MVI 803 1.1 6.6 4.2 2.4
MVI 804 1.5 9.1 5.5 3.2
MVI 805 1.85 – 7.0 4.0
MVI 806 2.2 – 7.6 4.4
156 As of: 06/2004 - Subject to change without prior notice
High Pressure Centrifugal PumpsWilo-Multivert MVI
Motor Data, Dimension Drawings
Motor Data, Dimension Drawings
MVI 807 3.0 – 10.9 6.3
MVI 808 3.0 – 10.9 6.3
MVI 810 3.7 – 13.5 7.8
MVI 811 4.0 – 14.5 8.4
MVI 812 5.5 _ – 10.5
MVI 814 5.5 – – 10.5
MVI 817 7.5 – – 14.3
MVI 819 7.5 – – 14.3
MVI 1602-6 1.5 – 5.5 3.2
MVI 1603-6 2.2 – 7.6 4.4
MVI 1604-6 3.0 – 10.9 6.3
MVI 1605-6 3.7 – 13.5 7.8
MVI 1606-6 4.0 – 14.5 8.4
MVI 1607-6 5.5 – – 10.8
MVI 1608-6 5.5 – – 10.8
MVI 1609-6 7.5 – – 14.3
MVI 1610-6 7.5 – – 14.3
MVI 1611-6 7.5 – – 14.3
Dimension drawings
Wilo-Multivert MVI 102 up to 124 Wilo-Multivert MVI 202 up to 220
Motor Data Nominal power P2 Nominal current IN
1~230 V, 50 Hz 3~230 V, 50 Hz 3~400 V, 50 Hz
[kW] [A]
H
Ø M
h 2
X
100
E
100
E
PN 16
75
Rp1/DN25
PN 25
4x14
Victaulic
75
Ø42
,4
DN 25
85
4x Ø 12
4x Ø 12
180
212
5050
4x Ø 12
180
212
100
E
H
Ø M
h 2
PN 16
75
4x Ø 12
180
212
Rp1/DN25
PN 25
Ø 4
2,4
DN 25
85
4x144x Ø 12
180
212
4x Ø 12
50
34,4 Victaulic
X
E
7550
157Vesion: 06/2004 - Subject to technical modifications
High Pressure Centrifugal PumpsWilo-Multivert MVI
Dimension Drawings
High
pre
ssur
e ce
ntrif
ugal
pum
ps
Dimension drawings
Wilo-Multivert MVI 402 up to 413 Wilo-Multivert MVI 802 up to MVI 819
Dimension Drawings
Wilo-Multivert MVI 1602-6 up to 1611-6
100
E
H
Ø M
h 2
PN 16
75
4x Ø 12
180
212
Rp11/4/DN32
PN 25
Ø 4
2,4
DN 32
85
4x144x Ø12
180
212
4x Ø 12
50
34,4 Victaulic
X
E
7550
130
E
H
h 2
75
215
252
DN 40
110
4x18
215
252
261
80
52,3
X
Rp11/2 /DN40
8080
For additional base platesee dimensions PN 16
Victaulicversion
VersionPN 25
VersionPN 16
4x ø12
4x ø12
4x ø12
ø60,
3
øM
130
E
H
h 2
PN 16
100
4x Ø 12
215
252
PN 25
Ø 6
0,3
DN 50
125
4x184x Ø12
215
252
E4x Ø 12
90
52,3 Victaulic
Ø M
X
Rp2 /DN50
9090
158 As of: 06/2004 - Subject to change without prior notice
High Pressure Centrifugal PumpsWilo-Multivert MVI
Dimensions, Weights
Dimensions, weights
2) incl. mating flanges, without packing
3) without packing
Dimensions, WeightsVersion PN 16 Oval flange
E H H Ø M X Weight 2)
1~230 V 3~400 V 1~230 V 3~400 V 1~230 V 3~400 V 1~230 V 3~400 V
[mm] [kg]
MVI 102 204 490 528 305 140 140 107 118 19.5 18.8
MVI 103 204 506 528 305 140 140 107 118 19.7 19.0
MVI 104 204 506 528 305 140 140 107 118 20.6 19.7
MVI 105 204 530 568 345 140 140 107 118 21.9 21.0
MVI 106 204 570 598 355 162 170 121 127 24.0 23.9
MVI 107 204 590 618 375 162 170 121 127 24.7 24.6
MVI 108 204 630 658 415 162 170 121 127 25.9 25.8
MVI 109 204 630 658 415 162 170 121 127 27.8 27.2
MVI 110 204 650 678 435 162 170 121 127 28.4 27.8
