siemens s4 switchboard
Post on 14-Apr-2017
230 Views
Preview:
TRANSCRIPT
Related catalogues Contents
Low-Voltage Controls and Distribution
SIRIUS
·
SENTRON
·
SIVACON
Order No.:CatalogE86060-K1002-A101-A7-7600Technical Information incl.
LV 1
LV 1 T
Systems
•
Controlgear: Contactors and contactor assemblies, solid-state switching devices
•
Protection equipment
•
Load feeders, motor starters and soft starters
•
Monitoring and control devices
•
Detecting devices
•
Commanding and signaling devices
•
Transformers
•
Power supplies
•
Planning and configuration with SIRIUS
•
Power Management System
•
SIVACON Power, distribution boards, busway and cubicle systems
•
SENTRON switching and protection devices for power distribution
•
Air circuit breakers, molded case circuit breakers, switch disconnectors
•
Software for power distribution
•
BETA low-voltage circuit protection
Low-Voltage
Controls and Components for Applications according to ULOrder no.:E86060-K1816-A101-A1-7600
LV 16 SIRIUS 3RV17 and 3RV18 circuit breakers according to UL 489
•
SIVACON Components for 8US Distribution Systems according to UL 508A
•
SENTRON 3WL5 air circuit breakers/non-automatic air circuit breakers according to UL 489/IEC
•
SENTRON 3VL Molded Case Circuit Breakers according to UL 489/IEC
•
ALPHA Devices according to UL Standard
•
BETA Devices according to UL standard
Industrial Communication
Industrial Communicationfor Automation and DrivesOrder No.:E86060-K6710-A101-B6-7600E86060-K6710-A121-A2-7600
IK PIIK PI N
PROFINET/Industrial Ethernet
•
Industrial Mobile Communicaton
•
PROFIBUS to IEC 61158/EN 50170
•
SIMATIC ET 200 distributed I/Os
•
AS-Interface to EN 50295/IEC 61158
•
Remote operation with SINAUT Telecontrol
•
Routers
•
ECOFAST system
SICUBE
System Cubicles and Cubicle Air-Conditioning
Order No.:
E86060-K1920-A101-A3-7600
LV 50 System cubicles
•
Cubicle modifications
•
Cubicle expansion components
•
Accessories
•
Special cubicles Cubicle solutions in applications
•
Cubicle air-conditioning
•
Special colors
SIDAC
Reactors and FiltersOrder No.:E86060-K2803-A101-A4-7600
LV 60 Commutating reactors for converters
•
Mains reactors for frequency converters
•
Iron-core output reactors
•
Ferrite output reactors
•
Iron-core smoothing reactors
•
Smoothing air-core reactors
•
Filter reactors
•
Application-specific reactors
•
Radio interference suppression filters
•
dv/dt filters
•
Sinewave filters
SIVACON 8PS
CD-K, BD01, BD2 Busbar Trunking Systemsup to 1250 AOrder No.:E86060-K1870-A101-A3-7600
LV 70 Busbar trunking systems, overview
•
CD-K system (25 A to 40 A)
•
BD01 system (40 A to 160 A)
•
BD2 system (160 A to 1250 A)
Automation & Drives
The A&D Offline MallCD-ROM:E86060-D4001-A110-C6-7600DVD:E86060-D4001-A510-C6-7600
CA 01 All Automation and Drives products,including those in the catalogs listed above.
A&D Mall
Internet:http://www.siemens.com/automation/mall
All Automation and Drives products, including those in the catalogs listed above.
Catalog-PDF
Internet:http://www.automation.siemens.com/cd
All catalogs for low-voltage controls and distribution can be downloaded as PDF files.
Registered trademarks Technical Assistance
All product designations may be registered trademarks or product names of Siemens AG or other supplying companies. Third parties using these trademarks or product names for their own purposes may infringe upon the rights of the trademark owners.Further information about low-voltage controls is available on the Internet at:http://www.siemens.com/lowvoltage
Expert technical assistance for Low-voltage controls and electrical installation.
Tel.: +49 (9 11) 8 95-59 00Fax: +49 (9 11) 8 95-59 07
E-Mail: technical-assistance@siemens.com
sivacon S4
Power Distribution Boards
Catalogue LV 56 · 2008
Introduction
1
Power Distribution Boards
2
Standard Configurations
3
Cubicles, Supporting Structure and Enclosures
4
Busbar System
5
Assembly Kits for Switching Devices
6
Covers, Modular Doors, Mounting Plates, 19” Rack
7
Internal Separation
8
Air-conditioning Products
9
Accessories
10
Mechanical Dimensions
11
Planning and Configuration
12
Appendix
13
Not valid:Catalogue LV 56 · 2006
Contact your local Siemensrepresentative for further information
© Siemens AG 2008
The products listed in this catalogue are ma-nufactured at produc-tion units working accor-ding to a quality system certified for conformity to EN 29001 (ISO 9001)
2
Siemens LV 56 · 2008
Information on catalogue LV 56 · 2008 and Manual SIVACON S4 · 2008
Catalogue LV 56 · 2008 contains the data relevant to selection and ordering.
Additional information is given in SIVACON S4 Manual.
Delivery class (DC)
1)
The delivery class indicates a product’s delivery time in working days from order receipt to product ready for dispatching from the warehouse.
Total deliver time is given by the sum of order processing time in the country of origin, predetermined delivery time and transport time.
Price
1)
The stated price is in
€
and refers to the price per unit (PU).
Price unit (PU)
The price unit specifies to how many items (IT), sets (ST) or metres (M) the stated price and weight applies.
Price group (PG)
1)
Each product is assigned to a price group.
Dimensions
All dimensions are expressed in mm.
1)
Information is provided on a separate price list.
Explanations
Siemens LV 56 · 2008
1
Introduction
1/2
Siemens Automation and DrivesWelcome
1/4 Sharpen your competitive edge
Totally Integrated Automation
1/6 Low-Voltage Power Distribution
with SIVACON, SENTRON and SIMARIS
1/2
Siemens LV 56 · 2008
Siemens Automation and Drives.Welcome
More than 60,000 people aiming for the same goal: in-
creasing your competitiveness. That's Siemens Automa-
tion and Drives.
We offer you a comprehensive portfolio for sustained
success in your sector, whether you’re talking automa-
tion engineering, drives or electrical installation sys-
tems. Totally Integrated Automation (TIA) and Totally In-
tegrated Power (TIP) form the core of our offering. TIA
and TIP are the basis of our integrated range of products
and systems for the manufacturing and process indus-
tries as well as building automation. This portfolio is
rounded off by innovative services over the entire life cy-
cle of your plants.
Learn for yourself the potential our products and sys-
tems offer. And discover how you can permanently in-
crease your productivity with us.
Your regional Siemens contact can provide more infor-
mation. He or she will be glad to help.
1/3
Siemens LV 56 · 2008
Siemens IK PI · 2000
1/4
1/4
Siemens LV 56 · 2008
Integrated energy distribution from a single source.Totally Integrated Power
Totally Integrated Power (TIP) brings together all the components of electrical energy distribution into an integrated whole. Thus TIP provides the answer to growing market demands in the planning, construction and use of utility buildings and industrial buildings.
On the basis of TIP, we offer integrated solutions for energy distri-bution, from medium voltage to the power outlet. Totally Integra-ted Power is based here on integration in planning and configu-ring as well as on perfectly matched products and systems.
1/5
Siemens LV 56 · 2008
Totally Integrated Power offers communication and software modules for connecting the energy distribution systems to industrial automation and building automation. This enables the implemen-tation of significant savings potential.
1/6
Siemens LV 56 · 2008
SIVACON power distribution boards
SENTRON switching devices
SIMARIS software for power distribution
Low-voltage power distribution with
SIVACON, SENTRON and SIMARIS
Non-residental buildings and industrial plants have one thing in
common: without electricity, everything comes to a halt. The avai-
lability, safety and cost effectiveness of the power distribution sys-
tem is of utmost importance – from the medium voltage supply
point through to the socket outlet. And only integrated solutions
can ensure maximum efficiency for planning, configuration and
operation.
The concept is called Totally Integrated Power from Siemens.
Total integration in planning and configuration creates synergies
and saves costs. Perfectly matched products and systems pro-
vide efficient engineering and reliable operation. In the field of
low-voltage power distribution, the following product ranges are
available:
SIVACON:
From flexible busbar trunking systems through to safe
power distribution boards and motor control centers.
SENTRON:
From well-proven switch disconnectors through to in-
telligent circuit breakers.
Software for power distribution:
Everything for dimensioning,
configuring, visualizing and controlling your power distribution.
Siemens LV 56 · 2008
2
SIVACON S4Power Distribution Boards
2/2 Introduction
2/3 General Data
2/6 Technical Data
2/7 Declaration of conformity
SIVACON S4 Power Distribution Boards
2
Introduction
■ Front view
SIVACON S4 is an AS (TTA-TSK) switchgear and controlgear system, type tested according to IEC 60439-1, CEI EN 60439-1, for installation as primary or secondary boards in industrial and service sector facilities, including hospitals, shopping centres, banks, schools. etc. The SIVACON S4 energy distribution concept consists of a full line-up of boards in galvanised
chromed sheet steel, of sturdy design, suitable for any installation modality: self-standing, flush or wall-mounted. SIVACON S4 low-voltage power distribution boards are constructed according to a modular design system and, by means of ad hoc assembly kits, can be combined to meet all power distribution needs.
2/2 Siemens LV 56 · 2008
2/3
Siemens LV 56 · 2008
SIVACON S4 Power Distribution Boards
2
■
Description
System
SIVACON S4 is a system of low-voltage power distribution boards, for indoor use, panelled on four sides, suitable for self-standing or wall-mounted installation.
The cubicle
The constituent elements of the cubicle framework, having a 2.5mm thick profile, are inserted into one another to form a parallelepiped shaped column. This provides the bearing structure supporting all add-on interior switchgear components, i.e., assembly kits, busbar systems, mounting plates, etc. Stable and rugged construction is ensured through the use of Torx self-tapping screws. Equipotential and safe grounding of all parts are also achieved.
The enclosure
Enclosure parts made of galvanised sheet steel are dimensioned as a function of the cubicle they are fitted to. Different versions make it possible to achieve various degrees of protection: IP 30/31, IP 40/41 or IP 55. Walls and doors are coated with slightly embossed RAL 7035 powder-paint. In addition to the standard two-way interlocking system, the doors can be equipped with numerous types of operating mechanism including rotary handles, with or without locks, to meet any need. Assembly kit covers are secure by means of captive quick-release screws. Opening and closing is by rotating the handle by
1
/
4
turn. Using the hinge option, the covers may open to the right or to the left.
Busbar system
The main busbar system of SIVACON S4 offers an appropriate scaling of rated currents, matched to a rated current of up to 4000 A and short-circuit currents of standard transformers.It is possible to set up systems with network configurations such as TN-C, TN-S, IT and TT. Vertical distribution busbar systems are available as cascaded versions up to 1600 A or non-cascaded versions up to 2700 A.
Internal separation
Depending on individual requirements, internal partitions are available from form 1 to form 4.
Assemly kits
For open and enclosed automatic breakers, disconnectors, SENTRON circuit breakers, modular units as well as contactors, a wide range of dedicated kits are available. Modular adjustable mounting plates or plates for electrotechnical use, as well as dedicated ventilation and air-conditioning components complete the line-up of parts for the construction of boards as typically used at industrial facilities or for automation purposes. The items available include a range of assembly kits for Siemens Sentron WL and VL circuit breakers, in fixed, plug-in and drawout versions, as well as kits with DIN rails, according to DIN 43656, for the wide range of the Beta Series modular devices.• The components of the cubicle and the assembly kits are
made of galvanised chromed sheet. • The components of the enclosure, such as panels and doors
are coated with slightly embossed RAL 7035 powder-paint. • Air-conditioning components complete the line-up of
SIVACON S4 system components.
General data
2/4
Siemens LV 56 · 2008
SIVACON S4 Power Distribution Boards
2
General Data
■
Applications
Main features
• Type AS (TTA-TSK) power distribution boards according to CEI EN 60439-1.
• Modular systems supplied loose (supplied as assembly kits with individually packaged components, including fasteners; assembly instructions for do-it-yourself installation).
• New design, ventilation and closing system.• Slightly embossed RAL 7035 powder coating.• Doors with universal stop.• Degree of protection IP30, IP31, IP40, IP41, IP55• Busbar system rated current up to 4000 A• Busbar system short-circuit current Icw up to 100 kA (1s).• Busbar system peak current Ipk up to 220 kA.• Height 2000 mm• Width 400, 600, 800, 1000, 1200 mm.• Depth 400, 600, 800 mm.• Kits for Sentron 3WL, 3VL, 3KA, 3KL circuit breakers, Beta
modular devices on DIN rails.• Kits of prefabricated bars for Sentron 3WL, 3VL circuit
breakers.• Internal separation form 1, 2, 3, 4.• Easy design and configuration with the SCFB software tool.
Construction and testing modalities
All installation and wiring operations must be performed in keeping with the information and data given in the catalogues and the assembly manuals.The installation and individual testing of the low-voltage boards must be performed according to standards IEC 60439-1 and CEI EN 60439-1.
Protection of the environment
To the best of our knowledge, our materials do not contain materials in concentrations or applications prohibited by directive 2002/95/EC (RoHs).All the materials used are recyclable.
2/5
Siemens LV 56 · 2008
SIVACON S4 Power Distribution Boards
2
■
Exploded view
Quick and easy assembly
1
5
13
11
8
9
156
7
10
14
4
12
17
18
6
1 Cubicle
2 Base with front covers
3 Base side covers
4 Supporting Structure
5 Blind top plate
6 Side panel with design
7 Giugiaro Design glazed wall
8 Front frame
9 Cable compartment cover
10 Covers for equipment kits
11 Segregation for horizontal busbars
12 Segregation for verticaldistribution busbars
13 Horizontal busbars
14 Vertical distribution busbars,non-cascaded
15 Real panel
16 Mounting plate forSentron VL circuit breaker
17 Blind bottom plate
18 Main grounding bar PE
2
3
16
16
0172
4
2/6
Siemens LV 56 · 2008
SIVACON S4 Power Distribution Boards
2
Technical Data
■
Overview
Standards and regulations
Type AS (TTA-TSK) assembled protection and circuit breakers for low-voltage (L.V. boards)
IEC 60439-1, EN 60439-1
Air clearances and creepage distances
Rated impulse withstand voltage (
U
imp
) 12 kVOvervoltage category IVPollution degree 3
Internal separation forms
1, 2b, 3b,4a, 4b
Rated insulation voltage (
U
i
)
1000 V
Rated operational voltage (
U
e
)
Up to 690 V
Rated frequency
50/60 Hz
Rated current (In) of(3-pole and 4-pole) busbar system
Main horizontal bars Rated currentRated peak current of busbar system (
I
pk
)Rated short-time current of busbar system (
I
cw
)
Up toUp to
Up to
4000 A220 kA
100 kA, 1s
Protection of people in the event of internal arcs
Type tested according to IEC 61641Degree of protection
≤
IP40, without glazed doorRated utilisation voltageRated short-time current without extra kit Length of internal arc without extra kitLength of internal arc with extra kit
400 V50 kA
100 ms300 ms
Surface treatment
Cubicle, interior components, enclosure Coated with RAL 7035 powder
GalvanisedEpoxy resinCold phosphatised Thickness of coating
min.
min.
20 µmRAL 7035
70 µm
Insulation class
According to IEC 61140, EN 61140 SK1
Degree of protection
According to IEC 60529, EN 60529 IP 30, IP 31, IP 40, IP 41, IP 55
Resistance to mechanical impacts
According to IEC 62262, paragraph 9.6 IP 3X
≥
IP 4XIK08IK10
Additional static loads on frame components
Front frame
Covers
Internal inner doorInternal door / double door
Door module
Exterior covers
revolvingfixedwith quick closing screws, H 50-300mmwith quick closing screws, H 350-550mmwith quick closing screws, H 600-800mmwith hinges
W 400, 600mmW 800mmW 1000, 1200mmH 150-200mmH 250-350mmH 400-800mm
1,0 kg5,0 kg0,5 kg1,0 kg2,0 kg0,0 kg2,5 kg
10,0 kg5,0 kg2,5 kg0,5 kg1,5 kg3,0 kg
10,0 kg
Max construction weight
According to IEC 62208, paragraph 9.3, 9.4,Type tested with static load by lifting a cubicle
1200 kg
Operating conditions
Ambient temperature
1)
Installation altitude
�
35 °C
�
2000 m
Frame parts:
2.5 mm – Galvanised chromed sheet steel, with 25mm hole pattern according to DIN 43 660
Dimensions
Exterior dimensions
Base
Height: 2000 mmWidth: 400, 600, 800, 1000, 1200 mmDepth: 400, 600, 800 mm
Height: 100, 200 mm
1)
For different ambient temperatures and installation altitudes, take into account the appropriate correction factors (see chapter on Planning and Configuration)
2/7
Siemens LV 56 · 2008
SIVACON S4 Power Distribution Boards
2
■
Overview
Declaration of conformity
2/8
Siemens LV 56 · 2008
SIVACON S4 Power Distribution Boards
2
■
Overview
Declaration of conformity
Siemens LV 56 · 2008
3
Standard Configurations
3/2 SIVACON S4 with Sentron 3VL circuit breakers and modular devices
3/3 SIVACON S4 with Sentron 3WL circuit breakers
3/4 SIVACON S4 with Sentron 3VL circuit breakers
3/5 SIVACON S4 with Sentron 3WL, 3VL circuit breakers and modular devices
3/2
Siemens LV 56 · 2006
Standard Configurations
3
SIVACON S4 with Sentron 3VLcircuit breakers and modular devices
■
Power distribution board data
Height x Width x Depth 2000mm x 1200mm x 400mmHeight of base, 100mmDegree of protection IP55 Main busbar system withoutVertical busbar system cascaded 1250 A, 50kAFront covers, full height doorInternal separation 2b
■
Assembly kit
Infeed Sentron 3VL1250, cable entry fromtop, terminals for cables,extended terminal covers
Starters Sentron 3VL, extended terminal covers, modulardevices
Cubicle, base, Supporting Structure, enclosures
8PQ1202-4BA02
1 Cubicle H2000/B1200/T400
8PQ3000-1BA38
2 Bottom plate partition crossbar
8PQ3000-1BA43
2 Exterior intermediate supporting structure
8PQ1012-0BA01
1 Base H100/B1200
8PQ1010-4BA01
1 Base side covers H100/P400
8PQ2000-6BA04
1 Fixed front frame H1800/B600
8PQ2197-2BA14
1 Cable compartment cover B200
8PQ2197-6BA14
1 IP55 glazed door, right/2-way interlock./H1975/B600
8PQ2197-4BA05
1 IP55 door, left/2-way interlock./H1975/B400
8PQ2302-4BA04
1 Bottom plate IP55/B200/P400
8PQ2306-4BA05
1 Bottom plate IP55/B600/P400
8PQ2304-4BA05
1 Bottom plate IP55/B400/P400
8PQ2302-4BA01
1 Top plate IP55/B1200/P400
8PQ2420-2BA01
1 Rear panel IP55/H2000/B1200
8PQ2520-4BA01
1 Side panel with design/H2000/P400
Busbar system
8PQ4000-0BA32
1 Support for vertical busbars, cascaded, 30x30
8PQ4000-0BA86
8 Copper busbar 30x10/L2000
8PQ4000-0BA85
1 Copper busbar 30x5 /L2000
Kits for switchgear, covers, mounting plates
8PQ2020-6BA02
1 Instrum. cover 4X72x72 + 1 sw./H200/B600
8PQ6000-3BA11
1 Kit for 3VL 7, 3/4 poles, vertical/H600/P600
8PQ2060-6BA03
1 Cover 3VL 7 3/4 poles, vertical/H600 B600
8PQ2020-6BA01
1 Cover H200/B600
8PQ6000-3BA36
1 DIN 24UM/B600 rail assembly kit
8PQ2015-6BA07
1 Cover for modular elements 24UM/H150/B600
8PQ6000-3BA18
2 Assembly kit for 3VL 2, 3, 4 poles, horiz./H200/B600
8PQ2020-6BA04
2 Cover for 3VL 1 3,3, 4 poles, horiz./H200/B600
8PQ6000-2BA87
1 Assembly kit 3VL 4, 4 poles, horiz./H250/B600
8PQ2025-6BA02
1 Cover for 3VL4, horiz. fixed, remov./H250/B600
Kits for switchgear, busbar connection
8PQ6000-1BA64
2 Vertical busbar connection kit for 3VL 3./4p/horiz./fixed
8PQ6000-1BA66
1 Vertical busbar connection kit for 3VL 4 /4p/horiz./fixed
Internal separation
8PQ4000-0BA06
1 Vertical partition for distribution busbars, form 2b H1900/P400
Accessories
8PQ9400-0BA06
1 SIVACON – SIEMENS cubicle ID plate
8PQ3000-0BA38
1 Cable anchoring brackets C30/P400 (600, 800)
8PQ9500-1BA36
1 Flat head square screws DIN 603 M10X55
8PQ9500-0BA05
1 Nuts M10 ISO 4032/M10
8PQ9500-0BA60
1 Clamping washer DIN 6796/10
8PQ9400-0BA02
1 Busbar connect. kitcable, conductors, small parts, screws, nuts, washers with locking edges for cable connection
02
00
10
20
02
02
00
3
3/3
Siemens LV 56 · 2008
Standard Configurations
3
SIVACON S4 with Sentron 3WL circuit breakers
■
Power distribution board data
Height x Width x Depth 2000mm x 2000mm x 600mmHeight of base 100mmDegree of protection IP30 Main busbar system Standard at top, 3200A, 65kADistribution busbar system, vertical cascaded, 2 x 1600AFront panels, coverInternal segregation 4b
■
Assembly kit
Infeed / starters Sentron 3WL Gr. II, fixed, connectionto distribution busbars.Cables from top/bottomMax 12 cables per phase per M12cable terminal
Cubicle, base, Supporting structure, enclosure
8PQ1208-6BA01
2 Cubicle H2000/ B800/P600
8PQ1204-6BA01
1 Cubicle H2000/B400/P600
8PQ3000-0BA01
2 Interior side upright H1600/P600
8PQ3000-0BA03
1 Interior side upright H1800/P600, 800
8PQ1204-4BA05
2 Board coupling kit
8PQ1018-0BA01
2 Base with front covers H100/B800
8PQ1014-0BA01
1 Base with front covers H100/B400
8PQ1010-6BA01
1 Base side covers H100/P600
8PQ2000-8BA03
2 Fixed front frame H1600/B800
8PQ2000-8BA03
1 Exterior cover IP4X/H1975/B400
8PQ2197-8BA11
2 Finishing frame IP3X/H1975/B800
8PQ2197-8BA11
1 Bottom plate IP55/B800/P600
8PQ2308-6BA06
1 Bottom plate IP4X/cables/B800/P600
8PQ2304-6BA05
1 Bottom plate IP55/B400/P600
8PQ2308-6BA03
1 Top plate IP4X/cables/B800/P600
8PQ2308-6BA02
1 Top plate IP4X//B800/P600
8PQ2304-6BA02
1 Top plate IP4X/B400/P600
8PQ2420-8BA02
2 Rear panel IP4X/H2000/B800
8PQ2420-4BA02
1 Rear panel IP4X/H2000/B400
8PQ2520-6BA01
1 Side panel with design H2000/P600
Busbar system
8PQ4000-0BA04
2 Main busbars holder 3200 A
8PQ4000-0BA37
1 Flying support (reinforcement)
8PQ4000-0BA82
1 Support for grounding bar PE
8PQ4000-0BA63
2 Support for vertical cascaded busbar /30x40
8PQ4000-0BA74
2 Kit for vertic./horiz. busbars 30x40/P600, 800
8PQ4000-0BA18
16 Copper busbar 50x10/L2000
8PQ4000-0BA17
16 Copper busbar 40x10/L2000
8PQ4000-0BA80
2 Copper busbar 40x5 / L2000
Kits for switchgear, covers, mounting plates
8PQ6000-3BA32
2 Kit for 3WL11 12,3/4 poles/fixed H550/B800
8PQ2055-8BA05
2 Cover for 3WL12/4P/H550/B800
8PQ2055-8BA01
2 Cover H550/B800
8PQ2050-8BA01
2 Cover H500/B800
Kits for switchgear, busbar connection
8PQ6000-0BA47
2 prefabricated distribution bars for 3WL1232/fixed/B800
8PQ6000-0BA65
2 prefabricated bars to cables for 3WL 1232/fixed/B800
Internal separation
8PQ3000-0BA54
1 Separation form 2b, main busbars B800/P600
8PQ4000-0BA03
1 Separation form 2b, distribution bars H1900/P600
8PQ4000-0BA07
1 Separation form 2b, distribution bars H1600/P600
8PQ3000-0BA82
2 Partition supporting rail H1600
8PQ5000-0BA10
2 Separation form 3 3WL12/3-4 poles/pull-out/H550/B800
8PQ5000-0BA21
2 Separation form 4 3WL12/3-4 poles/vert. bars/B800
8PQ5000-0BA38
2 Separation form 4 3WL12/3-4 poles/cables/B800
Accessories
8PQ9400-0BA06
1 SIEMENS SIVACON column ID plate
8PQ9400-0BA02
3 Busbar connection kit
8PQ9500-0BA16
1 Flat head screw DIN 603/M10x45
8PQ9500-1BA25
2 Flat head screw DIN 603/M10x65
8PQ9500-0BA60
3 Clamping washer DIN 6796/10
8PQ9500-0BA05
3 Hexagonal nut ISO4032/M10
8PQ3000-0BA73
2 Cable anchoring bracket
8PQ3000-0BA43
2 Cable anchoring bracket C30/B800cable, conductors, small parts, screws, nuts, washers with locking edges for cable connection
02
00
40
20
05
02
00
6
3/4
Siemens LV 56 · 2006
Standard Configurations
3
SIVACON S4 with Sentron 3VLand modular devices
■
Power distribution board data
Height x Width x Depth 2000mm x 1400mm x 400mmHeight of base 100mmDegree of protection IP55 Main busbar system withoutDistribution busbar system, vertical non-cascaded 630 A, 15kAFront covers, full height doorInternal separation 1
■
Assembly kit
Infeed Sentron 3VL 630, cable entry fromtop, terminals for several wires, extended terminal covers
Starters Sentron 3VLextended terminal covers, modulardevices
Cubicle, base, Supporting structure, enclosure
8PQ1206-4BA01
1 Cubicle H2000/ B600/P400
8PQ1208-4BA01
1 Cubicle H2000/B800/P400
8PQ3000-1BA38
1 Bottom plate partition crossbar P400
8PQ3000-1BA42
1 Exterior intermediate upright for covers
8PQ1204-4BA05
1 Board coupling kit
8PQ1204-4BA04
1 Switchboard coupling gasket IP55
8PQ1016-0BA01
1 Base with front covers H100/B600
8PQ1018-0BA01
1 Base with front covers H100/B800
8PQ1010-4BA01
1 Base side covers H100/P400
8PQ2000-6BA04
2 Fixed front frame H1800/B600
8PQ2000-2BA01
1 Covers for cable compartment IP3X/H2000/B200
8PQ2197-8BA14
1 IP55 glazed door/right/2-way interlock./H1975/B800
8PQ2197-6BA10
1 IP55 glazed door/left/2-way interlock./H1975/B600
8PQ2302-4BA04
1 Bottom plate IP55/B200/P400
8PQ2306-4BA05
2 Bottom plate IP55/B600/P400
8PQ2308-4BA01
1 Top plate IP55/B800/P400
8PQ2306-4BA01
1 Top plate IP4X/B600/P400
8PQ2420-8BA01
1 Rear panel IP55/H2000/B800
8PQ2420-6BA01
1 Rear panel IP55/H2000/B600
8PQ2520-4BA01
1 Side panel with design H2000/P400
Busbar system
8GF5763
10 Main busbar holder 30x10.50mm
8PQ3000-1BA42
2 Exterior intermediate upright for covers
8PQ4000-0BA86
8 Copper busbars 30x10/L2000
8PQ4000-0BA83
1 Copper busbars 20x5 / L2000
Kits for switchgear, covers, mounting plates
8PQ2020-6BA02
1 Cover for 4 instruments 1 sw. 72x72 H200/B600
8PQ3000-1BA56
1 Blind mounting plate kit H200/B600
8PQ6000-3BA05
1 Assembly kit for 3VL5 3, 4 poles/vertic. H400/B600
8PQ2040-6BA08
1 Cover for 3VL5 3, 4 poles/vertic./fixed, rim H400/B600
8PQ6000-3BA18
1 Assembly kit for 3VL2 3, 4 poles/horiz./fixed/H200/B600
8PQ2020-6BA04
1 Cover for 3VL1 3, 4 poles/horiz./fixed H200 B600
8PQ2020-6BA12
8 Cover for modular devices, 1 row, 24 UM/H200/B600
8PQ6000-3BA36
8 Modular DIN rails kit. 1 row, 24 UM/B600
8PQ3000-1BA61
1 Modular mounting plate H400/B600
8PQ2040-6BA01
1 Cover H400/B600
8PQ6000-3BA22
2 Assembly kit for 3VL2 3, 4 poles/vertic./fixed/H350/B600
8PQ2035-6BA03
2 Cover for 3VL1 3,4 poles/vertic./fixed, remov. H350/B600
8PQ2005-6BA01
2 Cover H50/B600
Accessories
8PQ9400-0BA06
1 SIEMENS SIVACON column ID plate
8PQ3000-0BA73
1 Cable anchoring brackets
8PQ3000-0BA42
1 Cable anchoring brackets C30/B600
8PQ6000-0BA16
1 Horizontal raceway fastening bracket
8PQ9600-0BA01
1 35mm DIN rail for terminal board L1600cable, conductors, small parts, screws, nuts, washers with locking edges for cable connection
02
00
70
20
08
02
00
9
3/5
Siemens LV 56 · 2008
Standard Configurations
3
SIVACON S4 with Sentron 3WL,Sentron 3VL and modular devices
■
Power distribution board data
Height x Width x Depth 2000mm x 2200mm x 600mmHeight of base 100mmDegree of protection IP30 Main busbar system withoutDistribution busbar system, vertical cascaded, 1600A, 50 kA 50mm
SystemFront covers, glazed doorInternal separation 4b
■
Assembly kit
Infeed Sentron 3WL Gr. I, fixed, centralconnection to main busbars, cableentry from top/bottom
Connector Sentron 3WL, Gr. I, fixedStarters Sentron 3VL with rear attachments
for cable connection at rearModular devices
Cubicle, base, Supporting structure, enclosure
8PQ1206-6BA01
1 Cubicle H2000/ B600/P600
8PQ1208-6BA01
2 Cubicle H2000/B800/P600
8PQ3000-1BA40
2 Bottom plate partition crossbar P600
8PQ3000-0BA03
3 Interior side upright H1800/P600, 800
8PQ3000-1BA36
2 Interior side upright H1800/P600
8PQ3000-1BA42
2 Exterior intermediate upright
8PQ1204-4BA05
2 Board coupling kit
8PQ1016-0BA01
1 Base with front covers H100/B600
8PQ1018-0BA01
2 Base with front covers H100/B800
8PQ1010-6BA01
1 Base side covers H100/P600
8PQ2000-6BA04
3 Fixed front frame H1800/B600
8PQ2000-2BA01
2 Covers for cable compartment IP3X/H2000/B200
8PQ2197-6BA10
1 IP55 glazed door/left/2-way interlock./H1975/B600
8PQ2197-8BA10
2 IP55 glazed door/left/2-way interlock./H1975/B800
8PQ2302-6BA04
2 Bottom plate IP55/B200/P600
8PQ2306-6BA05
3 Bottom plate IP55/B600/P600
8PQ2306-6BA02
1 Top plate IP4X/B600/P600
8PQ2308-6BA02
2 Top plate IP4X/B800/P600
8PQ2420-6BA02
1 Rear panel IP4X/H2000/B600
8PQ2420-8BA02
2 Rear panel IP4X/H2000/B800
8PQ2520-6BA01
1 Side panel with design H2000/P600
Busbar system
8PQ4000-0BA63
2 Support for distribution busbars, cascaded 30x40
8PQ4000-0BA82
1 Support for busbar PE
8GF5762
4 Support for busbars 20x5.50mm
8PQ4000-0BA17
16 Copper busbars 40x10/L2000
8PQ4000-0BA83
9 Copper busbars 20x5/L2000
Kits for switchgear, covers, mounting plates
8PQ6000-3BA31
2 Kit for 3WL11 3, 4 poles/3WL12/3p/H550/B600
8PQ2055-6BA07
2 Cover for 3WL11/4p/H550/B600
8PQ6000-2BA87
2 Kit for 3VL4/4p/horiz./H250/B600
8PQ2025-6BA02
2 Cover for 3VL4/4p/horiz./fixed, remov./H250/B600
8PQ6000-3BA18
2 Kit for 3VL2-3, 4 poles/horiz./fixed/H200/B600
8PQ2020-6BA04
2 Cover for 3VL1 3, 4 poles/horiz./fixed, remov./H200/B600
8PQ6000-3BA10
1 Kit for 3VL5 4 poles/horiz./H350/B600
8PQ2035-6BA04
1 Cover for 3VL 5/4poles/horiz./fixed, remov./H350/B600
8PQ6000-3BA36
6 Modular DIN rails kit, 1 row, 24 UM/B600
8PQ2020-6BA12
6 Modular cover, 1 row, 24 UM/B600
8PQ3000-1BA65
1 Modular mounting plate H600/B600
8PQ2040-6BA01
1 Cover H400/B600
8PQ2060-6BA01
1 Cover H600/B600
8PQ2030-6BA01
2 Cover H300/B600
8PQ2025-6BA01
1 Cover H250/B600
02
01
90
20
20
3/6 Siemens LV 56 · 2006
Standard Configurations
3
SIVACON S4 with Sentron 3WL,Sentron 3VL circuit breakers and modular device
Kits for switchgear, busbar connection8PQ6000-0BA34 3 Distribution busbar connection kit for 3WL11 16/fixed/B600
8PQ6000-0BA52 1 Cable connection kit for 3WL11 16/fixed/B600
8PQ6000-1BA64 2 Distribution busbar connection kit for 3VL3/4p/horiz./fixed
8PQ6000-1BA66 2 Distribution busbar connection kit for 3VL4/4p/horiz./fixed
8PQ6000-1BA68 1 Distribution busbar connection kit for 3VL5/horiz./fixedInternal separation8PQ4000-0BA03 2 Separ. form 2b for vertical bars H1900/P600
8PQ3000-0BA83 3 Supporting rail for crossbars and partitions H1800
8PQ5000-2BA61 7 Separ. form 3, horizontal/B600
8PQ5000-2BA57 1 Separ. form 3, vertic./rear/H350/B600
8PQ5000-2BA36 1 Separ. form 3, vertic./later./H350
8PQ5000-2BA54 2 Separ. form 3, vertic./rear/H200/B600
8PQ5000-2BA30 2 Separ. form 3, vertic./later./..250A/H200
8PQ5000-0BA07 2 Separ. form 3, 3WL11/3, 4 poles/estraib./H550/B600
8PQ5000-0BA30 3 Separ. form 4, 3WL11/3, 4 poles/cables/B600
8PQ5000-0BA14 1 Separ. form 4, 3WL11/3, 4 poles/distribuz./B600
8PQ5000-2BA55 2 Separ. form 3, vertic./rear/H250/B600
8PQ5000-2BA33 2 Separ. form 3, vertic./later./..400..630A/H250
8PQ9400-0BA03 5 Protective bellowsAccessories8PQ9400-0BA06 2 SIEMENS SIVACON column ID plate
8PQ9400-0BA02 2 Busbar connection kit
8PQ9500-1BA25 2 Flat head screw DIN 603/M10x65
8PQ9500-0BA60 2 Clamping washer DIN 6796/10
8PQ9500-0BA05 2 Hexagonal nut ISO4032/M10
8PQ3000-0BA73 1 Cable anchoring bracket
8PQ3000-0BA42 1 Cable anchoring bracket C30/B800
without screws, nuts and washers with locking edges for cable con-nection
02
02
1
Siemens LV 56 · 2008Siemens LV 56 · 2008
4
Cubicle, Supporting Structureand Enclosure
4/2 General Data
4/4 Cubicles and Supporting Structure
4/8 Base
4/9 Enclosure
4/2
Siemens LV 56 · 2008
Cubicle, Supporting Structure and Enclosure
4
General Data
■
Overview
3
14
2
1 Cubicle
2 Base with front covers
3 Glazed door Giugiaro Design
4 Rear wall
5
8
5
9
9
10 10
7
6
5 Side panel with design bar
6 Base besides covers
7 Bottom plate
8 Top plate
9 Supporting structure for main busbarsin standard position
10 Supporting structure for main busbars in standard positionand riser compartment 600mm + 200mm
NS
E0_
0167
0
4/3
Siemens LV 56 · 2008
Cubicle, Supporting Structure and Enclosure
4
General Data
■
Overview
Cross section of possible combinations of cubicles, Supporting structureand enclosures seen from above.
