IEEE1818 - 2017 Guide for the Design of Low Voltage AC and DC Auxiliary

Systems for SubstationsSponsored by the IEEE Substations Committee

Presented By Joe Gravelle

2

Organization of the Guide1. Scope / Purpose2. Normative References3. Definitions4. AC System Design5. DC System DesignAnnex A – BibliographyAnnex B - Conductor Sizing examplesAnnex C – Battery Sizing Examples

3

Organization of the Guide1. Scope / Purpose2. Normative References3. Definitions4. AC System Design5. DC System DesignAnnex A – BibliographyAnnex B - Conductor Sizing examplesAnnex C – Battery Sizing Examples

4

1.1 Scope• This guide provides guidelines for the design of

the ac and dc systems. • This guide covers the low voltage auxiliary

systems from the source(s) to the distribution point(s).

• Reliability requirements and load characteristics

5

1.2 Purpose• The low-voltage ac and dc auxiliary systems comprise

very important parts of the substation equipment. • Design of the ac and dc auxiliary systems

• reliability, • load requirements, • system configuration, • personnel safety, • safe and reliable operation• protection

6

2.0 Normative References• IEEE 485, IEEE 525

3.0 Definitions• Definitions are provided for technical terms used

in the guide.

7

Organization of the Guide1. Scope / Purpose2. Normative References3. Definitions4. AC System Design5. DC System DesignAnnex A – BibliographyAnnex B - AC examplesAnnex C – DC Examples

8

4.0 AC System Design • Design Criteria• Source Requirements• Load Analysis• Conductor Selection• Transformer(s)• Transfer Switch • Bus Layout• Panels• Protection• Equipment Specifications• Operations and Maintenance

9

4.1 Introduction• Design Criteria• Source Requirements

• Number of sources• 1 phase or 3 phase• Load Requirements

These sections define the AC system for the substation Application.

10

4.2 Design Criteria • AC system loads• 1 or 3 phase• System stability• Protection• Voltage

This section defines the AC system design.

11

4.3 AC sources • Transformer tertiary

• Substation bus

• Distribution line

• Generators

12

4.4 AC Load Analysis • Identification

• Amps/Volts/kW

• Equipment rating

• Demand factors

• Load calculations

13

4.5 Conductor Selection• Conductor Type

• Insulation

• Temperature Rating

• Size – Ampacity

• Voltage Drop

14

4.6 Station Auxiliary Transformer • Transformer Type

15

4.6 Station Auxiliary Transformer • Number of transformers

• Single/Three phase

• Transformer Ratings

• Transformer Connections

16

4.6 Station Auxiliary Transformer • Transformer Ratings

• KVA• Voltage• Short Circuit • Impedance• BIL

17

4.6 AC System Design • Transformer Connections Single Phase

18

4.6 AC System Design • Transformer Connections Three Phase

19

4.7 Transfer Switch • Manual / Automatic

• Considerations:

• Break before Make

• Switching Neutrals

20

4.8 Bus Layout - Distribution Configuration• Essential / Non-Essential Loads

• Simple Radial System

• Expanded Radial System

• Primary / Secondary Selective systems

21

4.8 Bus Layout and Distribution Circuit Configuration

22

4.9 AC Distribution Panelboards

• Application• Ratings• Short Circuit ratings• Standards

23

4.10 AC Auxiliary System Protection • Panelboard or Switchboard

• Circuit Breaker Selection

• Fuse Selection

24

4.11 Equipment Specifications• General considerations

• Standards

25

4.12 Operation - Maintenance Consideration• Accessible Disconnects

• Indoor/Outdoor Design

• Adequate Working Space

• Standby or Backup AC System

26

27

Organization of the Guide1. Scope / Purpose2. Normative References3. Definitions4. AC System Design5. DC System DesignAnnex A – BibliographyAnnex B - AC examplesAnnex C – DC Examples

28

DC System Design • Design Criteria• DC Equipment • One Line Diagram• Batteries• Chargers• Panels• Design Considerations • Maintenance Provisions

29

Battery System

30

Battery SystemSingle cell battery with acid

containment on a two step rack

31

5.1 DC System Design Criteria • Reliability

• Redundancy

• Environment

32

5.2 Equipment Served by the DC System • System Protection Equipment• Motor Operators• Breakers• SCADA• Fire Protection• Security

33

5.3 One Line Diagram • Power System One Line

• System protection• DC System One Line

• DC Load Calculations• DC Connections• Number of Batteries• Load Transfer

34

Substation One LineOperating sequence:

12D3 is normally closed, no generation on feeder circuitsOperating time for MOS 10 seconds

Transformer T1 differential:Trip 69CB1, 69CB3, 12CB1Open 69DT1

Breaker Failure on 12CB1:Open 12CB2, Open 12D3, Reclose 12CB2

35

DC System

Battery

Battery Charger

Panel

To DC Cab.

