mezzanine floor ltg. calculation.pdf
Post on 02-Jun-2018
233 Views
Preview:
TRANSCRIPT
8/10/2019 MEZZANINE FLOOR LTG. CALCULATION.pdf
http://slidepdf.com/reader/full/mezzanine-floor-ltg-calculationpdf 1/17
PANOS H
PANOS HF 2/26W TC-DEL EVG 200 WH 60 810 251
ceiling-recessed luminaire
Ceiling-recessed luminaire; lamp(s): 2/26W TC-DEL; horizontal lamp position; with high frequency ballast, (separateunit) ; reflector: facetted, aluminium-sputtered, mirrorbrite and iridescent-free, DSE-compatibel resp. UGR: 16/19 with
PANOS HF, with PANOS LF only with radial louvre (as accessory, please order separately); flange white;reflector/flange unit made of high-quality UV-resistant polycarbonate; mounting ring made of die-cast aluminium;electrical connection: 5-pole connector terminal; no-tool quick installation for ceiling thickness 1-25mm; ceilingcut-out: 200mm, mounting depth: 145mm; weight: 0.94 kgPlease note: attachments need to be ordered separately. The attachments holding-ring is included in the supply ofaccessories.
We reserve the right to make t echnical changes without prior notice. 04.2010 © Zumtobel
Light distribution STD - standardZS_PAN_F_HF_200.jpg ZS_PAN_M_H200.wm
0°
30 °30 °
60°60 °
90° 90°
120° 120°
150° 150°
180°
10 020 0300
cd/klm C270 | C90
C180 | C0
st5112.ldt
• Lamps: 2 x TC-DEL/26 W• Total luminous flux: 3600 lm• Color Rendering Index: 1B• Ballast: EVG Tridonic PC PRO• Connected Load: 51.0 W, Lambda = 0.98• CELMA EEI: A2
8/10/2019 MEZZANINE FLOOR LTG. CALCULATION.pdf
http://slidepdf.com/reader/full/mezzanine-floor-ltg-calculationpdf 2/17
MIREL
REP 4/18W T26 EVG M600 40 317 791
rec. lum. with prismatic controller
Rec. lum. with prismatic controller 4/18W, for T26, with high frequency ballast, recessed housing made of whitestove-enamelled sheet steel, 5-pole connector terminal; diffuser made of clear, non-yellowing methacrylate and
natural anodised decorative aluminium frame; Luminaire wired with halogen-free leads. Modul: 600; dimensions: 598x 598 x 94 mm, weight: 5.66 kg.
We reserve the right to make t echnical changes without prior notice. 04.2010 © Zumtobel
Light distribution STD - standard
ZS_MEL_F_REP.jpg
598
514
565
1 0
5 0
9 4
4 ,
5
12
576
L= 598 mm
ZS_MEL_M_M6004FL18W.wm
0°
30°30°
60°60°
90° 90°
120° 120°
150° 150°
180°
100200300
cd/klm C270 | C90
C180 | C0
D05872T1.ldt
• Lamps: 4 x T26/18 W• Total luminous flux: 5400 lm• Color Rendering Index: 1B• Ballast: EVG Tridonic PC PRO• Connected Load: 73.0 W, Lambda = 0.97• CELMA EEI: A2
8/10/2019 MEZZANINE FLOOR LTG. CALCULATION.pdf
http://slidepdf.com/reader/full/mezzanine-floor-ltg-calculationpdf 3/17
MIREL
REP 2/36W T26 EVG M600 40 317 722
rec. lum. with prismatic controller
Rec. lum. with prismatic controller 2/36W, for T26, with high frequency ballast, recessed housing made of whitestove-enamelled sheet steel, 5-pole connector terminal; diffuser made of clear, non-yellowing methacrylate and
natural anodised decorative aluminium frame; Luminaire wired with halogen-free leads. Modul: 600; dimensions:1198 x 298 x 94 mm, weight: 6.23 kg.
