Cypress Hill Elementary School
Nick Stuchlak – Lighting/Electrical
April 14, 2014
Senior Thesis Final Presentation
Outline
Building Overview
Lighting Design - Entrance
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
• Location: Houston, Texas
• Occupancy Type: ‘E’, Educational
• Stories: Two
• Construction Time Frame: 9/7/2012 – 11/26/2013
• Building Cost: $38.3 Million
• Project Delivery Method: Design-Build
• Total Floor Area: 115,000 Square Feet
Building Overview
Outline
Building Overview
Lighting Design - Entrance
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
• Location: Houston, Texas
• Occupancy Type: ‘E’, Educational
• Stories: Two
• Construction Time Frame: 9/7/2012 – 11/26/2013
• Building Cost: $38.3 Million
• Project Delivery Method: Design-Build
• Total Floor Area: 115,000 Square Feet
Building Overview
Outline
Building Overview
Lighting Design - Entrance
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
• Location: Houston, Texas
• Occupancy Type: ‘E’, Educational
• Stories: Two
• Construction Time Frame: 9/7/2012 – 11/26/2013
• Building Cost: $38.3 Million
• Project Delivery Method: Design-Build
• Total Floor Area: 115,000 Square Feet
Building Overview
Outline
Building Overview
Lighting Design - Entrance
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
Functions
• Grades K-5
• Multiple Classrooms
• Detached Gymnasium
• Cafeteria/Auditorium
• Library/Media Center
Building Overview
Outline
Building Overview
Lighting Design – Entrance
o Design Criteria
o Design
o Calculation
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
Spaces Analyzed
• South Façade and Entrance
• Circulation Hall
• Cafeteria/Auditorium
• Library/Media Center
Lighting Depth
Outline
Building Overview
Lighting Design – Entrance
o Design Criteria
o Design
o Calculation
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
Spaces Analyzed
• South Façade and Entrance
• Circulation Hall
• Cafeteria/Auditorium
• Library/Media Center
Lighting Depth
Outline
Building Overview
Lighting Design – Entrance
o Design Criteria
o Design
o Calculation
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
Spaces Analyzed
• South Façade and Entrance
• Circulation Hall
• Cafeteria/Auditorium
• Library/Media Center
Lighting Depth
Outline
Building Overview
Lighting Design – Entrance
o Design Criteria
o Design
o Calculation
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
Spaces Analyzed
• South Façade and Entrance
• Circulation Hall
• Cafeteria/Auditorium
• Library/Media Center
Lighting Depth
Outline
Building Overview
Lighting Design – Entrance
o Design Criteria
o Design
o Calculation
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
Design Criteria
• Safe
• Way Finding
• Reinforce architectural elements
• Interesting
• IES Illuminance and Uniformity Recommendations
• Power Density According to ASHRAE 90.1 Standards
Lighting Depth – Façade/Entrance
Outline
Building Overview
Lighting Design – Entrance
o Design Criteria
o Design
o Calculation
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
Design Criteria
• Safe
• Way Finding
• Reinforce architectural elements
• Interesting
• IES Illuminance and Uniformity Recommendations
• Power Density According to ASHRAE 90.1 Standards
Lighting Depth – Façade/Entrance
Outline
Building Overview
Lighting Design – Entrance
o Design Criteria
o Design
o Calculation
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
Design Criteria
• Safe
• Way Finding
• Reinforce architectural elements
• Interesting
• IES Illuminance and Uniformity Recommendations
• Power Density According to ASHRAE 90.1 Standards
Lighting Depth – Façade/Entrance
Outline
Building Overview
Lighting Design – Entrance
o Design Criteria
o Design
o Calculation
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
Design Criteria
• Safe
• Way Finding
• Reinforce architectural elements
• Interesting
• IES Illuminance and Uniformity Recommendations
• Power Density According to ASHRAE 90.1 Standards
Lighting Depth – Façade/Entrance
Outline
Building Overview
Lighting Design – Entrance
o Design Criteria
o Design
o Calculation
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
Design Criteria
• Safe
• Way Finding
• Reinforce architectural elements
• Interesting
• IES Illuminance and Uniformity Recommendations
• Power Density According to ASHRAE 90.1 Standards
Lighting Depth – Façade/Entrance
Outline
Building Overview
Lighting Design – Entrance
o Design Criteria
o Design
o Calculation
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
Design Criteria