Maint Charger & Battery

36

DC System distribution cabinet(s)

37

5.4 DC Batteries Battery System

Battery Charger(s)

Battery Disconnect(s)

DC Panel(s)

Maintenance Connections

DC Loads

38

5.4 DC Batteries

39

5.4 DC Battery Types Vented Lead Acid (VLA)

Valve Regulated Lead Acid (VRLA)

Nickel Cadmium (NiCad)

• For substation use, vented lead-acid cells are the most common

40

5.4 DC Battery

41

5.4 DC Battery

42

5.4 DC Battery

43

Battery SizingSizing the battery using IEEE 485 (Vented Lead Acid Batteries)

Defining the Duty Cycle (loading on battery based on time duration)

Continuous Load

Momentary Load

Worst Case Tripping

44

Continuous LoadsIndicating lamps, Microprocessor Relays, Electronic Meters, SCADA Systems, Annunciators, Communication Equipment

o For loads that are non-linear such as power supplies, the current increases as voltage declines.

o The watt rating is typically used to determine current at end of battery cycle discharge voltage

45

Momentary LoadsLock Out Relay (LOR) Breaker trippingMotor Operators Breaker Fail operation Considerations:

o Worst Case Tripping Scenarios

o MOD use Locked Rotor rating

o Breaker Fail use SOE not sum of all currents select highest

46

Worst Case Tripping Operating sequence:12D3 is normally closed, no generation on feeder circuitsOperating time for MOS 10 seconds

Transformer T1 differential:Trip 69CB1, 69CB3, 12CB1Open 69DT1

Breaker Failure on 12CB1:Open 12CB2, Open 12D3, Reclose 12CB2

Timing:T=0cy (0 sec)Trip 69CB1, 69CB3, 12CB1, open 69DT1Current=12+12+8+60=92A

T=12cy (0.2sec) (12CB1 breaker failure timer)Trip 12CB2, Re-Trip 12CB1 open 12D3Current=20+8+8+60=96A

T=600cy (10sec)Reclose 12CB2Current=6A

From the above, the worst case tripping load is 96A for the 12CB1 breaker failure.

47

Duty Cycle Duration1. Charger fails – Initiates Alarm to SCADA2. Dispatcher notices Alarm3. Dispatch contacts Substation Personal4. Substation Personal Drive to Substation5. Investigate Alarm6. Determines Charger Failed – contacts dispatch requesting maintenance 7. Dispatch contacts Maintenance8. Maintenance Technician Drives to Substation9. Maintenance attempts to repair charger (unsuccessful)10.Maintenance Supervisor locates spare charger11.Maintenance Supervisor contacts additional resources12.Resources drive to service center PU spare charger and drive to substation13.Replace failed Charger

48

Duty Cycle Example

49

Battery Chargers

Sizing battery Chargers

Charger Connections

Charger Circuit Protection

50

Battery Chargers

51

Battery Charger size

52

DC Panels

Considerations

Critical Loads vs non-Critical Loads

Circuit size

Number of circuits

53

DC Panels

54

DC Panels

55

Design Considerations• Battery location

• Maintenance considerations • Working clearances• Method for removing

battery cells• An eyewash station • Spill containment

systems• Terminal Covers

56

Battery Terminal Covers

57

Design Considerations

• Battery area temperature• Specifications published for sizing

• Heat and Cold impact battery performance

• Reference IEEE485 for effect on Battery Size

58

Design Considerations• Acid spill containment

• Spill Pans• Acid-resistant paint on the floor

59

Design Considerations• Battery racks

• Three types—step, tier, or stepped tier

• Height variations between cells can cause cell temperature differences within the same battery system

• acid-resistant coating applied to the structural frame

• seismic zone

60

Design Considerations • Battery rack

61

Design Considerations Circuit considerations • Grounded and ungrounded systems

• Ungrounded –Substation Control - SCADA

• Grounded ((+) grounded) – Communications

62

Design Considerations -Circuit considerations

• Isolation of Main DC cables • Recommendations - IEEE 1375

• Battery fuse • Battery circuit breaker• Battery disconnect switch • Mid-point battery fuse

63

Circuit considerations • Isolation of main dc cables - Separate the pos and neg cables

64

Design ConsiderationsCircuit considerations

• Coordination of overcurrent protection• Short-circuit levels• Fuses• Breakers• Equipment voltage ratings

65

Maintenance Provisions• Isolation switches

• Equipment accessibility

• Back-up supplies

66

Maintenance Provisions• Testing Provisions

67

DC System

Battery

Battery Charger

Panel

To DC Cab.

Maint Charger & Battery

68

AnnexAnnex A – Bibliography

Annex B - Conductor Sizing Example

Annex C – Battery Sizing Example

69