MVI 112 204 690 718 475 162 170 121 127 29.8 29.2
MVI 114 204 770 791 525 182 193 131 151 39.9 35.6
Version PN 25 Round flange
E H H Ø M X Weight 3)
1~230 V 3~400 V 1~230 V 3~400 V 1~230 V 3~400 V 1~230 V 3~400 V
[mm] [kg]
MVI 102 250 515 552 330 140 140 107 118 20.6 19.9
MVI 103 250 515 552 330 140 140 107 118 20.8 20.1
MVI 104 250 515 552 330 140 140 107 118 21.8 20.9
MVI 105 250 555 592 370 140 140 107 118 23.0 22.1
MVI 106 250 595 623 380 162 170 121 127 25.1 25.0
MVI 107 250 615 643 400 162 170 121 127 25.8 25.7
MVI 108 250 655 683 440 162 170 121 127 27.0 26.9
MVI 109 250 655 683 440 162 170 121 127 28.9 28.3
MVI 110 250 675 703 460 162 170 121 127 29.6 29.0
MVI 112 250 715 743 500 162 170 121 127 30.9 30.3
MVI 114 250 795 816 550 182 193 131 151 41.0 36.7
MVI 116 250 – 856 590 – 193 – 151 – 38.9
MVI 118 250 – 896 630 – 193 – 151 – 40.3
MVI 121 250 – 956 690 – 193 – 151 – 44.4
MVI 123 250 – 1,016 750 – 193 – 151 – 46.3
MVI 124 250 – 1,055 760 – 217 – 160 – 51.1
159Vesion: 06/2004 - Subject to technical modifications
High Pressure Centrifugal PumpsWilo-Multivert MVI
Dimensions, Weights
High
pre
ssur
e ce
ntrif
ugal
pum
ps
Version PN 25 Victaulic
E H H Ø M X Weight
3~400 V 1~230 V 3~400 V 1~230 V 3~400 V 3~400 V
[mm] [kg]
MVI 102 210 528 305 140 140 107 118 19.9
MVI 103 210 528 305 140 140 107 118 20.1
MVI 104 210 528 305 140 140 107 118 20.9
MVI 105 210 568 345 140 140 107 118 22.1
MVI 106 210 598 355 162 170 121 127 25.0
MVI 107 210 618 375 162 170 121 127 25.7
MVI 108 210 658 415 162 170 121 127 26.9
MVI 109 210 658 415 162 170 121 127 28.3
MVI 110 210 678 435 162 170 121 127 29.0
MVI 112 210 718 475 162 170 121 127 30.3
MVI 114 210 791 525 182 193 131 151 36.7
MVI 116 210 831 565 – 193 – 151 38.9
MVI 118 210 871 605 – 193 – 151 40.3
MVI 121 210 931 665 – 193 – 151 44.4
MVI 123 210 991 725 – 193 – 151 46.3
MVI 124 210 1,030 735 – 217 – 160 51.1
Version PN 16 Oval flange Version PN 25 Round flange
E1) H h2 Ø M X Weight 2) E H h2 Ø M X Weight 3)
1~230 V 3~400 V 1~230 V 3~400 V 1~230 V 3~400 V 1~230 V 3~400 V
[mm] [kg] [mm] [kg]
MVI 202 204 481.5 481.5 296.5 150 123 18.5 18 250 507 507 321.5 150 123 19.8 19.3
MVI 203 204 519 519 296.5 150 123 19.3 18.8 250 544 544 321.5 150 123 20.6 20.1
MVI 204 204 546 574 330.5 170 143 22.6 22.1 250 571 599 355.5 170 143 28.6 28.1
MVI 205 204 570 598 354.5 170 143 23.1 22.6 250 594 623 379.5 170 143 28.6 28.1
MVI 206 204 594 622 378.5 170 143 25.5 25 250 618 647 403.5 170 143 31.1 30.6
MVI 207 204 628 656 402.5 170 143 26 25.5 250 653 681 427.5 170 143 31.1 30.6
MVI 208 204 682 703 436.5 190 148 31 30.5 250 707 728 461.5 190 148 38.4 37.9
MVI 210 204 730 751 484.5 190 148 32.3 31.8 250 755 776 509.5 190 148 39.6 39.1
