WELCOME!
Today we’d like toIntroduce you to your North American Rotary UPSSolutions Partner!
BRINGS YOU
Rotary UPSyManufactured By
Euro Diesel HistoryOVER 20 YEARS IN SERVICEOVER 20 YEARS IN SERVICESERVING OVER 40 COUNTRIESOver 600MW Installed InternationallyOver 600MW Installed InternationallyContinuous Re-Investment in the OrganizationService Across the Globe
Grace Hollogne, Belgium>54000 Square Feet16 Test Bays
In Collaboration with YOUR TEAM P j tE i i • Project Management
• Test and Commissioning
• Service
• Engineering• R&D• Applications• Equipment Layout
SYSTEMSYSTEM
DESIGN
and MANUFACTURING
FACILITY INTEGRATION
D i
AUXILIARY EQUIPMENT APPLICATION
PACKAGING
• Switchgear/Controls• Cooling Systems• Fuel Systems• Exhaust Systems
•Design• Layout• Ease of Use• Shipping and Installation • Exhaust Systems
Our Focus is the Customer
Competency Cooperation
Customer
Experience Service
Customer
Experience Service
Power Quality - Power GenerationDesigned With You in Mind!Designed With You in Mind!
UPS THE OLD WAY
AlternatorDiesel Engine
Standby Diesel Static UPS+
Ai C diti iS it hb d UPS Modules Air ConditioningSwitchboards
PFC
B d t & C bli
Fire Protection& Security
Standby Battery Rooms
Spark-proof Lighting
Busduct & Cabling
AlternatorDiesel Engine
UPS OUR WAY – The UPS of the FUTURE!ACCUROTOR AlternatorDiesel Engine ACCUROTOR
ACCUROTORUPS Modules Air Conditioning
PFC
Spark-proof Lighting
Fire Protection
Standby Battery Rooms
& Security
SPACE SAVINGS
TRANSFORMER
GENSET ROOM
UPS 1200 KVA
SWITCHGEAR
CONTROL
GENSET 1500 KVASTATIC UPS ROOM
UPS 1200 KVA
AIR
COND
.
FUEL CONTROL PANEL
BATTERIES
BATTERIES
BATTERIYROOM
50% SPACE SAVINGS!
TRANSFORMER
NO-BREAK ROOM
CONTROL PANEL
VENT
FREE SPACE
NO-BREAK KS 1000 KW
FUEL SWITCH GEAR CONTROL PANEL FREE SPACE
LOWER CONSTRUCTION
COST!COST!
Static System Total Losses >10% $$$$$$
100% <90%
E1 SYSTEM EFFICIENCY >96%
The Power Conditioner
PROVIDES:Clean Continuous Clean Continuous
Power!!!
4Spikes Outages1
7x24 POWER CONDITIONER:
2
3
5
6
Frequency Deviation
Sags
Harmonics
Transients3 6Sags Transients
Harmonics Filter – Voltage HarmonicsInductive Series Divider
UTILITY CRITICAL LOAD
CHOKE
ENGINE CLUTCH STATO-ALTERNATOR
Harmonics Filter – Current and Zero Sequence
UTILITY CRITICAL
CHOKE
UTILITY CRITICAL LOAD
Inductive Shunt Divider
ENGINE CLUTCH STATO-ALTERNATOR
Power Factor CorrectionACTIVE POWER (KW)
UTILITY CRITICAL LOAD
CHOKE
( )
REACTIVE POWER (KVAr)
ENGINE CLUTCH STATO-ALTERNATOR
Voltage Regulation
UTILITY CRITICAL
CHOKE
LOAD
ENGINE CLUTCH STATO-ALTERNATOR
Input Short Circuits
UTILITY CRITICAL
CHOKE
LOAD
ENGINE CLUTCH STATO-ALTERNATOR
Output Short Circuits and Inrush
UTILITY
CRITICAL LOAD
CHOKE Clear Individual Fault and Continue to Support Other
Loads
ENGINE CLUTCH STATO-ALTERNATOR
The No Break E1
What Makes a No Break E1
5 64
2 31
Diesel EngineElectro Magnetic Clutch Switchgear
Control Panel – “VISION”12
45Electro-Magnetic Clutch
Stato-Alternator ChokeSwitchgear2
356
Very Few Components = High Reliability
5 64
2 31
Brush Less Exciter Switchgear“VISION” - Control Panel 1
245
Electro-Magnetic ClutchBrush Less ExciterStato-Alternator Flywheel 3000RPM Choke
Switchgear23
56
What’s Inside?
