anchor bolts before

Upload: irvan-herry-winarko

Post on 05-Apr-2018

237 views

Category:

Documents


5 download

TRANSCRIPT

  • 8/2/2019 Anchor Bolts Before

    1/117

    Summary for East - West Piperack ( Phase F and G )

    Sr. Pile Data Pile ca

    No. Type of Dia. of Nos. Nos. Total No. Length Width

    Module No. Fdn Pile Along Y Along X

    ( North ) ( East ) mm mm

    1 M-30-Intermediate Column Type 3 324 2 2 4 3000 3000

    2 M-30 & 31 Tower bay Type 2 457 3 2 6 4800 3000

    3 M-31 & 30 tower bay Type 2 457 3 2 6 4800 3000

    4 M-31 independent frame Type 1 324 2 2 4 2300 2300

    5 M-32 independent frame Type 1 324 1 2 2 2300 1200

    6 M-32 intermediate column Type 3 324 1 2 2 2300 1200

    7 M-32 & 33 tower bay Type 2 457 2 2 4 3000 3000

    8 M-33 independent frame Type 1 324 2 2 4 2300 2300

    9 M-34 independent frame Type 1 324 2 2 4 2300 2300

    10 M-34 & 35 tower bay Type 2 324 3 2 6 3600 2300

    11 M-35 independent frame Type 1 324 2 2 4 2300 2300

    12 M-36 independent frame Type 1 324 2 2 4 2300 2300

    13 M- 36 & 37 tower bay Type 2 324 3 2 6 3600 2300

    14 M-37 independent frame Type 1 324 2 2 4 2300 2300

    15 M-38 independent frame Type 1 324 2 2 4 2300 2300

    16 M-38 intermediate column Type 3 324 2 2 4 2300 2300

    17 M-38 & 39 tower bay Type 2 457 2 2 4 3000 3000

    18 M- 39 independent frame Type 1 457 1 2 2 3000 1200

    19 M-40 independent frame Type 1 324 2 2 4 2300 2300

    20 M-40 & 41 tower bay Type 2 324 3 2 6 3600 2300

  • 8/2/2019 Anchor Bolts Before

    2/117

    RTM Eng CALCULATION SHEETBY BAM DATE 14.07.05 SUBJECT : Factored S

    HKD. BY DATE

    Module no. Load comb. Horizontal Horizontal Vertical

    Fx (kN) Fy (kN) Fz (kN) Mx (Kn.m)

    30-IC 1 0.85 DLe + 1.5 WL 8 0 602

    2 0.85 DLe - 1.5 WL -8 0 578

    3 1.25 DLop + 1.5 LL 0 0 1442

    4 1.25 DLop + 1.25 TL 0 0 1298

    5 1.25 DLop - 1.25 TL 0 0 1298

    6 1.25 DLop + 0.7 ( 1.5 WL+ 1.5 6 0 1407

    7 1.25 DLop + 0.7 ( - 1.5 WL+ 1. -6 0 1390

    8 1.25 DLop + 0.7 ( 1.5 WL+ 1.2 6 0 1306

    9 1.25 DLop + 0.7 ( - 1.5 WL + 1 0 0 129010 1.25 DLop + 0.7 ( - 1.5 WL - 1. -6 0 1290

    11 1.25 DLop + 0.7 ( 1.5 WL - 1.2 6 0 1306

    12 1.25 DLop + 0.7 ( 1.5 LL - 1.25 0 0 1399

    13 1.25 DLop + 0.6 ( 1.5 WL+ 1.5 5 0 1392

    14 1.25 DLop + 0.6 ( - 1.5 WL+ 1. -5 0 1377

    15 1.25 DLop + 0.6 ( - 1.5 WL + 1 -5 0 1377

    16 1.25 DLop + 0.6 ( 1.5 WL + 1. 5 0 1392

    17 1.25 DLe + 1.5 WL 8 0 879

    18 1.25 DLe - 1.5 WL -8 0 855

    30-31TB 1 0.85 DLe + 1.5 WL 183 0 1180

    2 0.85 DLe - 1.5 WL -183 0 -234

    31.25 DL

    op+ 1.5 LL

    0 0 11534 1.25 DLop + 1.25 TL 113 0 1798

    5 1.25 DLop - 1.25 TL -113 0 293

    6 1.25 DLop + 0.7 ( 1.5 WL+ 1.5 129 0 1616

    7 1.25 DLop + 0.7 ( - 1.5 WL+ 1. -129 0 627

    8 1.25 DLop + 0.7 ( 1.5 WL+ 1.2 207 0 1917

    9 1.25 DLop + 0.7 ( - 1.5 WL + 1 -50 0 928

    10 1.25 DLop + 0.7 ( - 1.5 WL - 1. -207 0 174

    11 1.25 DLop + 0.7 ( 1.5 WL - 1.2 50 0 1163

    12 1.25 DLop + 0.7 ( 1.5 LL - 1.25 -79 0 594

    13 1.25 DLop + 0.6 ( 1.5 WL+ 1.5 178 0 1857

    14 1.25 DLop + 0.6 ( - 1.5 WL+ 1. -43 0 1010

    15 1.25 DLop + 0.6 ( - 1.5 WL + 1 -178 0 363

    16 1.25 DLop + 0.6 ( 1.5 WL + 1. 43 0 121117 1.25 DLe + 1.5 WL 183 0 1403

    18 1.25 DLe - 1.5 WL -183 0 -11

    31-30 TB 1 0.85 DLe + 1.5 WL 209 0 1601

    2 0.85 DLe - 1.5 WL -209 0 -92

    3 1.25 DLop + 1.5 LL 0 0 1784

    4 1.25 DLop + 1.25 TL 113 569 2333

    5 1.25 DLop - 1.25 TL -113 -569 828

    6 1.25 DLop + 0.7 ( 1.5 WL+ 1.5 146 0 2315

  • 8/2/2019 Anchor Bolts Before

    3/117

    7 1.25 DLop + 0.7 ( - 1.5 WL+ 1. -146 0 1131

    8 1.25 DLop + 0.7 ( 1.5 WL+ 1.2 225 255 2550

    9 1.25 DLop + 0.7 ( - 1.5 WL + 1 -68 255 1365

    10 1.25 DLop + 0.7 ( - 1.5 WL - 1. -225 -255 611

    11 1.25 DLop + 0.7 ( 1.5 WL - 1.2 68 255 1796

    12 1.25 DLop + 0.7 ( 1.5 LL - 1.25 -79 -399 1197

    13 1.25 DLop + 0.6 ( 1.5 WL+ 1.5 193 219 253414 1.25 DLop + 0.6 ( - 1.5 WL+ 1. -58 219 1519

    15 1.25 DLop + 0.6 ( - 1.5 WL + 1 -193 -219 872

    16 1.25 DLop + 0.6 ( 1.5 WL + 1. 58 -219 1887

    17 1.25 DLe + 1.5 WL 209 0 1956

    18 1.25 DLe - 1.5 WL -209 0 264

    31-IF 1 0.85 DLe + 1.5 WL 194 0 1558

    2 0.85 DLe - 1.5 WL -194 0 -93

    3 1.25 DLop + 1.5 LL 0 0 1752

    4 1.25 DLop + 1.25 TL 113 0 1653

    5 1.25 DLop - 1.25 TL -113 0 1443

    6 1.25 DLop + 0.7 ( 1.5 WL+ 1.5 136 0 2268

    71.25 DL

    op+ 0.7 ( - 1.5 WL+ 1.

    -136 0 11138 1.25 DLop + 0.7 ( 1.5 WL+ 1.2 215 0 2199

    9 1.25 DLop + 0.7 ( - 1.5 WL + 1 -57 0 1044

    10 1.25 DLop + 0.7 ( - 1.5 WL - 1. -215 0 897

    11 1.25 DLop + 0.7 ( 1.5 WL - 1.2 57 0 2052

    12 1.25 DLop + 0.7 ( 1.5 LL - 1.25 -79 0 1617

    13 1.25 DLop + 0.6 ( 1.5 WL+ 1.5 184 0 2228

    14 1.25 DLop + 0.6 ( - 1.5 WL+ 1. -49 0 1238

    15 1.25 DLop + 0.6 ( - 1.5 WL + 1 -184 0 1112

    16 1.25 DLop + 0.6 ( 1.5 WL + 1. 49 0 2102

    17 1.25 DLe + 1.5 WL 194 0 1903

    18 1.25 DLe - 1.5 WL -194 0 253

    32-IF 1 0.85 DLe + 1.5 WL 194 0 1221

    2 0.85 DLe - 1.5 WL -194 0 -4513 1.25 DLop + 1.5 LL 0 0 923

    4 1.25 DLop + 1.25 TL 29 0 843

    5 1.25 DLop - 1.25 TL -29 0 788

    6 1.25 DLop + 0.7 ( 1.5 WL+ 1.5 136 0 1476

    7 1.25 DLop + 0.7 ( - 1.5 WL+ 1. -136 0 306

    8 1.25 DLop + 0.7 ( 1.5 WL+ 1.2 156 0 1420

    9 1.25 DLop + 0.7 ( - 1.5 WL + 1 -116 0 250

    10 1.25 DLop + 0.7 ( - 1.5 WL - 1. -156 0 211

    11 1.25 DLop + 0.7 ( 1.5 WL - 1.2 116 0 1381

    12 1.25 DLop + 0.7 ( 1.5 LL - 1.25 -21 0 872

    13 1.25 DLop + 0.6 ( 1.5 WL+ 1.5 134 0 1398

    14 1.25 DLop + 0.6 ( - 1.5 WL+ 1. -99 0 39515 1.25 DLop + 0.6 ( - 1.5 WL + 1 -134 0 362

    16 1.25 DLop + 0.6 ( 1.5 WL + 1. 99 0 1365

    17 1.25 DLe + 1.5 WL 194 0 1402

    18 1.25 DLe - 1.5 WL -194 0 -270

    32-IC 1 0.85 DLe + 1.5 WL 8 0 269

    2 0.85 DLe - 1.5 WL -8 0 245

    3 1.25 DLop + 1.5 LL 0 0 615

    4 1.25 DLop + 1.25 TL 0 0 543

  • 8/2/2019 Anchor Bolts Before

    4/117

    5 1.25 DLop - 1.25 TL 0 0 543

    6 1.25 DLop + 0.7 ( 1.5 WL+ 1.5 6 0 602

    7 1.25 DLop + 0.7 ( - 1.5 WL+ 1. -6 0 585

    8 1.25 DLop + 0.7 ( 1.5 WL+ 1.2 6 0 551

    9 1.25 DLop + 0.7 ( - 1.5 WL + 1 -6 0 535

    10 1.25 DLop + 0.7 ( - 1.5 WL - 1. -6 0 535

    11 1.25 DLop + 0.7 ( 1.5 WL - 1.2 6 0 55112 1.25 DLop + 0.7 ( 1.5 LL - 1.25 0 0 593