MVI 212 204 – 799 532.5 190 148 – 33 250 – 824 557.5 190 148 – 40.6
MVI 214 – – – – – – – – 250 – 872 605.5 190 148 – 42.8
MVI 217 – – – – – – – – 250 – 983 687.5 213 158 – 46.2
MVI 220 – – – – – – – – 250 – 1055 759.5 213 158 – 48
MVI 402 204 519 481.5 296.5 150 123 19.3 18.8 250 544 507 321.5 150 123 20.6 20.1
MVI 403 204 522 550 306.5 170 143 22.5 22 250 547 575 331.5 170 143 23.8 23.3
MVI 404 204 546 574 330.5 170 143 24 23.5 250 571 599 355.5 170 143 25.3 24.8
MVI 405 204 570 598 354.5 170 143 24.9 24.4 250 595 623 379.5 170 143 26.2 25.7
MVI 406 204 634 655 388.5 190 148 29.5 29 250 659 680 413.5 190 148 30.8 30.3
MVI 407 204 658 679 412.5 190 148 30.2 29.7 250 683 704 437.5 190 148 31.5 31
MVI 408 204 – 703 436.5 190 148 – 30.5 250 – 728 461.5 190 148 – 31.8
MVI 410 204 – 751 484.5 190 148 – 34 250 – 776 509.5 190 148 – 35.3
MVI 412 204 – 838 542.5 213 158 – 41.2 250 – 863 567.5 213 158 – 42.5
MVI 414 – – – – – – – – 250 – 911 615.5 213 158 – 44.2
MVI 417 – – – – – – – – 250 – 983 687.5 213 158 – 46.6
MVI 419 – – – – – – – – 250 – 1,055 759.5 240 170 – 47
160 As of: 06/2004 - Subject to change without prior notice
High Pressure Centrifugal PumpsWilo-Multivert MVI
Dimensions, Weights
1) dimensions incl. mating flanges (2 Items at 25 mm)2) incl. mating flanges, without packing3) without packing
MVI 802 250 574 574 334 170 143 24.1 23.6 280 549 577 334 170 143 25.1 24.6
MVI 803 250 604 604 364 170 143 26 25.5 280 579 607 364 170 143 27 26.5
MVI 804 250 654 684 404 190 148 31 30.5 280 649 670 404 190 148 32 31.5
MVI 805 250 – 714 434 190 148 – 31.3 280 – 700 434 190 148 – 32.3
MVI 806 250 – 744 464 190 148 – 34.5 280 – 730 464 190 148 – 35.5
MVI 807 250 – 824 504 213 158 – 41.1 280 – 799 504 213 158 – 42.1
MVI 808 250 – 854 534 213 158 – 42 280 – 829 534 213 158 – 43
MVI 810 250 – 919 593 213 158 – 43.8 280 – 889 594 213 158 – 44.8
MVI 811 250 – 1,054 654 240 170 – 45 280 – 949 654 240 170 – 46
MVI 812 250 – 1,054 654 240 170 – 54.5 280 – 979 654 240 170 – 55.5
MVI 814 – – – – – – – – 280 – 1,039 714 240 170 – 67.8
MVI 817 – – – – – – – – 280 – 1,219 823 280 194 – 74.5
MVI 819 – – – – – – – – 280 – 1,279 883 280 194 – 77.4
MVI 1602-6 250 – 636 368.5 190 151 – 31 300 – 636 368.5 190 140 – 31
MVI 1603-6 250 – 712 443.5 190 151 – 35 300 – 712 443.5 190 140 – 35
MVI 1604-6 250 – 751 453.5 210 160 – 41.1 300 – 751 453.5 210 150 – 41.1
MVI 1605-6 250 – 827 528.5 210 160 – 51.3 300 – 827 528.5 210 150 – 51.3
MVI 1606-6 250 – 827 528.5 240 160 – 51.7 300 – 827 528.5 240 160 – 51.7
MVI 1607-6 250 – 933 603.5 240 168 – 53.4 300 – 933 603.5 240 160 – 53.4
MVI 1608-6 250 – 933 603.5 240 168 – 53.9 300 – 933 603.5 240 160 – 53.9
MVI 1609-6 250 – 1,099 698 280 180 – 76 300 – 1,099 698 280 180 – 75.1