We reserve the right to make t echnical changes without prior notice. 04.2010 © Zumtobel
Light distribution STD - standard
ZS_MEL_F_REP.jpg
298
214
265
1 0
5 0
9 4
4 ,
5
12
276
L= 1198 mm
ZS_MEL_M_M6002FL36W.wm
0°
30°30°
60°60°
90° 90°
120° 120°
150° 150°
180°
100200300
cd/klm C270 | C90
C180 | C0
D05868T2.ldt
• Lamps: 2 x T26/36 W• Total luminous flux: 6700 lm• Color Rendering Index: 1B• Ballast: EVG Tridonic PC PRO• Connected Load: 70.0 W, Lambda = 0.97• CELMA EEI: A2
8/10/2019 MEZZANINE FLOOR LTG. CALCULATION.pdf
http://slidepdf.com/reader/full/mezzanine-floor-ltg-calculationpdf 4/17
Project 1
10.01.20
Operator Telephone
Faxe-Mail
Engr Workshop MF004 / Summar
240
240
320
320320 320
320
320320
400
400400 400
400
400
400
400
400
480
480480
480 480
480
480
480
480480
15.96 m0.00 12.73
6.58 m
0.00
2.35
Height of Room: 3.200 m, Maintenance factor: 0.80 Values in Lux, Scale 1:1
Surface [%] Eav [lx] Emin [lx] Emax [lx]
Workplane / 361 169 535 0.46
Floor 20 322 148 469 0.45
Ceiling 70 74 50 132 0.66
Walls (6) 50 166 69 632
Workplane:Height: 0.750 mGrid: 64 x 32 PointsBoundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.462, Ceiling / Working Plane: 0.205.
Luminaire Parts List
Specific connected load: 11.89 W/m² = 3.29 W/m²/100 lx (Ground area: 92.09 m²)
No. Pieces Designation (Correction Factor) [lm] P [W
1 15 Zumtobel 40 317 791 REP 4/18W T26 EVG M600 [STD] (1.000) 5400 73
Total: 81000 1095
Pag
8/10/2019 MEZZANINE FLOOR LTG. CALCULATION.pdf
http://slidepdf.com/reader/full/mezzanine-floor-ltg-calculationpdf 5/17
Project 1
10.01.20
Operator Telephone
Faxe-Mail
Engr Workshop MF004 / Workplane / Value Chart (E
193 215 212 199 200 233 264 279 284 294 293 292 296 295 286 280 263 233 213 201 195
231 261 252 230 233 275 317 333 342 352 351 351 355 355 347 340 319 280 245 236 237
276 314 305 273 275 334 385 401 410 425 422 420 430 430 419 410 385 329 251 260 262
320 361 350 313 316 379 438 457 465 476 476 478 490 491 479 474 435
340 388 375 336 340 403 465 483 486 492 494 502 520 527 517 509 458
355 400 388 344 344 415 473 481 473 477 478 495 525 535 526 517 474
349 397 385 342 343 408 461 461 439 431 436 466 508 527 521 515 472
335 380 367 329 331 387 435 426 389 368 378 422 478 505 501 500 451
308 348 337 298 298 354 392 370 324 297 308 361 425 457 455 452 415
266 304 293 260 261 307 339 313 265 235 246 300 361 393 393 391 361
15.96 m0.00 12.73
6.58 m
0.00
2.35
Values in Lux, Scale 1 : 1Not all calculated values could be displayed.