    13 1.25 DLop + 0.6 ( 1.5 WL+ 1.5 5 0 593

    14 1.25 DLop + 0.6 ( - 1.5 WL+ 1. -5 0 579

    15 1.25 DLop + 0.6 ( - 1.5 WL + 1 -5 0 579

    16 1.25 DLop + 0.6 ( 1.5 WL + 1. 5 0 593

    17 1.25 DLe + 1.5 WL 8 0 390

    18 1.25 DLe - 1.5 WL -8 0 366

    32-33 TB 1 0.85 DLe + 1.5 WL 176 0 1394

    2 0.85 DLe - 1.5 WL -176 0 -107

    3 1.25 DLop + 1.5 LL 0 0 1502

    4 1.25 DLop + 1.25 TL 60 252 1637

    51.25 DL

    op- 1.25 TL

    -60 -252 9596 1.25 DLop + 0.7 ( 1.5 WL+ 1.5 123 0 1966

    7 1.25 DLop + 0.7 ( - 1.5 WL+ 1. -123 0 916

    8 1.25 DLop + 0.7 ( 1.5 WL+ 1.2 165 71 1947

    9 1.25 DLop + 0.7 ( - 1.5 WL + 1 -81 71 897

    10 1.25 DLop + 0.7 ( - 1.5 WL - 1. -165 -71 649

    11 1.25 DLop + 0.7 ( 1.5 WL - 1.2 81 71 1699

    12 1.25 DLop + 0.7 ( 1.5 LL - 1.25 -42 -176 1204

    13 1.25 DLop + 0.6 ( 1.5 WL+ 1.5 142 61 1977

    14 1.25 DLop + 0.6 ( - 1.5 WL+ 1. -70 61 1077

    15 1.25 DLop + 0.6 ( - 1.5 WL + 1 -142 -61 864

    16 1.25 DLop + 0.6 ( 1.5 WL + 1. 70 -61 1764

    17 1.25 DLe + 1.5 WL 176 0 1697

    18 1.25 DLe - 1.5 WL -176 0 19733-IF 1 0.85 DLe + 1.5 WL 176 0 1413

    2 0.85 DLe - 1.5 WL -176 0 -87

    3 1.25 DLop + 1.5 LL 0 0 1466

    4 1.25 DLop + 1.25 TL 13 0 1274

    5 1.25 DLop - 1.25 TL -13 0 1249

    6 1.25 DLop + 0.7 ( 1.5 WL+ 1.5 123 0 1930

    7 1.25 DLop + 0.7 ( - 1.5 WL+ 1. -123 0 880

    8 1.25 DLop + 0.7 ( 1.5 WL+ 1.2 132 0 1795

    9 1.25 DLop + 0.7 ( - 1.5 WL + 1 -115 0 745

    10 1.25 DLop + 0.7 ( - 1.5 WL - 1. -132 0 728

    11 1.25 DLop + 0.7 ( 1.5 WL - 1.2 115 0 1778

    12 1.25 DLop + 0.7 ( 1.5 LL - 1.25 -9 0 139613 1.25 DLop + 0.6 ( 1.5 WL+ 1.5 113 0 1842

    14 1.25 DLop + 0.6 ( - 1.5 WL+ 1. -98 0 942

    15 1.25 DLop + 0.6 ( - 1.5 WL + 1 -113 0 927

    16 1.25 DLop + 0.6 ( 1.5 WL + 1. 98 0 1827

    17 1.25 DLe + 1.5 WL 176 0 1725

    18 1.25 DLe - 1.5 WL -176 0 225

    34-IF 1 0.85 DLe + 1.5 WL 161 0 1358

    2 0.85 DLe - 1.5 WL -161 0 -89

  • 8/2/2019 Anchor Bolts Before

    5/117

    3 1.25 DLop + 1.5 LL 0 0 1423

    4 1.25 DLop + 1.25 TL 38 0 1255

    5 1.25 DLop - 1.25 TL -38 0 1183

    6 1.25 DLop + 0.7 ( 1.5 WL+ 1.5 113 0 1868

    7 1.25 DLop + 0.7 ( - 1.5 WL+ 1. -113 0 856

    8 1.25 DLop + 0.7 ( 1.5 WL+ 1.2 139 0 1751

    9 1.25 DLop + 0.7 ( - 1.5 WL + 1 -87 0 73910 1.25 DLop + 0.7 ( - 1.5 WL - 1. -139 0 688

    11 1.25 DLop + 0.7 ( 1.5 WL - 1.2 87 0 1700

    12 1.25 DLop + 0.7 ( 1.5 LL - 1.25 -27 0 1337

    13 1.25 DLop + 0.6 ( 1.5 WL+ 1.5 119 0 1797

    14 1.25 DLop + 0.6 ( - 1.5 WL+ 1. -74 0 930

    15 1.25 DLop + 0.6 ( - 1.5 WL + 1 -119 0 886

    16 1.25 DLop + 0.6 ( 1.5 WL + 1. 74 0 1754

    17 1.25 DLe + 1.5 WL 161 0 1656

    18 1.25 DLe - 1.5 WL -161 0 210

    34-35 TB 1 0.85 DLe + 1.5 WL 176 0 1356

    2 0.85 DLe - 1.5 WL -176 0 -43

    31.25 DL

    op+ 1.5 LL

    0 0 14564 1.25 DLop + 1.25 TL 40 229 1577

    5 1.25 DLop - 1.25 TL -40 -229 927

    6 1.25 DLop + 0.7 ( 1.5 WL+ 1.5 123 0 1884

    7 1.25 DLop + 0.7 ( - 1.5 WL+ 1. -123 0 905

    8 1.25 DLop + 0.7 ( 1.5 WL+ 1.2 151 56 1855

    9 1.25 DLop + 0.7 ( - 1.5 WL + 1 -95 56 876

    10 1.25 DLop + 0.7 ( - 1.5 WL - 1. -151 -56 649

    11 1.25 DLop + 0.7 ( 1.5 WL - 1.2 95 56 1627

    12 1.25 DLop + 0.7 ( 1.5 LL - 1.25 -28 -161 1167

    13 1.25 DLop + 0.6 ( 1.5 WL+ 1.5 130 48 1891

    14 1.25 DLop + 0.6 ( - 1.5 WL+ 1. -82 48 1052

    15 1.25 DLop + 0.6 ( - 1.5 WL + 1 -130 -48 857

    16 1.25 DLop + 0.6 ( 1.5 WL + 1. 82 -48 169617 1.25 DLe + 1.5 WL 176 0 1664

    18 1.25 DLe - 1.5 WL -176 0 266

    35- IF 1 0.85 DLe + 1.5 WL 161 0 1362

    2 0.85 DLe - 1.5 WL -161 0 -94

    3 1.25 DLop + 1.5 LL 0 0 1423

    4 1.25 DLop + 1.25 TL 40 0 1258

    5 1.25 DLop - 1.25 TL -40 0 1180

    6 1.25 DLop + 0.7 ( 1.5 WL+ 1.5 113 0 1871

    7 1.25 DLop + 0.7 ( - 1.5 WL+ 1. -113 0 853

    8 1.25 DLop + 0.7 ( 1.5 WL+ 1.2 141 0 1756

    9 1.25 DLop + 0.7 ( - 1.5 WL + 1 -85 0 737

    10 1.25 DLop + 0.7 ( - 1.5 WL - 1. -141 0 68311 1.25 DLop + 0.7 ( 1.5 WL - 1.2 85 0 1701

    12 1.25 DLop + 0.7 ( 1.5 LL - 1.25 -28 0 1335

    13 1.25 DLop + 0.6 ( 1.5 WL+ 1.5 121 0 1801

    14 1.25 DLop + 0.6 ( - 1.5 WL+ 1. -73 0 928

    15 1.25 DLop + 0.6 ( - 1.5 WL + 1 -121 0 882

    16 1.25 DLop + 0.6 ( 1.5 WL + 1. 73 0 1755

    17 1.25 DLe + 1.5 WL 161 0 1660

    18 1.25 DLe - 1.5 WL -161 0 205

  • 8/2/2019 Anchor Bolts Before

    6/117

    36- IF 1 0.85 DLe + 1.5 WL 161 0 1362

    2 0.85 DLe - 1.5 WL -161 0 -94

    3 1.25 DLop + 1.5 LL 0 0 1423

    4 1.25 DLop + 1.25 TL 38 0 1257

    5 1.25 DLop - 1.25 TL -38 0 1182

    6 1.25 DLop + 0.7 ( 1.5 WL+ 1.5 113 0 1871

    7 1.25 DLop + 0.7 ( - 1.5 WL+ 1. -113 0 8538 1.25 DLop + 0.7 ( 1.5 WL+ 1.2 139 0 1755

    9 1.25 DLop + 0.7 ( - 1.5 WL + 1 -87 0 736

    10 1.25 DLop + 0.7 ( - 1.5 WL - 1. -139 0 684

    11 1.25 DLop + 0.7 ( 1.5 WL - 1.2 87 0 1702

    12 1.25 DLop + 0.7 ( 1.5 LL - 1.25 -27 0 1336

    13 1.25 DLop + 0.6 ( 1.5 WL+ 1.5 119 0 1801

    14 1.25 DLop + 0.6 ( - 1.5 WL+ 1. -74 0 928

    15 1.25 DLop + 0.6 ( - 1.5 WL + 1 -119 0 883

    16 1.25 DLop + 0.6 ( 1.5 WL + 1. 74 0 1756

    17 1.25 DLe + 1.5 WL 161 0 1660

    18 1.25 DLe - 1.5 WL -161 0 205

    36-37 TB 10.85 DL

    e+ 1.5 WL

    176 0 14112 0.85 DLe - 1.5 WL -176 0 -99

    3 1.25 DLop + 1.5 LL 0 0 1456

    4 1.25 DLop + 1.25 TL 38 178 1513

    5 1.25 DLop - 1.25 TL -38 -178 990

    6 1.25 DLop + 0.7 ( 1.5 WL+ 1.5 123 0 1923

    7 1.25 DLop + 0.7 ( - 1.5 WL+ 1. -123 0 866

    8 1.25 DLop + 0.7 ( 1.5 WL+ 1.2 150 21 1849

    9 1.25 DLop + 0.7 ( - 1.5 WL + 1 -97 21 793

    10 1.25 DLop + 0.7 ( - 1.5 WL - 1. -150 -21 654

    11 1.25 DLop + 0.7 ( 1.5 WL - 1.2 97 21 1711

    12 1.25 DLop + 0.7 ( 1.5 LL - 1.25 -27 -125 1212

    13 1.25 DLop + 0.6 ( 1.5 WL+ 1.5 128 18 1886

    14 1.25 DLop + 0.6 ( - 1.5 WL+ 1. -83 18 98115 1.25 DLop + 0.6 ( - 1.5 WL + 1 -128 -18 862

    16 1.25 DLop + 0.6 ( 1.5 WL + 1. 83 -18 1768

    17 1.25 DLe + 1.5 WL 176 0 1720

    18 1.25 DLe - 1.5 WL -176 0 211

    37-IF 1 0.85 DLe + 1.5 WL 161 0 1362

    2 0.85 DLe - 1.5 WL -161 0 -94

    3 1.25 DLop + 1.5 LL 0 0 1423

    4 1.25 DLop + 1.25 TL 33 0 1250

    5 1.25 DLop - 1.25 TL -33 0 1188

    6 1.25 DLop + 0.7 ( 1.5 WL+ 1.5 113 0 1871

    7 1.25 DLop + 0.7 ( - 1.5 WL+ 1. -113 0 853

    8 1.25 DLop + 0.7 ( 1.5 WL+ 1.2 136 0 17509 1.25 DLop + 0.7 ( - 1.5 WL + 1 -90 0 732