Accu Rotor3000 RPM
Main Rotor1800 RPM
BrushLess Control
How is it a UPS?Conditioning DieselTransfer Conditioning
Accu - Rotor
ConditioningMode
Diesel Mode
TransferMode
ConditioningMode
3000
60,6 Hz
1900
1818
Utility 60,0 Hz
59,4 Hz
1800
1782
Diesel engineTime >
Speed Accu – Rotor
0
Speed (RPM) Mains FrequencyDiesel SpeedRedundant Start
NO‐BREAK E1® ‐ Conditioning ModeManual Bypass Optional
Input Voltage± 10%
Output Voltage± 1%
MainsCritical load
QD1 QD2
QD3
NO‐BREAK E1® ‐ Transfer ModeManual Bypass Optional
MainsCritical load
QD1 QD2
QD3
Available Power RatingsNO BREAK E1 = UPSNO BREAK E1 = UPS
100kW to 2400kW/3000kVA
DUAL OUTPUT CONCEPTNot all Loads Require UPSNot all Loads Require UPS
Office Lighting and General SupplyCooling Infrastructure for Data CentersCompressors and Ventilation Fans
2000kVA UPS CAPACITYENGINES CAPABLE UPTO 3000kVA
DON’T BUY STANDBY POWERDON T BUY STANDBY POWER –DESIGN a No-Break E1 with a Short Break Output
How is this done? SB1Non-critical Load
QD5QD6
Utility
QD3
Critical LoadyQD1 QD2
How is this done? SB0Non-critical Load
QD6
QD3
UtilityQD1 QD2
Critical Load
Available Power RatingsNO BREAK E1 UPSNO BREAK E1 = UPS
100kW to 2400kW/3000kVA
NO BREAK E1 + Short Break2400kW/3000kVA COMBINED TOTAL
Advantages of the NO‐BREAK E1+SBg$ One system critical and non‐critical loads$ Lower initial investment$ Lower initial investment$ Lower installation/building costs$ R d d fl$ Reduced floor space$ Lower maintenance costs$ Easily Configured
Vision Control
What is “E1 Vision” Control“E1 VISION” Control
Maximizes the reliability and maintainability of the NO‐BREAK E1
Reduces interfaces and single points of failure
Automatically Recognizes Single or Parallel Systems
Incorporates Web Based Monitoring
Integrates intelligence features such as:• diesel start reduction
• peak‐shaving and
• an energy saving feature in conditioning mode
Full Touch Screen Controls
PLC:PLC: SAIA PCD3SAIA PCD3
– plug‐in cards with 8 I/O
– digital and analog cards
5 omm ni ation ports– 5 communication ports
– model used: PCD3.M5540
– Web server used for Vision interface, l ll ( h ) l (W b
PCD3.M5540
Battery and memory modules
locally (touch screen) or remotely (Web browser with Java)
– memory: integrated RAM with battery + fl h d b k
40modules
flashcard backup
– multi‐master in communication
Interface :Interface : SAIA PCD7SAIA PCD7
12” l t h– 12” color touch screen
– ethernet link with the PLC
– dynamic IP address for external communication
– USB plug in front of control panel
KS‐Vision interface
KS5+ parallel system : ProfiKS5+ parallel system : Profi‐‐SS‐‐BUSBUS
– Profibus type network (terminated), SAIA Profi‐S‐BUS protocol
– High speed multi master network (1.5 Mbps)
– Redundant network feasible through fiber optics (copper / F.O. converters)
– Expandable network : network configuration not fixed
KS1 CONTROL PANEL
KS2 CONTROL PANEL
KSx CONTROL PANEL
…DIAGNOSTIC PLC (NOTPANEL PANEL PANELPLC (NOT MANDATORY)
END OF LINE (TERMINATION)
Profi‐S‐Bus network
END OF LINE (TERMINATION)
‐‐ links between PLCs : links between PLCs : ProfibusProfibus standardstandard
‐‐ shielded shielded connectorsconnectors
PLCPLC
From previous and to next PLC
SCREEN
DCMMODEM PSTN (RJ 11)
ETHERNET(RJ 45)
‐Modbus TCP/IP‐ Remote interface(s)
USB
USB memory stick‐system history Remote interface(s)
‐After sales‐Remote interface‐Debug / update PLC
‐events logs and data
Euro-Diesel After Sales
UR
O-D
IESE
L
PST N Internet E-mail or FAX
EU
Remoteinterface(s)
USB PLUGPassword protectionto display remote
USB memorystick
UST
OM
ER
US
(TC
P/U
DP)
Customer LANKS-Vision interface
ETHERNETPORT (RJ45)
TERMINALS (MODBUSRTU/ASCII)
interfacesCU
Building ManagementSystem (BMS)
MO
DB
U
ModemPHONE PLUG
(RJ11)
RTU/ASCII)
KS-Vision control panel
Installation Options
What are Our Installation Options?
WHATEVER YOU WANT!
EVERYTHING IS DESIGNED WITH YOU IN MIND!!
Any Application• Medium voltage systems• Main fuel storage systems
• Engine Cooling Systems
Indoor Installations• Engine Cooling Systems• Exhaust and NOx Reductions• Fuel Systems UL142 and UL2085
Outdoor Installations• Base Fuel Systems Ul142 and UL2085• Base Fuel Systems Ul142 and UL2085• Sound Attenuated • Plug and Play Applications
Project Management Services
STRIP LIGHT
FUELTANK
RE
TU
RN
FUE
L C
OO
LER
FE
ED
STATOFAN
STATOFAN
RADIATORFAN
SK
RADIATOR
STATOFAN
STATOFAN
STATOFAN
RADIATORFAN
RADIATORFAN
STRIP LIGHTSTRIP LIGHT 6.00 m6.00 m
RETURNFUEL COOLER
FEED
2
240/110V
TX
FUELTANK
RETURNFUEL COOLER
FEED
FAN
STATOFAN
STRIP LIGHT
14.00 m14.00 m
The Benefits
What Do You Get From A NO BREAK E1?
ADDED PROTECTION!
Regulate Output Voltage & Frequency +/‐ 1%g p g q y
Block Harmful Harmonics <2% THD
3x Input Short Circuit Capacityp p y
>10x Output Short Circuit Capacity
TOTAL SAVINGS WITH E1
$ Most EFFICIENT SYSTEM Available >96%
$ NO Air Conditioning
$ HIGHEST RELIABILITY
$ SMALLEST Footprint$ p
$ Offers Short Break Output Systems
$ Correct Power Factor (to approx Unity)$ Correct Power Factor (to approx Unity)
$ 10 YEAR Overhaul Interval – Longest in Industry
Service
Simple MaintenanceSimple Maintenance3x Per Year
< 12 Hours per Year
No Special Tools
10 Year Life Before O.H.
Thank You!
Please ContactE1 Dynamics877-898-6922For Further Application Discussions!