32
FR-XLPE/PVCShielded-LCTAPPLICATIONS
• Predominantly used in utility substations
• Can be installed indoors or outdoors, in cable
trays, conduit, underground duct, or direct
buried in wet or dry locations
• Conductor operating temperatures are not to
exceed 90°C wet or dry
• Rated 600 Volts
CONSTRUCTION DETAILS
• Conductors
• 14 AWG thru 10 AWG Annealed Class B
Copper Unilay Compressed Stranded
• Insulation
• Flame Retardant Cross-Linked
Polyethylene (FR-XLPE)
• Color Coded per preferred method in
ICEA S-73-532 standard
• Assembly
• Cabled with non-hygroscopic polyethylene
fillers in order to give the cable a circular
cross-section, when needed
• Wrapped with a Mylar binder
• Shield
• Longitudinally corrugated 5 mil annealed
copper tape
• Overall Jacket
• Heat, Moisture, and Sunlight Resistant Black
Polyvinyl Chloride (PVC)
• SOUTHWIRE XXAWG XX/C FR-XLPE (XHHW-2)
CDS 90C PVC JKT SHIELDED TYPE TC 600V
SUN. RES. DIRECT BURIAL YEAR SEQUENTIAL
FOOTAGE MARKS
SPECIFICATIONS
Southwire’s Type TC Substation Control Cable
meets or exceeds:
• All applicable ASTM Standards
• ANSI/ICEA S-73-532
• UL 44 Type XHHW-2 rated VW-1
• UL 1277
• UL 1581
• IEEE 1202
• ICEA T-29-520
• RoHS Compliant
OPTIONS
Strand:
• Stranding Classes – C, K
• Tin Coated Copper
Color Coding Methods:
• Color Coding per ICEA S-73-532
• Method 1, Table E1
• Method 1, Table E2
• Method 4
• Custom, available upon request
Insulation:
• PE/PVC
• PE
• FR-XLPE
• THHN
Binder Tape:
• Flame Retardant
Shielded Constructions:
• CU LCT
• CU Helical Tape
• AL Helical Tape
• AL Longitudinal
• With drain wire
Jacket:
• PVC
• LSZH-TP
• LSZH-TS
• CPE-TP
• CPE-TS
Other:
• Rip cord
• 1000 Volt rated
• Custom print
Additional constructions available upon request
SUBSTATION CONTROL CABLE | Shielded (LCT Shield)
CONDUCTOR TYPE14 – 10 AWG COPPER
INSULATION TYPE FR-XLPE
SHIELD TYPE LONGITUDINAL
CORRUGATED
COPPER TAPE
JACKET TYPEPVC
CONSTRUCTIONAT A GLANCE
1
1
2
2
4
4
3
3
33
SU
BS
TA
TIO
N C
ON
TR
OL
CA
BL
E |
Sh
ield
ed
(LC
T S
hie
ld)
FR
-XL
PE
/P
VC
Number of Conductors
Conductor Size
(AWG)
LCT Copper Tape Shield Thickness(inches)
Nominal Jacket Thickness (inches)
Nominal Overall Diameter Approximate Weight
(inches) (mm) (lbs/1000 ft) (kg/km)
Shielded AWG 14 (7 strands)
2 14 0.005 0.045 0.363 9.2 97 144
3 14 0.005 0.045 0.384 9.8 120 178
4 14 0.005 0.045 0.417 10.6 146 217
5 14 0.005 0.045 0.454 11.5 172 256
6 14 0.005 0.045 0.493 12.5 199 296
7 14 0.005 0.045 0.493 12.5 217 323
8 14 0.005 0.060 0.563 14.3 260 386
9 14 0.005 0.060 0.6018 15.3 288 428
10 14 0.005 0.060 0.652 16.6 319 474
12 14 0.005 0.060 0.673 17.1 360 536
Shielded AWG 12 (7 strands)
2 12 0.005 0.045 0.398 10.1 122 181
3 12 0.005 0.045 0.422 10.7 154 229
4 12 0.005 0.045 0.459 11.7 189 282
5 12 0.005 0.045 0.502 12.7 225 335
6 12 0.005 0.060 0.576 14.6 278 413
7 12 0.005 0.060 0.576 14.6 305 453
8 12 0.005 0.060 0.621 15.8 343 510
9 12 0.005 0.060 0.666 16.9 381 567
10 12 0.005 0.060 0.723 18.4 422 628
12 12 0.005 0.060 0.746 19.0 482 717
Shielded AWG 10 (7 strands)
2 10 0.005 0.045 0.446 11.3 159 237
3 10 0.005 0.045 0.4728 12.0 206 306
4 10 0.005 0.060 0.546 13.9 271 403
5 10 0.005 0.060 0.595 15.1 323 481
6 10 0.005 0.060 0.646 16.4 376 560
7 10 0.005 0.060 0.646 16.4 417 620
8 10 0.005 0.060 0.699 17.8 471 700
9 10 0.005 0.060 0.750 19.1 524 779
10 10 0.005 0.060 0.817 20.8 581 864
12 10 0.005 0.080 0.884 22.5 700 1042
Dimensions and weights shown above are nominal and subject to industry tolerances.