    10 1.25 DLop + 0.7 ( - 1.5 WL - 1. -136 0 688

    11 1.25 DLop + 0.7 ( 1.5 WL - 1.2 90 0 1707

    12 1.25 DLop + 0.7 ( 1.5 LL - 1.25 -23 0 1340

    13 1.25 DLop + 0.6 ( 1.5 WL+ 1.5 116 0 1797

    14 1.25 DLop + 0.6 ( - 1.5 WL+ 1. -77 0 924

    15 1.25 DLop + 0.6 ( - 1.5 WL + 1 -116 0 886

    16 1.25 DLop + 0.6 ( 1.5 WL + 1. 77 0 1759

  • 8/2/2019 Anchor Bolts Before

    7/117

    17 1.25 DLe + 1.5 WL 161 0 1660

    18 1.25 DLe - 1.5 WL -161 0 205

    38-IF 1 0.85 DLe + 1.5 WL 161 0 1288

    2 0.85 DLe - 1.5 WL -161 0 -168

    3 1.25 DLop + 1.5 LL 0 0 1255

    4 1.25 DLop + 1.25 TL 30 0 1105

    5 1.25 DLop - 1.25 TL -30 0 10456 1.25 DLop + 0.7 ( 1.5 WL+ 1.5 113 0 1711

    7 1.25 DLop + 0.7 ( - 1.5 WL+ 1. -113 0 692

    8 1.25 DLop + 0.7 ( 1.5 WL+ 1.2 134 0 1606

    9 1.25 DLop + 0.7 ( - 1.5 WL + 1 -92 0 587

    10 1.25 DLop + 0.7 ( - 1.5 WL - 1. -134 0 545

    11 1.25 DLop + 0.7 ( 1.5 WL - 1.2 92 0 1564

    12 1.25 DLop + 0.7 ( 1.5 LL - 1.25 -21 545 1180

    13 1.25 DLop + 0.6 ( 1.5 WL+ 1.5 115 0 1638

    14 1.25 DLop + 0.6 ( - 1.5 WL+ 1. -79 0 765

    15 1.25 DLop + 0.6 ( - 1.5 WL + 1 -115 0 729

    16 1.25 DLop + 0.6 ( 1.5 WL + 1. 79 0 1602

    171.25 DL

    e+ 1.5 WL

    161 0 155218 1.25 DLe - 1.5 WL -161 0 97

    38- IC 1 0.85 DLe + 1.5 WL 8 0 463

    2 0.85 DLe - 1.5 WL -8 0 433

    3 1.25 DLop + 1.5 LL 0 0 1004

    4 1.25 DLop + 1.25 TL 0 0 860

    5 1.25 DLop - 1.25 TL 0 0 860

    6 1.25 DLop + 0.7 ( 1.5 WL+ 1.5 6 0 972

    7 1.25 DLop + 0.7 ( - 1.5 WL+ 1. -6 0 951

    8 1.25 DLop + 0.7 ( 1.5 WL+ 1.2 6 0 871

    9 1.25 DLop + 0.7 ( - 1.5 WL + 1 -6 0 850

    10 1.25 DLop + 0.7 ( - 1.5 WL - 1. -6 0 850

    11 1.25 DLop + 0.7 ( 1.5 WL - 1.2 6 0 871

    12 1.25 DLop + 0.7 ( 1.5 LL - 1.25 0 0 96113 1.25 DLop + 0.6 ( 1.5 WL+ 1.5 5 0 956

    14 1.25 DLop + 0.6 ( - 1.5 WL+ 1. -5 0 938

    15 1.25 DLop + 0.6 ( - 1.5 WL + 1 -5 0 938

    16 1.25 DLop + 0.6 ( 1.5 WL + 1. 5 0 956

    17 1.25 DLe + 1.5 WL 8 0 674

    18 1.25 DLe - 1.5 WL -8 0 644

    38-39 TB 1 0.85 DLe + 1.5 WL 176 0 1103

    2 0.85 DLe - 1.5 WL -176 0 -406

    3 1.25 DLop + 1.5 LL 0 0 772

    4 1.25 DLop + 1.25 TL 30 318 1059

    5 1.25 DLop - 1.25 TL -30 -318 269

    6 1.25 DLop + 0.7 ( 1.5 WL+ 1.5 123 0 12687 1.25 DLop + 0.7 ( - 1.5 WL+ 1. -123 0 212

    8 1.25 DLop + 0.7 ( 1.5 WL+ 1.2 144 119 1355

    9 1.25 DLop + 0.7 ( - 1.5 WL + 1 -102 119 299

    10 1.25 DLop + 0.7 ( - 1.5 WL - 1. -144 -119 -28

    11 1.25 DLop + 0.7 ( 1.5 WL - 1.2 102 119 1030

    12 1.25 DLop + 0.7 ( 1.5 LL - 1.25 -21 -223 463

    13 1.25 DLop + 0.6 ( 1.5 WL+ 1.5 124 102 1321

    14 1.25 DLop + 0.6 ( - 1.5 WL+ 1. -88 102 416

  • 8/2/2019 Anchor Bolts Before

    8/117

    15 1.25 DLop + 0.6 ( - 1.5 WL + 1 -124 -102 137

    16 1.25 DLop + 0.6 ( 1.5 WL + 1. 88 -102 1042

    17 1.25 DLe + 1.5 WL 176 0 1267

    18 1.25 DLe - 1.5 WL -176 0 -242

    39- IF 1 0.85 DLe + 1.5 WL 86 0 637

    2 0.85 DLe - 1.5 WL -86 0 -123

    3 1.25 DLop + 1.5 LL 0 0 5834 1.25 DLop + 1.25 TL 20 0 548

    5 1.25 DLop - 1.25 TL -20 0 510

    6 1.25 DLop + 0.7 ( 1.5 WL+ 1.5 60 0 833

    7 1.25 DLop + 0.7 ( - 1.5 WL+ 1. -60 0 301

    8 1.25 DLop + 0.7 ( 1.5 WL+ 1.2 74 0 808

    9 1.25 DLop + 0.7 ( - 1.5 WL + 1 -46 0 277

    10 1.25 DLop + 0.7 ( - 1.5 WL - 1. -74 0 250

    11 1.25 DLop + 0.7 ( 1.5 WL - 1.2 46 0 782

    12 1.25 DLop + 0.7 ( 1.5 LL - 1.25 -14 0 554

    13 1.25 DLop + 0.6 ( 1.5 WL+ 1.5 64 0 801

    14 1.25 DLop + 0.6 ( - 1.5 WL+ 1. -40 0 345

    151.25 DL

    op+ 0.6 ( - 1.5 WL + 1

    -64 0 32316 1.25 DLop + 0.6 ( 1.5 WL + 1. 40 0 778

    17 1.25 DLe + 1.5 WL 86 0 757

    18 1.25 DLe - 1.5 WL -86 0 -2

    30- IF 1 0.85 DLe + 1.5 WL 161 0 1362

    2 0.85 DLe - 1.5 WL -161 0 -94

    3 1.25 DLop + 1.5 LL 0 0 1423

    4 1.25 DLop + 1.25 TL 34 0 1252

    5 1.25 DLop - 1.25 TL -34 0 1187

    6 1.25 DLop + 0.7 ( 1.5 WL+ 1.5 113 0 1871

    7 1.25 DLop + 0.7 ( - 1.5 WL+ 1. -113 0 853

    8 1.25 DLop + 0.7 ( 1.5 WL+ 1.2 136 0 1751

    9 1.25 DLop + 0.7 ( - 1.5 WL + 1 -89 0 733

    10 1.25 DLop + 0.7 ( - 1.5 WL - 1. -136 0 68711 1.25 DLop + 0.7 ( 1.5 WL - 1.2 89 0 1706

    12 1.25 DLop + 0.7 ( 1.5 LL - 1.25 -24 0 1339

    13 1.25 DLop + 0.6 ( 1.5 WL+ 1.5 117 0 1798

    14 1.25 DLop + 0.6 ( - 1.5 WL+ 1. -77 0 925

    15 1.25 DLop + 0.6 ( - 1.5 WL + 1 -117 0 886

    16 1.25 DLop + 0.6 ( 1.5 WL + 1. 77 0 1759

    17 1.25 DLe + 1.5 WL 161 0 1660

    18 1.25 DLe - 1.5 WL -161 0 205

    30-31 TB 1 0.85 DLe + 1.5 WL 176 0 1411

    2 0.85 DLe - 1.5 WL -176 0 -99

    3 1.25 DLop + 1.5 LL 0 0 1456

    4 1.25 DLop + 1.25 TL 34 200 15185 1.25 DLop - 1.25 TL -34 -200 985

    6 1.25 DLop + 0.7 ( 1.5 WL+ 1.5 123 0 1923

    7 1.25 DLop + 0.7 ( - 1.5 WL+ 1. -123 0 866

    8 1.25 DLop + 0.7 ( 1.5 WL+ 1.2 147 36 1853

    9 1.25 DLop + 0.7 ( - 1.5 WL + 1 -100 36 796

    10 1.25 DLop + 0.7 ( - 1.5 WL - 1. -147 -36 651

    11 1.25 DLop + 0.7 ( 1.5 WL - 1.2 100 36 1707

    12 1.25 DLop + 0.7 ( 1.5 LL - 1.25 -24 -140 1208

  • 8/2/2019 Anchor Bolts Before

    9/117

    13 1.25 DLop + 0.6 ( 1.5 WL+ 1.5 126 31 1889

    14 1.25 DLop + 0.6 ( - 1.5 WL+ 1. -86 31 984

    15 1.25 DLop + 0.6 ( - 1.5 WL + 1 -126 -31 859

    16 1.25 DLop + 0.6 ( 1.5 WL + 1. 86 -31 1765

    17 1.25 DLe + 1.5 WL 176 0 1720

    18 1.25 DLe - 1.5 WL -176 0 211

  • 8/2/2019 Anchor Bolts Before

    10/117

    JOB NO. 6780901

    pport reactions

    My (Kn.m) Mz (Kn.m)

    Moment

  • 8/2/2019 Anchor Bolts Before

    11/117

  • 8/2/2019 Anchor Bolts Before

    12/117

  • 8/2/2019 Anchor Bolts Before

    13/117

  • 8/2/2019 Anchor Bolts Before

    14/117

  • 8/2/2019 Anchor Bolts Before

    15/117

  • 8/2/2019 Anchor Bolts Before

    16/117

  • 8/2/2019 Anchor Bolts Before

    17/117

  • 8/2/2019 Anchor Bolts Before

    18/117

    Data

    No.of piles 4

    Pile diameter (Dp) 0.324 m

    Length of pile cap (L) 3 m

    Width of pile cap (B) 3 m

    Thickness of pile cap (D) 0.8 m

    C/C of piles (Sp) 1.8 m = 4d

    Edge distance (ed) 0.6 m

    Pile embedment in pilecap (ep) 0.1 m

    Bottom of pilecap below GL 1.6 m

    Depth of soil on pilecap 0.6 m

    Width of pedestal (b) 0.9 m

    Length of pedestal ( l ) 0.9 m

    Height of pedestal above GL 0.3 m

    Total height of pedestal 0.9 m

    Grade of concrete 30 N/mm2

    Grade of steel 400 N/mm2

    Density of concrete 25 kN/m3

    Density of soil 16 kN/m3

    Clear cover to bottom reinf 50 mm

    Lever arm 1.6 m

    Self weight of pilecap

    Self weight of pilecap 180 kN

    Self weight of pedestal 18 kN

    Total wt. of foundation 198 kN

    Factored wt. of foundation 248 kN

    Design of pile cap for module 30-IC

  • 8/2/2019 Anchor Bolts Before

    19/117

    0.6

    1.8

    0.6

    0.6 1.8 0.6

    ONE WAY SHEAR RESISTANCE (As per cl.15.5.3 of CSA std.A23.3-94)

    Main reinf. Diameter (db) 20 mm

    Effective depth of pile cap (d) 0.62 m

    (d =tpc-ep-cover-1.5db)

    Location of critical section 1.07 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 1.062 m

    If section falls beyond pile

    then no shear

    0.5*(Sp+Dp)< S No shear on the section

    ONE WAY SHEAR RESISTANCE (As per cl.13.4.6.2 of CSA std.A23.3-94)

    Parameters :

    l 1

    fc 0.6

    fs 0.85

    Critical shear section along 0.310 m

    a line located d/2 from the corner pile

    One way shear force (Vf) 422 kN

    from the corner pile

    Length of critical section bw 2.64 m

    2(d/2+Dp/2)+2* sqrt.(ed2+ed

    2)

    Vc1 =(260/(1000+d)).l.fc.sqrt.fc'.bw.d 1398.3 kN cl.11.3.5.2 of CSA std.A23.3-94

    Vc2=0.1.l.fc.sqrt.fc'.bw.d 538.1 kN

    Factored one way shear (Vr) 1398.3 kN Vr>Vf

    resistance w/o shear reinf.