• Safe
• Way Finding
• Reinforce architectural elements
• Interesting
• IES Illuminance and Uniformity Recommendations
• Power Density According to ASHRAE 90.1 Standards
Lighting Depth – Façade/Entrance
Outline
Building Overview
Lighting Design – Entrance
o Design Criteria
o Design
o Calculation
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
Lighting Depth – Façade/Entrance
Outline
Building Overview
Lighting Design – Entrance
o Design Criteria
o Design
o Calculation
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
Lighting Depth – Façade/Entrance
Outline
Building Overview
Lighting Design – Entrance
o Design Criteria
o Design
o Calculation
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
Lighting Depth – Façade/Entrance
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
o Design Criteria
o Design
o Calculation
Electrical Depth
Structural Breadth
Conclusion
Design Criteria
• Atmosphere
• Flexible
• IES Illuminance and Uniformity Recommendations
• Power Density According to ASHRAE 90.1 Standards
Lighting Depth – Cafeteria
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
o Design Criteria
o Design
o Calculation
Electrical Depth
Structural Breadth
Conclusion
Design Criteria
• Atmosphere
• Flexible
• IES Illuminance and Uniformity Recommendations
• Power Density According to ASHRAE 90.1 Standards
Lighting Depth – Cafeteria
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
o Design Criteria
o Design
o Calculation
Electrical Depth
Structural Breadth
Conclusion
Design Criteria
• Atmosphere
• Flexible
• IES Illuminance and Uniformity Recommendations
• Power Density According to ASHRAE 90.1 Standards
Lighting Depth – Cafeteria
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
o Design Criteria
o Design
o Calculation
Electrical Depth
Structural Breadth
Conclusion
Design Criteria
• Atmosphere
• Flexible
• IES Illuminance and Uniformity Recommendations
• Power Density According to ASHRAE 90.1 Standards
Lighting Depth – Cafeteria
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
o Design Criteria
o Design
o Calculation
Electrical Depth
Structural Breadth
Conclusion
Design Criteria
• Atmosphere
• Flexible
• IES Illuminance and Uniformity Recommendations
• Power Density According to ASHRAE 90.1 Standards
Lighting Depth – Cafeteria
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
o Design Criteria
o Design
o Calculation
Electrical Depth
Structural Breadth
Conclusion
Design Criteria
• Atmosphere
• Flexible
• IES Illuminance and Uniformity Recommendations
• Power Density According to ASHRAE 90.1 Standards
Lighting Depth – Cafeteria
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
o Design Criteria
o Design
o Calculation
Electrical Depth
Structural Breadth
Conclusion
Lighting Depth – Cafeteria
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
o Design Criteria
o Design
o Calculation
Electrical Depth
Structural Breadth
Conclusion
Lighting Depth – Cafeteria
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
o Design Criteria
o Design
o Calculation
Electrical Depth
Structural Breadth
Conclusion
Lighting Depth – Cafeteria
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
o Design Criteria
o Design
o Calculation
Electrical Depth
Structural Breadth
Conclusion
Lighting Depth – Cafeteria
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
Electrical Depth
o Photovoltaic Array
Structural Breadth
Conclusion
Electrical Depth
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
Electrical Depth
o Photovoltaic Array
Structural Breadth
Conclusion
Electrical Depth
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
Electrical Depth
o Photovoltaic Array
Structural Breadth
Conclusion
Electrical Depth
Assumptions
• Only undertaken to supplement gym. All excess power goes back
in the grid.
• Exempt from property and sales tax
• Optimized slope of 27 degrees facing south.
• 12 year loan period
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
Electrical Depth
o Photovoltaic Array
Structural Breadth
Conclusion
Electrical Depth
Assumptions
• Only undertaken to supplement gym. All excess power goes back
in the grid.
• Exempt from property and sales tax
• Optimized slope of 27 degrees facing south.
• 12 year loan period
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
Electrical Depth
o Photovoltaic Array
Structural Breadth
Conclusion
Electrical Depth
Assumptions
• Only undertaken to supplement gym. All excess power goes back
in the grid.
• Exempt from property and sales tax
• Optimized slope of 27 degrees facing south.