1
4
2
1 Supporting structure external for cover
2 Internal cover B200
3 Cover frame
4 Cubicle panelling IP3X or5
5 Door IP4X, IP55
0202
3
1
2
5
3
1
2
1 Supporting structure external for door
2 Outer plate B200, 400 or door B400, 600
3 Cover frame
4 Cubicle panelling IP3X or
5 Door IP4X, IP55
1 Supporting structure external for door
2 Outer plate B200, 400 or door B400, 600
3 Modular door
0202
2
3
2
2
3
4
0202
4
2
6
6 Cubicle
6
6 Cubicle
4
4 Cubicle
4/4
Siemens LV 56 · 2008
Cubicle, Supporting Structure and Enclosure
4
■
Description
The cubicle is a framework consisting of vertical and horizontal sections plus the fasteners necessary to assemble them.
This provides the bearing structure support to all add-on interior switchgear components. Stable and rugged construction is achieved through the use of galvanised sections and self-tapping screws. Equipotential and safe grounding of all constituent parts are also achieved.
The cubicle uprighte have holes spaced 25 mm apart for anchoring to the base or the floor. In the upper part these holes make it possible to fit crossbars, or eyebolts for board handling purposes.
The installation of interior components, kits, crossbars, supporting parts, etc., is facilitated by the presence of height, width and depth locators.
The supporting structure is made up of a vertical section, crossbars and fastening screws.
In cubicles of various heights and width it ensures segregation between the equipment compartment and the busbar compartment, partitioning the cubicles into equipment compartments and main, or distribution, busbars compartments.
■
Configuration
The values quoted below are the external dimensions.
A complete configuration is made of the following elements: cubicle, bottom plate partition crossbar and supporting structure for equipment heights of 1600mm or 1800mm.
To assemble two or more cubicles by width or depth, request the board coupling kit for each coupling point.
– Bottom plate partition not required
+++ Function performed by the cubicle
■
Selection and ordering data
Supporting strucutre
Heightmm
Widthmm
Deptmm
Cubicle Bottom plate partition
Equipment height
1800 mm 1600 mm
Cubicle and supporting structure with one section
2000 400 400
8PQ1204-4BA01
–
+++ 8PQ3000-0BA65
2000 600 400
8PQ1206-4BA01
–
+++ 8PQ3000-0BA65
2000 800 400
8PQ1208-4BA01
–
+++ 8PQ3000-0BA65
2000 1000 400
8PQ1201-4BA02
8PQ3000-1BA38
+++ 8PQ3000-0BA65
2000 1200 400
8PQ1202-4BA02
8PQ3000-1BA38
+++ 8PQ3000-0BA65
2000 400 600
8PQ1204-6BA01 – 8PQ3000-0BA03 8PQ3000-0BA01
2000 600 600
8PQ1206-6BA01 – 8PQ3000-0BA03 8PQ3000-0BA01
2000 800 600
8PQ1208-6BA01
–
8PQ3000-0BA03 8PQ3000-0BA01
2000 1000 600
8PQ1201-6BA02
8PQ3000-1BA40
8PQ3000-0BA03 8PQ3000-0BA01
2000 1200 600
8PQ1202-6BA02
8PQ3000-1BA40
8PQ3000-0BA03 8PQ3000-0BA01
2000 400 800
8PQ1204-8BA01 – 8PQ3000-0BA03 8PQ3000-0BA02
2000 600 800
8PQ1206-8BA01 – 8PQ3000-0BA03 8PQ3000-0BA02
2000 800 800
8PQ1208-8BA01
–
8PQ3000-0BA03 8PQ3000-0BA02
2000 1000 800
8PQ1201-8BA03
2x 8PQ3000-1BA38
8PQ3000-0BA03 8PQ3000-0BA02
2000 1200 800
8PQ1202-8BA02
2x 8PQ3000-1BA38
8PQ3000-0BA03 8PQ3000-0BA02
01
79
7
02
02
5
02
02
6
02
02
7
Cubicle and supporting structure
4/5
Siemens LV 56 · 2008
Cubicle, Supporting Structure and Enclosure
4
Cubicle and Supporting structure
■
Description
The
supporting structure external
is made up of a vertical section and the relative fasteners.
The Supporting structure for internal covers
constitutes a cubicle upright that makes it possible to fit a front frame and an interior cover in front of a cubicle part 200mm in width.
The Supporting strucutre for outer covers/door
constitutes two cubicle uprights and makes it possible to fit modular doors/a front frame and a door/exterior cover.
■
Configuration
The values quoted below are the external dimensions.
A complete configuration is made up of the following elements: cubicle, bottom plate partition crossbar, supporting structure, for an equipment height of 1800mm or 1600mm, and an supporting structure external for the installation of interior covers or an exterior cover/doors.
For separation forms >1 when using 200mm, 400mm, 600mm cubicles, as cable compartment or equipment compartment request an additional supporting structure, see page 4/7.
A combination of supporting structure external for internal covers and modular doors is not possible.
To assemble two or more cubicles by width or depth, request the board coupling kit for each coupling point.
– not possible
+++ Function performed by the supporting structure external
■
Selection and ordering data
Interior intermediate side upright Supporting structure external
Heightmm
Widthmm
Depthmm
Cubicle partition
Cubicle Bottom plate crossbar
Equipment height For upgrade
1800 mm 1600 mm Internal covers Door auter covers
Cubicles and Supporting structure with division into two sections
2000 800 400 600+200
8PQ1208-4BA01 8PQ3000-1BA38 +++ 8PQ3000-0BA658PQ3000-1BA31
8PQ3000-1BA42 8PQ3000-1BA43
2000 1000 400 600+400
8PQ1201-4BA02 8PQ3000-1BA38 +++ 8PQ3000-0BA658PQ3000-1BA31
– 8PQ3000-1BA43
2000 1000 400 800+200
8PQ1201-4BA02 8PQ3000-1BA38 +++ 8PQ3000-0BA658PQ3000-1BA31
8PQ3000-1BA42 8PQ3000-1BA43
2000 1200 400 600+600
8PQ1202-4BA02 8PQ3000-1BA38 +++ 8PQ3000-0BA658PQ3000-1BA31
– 8PQ3000-1BA43
2000 800 600 600+200
8PQ1208-6BA01 8PQ3000-1BA40 8PQ3000-0BA038PQ3000-1BA36
8PQ3000-0BA018PQ3000-1BA32
8PQ3000-1BA42 8PQ3000-1BA43
2000 1000 600 600+400
8PQ1201-6BA02 8PQ3000-1BA40 8PQ3000-0BA038PQ3000-1BA36
8PQ3000-0BA018PQ3000-1BA32
– 8PQ3000-1BA43
2000 1000 600 800+200
8PQ1201-6BA02 8PQ3000-1BA40 8PQ3000-0BA038PQ3000-1BA36
8PQ3000-0BA018PQ3000-1BA32
8PQ3000-1BA42 8PQ3000-1BA43
2000 1200 600 600+600
8PQ1202-6BA02 8PQ3000-1BA40 8PQ3000-0BA038PQ3000-1BA36
8PQ3000-0BA018PQ3000-1BA32
– 8PQ3000-1BA43
2000 800 800 600+200
8PQ1208-8BA01
2x 8PQ3000-1BA38
8PQ3000-0BA038PQ3000-1BA37
8PQ3000-0BA028PQ3000-1BA34
8PQ3000-1BA42 8PQ3000-1BA43
2000 1000 800 600+400
8PQ1201-8BA03
2x 8PQ3000-1BA38
8PQ3000-0BA038PQ3000-1BA37
8PQ3000-0BA028PQ3000-1BA34
– 8PQ3000-1BA43
2000 1000 800 800+200
8PQ1201-8BA03
2x 8PQ3000-1BA38
8PQ3000-0BA038PQ3000-1BA37
8PQ3000-0BA028PQ3000-1BA34
8PQ3000-1BA42 8PQ3000-1BA43
2000 1200 800 600+600
8PQ1202-8BA02
2x 8PQ3000-1BA38
8PQ3000-0BA038PQ3000-1BA37
8PQ3000-0BA028PQ3000-1BA34
– 8PQ3000-1BA43
01
79
7
02
02
5
02
02
8
02
02
9
02
03
0
4/6
Siemens LV 56 · 2008
Cubicle, Supporting Structure and Enclosure
4
■
Description
The supporting structrure external
is made up of a vertical section and the relative fasteners.
The supporting structure external of internal covers
constitutes a cubicle upright and makes it possible to fit a front frame and an interior cover in front of a cubicle part 200mm in width.
The supporting structure external outer cover/doors
constitutes two cubicle uprights and makes it possible to fit externally modular doors/a front frame and a door/ cover.
■
Configuration
The values quoted below are the external dimensions.
A complete configuration is made up of the following elements: cubicle, bottom plate partition crossbar, side supporting structure for an equipment height of 1800mm or 1600mm and an intermediate upright.
The exterior intermediate upright consists of the following combination of:
2 Supporting structure external for internal covers or1 Supporting structure external for internal covers and 1 intermediate upright for exterior cover/door. or2 Supporting structure external for outer cover/door
A combination of exterior intermediate upright for interior covers and modular doors is not possible.
For separation forms >1 when using 200mm, 400mm, 600mm cubicles, as cable compartment or equipment compartment request an additional intermediate upright, see page 4/7.
To assemble two or more cubicles by width or depth, request the board coupling kit.
+++ Function performed by the exterior supporting structure
■
Selection and ordering data
Supporting structure Supporting structure external
Heightmm
Widthmm
Depthmm
Cubicle sub-division into sections
Cubicle Bottom plate par-tition crossbars
Equipment height For upgrade
1800 mm 1600 mm Interior covers Modular doors/ex-terior covers
Cubicle and supporting structure with subdivision into three sections
2000 1000 400
200+600+200
8PQ1201-4BA02
2x 8PQ3000-1BA38
+++
8PQ3000-0BA652x 8PQ3000-1BA31
8PQ3000-1BA42 8PQ3000-1BA43
2000 1200 400
400+600+200
8PQ1202-4BA02
2x 8PQ3000-1BA38
+++
8PQ3000-0BA652x 8PQ3000-1BA31
8PQ3000-1BA42 8PQ3000-1BA43
2000 1200 400
200+800+200
8PQ1202-4BA02
2x 8PQ3000-1BA38
+++
8PQ3000-0BA652x 8PQ3000-1BA31
8PQ3000-1BA42 8PQ3000-1BA43
2000 1000 600
200+600+200
8PQ1201-6BA02
2x 8PQ3000-1BA40 8PQ3000-0BA032x 8PQ3000-1BA36
8PQ3000-0BA012x 8PQ3000-1BA32
8PQ3000-1BA42 8PQ3000-1BA43
2000 1200 600
400+600+200
8PQ1202-6BA02
2x 8PQ3000-1BA40 8PQ3000-0BA032x 8PQ3000-1BA36
8PQ3000-0BA012x 8PQ3000-1BA32
8PQ3000-1BA42 8PQ3000-1BA43
2000 1200 600
200+800+200
8PQ1202-6BA02
2x 8PQ3000-1BA40 8PQ3000-0BA032x 8PQ3000-1BA36
8PQ3000-0BA012x 8PQ3000-1BA32
8PQ3000-1BA42 8PQ3000-1BA43
2000 1000 800
200+600+200
8PQ1201-8BA03
4x 8PQ3000-1BA38 8PQ3000-0BA032x 8PQ3000-1BA37
8PQ3000-0BA022x 8PQ3000-1BA34
8PQ3000-1BA42 8PQ3000-1BA43
2000 1200 800
400+600+200
8PQ1202-8BA02
4x 8PQ3000-1BA38 8PQ3000-0BA032x 8PQ3000-1BA37
8PQ3000-0BA022x 8PQ3000-1BA34
8PQ3000-1BA42 8PQ3000-1BA43
2000 1200 800
200+800+200
8PQ1202-8BA02
4x 8PQ3000-1BA38 8PQ3000-0BA032x 8PQ3000-1BA37
8PQ3000-0BA022x 8PQ3000-1BA34
8PQ3000-1BA42 8PQ3000-1BA43
01
79
7
02
03
1
02
03
2
02
03
3
02
03
4
Cubicle supporting structure
4/7
Siemens LV 56 · 2008
Cubicle, Supporting Structure and Enclosure
4
Cubicle and Supporting structure
■
Description
The supporting structure is made up of vertical and horizontal sections and the relative fasteners. In cubicles of different depths the supporting structure ensures the creation of equipment and cable compartments and divides the cubicle into equipment compartment, main or distribution busbars compartment as well as cable compartment.
■
Configuration
For sepation forms 2, 3, 4 when using 200mm, 400mm or 600mm cubicles, in a cubicle partitioned on the left/right as cable compartment or equipment compartment, order an supporting structure kit as an additional component.
1
required only for supporting structure external for internal covers
■
Description
The kit for coupling two or more boards by width or depth consists of fastening plates and screws. The board coupling gasket kit with degree of protection IP55 consists of a self-adhesive gasket roll. .
■
Configuration
To assemble two or more cubicles by width or depth, request a board coupling kit for each coupling point.
For a degree of protection IP55, order an IP55 board coupling gasket kit as an additional component.
Supporting structure
Heightmm
Depthmm
Equipment height
1800 mm 1600 mm
Supporting structure
2000 400
8PQ3000-1BA42
1
8PQ3000-1BA31
2000 600
8PQ3000-1BA36 8PQ3000-1BA32
2000 800
8PQ3000-1BA37 8PQ3000-1BA34
02
03
5
02
03
6
Ordering code UI
Board coupling kit
Board coupling by width or depth kit 8PQ1204-4BA05
8PQ1204-4BA05
1
IP55 board coupling gasket 8PQ1204-4BA04
8PQ1204-4BA04
1
4/8
Siemens LV 56 · 2008
Cubicle, Supporting Structure and Enclosure
4
■
Description
The base kit is made of the following elements: corner pieces, front covers and the relative fasteners.
Ad hoc covers to be order separately are available for the side covers. The covers of the base are not suitable for board transport and handling.
For special situations, such as rolling, moving the cubicles on roller an ad hoc reinforcement kit is available (that can be applied along the width or the depth of the cubicle as a function of the direction of movement). Base reinforcements are mounted internally, at the front, back or side.
■
Configuration
For each board, consisting of one or more cubicles, the “side covers” kit must be ordered once for the H 100 base and twice for the H 200 base.
■
Selection and ordering data
Heightmm
Widthmm
Depthmm
Ordering code UI
Base with front covers
100 400 –
8PQ1014-0BA01
1
100 600 –
8PQ1016-0BA01
1
100 800 –
8PQ1018-0BA01
1
100 1000 –
8PQ1011-0BA01
1
100 1200 –
8PQ1012-0BA01
1
200 400 –
8PQ1024-0BA01
1
200 600 –
8PQ1026-0BA01
1
200 800 –
8PQ1028-0BA01
1
200 1000 –
8PQ1021-0BA01
1
200 1200 –
8PQ1022-0BA01
1
Base covers besides
100 – 400
8PQ1010-4BA01
2
100 – 600
8PQ1010-6BA01
2
100 – 800
8PQ1010-8BA01
2
Base reinforcement
100 – 400
8PQ1014-0BA02
2
100 – 600
8PQ1016-0BA02
2
100 – 800
8PQ1018-0BA02
2
100 400 –
8PQ1014-0BA02
2
100 600 –
8PQ1016-0BA02
2
100 800 –
8PQ1018-0BA02
2
100 1000 –
8PQ1011-1BA01
2
100 1200 –
8PQ1012-2BA01
2
01
64
20
17
98
01
64
30
16
44
Transport with base and lift truck Transport with reinforced base and rollers
01
07
8
01
07
9
Base
4/9
Siemens LV 56 · 2008
Cubicle, Supporting Structure and Enclosure
4
■
Description
The front or blind covers of the various assembly kits are anchored to a “cover frame” by means of quick locking screws (a hinge kit can be an option to obtain a rotary cover).
A cover frame 1600 or 1800 mm high in fixed or swivel versions is available. In the frame there is room to house the front covers of the assembly kits. The rotary mechanism enables the frame to be rotated over a 180° angle.
This gives full access to the interior components of the board.
■
Configuration
The cover frame are available for 600 mm and 800 mm wide cubicles.
Frame types available:
– H 1600 mm frame for assembly kits with built-in covers for busbar systems in the upper part and grounding bars in the lower part.
– H 1800 mm frame for assembly kits. For a rear upper busbar system, the space available in the upper section is 150 mm high and only 300 mm deep. This module can be used only for covers and DIN rail kits for modular units.
For an exact selection, see also the notes in chapter 5 “busbar systems”.
■
Selection and ordering data
Height for equipment mm
Widthmm
Ordering code UI
Fixed cover frame for front main busbars
1600 600
8PQ2000-6BA03
1
1600 800
8PQ2000-8BA03
1
Fixed cover frame without or with rear main busbars
1800 600
8PQ2000-6BA04
1
1800 800
8PQ2000-8BA04
1
Swivel cover frame for front main busbars
1600 600
8PQ2000-6BA02
1
1600 800
8PQ2000-8BA02
1
Swivel cover frame without or with rear main busbars
1800 600
8PQ2000-6BA01
1
1800 800
8PQ2000-8BA01
1
01
80
20
18
03
01
62
60
16
25
Enclosure
4/10
Siemens LV 56 · 2008
Cubicle, Supporting Structure and Enclosure
4
Enclosure
■
Description
For 600mm and 800mm wide cubicles with front frame, cubicle panelling are available as an alternative to doors.
With its thickness, the finishing frame ensures the same height as an adjacent door, as well as the same height of the cover of the uprights of the galvanised chromed cubicle.
Cubicle panelling, covers and finishing frame achieve a degree of protection of IP30/31.
■
Configuration
For use only in conjunction with a front frame.
Only for 600mm and 800mm wide cubicles.
■
Selection and ordering data
Height Widthmm
Degree of protection
Ordering code UI
Cubicle panelling
Cubicle height 600 IP30
8PQ2197-6BA11
1
Cubicle height 800 IP30
8PQ2197-8BA11
1
01
63
6
■
Description
A outer cover can be instead a door of 200mm and 400mm wide compartments.
The kit includes a painted cover, a green column identification strip, an anchoring support and the relative fasteners. This cover must be used in conjunction with the cover frame or as an alternative to the door.
■
Configuration
The covers can be can be mounted as desired on the front or the back of the cubicle.
For use only in conjunction with the supporting structure external for outer covers/door.
■
Selection and ordering data
Height cover Widthmm
Degree of protection
Ordering code UI
Outer cover
Cubicle height 200 IP40
8PQ2197-2BA15
1
Cubicle height 400 IP40
8PQ2197-4BA02
1
Cubicle height 200 IP55
8PQ2197-2BA14
1
Cubicle height 400 IP55
8PQ2197-4BA01
1
01
66
3
■
Description
For 200mm wide cubicle sections, an internal cover that can be mounted behind the door is available.
The kit is made up of a cover, an anchoring support and fasteners. This cover must be used in conjunction with a cover frame and can be placed behind the door.
■
Configuration
When a 200mm section is produced in a cubicle, this section can be placed indifferently on the left or the right side, and is closed with an interior cover.
For use only in conjunction with an supporting structure externa for internal covers.
■
Selection and ordering data
Height of cover Widthmm
Degree of protection
Ordering code UI
Internal cover for 200mm section
Cubicle height 200 IP30
8PQ2000-2BA01
1
01
79
9
4/11
Siemens LV 56 · 2008
Cubicle, Supporting Structure and Enclosure
4
Enclosure
■
Description
The SIVACON S4 door kit is made up of Giugiaro Design glazed doors or metal plate doors, a green column identification strip, hinges and preassembled bar lock closing system with two-way interlocking mechanism.
The two-way interlocking mechanism can be replaced with a rotary handle (standard doors are not suitable for semi-cylindrical profiles).
Thanks to the new hinge and locking system, the door hinges can be fitted either on the left or the right.
The position of the hinges can be easily modified at a later stage.
If it is deemed necessary to fit a closing system with rotary handle and semi-cylindrical profile with security key, on account of cylinder depth, a series of dedicated doors with right or left side hinges are available.
■
Configuration
Standard version doors use a 3mm two-way interlocking system.
The doors can be mounted indifferently to the front or back of the cubicle.
In cubicles with degree of protection IP40 the top plate, the doors and the rear wall must have the same degree of protection.
■
Selection and ordering data
Door type Door height mm
Door width mm
Degree of protection
Hinge position Ordering code UI
Cubicle door with two-way interlocking system
Finned plate door 1975 400 IP40 left
8PQ2197-4BA08
1
Finned plate door 1975 600 IP40 left
8PQ2197-6BA06
1
Finned plate door 1975 800 IP40 left
8PQ2197-8BA06
1
Finned plate door 1975 1000 IP40 left
8PQ2197-1BA06
1
Finned plate door 1975 400 IP40 right
8PQ2197-4BA11
1
Finned plate door 1975 600 IP40 right
8PQ2197-6BA13
1
Finned plate door 1975 800 IP40 right
8PQ2197-8BA13
1
Finned plate door 1975 1000 IP40 right
8PQ2197-1BA18
1
Plate door 1975 400 IP55 left
8PQ2197-4BA05
1
Plate door 1975 600 IP55 left
8PQ2197-6BA03
1
Plate door 1975 800 IP55 left
8PQ2197-8BA03
1
Plate door 1975 1000 IP55 left
8PQ2197-1BA03
1
Plate door 1975 400 IP55 right
8PQ2197-4BA10
1
Plate door 1975 600 IP55 right
8PQ2197-6BA12
1
Plate door 1975 800 IP55 right
8PQ2197-8BA12
1
Plate door 1975 1000 IP55 right
8PQ2197-1BA17
1
Glazed door 1975 600 IP55 left
8PQ2197-6BA10
1
Glazed door 1975 800 IP55 left
8PQ2197-8BA10
1
Glazed door 1975 1000 IP55 left
8PQ2197-1BA10
1
Glazed door 1975 600 IP55 right
8PQ2197-6BA14
1
Glazed door 1975 800 IP55 right
8PQ2197-8BA14
1
Glazed door 1975 1000 IP55 right
8PQ2197-1BA20
1
01
63
50
16
33
01
63
4
4/12 Siemens LV 56 · 2008
Cubicle, Supporting Structure and Enclosure
4
■ Description The SIVACON S4 door kit is made up of Giugiaro Design glazed doors or metal doors, a green column identification strip, hinges and preassembled bar lock closing system with rotary handle mechanism for semi-cylindrical profile.
■ Configuration Standard version doors use a two-way interlocking mechanism.
Semi-cylindrical profile: see chapter s10 “Accessories”.
The doors can be mounted indifferently to the front or back of the cubicle.
The hinges for double doors are hooked onto the cubicle externally.
The double doors of 1000mm wide cubicles are split into a 600mm left section and a 400mm right section. Opening sequence: right and then left.
The double doors of 1200mm wide cubicles are split 50/50. Opening sequence: right and then left.
In cubicles with degree of protection IP40, the top plate, the doors and the rear wall must have the same degree of protection.
■ Selection and ordering data
Door type Door height mm
Door width mm
Degree of protection
Hinge position Ordering code UI
Door with rotary handle for semi-cylindrical profile DIN 18252/18254, 8 x 45° Finned plate door 1975 400 IP40 left 8PQ2197-4BA06 1
Finned plate door 1975 600 IP40 left 8PQ2197-6BA04 1
Finned plate door 1975 800 IP40 left 8PQ2197-8BA04 1
Finned plate door 1975 1000 IP40 left 8PQ2197-1BA07 1
Finned plate door 1975 400 IP40 right 8PQ2197-4BA07 1
Finned plate door 1975 600 IP40 right 8PQ2197-6BA05 1
Finned plate door 1975 800 IP40 right 8PQ2197-8BA05 1
Finned plate door 1975 1000 IP40 right 8PQ2197-1BA08 1
Plate door 1975 400 IP55 left 8PQ2197-4BA03 1
Plate door 1975 600 IP55 left 8PQ2197-6BA01 1
Plate door 1975 800 IP55 left 8PQ2197-8BA01 1
Plate door 1975 1000 IP55 left 8PQ2197-1BA04 1
Plate door 1975 400 IP55 right 8PQ2197-4BA04 1
Plate door 1975 600 IP55 right 8PQ2197-6BA02 1
Plate door 1975 800 IP55 right 8PQ2197-8BA02 1
Plate door 1975 1000 IP55 right 8PQ2197-1BA05 1
Glazed door 1975 600 IP55 left 8PQ2197-6BA07 1
Glazed door 1975 800 IP55 left 8PQ2197-8BA07 1
Glazed door 1975 1000 IP55 left 8PQ2197-1BA11 1
Glazed door 1975 600 IP55 right 8PQ2197-6BA08 1
Glazed door 1975 800 IP55 right 8PQ2197-8BA08 1
Glazed door 1975 1000 IP55 right 8PQ2197-1BA12 1
Double door with two-way interlocking mechanism Finned plate door 1975 1000 IP40 – 8PQ2197-1BA14 1
Finned plate door 1975 1200 IP40 – 8PQ2197-2BA11 1
Plate door 1975 1000 IP55 – 8PQ2197-1BA13 1
Plate door 1975 1200 IP55 – 8PQ2197-2BA10 1
Double door with rotary handle for semi-cylindrical profile Finned plate door 1975 1000 IP40 – 8PQ2197-1BA16 1
Finned plate door 1975 1200 IP40 – 8PQ2197-2BA13 1
Plate door 1975 1000 IP55 – 8PQ2197-1BA15 1
Plate door 1975 1200 IP55 – 8PQ2197-2BA12 1
01
80
40
18
05
01
80
60
16
96
01
69
8
Enclosure
4/13Siemens LV 56 · 2008
Cubicle, Supporting Structure and Enclosure
4
Enclosure
■ DescriptionThe inner door kit includes a door and hinges. The inner door is mounted behind the main cubicle door and in front of the large-sized mounting plate for electrotechnical applications.
■ ConfigurationThe inner door requires a depth of 30 mm and cannot be used in conjunction with a cover frame.
■ Selection and ordering data
Height Widthmm
Ordering code UI
Inner door Cubicle height 600 8PQ2000-6BA05 1
Cubicle height 800 8PQ2000-8BA05 1
Cubicle height 1000 8PQ2000-1BA01 1
01
69
9
4/14 Siemens LV 56 · 2008
Cubicle, Supporting Structure and Enclosure
4
Enclosure
1) Lieferbar ab 02/2007.
■ DescriptionBottom plates are available with degree of protection IP55 without cable entry opening and with degree of protection IP40 with variable cable entry opening.
■ ConfigurationFor 800mm wide cubicles, order two 400mm deep bottom plates.
For 800mm, 1000mm, 1200mm wide cubicles, bottom plate selection depends on the combination of variants corresponding to cubicle subdivision.
■ Selection and ordering data
Widthmm
Depthmm
Degree of protection
Ordering code UI
Bottom plate without cable entry 200 400 IP55 8PQ2302-4BA04 1
400 400 IP55 8PQ2304-4BA05 1
600 400 IP55 8PQ2306-4BA05 1
800 400 IP55 8PQ2308-4BA05 1
200 600 IP55 8PQ2302-6BA04 1
400 600 IP55 8PQ2304-6BA05 1
600 600 IP55 8PQ2306-6BA05 1
800 600 IP55 8PQ2308-6BA05 1
Bottom plate with variable cable entry400 400 IP40 8PQ2304-4BA06 1
600 400 IP40 8PQ2306-4BA06 1
800 400 IP40 8PQ2308-4BA06 1
400 600 IP40 8PQ2304-6BA06 1
600 600 IP40 8PQ2306-6BA06 1
800 600 IP40 8PQ2308-6BA06 1
01631
01632
4/15Siemens LV 56 · 2008
Cubicle, Supporting Structure and Enclosure
4
Enclosure
■ Description Top plates are available with degree of protection IP55 and IP40 without cable entry opening. A version with degree of protection IP40 with variable cable entry opening is also available. The top plates with degree of protection IP55 are secured with screws on one side and snap into the board structure on the other. By means of a further upgrade, degree of protection IPX1 can be achieved.
■ ConfigurationFor cubicles with degree of protection IP 40, the top plates, the bottom plates, the doors and the panels must have the same degree of protection IP 40.
With the IPX1 upgrade, cubicles with degree of protection IP30 and IP40 can achieve degree of protection IP31 and IP41 respectively. Column height is increased by 62 mm.
■ Selection and ordering data
Widthmm
Depthmm
Degree of protection
Ordering code UI
Top plate without cable entry 400 400 IP40 8PQ2304-4BA02 1
400 600 IP40 8PQ2304-6BA02 1
400 800 IP40 8PQ2304-8BA02 1
600 400 IP40 8PQ2306-4BA02 1
600 600 IP40 8PQ2306-6BA02 1
600 800 IP40 8PQ2306-8BA02 1
800 400 IP40 8PQ2308-4BA02 1
800 600 IP40 8PQ2308-6BA02 1
800 800 IP40 8PQ2308-8BA02 1
1000 400 IP40 8PQ2301-4BA02 1
1000 600 IP40 8PQ2301-6BA02 1
1000 800 IP40 8PQ2301-8BA02 1
1200 400 IP40 8PQ2302-4BA02 1
1200 600 IP40 8PQ2302-6BA02 1
1200 800 IP40 8PQ2302-8BA02 1
400 400 IP55 8PQ2304-4BA01 1
400 600 IP55 8PQ2304-6BA01 1
400 800 IP55 8PQ2304-8BA01 1
600 400 IP55 8PQ2306-4BA01 1
600 600 IP55 8PQ2306-6BA01 1
600 800 IP55 8PQ2306-8BA01 1
800 400 IP55 8PQ2308-4BA01 1
800 600 IP55 8PQ2308-6BA01 1
800 800 IP55 8PQ2308-8BA01 1
1000 400 IP55 8PQ2301-4BA01 1
1000 600 IP55 8PQ2301-6BA01 1
1000 800 IP55 8PQ2301-8BA01 1
1200 400 IP55 8PQ2302-4BA01 1
1200 600 IP55 8PQ2302-6BA01 1
1200 800 IP55 8PQ2302-8BA01 1
Top plate with cable entry 400 400 IP40 8PQ2304-4BA03 1 400 600 IP40 8PQ2304-6BA03 1 400 800 IP40 8PQ2304-8BA03 1 600 400 IP40 8PQ2306-4BA03 1 600 600 IP40 8PQ2306-6BA03 1 600 800 IP40 8PQ2306-8BA03 1 800 400 IP40 8PQ2308-4BA03 1 800 600 IP40 8PQ2308-6BA03 1 800 800 IP40 8PQ2308-8BA03 1
Top plate upgrade for IPX1 400 400 IPX1 8PQ2304-4BA04 1 400 600 IPX1 8PQ2304-6BA04 1 400 800 IPX1 8PQ2304-8BA04 1 600 400 IPX1 8PQ2306-4BA04 1 600 600 IPX1 8PQ2306-6BA04 1 600 800 IPX1 8PQ2306-8BA04 1 800 400 IPX1 8PQ2308-4BA04 1 800 600 IPX1 8PQ2308-6BA04 1 800 800 IPX1 8PQ2308-8BA04 11000 400 IPX1 8PQ2301-4BA03 11000 600 IPX1 8PQ2301-6BA03 11000 800 IPX1 8PQ2301-8BA03 11200 400 IPX1 8PQ2302-4BA03 11200 600 IPX1 8PQ2302-6BA03 11200 800 IPX1 8PQ2302-8BA03 1
01628
01627
01630
01629
4/16 Siemens LV 56 · 2008
Cubicle, Supporting Structure and Enclosure
4
Enclosure
■ Description Rear panels are available with degrees of protection IP40 and IP55. Rear panels with degree of protection IP40 are galvanised chromed, and those with degree of protection IP55 are slightly embossed, RAL 7035 powder-coated.