    Max. of Vc1 & Vc2

    Pile cap is safe in one way shear

    d/2

    TWO-WAY SHEAR

    TWO-WAY SHEAR

    ONE WAY SHEAR - N/A

    ONE-WAY SHEAR

  • 8/2/2019 Anchor Bolts Before

    20/117

    TWO WAY SHEAR RESISTANCE (As per cl. 13.4.3.1 of CSA std.A23.3-94)

    Parameters:

    as for interior column 4

    as for exterior column 3

    p 3.14

    Critical section @ d/2 from pedestal face

    Length of critical shear section bo 6.08 m

    bo=2(b+d+l+d)

    Fraction of unbalanced moment

    transferred by eccentricity of shear

    gvx = 1-1/(1+2/3.sqrt.((b+d)/(l+d)) 0.4 cl.13.4.5.3 of CSA std.A23.3-94

    Polar moment of inertia of the critical 1.089E+12 mm4

    p.no.5-26 of CSA std.A23.3-94sect. About its centroidal axis (Jx)

    (b+d)d3/6+(b+d)

    3d/6+d(l+d)(b+d)

    2/2

    Polar moment of inertia of the critical 1.089E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    sect. About its centroidal axis (Jy)

    (l+d)d3/6+(l+d)

    3d/6+d(b+d)(l+d)

    2/2

    Distance from NA to extreme 0.76 m

    compression ex=(l+d)/2

    Distance from NA to extreme 0.76 m

    compression ey=(b+d)/2

    Location of critical section 0.76 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 1.062 m

    Factored shear stress (Vf) 0.480 N/mm2

    cl.13.4.5.5 of CSA std.A23.3-94

    Vf=K(Vf/bod+(gvMfe/J)x+(gvMfe/J)y)

    Factored shear resistance,Vr Smallest of Vc1,Vc2,Vc3

    w/o shear reinf.

    Vc1=(1+2/bc).0.2.l.fc.sqrt.(fc') 1.97 N/mm

    2

    Vc2=(as.d/bo+0.2).l.fc.sqrt.(fc') 2.0 N/mm

    2

    Vc3 =0.4lfc.sqrt.(fc')

    1.31 N/mm2

    Vr = min(Vc) 1.31 N/mm2

    Vr>Vf

    Pile cap is safe in two way shear

  • 8/2/2019 Anchor Bolts Before

    21/117

    TWO WAY SHEAR RESISTANCE (As per cl. 13.4.3.1 of CSA std.A23.3-94)

    Critical section @d/2 from corner pile

    Two way shear from corner pile Vf 422 kN

    length of critical section bo 1.94 m

    bo=p(Dp+d)/4+2ed

    Factored shear resistance,Vr Smallest of Vc1,Vc2,Vc3

    w/o shear reinf.

    Vc1=(1+2/bc).0.2.l.fc.sqrt.(fc') 1.97 N/mm

    2

    Vc2=(as.d/bo+0.2).l.fc.sqrt.(fc') 3.8 N/mm

    2

    Vc3 =0.4lfc.sqrt.(fc')

    1.31 N/mm2

    vr = min(Vc) 1.31 N/mm2

    Vr=vr.bo.d 1582.0 kN Vr>Vf

    Pile cap is safe in two way shear

    MOMENT RESISTANCE OF PILECAP

    Critical section @ face of pedestal

    Max.factored moment @ face of

    pedestalMf = 2.Vmax(Sp/2-b/2) 380.2 kN.m

    resistance factor Kr =Mf/1000.d2

    0.99 N/mm2

    p.2-4 of CPCA Concrete Design Handbook

    Ratio of average stress in rectangular

    compression block to the specified

    concrete strength

    a1=0.85-0.0015fc'

    0.805 >0.67 cl.10.1.7(c) of CSA std.A23.3-94

    Required ratio of tension reinforcement

    r = a1fcfc/fs.fy.(1-sqrt.(1-(2Kr/a1.fc.fc'))) 0.0030 P.no.123 of Reinforced Concrete Design -Pillai

    Required area of

    tension reinforcement As reqd. 1870 mm2/m

    Minimum area of tension reinforcement

    As min = 0.002*1000*(D-ep) 1400 mm2/m cl.7.8.1 of CSA std.A23.3-94

    Try 25M @ 200 mm :Bottom,E.W.

    area of tension reinforcement 3000 mm2/m o.k.

    Provide 25M @ 200 mm @ bottom e.w.

    Provide 16M @ 200 mm @ top e.w.

  • 8/2/2019 Anchor Bolts Before

    22/117

    ADFREEZE AND FROST HEAVE FOR PILE CAP

    Length of pile 16 m

    Area of pilecap A=L.B 9 m2

    Perimeter of pile cap =2(L+B) 12 m

    Compressive strength of Geospan Cs 40 kN/m2

    p. no. 35 of 38 in soil report

    Adfreeze value to be applied to sides 30 kN/m2

    p. no. 36 of 38 in soil report

    Allowable static skin friction below 10 m 75 kN/m2

    Table 5.1 of soil report

    Max. uplift due to adfreeze =A.Cs 360 kN

    Max. uplift from sides due to adfreeze 288 kN

    Total uplift 648 kN

    Dead load from structure 693 kN Refer S Dle in support reactions

    Skin friction beyond 10 m resisting uplift 915.6 kN

    Total resisting force 1608.6 kN >Total uplift

    No need of bond break around the pile cap

    1800

    4d = 1800600600

    600

    600

    3000

    3000

    800

    Fz (-ve)

    Fy (+ve)

    300

    600

    M25 @ 200 c/c e.w.M16 @ 200 c/c e.w.

    324 mm dia x 9.52 mm WT pile 16.0m length

  • 8/2/2019 Anchor Bolts Before

    23/117

    Data

    No. of piles 6

    Pile diameter (Dp) 0.457 m

    Length of pile cap (L) 4.8 m

    Width of pile cap (B) 3 m

    Thickness of pile cap (D) 0.8 m

    C/C of piles (Sp) 1.8 m = 4d

    Edge distance (ed) 0.6 m

    Pile embedment in pilecap (ep) 0.1 m

    Bottom of pilecap below GL 1.6 m

    Depth of soil on pilecap 0.6 m

    Width of pedestal (b) 0.9 m

    Length of pedestal ( l ) 0.9 m

    Height of pedestal above GL 0.3 m

    Total height of pedestal 0.90 m

    Grade of concrete 30 N/mm2

    Grade of steel 400 N/mm2

    Density of concrete 25 kN/m3

    Density of soil 16 kN/m3

    Clear cover to bottom reinf 50 mm

    Lever arm 1.6 m

    Self weight of pilecap

    Self weight of pilecap 288 kN

    Self weight of pedestal 18 kN

    Total wt. of foundation 306 kN

    Factored wt. of foundation 383 kN

    Design of pile cap for module 30-31 TB

  • 8/2/2019 Anchor Bolts Before

    24/117

    m 0.6

    1.8

    1.8

    0.6

    0.6 1.8 1.8 0.6

    ONE WAY SHEAR RESISTANCE (As per cl.15.5.3 of CSA std.A23.3-94)

    Main reinf. Diameter (db) 25 mm

    Effective depth of pile cap (d) 0.6125 m

    (d =tpc-ep-cover-1.5db)

    Location of critical section 1.0625 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 1.1285 m

    If section falls beyond pile

    then no shear

    0.5*(Sp+Dp)< S produces shear on the section

    ONE WAY SHEAR RESISTANCE (As per cl.13.4.6.2 of CSA std.A23.3-94)

    Parameters :

    l 1

    fc 0.6

    fs 0.85

    Critical shear section along 0.306 m

    a line located d/2 from the corner pile

    One way shear force (Vf) 445 kN

    from the corner pile

    Length of critical section bw 2.77 m

    2(d/2+Dp/2)+2* sqrt.(ed2+ed

    2)

    Vc1 =(260/(1000+d)).l.fc.sqrt.fc'.bw.d 1447.0 kN cl.11.3.5.2 of CSA std.A23.3-94

    Vc2=0.1.l.fc.sqrt.fc'.bw.d 556.9 kN

    Factored one way shear (Vr) 1447.0 kN Vr>Vf

    resistance w/o shear reinf.

    Max. of Vc1 & Vc2

    Pile cap is safe in one way shear

    TWO-WAY SHEAR

    TWO-WAY SHEAR

    ONE WAY SHEAR - N/A

    ONE WAY SHEAR

    d/2

  • 8/2/2019 Anchor Bolts Before

    25/117

    TWO WAY SHEAR RESISTANCE (As per cl. 13.4.3.1 of CSA std.A23.3-94)

    Parameters:

    as for interior column 4

    as for exterior column 3p 3.14

    Critical section @ d/2 from pedestal face

    Length of critical shear section bo 6.05 m

    bo=2(b+d+l+d)

    Fraction of unbalanced momenttransferred by eccentricity of shear

    gvx = 1-1/(1+2/3.sqrt.((b+d)/(l+d)) 0.4 cl.13.4.5.3 of CSA std.A23.3-94

    Polar moment of inertia of the critical 1.060E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    sect. About its centroidal axis (Jx)

    (b+d)d3/6+(b+d)3d/6+d(l+d)(b+d)2/2

    Polar moment of inertia of the critical 1.060E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    sect. About its centroidal axis (Jy)

    (l+d)d3/6+(l+d)

    3d/6+d(b+d)(l+d)

    2/2

    Distance from NA to extreme 0.76 m

    compression ex=l+d/2

    Distance from NA to extreme 0.76 m

    compression ey=b+d/2

    Location of critical section 0.76 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 1.1285 m

    Factored shear stress (Vf) 0.675 N/mm cl.13.4.5.5 of CSA std.A23.3-94

    Vf=K(Vf/bod+(gvMfe/J)x+(gvMfe/J)y)

    Factored shear resistance,Vr Smallest of Vc1,Vc2,Vc3

    w/o shear reinf.

    Vc1=(1+2/bc).0.2.l.fc.sqrt.(fc') 1.97 N/mm

    Vc2=(as.d/bo+0.2).l.fc.sqrt.(fc') 2.0 N/mm

    Vc3 =0.4lfc.sqrt.(fc') 1.31 N/mm

    Vr = min(Vc) 1.31 N/mm2

    Vr>Vf

    Pile cap is safe in two way shear

  • 8/2/2019 Anchor Bolts Before

    26/117

    TWO WAY SHEAR RESISTANCE (As per cl. 13.4.3.1 of CSA std.A23.3-94)

    Critical section @d/2 from corner pile

    Two way shear from corner pile Vf

    445 kN

    length of critical section bo 2.04 m

    bo=p(Dp+d)/4+2ed

    Factored shear resistance,Vr Smallest of Vc1,Vc2,Vc3

    w/o shear reinf.

    Vc1=(1+2/bc).0.2.l.fc.sqrt.(fc') 1.97 N/mm

    Vc2=(as.d/bo+0.2).l.fc.sqrt.(fc') 3.6 N/mm

    Vc3 =0.4lfc.sqrt.(fc'

    1.31 N/mm

    vr = min(Vc) 1.31 N/mm

    Vr=vr.bo.d 1642.2 kN Vr>Vf

    Pile cap is safe in two way shear

    MOMENT RESISTANCE OF PILECAP

    Critical section @ face of pedestal

    Max.factored moment @ face of

    pedestal

    Mf = 3.Vmax(Sp/2-b/2) 600.3 kN.m

    resistance factor Kr =Mf/1000.d2

    1.600 N/mm2

    p.2-4 of CPCA Concrete Design Handbook

    Ratio of average stress in rectangular

    compression block to the specified

    concrete strength

    a1=0.85-0.0015fc'

    0.805 >0.67 cl.10.1.7(c) of CSA std.A23.3-94

    Required ratio of tension reinforcement

    r = a1fcfc/fs.fy.(1-sqrt.(1-(2Kr/a1.fc.fc') 0.0050 P.no.123 of Reinforced Concrete Design -Pillai

    Required area of

    tension reinforcement As reqd. 3062 mm2/m

    Minimum area of tension reinforcementAs min = 0.002*1000*(D-ep) 1400 mm

    2/m cl.7.8.1 of CSA std.A23.3-94

    Try 25M @ 150 mm :Bottom,E.W.

    area of tension reinforcement 3500 mm2/m o.k.