Position of surface in room:Working plane with 0.100 m BoundaryZoneMarked point:(45.183 m, 39.792 m, 0.750 m)
Grid: 64 x 32 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Em
361 169 535 0.469 0.3
Pag
8/10/2019 MEZZANINE FLOOR LTG. CALCULATION.pdf
http://slidepdf.com/reader/full/mezzanine-floor-ltg-calculationpdf 6/17
Project 1
10.01.20
Operator Telephone
Faxe-Mail
Staff canteen GF052 / Summar
400
500
500500
500
500
500 500
500
600
600
600600
600
600
600
600 600 600
600
700
700700
700
700
12.52 m0.00 7.33
13.68 m
0.00
11.64
Height of Room: 3.200 m, Mounting Height: 3.289 m, Maintenance factor:0.80
Values in Lux, Scale 1:17
Surface [%] Eav [lx] Emin [lx] Emax [lx]
Workplane / 577 268 732 0.46
Floor 20 537 267 668 0.49
Ceiling 70 119 91 180 0.76
Walls (6) 50 275 126 591
Workplane:Height: 0.750 mGrid: 64 x 64 PointsBoundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.489, Ceiling / Working Plane: 0.206.
Luminaire Parts List
Specific connected load: 17.65 W/m² = 3.06 W/m²/100 lx (Ground area: 161.34 m²)
No. Pieces Designation (Correction Factor) [lm] P [W
1 39 Zumtobel 40 317 791 REP 4/18W T26 EVG M600 [STD] (1.000) 5400 73
Total: 210600 2847
Pag
8/10/2019 MEZZANINE FLOOR LTG. CALCULATION.pdf
http://slidepdf.com/reader/full/mezzanine-floor-ltg-calculationpdf 7/17
Project 1
10.01.20
Operator Telephone
Faxe-Mail
Staff canteen GF052 / Workplane / Value Chart (E
406501550569582571551518448
459587637654667653633589512
582659686709710703681631547
413479515539544557634661702717730726720691632539
448512550578589610644656684694700702688664607519
466529583608627640643655658666668664655627576497
476536591619634646647653654658659655646619570491
480546599634645654654658663662666659649623572498
476543594628639648646651653653657649640614564490
473534587617630637635641638641640635626599550470
475536591616634638636641638643638637625599550469
479546594628636647643648649647649640632603555477
481546594627637643642644646643647638628602553477
469535586615626635631637633635633627619591542465
478536589614631633633637633637632631617592543468
478538585616627635633636636633634627618592542471
464527577604618623623625623623622618607582532455
451506556581593599597601597601597594583559510436
442495544564581581583585582586580582566546498430
399447488510518527525530527526525519512491452394
354394432449456463463467465465461454453432396344
12.52 m0.00 7.33
13.68 m
0.00
11.64
Values in Lux, Scale 1 : 10Not all calculated values could be displayed.
Position of surface in room:
Working plane with 0.100 m BoundaryZoneMarked point:(79.458 m, 23.770 m, 0.750 m)
Grid: 64 x 64 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Em
577 268 732 0.464 0.36
Pag
8/10/2019 MEZZANINE FLOOR LTG. CALCULATION.pdf
http://slidepdf.com/reader/full/mezzanine-floor-ltg-calculationpdf 8/17
Project 1
10.01.20
Operator Telephone
Faxe-Mail
Sales Marketing MF007 / Summar
520520
520520
650650
650
650
650
650
650 650
650
650
780
780
780
780
780
780780 780
780
780
8.82 m0.00
9.76 m
0.00
Height of Room: 3.200 m, Mounting Height: 3.289 m, Maintenance factor:0.80
Values in Lux, Scale 1:12
Surface [%] Eav [lx] Emin [lx] Emax [lx]
Workplane / 693 296 919 0.42
Floor 20 627 296 820 0.47
Ceiling 70 143 98 189 0.68
Walls (4) 50 322 135 597
Workplane:Height: 0.750 mGrid: 64 x 64 PointsBoundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.468, Ceiling / Working Plane: 0.206.