• 12 year loan period
Initial Cost $1,497.30
Assessed Value $29,945.00
Annual Energy Savings $3,866.54
Payback Period 7.5 years
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
Electrical Depth
Structural Breadth
o Roof Truss Redesign
Conclusion
Structural Breadth
Assumptions
• Dead Load – 25 psf
• Live Load – 20 psf
• Weight of array – 4840 pounds
• Asymmetrical Loading
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
Electrical Depth
Structural Breadth
o Roof Truss Redesign
Conclusion
Structural Breadth
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
Electrical Depth
Structural Breadth
o Roof Truss Redesign
Conclusion
Structural Breadth
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
Electrical Depth
Structural Breadth
o Roof Truss Redesign
Conclusion
Structural Breadth
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
Electrical Depth
Structural Breadth
o Roof Truss Redesign
Conclusion
Structural Breadth
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
Electrical Depth
Structural Breadth
o Roof Truss Redesign
Conclusion
Structural Breadth
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
Electrical Depth
Structural Breadth
o Roof Truss Redesign
Conclusion
Structural Breadth
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
Electrical Depth
Structural Breadth
o Roof Truss Redesign
Conclusion
Structural Breadth
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
Electrical Depth
Structural Breadth
o Roof Truss Redesign
Conclusion
Structural Breadth
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
Electrical Depth
Structural Breadth
o Roof Truss Redesign
Conclusion
Structural Breadth
Outline
Building Overview
Lighting Design – Entrance
Lighting Design – Cafeteria
Electrical Depth
Structural Breadth
o Roof Truss Redesign
Conclusion
Structural Breadth
Member PV Load (kip) Dead Load (k) Total Dead Load (k) Total Live Load (k) Load Combo 1 (k) Load Combo 2 (k) Size
a-1 0.45 7.04 7.49 5.64 11.808 10.486 2L2x2x3/16
i-1 0.565 6.3 6.865 5.04 10.758 9.611 2L2x2x3/16
Outline
Building Overview
Lighting Design – Entrance
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
Acknowledgements
• Dr. Mistrick
• Dr. Boothby
• Shawn Good
• Leslie Beahm
• Prof. Parfitt
• Mother and Father
Conclusions
• Lighting designs build on each other by
developing a motif throughout connected
spaces
• Spaces are enhanced and save energy
• While the photovoltaic array does not save as
much power as one might initially think, it has
a low initial cost and will be a boon, especially
with its relatively short payback
• Roof trusses work in conjuncture with PV
arrays to optimize output and new truss design
will hold the weight of the modules
Outline
Building Overview
Lighting Design – Entrance
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
Questions
Outline
Building Overview
Lighting Design – Entrance
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
Supplemental Description Lamp Ballast Mounting Voltage Input Watts Manufacturer
120V OR 277V
120
120V OR 277V
36 Deco Lighting
41 Acclaim Lighting
11.5 Axis Lighting
9 Wac Lighting 120V OR 277V
Wall
Wall
Ceiling Recessed
WallV2 LED Wall Sconce 2700K LED Intergral Driver
V1LED Recessed Linear Strip. Two 1' long LED
boards with 60 LEDs per board. 3000K LED Integral Driver
X-2 BLUE LED Wet location Exterior Wall Graze RGBA Integral Driver
X-1 CFL Wet Location Exterior Down Light (1) 32W CFL-830 Electronic Ballast
Type
Outline
Building Overview
Lighting Design – Entrance
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
Supplemental
18 Delray Lighting
23.1 Journee Lighting
40.1 Prudential Lighting
18 Delray Lighting
18 Delray Lighting
120V OR 277V
120V OR 277V
120V OR 277V
Ceiling Recessed
Ceiling Recessed
Cove
Track
Ceiling Recessed
UNIVERSAL
120V OR 277VF1 LED Linear Cove 3000K LED Integral Driver
D1 LED Track Light for Stage (2) 4' T8-830 Integral Driver
C3 5" Horizontal Double Lamp Downlight 9W Quad Tube Electronic Ballast
C2 5" Horizontal Double Lamp Downlight 13W Quad Tube Electronic Ballast
C1 5" Horizontal Double Lamp Downlight 18W Triple Twin Tube Electronic Ballast
Outline
Building Overview
Lighting Design – Entrance
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
Supplemental
Outline
Building Overview
Lighting Design – Entrance
Lighting Design - Cafeteria
Electrical Depth
Structural Breadth
Conclusion
Supplemental