    Provide 25M @ 150 mm @ bottom e.w.

    Provide 16M @ 150 mm @ top e.w.

  • 8/2/2019 Anchor Bolts Before

    27/117

    ADFREEZE AND FROST HEAVE FOR PILE CAP

    Length of pile 16 m

    Area of pilecap A=L.B 14.4 m2

    Perimeter of pile cap =2(L+B) 15.6 m

    Compressive strength of Geospan Cs 40 kN/m2

    p. no. 35 of 38 in soil report

    Adfreeze value to be applied to sides 30 kN/m2

    p. no. 36 of 38 in soil report

    Allowable static skin friction below 10 75 kN/m2

    Table 5.1 of soil report

    Max. uplift due to adfreeze =A.Cs 576 kN

    Max. uplift from sides due to adfreeze 374.4 kN

    Total uplift 950 kN

    Dead load from structure 557 kN Refer S Dle in support reactions

    Skin friction beyond 10 m resisting uplif 1291.5 kN

    Total resisting force 1848.5 kN >Total uplift

    No need of bond break around the pile cap

    4d = 1800

    4d

    =1

    800

    4d = 1800 500500

    2800

    4600

    500

    500

    800

    Fz (-ve)Fy

    (+ve)

    300

    600

    M25 @ 150 c/c e.w.M16 @ 150 c/c e.w.

    457mm dia x 9.52 mm WT pile 16.0m length

  • 8/2/2019 Anchor Bolts Before

    28/117

    Data

    No. of piles 6

    Pile diameter (Dp) 0.457 m

    Length of pile cap (L) 4.8 m

    Width of pile cap (B) 3 m

    Thickness of pile cap (D) 0.8 m

    C/C of piles (Sp) 1.8 m = 4d

    Edge distance (ed) 0.6 m

    Pile embedment in pilecap (ep) 0.1 m

    Bottom of pilecap below GL 1.6 m

    Depth of soil on pilecap 0.6 m

    Width of pedestal (b) 0.9 m

    Length of pedestal ( l ) 0.9 m

    Height of pedestal above GL 0.3 m

    Total height of pedestal 0.90 m

    Grade of concrete 30 N/mm2

    Grade of steel 400 N/mm2

    Density of concrete 25 kN/m3

    Density of soil 16 kN/m3

    Clear cover to bottom reinf 50 mm

    Lever arm 1.6 m

    Self weight of pilecap

    Self weight of pilecap 288 kN

    Self weight of pedestal 18 kN

    Total wt. of foundation 306 kN

    Factored wt. of foundation 383 kN

    Design of pile cap for module 31-30 TB

  • 8/2/2019 Anchor Bolts Before

    29/117

    m 0.6

    1.8

    1.8

    0.6

    0.6 1.8 1.8 0.6

    ONE WAY SHEAR RESISTANCE (As per cl.15.5.3 of CSA std.A23.3-94)

    Main reinf. Diameter (db) 30 mm

    Effective depth of pile cap (d) 0.605 m

    (d =tpc-ep-cover-1.5db)

    Location of critical section 1.055 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 1.1285 m

    If section falls beyond pile

    then no shear

    0.5*(Sp+Dp)< S produces shear on the section

    ONE WAY SHEAR RESISTANCE (As per cl.13.4.6.2 of CSA std.A23.3-94)

    Parameters :

    l 1

    fc 0.6

    fs 0.85

    Critical shear section along 0.303 m

    a line located d/2 from the corner pile

    One way shear force (Vf) 613 kN

    from the corner pile

    Length of critical section bw 2.76 m

    2(d/2+Dp/2)+2* sqrt.(ed2+ed

    2)

    Vc1 =(260/(1000+d)).l.fc.sqrt.fc'.bw.d 1425.4 kN cl.11.3.5.2 of CSA std.A23.3-94

    Vc2=0.1.l.fc.sqrt.fc'.bw.d 548.6 kN

    Factored one way shear (Vr) 1425.4 kN Vr>Vf

    resistance w/o shear reinf.

    Max. of Vc1 & Vc2

    Pile cap is safe in one way shear

    TWO-WAY SHEAR

    TWO-WAY SHEAR

    ONE WAY SHEAR - N/A

    ONE WAY SHEAR

    d/2

  • 8/2/2019 Anchor Bolts Before

    30/117

    TWO WAY SHEAR RESISTANCE (As per cl. 13.4.3.1 of CSA std.A23.3-94)

    Parameters:

    as for interior column 4

    as for exterior column 3

    p 3.14

    Critical section @ d/2 from pedestal face

    Length of critical shear section bo 6.02 m

    bo=2(b+d+l+d)

    Fraction of unbalanced moment

    transferred by eccentricity of shear

    gvx = 1-1/(1+2/3.sqrt.((b+d)/(l+d)) 0.4 cl.13.4.5.3 of CSA std.A23.3-94

    Polar moment of inertia of the critical 1.031E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    sect. About its centroidal axis (Jx)

    (b+d)d3/6+(b+d)

    3d/6+d(l+d)(b+d)

    2/2

    Polar moment of inertia of the critical 1.031E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    sect. About its centroidal axis (Jy)(l+d)d

    3/6+(l+d)

    3d/6+d(b+d)(l+d)

    2/2

    Distance from NA to extreme 0.75 m

    compression ex=l+d/2

    Distance from NA to extreme 0.75 m

    compression ey=b+d/2

    Location of critical section 0.75 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 1.1285 m

    Factored shear stress (Vf) 0.931 N/mm2

    cl.13.4.5.5 of CSA std.A23.3-94

    Vf=K(Vf/bod+(gvMfe/J)x+(gvMfe/J)y)

    Factored shear resistance,Vr Smallest of Vc1,Vc2,Vc3

    w/o shear reinf.

    Vc1=(1+2/bc).0.2.l.fc.sqrt.(fc') 1.97 N/mm

    Vc2=(as.d/bo+0.2).l.fc.sqrt.(fc') 2.0 N/mm

    Vc3 =0.4lfc.sqrt.(fc'

    1.31 N/mm

    Vr =

    min(Vc

    ) 1.31 N/mm2

    Vr>Vf

    Pile cap is safe in two way shear

  • 8/2/2019 Anchor Bolts Before

    31/117

    TWO WAY SHEAR RESISTANCE (As per cl. 13.4.3.1 of CSA std.A23.3-94)

    Critical section @d/2 from corner pile

    Two way shear from corner pile Vf 613 kN

    length of critical section bo 2.03 m

    bo=p(Dp+d)/4+2ed

    Factored shear resistance,Vr Smallest of Vc1,Vc2,Vc3

    w/o shear reinf.

    Vc1=(1+2/bc).0.2.l.fc.sqrt.(fc') 1.97 N/mm

    Vc2=(as.d/bo+0.2).l.fc.sqrt.(fc') 3.6 N/mm

    Vc3 =0.4lfc.sqrt.(fc'

    1.31 N/mm

    vr = min(Vc) 1.31 N/mm2

    Vr=vr.bo.d 1617.4 kN Vr>Vf

    Pile cap is safe in two way shear

    MOMENT RESISTANCE OF PILECAP

    Critical section @ face of pedestal

    Max.factored moment @ face of

    pedestal

    Mf = 3.Vmax(Sp/2-b/2) 827.0 kN.m

    resistance factor Kr =Mf/1000.d2

    2.259 N/mm2

    p.2-4 of CPCA Concrete Design Handbook

    Ratio of average stress in rectangular

    compression block to the specified

    concrete strength

    a1=0.85-0.0015fc'

    0.805 >0.67 cl.10.1.7(c) of CSA std.A23.3-94

    Required ratio of tension reinforcement

    r = a1fcfc/fs.fy.(1-sqrt.(1-(2Kr/a1.fc.fc') 0.007 P.no.123 of Reinforced Concrete Design -Pillai

    Required area of

    tension reinforcement As reqd. 4395 mm2/m

    Minimum area of tension reinforcement

    As min = 0.002*1000*(D-ep) 1400 mm2/m cl.7.8.1 of CSA std.A23.3-94

    Try 30M @ 150 mm :Bottom,E.W.

    area of tension reinforcement 4900 mm2/m o.k.

    Provide 30M @ 150 mm @ bottom e.w.

    Provide 16M @ 150 mm @ top e.w.

  • 8/2/2019 Anchor Bolts Before

    32/117

    ADFREEZE AND FROST HEAVE FOR PILE CAP

    Length of pile 16 m

    Area of pilecap A=L.B 14.4 m2

    Perimeter of pile cap =2(L+B) 15.6 m

    Compressive strength of Geospan Cs 40 kN/m p. no. 35 of 38 in soil report

    Adfreeze value to be applied to sides 30 kN/m2

    p. no. 36 of 38 in soil report

    Allowable static skin friction below 10 m 75 kN/m2

    Table 5.1 of soil report

    Max. uplift due to adfreeze =A.Cs 576 kN

    Max. uplift from sides due to adfreeze 374.4 kN

    Total uplift 950 kN

    Dead load from structure 888 kN Refer S Dle in support reactions

    Skin friction beyond 10 m resisting uplif 1291.5 kN

    Total resisting force 2179.5 kN >Total uplift

    No need of bond break around the pile cap

    4d = 1800

    4d

    =1

    800

    4d = 1800 600600

    3000

    4800

    600

    600

    800

    Fz (-ve)Fy (+ve)

    300

    600

    M30 @ 150 c/c e.w.M16 @ 150 c/c e.w.

    457mm dia x 9.52 mm WT pile 16.0m length

  • 8/2/2019 Anchor Bolts Before

    33/117

    Data

    No.of piles 4

    Pile diameter (Dp) 0.324 m

    Length of pile cap (L) 2.3 m

    Width of pile cap (B) 2.3 m

    Thickness of pile cap (D) 0.8 m

    C/C of piles (Sp) 1.3 m = 4dEdge distance (ed) 0.5 m

    Pile embedment in pilecap (ep) 0.1 m

    Bottom of pilecap below GL 1.6 m

    Depth of soil on pilecap 0.6 m

    Width of pedestal (b) 0.9 m

    Length of pedestal ( l ) 0.9 m

    Height of pedestal above GL 0.3 m

    Total height of pedestal 0.9 m

    Grade of concrete 30 N/mm2

    Grade of steel 400 N/mm2

    Density of concrete 25 kN/m3

    Density of soil 16 kN/m3

    Clear cover to bottom reinf 50 mm

    Lever arm 1.6 m

    Self weight of pilecap

    Self weight of pilecap 106 kN

    Self weight of pedestal 18 kN

    Total wt. of foundation 124 kN

    Factored wt. of foundation 155 kN

    Design of pile cap for module 31-IF

  • 8/2/2019 Anchor Bolts Before

    34/117

    0.5

    1.3

    0.5

    0.5 1.3 0.5

    ONE WAY SHEAR RESISTANCE (As per cl.15.5.3 of CSA std.A23.3-94)

    Main reinf. Diameter (db) 20 mm

    Effective depth of pile cap (d) 0.62 m

    (d =tpc-ep-cover-1.5db)

    Location of critical section 1.07 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 0.812 m

    If section falls beyond pile

    then no shear

    0.5*(Sp+Dp)< S No shear on the section

    ONE WAY SHEAR RESISTANCE (As per cl.13.4.6.2 of CSA std.A23.3-94)

    Parameters :

    l 1

    fc 0.6

    fs 0.85

    Critical shear section along 0.310 m

    a line located d/2 from the corner pile

    One way shear force (Vf) 721 kN

    from the corner pile

    Length of critical section bw 2.36 m

    2(d/2+Dp/2)+2* sqrt.(ed2+ed

    2)

    Vc1 =(260/(1000+d)).l.fc.sqrt.fc'.bw.d 1248.5 kN cl.11.3.5.2 of CSA std.A23.3-94

    Vc2=0.1.l.fc.sqrt.fc'.bw.d 480.5 kN

    Factored one way shear (Vr) 1248.5 kN Vr>Vf

    resistance w/o shear reinf.