■ ConfigurationFor cubicles with degree of protection IP 40, the top plates, the bottom plates, the doors and the rear panels must have the same degree of protection IP 40.
■ Selection and ordering data
■ Description The side panels are powder-coated and are available with degree of protection IP 55, with or without Design bar.
■ ConfigurationFor each board, order one kit of side panels.
■ Selection and ordering data
Widthmm
Depthmm
Degree of protection
Ordering code UI
Rear panel 2000 400 IP40 8PQ2420-4BA02 1
2000 600 IP40 8PQ2420-6BA02 1
2000 800 IP40 8PQ2420-8BA02 1
2000 1000 IP40 8PQ2420-1BA02 1
2000 1200 IP40 8PQ2420-2BA02 1
2000 400 IP55 8PQ2420-4BA01 1
2000 600 IP55 8PQ2420-6BA01 1
2000 800 IP55 8PQ2420-8BA01 1
2000 1000 IP55 8PQ2420-1BA01 1
2000 1200 IP55 8PQ2420-2BA01 1
01
78
90
16
37
Widthmm
Depthmm
Degree of protection
Ordering code UI
Side panel with design 2000 400 IP55 8PQ2520-4BA01 2
2000 600 IP55 8PQ2520-6BA01 2
2000 800 IP55 8PQ2520-8BA01 2
Side panel without design 2000 400 IP55 8PQ2520-4BA02 2
2000 600 IP55 8PQ2520-6BA02 2
2000 800 IP55 8PQ2520-8BA02 2
01
64
00
16
39
Siemens LV 56 · 2008Siemens LV 56 · 2008
5
Busbar System
5/2 General Data
5/3 Main busbar system
5/7 Vertical distribution busbar system
5/11 Compact busbar systems
5/13 Copper bars
5/14 Busbar connection fasteners
5/2
Siemens LV 56 · 2008
Busbar System
5
General Data
■
Overview
2
1
4
3
1 System of main busbar withrectangular profile
2 Main busbar extension kit
3 Grounding bar PE
4 Busbar holder
5
5 Reinforcement
4
01
67
6
5/3
Siemens LV 56 · 2008
Busbar System
5
Main busbar system
■
Technical specifications
Admissible rated current for main busbar systems
These values refer to normal operating conditions and indoor installation in accordance with IEC 60439-1, in particular, at an ambient temperature of 35°C (24h average).In different operating conditions, the correction factors given in the “Planning and Configuration” chapter have to be taken into account.
Cross-sections for PE conductor
The cross-sections specified for PE conductors were type tested according to IEC 60439-1. According to IEC 60439-1 a PE conductor cross-section corresponding to 25% the cross-section of main conductors is also admissible.
Determination of the number of reinforcements as a function of short-circuit current and cubicle width
1) The number of reinforcements applies to a main busbar system. Since the 3700 A and 4000 A main busbar system is made up of two systems mounted in parallel, the number of reinforcements to be ordered must be doubled.
For the determination of the distances between busbar holders and reinforcements, refer to the SIVACON S4 Manual.
No. of bars per phase Dimensions[mm]
Rated current at an ambient temperature of 35 °C
Depth of cubicle 400mm Depth of cubicle 600mm Depth of cubicle 800mm
IP ≤ IP41 IP 55 IP ≤ IP41 IP 55 IP ≤ IP41 IP 55
2 20
×
10 1190 965 1190 965 1190 9652 30
×
10 1630 1310 1630 1310 1630 13104 20
×
10 1920 1420 1920 1540 1930 16504 30
×
10 2460 1790 2490 1950 2510 21104 40
×
10 2980 2150 3040 2350 3100 25604 50
×
10 3220 2330 3320 2570 3410 28202
×
4 20
×
10 3700 30002
×
4 30
×
10 4660 3680
No. of bars Dimensions[mm]
I
cw
1s
2 20
×
5 65 kA
2 30
×
5 85 kA
2 40
×
5 100 kA
2 30
×
10 100 kA
Busbar cross-section Width [mm] No. of reinforcements as a function of I
pk
, I
cw
and cubicle width
No of bars Dimensions[mm]
I
cw
= 25 kAI
pk
= 52,5 kAI
cw
= 35 kAI
pk
= 73,5 kAI
cw
= 50 kAI
pk
= 105 kAI
cw
= 65 kAI
pk
= 143 kAI
cw
= 85 kAI
pk
= 187 kAI
cw
= 100 kAI
pk
= 220 kA2 20
×
10 400 0 0 600 0 0 800 1 11000 1 11200 2 2
2 30
×
10 400 0 0 600 0 1 800 1 11000 1 21200 2 2
4 20
×
10 400 0 0 0 600 0 0 1 800 1 1 21000 2 2 31200 2 2 3
4 30
×
10 400 0 0 0 0 600 0 0 1 1 800 1 1 2 21000 2 2 3 31200 2 2 3 3
4 40
×
10 400 0 0 0 0 600 0 0 1 1 800 1 1 2 21000 1 1 3 31200 2 2 3 4
4 50
×
10 400 0 0 0 0 600 0 0 1 1 800 1 1 2 21000 1 1 3 31200 2 2 3 4
2
×
4
1
20
×
10 400 0 0 0 600 1 1 1 800 2 2 21000 3 3 31200 4 4 4
2
×
4
1
30
×
10 400 0 0 0 600 1 1 1 800 2 2 21000 3 3 31200 4 4 4
5/4
Siemens LV 56 · 2008
Busbar System
5
■
Description
The main busbar system of SIVACON S4 offers an appropriate scaling of rated currents, matched to the rated currents of standard version circuit breakers and transformers. The busbar holders have been designed for the use of rectangular copper profiles.By using 2, 4 or 8 sub-conductors per phase, it is possible to achieve high resistance to short-circuits and make the connections without having to drill holes. This arrangement also simplify handling of one or more cubicles.
The main horizontal busbar system provides for a variety of network configurations such as TN-C, TN-S, IT and TT. The connection of the PE bar to the cubicle is type-tested (resistance to short-circuits) and ensures a safe transfer of fault currents to the cubicle. For TN-C network systems, a type-tested connection (PEN jumper) between the PEN bar and the cubicle is available.
■
Configuration
SIVACON S4 main busbar system in standard position
- Installation position: front top - Cubicle depth 600 mm - Rated current up to 3200 A - Side upright for 1600mm high modules - Front frame for 1600mm high modules
SIVACON S4 main busbar system in standard position
- Installation position: front top - Cubicle depth 800 mm - Rated current up to 3200 A - Side upright for 1600mm high modules - Front frame for 1600mm high modules
SIVACON S4 main busbar system in standard position
- Installation position: front rear - Cubicle depth 800 mm - Rated current up to 3200 A - Side upright for 1600mm high modules - Front frame for 1600mm high modules or - Front frame for 1800mm high modules mm; the 150mm high upper module must be used only to fit the front cover
SIVACON S4 main busbar system in standard position
- Installation position: front top and rear (double upper system) - Cubicle depth 800 mm - Rated current up to 4000 A - Side upright for 1600mm high modules - Front frame for 1600mm high modules
SIVACON S4 main busbar system in standard position
- Installation position: front top - Cubicle depth 400 mm - Rated current up to 3200 A - Side upright for 1600mm high modules - Front frame for 1600mm high modules
SIVACON S4 main busbar system in optional position
- Installation position: at different heights at rear - Cubicle depth 800 mm - Rated current up to 3200 A - Side upright for 1800 mm high modules - Front frame for 1800 mm high modules - To position the busbars at an optional height other than in the upper part of the cubicle, order two 350mm long crossbars per cubicle
Main busbar system with PEN jumper
- The PEN jumper establishes the connection between the PEN bar and the cubicle. 1 PEN jumper per cubicle is required
PE bar connection
- The connection of the PE bar to the cubicle is included in the main busbar kit
01
70
20
17
03
01
70
40
17
05
01
70
10
16
92
01
70
60
17
10
Main busbar system
5/5
Siemens LV 56 · 2008
Busbar System
5
■
Selection and ordering data
■
Selection and ordering data
The number of reinforcements to be used depends on the value of the short-circuit current and cubicle width.
The additional internal arc protection kit is required for arcing times of between 100 ms and 300 ms. Order one kit per side panel.
Dimensionsmm
×
mmOrdering code UI
Main busbar holder kit up to 3200 A, with PE grounding bar connection to cubicle
20
×
10, 30
×
10, 40
×
10, 50
×
10
8PQ4000-0BA04
2
Main busbar holder kit up to 4000 A, with PE grounding bar connection to cubicle
20
×
10, 30
×
10, 40
×
10, 50
×
10
8PQ4000-0BA60
2
Busbar reinforcement kit
20
×
10, 30
×
10, 40
×
10, 50
×
10
8PQ4000-0BA37
1
Additional internal arc protection kit
8PQ9400-0BA21
2
02
03
7
12
1 12
1 12
1
Single-cubicle transport unit
02
03
8
Multi-cubicle transport unit
12
12
12
1
Main busbar holder1
Reinforcement2
01
68
50
16
86
01
68
70
20
39
Main busbar systems
5/6
Siemens LV 56 · 2008
Busbar System
5
■
Selection and ordering data
Dimensionsmm
×
mmOrdering code UI
Main busbars extension kit for L1, L2, L3, N or PEN
1
20
×
10
8PQ4000-0BA53
4
30
×
10
8PQ4000-0BA54
4
40
×
10
8PQ4000-0BA56
4
50
×
10
8PQ4000-0BA57
4
Extension kit for PE grounding bar
20
×
5, 30
×
5, 30
×
10
8PQ4000-0BA52
2
40
×
5, 40
×
10, 50
×
10
8PQ4000-0BA67
2
Connection kit for double main busbar system
1
(order 1 per cubicle; cannot be installed in 400mm wide cubicles)
–
8PQ4000-0BA62
1
PEN jumper for main busbar system
1
–
8PQ4000-0BA12
10
PE bar connection to cubicle (accessory)
–
8PQ4000-0BA82
6
01
67
40
16
73
01
79
00
17
06
01
71
0
Main busbar system
1) Without screws, washers and nuts.
5/7
Siemens LV 56 · 2008
Busbar System
5
Vertical distribution busbar system
■
Overview
Cascaded distribution busbar system with profiled busbarsSingle arrangement
Cascaded distribution busbar system with rectan-gular bars Single arrangement
Non-cascaded distribution busbars system with regular busbarsSingle arrangement
Cascaded distribution busbar system with profiled busbars Double arrangement, side-by-side
Cascaded distribution busbar system with rectan-gular bars Double arrangement, aligned
Non-cascaded distribution busbar system with rectangular bars Double arrangement, aligned
02
04
0
02
04
1
02
04
2
02
04
3
02
04
4
02
04
5
5/8
Siemens LV 56 · 2008
Busbar System
5
Vertical distribution busbar system
■
Technical specifications
Admissible rated current values for cascaded vertical distribution busbars
The rated sort-time current Icw for a cascaded vertical busbar system is determined on the basis of no. of busbars,
busbar size and shape, and the
number of busbar holders
.
These values refer to normal operating conditions and indoor installation in accordance with IEC 60439-1, in particular, at an ambient temperature of 35°C (24h average).In different operating conditions, the correction factors given in the “Planning and Configuration” chapter have to be taken into account.
Admissible rated current values for non-cascaded vertical distribution busbars
The rated sort-time current Icw of a non-cascaded vertical busbar system is determined on the basis of no. of busbars, busbar size, and
number of reinforcements
.
For each cubicle, order one kit (3 pcs.) of non-cascaded busbar holders.
These values refer to normal operating conditions and indoor installation in accordance with IEC 60439-1, in particular, at an ambient temperature of 35°C (24h average).In different operating conditions, the correction factors given in the “Planning and Configuration” chapter have to be taken into account.
No. of bars per phase Dimensions[mm]
Admissible current for a temperature of 35 °C
No. of holders per cubicle and per system
IP ≤ IP41 IP 55 I
cw
= 25 kAI
pk
= 52,5 kAI
cw
= 35 kAI
pk
= 73,5 kAI
cw
= 50 kAI
pk
= 105 kAI
cw
= 65 kAI
pk
= 143 kAI
cw
= 85 kAI
pk
= 187 kA
1 30
×
10 922 837 4 41 40
×
10 1100 980 4 42 30
×
10 1530 1337 4 4 4 52 40
×
10 1651 1543 4 4 4 5Profiled busbar 30
×
30 1289 1066 4 4 4 5Profiled busbar 40
×
30 1518 1217 4 4 4 52 x 2 30
×
10 3060 2674 4 5 82 x 2 40
×
10 3302 3086 4 5 82 x Profiled busbar 30
×
30 2578 2132 4 5 82 x Profiled busbar 40
×
30 3036 2434 4 5 8
No. of bars per phase Dimensions[mm]
Admissible current for a temperature of 35 °C
No. of reinforcements per cubicle
IP ≤ IP41 IP 55 I
cw
= 25 kAI
pk
= 52 kAI
cw
= 35 kAI
pk
= 73 kAI
cw
= 50 kAI
pk
= 105 kAI
cw
= 65 kAI
pk
= 143 kAI
cw
= 85 kAI
pk
= 187 kAI
cw
= 100 kAI
pk
= 220 kA
2 20
×
10 1010 820 0 02 30
×
10 1390 1110 0 0 24 20
×
10 1630 1207 0 0 2 24 30
×
10 2091 1520 0 0 2 2 24 40 × 10 2533 1825 0 0 0 2 2 44 50 × 10 2737 1980 0 0 0 2 2 4
5/9
Siemens LV 56 · 2008
Busbar System
5
Vertical distribution busbar system
■
Configuration
Cascaded vertical distribution busbar system
For profiled busbars, the connections are made by means of T-head screws. When using rectangular busbars,
the connections are made by means of screws and connection kits.
■
Selection and ordering data
Busbar dimensions mm
×
mmBusbar shape Cubicle
width mm
Cubicle depth mm
Position of main busbars
Position of vertical distri-bution bus-bars
Ordering code UI
Busbar holder kit for cascaded vertical distribution busbars
40
×
30 Profiled busbar 200 – – –
8PQ4000-0BA63
4
40
×
10 Rectangular busbar
200 – – –
8PQ4000-0BA63
4
30
×
30 Profiled busbar 200 – – –
8PQ4000-0BA32
4
30
×
10 Rectangular busbar
200 – – –
8PQ4000-0BA32
4
Busbar holder kit for non-cascaded vertical distribution busbars
20
×
10, 30
×
10, 40
×
10, 50
×
10 Rectangular busbar
200 – – –
8PQ4000-0BA77
3
20
×
10, 30
×
10, 40
×
10, 50
×
10 Rectangular busbar
400 – – –
8PQ4000-0BA31
3
Busbar reinforcement kit
20
×
10, 30
×
10, 40
×
10, 50
×
10 Rectangular busbar
– – – –
8PQ4000-0BA37
1
End support for non-cascaded vertical busbars
– – 200 – – –
8PQ4000-0BA78
1
– – 400 – – –
8PQ4000-0BA61
1
Anchoring support for N or PE bars in cable compartment
– – – – – –
8PQ4000-0BA11
4
01
69
00
16
88
01
68
70
16
89
01
70
7
5/10 Siemens LV 56 · 2008
Busbar System
5
Vertical distribution busbar system
■ Selection and ordering data
Bus bar dimensions mm × mm
Busbar shape Cubicle width mm
Cubicle depth mm
Position of main busbars
Position of vertical distri-bution bus-bars
Ordering code UI
Connection kit between cascaded vertical busbars/horizontal busbars 1
30 × 30, 30 × 10 – – 400 front right 8PQ4000-0BA45 1
40 × 30, 40 × 10 – – 400 front right 8PQ4000-0BA47 1
30 × 30, 30 × 10 – – 600, 800 front right 8PQ4000-0BA46 1
40 × 30, 40 × 10 – – 600, 800 front right 8PQ4000-0BA48 1
30 × 30, 30 × 10 – – 800 rear right 8PQ4000-0BA50 1
40 × 30, 40 × 10 – – 800 rear right 8PQ4000-0BA51 1
30 × 30, 30 × 10 – – 400 front left 8PQ4000-0BA73 1
40 × 30, 40 × 10 – – 400 front left 8PQ4000-0BA75 1
30 × 30, 30 × 10 – – 600, 800 front left 8PQ4000-0BA72 1
40 × 30, 40 × 10 – – 600, 800 front left 8PQ4000-0BA74 1
30 × 30, 30 × 10 – - 800 rear left 8PQ4000-0BA70 1
40 × 30, 40 × 10 – - 800 rear left 8PQ4000-0BA71 1
Connection kit between non-cascaded vertical busbars/horizontal busbars1
20 × 10, 30 × 10 – – 400 front – 8PQ4000-0BA38 1
40 × 10, 50 × 10 – – 400 front – 8PQ4000-0BA41 1
20 × 10, 30 × 10 – – 600, 800 front – 8PQ4000-0BA40 1
40 × 10, 50 × 10 – – 600, 800 front – 8PQ4000-0BA42 1
20 × 10, 30 × 10 – – 800 rear – 8PQ4000-0BA43 1
40 × 10, 50 × 10 – – 800 rear – 8PQ4000-0BA44 1
Busbar clamp kit for M10 screw– – – – – – 8PQ9400-0BA02 20
01
71
80
16
75
01
74
3
1) without screws, washers and nuts
5/11Siemens LV 56 · 2008
Busbar System
5
Compact busbar system
■ OverviewCompact busbar systems may be arranged as desired with uprights and crossbars.
02
04
6
02
04
7
Compact busbar systems 8GF57non-cascaded, anchored to crossbars
Compact busbar systems 8GF57cascaded, anchored to crossbars
5
1
3
5
2
4
Crossbars for anchoring depth-wise4
Supporting structure5
Non-cascaded busbar support1
Cascaded busbar support2
Crossbars for anchoring width-wise3
5/12
Siemens LV 56 · 2008
Busbar System
5
Compact busbar system
■
Technical specifications
Admissible rated current for copper busbars, for an ambient temperature of 35 °C according to DIN 43671
■
Description
Compact busbar systems are used for the distribution of currents up to 630A and rated short-time currents Icw upto 25 kA.
■
Configuration
Compact busbar systems, with pole centre distance of 50mm, can be used in conjunction with the rapid wiring assembly system for modular devices SIKclip.
For compact busbar systems, with pole centre distance of 60mm, a wide range of adapters for SIRIUS, SENTRON 3VL is available together with many other accessories.
■
Selection and ordering data
No. of busbars Dimensions[mm]
Rated current at a temperature of Holder spacing [mm]
65 °C 85 °C 105 °C I
cw
= 5 kA I
cw
= 10 kA I
cw
= 15 kA I
cw
= 20 kA I
cw
= 25 kA
1 15
×
5 222 293 349 600 400
1 20
×
5 274 362 430 600 600 400
1 30
×
5 379 500 595 600 600 450 352 300
1 30
×
10 573 756 900 600 600 400 300 250
Description No. of poles
Busbar dimensions mm
×
mmBusbar shape Arrangement Ordering code UI
Compact busbar system, 50mm pole centre distance
Busbar holder 4 15
×
5, 20
×
5, 30
×
5 Rectangular non-cascaded
8GF5762
1
Busbar holder 4 30
×
10 Rectangular non-cascaded
8GF5763
1
Busbar holder 4 15
×
5, 20
×
5, 30
×
5 Rectangular cascaded
8GF5760
1
Busbar holder 4 30
×
10 Rectangular cascaded
8GF5761
1
Compact busbar holder system, 60mm pole centre distance
Busbar holder 3 15
×
5, 20
×
5, 30
×
5, 30
×
10 Rectangular non-cascaded
8US1923-3AA01
1
Busbar holder 4 15
×
5, 20
×
5, 30
×
5, 30
×
10 Rectangular non-cascaded
8US1923-4AA00
1
Busbar holder end cover 3 – – –
8US1922-1AC00
1
Busbar holder end cover 4 – – –
8US1922-1AB00
1
Busbar cover section – 20
×
5, 30
×
5 Rectangular –
8US1922-2AA00
1
Busbar cover section – 20
×
10, 30
×
10 Rectangular –
8US1922-0BA00
1
02
04
80
20
49
Bild
5-9
BU
S 1
Bild
5-9
BU
S 2
Bild 5-9 BUS 3
5/13Siemens LV 56 · 2008
Busbar System
5
■ Selection and ordering data
Dimensionsmm × mm
Threading Current A
∆ TK
Lengthmm
Ordering code UI
Rigid busbar, perforated, with threading 15 × 5 M6 – – 2000 8GF5751 1
20 × 5 M6 – – 2000 8GF5737 1
30 × 5 M6 – – 2000 8GF5742 1
Rigid busbar, perforated 40 × 5 for M10 – – 2000 8PQ4000-0BA81 1
60 × 5 for M10 – – 1750 8PQ4000-1BA05 1
80 × 5 for M10 – – 2000 8PQ4000-1BA06 1
100 × 5 for M10 – – 2000 8PQ4000-1BA07 1
30 × 10 for M10 – – 2000 8GF5752 1
40 × 10 for M10 – – 2000 8PQ4000-0BA24 1
Rigid busbar 20 × 5 – – – 2000 8PQ4000-0BA83 1
30 × 5 – – – 2000 8PQ4000-0BA85 1
40 × 5 – – – 2000 8PQ4000-0BA80 1
15 × 10 – – – 2000 8PQ4000-1BA04 1
20 × 10 – – – 2000 8PQ4000-0BA84 1
30 × 10 – – – 2000 8PQ4000-0BA86 1
40 × 10 – – – 2000 8PQ4000-0BA17 1
50 × 10 – – – 2000 8PQ4000-0BA18 1
60 × 10 – – – 2000 8PQ4000-0BA87 1
80 × 10 – – – 2000 8PQ4000-0BA88 1
100 × 10 – – – 2000 8PQ4000-1BA00 1
120 × 10 – – – 2000 8PQ4000-1BA01 1
PVC insulated flexible busbar 13 × 3 × 0,5 – 160 20 2000 8GF5680 1
13 × 3 × 0,5 – 160 40 2000 8GF5686 1
20 × 5 × 1 – 250 20 2000 8GF5681 1
16 × 4 × 0,8 – 250 40 2000 8GF5687 1
32 × 5 × 1 – 400 20 2000 8GF5682 1
24 × 4 × 1 – 400 40 2000 8GF5688 1
40 × 8 × 1 – 630 20 2000 8GF5683 1
40 × 5 × 1 – 630 40 2000 8GF5690 1
40 × 10 × 1 – 800 30 2000 8PQ4000-1BA03 1
40 × 10 × 1 – 1000 40 2000 8PQ4000-1BA03 1
40 × 10 × 1 – 1250 50 2000 8PQ4000-1BA03 1
50 × 10 × 1 – 1250 20 2000 8PQ4000-1BA02 1
Rigid busbar, H shaped 30 × 30 – – – 1610 8PQ4000-0BA27 4
40 × 30 – – – 1610 8PQ4000-0BA26 4
01
67
90
16
79
01
67
80
16
80
01
67
7
Copper bars
5/14 Siemens LV 56 · 2008
Busbar System
5
■ DescriptionTo ensure a reliable connection of the copper busbars, it is important to select quality fasteners, of the right size, suitable and appropriately treated for the task.
The table below provides an overview of the various copper busbars - fasteners combination options, so as to facilitate selection and ordering.
■ ConfigurationThe stated quantity of fasteners applies to a 4-pole arrangement.
Rules for the calculation of the screw length for different busbar dimensions:– Length of screw with M8 threading = busbars profile + 15 mm– Length of screw with M10, M12 threading = busbars profile +
20 mm
■ Selection and ordering data
Profile Dimensionsmm × mm
Quan-tity
Ordering code Description
Main busbar systems with 2 bars per phase Connection from main busbars to:
Cascaded vertical busbars
Profiled busbar 30 × 30, 40 × 30 4 8PQ9500-0BA14 DIN 603 - M10x35 non-cascaded square screw 8 8PQ9500-0BA01 M10x25 T-head screw 12 8PQ9500-0BA60 DIN 6796 10 clamping washer12 8PQ9500-0BA05 Hexagonal nut ISO 4032 M10
Rectangular busbar 2 × 30 × 10 4 8PQ9500-0BA14 DIN 603 - M10x35 non-cascaded square screw 8 8PQ9500-1BA36 DIN 603 - M10x55 non-cascaded square screw 8 8PQ9400-0BA02 Rail clamp12 8PQ9500-0BA60 DIN 6796 - 10 clamping washer 12 8PQ9500-0BA05 ISO 4032 - M10 hexagonal nut
Rectangular busbar 2 × 40 × 10 4 8PQ9500-0BA14 DIN 603 - M10x35 non-cascaded square screw 8 8PQ9500-1BA25 DIN 603 - M10x65 non-cascaded square screw 8 8PQ9400-0BA02 Rail clamp12 8PQ9500-0BA60 DIN 6796 - 10 clamping washer 12 8PQ9500-0BA05 ISO 4032 - M10 hexagonal nut
Non-cascaded vertical busbars
Rectangular busbar 2 × 20 × 10, 2 × 40 × 10 12 8PQ9500-0BA14 DIN 603 - M10x35 non-cascaded square screw 12 8PQ9500-0BA60 DIN 6796 - 10 clamping washer 12 8PQ9500-0BA05 ISO 4032 - M10 hexagonal nut
Rectangular busbar 4 × 40 × 10, 4 × 50 × 10 8 8PQ9500-0BA14 DIN 603 - M10x35 non-cascaded square screw 8 8PQ9500-0BA16 DIN 603 - M10x45 non-cascaded square screw 16 8PQ9500-0BA60 DIN 6796 - 10 clamping washer 16 8PQ9500-0BA05 ISO 4032 - M10 hexagonal nut
Connection be-tween cubicle and main busbars
L1...3, N (PEN) Rectangular busbar 2 × 20 × 10, 2 × 30 × 10 8 8PQ9500-0BA16 DIN 603 - M10x45 non-cascaded square screw 8 8PQ9500-0BA60 DIN 6796 - 10 clamping washer 8 8PQ9500-0BA05 ISO 4032 - M10 hexagonal nut
Connection be-tween main bus-bar PEN ands cubicle
PEN (per cubicle) 2 8PQ9500-0BA34 DIN7500 - M6x10 self-tapping screw 1 8PQ9500-0BA14 DIN 603 - M10x35 non-cascaded square screw 1 8PQ9500-0BA60 DIN 6796 - 10 clamping washer 1 8PQ9500-0BA05 ISO 4032 - M10 hexagonal nut
Main busbar systems with 4 bars per phase Connection from main busbars to:
Cascaded vertical busbars
Profiled busbar 30 × 30, 40 × 30 4 8PQ9500-0BA16 DIN 603 - M10x45 non-cascaded square screw 8 8PQ9500-0BA01 M10x25 T-head screw 8 8PQ9400-0BA02 Rail clamp12 8PQ9500-0BA60 DIN 6796 10 clamping washer12 8PQ9500-0BA05 Hexagonal nut ISO 4032 M10
Rectangular busbar 2 × 30 × 10 4 8PQ9500-0BA16 DIN 603 - M10x45 non-cascaded square screw 8 8PQ9500-1BA36 DIN 603 - M10x55 non-cascaded square screw 8 8PQ9400-0BA02 Rail clamp12 8PQ9500-0BA60 DIN 6796 - 10 clamping washer 12 8PQ9500-0BA05 ISO 4032 - M10 hexagonal nut
Rectangular busbar 2 × 40 × 10 4 8PQ9500-0BA16 DIN 603 - M10x45 non-cascaded square screw 8 8PQ9500-1BA25 DIN 603 - M10x65 non-cascaded square screw12 8PQ9500-0BA60 DIN 6796 - 10 clamping washer 12 8PQ9500-0BA05 ISO 4032 - M10 hexagonal nut
Non-cascaded vertical busbars
Rectangular busbar 2 × 20 × 10, 2 × 40 × 10 12 8PQ9500-0BA16 DIN 603 - M10x45 non-cascaded square screw 12 8PQ9500-0BA60 DIN 6796 - 10 clamping washer 12 8PQ9500-0BA05 ISO 4032 - M10 hexagonal nut
Rectangular busbar 4 × 40 × 10, 4 × 50 × 10 16 8PQ9500-0BA16 DIN 603 - M10x45 non-cascaded square screw16 8PQ9500-0BA60 DIN 6796 - 10 clamping washer 16 8PQ9500-0BA05 ISO 4032 - M10 hexagonal nut
Connection be-tween cubicle and main busbars
L1...3, N (PEN) Rectangular busbar 4 × 20 × 10, 4 × 30 × 10 8 8PQ9500-0BA16 DIN 603 - M10x45 non-cascaded square screw 8 8PQ9500-0BA60 DIN 6796 - 10 clamping washer 8 8PQ9500-0BA05 ISO 4032 - M10 hexagonal nut
Rectangular busbar 4 × 40 × 10, 4 × 50 × 10 16 8PQ9500-0BA16 DIN 603 - M10x45 non-cascaded square screw16 8PQ9500-0BA60 DIN 6796 - 10 clamping washer16 8PQ9500-0BA05 ISO 4032 - M10 hexagonal nut
Connection be-tween main bus-bar PEN and cubicle
PEN (per cubicle) 2 8PQ9500-0BA34 DIN7500 - M6x10 self-tapping screw 1 8PQ9500-0BA16 DIN 603 - M10x45 non-cascaded square screw 1 8PQ9500-0BA60 DIN 6796 - 10 clamping washer 1 8PQ9500-0BA05 ISO 4032 - M10 hexagonal nut
Fasteners for connections between copper busbars
Siemens LV 56 · 2008
6
Assembly Kits for Switching Devices
6/2 General Data
6/3 Assembly kit for SENTRON 3WL circuit breakers
6/9 Assembly kit for SENTRON 3VL moulded case circuit breakers
6/20 Assembly kit for SENTRON 3VT moulded case circuit breakers
6/23 Assembly kit for SENTRON 3K disconnectors
6/26 Assembly kit for in-line fuse switch disconnectors SENTRON 3NJ4
6/29 Assembly kit for in-line fuseswitch disconnectorsSENTRON 3NJ6
6/32 Assembly kit for modular installation devices
6/2
Assembly Kits for Switching Devices
Siemens LV 56 · 2008
6
General Data
■
Overview
3
1
4
2
1 Assembly kit for SENTRON 3WLcircuit breakers
2 DIN rail for BETA modular devices
3 Assembly kit for SENTRON 3VLcase circuit breakers, horizontal intallation
4 Assembly kit for SENTRON 3VLcase circuit breakers, vertical installation
01
69
4
6/3
Siemens LV 56 · 2008
Assembly Kits for Switching Devices
6
Assembly kit for SENTRON 3WLcircuit breakers
■
Overview
3
1
4
2
1 Fixed part for draw-out version
2 Front attachments, flanged, horizontal, vertical
3 Switch position indicator contacts
4 Grounding contact
58
9
1110
76
5 Protective louvers
12
13
14
15
16
17
18
2519
20
21
22
23
24
6 PROFIBUS COM 15 communication module
7 CubicleBUS external modules
8 Auxiliary disconnectors, closing solenoid
9 Connector system for auxiliary units
10 Auxiliary contact modules
11 Front frame
12 Support for locking devices
13 Clear cover
14 Emergency stop button, locking key
15 Motorised mechanism
16 Operation counter
17 Breaker Status Sensor (BSS)
18 Electronic overcurrent release (ETU)
19 Reset solenoid
20 BDA (Breaker Data Adapter) module
21 4-line LCD display
22 Earth fault protection module
23 Rating Plug
24 Measuring function module
25 SENTRON WL circuit breaker
6/4
Assembly Kits for Switching Devices
Siemens LV 56 · 2008
6
Assembly kit for SENTRON 3WL circuit breakers
■
Technical specifications
1) Size II with
I
n max
≤ 2500 A.2) Size II with
I
n max
≤ 3200 A.
For further information, see the technical documents on SENTRON 3WL
Switching capacity
Size I II
Type 3WL11 3WL12
Switching capacity class N S N S H
Rated operating voltage
U
e
up to AC 415 V
I
cu
kA 55 66 66 80 100
I
cs
kA 55 66 66 80 100
I
cm
kA 121 145 145 176 220
Rated operating voltage
U
e
up to AC 500 V
I
cu
kA 55 66 66 80 100
I
cs
kA 55 66 66 80 100
I
cm
kA 112 145 145 176 220
Rated operating voltage
U
e
up to AC 690 V
I
cu
kA 42 50 50 75 85
I
cs
kA 42 50 50 75 85
I
cm
kA 88 105 105 165 187
Rated operating voltage
U
e
up to AC 1000 V
I
cu
kA – – – – 45
I
cs
kA – – – – 45
I
cm
kA – – – – 95
Rated short-time current
I
cw
of circuit breaker
Size I II
Type 3WL11 3WL12
Switching capacity class N S N S H
0,5 s kA 50 66 66 80 100
1 s kA 42 50 55 66 80
2 s kA 29,5 35 39 46 50
1)
/56
2)
3 s kA 24 29 32 37 40
1)
/50
2)
Rated short-circuit current
I
cc
of circuit breaker
Size I II
Type 3WL11 3WL12
Switching capacity class N S N S H
up to AC 500 V kA 50 66 66 80 100
up to AC 690 V kA 42 50 50 75 85
Size I II II
Type up to3WL11 10
3WL11 12 3WL11 16 3WL12 08 3WL12 10 3WL12 12 3WL12 16 3WL12 20 3WL12 25 3WL12 32
Minimum phase size
Busbars, Cu, piece 1
×
2
×
2
×
1
×
1
×
2
×
2
×
3
×
2
×
3
×
bare mm
2
60
×
10 40
×
10 50
×
10 50
×
10 60
×
10 40
×
10 50
×
10 50
×
10 100
×
10 100
×
10
Busbars, Cu piece 1
×
2
×
2
×
1
×
1
×
2
×
2
×
3
×
2
×
3
×
insulated, black mm
2
60
×
10 40
×
10 50
×
10 50
×
10 60
×
10 40
×
10 50
×
10 50
×
10 100
×
10 100
×
10
6/5
Siemens LV 56 · 2008
Assembly Kits for Switching Devices
6
Assembly kit for SENTRON 3WLcircuit breakers
■
Description
The assembly kit for SENTRON 3WL circuit breakers is made up of: • Mounting plate• Crossbars • Cover with cut-out and fast closing screws (designed for the
installation of the Sentron 3WL with cover frame) • Separation partition • Fasteners
The horizontal plate is suitable for the installation of circuit breakers, in fixed and draw out versions of different sizes. Horizontal separation ensures the required arcing spaces.
