ThemajordifferencebetweenthemeasuringCTsandProtectionCTsare:
(1)ThemeasuringCTsaremoreaccuratethantheprotectionCTs.ThemostcommoncompositeerrorlevelsofmeasuringCTsare0.5and1,whilethemostcommoncompositeerrorlevelsforprotectionCTsare5and10.
(2)ThesaturationlevelsofprotectionCTsaremuchhigherthantheCT'scurrentratings.ForprotectionCTs,itis10,15,20or30timeshigher,whileformeasuringCTitisatbest2times.
(3)ProtectionCTcanbeusedforthecoursemeasuringpurpose(notaccuratemeasurement),whilemeasuringCTshallnotbeusedforprotectionpurposebecauseoflowsaturationlevel.
(4)TheCTclass(IEC60044)forprotectionCTisdenotedby'P'(example5P20),whilethemeasuringCTisbyM(example1M)
Seethefollowinglinksforadditionalhelp: