We reserve the right to modify technical specif ications without prior notice.83063800bUK – Translation of the operating manual © Alpha-InnoTec GmbH
Accessories for Dual Air / Water Heat Pumps
Operat ing Manual
HYDrAulic TOWer DuAl
uK
HTD S
Supplement to Operating Manual
2We reserve the right to modify technical specif ications without prior notice.83063800bUK – Translation of the operating manual © Alpha-InnoTec GmbH
Please read firstThe “Model Device Information” is an integral part of the product. It supplements the operating manual “HTD”. In addition to this “Model Device Information”, the operat-ing manual “HTD” must also be available to you.
Since this “Model Device Information” was written for several different models of the unit, always comply with the parameters for the respective model.
The “Model Device Information” is intended only for persons assigned to work on or operate the unit. Treat all constituent parts confidentially. The information con-tained herein is protected by copyright. No part of this information may be reproduced, transmitted, copied, stored in electronic data systems or translated into an-other language, either wholly or in part, without the ex-press written permission of the manufacturer.
3
contents
INforMATIoN for USerS AND qUAlIfIeD perSoNNel
pleASe reAD fIrST ..................................................................2
TecHNIcAl DATA / Scope of DelIvery ..........................4
perforMANce cUrveS .........................................................6
TerMINAl DIAGrAM ...............................................................7
cIrcUIT DIAGrAMS ................................................................8
ec DeclArATIoN of coNforMITy .............................. 11
We reserve the right to modify technical specif ications without prior notice.83063800bUK – Translation of the operating manual © Alpha-InnoTec GmbH
4
Unit designationAccessory for heat pump model LWD 50ASX - LWD 70ASX • applicable ı — not applicable
Functionally relevant • applicable ı — not applicableInstallation location Indoors ı Outdoors • applicable ı — not applicableConformity CEHeating circuit Heating circuit efficiency pump integrated: • yes — no
Free compression heat pump ∆p ı Flow rate bar ı l/hFlow rate: minimum throughout ı Maximum throughput l/hmax. permissible operating pressure barmax. permissible operating temperature °CExpansion vessel: Volume ı Normal inlet pressure l ı barVolume of buffer tank l3-way valve, heating/hot water integrated: • yes — noHeat metering integrated: • yes — no
Domestic hot water tank Net contents lCorrosion protection: Impressed current anode ı Galvanic anode • applicable ı — not applicableHot water temperature Up to °COutput capacity at 38°C | 45 °C if removed at 10 l/min, storage temperature 60 °C l ı lOutput capacity at 38°C | 45 °C if removed at 10 l/min, storage temperature 50 °C** l ı lHeat exchanger area, heat pump m²max. permissible operating pressure bar
General unit data Housing dimensions (Height ı Width ı Depth) mm ı mm ı mmTotal weight kgConnections Heating circuit ...
Heat pumpCold water ...Domestic hot water ...Circulation ...
Electrics Voltage code ı all-pole circuit breaker heat pump 5 kW*) ... ı AVoltage code ı all-pole circuit breaker heat pump 7 kW*) ... ı AVoltage code ı circuit breaker control voltage *) ... ı AVoltage code ı circuit breaker electric heating element *) ... ı AProtection type IPOutput, electric heating element 3 ı 2 ı 1 phase kW ı kW ı kWCirculating pump, heating circuit: maximum power consumption ı current consumption kW ı A
Heating and heat pump regulator
Included in scope of delivery: • yes — no
Safety equipment Safety assembly heating circuit ı Safety assembly heat source Included in scope of delivery: • yes — no
Overflow valve integrated: • yes — noFactory setting (adjust when commissioning the system) bar
Sound Sound pressure level in free field/sound power level dB(A) / dB(A)
* comply with local regulations ** Factory setting
We reserve the right to modify technical specif ications without prior notice.83063800bUK – Translation of the operating manual © Alpha-InnoTec GmbH
Technical data / scope of delivery
5
HTD/S — ı • ı —
• • ı —
••
0,40 ı 1600 900 ı 2000
370
12 ı 1,562••
180 — ı •
62285 ı 230215 ı 170
2,310
1800 ı 600 ı 834150
Rp 1“ IGRp 1“ IGR 1“ AGR 1“ AGR ¾“ AG
1~/N/PE/230V/50Hz ı C161~/N/PE/230V/50Hz ı C201~/N/PE/230V/50Hz ı B161~/N/PE/230V/50Hz ı B32
206 ı 4 ı 20,07 ı 0,31
•
• ı —•
0,5529 / 43813310a
We reserve the right to modify technical specif ications without prior notice.83063800bUK – Translation of the operating manual © Alpha-InnoTec GmbH
6We reserve the right to modify technical specif ications without prior notice.83063800bUK – Translation of the operating manual © Alpha-InnoTec GmbH
HTD S Freie Pressung
0,0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,0 0,5 1,0 1,5 2,0 2,5 3,0
∆p (b
ar)
∆pmax
“ ” (m3/h)
Bezeichnung:
Datei: 812032 Freie Pressung HTD(S)
812032
Seite: 1/1Zeichnungsnummer:
Legende:“ ” Volumenstrom Heizwasser in m3/h∆pmax freie Pressung maximal (Werkseinstellung)
Freie Pressung HTD(S)
812032- /PEP 015-2011 / Liska / 21.06.2012
Änd./ÄM/Ersteller/Datum
Legend: UK812022
“” Flow rate, heating water
∆p (bar) Free compression, heating circuit
7
-F1
0-F
11
-F12
A1
A2
-Q14-F
13
A1
A2
PE
2
ZW
2
EV
U
MIS
4
1
L
PE
TBW
connection
control unit -->
external unit
ZIP
1~N/PE/230V/50Hz
X7
Function
F13
1L1
LIN
FP
1
MZ1
ZIP
Nam
e
1~N/PE/230V/50Hz
ZW2/SST
3
HUP
N
2
1~N/PE/230V/50Hz
GND
3
Information
on fuses can be found in the technical data
ZW1
BUP
M
A1
X7
TA
Du
al a
ir-wa
ter
GND
-X3
A5
A1
-X1
0
1N
F12
Controller board; A
ttention: I-max =
6A
/230VA
C
2
X10
GND
ZUP
GND
PEX
ASD
1~N/PE/230V/50Hz
FP1
-X2
-X7
A3
TRL
VBO
PE
MA1
ZW
2
Cut out a
uxiliary heating 1
Leg
en
d:
Q14
A5
3
-X0
UK
83
1180
Cut out a
uxiliary heating 2
Cut out controller unit
Sub-distribution unit intern
al installation
A2
RFV
GND
PE
Contactor ele
ctric heating ele
ment hot w
ater or buffer tank
L
F10
F11
Term
inal strips on controller board (see sticker)
Cut out com
pressor
Heating circuit circulating pum
p
ZW
2/SS
T
Term
inal in the sw
itch box; pow
er supply add
itional heating output
TR
L
FP
1
External return sensor
ZW
1
Motor protection
MO
T
ZIP
MA
1/MIS
L1
TB
W
circulation pump
-X4
Term
inals
TB1
TB
1
HU
P
Sensor m
ixing circuit 1
12
Hot w
ater circulating pum
p/switching valve
No function
Pum
p for mixing circuit 1
PE
1
bl
3
br
X0-X
4
Charge/discharge/cooling m
ixer 1 close
dM
Z1/M
IS
PE
X
EV
U
Control signal of add
itional heat generator 1; internally w
ired
BU
P
Accessories: R
emote control
External sensor
X7
Hot w
ater gauge/therm
ostat
A4 -X
L1
N
L1
A3
X7
PE
M
TA
GND
BU
P
Hot w
ater or buffer storage tank
RFV
3
MOT
Charge/discharge/cooling m
ixer 1 open
X10
TBW
EVU
ZU
P
A2
Term
inal strip in the sw
itch box; N/P
E distrib
ution for external 230V devices
RF
V
Auxiliary circulation pum
p
Term
inal in the sw
itch box for com
pressor output
A4
Energy supplier contact; close
d on release; bridge if no blocking inte
rval
X10
TAX7
TB1
Control e
lement
3
LIN
L1
NControl signal of add
itional heat generator 2
ZU
P
HU
P
External unit
Term
inal diagram, dual 230V
hydraulic tower
831180
Achim
Pfleg
er1
3.07.2
012
-P
EP
015/2011
12
34
56
78
910
1112
1314
1516
12
34
56
78
910
1112
1314
1516 1
/1
1
19.1
1.2
012
-A
chim P
fleger
150714;
Blatt-N
r.
Zusta
ndÄ
nde
rung
Bea
rb.
Datu
mN
ame
Bl vo
n An
z
Datu
m
We reserve the right to modify technical specif ications without prior notice.83063800bUK – Translation of the operating manual © Alpha-InnoTec GmbH
Terminal diagram HTD S
8
1L1
-X7
1N.
PE
12
-Q5
/2.7
34
53
1
64
2
-E22
ZW
1
56
L1
-X7
NP
E
LN
PE
1-X
02
12
3P
E
34
PE
Cable
LIN
2
Unit co
nnection
-K11
X7
1
1~N
/PE
/230V/50H
z
LIN
LIN bus
Pow
er supply, compressor output -->
exte
rnal unit
X7
12V/LIN
/GN
D
L1,N,P
E; P
ower supp
ly compressor;
1~N
/PE
/230V/50H
z1L1,1N
,PE
; Pow
er supply au
x. heating
Control e
lement
Contactor for auxiliary heating
1~N
/PE
/230V/50H
z
Operating m
aterials
E22
UK
81
7391
X7
Leg
en
d:
Auxiliary heating
Function
1~N
/PE
/230V/50H
z
ZW
1K
11Q
5
X7
Dual 230V
hydraulic tower
817391
Achim
Pfleg
er1
3.06.2
012
-P
EP
015/2011
12
34
56
78
910
1112
1314
1516
12
34
56
78
910
1112
1314
1516 1
/2
1
19.1
1.2
012
Achim
Pfleg
er
150714;
Blatt-N
r.
Zusta
ndÄ
nde
rung
Bea
rb.
Datu
mN
ame
Bl vo
n An
z
Datu
m
We reserve the right to modify technical specif ications without prior notice.83063800bUK – Translation of the operating manual © Alpha-InnoTec GmbH
HTD S circuit diagram 1/2
9
PE
NL
L-X
0
L
-X1
0
NN
PE
PE
L-X
0L
L
MOT
-X2
EVU
-X2
ASD
-X2
HUP
-X3
M1
brbl
PE
brblbk
-M4
ZW1
-X3
ϑ
-ST
B
A1
A2
-Q5
ZW
1
0-1
0V14
GN
D14
12
N5
6
-Y1
BUP
-X3
ϑ
TBW
-X4
-R9
TB
W
GND
ϑ
TVL
-X5
-R5
TV
L
GND
ϑ
TRL
-X5
-R4
TR
L
GND
0-10
V7
GN
D7
AO2
-X6
GND
12
/1.33
4/1.4
56
/1.4
R9
TB
WD
omestic hot w
ater sensor
Com
fort board
Y1
K12
Diverting valve for dom
estic hot water
-K12
Supply term
inals in switchbox of hydraulic m
odule; N
/PE
distribution for external 230V units
Safety tem
perature limiter, ad
ditional heating
R4
X10
Leg
en
d:ZW
1R
eturn sensor
1~N
/PE
/230V/50H
z
Contactor for auxiliary heating
X10
K10
Energy supplier contact; close
d on release; bridge if no blocking inte
rval
M4
BU
P
TR
L
HU
P
ST
B
bl
EV
U
Function
br
EV
U
Flow
sensor
1~N/P
E/230V
/50Hz
blbl
br
C 1
Q5
-K10
Operating m
aterials
Controller supply
R5
Heating pum
p;
TV
L
UK
81
7391
Controller board; A
ttention: I-max =
6A
/230VA
C
23
0V
AC
Dual 230V
hydraulic tower
817391
Achim
Pfleg
er1
3.06.2
012
-P
EP
015/2011
12
34
56
78
910
1112
1314
1516
12
34
56
78
910
1112
1314
1516 2
/2
2
19.1
1.2
012
Achim
Pfleg
er
150714;
Blatt-N
r.
Zusta
ndÄ
nde
rung
Bea
rb.
Datu
mN
ame
Bl vo
n An
z
Datu
m
We reserve the right to modify technical specif ications without prior notice.83063800bUK – Translation of the operating manual © Alpha-InnoTec GmbH
circuit diagram 2/2 HTD S
10We reserve the right to modify technical specif ications without prior notice.83063800bUK – Translation of the operating manual © Alpha-InnoTec GmbH
11
ec declaration of conformityin accordance with the EC Machinery Directive 2006/42/EC, Annex IIA
The undersignedconfirms that the following designated device(s) as designed and marketed by us ful-fill the standardized ec directives, the ec safety standards and the product-specific ec standards. In the event of modification of the device(s) without our approval, this declaration shall become invalid.
Designation of the Device(s)
Heat Pump
Unit model Number Unit model NumberLWD 50A* 100 601 + HMD 1 (E) 150 705 01 (41)LWD 70A* 100 602 + HMD 1 (E) 150 705 01 (41)LWD 50A/SX* 100 603 + HMD 1/S (E) 150 708 01 (41)LWD 70A/SX* 100 604 + HMD 1/S (E) 150 708 01 (41)LWD 50A/RX* 100 605 + HMD 1/R (E) 150 711 01 (41)LWD 70A/RX* 100 606 + HMD 1/R (E) 150 711 01 (41)LWD 50A/RSX* 100 607 + HMD 1/RS (E) 150 712 01 (41)LWD 70A/RSX* 100 608 + HMD 1/RS (E) 150 712 01 (41)LWD 50A* 100 601 + HTD 150 713 41LWD 70A* 100 602 + HTD 150 713 41LWD 50A/SX* 100 603 + HTD/S 150 714 41LWD 70A/SX* 100 604 + HTD/S 150 714 41
* Pressure equiPment comPonent
Category IIModule A1Designated position:TÜV-SÜD Industrie Service GmbH (Nr.:0036)
company: place, date: Kasendorf, 23.10.2012
Signature:
Jesper Stannow Technical Director
Unterschrift:
Jesper Stannow leiter entwicklung