■
Configuration
The assembly kits for Sentron 3WL circuit breakers are suitable for currents of up to 3200 A.
The Sentron 3WL 1240 circuit breaker can be installed only in 800mm deep cubicles.
The assembly kit for Sentron 3WL circuit breakers can be installed only in 600mm and 800mm deep cubicles.
The cover has a cut-out to fit the relative frame 3WL 9111-0AP01-0AA0.
■
Selection and ordering data
■
Description
The support kit consists of a strip in fibreglass reinforced plastic sized 25x25mm and the relative fasteners to secure it to the cubicle or to the side upright.
■
Configuration
The distance between the circuit breaker terminal bar and the support and the distance between two supports is
≤
100mm.
■
Selection and ordering data
Size No. of poles Widthmm
Module height mm
Mounting plate SENTRON 3WL
Cover SENTRON 3WL
Assembly kit for Sentron 3WL, in fixed and draw out versions
BG I, BG II 3 600 550
8PQ6000-3BA31 8PQ2055-6BA05
BG I 4 600 550
8PQ6000-3BA31 8PQ2055-6BA07
BG I 3/4 800 550
8PQ6000-3BA32 8PQ2055-8BA04
BG II 3 800 550
8PQ6000-3BA32 8PQ2055-8BA07
BG II 4 800 550
8PQ6000-3BA32 8PQ2055-8BA05
02
05
0
02
05
1
Size No. of poles Width mm
Support Ordering code
UI
Support for Sentron 3WL, in fixed and draw out versions
BG I 3/4 600
8PQ6000-4BA35
4
BG II 3 600
8PQ6000-4BA36
4
BG I 3/4 800
8PQ6000-4BA37
4
BG II 3/4 800
8PQ6000-4BA38
4
02
05
7
6/6
Assembly Kits for Switching Devices
Siemens LV 56 · 2008
6
Assembly kit for SENTRON 3WL circuit breakers
■
Description
The support kit is made up of crossbars, corner pieces and the fasteners to secure the support to the structure or the side upright.
■
Configuration
For the arrangement of supports in standard position in the SIVACON S4 system, see chapter 11 “Dimensions”.The connection of distribution busbars is not included in the kit. The busbars must be mounted by the board installation technician.
■
Selection and ordering data
Size No. of poles Widthmm
Support Ordering code
UI
Support for busbar connection kit for Sentron 3WL, in fixed and draw out versions
BG I 3,4 600
8PQ3000-1BA70
1
BG II 3 600
8PQ3000-1BA70
1
BG I, BG II 3,4 800
8PQ3000-1BA71
1
Support busway connection SIVACON 8PS
NSE
0_0
20
58
02
21
1
6/7
Siemens LV 56 · 2008
Assembly Kits for Switching Devices
6
Assembly kit for SENTRON 3WLcircuit breakers
■
Description
The connections to SIVACON 8PS busways are optimised for the connection of Sentron 3WL circuit breakers in the SIVACON S4 system.
■
Configuration
It is important to select the correct combination of circuit breaker, busway connection and busway.
■
Selection and ordering data
Busway connection Ordering code
Conductor configuration
Suitable for busways In [A]
Suitable for busways In [A]
Suitable for busways In [A]
Sentron 3WL GR I
BVP:660299 100% PEN LDA3423(5)-... 1600
LDA2423(5)-... 1250
LDA1423(5)-... 1100
BVP:660300 100% N 100% PE LDA3623(5)-... 1600
LDA2623(5)-... 1250
LDA1623(5)-... 1100
BVP:660301 100% PEN LDA4423(5)-... 2000
– –
BVP:660302 100% N 100% PE LDA2623(5)-... 2000
– –
Sentron 3WL GR II
BVP:660303 100% PEN LDA3423(5)-... 2600
LDA2423(5)-... 2000
–
BVP:660304 100% N 100% PE LDA3623(5)-... 2600
LDA2623(5)-... 2000
–
BVP:660305 50% PEN LDA6413(5)-... 3000
LDA5413(5)-... 2500
LDA4413(5)-... 2000
BVP:660306 100% PEN LDA6423(5)-... 3000
LDA5423(5)-... 2500
LDA4423(5)-... 2000
BVP:660307 50% N 50% PE LDA6613(5)-... 3000
LDA5613(5)-... 2500
LDA4613(5)-... 2000
BVP:660308 100% N 50% PE LDA6623(5)-... 3000
LDA5623(5)-... 2500
LDA4623(5)-... 2000
BVP:660309 50% PEN LDA6413(5)-... 3400
– –
BVP:660310 100% PEN LDA6423(5)-... 3400
– –
BVP:660311 50% N 50% PE LDA6613(5)-... 3400
– –
BVP:660312 100% N 50% PE LDA6623(5)-... 3400
– –
Buswayconnection Ordering code
Conductor configuration
Suitable for busways In [A]
Suitable for busways In [A]
Suitable for busways In [A]
Suitable for busways In [A]
Suitable for busways In [A]
Sentron 3WL GR I
BVP:660321 100% PEN LXC0341-... 1400 LXC0141-... 1000 LXA0141-... 800 – –
BVP:660322 100% N 100% PE LXC0351-... 1400 LXC0151-... 1000 LXA0151-... 800 – –
BVP:660323 100% PEN LXA0541-... 1600 LXC0441-... 1600 LXA0441-... 1250 LXC0241-... 1250 LXA0241-... 1000
BVP:660324 100% N 100% PE LXA0551-... 1600 LXC0451-... 1600 LXA0451-... 1250 LXC0251-... 1250 LXA0251-... 1000
Sentron 3WL GR II
BVP:660325 100% PEN LXA0641-... 2000 LXC0541-... 2000 – – –
BVP:660326 100% N 100% PE LXA0651-... 2000 LXC0551-... 2000 – – –
BVP:660327 100% PEN LXC0641-... 2500 – – – –
BVP:660328 100% N 100% PE LXC0651-... 2500 – – – –
BVP:660329 100% PEN LXA0741-... 2500 – – – –
BVP:660330 100% N 100% PE LXA0751-... 2500 – – – –
BVP:660331 100% PEN LXC0741-... 3200 – – – –
BVP:660332 100% N 100% PE LXC0751-... 3200 – – – –
BVP:660333 100% PEN LXA0841-... 3200 – – – –
BVP:660334 100% N 100% PE LXA0851-... 3200 – – – –
6/8
Assembly Kits for Switching Devices
Siemens LV 56 · 2008
6
Assembly kit for SENTRON 3WL circuit breakers
■
Description
The prefabricated Cu busbar kit for Sentron 3WL circuit breakers is made up of: • Crossbars • Support• Reinforcement • Copper busbars • Protective isolation shield • Fasteners
With the cable entry variants and connection to the vertical distribution busbars variants, the system offers connection kits type tested in terms of CT mounting and number of connection points, in cascaded form, for the respective circuit breaker rated currents. Through the combination of variants it is possible to achieve functions such as incomer, outgoing and coupler.
■
Configuration
The Cu connecting busbar kit for Sentron 3WL circuit breakers going to the cable connection system occupies the heights of the module specified above or below the circuit breaker.
To be able to anchor, bend and connect the cables it is necessary to leave enough space for the assembly operations.
Construction of connecting busbars for Sentron 3WL circuit breakers with horizontal rear terminal bars for fixed versions.
Construction of connecting busbars for Sentron 3WL circuit breakers with flanged terminal bars for draw out versions.
■
Selection and ordering data
Module height
Size Cur-rent
No. of poles
Version Widthmm
above the breaker mm
below the breaker mm
Ordering code UI
Kit of prefabricated busbars for Sentron 3WL for connection to the vertical bars, cascaded
BG I 1600A 3/4 Fixed 600 250 300
8PQ6000-0BA34
1
BG I 1600A 3/4 Draw out 600 250 300
8PQ6000-0BA33
1
BG I 1600A 3/4 Fixed 800 250 300
8PQ6000-2BA45
1
BG I 1600A 3/4 Draw out 800 250 300
8PQ6000-2BA44
1
BG II 2000A 3/4 Fixed 800 300 350
8PQ6000-0BA41
1
BG II 2000A 3/4 Draw out 800 300 350
8PQ6000-0BA40
1
BG II 3200A 3/4 Fixed 800 300 350
8PQ6000-0BA47
1
BG II 3200A 3/4 Draw out 800 300 350
8PQ6000-0BA46
1
Kit of prefabricated busbars for Sentron 3WL for connection to the connecting cables
BG I 1600A 3/4 Fixed 600 200 250
8PQ6000-0BA52
1BG I 1600A 3/4 Draw out 600 200 250
8PQ6000-0BA51
1BG I 1600A 3/4 Fixed 800 200 250
8PQ6000-2BA47
1BG I 1600A 3/4 Draw out 800 200 250
8PQ6000-2BA46
1BG II 2000A 3/4 Fixed 800 350 400
8PQ6000-0BA58
1BG II 2000A 3/4 Draw out 800 350 400
8PQ6000-0BA57
1BG II 3200A 3/4 Fixed 800 350 400
8PQ6000-0BA65
1BG II 3200A 3/4 Draw out 800 350 400
8PQ6000-0BA64
1
Sentron 3WL with horizontal rear terminal bars, for fixed version Sentron 3WL with flanges, for draw out version
02
05
4
02
05
5
6/9
Siemens LV 56 · 2008
Assembly Kits for Switching Devices
6
Assembly kit for SENTRON 3VLmoulded case circuit breakers
■
Overview
3
1
4
2
1 Fixed part for plugin version
2 Side panels for draw out version
3 Phase separators
4 Front terminal bars, divergent
5
89
11
10
7 6
5 Front terminal bars, straight
12
13
14
15
161718
19
20
21
6 Terminals for Al/Cu cables
7 Terminals for copper cables and busbars
8 Terminal cover, extended
9 Terminal cover, standard
10 Front frame
11 Motorised operating mechanismwith spring accumulator
12 Direct rotary operating mechanism
13 Door locking rotary operating mechanism
14 SENTRON VL circuit breaker
15 Internal accessories
16 Electronic overcurrent release
17 Thermal/magnetic overcurrent release
18 DI module - RCD
19 Rear connections - flat and round
20 COM 10 PROFIBUS-DP communication module
21 Handheld testing device
10
3
45
89
76
6/10
Assembly Kits for Switching Devices
Siemens LV 56 · 2008
6
■
Technical specifications
Type VL 160X
3VL1
VL 160
3VL2
VL 250
3VL3
VL 400
3VL4
VL 630
3VL5
VL 800
3VL6
VL 1250
3VL7
VL 1600
3VL8
Connection dimensions and types for main circuits
Box terminals
Single- or multi-wire cable only copper mm2 2,5-95 2,5-95 25-185 50-300 – – – –
Flexible wire with sleeve connector mm2 2,5-50 2,5-50 25-120 50-240 – – – –
Busbar mm 12 × 10 12 × 10 17 × 10 25 × 10 – – – –
Clamp for flexible bar mm – – – – 2 pieces6 × 32
– – –
Power supply terminals with multiple cables
Single- or multi-wire cable copper or Al mm2 16-70 16-70 25-185 50-300 – – – –
Flexible wire with sleeve connector mm2 10-50 10-50 25-120 50-240 – – – –
Multiple feed-in terminal
Power supply terminals for cables copper or Al mm2 – – – 2 pieces50-120
2 pieces50-240
3 pieces50-240
4 pieces50-240
–
Flexible wire with end terminal mm2 – – – 2 pieces50-95
2 pieces50-185
3 pieces50-185
4 pieces50-185
–
Direct busbar connection copper or Al mm 17 × 7 22 × 7 24 × 7 32 × 10 40 × 10 2 × 40 × 10 2 × 50 × 10 3 × 60 × 10
Screw type for screwed connection M 5 M 5 M 8 M 8 M 6 M 8 M 8 –
Assembly kit for SENTRON 3VL moulded case circuit breakers
6/11
Siemens LV 56 · 2008
Assembly Kits for Switching Devices
6
Assembly kit for SENTRON 3VL mouldedcase circuit breaker, horizontal installation
■
Description
The equipment support assembly kit contains a deep mounting plate for front and rear terminal bars and fastening crossbars. For installation on the front frame, choice of covers includes versions suitable for direct, motorised and rotary front operating mechanisms. The covers are secured to the front frame by means of fast closing screws (1/4 of a turn). Hinges to be fitted to the individual covers are available as an option. The
Link-N
kit includes support, cover and fasteners. In the 3- and 4-pole moulded case circuit breaker combination this kit provides the internal separation for a branch unit.
■
Configuration
For horizontal installation and front connections, extended terminal covers have to be ordered. A combination of front frame and covers with modular doors in a cubicle is not possible.
■
Selection and ordering data
■
Description
The prefabricated Cu busbar kit for Sentron 3VL moulded case circuit breakers for horizontal installation is made up of: • Crossbars • Support• Plastic reinforcement • Copper busbars • Protective isolation shield • Fastening screws With the cable entry variants and connection to the vertical distribution busbars variants, the system offers connection kits type-tested in terms of CT mounting and number of connection points to the busbars, in cascaded form, for the respective circuit breaker rated currents.
■
Configuration
The height of the connecting busbars kit matches the type of circuit breaker. The connecting busbar kit is suitable for branch units without differential module. In addition to the copper busbars and the cover, the “connecting busbar” kit for Sentron VL circuit breakers for connection to the cables contains lateral partitions with connecting terminals. When fitting connecting busbar kit for Sentron VL circuit breakers for connection to the cascaded vertical busbars in a 600 mm cubicle, the vertical distribution busbar system must be housed in the same cubicle (800 mm cubicle with riser compartment 600 + 200 mm).
■
Selection and ordering data
Circuit breaker
No. of poles
Connection Cover with cut-out for type of op. mechanism
Heightmm
Widthmm
Depth
1
mmMax no. of circuit breakers
Link-N support Equipment mounting plate
Cover
Sentron 3VL moulded case circuit breakers, fixed, horizontal installation
VL 160X 3 front, rear
Direct, mot. rotary front mech.
150 600 400 1
8PQ6000-2BA74 8PQ2015-6BA03
VL 160X 4 front, rear
Direct, mot. rotary front mech.
200 600 400 1
8PQ6000-3BA52 8PQ6000-2BA80 8PQ2020-6BA04
VL 160/250 3 front, rear
Direct, mot. rotary front mech.
150 600 400 1
8PQ6000-3BA13 8PQ2015-6BA03
VL 160/250 4 front, rear
Direct, mot. rotary front mech.
200 600 400 1
8PQ6000-3BA52 8PQ6000-3BA18 8PQ2020-6BA04
VL 400 3 front, rear
Direct, mot. rotary front mech.
200 600 400 1
8PQ6000-2BA84 8PQ2020-6BA06
VL 400 4 front, rear
Direct, mot. rotary front mech.
250 600 400 1
8PQ6000-3BA53 8PQ6000-2BA87 8PQ2025-6BA02
VL 630 3 front, rear
Direct, mot. rotary front mech.
300 600 400 1
8PQ6000-3BA01 8PQ2030-6BA03
VL 630 4 front, rear
Direct, mot. rotary front mech.
350 600 400 1
8PQ6000-3BA54 8PQ6000-3BA10 8PQ2035-6BA04
VL 800 3 rear
Direct, mot. rotary front mech.
300 600 400 1
8PQ6000-3BA08 8PQ2030-6BA02
VL 800 4 rear
Direct, mot. rotary front mech.
350 600 400 1
8PQ6000-4BA16 8PQ2035-6BA05
02
06
4
02
05
9
02
06
0
Circuit breaker
No. of poles
Version Ad hoc covers for type of op. mech.
Max. no. of switches
Height of module mm
Widthmm
Ordering code UI
Kit of connecting bars for Sentron 3VL for connection to cascaded vertical distribution bars
VL 250 3 fixed direct 1 150 600
8PQ6000-1BA63
1
VL 250 4 fixed direct 1 200 600
8PQ6000-1BA64
1
VL 400 3 fixed direct 1 200 600
8PQ6000-1BA65
1
VL 400 4 fixed direct 1 250 600
8PQ6000-1BA66
1
VL 630 3 fixed direct 1 300 600
8PQ6000-1BA67
1
VL 630 4 fixed direct 1 350 600
8PQ6000-1BA68
1
Kit of connecting bars for Sentron 3VL for connection to the cables
VL 250 3 fixed direct 1 150 600
8PQ6000-1BA70
1
VL 250 4 fixed direct 1 200 600
8PQ6000-1BA71
1
VL 400 3 fixed direct 1 200 600
8PQ6000-1BA72
1
VL 400 4 fixed direct 1 250 600
8PQ6000-1BA73
1
VL 630 3 fixed direct 1 300 600
8PQ6000-1BA74
1
VL 630 4 fixed direct 1 350 600
8PQ6000-1BA75
1
01
65
20
16
53
1 minimum depth
6/12
Assembly Kits for Switching Devices
Siemens LV 56 · 2008
6
■ Description The equipment support assembly kit contains a deep mounting plate for front and rear terminal bars and fastening crossbars.
For installation on the front frame, choice of covers includes versions suitable for direct, motorised and rotary front operating mechanisms. The covers are secured to the front frame by means of fast closing screws (1/4 of a turn).
Hinges to be fitted to the individual covers are available as an option.
The Link-N kit includes support, cover and fasteners. In the 3- and 4-pole moulded case circuit breaker combination this kit provides for the internal separation for a branch unit.
■ Configuration For horizontal installation and front connections, extended terminal covers have to be ordered.
To improve the stability of the kits for VL 400 and 630 in plug-in version it is necessary to fit a reinforcement kit for each branch unit.
A combination of front frame and covers with modular doors in a cubicle is not possible.
■ Selection and ordering data
Circuit breaker
No. of poles
Connec-tion
Ad hoc cover for type of op. mech.
Height of module mm
Widthmm
Depthmm
Max. no. of circuit breakers
N-Link support Equipment mounting plate
Cover
Sentron 3VL moulded case circuit breakers, plug-in, for horizontal installation VL 160X 3 front, rear Direct, mot. rotary front mech. 150 600 400 1 8PQ6000-3BA24 8PQ2015-6BA03
VL 160X 4 front, rear Direct, mot. rotary front mech. 200 600 400 1 8PQ6000-3BA52 8PQ6000-3BA27 8PQ2020-6BA04
VL 160/250 3 front, rear Direct, mot. rotary front mech. 150 600 400 1 8PQ6000-3BA24 8PQ2015-6BA03
VL 160/250 4 front, rear Direct, mot. rotary front mech. 200 600 400 1 8PQ6000-3BA52 8PQ6000-3BA27 8PQ2020-6BA04
VL 400 3 front Direct, mot. rotary front mech. 200 600 400 1 8PQ6000-2BA84 8PQ2020-6BA06
VL 400 3 rear Direct, mot. rotary front mech. 200 600 600/800 1 8PQ6000-2BA84 8PQ2020-6BA06
VL 400 4 front Direct, mot. rotary front mech. 250 600 400 8PQ6000-3BA53 8PQ6000-2BA87 8PQ2025-6BA02
VL 400 4 rear Direct, mot. rotary front mech. 250 600 600/800 8PQ6000-3BA53 8PQ6000-2BA87 8PQ2025-6BA02
VL 630 3 front Direct, mot. rotary front mech. 300 600 400 1 8PQ6000-3BA01 8PQ2030-6BA03
VL 630 3 rear Direct, mot. rotary front mech. 300 600 600/800 1 8PQ6000-3BA01 8PQ2030-6BA03
VL 630 4 front Direct, mot. rotary front mech. 350 600 400 1 8PQ6000-3BA54 8PQ6000-3BA10 8PQ2035-6BA04
VL 630 4 rear Direct, mot. rotary front mech. 350 600 600/800 1 8PQ6000-3BA54 8PQ6000-3BA10 8PQ2035-6BA04
02
06
4
02
05
9
02
06
0
Assembly kit for SENTRON 3VL moulded case circuit breaker, for horizontal installation
1 Minimum depth
6/13
Siemens LV 56 · 2008
Assembly Kits for Switching Devices
6
Assembly kit for SENTRON 3VL mouldedcase circuit breaker, for horizontal installation
■
Description
The equipment support assembly kit contains a deep mounting plate for front and rear terminal bars and fastening crossbars. For installation on the front frame, choice of covers includes versions suitable for direct, motorised and rotary front operating mechanisms. The covers are secured to the front frame by means of fast closing screws (1/4 of a turn). Hinges to be fitted to the individual covers are available as an option. The
Link-N
kit includes support, cover and fasteners. In the 3- and 4-pole moulded case circuit breaker combination this kit provides for the internal separation for a branch unit.
■
Configuration
For horizontal installation and front connections, extended terminal covers have to be ordered. A combination of front frame and covers with modular doors in a cubicle is not possible.
■
Selection and ordering data
Circuit breaker
No. of poles
Connec-tion
Ad hoc cover for type of op. mech.
Height of module mm
Widthmm
Depth
1
mmMax. no. of circuit breakers
Equipment mounting plate
Cover
Sentron 3VL moulded case circuit breaker, draw out, for horizontal installation
VL 160/250 3/4
front, rear Direct, mot. rotary front mech.
250 600 400 1
8PQ6000-3BA27 8PQ2020-6BA21
VL 400 3/4
front, rear Direct, mot. rotary front mech.
300 600 400 1
8PQ6000-2BA87 8PQ2025-6BA11
VL 630 3
front, rear Direct, mot. rotary front mech.
300 600 400 1
8PQ6000-3BA01 8PQ2030-6BA17
VL 630 4
front, rear Direct, mot. rotary front mech.
350 600 400 1
8PQ6000-3BA10 8PQ2035-6BA17
02
05
9
02
14
0
Circuit breaker
No. of poles
Connec-tion
Ad hoc cover for type of op. mech.
Height of module mm
Widthmm
Depth
1
mmMax. no. of circuit breakers
Reinforcement
Reinforcement per Sentron 3VL circuit breaker kit, draw out, horizontal installation
VL 400 3/4 600 400 1
8PQ6000-4BA17
VL 630 3 600 400 1
8PQ6000-4BA20
VL 630 4 600 400 1
8PQ6000-4BA18
02
13
9
Circuit breaker
No. of poles
Connec-tion
Ad hoc cover for type of op. mech.
Height of module mm
Widthmm
Depth
1
mmMax. no. of circuit breakers
N-Link Equipment mounting plate
Cover
Sentron 3VL compact moulded case circuit breaker with RCD, with fixed mounting technology, mounted horizontally
VL 160X 3
front, rear Direct, mot. rotary front mech.
150 600 400 1
8PQ6000-2BA73 8PQ2015-6BA05
VL 160X 4
front, rear Direct, mot. rotary front mech.
200 600 400 1
8PQ6000-3BA52 8PQ6000-2BA78 8PQ2020-6BA08
VL 160/250 3
front Direct, mot. rotary front mech.
150 600 400 1
8PQ6000-3BA14 8PQ2015-6BA04
VL 160/250 4
rear Direct, mot. rotary front mech.
200 600 400 1
8PQ6000-3BA52 8PQ6000-3BA20 8PQ2020-6BA05
02
06
4
02
06
2
02
06
3
Circuit breaker
No. of poles
Connec-tion
Ad hoc cover for type of op. mech.
Height of module mm
Widthmm
Depth
1
mmMax. no. of circuit breakers
N-Link Equipment mounting plate
Cover
Sentron 3VL compact moulded case circuit breaker, with plug-in technology, mounted horizontally
VL 160X 3
front, rear Direct, mot. rotary front mech.
150 600 400 1
8PQ6000-2BA75 8PQ2015-6BA06
VL 160X 4
front, rear Direct, mot. rotary front mech.
200 600 400 1
8PQ6000-3BA52 8PQ6000-2BA81 8PQ2020-6BA07
VL 160/250 3
fron Direct, mot. rotary front mech.
150 600 400 1
8PQ6000-2BA75 8PQ2015-6BA04
VL 160/250 4
rear Direct, mot. rotary front mech.
200 600 400 1
8PQ6000-3BA52 8PQ6000-2BA81 8PQ2020-6BA05
02
06
4
02
06
2
02
06
3
1 Minimum depth
6/14
Assembly Kits for Switching Devices
Siemens LV 56 · 2008
6
Assembly kit for SENTRON 3VL moulded case circuit breaker, for horizontal installation
■ Description The equipment support assembly kit contains a deep mounting plate for front and rear terminal bars and fastening crossbars.
The modular doors kit with degree of protection IP4X with holes for the 8UC door locking mechanism contains a door, hinges, individual cover and fasteners.
The Link-N kit includes support, cover and fasteners. In the 3- and 4-pole moulded case circuit breaker combination this kit provides for the internal separation for a branch unit.
■ ConfigurationFor horizontal installation and front connections, extended terminal covers have to be ordered.
A combination of front frame and covers with modular doors in a cubicle is not possible.
For a degree of protection IP55 an upgrade to IP55 is available (see chapter 7, modular doors).
a Due to the length of the operating mechanism, an height 50mm module above the assembly kit should be provided for at the design stage.
■ Selection and ordering data
■ Selection and ordering data
Circuit breaker
No. of poles
Connec-tion
Ad hoc cover for type of op. mech.
Height of module mm
Widthmm
Depth1
mmMax. no. of circuit breakers
N-Link support Equipment mounting plate
Modular door
Sentron 3VL moulded case circuit breaker, fixed, for horizontal installation VL 160X 3 front, rear 8UC-door locking mech., Gr. 2 150 600 400 1 8PQ6000-2BA74 8PQ2015-6BA14VL 160X 4 front, rear 8UC-door locking mech., Gr. 2 200 600 400 1 8PQ6000-3BA52 8PQ6000-2BA80 8PQ2020-6BA16VL 160/250 3 front, rear 8UC-door locking mech., Gr. 2 150 600 400 1 8PQ6000-3BA13 8PQ2015-6BA14VL 160/250 4 front, rear 8UC-door locking mech., Gr. 2 200 600 400 1 8PQ6000-3BA52 8PQ6000-3BA18 8PQ2020-6BA16VL 400 a 3 front, rear 8UC-door locking mech., Gr. 2 200 600 400 1 8PQ6000-2BA84 8PQ2020-6BA20VL 400 4 front, rear 8UC-door locking mech., Gr. 3 250 600 400 1 8PQ6000-3BA53 8PQ6000-2BA87 8PQ2025-6BA10VL 630 3 front, rear 8UC-door locking mech., Gr. 3 300 600 400 1 8PQ6000-3BA01 8PQ2030-6BA15VL 630 4 front, rear 8UC-door locking mech., Gr. 3 350 600 400 1 8PQ6000-3BA54 8PQ6000-3BA10 8PQ2035-6BA15VL 800 3 rear 8UC-door locking mech., Gr. 3 300 600 400 1 8PQ6000-3BA08 8PQ2030-6BA16VL 800 4 rear 8UC-door locking mech., Gr. 3 350 600 400 1 8PQ6000-4BA16 8PQ2035-6BA16
02
06
4
02
05
9
02
06
1
Circuit breaker
No. of poles
Connec-tion
Ad hoc cover for type of op. mech.
Height of module mm
Widthmm
Depth1
mmMax. no. of circuit breakers
N-Link support Equipment mounting plate
Modular door
Sentron 3VL moulded case circuit breaker, plug-in, for horizontal installation VL 160X 3 front, rear 8UC-door locking mech., Gr. 2 150 600 400 1 8PQ6000-3BA24 8PQ2015-6BA14VL 160X 4 front, rear 8UC-door locking mech., Gr. 2 200 600 400 1 8PQ6000-3BA52 8PQ6000-3BA27 8PQ2020-6BA16VL 160/250 3 front, rear 8UC-door locking mech., Gr. 2 150 600 400 1 8PQ6000-3BA24 8PQ2015-6BA14VL 160/250 4 front, rear 8UC-door locking mech., Gr. 2 200 600 400 1 8PQ6000-3BA52 8PQ6000-3BA27 8PQ2020-6BA16VL 400 a 3 front, rear 8UC-door locking mech., Gr. 3 200 600 400 1 8PQ6000-2BA84 8PQ2020-6BA20VL 400 4 front, rear 8UC-door locking mech., Gr. 3 250 600 400 1 8PQ6000-3BA53 8PQ6000-2BA87 8PQ2025-6BA10VL 630 3 front, rear 8UC-door locking mech., Gr. 3 300 600 400 1 8PQ6000-3BA01 8PQ2030-6BA15VL 630 4 front, rear 8UC-door locking mech., Gr. 3 350 600 400 1 8PQ6000-3BA54 8PQ6000-3BA10 8PQ2035-6BA15
02
06
4
02
05
9
02
06
1
1 Minimum depth
6/15Siemens LV 56 · 2008
Assembly Kits for Switching Devices
6
Assembly kit for SENTRON 3VL mouldedcase circuit breaker, for horizontal installation
■ Description The equipment support assembly kit contains a deep mounting plate for front and rear terminal bars and fastening crossbars.
The modular doors kit with degree of protection IP4X with holes for the 8UC door locking mechanism contains a door, hinges, individual cover and fasteners.
The Link-N kit includes support, cover and fasteners. In the 3- and 4-pole moulded case circuit breaker combination this kit provides for the internal separation for a branch unit.
■ Configuration For horizontal installation and front connections, extended terminal covers have to be ordered.
A combination of front frame and covers with modular doors in a cubicle is not possible.
For a degree of protection IP55 an upgrade to IP55 is available (see chapter 7, modular doors).
■ Selection and ordering data
■ Selection and ordering data
Circuit breaker
No. of poles
Connec-tion
Ad hoc cover for type of op. mech.
Height of module mm
Widthmm
Depth1
mmMax. no. of circuit breakers
N-Link support Equipment mounting plate
Modular door
Sentron 3VL moulded case circuit breaker with differential module, fixed, for horizontal installation VL 160/250 3 front, rear 8UC-door locking mech., Gr. 2 150 600 400 1 8PQ6000-3BA14 8PQ2015-6BA16VL 160/250 4 front, rear 8UC-door locking mech., Gr. 2 200 600 400 1 8PQ6000-3BA52 8PQ6000-3BA20 8PQ2020-6BA17
02
06
4
02
06
2
02
06
1
Circuit breaker
No. of poles
Connec-tion
Ad hoc cover for type of op. mech.
Height of module mm
Widthmm
Depth1
mmMax. no. of circuit breakers
N-Link support Equipment mounting plate
Modular door
Sentron 3VL moulded case circuit breaker with differential module, plug-in, for horizontal installation VL 160/250 3 front, rear 8UC-door locking mech., Gr. 2 150 600 400 1 8PQ6000-2BA75 8PQ2015-6BA16VL 160/250 4 front, rear 8UC-door locking mech., Gr. 2 200 600 400 1 8PQ6000-3BA52 8PQ6000-2BA81 8PQ2020-6BA17
02
06
4
02
06
2
02
06
1
1 Minimum depth
6/16
Assembly Kits for Switching Devices
Siemens LV 56 · 2008
6
Assembly kit for SENTRON 3VL moulded case circuit breaker, for vertical installation
■ Description The equipment support assembly kit contains a deep mounting plate for front and rear terminal bars and fastening crossbars.
For installation on the front frame, choice of covers includes versions suitable for direct, motorised and rotary front operating mechanism. The covers are secured to the front frame by means of fast closing screws (1/4 of a turn).
Hinges to be fitted to the individual covers are available as an option.
The Link-N kit includes support, cover and fasteners. In the 3- and 4-pole moulded case circuit breaker combination this kit provides for the internal separation for a branch unit.
■ Configuration Shielding is provided for the motorised operating mechanism with spring accumulator.
For circuit breaker, base or rack and motorised operating mechanism combinations, take into due account the indications given in the dimensional drawings 11/15.
b For front terminal bars, two additional covers, height 100mm each, are required. Moreover, extended terminal covers have to be ordered for the respective circuit breaker.
■ Selection and ordering data
■ Selection and ordering data
Circuit breaker
No. of poles
Connec-tion
Ad hoc cover for type of op. mech.
Height of module mm
Widthmm
Depth1
mmMax. no. of circuit breakers
N-Link support Equipment mounting plate
Cover
Sentron 3VL moulded case circuit breaker, fixed, for vertical installation VL 160X 3 front, rear Direct, mot. rotary front mech. 350 600 400 1-4 8PQ6000-2BA76 8PQ2035-6BA02
VL 160X 4 front, rear Direct, mot. rotary front mech. 350 600 400 1-3 8PQ6000-2BA82 8PQ2035-6BA03
VL 160/250 3 front, rear Direct, mot. rotary front mech. 350 600 400 1-4 8PQ6000-3BA16 8PQ2035-6BA02
VL 160/250 4 front, rear Direct, mot. rotary front mech. 350 600 400 1-3 8PQ6000-3BA22 8PQ2035-6BA03
VL 400 b 3 front, rear Direct, mot. rotary front mech. 400 600 400 1-3 8PQ6000-2BA85 8PQ2040-6BA07
VL 400 b 4 front, rear Direct, mot. rotary front mech. 400 600 400 1-2 8PQ6000-2BA88 8PQ2040-6BA05
VL 630 b 3/4 front, rear Direct, mot. rotary front mech. 400 600 400 1 8PQ6000-3BA54 8PQ6000-3BA05 8PQ2040-6BA08
VL 630 b 3 front, rear Direct, mot. rotary front mech. 400 600 400 1-2 8PQ6000-3BA02 8PQ2040-6BA06
VL 160X 3 front, rear Direct, mot. rotary front mech. 350 800 400 1-5 8PQ6000-2BA77 8PQ2035-8BA02
VL 160X 4 front, rear Direct, mot. rotary front mech. 350 800 400 1-4 8PQ6000-2BA83 8PQ2035-8BA03
VL 160/250 3 front, rear Direct, mot. rotary front mech. 350 800 400 1-5 8PQ6000-3BA17 8PQ2035-8BA02
VL 160/250 4 front, rear Direct, mot. rotary front mech. 350 800 400 1-4 8PQ6000-3BA23 8PQ2035-8BA03
VL 400 b 3 front, rear Direct, mot. rotary front mech. 400 800 400 1-4 8PQ6000-2BA86 8PQ2040-8BA08
VL 400 b 4 front, rear Direct, mot. rotary front mech. 400 800 400 1-3 8PQ6000-3BA00 8PQ2040-8BA07
VL 630 b 3 front, rear Direct, mot. rotary front mech. 400 800 400 1-3 8PQ6000-3BA03 8PQ2040-8BA06
VL 630 b 4 front, rear Direct, mot. rotary front mech. 400 800 400 1-2 8PQ6000-3BA06 8PQ2040-8BA05
02
07
0 02
06
5
02
06
6
Circuit breaker
No. of poles
Connec-tion
Ad hoc cover for type of op. mech.