MVI 1610-6 250 – 1,099 698 280 180 – 76.4 300 – 1,099 698 280 180 – 75.5
MVI 1611-6 250 – 1,175 773 280 180 – 76.8 300 – 1,175 773 280 180 – 77.6
Version Victaulic 3~400 V
E H h2 Ø M X Weight
[mm] [kg]
MVI 202 210 516.5 296.5 150 123 19
MVI 203 210 516.5 296.5 150 123 20
MVI 204 210 570.5 330.5 170 143 28
MVI 205 210 594.5 354.5 170 143 28
MVI 206 210 618.5 378.5 170 143 30
MVI 207 210 642.5 402.5 170 143 30
MVI 208 210 716.5 436.5 190 148 37.5
MVI 210 210 764.5 484.5 190 148 39
MVI 212 210 812.5 532.5 190 148 40.5
MVI 214 210 860.5 580.5 190 148 42.5
MVI 217 210 963 662.5 213 158 46
MVI 220 210 1,055 734.5 213 158 48
MVI 402 210 535.5 296.5 150 123 20
MVI 403 210 546.5 306.5 170 143 23
MVI 404 210 570.5 330.5 170 143 24.5
MVI 405 210 594.5 354.5 170 143 25.5
Version PN 16 Oval flange Version PN 25 Round flange
E1) H h2 Ø M X Weight 2) E H h2 Ø M X Weight 3)
1~230 V 3~400 V 1~230 V 3~400 V 1~230 V 3~400 V 1~230 V 3~400 V
[mm] [kg] [mm] [kg]
161Vesion: 06/2004 - Subject to technical modifications
High Pressure Centrifugal PumpsWilo-Multivert MVI
Dimensions, Weights
High
pre
ssur
e ce
ntrif
ugal
pum
ps
MVI 406 210 668.5 388.5 190 148 30
MVI 407 210 692.5 412.5 190 148 31
MVI 408 210 716.5 436.5 190 148 31.5
MVI 410 210 764.5 484.5 190 148 35
MVI 412 210 862.5 542.5 213 158 42.5
MVI 414 210 910.5 590.5 213 158 44
MVI 417 210 988 662.5 213 158 46.5
MVI 419 210 1,111 734.5 240 170 47
MVI 1602 261 648.5 368.5 190 140 31.4
MVI 1603 261 723.5 443.5 190 140 35.4
MVI 1604 261 773.5 453.5 210 150 41.5
MVI 1605 261 848.5 528.5 210 150 51.7
MVI 1606 261 928.5 528.5 240 160 52.1
MVI 1607 261 1,004 603.5 240 160 53.8
MVI 1608 261 1,004 603.5 240 160 54.2
MVI 1610 261 1,098 698 280 180 75.5
MVI 1611 261 1,098 698 280 180 75.9
MVI 1612 261 1,173 773 280 180 78
Version Victaulic 3~400 V
E H h2 Ø M X Weight
[mm] [kg]
162 As of: 06/2004 - Subject to change without prior notice
High Pressure Centrifugal PumpsWilo-Multivert MVI
Dimensions, Weights
Wilo-Multivert MVI 1602 up to MVI 1614 Wilo-Multivert MVI 3202 up to MVI 3212
Pump curves in accordance with ISO 9906, Class 2 Pump curves in accordance with ISO 9906, Class 2
Wilo-Multivert MVI 5202 up to MVI 5209
Pump curves in accordance with ISO 9906, Class 2
0 1,0 2,0 3,0 4,0 5,0 6,0 7,0
14
12
10
8
6
4
2
0
250
225
200
175
150
125
100
75
50
25
0
201510
50
80604020
0
Q
Q
Q
0 5 10 15 20 25
1614
16131612
1610
1609
1608
1607
1605
1603
Wilo-Multivert-MVI 1602-161450 Hz
p
0 5 10 15 20 25
0 5 10 15 20 25
16141613
1611
16071608
1605
1611
1606
1602
1604
1602
1612
16101609
1606
1603
[l/s]
p[%
]
NPS
H [m
]H
[m]
P 2[kW
]
[m3/h]
[m3/h]
[m3/h]
1604
NPSH
0 2,0 4,0 6,0 8,0 10,0 12,0 14,0
20
15
10
5
0
80
60
40
20
0
Q
Q
Q
3212