    Max. of Vc1 & Vc2

    Pile cap is safe in one way shear

    d/2

    TWO-WAY SHEAR

    TWO-WAY SHEAR

    ONE WAY SHEAR - N/A

    ONE-WAY SHEAR

  • 8/2/2019 Anchor Bolts Before

    35/117

    TWO WAY SHEAR RESISTANCE (As per cl. 13.4.3.1 of CSA std.A23.3-94)

    Parameters:

    as for interior column 4

    as for exterior column 3

    p 3.14

    Critical section @ d/2 from pedestal face

    Length of critical shear section bo 6.08 m

    bo=2(b+d+l+d)

    Fraction of unbalanced momenttransferred by eccentricity of shear

    gvx = 1-1/(1+2/3.sqrt.((b+d)/(l+d)) 0.4 cl.13.4.5.3 of CSA std.A23.3-94

    Polar moment of inertia of the critical 1.089E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    sect. About its centroidal axis (Jx)

    (b+d)d3/6+(b+d)

    3d/6+d(l+d)(b+d)

    2/2

    Polar moment of inertia of the critical 1.089E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    sect. About its centroidal axis (Jy)

    (l+d)d3/6+(l+d)

    3d/6+d(b+d)(l+d)

    2/2

    Distance from NA to extreme 0.76 m

    compression ex=(l+d)/2

    Distance from NA to extreme 0.76 m

    compression ey=(b+d)/2

    Location of critical section 0.76 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 0.812 m

    Factored shear stress (Vf) 0.676 N/mm cl.13.4.5.5 of CSA std.A23.3-94

    Vf=K(Vf/bod+(gvMfe/J)x+(gvMfe/J)y)

    Factored shear resistance,Vr Smallest of Vc1,Vc2,Vc3

    w/o shear reinf.

    Vc1=(1+2/bc).0.2.l.fc.sqrt.(fc') 1.97 N/mm

    Vc2=(as.d/bo+0.2).l.fc.sqrt.(fc') 2.0 N/mm

    2

    Vc3 =0.4lfc.sqrt.(fc')

    1.31 N/mm

    Vr = min(Vc) 1.31 N/mm Vr>Vf

    Pile cap is safe in two way shear

  • 8/2/2019 Anchor Bolts Before

    36/117

    TWO WAY SHEAR RESISTANCE (As per cl. 13.4.3.1 of CSA std.A23.3-94)

    Critical section @d/2 from corner pile

    Two way shear from corner pile Vf 721 kN

    length of critical section bo 1.74 m

    bo=p(Dp+d)/4+2ed

    Factored shear resistance,Vr Smallest of Vc1,Vc2,Vc3

    w/o shear reinf.

    Vc1=(1+2/bc).0.2.l.fc.sqrt.(fc') 1.97 N/mm

    2

    Vc2=(as.d/bo+0.2).l.fc.sqrt.(fc') 4.2 N/mm

    Vc3 =0.4lfc.sqrt.(fc')

    1.31 N/mm2

    vr = min(Vc) 1.31 N/mm

    Vr=vr.bo.d 1419.0 kN Vr>Vf

    Pile cap is safe in two way shear

    MOMENT RESISTANCE OF PILECAP

    Critical section @ face of pedestal

    Max.factored moment @ face of

    pedestal

    Mf = 2.Vmax(Sp/2-b/2) 288.3 kN.m

    resistance factor Kr =Mf/1000.d2

    0.750 N/mm2

    p.2-4 of CPCA Concrete Design Handbook

    Ratio of average stress in rectangular

    compression block to the specifiedconcrete strength

    a1=0.85-0.0015fc'

    0.805 >0.67 cl.10.1.7(c) of CSA std.A23.3-94

    Required ratio of tension reinforcement

    r = a1fcfc/fs.fy.(1-sqrt.(1-(2Kr/a1.fc.fc'))) 0.0023 P.no.123 of Reinforced Concrete Design -Pillai

    Required area of

    tension reinforcement As reqd. 1405 mm2/m

    Minimum area of tension reinforcement

    As min = 0.002*1000*(D-ep) 1400 mm2/m cl.7.8.1 of CSA std.A23.3-94

    Try 20M @ 200 mm :Bottom,E.W.

    area of tension reinforcement 1800 mm

    2

    /m o.k.

    Provide 20M @ 200 mm @ bottom e.w.

    Provide 16M @ 200 mm @ top e.w.

  • 8/2/2019 Anchor Bolts Before

    37/117

    ADFREEZE AND FROST HEAVE FOR PILE CAP

    Length of pile 16 m

    Area of pilecap A=L.B 5.29 m2

    Perimeter of pile cap =2(L+B) 9.2 m

    Compressive strength of Geospan Cs 40 kN/m p. no. 35 of 38 in soil report

    Adfreeze value to be applied to sides 30 kN/m2

    p. no. 36 of 38 in soil report

    Allowable static skin friction below 10 m 75 kN/m2

    Table 5.1 of soil report

    Max. uplift due to adfreeze =A.Cs 212 kN

    Max. uplift from sides due to adfreeze 220.8 kN

    Total uplift 432 kN

    Dead load from structure 862 kN Refer S Dle in support reactions

    Skin friction beyond 10 m resisting uplift 915.6 kN

    Total resisting force 1777.6 kN >Total uplift

    No need of bond break around the pile cap

    4d

    =

    1300

    4d = 1300500500

    500

    500

    2300

    2300

    800

    Fz (-ve)

    Fy (+ve)

    300

    600

    M20 @ 200 c/c e.w.M16 @ 200 c/c e.w.

    324 mm dia x 9.52 mm WT pile 16.0m length

  • 8/2/2019 Anchor Bolts Before

    38/117

    Data

    No.of piles 2

    Pile diameter (Dp) 0.324 m

    Length of pile cap (L) 2.3 m

    Width of pile cap (B) 1 m

    Thickness of pile cap (D) 0.8 m

    C/C of piles (Sp) 1.3 m = 4d

    Edge distance in 'x' direction (edx) 0.5 m

    Edge distance in 'Y' direction (edy) 0.6 m

    Pile embedment in pilecap (ep) 0.1 m

    Bottom of pilecap below GL 1.6 m

    Depth of soil on pilecap 0.6 m

    Width of pedestal (b) 0.9 m

    Length of pedestal ( l ) 0.9 m

    Height of pedestal above GL 0.3 m

    Total height of pedestal 0.9 m

    Grade of concrete 30 N/mm2

    Grade of steel 400 N/mm2

    Density of concrete 25 kN/m3

    Density of soil 16 kN/m3

    Clear cover to bottom reinf 50 mm

    Lever arm 1.6 m

    Self weight of pilecap

    Self weight of pilecap 46 kN

    Self weight of pedestal 18 kN

    Total wt. of foundation 64 kN

    Factored wt. of foundation 80 kN

    Design of pile cap for module 32-IF

  • 8/2/2019 Anchor Bolts Before

    39/117

    0.5

    1.3

    0.5

    0.6 0.6

    ONE WAY SHEAR RESISTANCE (As per cl.15.5.3 of CSA std.A23.3-94)

    Main reinf. Diameter (db) 20 mm

    Effective depth of pile cap (d) 0.62 m

    (d =tpc-ep-cover-1.5db)

    Location of critical section 1.07 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 0.812 m

    If section falls beyond pile

    then no shear

    0.5*(Sp+Dp)< S No shear on the section

    TWO WAY SHEAR RESISTANCE (As per cl. 13.4.3.1 of CSA std.A23.3-94)

    Parameters :

    l 1

    fc 0.6

    fs 0.85as for interior column 4

    as for exterior column 3

    p 3.14

    Critical section @ d/2 from pedestal face

    Length of critical shear section bo 6.08 m

    bo=2(b+d+l+d)

    Fraction of unbalanced momenttransferred by eccentricity of shear

    gvx = 1-1/(1+2/3.sqrt.((b+d)/(l+d)) 0.4 cl.13.4.5.3 of CSA std.A23.3-94

    Polar moment of inertia of the critical 1.089E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    TWO-WAY SHEAR

    ONE WAY SHEAR - N/A

  • 8/2/2019 Anchor Bolts Before

    40/117

    sect. About its centroidal axis (Jx)

    (b+d)d3/6+(b+d)

    3d/6+d(l+d)(b+d)

    2/2

    Polar moment of inertia of the critical 1.089E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    sect. About its centroidal axis (Jy)

    (l+d)d3/6+(l+d)

    3d/6+d(b+d)(l+d)

    2/2

    Distance from NA to extreme 0.76 m

    compression ex=(l+d)/2

    Distance from NA to extreme 0.76 m

    compression ey=(b+d)/2

    Location of critical section 0.76 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 0.812 m

    Factored shear stress (Vf) 0.447 N/mm cl.13.4.5.5 of CSA std.A23.3-94

    Vf=K(Vf/bod+(gvMfe/J)x+(gvMfe/J)y)

    Factored shear resistance,Vr Smallest of Vc1,Vc2,Vc3

    w/o shear reinf.

    Vc1=(1+2/bc).0.2.l.fc.sqrt.(fc') 1.97 N/mm

    2

    Vc2=(as.d/bo+0.2).l.fc.sqrt.(fc') 2.0 N/mm

    Vc3 =0.4lfc.sqrt.(fc')

    1.31 N/mm

    Vr = min(Vc) 1.31 N/mm2

    Vr>Vf

    Pile cap is safe in two way shear

  • 8/2/2019 Anchor Bolts Before

    41/117

    MOMENT RESISTANCE OF PILECAP

    Critical section @ face of pedestal

    Max.factored moment @ face of

    pedestal

    Mf =.Vmax(Sp/2-b/2) 196.0 kN.m

    resistance factor Kr =Mf/1000.d2

    0.51 N/mm2

    p.2-4 of CPCA Concrete Design Handbook

    Ratio of average stress in rectangular

    compression block to the specified

    concrete strength

    a1=0.85-0.0015fc'

    0.805 >0.67 cl.10.1.7(c) of CSA std.A23.3-94

    Required ratio of tension reinforcement

    r = a1fcfc/fs.fy.(1-sqrt.(1-(2Kr/a1.fc.fc'))) 0.0015 P.no.123 of Reinforced Concrete Design -Pillai

    Required area of

    tension reinforcement As reqd. 947 mm2/m

    Minimum area of tension reinforcement

    As min = 0.002*1000*(D-ep) 1400 mm

    2

    /m cl.7.8.1 of CSA std.A23.3-94

    Try 20M @ 200 mm :Bottom,E.W.

    area of tension reinforcement 1800 mm2/m o.k.

    Provide 20M @ 200 mm @ bottom e.w.

    Provide 16M @ 200 mm @ top e.w.

  • 8/2/2019 Anchor Bolts Before

    42/117

    ADFREEZE AND FROST HEAVE FOR PILE CAP

    Length of pile 16 m

    Area of pilecap A=L.B 2.3 m2

    Perimeter of pile cap =2(L+B) 6.6 m

    Compressive strength of Geospan Cs 40 kN/m p. no. 35 of 38 in soil report

    Adfreeze value to be applied to sides 30 kN/m2

    p. no. 36 of 38 in soil report

    Allowable static skin friction below 10 m 75 kN/m2

    Table 5.1 of soil report

    Max. uplift due to adfreeze =A.Cs 92 kN

    Max. uplift from sides due to adfreeze 158.4 kN

    Total uplift 250 kN

    Dead load from structure 453 kN Refer S Dle in support reactions

    Skin friction beyond 10 m resisting uplift 915.6 kN

    Total resisting force 1368.6 kN >Total uplift

    No need of bond break around the pile cap

    4

    d

    =1

    300

    600600

    500

    500

    2300

    1200

    800

    Fz (-ve)

    Fy (+ve)

    300

    600

    M20 @ 200 c/c e.w.M16 @ 200 c/c e.w.