Luminaire Parts List
Specific connected load: 22.14 W/m² = 3.20 W/m²/100 lx (Ground area: 85.72 m²)
No. Pieces Designation (Correction Factor) [lm] P [W
1 26 Zumtobel 40 317 791 REP 4/18W T26 EVG M600 [STD] (1.000) 5400 73
Total: 140400 1898
Pag
8/10/2019 MEZZANINE FLOOR LTG. CALCULATION.pdf
http://slidepdf.com/reader/full/mezzanine-floor-ltg-calculationpdf 9/17
Project 1
10.01.20
Operator Telephone
Faxe-Mail
Sales Marketing MF007 / Workplane / Value Chart (E
443494545589587550505470424395396394389371337
519588647689690655601551501476476475463444408
566648720768770732672615566539533535526503453
630716794847848812754701653626621617614580526
661751828880881851799750699680678668660625570
688770843909915881842813763737738729708669610
680766841892898889856822787768759740721675608
680759828883895887870849818804794768747694630
670747812865879880868859836824821795766716651
651730793844863865860861840831831806770723658
641713782827842852854843832833824796769717646
636709769814829847851842836837826798777718649
636711769820840848852854841838839812780729660
625699755806830835840846832830831806770723657
616684748793811824831826818823814789765710641
609675732775790808816807805806798771752696628
596666721770788796804807797796797773744695627
559624680725746750757760750750752729698657593
532587644684700707716714706709705683661617556
473520569601618629636629629629624606588546490
435480520556573578583585579578579563539506459
8.82 m0.00
9.76 m
0.00
Values in Lux, Scale 1 : 7Not all calculated values could be displayed.
Position of surface in room:
Working plane with 0.100 m BoundaryZoneMarked point:(70.561 m, 45.893 m, 0.750 m)
Grid: 64 x 64 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Em
693 296 919 0.428 0.32
Pag
8/10/2019 MEZZANINE FLOOR LTG. CALCULATION.pdf
http://slidepdf.com/reader/full/mezzanine-floor-ltg-calculationpdf 10/17
Project 1
10.01.20
Operator Telephone
Faxe-Mail
HR Department MF068 / Summar
420560
560
560
560
700
700700700700700
700 700
700 700
38.33 m0.00 33.15
4.25 m
0.00
3.28
Height of Room: 3.200 m, Mounting Height: 3.289 m, Maintenance factor:0.80
Values in Lux, Scale 1:27
Surface [%] Eav [lx] Emin [lx] Emax [lx]
Workplane / 620 157 824 0.25
Floor 20 545 128 710 0.23
Ceiling 70 121 47 160 0.38
Walls (6) 50 261 49 769
Workplane:Height: 0.750 mGrid: 128 x 32 PointsBoundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.423, Ceiling / Working Plane: 0.196.
Luminaire Parts List
Specific connected load: 21.97 W/m² = 3.54 W/m²/100 lx (Ground area: 146.79 m²)
No. Pieces Designation (Correction Factor) [lm] P [W1 33 Zumtobel 40 317 791 REP 4/18W T26 EVG M600 [STD] (1.000) 5400 73
2 16 Zumtobel 60 810 251 PANOS HF 2/26W TC-DEL EVG 200 WH [STD] (1.000) 3600 51
Total: 235800 3225
Pag
8/10/2019 MEZZANINE FLOOR LTG. CALCULATION.pdf
http://slidepdf.com/reader/full/mezzanine-floor-ltg-calculationpdf 11/17
Project 1
10.01.20
Operator Telephone
Faxe-Mail
HR Department MF068 / Workplane / Value Chart (E
348466480597644666689692678677683650616664677673648606
363594558693778807816818818810808760718797802794782730
251510486568638664671671674666661618584660660653647600
38.33 m0.00 33.15
4.25 m
0.00
3.28
Values in Lux, Scale 1 : 27Not all calculated values could be displayed.