3211
3210
3209
3208
3207
3206
3205
0 8 16 24 32 40 48
20
40
60
80
100
120
140
160
180
200
220
240
3202
3203
p
80 16 24 32 40 48
80 16 24 32 40 48
25
20
15
10
5
0
Wilo-Multivert-MVI 320050 Hz
3204
[l/s]
p[%
]
NPS
H [m
]H
[m]
P 2[kW
]
[m3/h]
[m3/h]
[m3/h]
N.P.S.H
32123211321032093208320732063205320432033202
0 5 10 15 20
25
20
15
10
5
0
200
180
160
140
120
100
80
60
|40
20
0
86420
80604020
0
5209
NPSH
Q
p
5208
5207
5206
5205
5204
5203
5202
0 10 20 30 40 50 60 70
Wilo-Multivert-MVI 5202-520950 Hz
0 10 20 30 40 50 60 70
Q
Q
0 10 20 30 40 50 60 70
[l/s]
p[%
]
NPS
H [m
]H
[m]
P 2[kW
]
[m3/h]
[m3/h]
[m3/h]
5207
5205
52035202
52085209
5204
5206
163Vesion: 06/2004 - Subject to technical modifications
High Pressure Centrifugal PumpsWilo-Multivert MVI
Terminal Diagram, Motor Data
High
pre
ssur
e ce
ntrif
ugal
pum
ps
Motor Data
Terminal diagram
Terminal Diagram, Motor Data
Nominal power P2 Nominal current IN
3~230 V, 50 Hz 3~400 V, 50 Hz
[kW] [A]
MVI 1602 2.2 7.6 4.4
MVI 1603 3.0 10.9 6.3
MVI 1604 4.0 14.5 8.4
MVI 1605 5.5 – 10.8
MVI 1606 5.5 – 10.8
MVI 1607 7.5 – 14.3
MVI 1608 7.5 – 14.3
MVI 1609 9.0 – 17.9
MVI 1610 11.0 – 21.0
MVI 1611 11.0 – 21.0
MVI 1612 15.0 – 27.8
MVI 1613 15.0 – 27.8
MVI 1614 15.0 – 27.8
MVI 3202 4.0 14.9 8.4
MVI 3203 5.5 – 10.8
MVI 3204 7.5 – 14.3
MVI 3205 9.0 – 17.9
MVI 3206 11.0 – 21.0
MVI 3207 15.0 – 27.8
MVI 3208 15.0 – 27.8
MVI 3209 18.5 – 34.0
MVI 3210 18.5 – 34.0
MVI 3211 22.0 – 40.0
MVI 3212 22.0 – 40.0
MVI 5202 5.5 – 10.8
MVI 5203 7.5 – 14.3
MVI 5204 11.0 – 21.0
MVI 5205 15.0 – 27.8
MVI 5206 15.0 – 27.8
MVI 5207 18.5 – 34.0
MVI 5208 22.0 – 40.0
MVI 5209 22.0 – 40.0
Y ? -
W 2
W 1V1U1
V2U2
L 3L 2L 1
W 2
W 1V1U1
V2U2
L 3L 2L 1
W 2
W 1V1U1
V2U2
L 3
L 3
L 2
L 2
L 1
L 1
W 2
W 1V1U1
V2U23 ~ 400 V
3 ~ 230 V
3 ~ 400 V 3 ~ 230 V
5,5 kW 4 kW
164 As of: 06/2004 - Subject to change without prior notice
High Pressure Centrifugal PumpsWilo-Multivert MVI
Dimension Drawings
Dimension drawings
Wilo-Multivert MVI 1602 up to MVI 1614 Wilo-Multivert MVI 3202 up to MVI 3212
Dimension Drawings
Wilo-Multivert MVI 5202 up to 5209
252 194
300
90DN
50
125
4 x Ø 18
h 2
H
Ø M 130
4 x Ø 14
215
X
B A
320
FDN
65
145
K
h 2
H
Ø M C1
4 x Ø 14
C2
X
260 260
320
105
DN
80
16
0
8x18
h 2
H
Ø M 220
4 x Ø14
220
X
165Vesion: 06/2004 - Subject to technical modifications
High Pressure Centrifugal PumpsWilo-Multivert MVI
Dimensions, Weights
High
pre
ssur
e ce
ntrif
ugal
pum
ps
Dimensions, weights
Dimensions, Weights
Version PN 16 Version PN 25
A B C1 C2 F H h2 ØM X K Weight A B C1 C2 F H h2 ØM X K Weight
[mm] [kg] [mm] [kg]
MVI 1602 – – – – – 714 419 190 140 – 58 – – – – – 714 419 190 140 – 58
MVI 1603 – – – – – 749 429 215 150 – 65 – – – – – 749 429 215 135 – 65