Height of module mm
Widthmm
Depth1
mmMax. no. of circuit breakers
N-Link support Equipment mounting plate
Cover
Sentron 3VL moulded case circuit breaker, fixed, for vertical installation VL 800 b 3/4 front, rear Direct, mot. rotary front mech. 600 600 400 1 8PQ6000-3BA55 8PQ6000-3BA07 8PQ2060-6BA02
VL 1250 b 3/4 front, rear Direct, mot. rotary front mech. 600 600 400 1 8PQ6000-3BA56 8PQ6000-3BA11 8PQ2060-6BA03
VL 1600 b 3/4 front, rear Direct, mot. rotary front mech. 700 600 400 1 8PQ6000-3BA56 8PQ6000-3BA12 8PQ2070-6BA01
02
07
0
02
14
1
02
06
6
1 Minimum depth
6/17Siemens LV 56 · 2008
Assembly Kits for Switching Devices
6
Assembly kit for SENTRON 3VL mouldedcase circuit breaker, for vertical installation
■ DescriptionThe equipment support assembly kit contains a deep mounting plate for front and rear terminal bars and fastening crossbars.
For installation on the front frame, choice of covers includes versions suitable for direct, motorised and rotary front operating mechanism. The covers are secured to the front frame by means of fast closing screws (1/4 of a turn).
Hinges to be fitted to the individual covers are available as an option.
The Link-N kit includes support, cover and fasteners. In the 3- and 4-pole moulded case circuit breaker combination this kit provides for the internal separation for a branch unit.
■ Configuration a For front terminal bars, two additional covers, H50mm each,
are required. Moreover, extended terminal covers have to be ordered for the respective circuit breaker.
b For front terminal bars, two additional covers, H100mm each, are required. Moreover, extended terminal covers have to be ordered for the respective circuit breaker.
Shielding is provided for the motorised operating mechanism with spring accumulator.
For circuit breaker, base or rack and motorised operating mechanism combinations, take into due account the indications given in the dimensional drawings 11/15.
■ Selection and ordering data
Circuit breaker
No. of poles
Connec-tion
Ad hoc cover for type of op. mech.
Height of module mm
Width mm
Depth1
mmMax. no. of circuit breakers
N-Link support Equipment mounting plate
Cover
Sentron 3VL moulded case circuit breaker, plug-in, for vertical installation VL 160X a 3 front, rear Direct, mot. rotary front mech. 350 600 400 1-4 8PQ6000-3BA25 8PQ2035-6BA02
VL 160X a 4 front, rear Direct, mot. rotary front mech. 350 600 400 1-3 8PQ6000-3BA28 8PQ2035-6BA03
VL 160/250 a 3 front, rear Direct, mot. rotary front mech. 350 600 400 1-4 8PQ6000-3BA25 8PQ2035-6BA02
VL 160/250 a 4 front, rear Direct, mot. rotary front mech. 350 600 400 1-3 8PQ6000-3BA28 8PQ2035-6BA03
VL 400 b 3 front, rear Direct, mot. rotary front mech. 400 600 400 1-3 8PQ6000-2BA85 8PQ2040-6BA07
VL 400 b 4 front, rear Direct, mot. rotary front mech. 400 600 400 1-2 8PQ6000-2BA88 8PQ2040-6BA05
VL 630 b 3/4 front, rear Direct, mot. rotary front mech. 400 600 400 1 8PQ6000-3BA54 8PQ6000-3BA05 8PQ2040-6BA08
VL 630 b 3 front, rear Direct, mot. rotary front mech. 400 600 400 1-2 8PQ6000-3BA02 8PQ2040-6BA06
VL 160X a 3 front, rear Direct, mot. rotary front mech. 350 800 400 1-5 8PQ6000-3BA26 8PQ2035-8BA02
VL 160X a 4 front, rear Direct, mot. rotary front mech. 350 800 400 1-4 8PQ6000-3BA30 8PQ2035-8BA03
VL 160/250 a 3 front, rear Direct, mot. rotary front mech. 350 800 400 1-5 8PQ6000-3BA26 8PQ2035-8BA02
VL 160/250 a 4 front, rear Direct, mot. rotary front mech. 350 800 400 1-4 8PQ6000-3BA30 8PQ2035-8BA03
VL 400 b 3 front, rear Direct, mot. rotary front mech. 400 800 400 1-4 8PQ6000-2BA86 8PQ2040-8BA08
VL 400 b 4 front, rear Direct, mot. rotary front mech. 400 800 400 1-3 8PQ6000-3BA00 8PQ2040-8BA07
VL 630 b 3 front, rear Direct, mot. rotary front mech. 400 800 400 1-3 8PQ6000-3BA03 8PQ2040-8BA06
VL 630 b 4 front, rear Direct, mot. rotary front mech. 400 800 400 1-2 8PQ6000-3BA06 8PQ2040-8BA05
02
07
0 02
06
5
02
06
6
1 Minimum depth
6/18
Assembly Kits for Switching Devices
Siemens LV 56 · 2008
6
■ Description The equipment support assembly kit contains a deep mounting plate for front and rear terminal bars and fastening crossbars.
For installation on the front frame, choice of covers includes versions suitable for direct, motorised and rotary front operating mechanism. The covers are secured to the front frame by means of fast closing screws (1/4 of a turn).
Hinges to be fitted to the individual covers are available as an option.
■ Configuration For circuit breaker, base or rack and motorised operating mechanism combinations, take into due account the indications given in the dimensional drawings 11/15.
a For front terminal bars, two additional covers, height 50mm each, are required. Moreover, extended terminal covers have to be ordered for the respective circuit breaker.
b For front terminal bars, two additional covers, height 100mm each, are required. Moreover, extended terminal covers have to be ordered for the respective circuit breaker.
■ Selection and ordering data
■ Selection and ordering data
Circuit breaker
No. of poles
Connection Ad hoc cover for type of op. mech.
Height of module mm
Widthmm
Depth1
mmMax. no. of circuit breakers
Equipment mounting plate
Cover
Sentron 3VL moulded case circuit breaker, draw out, for vertical installation VL 400 b 3/4 front, rear Direct, rotary front 400 600 400 1 8PQ6000-2BA88 8PQ2040-6BA17
VL 630 b 3/4 front, rear Direct, rotary front 400 600 400 1 8PQ6000-3BA05 8PQ2060-6BA12
VL 160/250 a 3 front, rear Direct, rotary front 350 800 400 1-3 8PQ6000-3BA26 8PQ2035-8BA08
VL 160/250 a 4 front, rear Direct, rotary front 350 800 400 1-2 8PQ6000-3BA30 8PQ2040-8BA15
VL 400 b 3 front, rear Direct, rotary front 400 800 400 1-2 8PQ6000-2BA86 8PQ2040-8BA16
VL 400 b 4 front, rear Direct, rotary front 400 800 400 1 8PQ6000-3BA00 8PQ2040-8BA17
VL 630 b 3/4 front, rear Direct, rotary front 400 800 400 1 8PQ6000-3BA06 8PQ2040-8BA20
Circuit breaker No. of poles
Connection Ad hoc cover for type of op. mech.
Height of module mm
Breitemm
Depth1
mmMax. no. of circuit breakers
Equipment mounting plate
Cover
Sentron 3VL moulded case circuit breaker, draw out, vertical installation VL 800 b 3 front, rear Direct 600 600 600/800 1 8PQ6000-3BA87 8PQ2060-6BA13
VL 800 b 4 front, rear Direct 600 600 600/800 1 8PQ6000-3BA88 8PQ2060-6BA14
VL 1250/1600 b 3 front, rear Direct 650 600 600/800 1 8PQ6000-4BA00 8PQ2065-6BA05
VL 1250/1600 b 4 front, rear Direct 650 600 600/800 1 8PQ6000-4BA01 8PQ2065-6BA06
02
06
5
02
06
7
02
06
8
02
06
9
Assembly kit for SENTRON 3VL moulded case circuit breaker, for vertical installation
1 Minimum depth
6/19Siemens LV 56 · 2008
Assembly Kits for Switching Devices
6
■ Description The equipment support assembly kit contains a deep mounting plate for front and rear terminal bars and fastening crossbars.
The modular doors kit with degree of protection IP4X with holes for the 8UC door locking mechanism contains a door, hinges, individual cover and fasteners.
The Link-N kit includes support, cover and fasteners. In the 3- and 4-pole moulded case circuit breaker combination this kit provides for the internal separation for a branch unit.
■ ConfigurationExtended terminal covers have to be ordered for front terminal bars.
■ Selection and ordering data
Circuit breaker
No. of poles
Connec-tion
Ad hoc cover for type of op. mech.
Height of module mm
Widthmm
Depth1
mmMax. no. of circuit breakers
N-Link support Equipment mounting plate
Cover
Sentron 3VL moulded case circuit breakers, plug-in, for horizontal installation VL 630 3/4 rear 8UC-door locking mech., Gr. 3 400 600 400 1 8PQ6000-3BA54 8PQ6000-3BA05 8PQ2040-6BA16
VL 630 3/4 front 8UC-door locking mech., Gr. 3 600 600 400 1 8PQ6000-3BA54 8PQ6000-3BA05 8PQ2060-6BA17
VL 800 3/4 rear 8UC-door locking mech., Gr. 3 600 600 400 1 8PQ6000-3BA55 8PQ6000-3BA07 8PQ2060-6BA10
VL 800 3/4 front 8UC-door locking mech., Gr. 3 800 600 400 1 8PQ6000-3BA55 8PQ6000-3BA07 8PQ2080-6BA05
VL 1250 3/4 rear 8UC-door locking mech., Gr. 3 600 600 400 1 8PQ6000-3BA56 8PQ6000-3BA11 8PQ2060-6BA11
VL 1250 3/4 front 8UC-door locking mech., Gr. 3 800 600 400 1 8PQ6000-3BA56 8PQ6000-3BA11 8PQ2080-6BA06
VL 1600 3/4 rear 8UC-door locking mech., Gr. 3 700 600 400 1 8PQ6000-3BA56 8PQ6000-3BA12 8PQ2070-6BA02
VL 1600 3/4 front 8UC-door locking mech., Gr. 3 900 600 400 1 8PQ6000-3BA56 8PQ6000-3BA12 8PQ2090-6BA010
20
70 0
20
65 0
20
61
Assembly kit for SENTRON 3VL mouldedcase circuit breaker, for vertical installation
1 Minimum depth
6/20
Assembly Kits for Switching Devices
Siemens LV 56 · 2008
6
■ Overview
Assembly kit for 3VT moulded case circuit breakers
3
1
2
1 Assembly kit for 3VT1, fixed, vertical
2 Assembly kit for 3VT2, fixed horizontalwith mechanical lock
3 Assembly kit for 3VT3, draw out, vertical
02
15
7
2
2
6/21Siemens LV 56 · 2008
Assembly Kits for Switching Devices
6
■ Description The equipment support assembly kit contains a deep mounting plate for front and rear terminal bars and fastening crossbars.
For installation on the front frame, choice of covers includes versions suitable for direct, motorised and rotary front operating mechanism. The covers are secured to the front frame by means of fast closing screws (1/4 of a turn).
Hinges to be fitted to the individual covers are available as an option.
■ ConfigurationFor the connection always use insulated busbars or cables.
■ Selection and ordering data
■ Selection and ordering data
■ Description The mechnical interlock assembly kit contains a device holder with holes to fit the locking elements, the supporting rails and the fasteners.
■ Configuration For the mechanical coupling of 2 circuit breakers installed in the horizontal position use the mechanical interlocking assembly and the relative accessories.
■ Selection and ordering data
Circuit breaker
No. of poles
Connec-tion
Ad hoc cover for type of op. mech.
Height of module mm
Widthmm
Depth1
mmMax. no. of circuit breakers
Equipment mounting plate
Cover
3VT moulded case circuit breakers, fixed and plug-in, for horizontal installation 3VT1 (160A) 3/4 front, rear Direct 150 600 400 1 8PQ6000-4BA21 8PQ2015-6BA17
3VT2 (250A) 3 front, rear Direct, motorised 150 600 400 1 8PQ6000-4BA23 8PQ2015-6BA18
3VT2 (250A) 4 front, rear Direct, motorised 200 600 400 1 8PQ6000-4BA24 8PQ2020-6BA22
3VT3 (630A) 3 front, rear Direct, motorised 200 600 400 1 8PQ6000-4BA27 8PQ2020-6BA23
3VT3 (630A) 4 front, rear Direct, motorised 250 600 400 1 8PQ6000-4BA26 8PQ2025-6BA14
Circuit breaker
No. of poles
Connec-tion
Ad hoc cover for type of op. mech.
Height of module mm
Widthmm
Depth1
mmMax. no. of circuit breakers
Equipment mounting plate
Cover
3VT moulded case circuit breakers, draw out, for horizontal installation 3VT2 (250A) 3/4 front, rear Direct, motorised 250 600 400 1 8PQ6000-4BA22 8PQ2025-6BA13
3VT3 (630A) 3/4 front, rear Direct, motorised 300 600 400 1 8PQ6000-4BA25 8PQ2030-6BA20
02
14
2
02
14
3
02
14
40
21
44
02
14
5
Circuit breaker
No. of poles
Connec-tion
Ad hoc cover for type of op. mech.
Height of module mm
Widthmm
Depth1
mmEquipment mounting plate
Cover
Mechanical lock for Sentron 3VT moulded case circuit breaker, for horizontal installation 3VT2, 3VT3 – – – 100 600 400 8PQ6000-4BA34 8PQ2010-6BA01
02
14
6 02
14
7
Assembly kit for 3VT mouldedcase circuit breakers, for horizontal installation
1 Minimum depth
6/22
Assembly Kits for Switching Devices
Siemens LV 56 · 2008
6
■ Description The equipment support assembly kit contains a deep mounting plate for front and rear terminal bars and fastening crossbars.
For installation on the front frame, choice of covers includes versions suitable for direct, motorised and rotary front operating mechanism. The covers are secured to the front frame by means of fast closing screws (1/4 of a turn).
Hinges to be fitted to the individual covers are available as an option.
■ Configuration For the connection always use insulated busbars or cables.
a Front terminal bars and a breaking capacity ≤ 35 kA require two additional covers, 150mm each. Moreover, the phase separators and the terminal covers have to ordered.
b Front terminal bars and a breaking capacity ≤ 65 kA require two additional covers, 200mm each. Moreover, the phase separators and the terminal covers have to ordered.
■ Selection and ordering data
■ Selection and ordering data
■ Selection and ordering data
Circuit breaker No. of poles
Connection Ad hoc cover for type of op. mech.
Height of module mm
Widthmm
Depth1
mmMax. no. of circuit breakers
DIN rail Cover
Sentron 3VT moulded case circuit breakers, fixed, for vertical installation 3VT1 (160A) 3 front Direct 450 600 400 1-5 8PQ6000-3BA36 8PQ2045-6BA07
3VT1 (160A) 3 front Motorised 450 600 400 1-2 8PQ6000-3BA36 8PQ2045-6BA07
3VT1 (160A) 4 front Direct 450 600 400 1-3 8PQ6000-3BA36 8PQ2045-6BA07
3VT1 (160A) 4 front Motorised 450 600 400 1-2 8PQ6000-3BA36 8PQ2045-6BA07
Circuit breaker No. of poles
Connection Ad hoc cover for type of op. mech.
Height of module mm
Widthmm
Depth1
mmMax. no. of circuit breakers
Equipment mounting plate
Cover
3VT moulded case circuit breakers, fixed and plug-in, for vertical installation 3VT2 (250A) a,b 3 front, rear Direct, motorised 350 600 400 1-3 8PQ6000-4BA28 8PQ2035-6BA18
3VT2 (250A) a,b 4 front, rear Direct, motorised 350 600 400 1-2 8PQ6000-4BA30 8PQ2035-6BA20
3VT3 (630A) a,b 3 front, rear Direct, motorised 400 600 400 1-2 8PQ6000-4BA31 8PQ2040-6BA18
3VT3 (630A) a,b 4 front, rear Direct, motorised 400 600 400 1-2 8PQ6000-4BA32 8PQ2040-6BA20
Circuit breaker No. of poles
Connection Ad hoc cover for type of op. mech.
Height of module mm
Widthmm
Depth1
mmMax. no. of circuit breakers
Equipment mounting plate
Cover
3VT moulded case circuit breakers, draw out, for vertical installation 3VT2 (250A) a,b 3 front, rear Direct, motorised 350 600 400 1-2 8PQ6000-4BA28 8PQ2035-6BA18
3VT2 (250A) a,b 4 front, rear Direct, motorised 350 600 400 1-2 8PQ6000-4BA30 8PQ2035-6BA20
3VT3 (630A) a,b 3 front, rear Direct, motorised 400 600 400 1-2 8PQ6000-4BA31 8PQ2040-6BA18
3VT3 (630A) a,b 4 front, rear Direct, motorised 400 600 400 1 8PQ6000-4BA33 8PQ2040-6BA21
02
14
8
02
14
9
02
15
0
02
15
1
02
15
2
02
15
3
Assembly kit for 3VT moulded case circuit breakers, for vertical installation
1 Minimum depth
6/23Siemens LV 56 · 2008
Assembly Kits for Switching Devices
6
Assembly kit for SENTRON 3K disconnectors
■ Overview
1
2
1 BS 88 fuse from IEC NH to British standard
3
6
5
4
5 8UC9 handle fox fixed installation in standard version(black) and emergency version (red)
6 8UC6 door locking handle witx ± 5 mm adaptiontolerance in horizontal/vertical directionStandard version (black) and emergency version(red/yellow)All disconnector components up to the operatingmechanism are provided with unique identificazionfeatures
Choice of
2 IP20 fuse cover
3 IP20 single-pole cover, from 63 to 630 A
4 Standard products from the 3SB1 rangeare used as auxiliary contacts
6/24
Assembly Kits for Switching Devices
Siemens LV 56 · 2008
6
Assembly kit for SENTRON 3K disconnectors
■ Technical specifications
1) Technical specifications for CSA approval upon request.
Standard IEC 60947-1, IEC 60947-3, VDE 0660 Teil 107
Type 3KL50 3KL52 3KL53 3KL551) 3KL571) 3KL611)
Rated continuous current Iufor fuses according to DIN 43620
ASize
6300 u. 000
12500 u. 000
16000 u. 000
2501 and 2
4001 and 2
6303 and 2
Cable lug, max (multiwire) conductor size mm2 35 70 120 150 2 × 150or1 × 240
2 × 240
Tightening torqueConnecting screw
Nm 6 ... 7,5M6
7 ... 10M6
18 ... 22M8
35 ... 45M10
35 ... 45M10
56M12
Type 3KA71 1
Rated continuous current Iu A 32 45 63 80 100 125
Cable lug, max (multiwire) conductor size mm2 50 50 50 50 50 50
Busbar size mm2 16×3 16×3 16×3 16×3 16×3 16×3
Type 3KA71 2
Rated continuous current Iu A 160 200 250
Cable lug, max (multiwire) conductor size mm2 120 120 120
Busbar size mm2 20×5 20×5 20×5
Type 3KA71 3
Rated continuous current Iu A 315 400
Cable lug, max (multiwire) conductor size mm2 2×150 2×150
Busbar size mm2 2×25×5 2×25×5
Type 3KA71 4
Rated continuous current Iu A 630
Cable lug, max (multiwire) conductor size mm2 2×185
Busbar size mm2 2×32×6
Type 3KA71 5
Rated continuous current Iu A 800 1000 1250 1600 2000 2500 3150
Cable lug, max (multiwire) conductor size mm2 2×240 – – – – – –
Busbar size mm2 2×50×5 2×50×6 2×50×8 3×50×8 3×50×12 4×50×12 8×50×12
Type 3KA71 6
Rated continuous current Iu A 1600 2000 2500 3150
Cable lug, max (multiwire) conductor size mm2 – – – –
Busbar size mm2 2×80×10 2×80×10 3×80×10 2×100×10
Type 3KL71 1
Rated continuous current Iu A 32 45 63 80
Cable lug, max (multiwire) conductor size mm2 25 25 25 25
Busbar size mm2 12×3 12×3 12×3 12×3
Type 3KL71 2
Rated continuous current Iu A 100 125 160
Cable lug, max (multiwire) conductor size mm2 70 70 70
Busbar size mm2 16×4 16×4 16×4
Type 3KL71 3
Rated continuous current Iu A 200 250
Cable lug, max (multiwire) conductor size mm2 120 120
Busbar size mm2 25×4 25×4
Type 3KL71 4
Rated continuous current Iu A 315 400
Cable lug, max (multiwire) conductor size mm2 240 240
Busbar size mm2 32×5 32×5
Type 3KL71 5
Rated continuous current Iu A 630 800
Cable lug, max (multiwire) conductor size mm2 2×185 2×185
Busbar size mm2 2×40×6 2×40×6
6/25Siemens LV 56 · 2008
Assembly Kits for Switching Devices
6
Assembly kit for SENTRON 3K disconnectors
■ DescriptionThe assembly kit for 3K disconnectors is made up of: • Mounting plate• Crossbars • Cover with holes to fit a door locking mechanism and fast
closing screws • Fastening screws
The depth adjustable mounting plate is mounted on crossbars and is suitable for front or rear terminal bars for the connection of cables or busbars.
■ Configuration a Due to the size of its handle, the 1250A/50 kA 3KA715
disconnector requires an additional H = 200mm cover to be placed in the upper part (kit height + 200 mm).
b Due to the size of its handle, the 3KA715 disconnector can be installed only in versions up to 1250A/35 kA.
The respective terminal covers must be ordered too for the disconnector
■ Selection and ordering data
■ Selection and ordering data
Circuit breaker No. of poles
Connec-tion
Ad hoc cover for type of op. mech. Height of module mm
Widthmm
Depth1
mmMax. no. of circuit breakers
Equipment mounting plate
Cover
Sentron 3K disconnector, horizontal installation 3KL50, 3KL52 3/4 front, rear Door-coupling rotary operating mechanism 300 600 400 1 8PQ6000-2BA65 8PQ2030-6BA06
3KL55, 3KL57 3/4 front, rear Door-coupling rotary operating mechanism 350 600 400 1 8PQ6000-2BA71 8PQ2035-6BA08
3KL61 3/4 front, rear Door-coupling rotary operating mechanism 550 600 400 1 8PQ6000-2BA50 8PQ2055-6BA02
3KL711, 3KA711 3/4 front, rear Door-coupling rotary operating mechanism 200 600 400 1 8PQ6000-2BA52 8PQ2020-6BA10
3KL712, 3KA712 3/4 front, rear Door-coupling rotary operating mechanism 250 600 400 1 8PQ6000-2BA55 8PQ2025-6BA03
3KL713, 3KA713 3/4 front, rear Door-coupling rotary operating mechanism 300 600 400 1 8PQ6000-2BA58 8PQ2030-6BA04
3KL714, 3KA714 3/4 front, rear Door-coupling rotary operating mechanism 350 600 400 1 8PQ6000-2BA62 8PQ2035-6BA06
3KL715, 3KA715 a 3/4 front, rear Door-coupling rotary operating mechanism 450 600 400 1 8PQ6000-2BA67 8PQ2045-6BA02
Circuit breaker No. of poles
Connec-tion
Ad hoc cover for type of op. mech. Height of module mm
Widthmm
Depth1
mmMax. no. of circuit breakers
Equipment mounting plate
Cover
Sentron 3K disconnector, vertical installation3KL50, 3KL52 3/4 front, rear Door locking mech. 250 600 400 1 8PQ6000-2BA66 8PQ2025-6BA05
3KL55, 3KL57 3/4 front, rear Door locking mech. 350 600 400 1 8PQ6000-2BA72 8PQ2035-6BA10
3KL61 3 front, rear Door locking mech. 450 600 400 1 8PQ6000-2BA51 8PQ2045-6BA01
3KL711, 3KA711 3/4 front, rear Door locking mech. 200 600 400 1 8PQ6000-2BA53 8PQ2020-6BA11
3KL712, 3KA712 3/4 front, rear Door locking mech. 250 600 400 1 8PQ6000-2BA56 8PQ2025-6BA04
3KL713, 3KA713 3/4 front, rear Door locking mech. 300 600 400 1 8PQ6000-2BA60 8PQ2030-6BA05
3KL714, 3KA714 3/4 front, rear Door locking mech. 350 600 400 1 8PQ6000-2BA63 8PQ2035-6BA07
3KL715, 3KA715 b 3/4 front, rear Door locking mech. 450 600 400 1 8PQ6000-2BA68 8PQ2045-6BA03
3KL711, 3KA711 3/4 front, rear Door locking mech. 200 800 400 1 8PQ6000-2BA54 8PQ2020-8BA04
3KL712, 3KA712 3/4 front, rear Door locking mech. 250 800 400 1 8PQ6000-2BA57 8PQ2025-8BA02
3KL713, 3KA713 3/4 front, rear Door locking mech. 300 800 400 1 8PQ6000-2BA61 8PQ2030-8BA02
3KL714, 3KA714 3/4 front, rear Door locking mech. 350 800 400 1 8PQ6000-2BA64 8PQ2035-8BA04
3KL715, 3KA715 3/4 front, rear Door locking mech. 450 800 400 1 8PQ6000-2BA70 8PQ2045-8BA01
02
07
1
02
07
2
02
07
3
02
07
4
1 Minimum depth
6/26
Assembly Kits for Switching Devices
Siemens LV 56 · 2008
6
Assembly kit for in-line fuse switch disconnectors SENTRON 3NJ4
■ Overview
02
07
5
6/27Siemens LV 56 · 2008
Assembly Kits for Switching Devices
6
Assembly kit for in-line fuse switch disconnectorsSENTRON 3NJ4
■ Technical Data
1) When using different devices, take into account the load factor specified in standard EN 60439 part 1/DIN VDE 0660 part 500, Table 12) The minimum space needed for the casing is 0,185 m3.3) A special kit supplied on request is necessary for the 2 x 240 mm2 connection.
Rated currents for the horizontal distribution rails
The data refer to normal operating conditions for indoor models as specified in standard IEC 60439-1, in particular with reference to an ambient temperature of 35 °C (24 h average). In different operating conditions, take into account the correction factors given in the chapter on “Planning and configuration”.
Standards IEC 60947-1, IEC 60947-3, VDE 0660 Teil 107
Type 3NJ41 03NJ5 0
3NJ41 2 3NJ41 3 3NJ41 4
Conventional thermal current in free air Ith 1)in enclosed place Ithe 2)
AA
160160
250225
400360
630567
Rated insulation voltage Ui V 750 1000 1000 1000
Rated operating voltage Ue AC 40 Hz ... 60 Hz V
690 690 690 690
Rated conditional short-circuit current with fusesfrom AC 40 Hz to 60 Hz 690 V
max. rated current of fuses In admissible fuse cut-off current
For fuse kitaccording to standard IEC 60269-2-1 or sectioning brackets
kA(actual value)AkA(peak value)size/A
50
16015
00/160
50
25028
1/250
50
40039
1 und2/250 und400
50
63052
2 und3/400 und630
Degree of protectionwith open handle insertwith side cover and clampswith closed handle insert
IP30
IP10
IP30
IP10
IP30
IP10
IP30
IP10
Power dissipated from main current lines Ith W 18 23 49 110
Main conductor connectionConnecting screwsFlat railsTerminal, max. size of (multiwire) conductorTightening torqueBracket / V-clamp
mmmm2
Nmmm2
M8249510 ... 151,5 ... 70
M104224030 ... 3525 ... 300
M124224030 ... 3525 ... 300
M12422403)30 ... 3525 ... 300
Fastening screwsfor installation on busbarstightening torque required
NmM816 ... 18
M1235 ... 40
M1235 ... 40
M1235 ... 40
No. of bars Dimensions Rated current at 35° C ambient temperature
[mm] IP ≤ IP41 IP 55
1 60 x 10 1560 1280
1 80 x 10 1740 1430
1 100 x 10 2180 1790
6/28
Assembly Kits for Switching Devices
Siemens LV 56 · 2008
6
Assembly kit for in-line fuse switch disconnectors SENTRON 3NJ4
■ DescriptionThe device holder is made up of crossbars and depth adjustable corner supports for the horizontal installation of distribution busbars. The panels are secured to the frame by means of a snap-in system.
■ ConfigurationThe device holder is suitable for use behind a closed door.
Kit for the connection of cables from the bottom and from the top.
Copper busbars are not included in the kit.
Two supports for the distribution busbars must be ordered.
■ Selection and ordering data
Switch Num-ber of poles
Installation technique
Heightmm
Widthmm
Switches for kit
Device holder Support for distribution busbars
Direct activation panel
Sentron 3NJ4 disconnector with fuses3NJ4, BG 1, 2, 3 3 fixed 800 600 4 8PQ6000-2BA48 3NJ5974-0AB 8PQ2000-6BA06
3NJ4, BG 1, 2, 3 3 fixed 800 800 6 8PQ6000-2BA48 3NJ5974-0AB 8PQ2000-8BA06
Configuration for cable entry from the bottom Configuration for cable entry from the top
02
07
6
02
07
7
02
07
8
02
07
9
02
08
0
6/29Siemens LV 56 · 2008
Assembly Kits for Switching Devices
6
Assembly kit for in-line fuse switch disconnectorsSENTRON 3NJ6
■ Overview
3
1
4
2
2 3NJ6 in-line fuse disconnectors
3 Cable connection compartment door
4 Fixed cover for PE busbars
3N
76
1 Fixed cover for busbars
6/30
Assembly Kits for Switching Devices
Siemens LV 56 · 2008
6
Assembly kit for in-line fuse switch disconnectors SENTRON 3NJ6
■ Technical Data
1) Standard IEC 60439 requires that rated uninterrupted current be reduced if busbars are installed in the control board.
Rated currents for the vertical distribution busbar system
The data refer to normal operating conditions for indoor models as specified in standard IEC 60439-1, in particular with reference to an ambient temperature of 35 °C (24 h average). In different operating conditions, take into account the correction factors given in the chapter on “Planning and configuration”.
Standards IEC 60947-1
TypeBreaking capacity
3NJ60 0.-1S
3NJ60 0.-3H
3NJ60 1.-1S
3NJ60 1.-3H
3NJ60 2.-1S
3NJ60 2.-3H
3NJ60 3.-1S
3NJ60 3.-3H
Rated uninterrupted current Iu1)
for kit wtih fuses according to standard IEC 60269
A 160 250 400 630
Rated operating current Ue• with a rated current of
AC VHz
69050/60
Rated insulation voltage Ui V 1000
Rated impulse current Uimp V 8000
Rated conditional short circuit current• Short-circuit resistance (actual value) kA 100• Short-circuit switching capacity (actual value)
kA 55 66 55 66 55 66 55 66
Rated operating current Ie• with AC 500 V AC-22B
AC-23B• with AC 690 V AC-22B
AC23B
AAAA
160–160–
160160160125
250–200–
250250200200
400–400–
400400400315
630–630–
630630630500
Short-circuit breaking power• with AC 500 V cosϕ = 0,65
cosϕ = 0,35• with AC 690 V cosϕ = 0,95
cosϕ = 0,35
AAAA
480–480–
48012804801000
750–600–
75020006001600
1200–1200–
1200320012002520
1890–1890–
1890504018904000
Operating life• overall
• mechanical
• electrical (690 V, cosϕ = 0,65)
operat-ing cy-clesoperat-ing cy-clesoperat-ing cy-cles
1600
1400
200
1600
1400
200
1000
800
200
1000
800
200
Power dissipated(including NH fuses with lower dissipation power according to VDE 0636 part 2)
W 39 73 114 215
Permissible operating position horizontal
Degree of protection (in operating condi-tions)
IP41
Main conductor connection• Terminal connection
– Conductor sizeAl/Cu, single or multiwireaccording to DIN 46235 (Cu) and DIN 46239 (Al)
– screw dimensions– tightening torque
mm2
Nm
1 x 10 ... 95
M815
1 x 95 ... 240
M1230
1 x 300,2 x 95 ... 240
2 x M1230
1 x 300,2 x 95 ... 240
2 x M1230
• Clamp connection– conductor size (Al/Cu), rn– conductor size (Al/Cu), re– conductor size (Al/Cu), sm– conductor size (Al/Cu), se– tightening torque required
mm2
mm2
mm2
mm2
Nm
1 x 10 ... 501 x 10 ... 501 x 35 ... 951 x 50 ... 9510
1 x 16 ... 351 x 16 ... 701 x 35 ... 2401 x 35 ... 30025
2 x 16 ... 352 x 16 ... 702 x 35 ... 2402 x 35 ... 30025
2 x 16 ... 352 x 16 ... 702 x 35 ... 2402 x 35 ... 30025
No. of bars Dimensions Rated current at 35° C ambient temperature
[mm] IP ≤ IP41
1 60 x 10 1560
1 80 x 10 2100
6/31Siemens LV 56 · 2008
Assembly Kits for Switching Devices
6
Assembly kit for in-line fuse switch disconnectorsSENTRON 3NJ6
■ DescriptionThe assembly kit for Sentron 3NJ6 in-line fuse disconnectors in horizontal configuration contains vertical bars and busbar supports suitable for 3- and 4-pole versions.
The device compartment consists of a modular door, vertical and horizontal partitions, a device holder.
■ ConfigurationDepending on the interior organisation of the rack, configure the rack, interior bearing structures with a usable height of 1600 mm, exterior bearing structures and partitions.
The assembly kit can be used with racks 1000mm or 1200mm width and 400mm, 600mm or 800mm deep, and it occupies a width of 600 mm.
