Transcript
  • ThemajordifferencebetweenthemeasuringCTsandProtectionCTsare:

    (1)ThemeasuringCTsaremoreaccuratethantheprotectionCTs.ThemostcommoncompositeerrorlevelsofmeasuringCTsare0.5and1,whilethemostcommoncompositeerrorlevelsforprotectionCTsare5and10.

    (2)ThesaturationlevelsofprotectionCTsaremuchhigherthantheCT'scurrentratings.ForprotectionCTs,itis10,15,20or30timeshigher,whileformeasuringCTitisatbest2times.

    (3)ProtectionCTcanbeusedforthecoursemeasuringpurpose(notaccuratemeasurement),whilemeasuringCTshallnotbeusedforprotectionpurposebecauseoflowsaturationlevel.

    (4)TheCTclass(IEC60044)forprotectionCTisdenotedby'P'(example5P20),whilethemeasuringCTisbyM(example1M)

    Seethefollowinglinksforadditionalhelp:

    http://cr4.globalspec.com/thread/43440

    http://www.itluk.com/introductionprotectiontransformers.html

    http://community.myelectrical.com/wikis/myelectricalwiki/ctdimensioning.aspx

    http://cr4.globalspec.com/thread/51403


Top Related