  • ThemajordifferencebetweenthemeasuringCTsandProtectionCTsare:

    (1)ThemeasuringCTsaremoreaccuratethantheprotectionCTs.ThemostcommoncompositeerrorlevelsofmeasuringCTsare0.5and1,whilethemostcommoncompositeerrorlevelsforprotectionCTsare5and10.

    (2)ThesaturationlevelsofprotectionCTsaremuchhigherthantheCT'scurrentratings.ForprotectionCTs,itis10,15,20or30timeshigher,whileformeasuringCTitisatbest2times.

    (3)ProtectionCTcanbeusedforthecoursemeasuringpurpose(notaccuratemeasurement),whilemeasuringCTshallnotbeusedforprotectionpurposebecauseoflowsaturationlevel.

    (4)TheCTclass(IEC60044)forprotectionCTisdenotedby'P'(example5P20),whilethemeasuringCTisbyM(example1M)