For each assembly kit for Sentron 3NJ6 in-line fuse disconnectors, configure 8 protective covers 3NJ6916-4EA00.
The 400mm and 600mm wide cable connecting compartment can be equipped with standard components for N and PE busbars, and cable supporting brackets.
Depending on field conditions, it is necessary to configure a fixed cover before the busbars, a fixed cover before the PE busbars and a door (for the cable connecting compartment).
Max degree of protection IP41
Copper busbars are not included in the kit.
■ Selection and ordering data
Number of poles
Installation technique
Heightmm
Widthmm
Ordering code UI
Assembly kit for Sentron 3NJ6 in-line fuse disconnectors, plug-in installation, horizontal configuration3/4 steck 1600 600 8PQ3000-1BA48 1
Compartment with modular door for on site installation of Sentron 3NJ6 in-line fuse disconnectors200 600 8PQ3000-1BA50 1400 600 8PQ3000-1BA51 1
Protective covers for Sentron 3NJ6 in-line fuse disconnectors 3NJ6916-4EA00 1
02
08
20
20
83
02
08
4
6/32
Assembly Kits for Switching Devices
Siemens LV 56 · 2008
6
Assembly kits for modular installations devices
■ Overview
02
09
0
6/33Siemens LV 56 · 2008
Assembly Kits for Switching Devices
6
Assembly kit for modular installation devices
■ Description The kit for modular devices mounted on DIN rails is made up of: • Support brackets • Variable depth 35mm DIN rail in ALU • Cover with cut-out DIN and fast closing screws (1/4 turn) • Fastening screws The multiple DIN rail makes it possible to snap the Sikclip wiring system onto the rear side. The DIN rail can be modifies and adjusted for depth as desired.The horizontal raceway fastening kit contains the support and the necessary fasteners.
■ Configuration The DIN rail can be adjusted for a distance from the front cover of 47.5mm, 56.5mm and 75.5mm.
The support bracket makes it possible to fit a vertical raceway up to 60mm in width.
For each row, order 1 DIN rail kit of matching width.
■ Selection and ordering data
■ Selection and ordering data
■ Selection and ordering data
Row centre distance mm
Height of module mm
Widthmm
Modular units DIN rail Cover
DIN rail assembly kit for modular devices, 1 row150 150 600 24 8PQ6000-3BA36 8PQ2015-6BA07
200 200 600 24 8PQ6000-3BA36 8PQ2020-6BA12
150 150 800 36 8PQ6000-3BA37 8PQ2015-8BA03
200 200 800 36 8PQ6000-3BA37 8PQ2020-8BA05
02
09
1
02
09
2
Row centre distancemm
Height of modulemm
Widthmm
Modular units DIN rail Cover
DIN rail assembly kit for modular devices, 2 row150 300 600 48 2 x 8PQ6000-3BA36 8PQ2030-6BA07
200 400 600 48 2 x 8PQ6000-3BA36 8PQ2040-6BA10
150 300 800 72 2 x 8PQ6000-3BA37 8PQ2030-8BA03
200 400 800 72 2 x 8PQ6000-3BA37 8PQ2040-8BA10
Row centre distancemm
Height of modulemm
Widthmm
Modular units DIN rail Cover
DIN rail assembly kit for modular devices, 3 row150 450 600 72 3 x 8PQ6000-3BA36 8PQ2045-6BA04
200 600 600 72 3 x 8PQ6000-3BA36 8PQ2060-6BA04
150 450 800 108 3 x 8PQ6000-3BA37 8PQ2045-8BA02
200 600 800 108 3 x 8PQ6000-3BA37 8PQ2060-8BA02
Row centre distance
Height of module mm
Widthmm
Modular units Ordering code UI
Horizontal raceway fastening brackets – – – – 600/800 8PQ6000-0BA16 2
02
09
1
02
09
3
02
09
1
02
09
4
01
66
0
6/34
Assembly Kits for Switching Devices
Siemens LV 56 · 2008
6
Assembly kit for modular installation devices
■ Description Sikclip is a quick wiring system simplifying the connection of flush-mounted circuit breakers.
– for direct mounting on the rear vertical CU busbar
– fixing with clips onto the back of the DIN rail (top hat rail).
Distribution terminal blocks with IMQ label, in 2-pole or 4-pole versions, for currents up to 125 A. Icw up to 4.3 kA and Ipk up to 22 kA. For direct fastening onto the DIN rails.
■ Technical specifications
■ Selection and ordering data
Max. rated operating current In 250 A at 40 °C ambient temperature
Max. rated output current In 63 A at 40 °C ambient temperature
Rated operating voltage Un AC 400 V
Rated insulation voltage AC 660 V
Test voltage 2,5 kV, 50 Hz
Degree of protection IP20
Connecting conductors 40 A (6 mm2), 63 A (10 mm2)
Type of connecting conductor H07VK
Colour RAL 7035
Operating temperature –5 °C to +60 °C
Applicable standards EN 60947-1, EN 60439-3
Model Length Colour Ordering code
Sikclip wiring system
12 TE 5ST2 520
24 TE 5ST2 521
36 TE 5ST2 522
Connecting conductors
6 mm2 120 mm black 5ST2 523
blue 5ST2 524
10 mm2 120 mm black 5ST2 525
blue 5ST2 526
6 mm2 220 mm black 5ST2 527
blue 5ST2 528
10 mm2 220 mm black 5ST2 530
blue 5ST2 531
Push-in connector 5ST2 532
Brackets for anchoring to back of DIN rail (pair) 5ST2 533
Model TE Icw (1 s)kA
IpkkA
Ordering code
Distribution terminal blocks �100 A 7 openings per pole 2 poles 4 3,1 20 8GF9 871
5 × 1,5 up to 6 mm2 +2 × 6 up to 16 mm2
4 poles 5 3,1 20 8GF9 872
125 A 11 openings per pole 2 poles 7 4,3 22 8GF9 873
7 × 1,5 up to 6 mm2 +2 × 6 up to 16 mm2 +2 × 16 up to 35 mm2
4 poles 7 4,2 22 8GF9 874
15 openings per pole 2 poles 8 4,2 22 8GF9 875
11 × 1,5 up to 6 mm2 +2 × 6 up to 16 mm2 +2 × 16 up to 35 mm2
4 poles 8 4,3 22 8GF9 876
Siemens LV 56 · 2008
7
Covers, Modular Doors, Mounting Plate, 19” Rack
7/2 Covers
7/4 Modular doors
7/7 Modular mounting plates
7/8 Mounting plate for electrotechnical applications
7/9 19” rack
7/2
Siemens LV 56 · 2008
Covers, Modular Doors, Mounting Plate, 19” Rack
7
■
Description
The kit consists a cover and guick-release locks.
The covers are secured to the board frame by means of captive fast closing screws (1/4 of a turn).
1/4 turn screws are tightened and loosened by means of a flathead screwdriver.
In addition to fastening the cover, the screw also performs a grounding function for the cover.
Using the hinge options, the cover can be hinged on the right or the left as desired.
The hinges are mounted without having to use any additional mechanical parts and also perform a grounding function for the cover.
■
Configuration
If the fast closing screws are replaced with hinges, the holes must be closed with plugs.
Use a pair of hinges per cover.
■
Selection and ordering data
Cut-out Height of module mm
Widthmm
Ordering code UI
Covers without cut-outs
– 50 600
8PQ2005-6BA01
1
– 100 600
8PQ2010-6BA01
1
– 150 600
8PQ2015-6BA02
1
– 200 600
8PQ2020-6BA01
1
– 250 600
8PQ2025-6BA01
1
– 300 600
8PQ2030-6BA01
1
– 350 600
8PQ2035-6BA01
1
– 400 600
8PQ2040-6BA01
1
– 500 600
8PQ2050-6BA01
1
– 550 600
8PQ2055-6BA01
1
– 600 600
8PQ2060-6BA01
1
– 650 600
8PQ2065-6BA01
1
– 800 600
8PQ2080-6BA01
1
– 50 800
8PQ2005-8BA01
1
– 100 800
8PQ2010-8BA01
1
– 150 800
8PQ2015-8BA02
1
– 200 800
8PQ2020-8BA01
1
– 250 800
8PQ2025-8BA01
1
– 300 800
8PQ2030-8BA01
1
– 350 800
8PQ2035-8BA01
1
– 400 800
8PQ2040-8BA01
1
– 500 800
8PQ2050-8BA01
1
– 550 800
8PQ2055-8BA01
1
– 600 800
8PQ2060-8BA01
1
– 650 800
8PQ2065-8BA01
1
– 800 800
8PQ2080-8BA01
1
Covers with cut-outs
2 instruments 72 x 72 mm + 2 change-over switches 200 600
8PQ2020-6BA03
1
4 instruments 72 x 72 mm + 1 change-over switch 200 600
8PQ2020-6BA02
1
2 instruments 72 x 72 mm + 2 change-over switches 200 800
8PQ2020-8BA03
1
4 instruments 72 x 72 mm + 1 change-over switch 200 800
8PQ2020-8BA02
1
01
66
10
16
93
Covers
7/3
Siemens LV 56 · 2008
Covers, Modular Doors, Mounting Plate, 19” Rack
7
Covers
■
Description
The kit consists a cover and guick-release locks.
The covers are secured to the board frame by means of captive fast closing screws (1/4 of a turn).
1/4 turn screws are tightened and loosened by means of a slot or cross-slot screwdriver.
In addition to fastening the cover, the screw also performs a grounding function for the cover.
Using the hinge options, the cover can be hinged on the right or the left as desired.
The hinges are mounted without having to use any additional mechanical parts and also perform a grounding function for the cover.
■
Configuration
If the fast closing screws are replaced with hinges, the holes must be closed with plugs.
Use a pair of hinges per cover.
■
Selection and ordering data
Cut-out Height of module mm
Widthmm
Ordering code UI
Covers 400mm with cut-outs
2 instruments 96 x 96 mm + 2 change-over switches 400 600
8PQ2040-6BA04
1
4 instruments 96 x 96 mm + 1 change-over switch 400 600
8PQ2040-6BA03
1
2 instruments 96 x 96 mm + 2 change-over switches 400 800
8PQ2040-8BA04
1
4 instruments 96 x 96 mm + 1 change-over switch 400 800
8PQ2040-8BA03
1
Covers with ventilation fins
ventilated 100 600
8PQ2010-6BA02
1
ventilated 100 800
8PQ2010-8BA02
1
Cover hinges kit
– – –
8PQ2000-0BA01
10
Closing plugs for cover holes
– – –
8PQ2000-0BA02
10
01
80
90
18
10
01
81
10
16
97
01
81
2
7/4
Siemens LV 56 · 2008
Covers, Modular Doors, Mounting Plate, 19” Rack
7
Modular doors
■
Overview
2
1
3
1 Exterior front cover for main busbars
2 Modular door
3 Cover for degree of protection IP55
4 Exterior front cover for PE bar
402
09
5
3
2
2
7/5
Siemens LV 56 · 2008
Covers, Modular Doors, Mounting Plate, 19” Rack
7
Modular doors
■
Description
The “exterior front covers” kit for the main busbars and the PE bar contains the cover and an anchoring support.
■
Configuration
Each cubicle with modular doors must be fitted with a front cover before the busbars and the PE bar.
■
Selection and ordering data
Height of module mm
Widthmm
Ordering code IP55 upgrade
Exterior front cover for main busbars
225 600
8PQ2022-6BA01 8PQ2022-6BA02
225 800
8PQ2022-8BA01 8PQ2022-8BA02
Height of module mm
Widthmm
Ordering code IP55 upgrade
Exterior front cover for PE bars
175 600
8PQ2000-6BA07 8PQ2015-6BA13
175 800
8PQ2000-8BA07 8PQ2015-8BA08
02
09
6
02
09
7
02
15
8
02
09
8
7/6
Siemens LV 56 · 2008
Covers, Modular Doors, Mounting Plate, 19” Rack
7
Modular doors
■
Description
The modular doors kit contains a door with degree of protection IP4X, door hinge support, hinges, green column identification strip and two-way interlocking mechanism.
The “front covers” kit contains the cover and an anchoring support.
■
Configuration
A combination of front frame and covers with modular doors in a cubicle is not possible.
When using the equipment with modular doors, the remaining heights must be closed with 50mm or 100mm height front covers.
■
Selection and ordering data
Height of module mm
Widthmm
Ordering code IP55 upgrade
Modular doors
150 600
8PQ2015-6BA10 8PQ2015-6BA12
200 600
8PQ2020-6BA14 8PQ2020-6BA15
250 600
8PQ2025-6BA07 8PQ2025-6BA08
300 600
8PQ2030-6BA10 8PQ2030-6BA12
350 600
8PQ2035-6BA12 8PQ2035-6BA13
400 600
8PQ2040-6BA12 8PQ2040-6BA13
450 600
8PQ2045-6BA05 8PQ2045-6BA06
500 600
8PQ2050-6BA03 8PQ2050-6BA04
550 600
8PQ2055-6BA04 8PQ2055-6BA06
600 600
8PQ2060-6BA06 8PQ2060-6BA07
650 600
8PQ2065-6BA03 8PQ2065-6BA04
700 600
8PQ2070-6BA03 8PQ2070-6BA04
750 600
8PQ2075-6BA01 8PQ2075-6BA02
800 600
8PQ2080-6BA03 8PQ2080-6BA04
150 800
8PQ2015-8BA05 8PQ2015-8BA07
200 800
8PQ2020-8BA07 8PQ2020-8BA08
250 800
8PQ2025-8BA04 8PQ2025-8BA05
300 800
8PQ2030-8BA05 8PQ2030-8BA06
350 800
8PQ2035-8BA06 8PQ2035-8BA07
400 800
8PQ2040-8BA12 8PQ2040-8BA13
450 800
8PQ2045-8BA03 8PQ2045-8BA04
500 800
8PQ2050-8BA03 8PQ2050-8BA04
550 800
8PQ2055-8BA03 8PQ2055-8BA06
600 800
8PQ2060-8BA04 8PQ2060-8BA05
650 800
8PQ2065-8BA03 8PQ2065-8BA04
700 800
8PQ2070-8BA01 8PQ2070-8BA02
750 800
8PQ2075-8BA01 8PQ2075-8BA02
800 800
8PQ2080-8BA03 8PQ2080-8BA04
Height of module mm
Widthmm
Ordering code IP55 upgrade
Front covers
50 600
8PQ2005-6BA04 8PQ2005-6BA03
100 600
8PQ2010-6BA04 8PQ2010-6BA03
50 800
8PQ2005-8BA04 8PQ2005-8BA03
100 800
8PQ2010-8BA04 8PQ2010-8BA03
02
15
9
02
05
3
02
09
9
02
10
0
7/7
Siemens LV 56 · 2008
Covers, Modular Doors, Mounting Plate, 19” Rack
7
■
Description
The modular mounting plate kit is made up of: • Mounting plate • Crossbars • Cover and fast closing screws • Fastening screws
The mounting plate can be ordered with or without holes and can be adjusted for depth.
■
Configuration
In mounting plates with holes, hole spacing is 25 x 25 mm.
Hole diameter is 5.4 mm and the holes are suitable for M6 self-tapping screws.
■
Selection and ordering data
Height of module mm
Widthmm
Ordering code UI
Mounting plate kit without holes
200 600
8PQ3000-1BA56
1
400 600
8PQ3000-1BA61
1
600 600
8PQ3000-1BA65
1
800 600
8PQ3000-1BA26
1
200 800
8PQ3000-1BA58
1
400 800
8PQ3000-1BA63
1
600 800
8PQ3000-1BA67
1
800 800
8PQ3000-1BA28
1
Mounting plate kit with holes
200 600
8PQ3000-1BA57
1
400 600
8PQ3000-1BA62
1
600 600
8PQ3000-1BA66
1
800 600
8PQ3000-1BA27
1
200 800
8PQ3000-1BA60
1
400 800
8PQ3000-1BA64
1
600 800
8PQ3000-1BA68
1
800 800
8PQ3000-1BA30
1
02
10
10
21
02
Modular mounting plates
7/8
Siemens LV 56 · 2008
Covers, Modular Doors, Mounting Plate, 19” Rack
7
■
Description
The “mounting plate” kit for electrotechnical applications contains the mounting plate and the brackets to fasten it to the cubicle.
The brackets are fastened to the side upright or to the rear part of the cubicle.
To facilitate the installation of the mounting plate, the lower fastening brackets are designed for slanted plate insertion when the plate has been made ready and wired on the work bench.
The connecting panel kit makes it possible to create an uninterrupted surface when two or more adjacent boards have to be mechanically connected.
■
Configuration
By means of 6 additional crossbars the mounting plate can be adjusted for depth.
The crossbars are described in the chapter on “Accessories”.
■
Selection and ordering data
Height of module mm
Widthmm
Ordering code UI
Mounting plate
1600 400
8PQ3000-0BA33
1
1600 600
8PQ3000-0BA35
1
1600 800
8PQ3000-0BA37
1
1600 1000
8PQ3000-1BA06
1
1600 1200
8PQ3000-1BA07
1
1900 400
8PQ3000-0BA32
1
1900 600
8PQ3000-0BA34
1
1900 800
8PQ3000-0BA36
1
1900 1000
8PQ3000-1BA04
1
1900 1200
8PQ3000-1BA05
1
Connecting panel
1600 –
8PQ3000-1BA10
1
1900 –
8PQ3000-1BA08
1
01
67
20
17
00
Mounting plate for electrotechnical applications
7/9
Siemens LV 56 · 2008
Covers, Modular Doors, Mounting Plate, 19” Rack
7
■
Description
For the installation of a 19” rack, a fixed version kit for 600mm wide cubicles and a swivel version kit for 800mm wide cubicles are available.
■
Configuration
1 height unit (HE) = 44.45 mm.
Swivel version kit for use with right or left hinges.
The maximum weight of the rack is 160 kg.
■
Selection and ordering data
Equipment height mm
Height of electronic unit HE
Cubicle width mm
Version Ordering code UI
Kit per 19” rack
1800 39 600 fixed
8PQ3000-1BA11
1
1800 39 800 swivel
8PQ3000-1BA12
1
NSE
X_0
00
07
19” rack
7/10 Siemens LV 56 · 2008
Covers, Modular Doors, Mounting Plate, 19” Rack
7
Notes
Siemens LV 56 · 2008
8
Internal Separation
8/2 General Data
8/4 Main busbar system
8/7 Vertical distribution busbar system
8/9 Modular Separation for Switching Devices
8/2
Siemens LV 56 · 2008
Internal Separation
8
General Data
■
Overview
A fundamental characteristic of switchgear is the presence of internal separation forms as required by the applicable standards.
The main purpose of internal partitions is to make sure that all switching, control and maintenance operations can be performed in full safety, while ensuring uninterrupted system operation.
Advantages
−
Reduction of possible hazards during connection, scheduled maintenance and extraordinary maintenance operations
−
Attenuation of consequences of local faults and faster resumption of regular operation
Applications:
−
Protection against contact between live parts belonging to adjacent functional units. Degree of protection required: IP2X or IPXXB;
−
Protection against the intrusion of foreign bodies from a functional unit into an adjacent functional unit. Degree of protection required: IP 2X or higher;
−
Low risk of internal arc triggering.
Functional unit (definition): part of a switchgear containing all the electrical and mechanical components that contribute to the fulfilment of the same function, e.g., infeed and outfeed circuit breakers, measuring unit, etc.
SIVACON S4
With SIVACON S4, internal separation form 2b is achieved by separating the main busbar systems and the distribution busbars by means of partitions and covers.
Assembly kits for switching and protection devices which comply with internal separation form 1 in their basic version do not require any additional separation to achieve internal separation form 2b.
If only 1 circuit breaker per cubicle is used, form 3b corresponds to form 4b (3b = 4b).
Definitions according to IEC 60439-1, CEI EN 60439-1
Special separation forms or higher degrees of protection must be agreed upon by the manufacturer and the user.
■
Form 1
No internal separation
■
Form 2
Separation between busbars and functional units
■
Form 2a
Separation between busbars and functional units, no separation between connections and busbars
■
Form 2b
Separation between busbars and functional units, separation between connections and busbars
■
Form 3
• Separation between busbars and all functional units
• Separation between all the functional units• Separation between the connections of
conductors going to the exterior and the functional units, but no separation between the connections and the functional units
■
Form 3a
No separation between connections and busbars
■
Form 3b
Separation between connections and busbars
■
Form 4
• Separation between busbars and all functional units
• Separation between all the functional units• Separation between the connections of
conductors going to the exterior which are associated with functional units and the connections of all the other functional units and the busbars
■
Form 4a
Connections in the same cell as the functional unit concerned
■
Form 4b
Connections not in the same cell as the functional unit concerned
8/3
Siemens LV 56 · 2008
Internal Separation
8
General Data
Form 1
Form 2a
Form 3a
Form 4a
Form 2b
Form 3b
Form 4b
Functional unit
°
Input and output connections
1 Main busbars
2 Distribution busbars
3 Input circuit
4 Output circuit
01
73
40
17
35
01
73
6
01
73
7
01
73
8
01
73
9
01
74
0
8/4
Siemens LV 56 · 2008
Internal Separation
8
Main busbar system
■
Overview
Main busbar system in standard position, top front depth 400mm
Main busbar system in standard position, top front depth 600mm
Main busbar system in standard position, top front - rear depth 800mm
Main busbar system in standard position, top front and rear depth 800mm
Main busbar system in standard position in optional adjustable position, rear depth 800mm
02
10
6
02
10
3
02
10
4
02
10
5
02
10
7
8/5
Siemens LV 56 · 2008
Internal Separation
8
Main busbar system
■
Description
The form 2b separation kit for horizontal main busbar systems contains the metal parts and the fastening screws need to achieve this separation form.
■
Configuration
One piece per cubicle corresponding to the relative dimensions for equipment compartment or cable compartment.
To use a section as a riser duct it is necessary to use a side upright matching the equipment height and depth, with no bottom plate partition.
■
Selection and ordering data
Position of main busbars Widthmm
Cubicle depth mm
Height of module mm
Ordering code UI
Busbar system in standard position, form 2b separation
front top 200 600 225
8PQ3000-1BA53
1
front top 400 600 225
8PQ3000-0BA52
1
front top 600 600 225
8PQ3000-0BA53
1
front top 800 600 225
8PQ3000-0BA54
1
front top 1000 600 225
8PQ3000-1BA14
1
front top 1200 600 225
8PQ3000-1BA16
1
front or rear top 200 800 225
8PQ3000-1BA54
1
front or rear top 400 800 225
8PQ3000-0BA55
1
front or rear top 600 800 225
8PQ3000-0BA56
1
front or rear top 800 800 225
8PQ3000-0BA57
1
front or rear top 1000 800 225
8PQ3000-1BA17
1
front or rear top 1200 800 225
8PQ3000-1BA18
1
front or rear top 200 800 225
8PQ3000-1BA55
1
front or rear top 400 800 225
8PQ3000-0BA58
1
front or rear top 600 800 225
8PQ3000-0BA60
1
front or rear top 800 800 225
8PQ3000-0BA61
1
front or rear top 1000 800 225
8PQ3000-1BA20
1
front or rear top 1200 800 225
8PQ3000-1BA21
1
Busbar system in free position, form 2b separation
front top 200 400 225
8PQ3000-1BA52
1
front top 400 400 225
8PQ3000-0BA67
1
front top 600 400 225
8PQ3000-0BA68
1
front top 800 400 225
8PQ3000-0BA70
1
front top 1000 400 225
8PQ3000-1BA13
1
front top 1200 400 225
8PQ3000-1BA15
1
rear variable 400 400*, 600*, 800 250
8PQ3000-0BA78
1
rear variable 600 400*, 600*, 800 250
8PQ3000-0BA80
1
rear variable 800 400*, 600*, 800 250
8PQ3000-0BA81
1
rear variable 1000 400*, 600*, 800 250
8PQ3000-1BA22
1
rear variable 1200 400*, 600*, 800 250
8PQ3000-1BA23
1
* with modular door.
01
72
60
17
27
01
72
8
8/6
Siemens LV 56 · 2008
Internal Separation
8
General Data
■
Overview
2
1
1
1 Form 2b separation for horizontal main busbar system
2 Form 2b separation for vertical distribution busbars
2
2
01
72
5
8/7
Siemens LV 56 · 2008
Internal Separation
8
Vertical distribution busbar system
■
Description
The form 2b vertical distribution busbar separation kit contains the parts and the fasteners needed to achieve this separation form.
■
Configuration
For cubicles placed side-by-side, order an additional separation kit to obtain form 2b for the vertical busbars or separation between cubicles.
The protective front separation for the busbar compartment cannot be fitted to the back of 400 mm deep cubicles.
■
Selection and ordering data
Position of main busbars Widthmm
Cubicle depth mm
Ordering code UI
Vertical distribution busbar system with main busbars at the top, form 2b separation
front 200, 400 400
8PQ4000-0BA05
1
front 200, 400 600
8PQ4000-0BA07
1
front and rear 200, 400 800
8PQ4000-0BA64
1
front and rear 200 800
8PQ4000-0BA02
1
front and rear 400 800
8PQ4000-0BA01
1
Vertical distribution busbar system without main busbars, form 2b separation
front and rear 200, 400 400
8PQ4000-0BA06
1
front and rear 200, 400 600
8PQ4000-0BA03
1
front and rear 200, 400 800
8PQ4000-0BA76
1
Additional front cover for vertical busbar compartment
– 200 –
8PQ3000-0BA50
1
– 400 –
8PQ3000-0BA51
1
01
72
20
17
23
01
74
10
17
29
01
74
10
16
65
8/8
Siemens LV 56 · 2008
Internal Separation
8
Vertical distribution busbar system
■
Description
The separation between cubicles kit is symmetrically split and is provided with removable pre-sectioning units for use in conjunction with horizontal busbar systems.
■
Configuration
For 800 mm deep cubicles, order two 400 mm deep separation kits.
■
Selection and ordering data
Cubicle depth mm
Height Ordering code UI
Vertical separation between cubicles
400 cubicle height
8PQ3000-0BA15
1
600 cubicle height
8PQ3000-0BA16
1
01
64
1
8/9
Siemens LV 56 · 2008
Internal Separation
8
Modular Separation for Switching Devices
■
Description
The crossbars and separation supporting rails kit makes it possible to fasten the rear of the kit supporting crossbars without having to use screws.
It is also used to fasten the horizontal and vertical partitions in the rear part of the cubicle in form
≥
2b without having to use screws.
■
Configuration
Order 1 crossbars and separation supporting rails kit for cubicles sized 600 mm or 800 mm.
Required to achieve separation forms 3 and 4.
■
Selection and ordering data
Equipment height mm
Ordering code UI
Crossbars and separation supporting rails kit, for forms 3 and 4 separation
1600
8PQ3000-0BA82
2
1800
8PQ3000-0BA83
2
01
74
40
21
08
02
10
9
8/10
Siemens LV 56 · 2008
Internal Separation
8
Modular Separation for Switching Devices
■
Description
The form 3 separation kit for Sentron 3WL circuit breakers ensures rear and side separation.
■
Design
The form 3 separation kit for Sentron 3WL circuit breakers can be installed only in 600mm and 800mm deep cubicles.
This separation cannot be used for circuit breaker 3WL 1240.
■
Selection and ordering data
■
Selection and ordering data
Size No. of poles Widthmm
Height of module mm
Ordering code UI
Sentron 3WL, fixed version, form 3 separation
Gr I 3/4 600 550
8PQ5000-0BA08
1
Gr II 3 600 550
8PQ5000-0BA13
1
Gr I 3/4 800 550
8PQ5000-1BA65
1
Gr II 3/4 800 550
8PQ5000-0BA11
1
Sentron 3WL, draw out version, form 3 separation
Gr I 3/4 600 550
8PQ5000-0BA07
1
Gr II 3 600 550
8PQ5000-0BA12
1
Gr I 3/4 800 550
8PQ5000-1BA66
1
Gr II 3/4 800 550
8PQ5000-0BA10
1
Size Current No. of poles Version Width
mm
Height of module
above the circuit breaker mm
under the circuit breaker mm
Ordering code UI
Sentron 3WL, connection to the cables, form 4 separation
Gr I 1600 3/4 Fixed/Draw out 600 200 250
8PQ5000-0BA30
1
Gr I 1600 3/4 Fixed/Draw out 800 200 250
8PQ5000-1BA68
1
Gr II 3200 3/4 Fixed/Draw out 800 350 400
8PQ5000-0BA38
1
Sentron 3WL, connection to the vertical distribution busbars, form 4 separation
Gr I 1600 3/4 Fixed/Draw out 600 250 300
8PQ5000-0BA14
1
Gr I 1600 3/4 Fixed/Draw out 800 250 300
8PQ5000-1BA67
1
Gr II 3200 3/4 Fixed/Draw out 800 300 350
8PQ5000-0BA21
1
Cubicle with built-in busbars and form 3 and 4b separation
01
64
80
16
48
01
65
00
16
49
02
11
0
8/11
Siemens LV 56 · 2008
Internal Separation
8
Modular Separation for Switching Devices
■
Overview
01
63
8
1
2
Separation for 400mm deep cubicles
01
81
6 1
1 Horizontal partition
2
3
3 Rear vertical separation
33
Separation for 600mm and 800mm deep cubicles
2 Vertical separation on connecting cable side
8/12
Siemens LV 56 · 2008
Internal Separation
8
Modular Separation for Switching Devices
■
Description
For assembly kits such as Sentron 3VL, 3VT, 3K, modular devices on DIN rail and modular mounting plates, a modular separation system is available.
Equipment assembly kits achieve form 1 separation.
Form 2b is achieved through the separation of main bars and vertical distribution busbars.
Form 4b is achieved through the combination of horizontal, vertical and rear partitions.
■
Configuration
For modular devices on DIN rail supporting crossbars must also be provided.
400mm deep cubicles require a horizontal partition and a vertical partition for each branch unit.
600mm and 800mm deep cubicles require a horizontal partition and a vertical partition for each branch unit.
For 50mm high vertical partitions, order 2 25mm kits.
Height of module mm
Widthmm
Cubicle depth mm
Branch current A
Ordering code UI
Fastening crossbars
25 – 400, 600, 800 –
8PQ5000-2BA63
2
Horizontal partition
– 600 400, 600, 800 –
8PQ5000-2BA61
1– 800 400, 600, 800 –
8PQ5000-2BA62
1
Vertical separation on connecting cable side
25 – 400, 600, 800 –
8PQ5000-2BA63
1100 – 400, 600, 800 –
8PQ5000-2BA27
1150 – 400, 600, 800 –
8PQ5000-2BA28
1200 – 400, 600, 800 ≤ 250
8PQ5000-2BA30
1200 – 400, 600, 800 ≥ 400
8PQ5000-2BA31
1250 – 400, 600, 800 ≤ 250
8PQ5000-2BA32
1250 – 400, 600, 800 ≥ 400
8PQ5000-2BA33
1300 – 400, 600, 800 ≤ 250
8PQ5000-2BA34
1300 – 400, 600, 800 ≥ 400
8PQ5000-2BA35
1300 – 400, 600, 800 ≥ 800
8PQ5000-2BA46
1350 – 400, 600, 800 –
8PQ5000-2BA36
1350 – 400, 600, 800 ≥ 800
8PQ5000-2BA47
1400 – 400, 600, 800 –
8PQ5000-2BA37
1450 – 400, 600, 800 –
8PQ5000-2BA38
1500 – 400, 600, 800 –
8PQ5000-2BA40
1550 – 400, 600, 800 –
8PQ5000-2BA41
1600 – 400, 600, 800 –
8PQ5000-2BA42
1600 – 400, 600, 800 ≥ 800
8PQ5000-2BA48
1650 – 400, 600, 800 –
8PQ5000-2BA43
1700 – 400, 600, 800 –
8PQ5000-2BA44
1700 – 400, 600, 800 ≥ 800
8PQ5000-2BA50
1800 – 400, 600, 800 –
8PQ5000-2BA45
1
Rear vertical separation
50 600 600, 800 –
8PQ5000-2BA51
1
100 600 600, 800 –
8PQ5000-2BA52
1
150 600 600, 800 –
8PQ5000-2BA53
1
200 600 600, 800 –
8PQ5000-2BA54
1
250 600 600, 800 –
8PQ5000-2BA55
1
300 600 600, 800 –
8PQ5000-2BA56
1
350 600 600, 800 –
8PQ5000-2BA57
1
450 600 600, 800 –
8PQ5000-2BA58
1
550 600 600, 800 –
8PQ5000-2BA60
1
02
11
10
21
12
02
11
30
21
14
8/13
Siemens LV 56 · 2008
Internal Separation
8
Modular Separation for Switching Devices
■
Description
Form 4 separation kit per Sentron 3VL in draw out version, consisting of horizontal, vertical and rear partitions.
■
Configuration
For each Sentron 3VL kit in draw out version, order 1 separation kit.
■
Selection and ordering data
Circuit breaker No. of poles
Height of module mm
Widthmm
Cubicle depth mm
Cable connection
Ordering code UI
Sentron 3VL, horizontal installation, form 4 separation
VL160, VL250 3/4 250 600 400 front
8PQ5000-1BA76
1
VL400 3/4 300 600 400 front
8PQ5000-1BA77
1
VL630 4 350 600 400 front
8PQ5000-1BA80
1
VL630 3 300 600 400 front
8PQ5000-1BA81
1
VL160, VL250 3/4 250 600 600, 800 front, rear
8PQ5000-1BA82
1
VL400 3/4 300 600 600, 800 front, rear
8PQ5000-1BA84
1
VL630 3/4
1)
Sentron 3VL, pull-out, vertical installation, form 4 separation
VL160, VL250 3/4 350 600 400, 600, 800 front, rear
8PQ5000-1BA86
1
VL400, VL630 3/4 400 600 400, 600, 800 front
8PQ5000-1BA87
1
VL800 3/4 600 600 600, 800 front, rear
8PQ5000-1BA88
1
VL1250/VL1600 3/4 650 600 600, 800 front, rear
8PQ5000-2BA00
1
VL160, VL250 3/4 350 800 400, 600, 800 front, rear
8PQ5000-2BA01
1
VL400/630 3/4 400 800 400, 600, 800 front, rear
8PQ5000-2BA02
1
02
11
50
21
16
02
11
7
1) siehe modulare Unterteilung Kapitel 8/13
8/14
Siemens LV 56 · 2008
Internal Separation
8
Modular Separation for Switching Devices
■
Description
The “connecting terminal” kit achieves separation from form 4a to form 3b.