MVI 1604 – – – – – 864 464 235 160 – 76 – – – – – 864 464 235 160 – 76
MVI 1605 – – – – – 898 498 235 160 – 77 – – – – – 898 498 235 160 – 77
MVI 1606 – – – – – 933 533 235 160 – 79 – – – – – 933 533 235 160 – 79
MVI 1607 – – – – – 1,072 622 265 180 – 103 – – – – – 1,072 622 265 180 – 103
MVI 1608 – – – – – 1,072 622 265 180 – 104 – – – – – 1,072 622 265 180 – 104
MVI 1609 – – – – – – – – – – – – – – – – 1,141 691 300 180 – 122
MVI 1610 – – – – – – – – – – – – – – – – 1,141 691 300 180 – 122
MVI 1611 – – – – – – – – – – – – – – – – 1,210 760 300 180 – 126
MVI 1612 – – – – – – – – – – – – – – – – 1,350 790 325 240 – 154
MVI 1613 – – – – – – – – – – – – – – – – 1,419 859 325 240 – 158
MVI 1614 – – – – – – – – – – – – – – – – 1,419 859 325 240 – 158
MVI 3202 239 235 195 195 105 840 440 235 160 4x18 80 262 260 220 220 120 855 455 235 160 8x18 84
MVI 3203 239 235 195 195 105 886 486 235 160 4x18 82 262 260 220 220 120 901 501 235 160 8x18 86
MVI 3204 239 235 195 195 105 1,002 552 265 180 4x18 105 262 260 220 220 120 1,017 567 265 180 8x18 109
MVI 3205 239 235 195 195 105 1,094 644 300 180 4x18 124 262 260 220 220 120 1,109 659 300 180 8x18 128
MVI 3206 239 235 195 195 105 1,094 644 300 180 4x18 124 262 260 220 220 120 1,139 689 300 180 8x18 128
MVI 3207 239 235 195 195 105 1,326 766 325 240 4x18 159 262 260 220 220 120 1,341 781 325 240 8x18 163
MVI 3208 239 235 195 195 – – – – – – – 262 260 220 220 120 1,341 827 325 240 8x18 163
MVI 3209 239 235 195 195 – – – – – – – 262 260 220 220 120 1,387 827 325 240 8x18 179
MVI 3210 239 235 195 195 – – – – – – – 262 260 220 220 120 1,525 965 325 240 8x18 185
MVI 3211 239 235 195 195 – – – – – – – 262 260 220 220 120 1,555 965 370 260 8x18 210
MVI 3212 239 235 195 195 – – – – – – – 262 260 220 220 120 1,555 965 370 260 8x18 210
MVI 5202 – – – – – 872 472 235 160 – 82.5 – – – – – 872 472 235 160 – 82.5
MVI 5203 – – – – – 1,004 554 265 180 – 105.5 – – – – – 1,004 554 265 180 – 105.5
MVI 5204 – – – – – 1,065 615 265 180 – 123 – – – – – 1,065 615 265 180 – 123
MVI 5205 – – – – – 1,328 767 325 240 – 156.5 – – – – – 1,328 767 325 240 – 156.5
MVI 5206 – – – – – 1,328 767 325 240 – 157.5 – – – – – 1,328 767 325 240 – 157.5
MVI 5207 – – – – – 1,451 891 325 240 – 178 – – – – – 1,451 891 325 240 – 178
MVI 5208 – – – – – – – – – – – – – – – – 1,481 891 370 260 – 202
MVI 5209 – – – – – – – – – – – – – – – – 1,542 952 370 260 – 205
185Vesion: 06/2004 - Subject to technical modifications
High Pressure Centrifugal PumpsAccessories
High
pre
ssur
e ce
ntrif
ugal
pum
ps
Accessories Accessories
Stainless steel mating flange (oval and round)Stainless steel mating flange for the cases, in which contact of the fluid with the standard series GG flanges is not desired.