Position of surface in room:Working plane with 0.100 m Boundary
ZoneMarked point:(85.839 m, 48.692 m, 0.750 m)
Grid: 128 x 32 Points
Eav
[lx] Emin
[lx] Emax
[lx] u0 Emin
/ Em
620 157 824 0.254 0.19
Pag
8/10/2019 MEZZANINE FLOOR LTG. CALCULATION.pdf
http://slidepdf.com/reader/full/mezzanine-floor-ltg-calculationpdf 12/17
Project 1
10.01.20
Operator Telephone
Faxe-Mail
Female Prayer RM MF013 / Summar
210
210
280
280 280
280
280
280280
280
350
350
350 350
350
350
350350
350
420
420420
420
420
420
420420420
5.68 m0.00
6.04 m
0.00
Height of Room: 3.200 m, Mounting Height: 3.345 m, Maintenance factor:0.80
Values in Lux, Scale 1:7
Surface [%] Eav [lx] Emin [lx] Emax [lx]
Workplane / 332 138 468 0.4
Floor 20 292 136 427 0.46
Ceiling 70 50 34 59 0.67
Walls (4) 50 99 36 178
Workplane:Height: 0.750 mGrid: 64 x 64 PointsBoundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.278, Ceiling / Working Plane: 0.151.
Luminaire Parts List
Specific connected load: 13.38 W/m² = 4.03 W/m²/100 lx (Ground area: 34.30 m²)
No. Pieces Designation (Correction Factor) [lm] P [W
1 9 Zumtobel 60 810 251 PANOS HF 2/26W TC-DEL EVG 200 WH [STD] (1.000) 3600 51
Total: 32400 459
Pag
8/10/2019 MEZZANINE FLOOR LTG. CALCULATION.pdf
http://slidepdf.com/reader/full/mezzanine-floor-ltg-calculationpdf 13/17
Project 1
10.01.20
Operator Telephone
Faxe-Mail
Female Prayer RM MF013 / Workplane / Value Chart (E
166 185 208 234 254 263 269 271 270 270 267 262 247 221 199 182
188 204 217 242 280 306 304 292 288 296 309 298 264 232 212 206
199 223 252 276 312 327 337 335 328 335 332 328 300 266 242 224
230 256 284 315 352 378 378 375 365 378 381 367 342 295 280 249
242 272 300 335 376 396 406 398 392 402 398 393 362 319 295 268
257 283 298 336 393 429 426 407 401 416 435 419 372 329 298 281
259 295 332 378 416 433 441 442 439 442 440 428 403 353 319 287
265 301 337 384 422 440 448 450 447 450 447 436 409 360 325 293
270 297 315 355 414 451 448 429 423 439 457 440 393 346 314 296
266 304 337 376 419 440 451 444 439 448 444 437 404 359 330 298
276 314 347 385 428 461 459 455 445 459 464 448 416 361 342 302
262 298 332 366 414 437 447 439 430 442 443 436 398 351 322 295
269 298 321 363 415 449 449 434 426 441 454 439 395 345 314 295
263 299 339 387 420 437 445 451 449 449 443 432 411 362 327 290
261 292 321 366 407 434 438 430 426 432 440 427 391 342 309 287
246 277 302 340 384 413 418 405 401 409 421 410 366 327 295 275
239 267 296 330 369 395 397 391 381 396 396 385 355 307 290 260
215 240 268 300 331 351 355 356 347 357 352 343 321 281 263 235
190 212 229 258 289 311 315 307 307 310 318 308 277 251 225 213
176 195 213 239 267 285 288 282 280 283 289 280 254 224 203 194
155 171 195 220 239 244 250 255 253 254 248 244 233 207 187 168
5.68 m0.00
6.04 m
0.00
Values in Lux, Scale 1 : 4Not all calculated values could be displayed.