Separation from form 3b to form 4b is achieved through the combination of connecting terminal and protective bellows.
■
Configuration
In addition to the partitions, the required number of terminals (with or without copper busbars) has to be ordered.
When using the connecting busbar assembly kit for SENTRON 3VL circuit breakers, terminals need not be ordered.
■
Selection and ordering data
CurrentA
Busbarmm
×
mmOrdering code UI
2
×
25
×
5 1
×
30/40
×
10
Connecting terminal, separation installation from 4a to 3b
– without busbar
8PQ5000-0BA05
4
250 A 2
×
25
×
5
8PQ5000-0BA72
2
400 A 1
×
30
×
10
8PQ5000-0BA73
4
630 A 1
×
40
×
10
8PQ5000-0BA74
4
Bellows, separation installation from 3b to 4b
– –
8PQ9400-0BA03
4
01
68
3
01
73
2
01
71
6
Siemens LV 56 · 2008
9
Air-Conditioning Products
9/2 Introduction
9/2 Filter Fans
9/3 Air-Conditioning/Cooling Units
9/4 Heat Exchangers
9/5 Fan Heaters
9/5 Thermostats
9/2
Siemens LV 56 · 2008
Air-Conditioning Products
9
■
Overview
Switchgear may be subject to overheating, condensate or mould formation due to the presence of hot, cold or moist air in the immediate surroundings.
In this case, the cubicle should be air-conditioned.
The following air-conditioning units are available for this pur-pose:• Filter fans • Air-conditioning/cooling units • Heat exchangers • Heaters/thermostats
When selecting the individual air-conditioning units, the follo-wing factors must be taken into account: ambient temperature, power dissipated from the devices installed, maximum admis-sible temperatures of the devices, heat dissipated via the cu-bicle, and degree of protection required.
The installation of air-conditioning devices improves the reliabi-lity of switchgear and controlgear, making for enhanced ma-chine and system availability.
■
Description
Using fans and equipping the switchgear enclosures with venti-lation fins are the most economical methods to control the tem-perature inside a cubicle.
However, the temperature reached inside the board is higher than ambient temperature.
■
Configuration
When adopting filter fans the temperature via the board enclos-ure must not be considered.
Filter fans must be installed in the lower part of the board. If pos-sible, outlet filters must be installed in the upper part, on the door or a side panel.
The use of thermostats makes for longer filter fan and filter life.
Outlet filters should be at least the same size as the cut-out made in the door for the filter fan.
A simple formula to determine the quantity of air needed is:Air needed = 1,2 x Pv /
∆
t
∆
t = interior temperature - ambient temperature Pv = Installed power dissipated
For an exact determination, computation software can be sup-plied on request.
Notice - the standard colour is RAL 7032: special colour orders must be defined with -Z Z = specify the RAL.
■
Selection and ordering data
SizeV AC
Air flow-rate through free in-take IP54W/K
Air flow-rate with outlet filter IP54
Exterior dimensions mm x mm
Cut-out in door mm x mm
Ordering code UI
Filter fans with standard filter mat for door-mounted installation
230 24 (IP43) 15 (IP43) 105 x 105 92 x 92
8MR3101-0MA
1
115 24 (IP43) 15 (IP43) 105 x 105 92 x 92
8MR3101-0JA
1
230 58 43 150 x 150 125 x 125
8MR3102-0MA
1
115 58 43 150 x 150 125 x 125
8MR3102-0JA
1
230 155 108 250 x 250 223 x 223
8MR3103-0MA
1
115 155 108 250 x 250 223 x 223
8MR3103-0JA
1
230 255 231 250 x 250 223 x 223
8MR3104-0MA
1
115 255 231 250 x 250 223 x 223
8MR3104-0JA
1
230 478 368 325 x 325 291 x 291
8MR3105-0MA
1
115 478 368 325 x 325 291 x 291
8MR3105-0JA
1
230 606 437 325 x 325 291 x 291
8MR3106-0MA
1
115 606 437 325 x 325 291 x 291
8MR3106-0JA
1
Filter fan for top plate installation with standard filter mat
230 450 (IP33) 346 (IP33) 417 x 367 345 x 265
8MR3140-1DA
1
230 800 (IP33) 540 (IP33) 530 x 350 345 x 265
8MR3180-1DA
1
Outlet filter with standard filter mat for door-mounted installation
105 x 105 92 x 92
8MR3111-0AA
1
150 x 150 125 x 125
8MR3112-0AA
1
250 x 250 223 x 223
8MR3113-0AA
1
325 x 325 291 x 291
8MR3115-0AA
1
Filter fans
Introduction
9/3
Siemens LV 56 · 2008
Air-Conditioning Products
9
■
Description
Air-conditioners are used for ambient temperatures higher than the temperature admissible for the equipment installed in the cubicle. All the units work with FCC free cooling systems-Air-conditioners dehumidify the air inside the cubicle.
■
Applications
Cooling units for door, side panel or roof mounting
Two separate cooling circuits ensure that no hot air remains inside the cubicle.High-performance radial fans provide for effective air circulation inside the cubicle. Temperature controller with built-in thermostat (roof mounted).
Side-panel mounted units
Standard electronic components, technical characteristics:
• Test module
• Temperature limit
• Time lat at start-up
• Door contact function
• Fault indicator contact
• On-site diagnostics
• UL approval.
Notice - the standard colour is RAL 7032: special colours orders must be defined with -Z Z = specify the RAL.
■
Selection and ordering data
PowerW
VoltageV
Ordering code UI*
Panel or door (flush) mounted air-conditioners
1000 230
8MR5 510–1TE
1 piece
1500
8MR5 515–1TE
1 piece
2000 400/440
8MR5 520–1TE
1 piece
2500
8MR5 525–1TE
1 piece
Filter fans with standard filter mat
320 115/320
8MR4 032–1SA
1 piece
500
8MR4 050–1SA
1 piece
820
8MR5 082–1SA
1 piece
1100
8MR5 110–1SA
1 piece
1400
8MR5 140–1SA
1 piece
1400 400/440
8MR5 144–1SA
1 piece
1800
8MR5 180–1SA
1 piece
2500
8MR5 250–1SA
1 piece
3200 230
8MR4 320–2SB
1 piece
5000
8MR4 500–2SB
1 piece
Roof-mounted air-conditioners
810 230
8MR5 081–1DA
1 piece
1150
8MR5 115–1DA
1 piece
1600
8MR5 160–1DA
1 piece
3000 400
8MR5 300–1DA
1 piece
3200 400
8MR4 320–2DB
1 piece
5000
8MR4 500–2DB
1 piece
* You can order this quantity or multiples thereof.
Air-Conditioning/cooling Units
9/4
Siemens LV 56 · 2008
Air-Conditioning Products
9
■
Description
Air-air principle (8ME78)
The heat exchangers working according to the air-air principle use two fully separate air circuits: an exterior circuit and an inner circuit.
A fan draws in cold air from the exterior. By means of another fan the hot interior air is conveyed to an element separated by laminas, which, in its turn, conveys the air onto the exterior circuit.
Air-water principle (8MR5)
The heat exchangers working according to the air-water principle use 1 air circuit.
A fan conveys the hot air inside the cubicle to the heat exchanger.
In this manner, the heat is transferred to the cooling medium (water) and the temperature of the air inside the cubicle is reduced.
Notice - the standard colour is RAL 7032: special colour orders must be defined with -Z Z = specify the RAL.
■
Selection and ordering data
Version VoltageV
Size Ordering code UI*
Heat exchangers
Aluminium, not treated 220-240 16/06
8ME7 844-0
1 piece
Painted RAL 7032 220-240 16/06
8ME7 844-1
1 piece
Aluminium, not treated 220-240 20/06
8ME7 864-0
1 piece
Painted RAL 7032 220-240 20/06
8ME7 864-1
1 piece
PowerW
VoltageV
H
×
W
×
Dmm
Ordering code UI*
Heat exchangers for side mounting
650 230 500
×
200
×
100
8MR5 065-2WS
1 piece
1000 500
×
200
×
100
8MR5 100-2WS
1 piece
1450 1350
×
390
×
189
8MR5 145-2WS
1 piece
1500 950
×
400
×
115
8MR5 150-2WS
1 piece
2450 230 1350
×
390
×
189
8MR5 245-2WS
1 piece
3000 950
×
400
×
190
8MR5 300-2WS
1 piece
4000 860
×
560
×
137
8MR5 400-2WS
1 piece
5000 1400
×
460
×
235
8MR5 500-2WS
1 piece
Heat exchangers for roof mounting
1450 230 600
×
390
×
140
8MR5 145-2WD
1 piece
2100 720
×
465
×
190
8MR5 210-2WD
1 piece
35 C°
25 C°
NSE0_01391
Hot air fromthe equipment
Cubicle
Cold airrecirculation
Heat Exchangers
* You can order this quantity or multiples thereof.
9/5
Siemens LV 56 · 2008
Air-Conditioning Products
9
■
Applications
Cubicle heaters are used to prevent malfunctions probably caused by condensation formation and corrosion phenomena as well as to maintain a minimum interior temperature.
The design of the aluminium profile ensures even temperature distribution, making for optimised heating effects.
■
Configuration
To prevent corrosion problems, the difference between exterior and interior temperatures must be about 5K.
The required heating power can be determined from the Pv /
∆
T diagram given in chapter 12/9.
P
Heizung
= Pv x k3 x k4 x k5 x k6
■
Selection and ordering data
Power W
VoltageV
Series Ordering code UI*
Heaters
10 110-250 HGK047
8MR2 110-0B
2 pieces
20 HGK047
8MR2 110-2B
2 pieces
30 HGK047
8MR2 110-3B
2 pieces
15 110-250 HG140
8MR2 130-1A
2 pieces
20 HG140
8MR2 130-3A
2 pieces
45 HG140
8MR2 130-4A
1 piece
60 HG140
8MR2 130-6A
1 piece
75 HG140
8MR2 130-7A
1 piece
100 HG140
8MR2 130-0A
1 piece
150 HG140
8MR2 130-5A
1 piece
Fan Heaters
Thermostats
■
Applications
The (NC/NO) thermostats installed in cubicles are used to control the interior temperature and make sure that the admissible temperatures of the devices are not exceeded.
They are used to control the operation of cooling units, filter fans, heat exchangers.
■
Selection and ordering data
Version Temperature°C
Series Ordering code UI*
Thermostats
NC 0 ... + 60 KTO 01140
8MR2 170-1BA
3 pieces
– 10 ... + 50 KTO 01140
8MR2 170-1CA
3 pieces
+ 20 ... + 80 KTO 01140
8MR2 170-1DA
3 pieces
NO 0 ... + 60 KTS 01141
8MR2 170-1BB
3 pieces
– 10 ... + 50 KTS 01141
8MR2 170-1CB
3 pieces
+ 20 ... + 80 KTS 01141
8MR2 170-1DB
3 pieces
Twin thermostat
NC/NO + 20 ... + 80 ZR 011
8MR2 170-1E
2 pieces
Mechanical thermostats
CO + 10 ... + 60 FZK 011
8MR2 170-1A
2 pieces
– 20 ... + 30 FZK 011
8MR2 170-1B
1 piece
* You can order this quantity or multiples thereof.
9/6
Siemens LV 56 · 2008
Air-Conditioning Products
9
Notes
Siemens LV 56 · 2008
10
Accessories
10/2 Fasteners
10/3 Miscellaneous Parts
10/2
Siemens LV 56 · 2008
Accessories
10
Fasteners
■
Selection and ordering data
Description Ordering code UI
Fasteners for mechanical connections
Self-tapping screw DIN 7500 - M6x10
8PQ9500-0BA34
100
Self-tapping screw DIN 7500 - M6x16
8PQ9500-0BA32
100
Self-tapping screw DIN 7500 - M6x20
8PQ9500-0BA31
100
RAL7035 caps for self-tapping screws
8PQ9400-0BA14
100
Self-tapping hex-head screw DIN 7500 - M6x12
8PQ9500-1BA07
100
Description Ordering code UI
Fasteners for electrical connections, rectangular profiles
1
Carriage bolt DIN 603 - M10x35
8PQ9500-0BA14
50
Carriage bolt DIN 603 - M10x45
8PQ9500-0BA16
50
Carriage bolt DIN 603 - M10x55
8PQ9500-1BA36
50
Carriage bolt DIN 603 - M10x65
8PQ9500-1BA25
50
Busbar connection kit for M10 screw
8PQ9400-0BA02
20
Description Ordering code UI
Fasteners for busbar electrical connections, with H profiles H
1
T-head screw - M10x25
8PQ9500-0BA01
100
T-head screw - M10x35
8PQ9500-0BA02
100
Description Ordering code UI
Fasteners for electrical connections
1
Hexagon-head screw ISO 4017 - M8x25
8PQ9500-0BA77
50
Hexagon-head screw ISO 4017 - M8x35
8PQ9500-0BA78
50
Hexagon-head screw ISO 4017 - M12x40
8PQ9500-0BA88
50
Hexagon-head screw ISO 4014 - M12x50
8PQ9500-0BA64
50
Hexagon-head screw ISO 4014 - M12x60
8PQ9500-1BA02
50
Hexagon-head screw ISO 4014 - M12x80
8PQ9500-1BA51
50
Hexagonal nut ISO 4032 - M8
8PQ9500-0BA07
50
Hexagonal nut ISO 4032 - M10
8PQ9500-0BA05
50
Hexagonal nut ISO 4032 - M12
8PQ9500-0BA04
50
Clamping washer DIN 6796 - 8
8PQ9500-0BA58
50
Clamping washer DIN 6796 - 10
8PQ9500-0BA60
50
Clamping washer DIN 6796 - 12
8PQ9500-0BA61
50
Washer DIN 125 - 8.4
8PQ9500-0BA70
50
Washer DIN 125 - 10.5
8PQ9500-0BA67
50
Washer DIN 125 - 13
8PQ9500-1BA33
50
Lock washer BN208012 - 8
8PQ9500-0BA48
50
Lock washer BN208012 - 10
8PQ9500-0BA50
50
Lock washer BN208012 - 12
8PQ9500-0BA51
50
01
71
90
17
20
01
74
30
17
42
1) For electrical connections make exclusive use of 8.8 strength class fasteners.
10/3
Siemens LV 56 · 2008
Accessories
10
Miscellaneous Parts
■
Selection and ordering data
Description Ordering code UI
Column ID plate
“SIVACON SIEMENS” ID plate
8PQ9400-0BA06
1
Door and special covers
1/4 turn screws
8PQ9400-0BA17
20
Rotary handle with flat cylinder, hinged on left side
8PQ9400-0BA07
1
Button operated handle, lockable, hinged on left side
8PQ9400-0BA08
1
Semi-cylindrical profile acc. to DIN 18252/18254 8x45°, adjustable, various locks
8PQ9400-0BA26
1
Key with two-way locking mechanism, 3mm
8PQ9400-0BA12
10
Mechanical accessory parts
Crossbar for installation in cubicle, 400mm wide
8PQ3000-0BA12
2Crossbar for installation in cubicle, 600mm wide
8PQ3000-0BA71
2Crossbar for installation in cubicle, 800mm wide
8PQ3000-0BA72
2Crossbar for installation in cubicle, 1000mm wide
8PQ3000-0BA84
2Crossbar for installation in cubicle, 1200mm wide
8PQ3000-0BA85
2Crossbar for installation in cubicle, 400mm deep, with side upright or 600mm, 800mm deep
8PQ3000-0BA10
2Crossbar for installation in cubicle, 600mm deep (without side upright)
8PQ3000-1BA24
2Crossbar for installation in cubicle, 800mm deep (without side upright)
8PQ3000-1BA25
2
Universal mounting bracket
8PQ9400-0BA01
10
Cable bracket, C30 profile, cubicle depth 400mm, 600mm, 800mm
8PQ3000-0BA38
5Cable bracket, C30 profile, cubicle width 400mm
8PQ3000-0BA41
5Cable bracket, C30 profile, cubicle width 600mm
8PQ3000-0BA42
5Cable bracket, C30 profile, cubicle width 800mm
8PQ3000-0BA43
5Cable bracket, C30 profile, cubicle width 1000mm
8PQ3000-0BA86
5Cable bracket, C30 profile, cubicle width 1200mm
8PQ3000-0BA87
5Corner piece to fasten cable brackets
8PQ3000-0BA73
10
Double profile DIN rail, 35mm, L = 1600mm
8PQ9600-0BA01
1
Lifting eyebolts
8PQ9400-0BA11
4
Lifting brackets for 400mm wide cubicle
8PQ3000-0BA88
2
Lifting brackets for 600mm wide cubicle
8PQ3000-1BA00
2
Lifting brackets for 800mm wide cubicle
8PQ3000-1BA01
2
Lifting brackets for 1000mm wide cubicle
8PQ3000-1BA02
2
Lifting brackets for 1200mm wide cubicle
8PQ3000-1BA03
2
02
12
00
21
54
01
71
70
21
21
02
12
20
00
04
01
68
10
16
68
01
68
20
16
84
01
66
90
17
15
10/4
Siemens LV 56 · 2008
Accessories
10
Miscellaneous Parts
■
Selection and ordering data
Description Ordering code UI
Electrical accessories
Lamp with 11 W fluorescent tube, Schuko socket, On/Off switch and magnetic clamp
8MF4900
1
Schuko socket max 250 V, with 6,3 A fuse, mounting on 35 mm DIN rail
8MF9300
1
Schuko socket max 250 V, without 16 A fuse, mounting on 35 mm DIN rail
8MF9005
1
Limit switch for single door, 1 NO/NC
8MF4310
1
Limit switch for double door, 1 NO/NC
8MF4311
1
Door grounding strip, 6mm
2
8PQ9400-0BA15
10
Cable entry for segregation
8PQ9400-0BA16
20
Tools
Bit for Torx screwdriver M6 1/4” 50mm
8PQ9400-0BA05
5
Bit for Torx screwdriver M6 1/4” 200mm
8PQ9400-0BA10
2
Screwdriver with case and charger
8PQ9400-0BA22
1
Repair paint
Spray - RAL 7035
8GF9388-2
1
Spray basic blue-green colour
8PQ9400-0BA04
1
Other parts
Solid frames for modular devices 12 UM
8GK9910-0KK00
1
Depth adapters for modular devices from 70 to 55mm deep
8GF9670-1
1
Cover for modular devices
5ST3800
1
Instrument plug 72mm x 72mm
8GF7770-4
1
Instrument plug 96mm x 96mm
8GF7770-5
1
Plastic diagram pocket DIN A4
8GD9132
1
ID stickers, L1, L2, L3, N, PE
8GK9920-0KK27
10
02
12
40
21
25
02
12
60
21
27
02
15
50
21
56
11
Siemens LV 56 · 2008
Mechanical Dimensions
11/2 Cubicle
11/3 Base and Enclosure
11/4 Enclosure
11/6 Busbar System
11/8 Terminals
11/9 Mounting Plates
11/10 Covers, modular doors
11/11 SIVACON 8PS Duct Connections
11/15 SENTRON 3VL with Motorised Operating Mechanism
11/2
Siemens LV 56 · 2008
Mechanical Dimensions
11
Cubicle
■
Structure
■
Floor anchoring of cubicle without base
01
75
0
01
75
2
01
75
3
WWidth
dDepth
hHeight
400 400 2000
600 600
800 800
1000
1200
d L2 w L1
400 350,0 400 250,0
600 550,0 600 450,0
800 750,0 800 650,0
1000 850,0
1200 1050,0
d L2 w L1
400 350,0 400 310,0
600 550,0 600 510,0
800 750,0 800 710,0
1000 910,0
1200 1110,0
11/3
Siemens LV 56 · 2008
Mechanical Dimensions
11
Base and Enclosure
■
Base
01
75
5
d L2 w L1
400 350,0 400 250,0
600 550,0 600 450,0
800 750,0 800 650,0
1000 850,0
1200 1050,0
■
Door, rear and side panel, with and without design strip
01
75
7
■
Top plate upgraded to IP X1
01
75
4
01
75
6
Side panel with design strip
Side panel without design strip
Rear panel
Door
01
75
8
Front view
01
75
9
Side view
11/4
Siemens LV 56 · 2008
Mechanical Dimensions
11
01
76
3
01
76
2
Enclosure
■
Top plate with cable entry
11/5
Siemens LV 56 · 2008
Mechanical Dimensions
11
01
76
10
17
60
Enclosure
■
Bottom plate with cable entry
11/6
Siemens LV 56 · 2008
Mechanical Dimensions
11
NSE
X_0
00
06
01
76
8
01
76
6
01
76
4
01
76
5
01
76
7
Busbar System
■
Main busbar systems in standard position
■
Busbar systems in free position
■
Grounding bar PE
11/7
Siemens LV 56 · 2008
Mechanical Dimensions
11
01
77
0
01
76
9
01
77
2
01
77
1
Busbar System
■
Vertical busbar systems, cascaded
■
Vertical busbar systems, non-cascaded
11/8
Siemens LV 56 · 2008
Mechanical Dimensions
11
01
74
9
01
78
4
01
78
3
Terminals
■
Terminal
up to 250 A up to 400 A up to 630 A
■
Busbar arrangement
11/9
Siemens LV 56 · 2008
Mechanical Dimensions
11
01
77
5
01
77
4
01
77
3
01
78
1
01
77
7
01
77
9
01
77
8
Mounting Plates
■
Modular mounting plates, with and without holes
■
Galvanised chrome plate for electrotechnical applications
Position L
A 86,0
B 106,0
C 126,0
D 145,0
E 175,0
F 204,0
G 210,0
H 229,0
I 249,0
K 264,0
L 284,0
w L
600 253
800 353
w L
400 320
600 520
800 720
1000 920
1200 1120
11/10
Siemens LV 56 · 2008
Mechanical Dimensions
11
Covers, Modular Doors
■
Cover
■
Modular door
02
18
3
Cover
Interior door or modular door
02
12
8
02
12
9
Position L
A 170
B 190
C 210
D 229
E 259
F 288
G 294
H 313
I 333
K 330
L 368
11/11
Siemens LV 56 · 2008
Mechanical Dimensions
11
SIVACON 8PS Duct Connections
■
SIVACON 8PS with connections to top
■
SIVACON 8PS with connections to bottom
02
18
0
02
17
9
02
18
1
02
18
2
11/12
Siemens LV 56 · 2008
Mechanical Dimensions
11
SIVACON 8PS Duct Connections
■
Cut-out in top plate for combination of RX duct with Sentron 3WL Gr I, 3, 4 poles and 3WL Gr. II, 3 poles
■
Cut-out in top plate for combination of LX duct with Sentron 3WL Gr I, 3, 4 poles and 3WL Gr. II, 3 poles
02
16
0
02
16
10
21
63
02
16
2
11/13
Siemens LV 56 · 2008
Mechanical Dimensions
11
SIVACON 8PS Duct Connections
■
Cut-out in top plate for combination of DX duct with Sentron 3WL Gr II, 3 and 4 poles
■
Cut-out in top plate for combination of duct LX05..., LX06..., LX07 with Sentron 3WL Gr. II, 3 and 4 poles
02
16
5
02
16
4
02
16
7
02
16
6
11/14
Siemens LV 56 · 2008
Mechanical Dimensions
11
SIVACON 8PS Duct Connections
■
Cut-out in top plate for combination of duct LX08... with Sentron 3WL gr. II, 3 and 4 poles
02
16
9
02
16
8
11/15
Siemens LV 56 · 2008
Mechanical Dimensions
11
SENTRON 3VL with MotorisedOperating Mechanism
■
Dimensions for equipment combination including, circuit breaker, removable or fixed door and motorised operating mechanism
02
21
2
Equipment mounting plate installed in the deepest mounting position. For rear terminal bars, the use of rear vertical partitions is limited.
* In sectioning position, the dimensions increase from 27 to 32mm. Take into account the additional space necessary to pull out the equipment.
Dimensions when set to ON * [mm]
Above the cover
A
Above the cubicle
B
Above the inner door
C
VL 160-250 50 -12 -37
VL 400 72 10 -14
VL 630 111 48 23
VL 800 105 43 18
VL 1250/1600 126 62 37
11/16
Siemens LV 56 · 2008
Mechanical Dimensions
11
Notes
12
Siemens LV 56 · 2008
Planningand Configuration
12/2 SIMARIS CFB
12/3 Configuration Procedure
12/4 Check List for SIVACON S4
12/6 Correction Factors
12/8 Internal Temperature ofLow-Voltage Power Distribution Boards
12/10 Example
12/2
Siemens LV 56 · 2008
Planning and Configuration
12
■
Overview
With SIMARIS CFB easy planning and programming
SIMARIS CFB facilitates offer processing and project execution thanks to the following functions:
• Management of project and customer data
• Configuration of SIVACON S4 low-voltage distribution board with integrated selection of specific equipment and devices as a function of geographic location
• Price determination/calculation
• Output functions: list of components, images, SingleLine, bid documents
It is always possible to integrate new products, such as Alpha small distribution boards, at any time
■
Advantages
• Easy to manage Windows interface
• Integrated product database, updated by download
• Rule-based configuration with choice of characteristics not depending on product
• A detailed knowledge of products and systems is not required
• Possibility to make changes with ease at both offer and construction stage
• Many output functions
• Order placement by e-mail
• Reduced workload
SIMARIS CFB
12/3
Siemens LV 56 · 2008
Planning and Configuration
12
■
Overview
The planning and configuration of low-voltage power distribution boards is an important, cost-determining factor within the scope of power distribution board construction. The following notes are based on a network calculated with a special procedure. This chapter is to support the manufacturer of power distribution
boards with the planning and configuration of low-voltage power distribution boards. Additionally, the manufacturer has to comply with international standards and regional provisions. The terms used are explained in the Appendix.
■
Configuration procedure
1. Reading of specification and determination of characteristics (check list)- Network system, voltage level- Transformer power, input currents, short-circuit strength- Ambient temperature, degree of protection- Mounting type (single-front / back-to-back / free-standing /
wall)- Arrangement of power distribution board / installation
surface (operating and maintenance aisles, escape direction)
- Type of connection (cable or busbar)- Access to cable, busbar connection (front, rear)- Cable/busbar entry (top, bottom)- Ambient conditions (condensation, chemical emissions)- Device installation systems (fixed, plug-in, withdrawable
design)- Safety requirements (internal separation, resistance to
internal arcs)- Date of delivery (tender / order)- Reserve
2. Configuration of power distribution board (conversion of characteristics into power distribution board technology)- Determination of the busbar system- Arrangement of incoming feeders and couplings- Determination of feeders- Feeder-section allocation
3. Optimisation of power distribution boards- Optimised space utilisation concerning:
• Device selection• Feeder arrangement
- Cost optimisation concerning:• Device selection• Busbar version (reduced cross-section with centre
infeed)
4. Testing of power distribution board configuration- Determination of the power loss per section- Determination of the section's internal temperature- Verification that the section’s internal temperature <= max.
ambient temperature of the applied devices- Determination of the reduction factors in accordance with
the calculated ambient temperature of the applied devices- Verification that max. operating current <= rated current x
reduction factor- If one of the conditions to be verified is not complied with,
the power distribution board configuration has to be modified concerning• device selection• feeder arrangement and the tests must be repeated..
Configuration Procedure
12/4
Siemens LV 56 · 2008
Planning and Configuration
12
Check List for SIVACON S4
■
Check List for SIVACON S4
Project name: ______________________________________________________________________________________
Customer: _______________________________________________________________________________________
Planner: _______________________________________________________________________________________
Date of delivery:__________________
Installation site/height: _______ m (above MSL)
Ambient temperatue: _______ °C Relative air humidity: ______________ %
Condensation risk?
�
yer
�
no
Harmful substance:_____________________________________
Mounting type:
�
single-front
�
back-to-back
�
wall
�
free-standing
Degree of protection to interior: IP _______________ Internal separation: form _____________
Degree of protection to cable floor: IP _______________
Requirements regarding resistence to internal arcs:
�
yes
�
no
�
which: _______________________
Maximum distribution board dimensions: W
×
H
×
D ______________ mm Room height: __________ mm
Maximum transport dimensions: W
×
H
×
D ______________ mm
Network type:
�
TN-S
�
TN-C
�
TN-C-S
�
TT
�
IT
Cross-section PEN/N:
�
reduced ________%
�
full 100%
�
IEC
Cross-section PE:
�
acc. to type test
�
25% of external conductor cross-section
Transformer power: ________________________ kVA
Rated current of infeed: ________________________ A
Frequency: ________________________ Hz
Rated operating voltage: ________________________ V
Rated short-time withstand current I
cw
(1 sec.) ________________________ kA
12/5
Siemens LV 56 · 2008
Planning and Configuration
12
Check List for SIVACON S4
Infeeds
Connection:
�
busbar
�
cable
Access to calbe/busbar entry:
�
from the front
�
from the rear
Cable / busbar entry:
�
top
�
bottom
Intallation system for switching devices:
Air circuit breakers(ACB):
�
fixed-mounted
�
withdrawable
Molded case circuit breakers (MCCB)
≥
630A:
�
fixed-mounted
�
withdrawable
Molded case circuit breakers (MCCB) <= 630A:
�
fixed-mounted
�
withdrawable
�
plug-in design
Switch disconnectors (LBS)
�
fixed-mounted
�
fuseless
�
fused
Remarks: __________________________________________________________________________________
__________________________________________________________________________________
Feeders
Connection:
�
busbar
�
cable
Access to calbe/busbar entry:
�
from the front
�
from the rear
Cable / busbar entry:
�
top
�
bottom
Intallation system for switching devices:
Air circuit breakers(ACB):
�
fixed-mounted
�
withdrawable
Molded case circuit breakers (MCCB)
≥
630A:
�
fixed-mounted
�
withdrawable
Molded case circuit breakers (MCCB) <= 630A:
�
fixed-mounted
�
withdrawable
�
plug-in design
Switch disconnectors (LBS)
�
fixed-mounted
�
fuseless
�
fused
Remarks: __________________________________________________________________________________
__________________________________________________________________________________
Feeder reserve: _______________ %
Empty space reserve: _______________ %
Miscellaneous: __________________________________________________________________________________
__________________________________________________________________________________
12/6
Siemens LV 56 · 2008
Planning and Configuration
12
The low air density at altitudes over 2000 m affects the electrical characteristics of the power distribution board. The rated
currents are subject to the following correction factors for installation heights above 2000 m over MSL..
Correction Factors
■
Rated currents and initial short-circuit AC currents of three-phase distribution transformers with 50 to 3150 KVA
Rated voltage U
cT
400/230, 50 Hz 525 V, 50 Hz 690/400 V, 50 Hz
Rated value of the short-circuit voltage u
k
t
4%
1)
6%
2)
4%
1)
6%
2)
4%
1)
6%
2)
Rated power Rated current
I
r
Initial short-circuit AC current
I
k
3)
Rated current
I
r
Initial short-circuit AC current
I
k
3)
Rated current
I
r
Initial short-circuit AC current
I
k
3)
kVA A A A A A A A A A
50 72 1933 1306 55 1473 995 42 1116 754
100 144 3871 2612 110 2950 1990 84 2235 1508
160 230 6209 4192 176 4731 3194 133 3585 2420
200 288 7749 5239 220 5904 3992 167 4474 3025
250 360 9716 6552 275 7402 4992 209 5609 3783
315 455 12247 8259 346 9331 6292 262 7071 4768
400 578 15506 10492 440 11814 7994 335 8953 6058
500 722 19438 13078 550 14810 9964 418 11223 7581
630 910 24503 16193 693 18669 12338 525 14147 9349
800 1154 – 20992 880 – 15994 670 – 12120
1000 1444 – 26224 1100 – 19980 836 – 15140
1250 1805 – 32791 1375 – 24984 1046 – 18932
1600 2310 – 41857 1760 – 31891 1330 – 24265
2000 2887 – 52511 2200 – 40008 1674 – 30317
2500 3608 – 65547 2749 – 49941 2090 – 37844
3150 4550 – 82656 3470 – 62976 2640 – 47722
1)
u
k
r
= 4%, standardised in accordance with DIN 42503 for Srt = 50 ... 630 kVA2)
u
k
r
= 6%, standardised in accordance with DIN 42511 for Srt = 100 ... 1600 kVA3)
I
k
Unaffected initial short-circuit AC current of the transformer upon connection to a network with unlimited short-circuit power considering the voltage factorand the correction factor of the transformer impedance in acc. with DIN EN 60909 I DIN VDE 0102 (July 2002)
■
Correction factors for installation heights over 2000 m above MSL
Correction factors for installation heights over 2000 m above MSL
Altitude ofinstallation site
K1 for the load
up to
up to
up to
up to
2200 m2400 m2500 m2700 m2900 m
3000 m3300 m3500 m
4000 m4500 m
5000 m
0,880,870,860,850,84
0,830,820,81
0,780,76
0,74
I
n
= I
n <= 2000 m
x k1
If the boards are erected at altitudes over 2000 m, the devices' reduced switching capacity must be taken into account. For the
correction factors, refer to the technical documents of the devices.
■
Reduced switching capacity for erection heights over 2000 m above MSL
12/7
Siemens LV 56 · 2008
Planning and Configuration
12
■
Correction factors for busbar systems at ambient temperatures of <> 35 °C
The rated currents for main busbar and distribution busbar systems indicated in the catalogue refer to the ambient temperatures for indoor installation described in IEC/EN 60439-1.Consequently, the ambient temperature for low-voltage power
distribution boards does not exceed +40 °C and the average value of a period of 24 h is not higher than +35 °C. For ambient temperatures, whose average value deviates from this ambient temperature, the following correction factors must be observed.
I
n
= I
n 35 °C
x K2
■
Correction factors for devices
At ambient temperatures of >40 °C, the rated operating current has to be derated for devices. The ambient temperature of the devices complies with the internal temperature of the lowvoltage
power distribution boards at the installation site. For the correction factors, refer to the technical documents of the devices.
Correction Factors
0,8
0,85
0,9
0,95
1
1,05
1,1
1,15
15 20 25 30 35 40 45 50 55
Ambient temperature [°C](1) Main busbars(2) Vertical disribution busbars
K2
1
2
12/8
Siemens LV 56 · 2008
Planning and Configuration
12
Internal Temperatureof Low-Voltage Power Distribution Boards
■
Determination of the internal temperature of low-voltage power distribution boards
With a calculation in accordance with IEC 60890, the internal temperature of low-voltage power distribution boards can be specified on the basis of the total power loss and the system structure.
