    SHORT COURSE

    MOTOR CURRENT SIGNATURE ANALYSIS

    FOR

    DIAGNOSIS OF FAULTS IN INDUCTION MOTOR DRIVES

    Prof Bill Thomson

    Director and Consultant

    EM Diagnostics Ltd

    EM Diagnostics Ltd 20 Greystone Road, Alford, Aberdeenshire, AB33 8TY, Scotland, UK

    Tel : +44 (0) 19755 62446 Fax : +44 (0) 19755 62628

    e-mail : [email protected] web site : www.mcsainterpreter.com

    William T. Thomson EM Diagnostics Ltd 2001 - unauthorised copying, reproduction or amendment of all or part prohibited.

    mailto:[email protected]://www.mcsainterpreter.com/http://www.mcsainterpreter.com/mailto:[email protected]
  • 7/28/2019 Anlise de corrente

    2/20

    2

    MCSA : MOTOR CURRENT SIGNATURE ANALYSIS

    INDUCTION MOTOR DRIVES

    DIAGNOSE PROBLEMS PRIOR TO MOTORDRIVE FAILURE

    BROKEN ROTOR BARS ABNORMAL AIRGAP ECCENTRICITY

    SHORTED TURNS IN LV STATORS

    ABNORMAL ROTOR DYNAMICS

    PUMP WEAR MISALIGNMENT

    William T. Thomson EM Diagnostics Ltd 2001 - unauthorised copying, reproduction or

    amendment of all or part prohibited

  • 7/28/2019 Anlise de corrente

    3/20

    3

    INDUCTION MOTOR DRIVE SYSTEMS

    WHY SO IMPORTANT?

    USA 800,000 MW GENERATING CAPACITY

    40-50% CONSUMED BY INDUCTION MOTORS

    320,000MW PLANT SYSTEMS

    328 MILLION HORSEPOWER

  • 7/28/2019 Anlise de corrente

    4/20

    4

    Power

    Utilities

    Oil & Gas

    Chemical

    Refineries

    Pulp &

    Paper

    Mining

    Shipping

    MOD

    Transport

    Nuclear

    WindPower

    DuPont

    Kodak

    Ford

    Uptime of

    Induction Motor

    Drive Systems

  • 7/28/2019 Anlise de corrente

    5/20

    5

    8 CW Induction

    Motor Drives

    8 PA Induction

    Motor Drives8 ID Induction

    Motor Drives

    26 Mill Motors

    Induction Motor

    Drives

    8Coal Conveyor

    Induction Motor

    Drives

    8 FD Induction

    Motor Drives

    8 Compressor

    Induction Motor

    Drives

    Numerous

    other

    InductionMotor Drives

    2000 MW Coal

    Fired

    Power Station

  • 7/28/2019 Anlise de corrente

    6/20

    6

    3 PHASE, SCIM, 6.6kV,

    2800kW/3753H.P., 2-POLE,

    3570r.p.m., 60Hz,

    (Full-load slip = 0.00833 or

    0.833%)

    William T. Thomson EM Diagnostics Ltd 2001 - unauthorisedcopying, reproduction or amendment of all or part prohibited

  • 7/28/2019 Anlise de corrente

    7/20

    7

    MOTOR CURRENT SIGNATURE ANALYSIS

    CONDITION MONITORING TECHNIQUE

    INSURANCE POLICY

    TO PREVENT FAILURES

    REDUCE DOWNTIME AND REPAIR COSTS

    PREVENT LOST PRODUCTION

    INCREASE RELIABILITY - PRODUCT DELIVERY

  • 7/28/2019 Anlise de corrente

    8/20

    8

    MCSA

    MCSA : On-Line Monitoring and Analysis of Current to Assess

    the Condition of an Induction Motor Drive System

  • 7/28/2019 Anlise de corrente

    9/20

    9

    APPLICATION OF CURRENT TRANSFORMER CT

  • 7/28/2019 Anlise de corrente

    10/20

    10

    MCSA Instrumentation

  • 7/28/2019 Anlise de corrente

    11/20

    11

    Time Domain signals and Current Spectra

  • 7/28/2019 Anlise de corrente

    12/20

    12

    CURRENT SIGNATURE DUE TO BROKEN BARS

    LOWER

    SIDEBAND

    f1 =SUPPLY FREQUENCY (60 Hz)

    Hz

    dB

    UPPER

    SIDEBAND

  • 7/28/2019 Anlise de corrente

    13/20

    13

    SIGNATURE PATTERN DUE TO BROKEN BARS

    TWICE SLIP FREQUENCY SIDEBANDS : 2sf1

    fsb = f12sf1

    -2sf1 +2sf1

    f1dB

    Hz

    IDEALISED

    Current Spectrum Due to

    Broken Rotor Bars

  • 7/28/2019 Anlise de corrente

    14/20

    14

    MCSA ON GM3802A (January, 2002)

    3-PH, HV, SCIM, 4155HP/3.1MW, 11kV, 2974r.p.m., 195A 50 Hz

    BROKEN ROTOR BARLIFTED OUT OF THE SLOT

    N=46 dB

    William T. Thomson EM Diagnostics Ltd 2001 - unauthorised copying,

    reproduction or amendment of all or part prohibited

  • 7/28/2019 Anlise de corrente

    15/20

    15

    3-PH, HV, SCIM, 4155HP/3.1MW, 11kV, 2974r.p.m., 195A

    BROKEN ROTOR BARLIFTED IN THE SLOT

    SECONDARY DAMAGE TO HV STATOR

    William T. Thomson EM Diagnostics Ltd 2001 - unauthorised copying, reproduction or amendment of all or partprohibited

  • 7/28/2019 Anlise de corrente

    16/20

    16

    3-PH, HV, SCIM, 4155HP/3.1MW, 11kV, 2974r.p.m., 195A

    BROKEN ROTOR BARLIFTED IN THE SLOT

    SECONDARY DAMAGE TO HV STATOR

    OFFSHORE OIL PRODUCTION PLATFORM

    TOTAL REPAIR COSTS : $270,000.00

    (Removal, transport, repair & re-installation costs)

    THE BOSS IS NOT HAPPY

    PREVENT THIS HAPPENING AGAIN

    YOUR JOB IS ON THE LINE

  • 7/28/2019 Anlise de corrente

    17/20

    17

    Case History : Large Sea Water Injection Pump

    3-Phase SCIM, 6600V, 60Hz, 3.6MW/4285h.p.,376A,3580r.p.m., Star connected

    Full-load slip? s=(Ns-Nr)/Ns = 0.0055(0.55%)

    Sidebands = 2*0.0055*60 = 0.67 Hz (at full load)

    or

    Pole Pass Sidebands = 2 *(60 - 59.667) = 0.67 Hz

  • 7/28/2019 Anlise de corrente

    18/20

    18

    1985 : 20 BARS BROKEN OUT OF 46

  • 7/28/2019 Anlise de corrente

    19/20

    19

    INDUCTION MOTORGEARBOX COMPRESSOR

    3phase, 415 V, 134 kW/180 H.P., 210 A, 1485 r.p.m., 50 Hz R = 58

    1982 150 A

  • 7/28/2019 Anlise de corrente

    20/20

    20

    DIE CAST ROTOR FAULTY END RING

    INSPECTION FOLLOWING ON-LINE MCSA

    William T. Thomson EM Diagnostics Ltd 2001 - unauthorised copying, reproduction or amendment of all or part prohibited