Materials:Mating flanges: PN 16 1.4301 (Oval)/1.4404 (Round)Bolts: Galv. steelSeal: EPDM/Viton
A B C DG 1 99 75 26 ± 1G 1 1 4 99 75 27 ± 1G 1 1 2 130 100 29 ± 1
Scope of delivery:The set consists of 2 mating flanges and bolts. Seals should be ordered separately!To suit the pump application: stating EPDM or Viton version as may be required.
Technical Data:For approved fluids, See the list of resistance of materials to fluid mediaOperating pressure 16 / 25 bar (See pump application limits)Fluid temperature 50 °C / 120 °C (See also pump application limits)
without diagram
Steel mating flange (round)The set comprises 2 items, mating flange as round flange, in steel, for pump series MVI.
Victaulic CouplingsQuick connection couplings for pumps with Victaulic – connector ports.
Materials:Coupling halves: Galv. Cast ironBolts: Galv. steelSeal: EPDM/VitonInserts: 1.4435
Pump-Type Ø D DN Ø F L H MMVI / MVIS200/400 42.2 34.4 R 1 1 4 219 50 320 – 323MVI / MVIS800/1600 60.3 52.3 R 2 261 80 378
Scope of delivery:The set consists of 2 couplings incl. screws, seals and installation manual.
Technical Data:For approved fluids, See the list of resistance of materials to fluid mediaOperating pressure 16 / 25 bar (See pump application limits)Fluid temperature 50 ° / 120 °C
Bypass SetThe use of the bypass set always makes sense when the fluid contains a high amount of air or oxygen or shows a trend to gas formation.By means of the bypass set a concentration of air or gas in the upper region of the pump hydraulics on MVI pumps, and thus in the area of the mechanical seal, is largely avoided.
Typical applications where the use of the bypass installation is beneficial to the user are:Condensate pumping / Pressure boosting, where the pump/s displace water from tanks, which are vented to the atmosphere.
Materials:Pipe union MS, nickel platedSeal EPDM/Vitonall other components 1.4404
Scope of delivery:The set contains all the components required for the installation of the complete bypass pipe.
Technical Data:Operating pressure Max. 25 bar (see also pump application limits)Fluid temperature Max. 120 °CNominal connection diameter MVI 2/4/8/16/32 1/8"
B
A
C
D
DN
M
L
F
Ø D
H
186 As of: 06/2004 - Subject to change without prior notice
High Pressure Centrifugal PumpsAccessories
without diagram
Pressure SensorTo upgrade water supply/pressure booster sets with series MVISE, MVIE and MHIE to be capable of auto-matic pressure-sensitive operation. The sensor is installed on the discharge side of the pump.Note:Please follow the installation instructions in the installation and operation manual for the pumps.
Technical Data:Pressure range 0 - 10 barSignal range 4 - 20 mA
OptionsSensors for pressure ranges0 -16. 0 - 25. 0 - 40 bar
without diagram
PTC resistor control unitControl unit for control cabinet installation for all pumps in the MVI series, which are equipped with PTC resistor sensors.