1. Power loss of busbar systems per section
For the determination of the power loss of main busbars and distribution busbar systems, the operating current [A] on the respective length [m] has to be specified. The power loss assigned to the respective busbar configuration is illustrated in the following diagram.
P
V Main busbar system
= P
V
[W/m] x Länge [m]P
V Distribution busbar system
= P
V
[W/m] x Länge [m]P
V Busbar system/section
= P
V main busbar system
+ P
V distribution busbar system
(1) 2x(20x10) mm2
(2) 2x(30x10) mm2
(3) 4x(20x10) mm2
(4) 4x(30x10) mm20
200
400
600
800
1000
0 500 1000 1500 2000 2500I [A]
Pv
[W/m
] 4
3
2
1
Main busbar systems
Distribution busbar systems
(5) 4x(40x10) mm2
(6) 4x(50x10) mm2
(7) 2x4x(20x10) mm2
(8) 2x4x(30x10) mm2
0
200
400
600
800
1000
1200
0 500 1000 1500 2000 2500 3000 3500 4000I [A]
Pv
[W/m
]
5
6
7
8
0
100
200
300
400
500
600
0 200 400 600 800 1000 1200 1400
I [A]
910
11
12
Pv
[W/m
]
(9) DIN rail 30x30 mm(10) DIN rail 40x30 mm(11) 2x(30x10) mm2
(12) 2x(40x10) mm2
12/9
Siemens LV 56 · 2008
Planning and Configuration
12
Internal Temperatureof Low-Voltage Power Distribution Boards
■
Determination of the internal temperature of low-voltage power distribution boards
2. Power loss of devices per section
For the power loss, refer to the technical documents of the devices. In this context, the actual utilisation (operating current, temporal simultaneousness, rated load factor) has to be observed.
For terminal bars, cables and lines as well as for small devices, a percentage increase of 10% has to be considered.
I
r
= operating current
I
n
= rated current
P
Vn device
= power loss device at rated current
P
V device
= P
V devicet
x (I
r
/ I
n
)
2
P
V device / section
= total (P
V device
) x 1,1
3. Installed power loss per section
The installed power loss per section is the sum of the power loss of busbar systems and devices.
P
V section
= PV busbar system / section+ PV device/section
4. Determination of the section’s internal temperature
The diagram below illustrates the correlation between the installed power loss and the temperature difference, based on the calculation procedure of IEC 60890 as well as the specific data of SIVACON S4. The diagram refers to a section in degree of protection IP55 which is installed side-by-side with a free roof and rear panel. In case of deviating conditions, the correction factors of the following table have to be considered.
Ventilated sectionDegree of protection <= IP4Xk3
Section with freeside panelk4
1,65 1,09
Roof not free
k5
Rear panel not free
k6
0,95 0,92
PV =
(1) 2000x400x600(2) 2000x400x800(3) 2000x600x400(4) 2000x600x600
dT
[K
]
Height x width x depth [mm] of the section
Pdiss [W]
(5) 2000x600x800(6) 2000x800x400(7) 2000x800x600(8) 2000x800x800
0,0
5,0
10,0
15,0
20,0
25,0
30,0
35,0
40,0
0 100 200 300 400 500
1
2 3
4
56 7
8
The determined temperature difference refers to the average height in the section. The temperature linearly increases from the average section height to the complete section height with sufficient accuracy and has to be specified for SIVACON S4 with a correction factor of 1.4.
Internal temperature in average section height [°C] = Ambient temperature of the power distribution board [°C] + temperature difference dT [K]
Internal temperature in complete section height [°C] = Ambient temperature of power distribution board [°C] + Temperature difference dT [K] x 1.4
PV section
k3 x k4 x k5 x k6
12/10
Siemens LV 56 · 2008
Planning and Configuration
12
Example
■
Example for a power distribution board configuration test
Power distribution board data
Rated operating voltage Ue 400V / 50HzRated short-time current Icw 35kARated load factor 0.8Degree of protection IP40Ambient temperature 35 °CSection height 2000mmBase height 100mmSection depth 600mmCable connection infeed from the topCable connections outputs rear bottom
(rear panel free)Front view
Determination of the power loss per section
P
V section 1
= (P
V busbar system section 1
+ P
V device section 1
) x 1,1 = 743,81 W
P
V section 2
= (P
V busbar system section 2
+ P
V device section 2
) x 1,1 = 354,82 W
Determination of the internal temperature
Factors section 1k3 1.65k4 1.09k5 0.85k6 1
Factors section 2k3 1.65k4 1.09k5 1k6 1
P
V section 1
= 486.56 WP
V section 2
= 197.29 W
Internal temperature in acc. with diagram page 12/9
Temperature difference in half section height section 1 22 KTemperature difference in half section height section 2 12 K
Internal temperature in half section height for section 1 57 °CInternal temperature in half section height for section 2 47 °C
Internal temperature in section height for section 1 66 °CInternal temperature in section height for section 2 52 °C
Configuration test
According to the technical documents of the devices, the limit temperatures are not exceeded.
The devices are able to carry the specified rated currents.
01
62
5
Determination of the power loss of the busbar systems per section
P
V busbar section 1
= 86,6 W
Determination of devices power lass per section
P
V device section 1
= 597.46 W x 1.1 = 657.21 W
P
V device section 2
= 322.56 W x 1.1 = 354.82 W
I
n
×
0,8 [A] Lenght [m] P
V busbar system
[W/m]P
V busbar system
[W]
Section 1 200 0,45 8 3,6
520 0,2 50 10
904 0,3 160 48
704 0,25 100 25
Location I
n
[A] I
n
x 0,8 [A] P
V device max
[W] P
V device
[W]
Section 1 Infeed 01.D1 1424 – 825 495.06
Output 01.J1 250 200 80 51.20
Output 01.K1 250 200 80 51.20
Section 2 Output 02.D1 250 200 80 51.20
Output 02.F1 400 320 170 108.80
Output 02.K2 630 504 254 162.56
13
Siemens LV 56 · 2008
Appendix
13/2 Glossary
13/8 Order Information
13/10 Standards and Approvals
13/11 Quality Management
13/12 Online Services
13/13 Customer Support
13/14 Training
13/15 Subject Index
13/16 Conditions of Sale and Delivery, Export Regulations
13/2
Siemens LV 56 · 2008
Appendix
13
Glossary
■
Rated values/definitions
The terms defined below are used in the present catalogue in accordance with IEC 60439-1 and EN 60439-1.
Low-voltage switchgear and controlgear assembly
IEC/EN 60439-1; 2.1.1
Assembly of one or more switching devices combined with corresponding operating equipment for control, measuring and signalling tasks and with protective and control devices, etc. The individual devices are completely assembled by the manufacturer, including all internal electrical and mechanical connections and construction components.
Type-tested low-voltage switchgear and controlgear assembly (TTA)
IEC/EN 60439-1; 2.1.1.1
Low-voltage switchgear and controlgear assembly which complies with the original type or system of the switchgear and controlgear assembly type-tested in accordance with this standard without significant deviations.
Functional unit
IEC/EN 60439-1; 2.1.5
Part of a switchgear and controlgear assembly with all electrical and mechanical components which contribute to the execution of the same function.
Cubicle
IEC/EN 60439-1; 2.4.1
Component of a switchgear and controlgear assembly which serves the accommodation of various components of a switchgear and controlgear assembly or of an enclosure.
Section
IEC/EN 60439-1; 2.2.1
Component of a switchgear and controlgear assembly positioned between two successive vertical limiting levels.
Rated values
In accordance with IEC/EN 60439-1;4, the manufacturers of lowvoltage switchgear and controlgear assemblies state rated values. These rated values apply to the specified operating conditions and characterise the usability of switchgear and controlgear assemblies. The coordination of the operating equipment or the configuration of the switchgear and controlgear assemblies must be based on these rated values.
Rated short-time withstand current (Icw)
IEC/EN 60439-1; 4.3
As the effective short-circuit current value, the rated short-time withstand current characterises the thermal strength of switchgear and controlgear assembly circuits during a short-time load. The rated short-time withstand current is normally determined for the duration of 1 sec; deviating time values must be indicated. The rated short-time withstand current is stated for the distribution and/or main busbars of switchgear and controlgear assemblies.
Rated peak withstand current (Ipk)
IEC/EN 60439-1; 4.4
As peak value of the peak current, the rated peak withstand current characterises the dynamic strength of switchgear and controlgear assembly circuits. The rated peak withstand current is stated for the distribution and/or main busbars of switchgear and controlgear assemblies.
Section panel
IEC/EN 60439-1; 2.2.2
Component of a switchgear and controlgear assembly positioned between two superimposed horizontal limiting levels inside a section.
Compartment
IEC/EN 60439-1; 2.2.3
Section or section panel which is encased with the exception of openings required for connection, control or ventilation.
Transport unit
IEC/EN 60439-1; 2.2.4
Part of a switchgear and controlgear assembly or complete switchgear and controlgear assembly which is not disassembled for transportation.
Rated diversity factor
IEC/EN 60439-1; 4.7
The rated diversity factor of a switchgear and controlgear assembly or of a component of a switchgear and controlgear assembly (e.g. section, section panel) which comprises several main circuits is the ratio of the largest sum of all currents which are to be expected in the respective main circuits at any given time to the sum of the rated currents of all main circuits of the switchgear and controlgear assembly or of the affected part of the switchgear and controlgear assembly. If the manufacturer states a rated diversity factor, this value must be taken as a basis for the temperature-rise test.
Rated conditional short-circuit current (Icc)
IEC/EN 60439-1; 4.5
The rated conditional short-circuit current corresponds to the uninfluenced short-circuit current which a circuit of the switchgear and controlgear assembly, that is protected by short-circuit protective devices, may carry without damage (for a limited time). The rated conditional short-circuit current is therefore stated for outgoing and/or incoming feeders, e.g. with circuit breakers.
Rated impulse withstand voltage (Uimp)
IEC/EN 60947-1; 4.3.1.3
Parameter for the resistance of clearances inside switching devices to impulse overvoltages. The application of suitable switching devices prevents disconnected system parts from transmitting overvoltages from the network in which they are applied.
Number of main current circuits Rated diversity factor
2 and 3 0.94 and 5 0.86 up to and including 9 0.710 uand more 0.6
13/3
Siemens LV 56 · 2008
Appendix
13
Glossary
Rated current (In) (of circuit breakers)
IEC/EN 60947-2; 4.3.2.3
Current which, for circuit breakers, corresponds to the rated continuous current and the conventional thermal current.
➔
Rated continuous current
Rated control voltage (Uc)
IEC/EN 60947-1; 4.5.1
Voltage applied to the actuating NO contact of a control circuit. It may deviate from the rated control supply voltage if transformers or resistors are connected to the control circuit.
Rated ultimate short-circuit breaking capacity (Icu)
IEC/EN 60947-2; 4.3.5.2.1
Maximum short-circuit current which can be interrupted by a circuit breaker (test O – CO). After a short-circuit switch-off, the circuit breaker is able to trip with increased tolerances in the case of overload.
Rated service short-circuit breaking capacity (Ics)
IEC/EN 60947-2; 4.3.5.2.2
The short-circuit current depending on the rated operating voltage which can be repeatedly interrupted by a circuit breaker (test O – CO – CO). After the short-circuit breaking, the circuit breaker is able to continue to carry the rated current in the case of increased selfheating and to trip in case of overload.
➔
Rated continuous current
➔
Rated operating voltage
Rated operating capacity
IEC/EN 60947-1; 4.3.2.3
Capacity which can be switched by switching devices with the assigned rated operating voltage in accordance with the utilisation category, e.g. power contactor of utilisation category AC-3: 37 kW at 400 V.
Rated operating voltage (
Ue
)
IEC/EN 60947-1; 4.3.1.1
Voltage to which the characteristic values of switching devices are referred to. The maximum rated operating voltage must, in no case, exceed the rated insulation voltage.
➔
Rated insulation voltage
Rated operating current (Ie)
IEC/EN 60947-1; 4.3.2.3
Current which can be carried by switching devices in consideration of the rated operating voltage, the operating time, the utilisation category and the ambient temperature.
➔
Rated operating voltage
Rated continuous current (Iu)
IEC/EN 60947-1; 4.3.2.4
Current which can be carried by switching devices in continuous operation (for weeks, months or years).
Rated making capacity
IEC/EN 60947-1; 4.3.5.2
Current which can be switched on by switching devices with the respective rated operating voltage in accordance with the utilisation category.
➔
Rated operating voltage
Rated frequency
IEC/EN 60947-2; 4.3.3
Frequency for which switching devices are dimensioned and to which the other characteristic data refer.
➔
Rated operating voltage, rated continuous current
Rated insulation voltage (Ui)
IEC/EN 60947-1; 4.3.1.2
Voltage to which the insulation tests and creepage distances refer. The maximum rated operating voltage must, in no case, exceed the rated insulation voltage.
➔
Rated operating voltage
Rated short-circuit breaking capacity (Icn)
IEC/EN 60947-1; 4.3.6.3
Maximum current which can be switched off by switching devices with the rated operating voltage and frequency without causing damage. The value is stated as effective value.
➔
Rated operating voltage
Rated short-circuit breaking capacity (Icm)
IEC/EN 60947-1; 4.3.6.2
Maximum current which can be switched on by switching devices with a certain rated operating voltage and frequency without causing damage. Deviating from the other characteristic data, the value is stated as peak value.
➔
Rated operating voltage
13/4
Siemens LV 56 · 2008
Appendix
13
Glossary
■
Ambient conditions / Degrees of protection
The climate and external ambient conditions (natural impurities, toxic chemically active substances, small animals) may have severe repercussions on the functionality of electrical systems. The effect depends on the climatic protection of the room in which the system is installed.In the presence of high concentrations of toxic substances it is advisable to adopt appropriate measures to reduce them, for example:– Intake of air from an area with a lower pollution level
– Exposing the area to a mild overpressure (e.g., introducing non polluted air into the system)
– Climate control of the room where the system is installed (reducing the temperature, relative humidity of the air < 60%, possible installation of a purifying filter)
– Attenuation of overheating (overdimensioning of electrical equipment and components such as main busbars and distribution busbars)
Ambient conditions Class Classification of ambient conditions with the relative limit values (defined according to standard IEC 60721-3-3)
Measurements
Climatic 3K4 Minimum temperature of the airMaximum temperature of the air
Minimum relative humidity of the airMaximum relative humidity of the airMinimum absolute humidity of the airMaximum absolute humidity of the airTemperature variation rateMinimum air pressureMaximum air pressureSolar radiationThermal radiationMovement of the airCondensate formation
Matter deposited by the windWater (other than rain)
Ice accumulation
– 5 °C
1)
+ 40 °C + 35 °C (24h-Mittel)
2)
5 %95 %1 g/m_29 g/m_0,5 °C/min70 kPA106 kPA700 W/m
2
–1,0 m/spossible
NoSee other ambient climatic conditionsNo
–
Provide heating, if frequent 1 per day for 2 hours
Other ambient climatic conditions
3Z1
3Z73Z93Z10
Thermal radiation is negligible
Water drops as defined in standard IEC 60068-2-18Water spray as defined in standard IEC 60068-2-18Water jets as defined in standard IEC 60068-2-18
IPX1 IPX4IPX5
Biological 3B2 Flora
Fauna
Mold formation
Presence of rodents and other harmful animals, other than termites
IP4X, including protec-tion for technical floors
Chemically active substances
3C3 Marine saltSulphurous anhydride SO
2
Hydrogen sulphide H
2
SChlorine Cl
2
Hydrogen chloride HClHydrofluoric acid HFAmmonia NH
3
Ozone O
3
Nitrogen oxide NO
x
Salt mist
≤
2 mg/dm
2
5,0 mg/m
3
(2 ppm)3,0 mg/m
3
(2 ppm)0,3 mg/m
3
(0,1 ppm)1,0 mg/m
3
(0,7 ppm)0,1 mg/m
3
(0,06 ppm)10,0 mg/m
3
(14,3 ppm)0,1 mg/m
3
(0,05 ppm)3,0 mg/m
3
(1,66 ppm)
Mechanically active substances
3S1
3S3
Sand in the airDust (matter in suspension)Dust (matter deposited)
Sand in the airDust (matter in suspension)Dust (matter deposited)
–0,01 mg/m
3
0,4 mg/(m
2
* h)
300 mg/m
3
0,4 mg/m
3
15 mg/(m
2
* h)
< IP5X
≥
IP5X
1) According to standard IEC60721-3-3 the minimum admissible air temperature is + 5° C 2) Higher values can be admitted on request (see dimensioning tables)
13/5
Siemens LV 56 · 2008
Appendix
13
PE
L1
L2
L3
N
1
PEN
L1
L2
L3
1
PEN
L1
L2
L3
1
PE
N
■
Network systems
Distribution systems (network types) in acc. with IEC 60364-3 (DIN VDE 0100-300)
Determination of protective measures and selection of the electricaloperating equipment according to the distribution system.
TN systems
TN-S system
The neutral conductor and protective conductor function are consistently separated in this system.
TN-C system
The neutral conductor and protective conductor function are composite throughout the entire system.
TN-C-S system
Combination of the neutral and the protective conductor function. In one part of the system, they are composite in one conductor, while they are separated in another part.
1 Body
Glossary
13/6
Siemens LV 56 · 2008
Appendix
13
Glossary
N
L1
L2
L3
1
PE
TT system
In the TT system, one point is directly earthed; the elements of the electrical system are connected to earth electrodes which are separated from the signal earth. The TT system corresponds to the system in which today the protective measures protective earthing, RCCB and fault-voltage circuit breaker are applied.
IT system
The IT system features no direct connection between active conductors and earthed parts; the elements of the electrical system are earthed. The IT system corresponds to the system in which today the protective conductor system protective measure is applied.
First letter = Earthing condition of the supplying current source
T = Direct earthing of one pointI = Either insulation of all active parts of the
earth or connection of one point to the earth via impedance
Second letter = Earthing condition of the elements of the electrical system
T = Elements are directly earthed, irrespective of a possible earthing of one point of the current supply
N =Elements are directly connected to the signal earth; in AC current networks, the earthed point is generally the star point
Further letters = Arrangement of the neutral and the protective conductor
S = Neutral and protective conductor function by means of separated conductors
C =Neutral and protective conductor function combined in one conductor (PEN)
L1
L2
L3
1
PE
2
1 Body
2 Impedance
■
Network systems
Distribution systems (network types) in acc. with IEC 60364-3 (DIN VDE 0100-300)
Determination of protective measures and selection of the electrical operating equipment according to the distribution system.
13/7
Siemens LV 56 · 2008
Appendix
13
Glossary
2)
Minimum aisle width700 or 600 mm Escape direction Free minimum
clearance 500 mm 1)
■
Operating and maintenance aisles
1) Minimum passage height beneath covers or casings.
(in acc. with DIN VDE 0100 Part 729)
■
Minimum passage height beneath covers or casings.
1) With opposing power distribution board fronts, constriction by open doors (i.e. doors which do not close towards the escape direction) is only accountedfor on one side.
2) Door widths must be observed, i.e. a minimum door opening angle of 90°.
500
2000
700 700 700
600
700
1)
13/8
Siemens LV 56 · 2008
Appendix
13
Order Information
■
Logistics
General
Our logistics service offers “quality from the order to the delivery” pertaining to delivery service, communication and environmental protection. To maintain this high quality, we focus on the optimisation of the logistical procedures on the basis of a customised infrastructure and automatic DP order processing.
We attach major importance to personal support, deliveries in due time and area-wide transportation.
The DIN-ISO-9001 certification and a consistent quality management are vital issues for us.
The automatic DP order processing is fast, cost-effective and fail-safe. If you would like to exploit these benefits, please do not hesitate to contact us.
Packaging, packing units
Our device and shipping packagings offer protection against dust and mechanical damage during transport, thus ensuring that the customer receives the devices in a flawless condition. When selecting and designing our packagings, we set great value upon environmental compatibility, re-usability (e. g. crumpled paper instead of styrofoam chips as transport protection in shipping packages up to 32 kg) and above all, upon waste prevention.
Unless otherwise stated in the selection and ordering data of this catalogue, our devices are supplied in separate individual packages.
The device order numbers can be easily identified by means of the EAN bar code, which simplifies both order and warehouse logistics. The low-voltage controls and distribution master data include the allocation of order numbers and EAN code for data processing.
13/9
Siemens LV 56 · 2008
Appendix
13
Order Information
■
Ag and Cu surcharges
Surcharges for copper (Cu) and silver (Ag) will be added to the prices of certain products. The amount of the surcharge depends on the percentage taken from the current list price.
Calculation of the surcharges is governed by the official Ag quotation for refined silver and the applicable Cu-DEL quotation on the date of receipt of order or of call-off.
The prices for products include the price of copper calculated on the basis of a list price of
€
150/100 kg.
When small orders are placed, the costs associated with order processing are greater than the order value. We recommend therefore that you combine several small orders. Where this is not possible, we unfortunately find it necessary to charge a processing supplement of
€
20.-- to cover our costs for order processing and invoicing for all orders with a net goods value of less than
€
250.--.
■
Small orders
■
Orders for special designs
For ordering products that differ from the versions listed in the catalog, the order number specified in the catalog must be supplemented with
“–Z”
; the required features must be specified by means of the alphanumeric order codes or in plain text.
13/10
Siemens LV 56 · 2008
Appendix
13
Standards and Approvals
■
CE mark of conformity
Manufacturers of products which fall within the subject area to which EU directives apply must identify their products, instruction manuals or packaging with a CE mark of conformity.
The CE mark of conformity confirms that a product fulfills the appropriate basic requirements of all pertinent directives. The mark of conformity is a mandatory requirement for putting products into circulation throughout the EU.
All the products in this catalog are in conformance with the EU directives and bear the CE mark of conformity.
• Low-voltage directive (NS 73/23/EU)
• EMC directive (EMC 89/336/EU)
The manufacturer of the system assembled from individual modules is responsible for the preparation of the EC declaration of conformity.
■
ALPHA/LOVAG
The Low-Voltage Controls and Distribution Division of Siemens AG is a member of the "Gesellschaft zur Prüfung und Zertifizierung von Niederspannungsgeräten e.V. ALPHA" (Society for Testing and Certification of Low-Voltage Equipment), Frankfurt am Main.
The responsibility of manufacturers and the high quality of products are promoted by ALPHA by means of supportive procedural guidelines for testing equipment according to the currently valid standards.
Providing specific conditions are fulfilled, ALPHA can also issue officially recognized product certificates if required. As a member of LOVAG, ALPHA is also working towards obtaining international recognition for declarations of conformity and certificates.
LOVAG (Low-Voltage Agreement Group) is a body comprising international specialists from certification bodies and industry who are working together to create a standardized European certificate.
List of LOVAG members
ALPHA Germany ASEFA France ACAE ItalyCEBEC Belgium Intertek Semko AB SwedenAPPLUSS Spain
Appendix
Quality Management
■
Quality management
The quality management system of our A&D division complies with the international standard EN ISO 9001.
The products and systems described in this catalog are sold under application of a quality management system certified by DQS and TÜV Management Service GmbH in accordance with ISO 9001. The certificates are recognized in all IQ Net countries.
DQS Registered Certificate Nos.:
Siemens AGAutomation and Drives
• Industrial Automation SystemsReg. No.: 001323 QM
• Industrial Communication SIMATIC NETReg. No.: 002613 QM.
TÜV (German Technical Inspectorate)Registered Certificate No.:
Siemens AGAutomation and Drives
• Low-Voltage ControlsReg. No.: 12 100 16950 TMS.
BVQI Registered Certificate No.:
Siemens AGAutomation and Drives
• Electrical Installation TechnologyReg. No.: 117779
13/11Siemens LV 56 · 2008
13
13/12
Siemens LV 56 · 2008
Appendix
13
Online-Services
■
A&D in the WWW
A detailed knowledge of the range of products and services available is essential when planning and configuring automation systems. It goes without saying that this information must always be fully up-to-date.
The Siemens Automation and Drives Group (A&D) has therefore built up a comprehensive range of information in the World Wide Web, which offers quick and easy access to all data required.
Under the address
http://www.siemens.com/automation
you will find everything you need to know about products, sys-tems and services.
■
Product selection using the Offline Mall of Automation and Drives
Detailed information together with convenient interactive func-tions:
The Offline Mall CA 01 covers more than 80,000 products and thus provides a full summary of the Siemens Automation and Drives product base.
Here you will find everything that you need to solve tasks in the fields of automation, switchgear, installation and drives. All infor-mation is linked into a user interface which is easy to work with and intuitive.
After selecting the product of your choice you can order at the press of a button, by fax or by online link.
Information on the interactive catalog CA 01 can be found on the Internet under
http://www.siemens.com/automation/ca01
or on CD-ROM and DVD..
■
Easy shopping with the A&D Mall
The A&D Mall is the virtual department store of Siemens AG in the Internet. Here you have access to a huge range of products presented in electronic catalogs in an informative and attractive way.
Data transfer via EDIFACT allows the whole procedure from se-lection through ordering to tracking of the order to be carried out online via the Internet.
Numerous functions are available to support you.
For example, powerful search functions make it easy to find the required products, which can be immediately checked for avai-lability. Customer-specific discounts and preparation of quotes can be carried out online as well as order tracking and tracing.
Please visit the A&D Mall on the Internet under:
http://www.siemens.com/automation/mall
13/13
Siemens LV 56 · 2008
Appendix
13
Customer Support
.I
In the face of harsh competition you need optimum conditions to keep ahead all the time:A strong starting position. A sophisticated strategy and team for the necessary support - in every phase.Service & Support from Siemens provides this support with a complete range of different services for automation and drives.
In every phase: from planning and startup to maintenance and upgrading.
Our specialists know when and where to act to keep the produc-tivity and cost-effectiveness of your system running in top form.
■
Online support
The comprehensive information system available round the clock via Internet ranging from Product Support and Service & Support services to Support Tools in the Shop.http://www.siemens.com/automation/service&support
■
Technical consulting
Support in the planning and de-signing of your project from de-tailed actual-state analysis, target definition and consulting on product and system questi-ons right to the creation of the automation solution.
2
)
Technical assistance
Expert technical assistance
1
) for Low-voltage controls and electrical installation.
Tel.: +49 (0) 9 11 8 95-59 00Fax: +49 (0) 9 11 8 95-59 07
E-Mail: technical-assistance @siemens.com
1) Contact:Technical assistance for product selection · Old/new coding ·Competitor coding · Special versions · Special requirements · Salespromotion (Infoline).Your regional contacts for sales support (prices, discounts, delivery times).Technical Support for commissioning support and after-sales service.
■ Configuration and software engineeringSupport in configuring and de-veloping with customeroriented services from actual configurati-on to implementation of the au-tomation project.2)
■ Technical supportCompetent consulting in techni-cal questions covering a wide range of customer-oriented ser-vices for all our products and sy-stems.
Tel.: +49 (0) 180 50 50 222Fax: +49 (0) 180 50 50 223
http://www.siemens.com/automation/support-request
■ Service on siteWith service on site we offer ser-vices for startup and mainte-nance, essential for ensuring system availability.
Tel.: +49 (0) 180 50 50 444 2)
■ Repairs and spare partsIn the operating phase of a ma-chine or automation system we provide a comprehensive repair and spare parts service ensu-ring the highest degree of ope-rating safety and reliability.
Tel.: +49 (0) 180 50 50 446 2)
■ Optimization and upgradingTo enhance productivity and save costs in your project we of-fer high-quality services in opti-mization and upgrading.2)
2) For country-specific telephone numbers go to our Internet site at: http://www.siemens.com/automation/service&support
13/14 Siemens LV 56 · 2008
Appendix
13
Training
■ Training is decisive for your success
SITRAIN® - the Siemens Training for Automation and Industrial Solutions - provides you with comprehensive support when sol-ving your tasks.
Training by the market leader in automation, plant installation and support permits you to make your decisions with certainty and full command. Especially where the optimum and efficient use of products and plants are concerned. You can eliminate deficiencies in existing plants, and exclude expensive faulty planning right from the beginning.
All in all, this represents an enormous gain for your com-pany: shortened startup times, optimized plant components, faster troubleshooting, reduced down times. In other words, increased profits and lower costs.
Top trainers
Our trainers know their topics in practice, and possess compre-hensive didactic experience. Course developers have a direct wire to product development, and directly pass on their know-ledge to the trainers.
Practical experience
The practical experience of our trainers makes it possible for them to pass on theoretical matter in a plausible manner. But since it is known that all theory is drab, we attach great impor-tance to practical exercises which can comprise up to half of the course time. You can therefore immediately implement your new knowledge in practice. We train you on state-of-the-art methodi-cally/didactically designed training equipment. You feel absolu-tely certain when trained in this manner.
Wide variety
With a total of approx. 300 local attendance courses, we train the complete range of A&D products and a large portion of the sys-tem solutions from I&S. Telecourses, teach-yourself software and seminars presented on the Web supplement our classical range of courses.
Close to our customers
The distance is short. You can find us approx. 60 times in Ger-many, and worldwide in 62 countries. You wish to have individual training instead of one of our 300 courses? No problem: we will provide a program tailored exactly to your personal require-ments. Training can be carried out in our Training Centers or at your company.
■ The right mixture: Blended Learning
Blended learning is understood to be the combination of various training media and sequences. For example, a local attendance course in a Training Center can be optimally supplemented by a teach-yourself program as preparation or follow-up. Further-more, SITRAIN utilizes supported online training for live instruc-tion on the Internet at agreed times.
The right mixture is the solution. Therefore blended learning can convey complex topics well, and train networked thin-king. Additional effect: reduced travelling costs and periods of absence through training sequences independent of loca-tion and time.
■ The international training portal
http://www.siemens.com/sitrain
All training facilities at a glance: search in the worldwide range of courses at leisure, call up all course dates online, utilize the daily updated display of vacant course spaces - and register di-rectly.
■ Customer comments on Sitrain
" ... the good course documents, competence and flexibility con-vinced me.” [Manfred Riek from Festo Systemtechnik, responsible for plan-ning the basic and further training of project engineers]
" ... represents effective training, constructive dialogs, and solu-tions which provide great help."[Günter Niedermaier, electrical design manager at AMT, Aalen]
■ Contact
Visit us on the Internet at:
http://www.siemens.com/sitrain
or let us advise you personally. You can request our latest trai-ning catalog from:
Course office, Infoline Germany:Tel.: +49 (0)1805 / 23 56 11 (0.12 €/Min)Fax: +49 (0)1805 / 23 56 12
13/15Siemens LV 56 · 2008
Appendix
13
Subject Index
13/16 Siemens LV 56 · 2008
Appendix
13
Terms and conditions of sale and deliveryExport regulations
■ Terms and conditions of sale and delivery
By using this catalog you can acquire hardware and software products described therein from Siemens AG subject to the fol-lowing terms. Please note! The scope, the quality and the con-ditions for supplies and services, including software products, by any Siemens entity having a registered office outside of Ger-many, shall be subject exclusively to the General Terms and Conditions of the respective Siemens entity. The following terms apply exclusively for orders placed with Siemens AG.
For customers with a seat or registered office in GermanyThe “General Terms of Payment” as well as the “General Condi-tions for the Supply of Products and Services of the Electrical and Electronics Industry” shall apply.For software products, the “General License Conditions for Soft-ware Products for Automation and Drives for Customers with a Seat or registered Office in Germany” shall apply.
For customers with a seat or registered office outside of Germany
The “General Terms of Payment” as well as the “General Condi-tions for Supplies of Siemens, Automation and Drives for Custo-mers with a Seat or registered Office outside of Germany” shall apply.For software products, the “General License Conditions for Soft-ware Products for Automation and Drives for Customers with a Seat or registered Office outside of Germany” shall apply.
GeneralThe dimensions are in mm. In Germany, according to the Ger-man law on units in measuring technology, data in inches only apply to devices for export.Illustrations are not binding.Insofar as there are no remarks on the corresponding pages, - especially with regard to data, dimensions and weights given - these are subject to change without prior notice.The prices are in € (Euro) ex works, exclusive packaging.The sales tax (value added tax) is not included in the prices. It shall be debited separately at the respective rate according to the applicable legal regulations.Prices are subject to change without prior notice. We will debit the prices valid at the time of delivery.Surcharges will be added to the prices of products that contain silver, copper, aluminum, lead and/or gold if the respective basic official prices for these metals are exceeded. These surcharges will be determined based on the official price and the metal fac-tor of the respective product.The surcharge will be calculated on the basis of the official price on the day prior to receipt of the order or prior to the release or-der.The metal factor determines the official price as of which the me-tal surcharges are charged and the calculation method used. The metal factor, provided it is relevant, is included with the price information of the respective products.
An exact explanation of the metal factor and the text of the Com-prehensive Terms and Conditions of Sale and Delivery are avai-lable free of charge from your local Siemens business office un-der the following Order Nos.:• 6ZB5310-0KR30-0BA1
(for customers based in Germany)• 6ZB5310-0KS53-0BA1
(for customers based outside Germany)or download them from the Internethttp://www.siemens.com/automation/mall (Germany: A&D Mall Online-Help System)
■ Export regulations
The products listed in this catalog / price list may be subject to European / German and/or US export regulations.Therefore, any export requiring a license is subject to approval by the competent authorities.According to current provisions, the following export regulations must be observed with respect to the products featured in this catalog / price list:
Even without a label or with an “AL: N” or “ECCN: N”, authoriza-tion may be required due to the final destination and purpose for which the goods are to be used.The deciding factors are the AL or ECCN export authorization in-dicated on order confirmations, delivery notes and invoices.Errors excepted and subject to change without prior notice.
A&D/VuL_ohne MZ/En 05.09.06
AL Number of the German Export List Products marked other than “N” require an export license.In the case of software products, the export desi-gnations of the relevant data medium must also be generally adhered to.Goods labeled with an “AL“ not equal to “N” are subject to a European or German export authori-zation when being exported out of the EU.
ECCN Export Control Classification NumberProducts marked other than “N” are subject to a reexport license to specific countries.In the case of software products, the export desi-gnations of the relevant data medium must also be generally adhered to.Goods labeled with an “ECCN“ not equal to “N” are subject to a US re-export authorization.
top related