Position of surface in room:Working plane with 0.100 m BoundaryZoneMarked point:(64.361 m, 31.451 m, 0.750 m)
Grid: 64 x 64 Points
Eav
[lx] Emin
[lx] Emax
[lx] u0 Emin
/ Em
332 138 468 0.414 0.29
Page
8/10/2019 MEZZANINE FLOOR LTG. CALCULATION.pdf
http://slidepdf.com/reader/full/mezzanine-floor-ltg-calculationpdf 14/17
Project 1
10.01.20
Operator Telephone
Faxe-Mail
Male Prayer RM MF021 / Summar
120
120
120
120
180
180
180
240
240240 240
240
240
240
240240
240240
300
11.49 m0.00
4.28 m
0.00
Height of Room: 3.200 m, Mounting Height: 3.345 m, Maintenance factor:0.80
Values in Lux, Scale 1:8
Surface [%] Eav [lx] Emin [lx] Emax [lx]
Workplane / 210 48 304 0.22
Floor 20 186 66 274 0.35
Ceiling 70 32 21 42 0.65
Walls (4) 50 61 21 150
Workplane:Height: 0.750 mGrid: 128 x 64 PointsBoundary Zone: 0.100 m
UGR Lengthways- Across to luminaire axisLeft Wall 11 <10Lower Wall 11 <10(CIE, SHR = 1.00.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.271, Ceiling / Working Plane: 0.154.
Luminaire Parts List
Specific connected load: 8.30 W/m² = 3.95 W/m²/100 lx (Ground area: 49.16 m²)
No. Pieces Designation (Correction Factor) [lm] P [W
1 8 Zumtobel 60 810 251 PANOS HF 2/26W TC-DEL EVG 200 WH [STD] (1.000) 3600 51
Total: 28800 408
Page
8/10/2019 MEZZANINE FLOOR LTG. CALCULATION.pdf
http://slidepdf.com/reader/full/mezzanine-floor-ltg-calculationpdf 15/17
8/10/2019 MEZZANINE FLOOR LTG. CALCULATION.pdf
http://slidepdf.com/reader/full/mezzanine-floor-ltg-calculationpdf 16/17
Project 1
10.01.20
Operator Telephone
Faxe-Mail
Corridor / Summar
93.65 m0.00 54.50
10.90 m
0.00
Height of Room: 3.200 m, Mounting Height: 3.345 m, Maintenance factor:0.80
Values in Lux, Scale 1:67
Surface [%] Eav [lx] Emin [lx] Emax [lx]
Workplane / 325 132 692 0.40Floor 20 269 121 510 0.45
Ceiling 70 83 48 152 0.58
Walls (8) 50 180 56 1075
Workplane:Height: 0.750 mGrid: 128 x 64 PointsBoundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.572, Ceiling / Working Plane: 0.253.
Luminaire Parts List
Specific connected load: 14.51 W/m² = 4.46 W/m²/100 lx (Ground area: 204.53 m²)
No. Pieces Designation (Correction Factor) [lm] P [W
1 18 Zumtobel 40 317 722 REP 2/36W T26 EVG M600 [STD] (1.000) 6700 70
2 15 Zumtobel 40 317 791 REP 4/18W T26 EVG M600 [STD] (1.000) 5400 73
3 12 Zumtobel 60 810 251 PANOS HF 2/26W TC-DEL EVG 200 WH [STD] (1.000) 3600 51
Total: 244800 2967
Page
8/10/2019 MEZZANINE FLOOR LTG. CALCULATION.pdf
http://slidepdf.com/reader/full/mezzanine-floor-ltg-calculationpdf 17/17
Project 1
10.01.20
Operator Telephone
Faxe-Mail
Corridor / Workplane / Value Chart (E
93.65 m0.00 54.50
10.90 m
0.00
Values in Lux, Scale 1 : 67Not all calculated values could be displayed.
Position of surface in room:Working plane with 0.100 m Boundary
ZoneMarked point:(31.439 m, 37.670 m, 0.750 m)
Grid: 128 x 64 Points
Eav [lx] Emin [lx] Emax [lx] u0 Emin / Em
325 132 692 0.406 0.19
top related