    324 mm dia x 9.52 mm WT pile 16.0m length

  • 8/2/2019 Anchor Bolts Before

    43/117

    Data

    No.of piles 2

    Pile diameter (Dp) 0.324 m

    Length of pile cap (L) 2.3 m

    Width of pile cap (B) 1.2 m

    Thickness of pile cap (D) 0.8 m

    C/C of piles (Sp) 1.3 m = 4d

    Edge distance in 'x' direction (edx) 0.5 m

    Edge distance in 'Y' direction (edy) 0.6 m

    Pile embedment in pilecap (ep) 0.1 m

    Bottom of pilecap below GL 1.6 m

    Depth of soil on pilecap 0.6 m

    Width of pedestal (b) 0.9 m

    Length of pedestal ( l ) 0.9 m

    Height of pedestal above GL 0.3 m

    Total height of pedestal 0.9 m

    Grade of concrete 30 N/mm2

    Grade of steel 400 N/mm2

    Density of concrete 25 kN/m3

    Density of soil 16 kN/m3

    Clear cover to bottom reinf 50 mm

    Lever arm 1.6 m

    Self weight of pilecap

    Self weight of pilecap 55 kN

    Self weight of pedestal 18 kN

    Total wt. of foundation 73 kN

    Factored wt. of foundation 92 kN

    Design of pile cap for module 32-IC

  • 8/2/2019 Anchor Bolts Before

    44/117

    0.5

    1.3

    0.5

    0.6 0.6

    ONE WAY SHEAR RESISTANCE (As per cl.15.5.3 of CSA std.A23.3-94)

    Main reinf. Diameter (db) 20 mm

    Effective depth of pile cap (d) 0.62 m

    (d =tpc-ep-cover-1.5db)

    Location of critical section 1.07 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 0.812 m

    If section falls beyond pile

    then no shear

    0.5*(Sp+Dp)< S No shear on the section

    TWO WAY SHEAR RESISTANCE (As per cl. 13.4.3.1 of CSA std.A23.3-94)

    Parameters :

    l 1

    fc 0.6

    fs 0.85

    as for interior column 4

    as for exterior column 3

    p 3.14

    Critical section @ d/2 from pedestal face

    Length of critical shear section bo 6.08 m

    bo=2(b+d+l+d)

    Fraction of unbalanced momenttransferred by eccentricity of shear

    gvx = 1-1/(1+2/3.sqrt.((b+d)/(l+d)) 0.4 cl.13.4.5.3 of CSA std.A23.3-94

    Polar moment of inertia of the critical 1.089E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    sect. About its centroidal axis (Jx)

    (b+d)d3/6+(b+d)

    3d/6+d(l+d)(b+d)

    2/2

    TWO-WAY SHEAR

    ONE WAY SHEAR - N/A

  • 8/2/2019 Anchor Bolts Before

    45/117

    Polar moment of inertia of the critical 1.089E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    sect. About its centroidal axis (Jy)

    (l+d)d3/6+(l+d)

    3d/6+d(b+d)(l+d)

    2/2

    Distance from NA to extreme 0.76 m

    compression ex=(l+d)/2

    Distance from NA to extreme 0.76 mcompression ey=(b+d)/2

    Location of critical section 0.76 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 0.812 m

    Factored shear stress (Vf) 0.187 N/mm cl.13.4.5.5 of CSA std.A23.3-94

    Vf=K(Vf/bod+(gvMfe/J)x+(gvMfe/J)y)

    Factored shear resistance,Vr Smallest of Vc1,Vc2,Vc3

    w/o shear reinf.

    Vc1=(1+2/bc).0.2.l.fc.sqrt.(fc') 1.97 N/mm

    2

    Vc2=(as.d/bo+0.2).l.fc.sqrt.(fc') 2.0 N/mm

    Vc3 =0.4lfc.sqrt.(fc')

    1.31 N/mm

    Vr = min(Vc) 1.31 N/mm Vr>Vf

    Pile cap is safe in two way shear

  • 8/2/2019 Anchor Bolts Before

    46/117

    MOMENT RESISTANCE OF PILECAP

    Critical section @ face of pedestal

    Max.factored moment @ face of

    pedestal

    Mf =.Vmax(Sp/2-b/2) 70.9 kN.m

    resistance factor Kr =Mf/1000.d2

    0.18 N/mm2

    p.2-4 of CPCA Concrete Design Handbook

    Ratio of average stress in rectangular

    compression block to the specified

    concrete strength

    a1=0.85-0.0015fc'

    0.805 >0.67 cl.10.1.7(c) of CSA std.A23.3-94

    Required ratio of tension reinforcement

    r = a1fcfc/fs.fy.(1-sqrt.(1-(2Kr/a1.fc.fc'))) 0.0005 P.no.123 of Reinforced Concrete Design -Pillai

    Required area of

    tension reinforcement As reqd. 338 mm2/m

    Minimum area of tension reinforcement

    As min = 0.002*1000*(D-ep) 1400 mm /m cl.7.8.1 of CSA std.A23.3-94

    Try 20M @ 200 mm :Bottom,E.W.

    area of tension reinforcement 1800 mm2/m o.k.

    Provide 20M @ 200 mm @ bottom e.w.

    Provide 16M @ 200 mm @ top e.w.

  • 8/2/2019 Anchor Bolts Before

    47/117

    ADFREEZE AND FROST HEAVE FOR PILE CAP

    Length of pile 16 m

    Area of pilecap A=L.B 2.76 m2

    Perimeter of pile cap =2(L+B) 7 m

    Compressive strength of Geospan Cs 40 kN/m p. no. 35 of 38 in soil report

    Adfreeze value to be applied to sides 30 kN/m2

    p. no. 36 of 38 in soil report

    Allowable static skin friction below 10 m 75 kN/m2

    Table 5.1 of soil report

    Max. uplift due to adfreeze =A.Cs 110 kN

    Max. uplift from sides due to adfreeze 168 kN

    Total uplift 278 kN

    Dead load from structure 302 kN Refer S Dle in support reactions

    Skin friction beyond 10 m resisting uplift 915.6 kN

    Total resisting force 1217.6 kN >Total uplift

    No need of bond break around the pile cap

    4d

    =1

    300

    600600

    500

    500

    2300

    1200

    800

    Fz (-ve)

    Fy (+ve)

    300

    600

    M20 @ 200 c/c e.w.M16 @ 200 c/c e.w.

    324 mm dia x 9.52 mm WT pile 16.0m length

  • 8/2/2019 Anchor Bolts Before

    48/117

    Data

    No.of piles 4

    Pile diameter (Dp) 0.457 m

    Length of pile cap (L) 3 m

    Width of pile cap (B) 3 m

    Thickness of pile cap (D) 0.8 m

    C/C of piles (Sp) 1.8 m = 4d

    Edge distance (ed) 0.6 m

    Pile embedment in pilecap (ep) 0.1 m

    Bottom of pilecap below GL 1.6 m

    Depth of soil on pilecap 0.6 m

    Width of pedestal (b) 0.9 m

    Length of pedestal ( l ) 0.9 m

    Height of pedestal above GL 0.3 m

    Total height of pedestal 0.9 m

    Grade of concrete 30 N/mm2

    Grade of steel 400 N/mm2

    Density of concrete 25 kN/m3

    Density of soil 16 kN/m3

    Clear cover to bottom reinf 50 mm

    Lever arm 1.6 m

    Self weight of pilecap

    Self weight of pilecap 180 kN

    Self weight of pedestal 18 kN

    Total wt. of foundation 198 kN

    Factored wt. of foundation 248 kN

    Design of pile cap for module 32-33 TB

  • 8/2/2019 Anchor Bolts Before

    49/117

    0.6

    1.8

    0.6

    0.6 1.8 0.6

    ONE WAY SHEAR RESISTANCE (As per cl.15.5.3 of CSA std.A23.3-94)

    Main reinf. Diameter (db) 25 mm

    Effective depth of pile cap (d) 0.6125 m

    (d =tpc-ep-cover-1.5db)

    Location of critical section 1.0625 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 1.1285 m

    If section falls beyond pile

    then no shear

    0.5*(Sp+Dp)< S produces shear on the section

    ONE WAY SHEAR RESISTANCE (As per cl.13.4.6.2 of CSA std.A23.3-94)

    Parameters :

    l 1

    fc 0.6fs 0.85

    Critical shear section along 0.306 m

    a line located d/2 from the corner pile

    One way shear force (Vf) 654 kN

    from the corner pile

    Length of critical section bw 2.77 m

    2(d/2+Dp/2)+2* sqrt.(ed2+ed

    2)

    Vc1 =(260/(1000+d)).l.fc.sqrt.fc'.bw.d 1447.0 kN cl.11.3.5.2 of CSA std.A23.3-94

    Vc2=0.1.l.fc.sqrt.fc'.bw.d 556.9 kN

    Factored one way shear (Vr) 1447.0 kN Vr>Vf

    resistance w/o shear reinf.

    Max. of Vc1 & Vc2

    Pile cap is safe in one way shear

    d/2

    TWO-WAY SHEAR

    TWO-WAY SHEAR

    ONE WAY SHEAR - N/A

    ONE-WAY SHEAR

  • 8/2/2019 Anchor Bolts Before

    50/117

    TWO WAY SHEAR RESISTANCE (As per cl. 13.4.3.1 of CSA std.A23.3-94)

    Parameters:

    as for interior column 4

    as for exterior column 3

    p 3.14

    Critical section @ d/2 from pedestal face

    Length of critical shear section bo 6.05 m

    bo=2(b+d+l+d)

    Fraction of unbalanced moment

    transferred by eccentricity of shear

    gvx = 1-1/(1+2/3.sqrt.((b+d)/(l+d)) 0.4 cl.13.4.5.3 of CSA std.A23.3-94

    Polar moment of inertia of the critical 1.060E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    sect. About its centroidal axis (Jx)

    (b+d)d3/6+(b+d)

    3d/6+d(l+d)(b+d)

    2/2

    Polar moment of inertia of the critical 1.060E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    sect. About its centroidal axis (Jy)

    (l+d)d3/6+(l+d)

    3d/6+d(b+d)(l+d)

    2/2

    Distance from NA to extreme 0.76 m

    compression ex=(l+d)/2

    Distance from NA to extreme 0.76 m

    compression ey=(b+d)/2

    Location of critical section 0.76 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 1.1285 m

    If section falls beyond or inside pile No shear on the sectionthen no shear

    Factored shear stress (Vf) 0.600 N/mm cl.13.4.5.5 of CSA std.A23.3-94

    Vf=K(Vf/bod+(gvMfe/J)x+(gvMfe/J)y)

    Factored shear resistance,Vr Smallest of Vc1,Vc2,Vc3

    w/o shear reinf.

    Vc1=(1+2/bc).0.2.l.fc.sqrt.(fc') 1.97 N/mm

    Vc2=(as.d/bo+0.2).l.fc.sqrt.(fc') 2.0 N/mm

    2

    Vc3 =0.4lfc.sqrt.(fc') 1.31 N/mm2

    Vr = min(Vc) 1.31 N/mm Vr>Vf

    Pile cap is safe in two way shear

  • 8/2/2019 Anchor Bolts Before

    51/117

    TWO WAY SHEAR RESISTANCE (As per cl. 13.4.3.1 of CSA std.A23.3-94)

    Critical section @d/2 from corner pile

    Two way shear from corner pile Vf 654 kN

    length of critical section bo 2.04 m

    bo=p(Dp+d)/4+2ed

    Factored shear resistance,Vr Smallest of Vc1,Vc2,Vc3

    w/o shear reinf.

