fieldpoint primer
Post on 01-Jan-2016
34 Views
Preview:
DESCRIPTION
TRANSCRIPT
www.natinst.comwww.natinst.com
FieldPoint Primer
Eloisa Acha
Automation Applications Engineer
Tue. 10:15a and 11:15a
Wed. 10:15a, 11:30a, 12:45p, 2:00p, 3:30p, and 4:45p
Exhibit Hall (3F)
www.natinst.comwww.natinst.com
FieldPoint – Distributed I/OFieldPoint – Distributed I/O
NN NNControl Panel
Flow
Pressure Alarm Conditions
STOP
Temperature
Industrial Network
NN NN NN NN
ModularIndustrial
Easy-to-UseNetworked
www.natinst.comwww.natinst.com
FieldPoint – I/O OptionsFieldPoint – I/O Options
I/O ModulesI/O ModulesModel Type Ch I/O RangesFP-AI-100 Analog Input, 12-bit 8 1 V to 36V, 20 mAFP-AI-110 Analog Input, 16-bit 8 mV, V, 20 mAFP-AI-111 Analog Input, 16-bit 16 20 mAFP-TC-120 Thermocouples 8 J,K,T,E,R,S,B,N, mVFP-RTD-122 RTDs, Resistance 8 PT100, PT1000FP-AO-200 Analog Output 8 0-20 mAFP-DI-330 Discrete Input 8 5V to 240 VAC/DC
FP-DI-300 Discrete Input 8 24 VDCFP-DI-301 Discrete Input 16 24 VDCFP-DO-400 Discrete Output 8 24 VDCFP-DO-401 Discrete Output 16 24 VDCFP-RLY-420 Relays, SPST 8 3A @ 35 VDC/240 VAC
FP-CTR-500 Counter Input 8 50 kHz, 24 VDC
FP-PWM-520 Pulse-Width-Modulated Outputs
8 1A @ 5-24 VDC
Model TypeFP-TB-1 Screw TerminalsFP-TB-2 Spring Terminals
Terminal Bases
www.natinst.comwww.natinst.com
Network Interface OptionsNetwork Interface Options Serial Ethernet TCP/IP
• 10 Mbps and 100 Mbps
FOUNDATION Fieldbus, H1• Embedded function blocks
– AI, AO, DI, DO, PID
Wireless• Spread spectrum, 900MHz• Works via RS-232
www.natinst.comwww.natinst.com
FieldPoint with RS-232/RS-485FieldPoint with RS-232/RS-485
Control Panel
Flow
Pressure Alarm Conditions
STOP
Temperature
RS-232 orRS-485
FP-1000 RS-232 network interface• Connects directly to PC COM port
• Second RS-485 connector to additional FP-1001 modules
FP-1001 RS-485 network interface
RS-485
Up to 25 banks (1,200 m)
www.natinst.comwww.natinst.com
Ethernet ConnectivityEthernet Connectivity
FP-1600 network interface• TCP/IP compatibility
• 10 Mbps and 100 Mbps
• Event-driven communications
• Instant data connectivity to network, intranet, and Internet
10Base-T or 100Base-TX
www.natinst.comwww.natinst.com
Distributed Control with FieldbusDistributed Control with Fieldbus
FP-3000 network interface/controller module• FOUNDATION Fieldbus H1
• Link Active Scheduler
Embedded function blocks• PID function block for stand-alone, distributed control
• AI, AO, DI, DO, CDO blocks– Alarming, trending, filtering, scaling, interlocks
PIDPID
FP-3000
AI AO
www.natinst.comwww.natinst.com
FieldPoint TechnologyFieldPoint Technology
Plug and Play installation and replacementProgrammable power-up
and watchdog statesRobustness and reliability
• Isolation on each module• Wide operating temperature range
-40 °C to + 70 °C (-40 °F to +160 °F)
www.natinst.comwww.natinst.com
Configuration SoftwareConfiguration Software
Quick configuration• Network and communications
– Baud rate, addressing, IP, etc.
• FieldPoint hardware– Ranges, filters, power-up states, etc.
• Servers – Named tags, scan rate, etc.
Troubleshooting, monitoringWindows NT/98/95
www.natinst.comwww.natinst.com
FieldPoint SoftwareFieldPoint Software
FieldPoint Server• BridgeVIEW• LabVIEW VIs• LabWindows/
LabWindows/CVI
Lookout driver OPC Server
FieldPointServer
FieldPointServer
BridgeVIEWBridgeVIEW LabVIEW,LW/CVI
LabVIEW,LW/CVI
LookoutDriver
LookoutDriver
NN NN
Third-PartyOPC clientThird-PartyOPC client
top related