    Vc1=(1+2/bc).0.2.l.fc.sqrt.(fc') 1.97 N/mm

    2

    Vc2=(as.d/bo+0.2).l.fc.sqrt.(fc') 3.6 N/mm

    Vc3 =0.4lfc.sqrt.(fc')

    1.31 N/mm2

    vr = min(Vc) 1.31 N/mm

    Vr=vr.bo.d 1642.2 kN Vr>Vf

    Pile cap is safe in two way shear

    MOMENT RESISTANCE OF PILECAP

    Critical section @ face of pedestal

    Max.factored moment @ face of

    pedestal

    Mf = 2.Vmax(Sp/2-b/2) 588.2 kN.m

    resistance factor Kr =Mf/1000.d2

    1.57 N/mm2

    p.2-4 of CPCA Concrete Design Handbook

    Ratio of average stress in rectangular

    compression block to the specified

    concrete strength

    a1=0.85-0.0015fc'

    0.805 >0.67 cl.10.1.7(c) of CSA std.A23.3-94

    Required ratio of tension reinforcement

    r = a1fcfc/fs.fy.(1-sqrt.(1-(2Kr/a1.fc.fc'))) 0.0049 P.no.123 of Reinforced Concrete Design -Pillai

    Required area of

    tension reinforcement As reqd. 2997 mm2/m

    Minimum area of tension reinforcement

    As min = 0.002*1000*(D-ep) 1400 mm /m cl.7.8.1 of CSA std.A23.3-94

    Try 25M @ 200 mm :Bottom,E.W.

    area of tension reinforcement 3000 mm2/m o.k.

    Provide 25M @ 200 mm @ bottom e.w.

    Provide 16M @ 200 mm @ top e.w.

  • 8/2/2019 Anchor Bolts Before

    52/117

    ADFREEZE AND FROST HEAVE FOR PILE CAP

    Length of pile 16 m

    Area of pilecap A=L.B 9 m2

    Perimeter of pile cap =2(L+B) 12 m

    Compressive strength of Geospan Cs 40 kN/m p. no. 35 of 38 in soil report

    Adfreeze value to be applied to sides 30 kN/m2

    p. no. 36 of 38 in soil report

    Allowable static skin friction below 10 m 75 kN/m2

    Table 5.1 of Thurber report

    Max. uplift due to adfreeze =A.Cs 360 kN

    Max. uplift from sides due to adfreeze 288 kN

    Total uplift 648 kN

    Dead load from structure 757 kN Refer S Dle in support reactions

    Skin friction beyond 10 m resisting uplift 1291.5 kN

    Total resisting force 2048.5 kN >Total uplift

    No need of bond break around the pile cap

    4d

    =1

    300

    4d = 1800500500

    500

    500

    2800

    2800

    800

    Fz (-ve)

    Fy (+ve)

    300

    600

    M25 @ 200 c/c e.w.M16 @ 200 c/c e.w.

    457 mm dia x 9.52 mm WT pile 16.0m length

  • 8/2/2019 Anchor Bolts Before

    53/117

    Data

    No.of piles 4

    Pile diameter (Dp) 0.324 m

    Length of pile cap (L) 2.3 m

    Width of pile cap (B) 2.3 m

    Thickness of pile cap (D) 0.8 m

    C/C of piles (Sp

    ) 1.3 m = 4d

    Edge distance (ed) 0.5 m

    Pile embedment in pilecap (ep) 0.1 m

    Bottom of pilecap below GL 1.6 m

    Depth of soil on pilecap 0.6 m

    Width of pedestal (b) 0.9 m

    Length of pedestal ( l ) 0.9 m

    Height of pedestal above GL 0.3 m

    Total height of pedestal 0.9 m

    Grade of concrete 30 N/mm2

    Grade of steel 400 N/mm2

    Density of concrete 25 kN/m3

    Density of soil 16 kN/m3

    Clear cover to bottom reinf 50 mm

    Lever arm 1.6 m

    Self weight of pilecap

    Self weight of pilecap 106 kN

    Self weight of pedestal 18 kN

    Total wt. of foundation 124 kN

    Factored wt. of foundation 155 kN

    Design of pile cap for module 33-IF

  • 8/2/2019 Anchor Bolts Before

    54/117

    0.5

    1.3

    0.5

    0.5 1.3 0.5

    ONE WAY SHEAR RESISTANCE (As per cl.15.5.3 of CSA std.A23.3-94)

    Main reinf. Diameter (db) 20 mm

    Effective depth of pile cap (d) 0.62 m

    (d =tpc-ep-cover-1.5db)

    Location of critical section 1.07 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 0.812 m

    If section falls beyond pile

    then no shear

    0.5*(Sp+Dp)< S No shear on the section

    ONE WAY SHEAR RESISTANCE (As per cl.13.4.6.2 of CSA std.A23.3-94)

    Parameters :

    l 1

    fc 0.6fs 0.85

    Critical shear section along 0.310 m

    a line located d/2 from the corner pile

    One way shear force (Vf) 597 kN

    from the corner pile

    Length of critical section bw 2.36 m

    2(d/2+Dp/2)+2* sqrt.(ed2+ed

    2)

    Vc1 =(260/(1000+d)).l.fc.sqrt.fc'.bw.d 1248.5 kN cl.11.3.5.2 of CSA std.A23.3-94

    Vc2=0.1.l.fc.sqrt.fc'.bw.d 480.5 kN

    Factored one way shear (Vr) 1248.5 kN Vr>Vf

    resistance w/o shear reinf.

    Max. of Vc1 & Vc2

    Pile cap is safe in one way shear

    d/2

    TWO-WAY SHEAR

    TWO-WAY SHEAR

    ONE WAY SHEAR - N/A

    ONE-WAY SHEAR

  • 8/2/2019 Anchor Bolts Before

    55/117

    TWO WAY SHEAR RESISTANCE (As per cl. 13.4.3.1 of CSA std.A23.3-94)

    Parameters:

    as for interior column 4

    as for exterior column 3

    p 3.14

    Critical section @ d/2 from pedestal face

    Length of critical shear section bo 6.08 m

    bo=2(b+d+l+d)

    Fraction of unbalanced moment

    transferred by eccentricity of shear

    gvx = 1-1/(1+2/3.sqrt.((b+d)/(l+d)) 0.4 cl.13.4.5.3 of CSA std.A23.3-94

    Polar moment of inertia of the critical 1.089E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    sect. About its centroidal axis (Jx)

    (b+d)d3/6+(b+d)

    3d/6+d(l+d)(b+d)

    2/2

    Polar moment of inertia of the critical 1.089E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    sect. About its centroidal axis (Jy)

    (l+d)d3/6+(l+d)

    3d/6+d(b+d)(l+d)

    2/2

    Distance from NA to extreme 0.76 m

    compression ex=(l+d)/2

    Distance from NA to extreme 0.76 m

    compression ey=(b+d)/2

    Location of critical section 0.76 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 0.812 m

    If section falls beyond or inside pile No shear on the sectionthen no shear

    Factored shear stress (Vf) 0.585 N/mm2

    cl.13.4.5.5 of CSA std.A23.3-94

    Vf=K(Vf/bod+(gvMfe/J)x+(gvMfe/J)y)

    Factored shear resistance,Vr Smallest of Vc1,Vc2,Vc3

    w/o shear reinf.

    Vc1=(1+2/bc).0.2.l.fc.sqrt.(fc') 1.97 N/mm

    Vc2=(as.d/bo+0.2).l.fc.sqrt.(fc') 2.0 N/mm

    Vc3 =0.4lfc.sqrt.(fc' 1.31 N/mm

    Vr = min(Vc) 1.31 N/mm Vr>Vf

    Pile cap is safe in two way shear

  • 8/2/2019 Anchor Bolts Before

    56/117

    TWO WAY SHEAR RESISTANCE (As per cl. 13.4.3.1 of CSA std.A23.3-94)

    Critical section @d/2 from corner pile

    Two way shear from corner pile Vf 597 kN

    length of critical section bo 1.74 m

    bo=p(Dp+d)/4+2ed

    Factored shear resistance,Vr Smallest of Vc1,Vc2,Vc3

    w/o shear reinf.

    Vc1=(1+2/bc).0.2.l.fc.sqrt.(fc') 1.97 N/mm

    2

    Vc2=(as.d/bo+0.2).l.fc.sqrt.(fc') 4.2 N/mm

    Vc3 =0.4lfc.sqrt.(fc')

    1.31 N/mm

    vr = min(Vc) 1.31 N/mm2

    Vr=vr.bo.d 1419.0 kN Vr>Vf

    Pile cap is safe in two way shear

    MOMENT RESISTANCE OF PILECAP

    Critical section @ face of pedestal

    Max.factored moment @ face of

    pedestal

    Mf = 2.Vmax(Sp/2-b/2) 238.8 kN.m

    resistance factor Kr =Mf/1000.d2

    0.62 N/mm2

    p.2-4 of CPCA Concrete Design Handbook

    Ratio of average stress in rectangular

    compression block to the specified

    concrete strength

    a1=0.85-0.0015fc'

    0.805 >0.67 cl.10.1.7(c) of CSA std.A23.3-94

    Required ratio of tension reinforcement

    r = a1fcfc/fs.fy.(1-sqrt.(1-(2Kr/a1.fc.fc'))) 0.0019 P.no.123 of Reinforced Concrete Design -Pillai

    Required area of

    tension reinforcement As reqd. 1158 mm2/m

    Minimum area of tension reinforcement

    As min = 0.002*1000*(D-ep) 1400 mm /m cl.7.8.1 of CSA std.A23.3-94

    Try 20M @ 200 mm :Bottom,E.W.

    area of tension reinforcement 1800 mm2/m o.k.

    Provide 20M @ 200 mm @ bottom e.w.

    Provide 16M @ 200 mm @ top e.w.

  • 8/2/2019 Anchor Bolts Before

    57/117

    ADFREEZE AND FROST HEAVE FOR PILE CAP

    Length of pile 16 m

    Area of pilecap A=L.B 5.29 m2

    Perimeter of pile cap =2(L+B) 9.2 m

    Compressive strength of Geospan Cs 40 kN/m2

    p. no. 35 of 38 in soil report

    Adfreeze value to be applied to sides 30 kN/m2

    p. no. 36 of 38 in soil report

    Allowable static skin friction below 10 m 75 kN/m2

    Table 5.1 of soil report

    Max. uplift due to adfreeze =A.Cs 212 kN

    Max. uplift from sides due to adfreeze 220.8 kN

    Total uplift 432 kN

    Dead load from structure 780 kN Refer S Dle in support reactions

    Skin friction beyond 10 m resisting uplift 915.6 kN

    Total resisting force 1695.6 kN >Total uplift

    No need of bond break around the pile cap

    4d

    =1

    300

    4d = 1300500500

    500

    500

    2300

    2300

    800

    Fz (-ve)

    Fy (+ve)

    300

    600

    M20 @ 200 c/c e.w.M16 @ 200 c/c e.w.

    324 mm dia x 9.52 mm WT pile 16.0m length

  • 8/2/2019 Anchor Bolts Before

    58/117

    Data

    No.of piles 4

    Pile diameter (Dp) 0.324 m

    Length of pile cap (L) 2.3 m

    Width of pile cap (B) 2.3 m

    Thickness of pile cap (D) 0.8 m

    C/C of piles (Sp

    ) 1.3 m = 4d

    Edge distance (ed) 0.5 m

    Pile embedment in pilecap (ep) 0.1 m

    Bottom of pilecap below GL 1.6 m

    Depth of soil on pilecap 0.6 m

    Width of pedestal (b) 0.9 m

    Length of pedestal ( l ) 0.9 m

    Height of pedestal above GL 0.3 m

    Total height of pedestal 0.9 m

    Grade of concrete 30 N/mm2

    Grade of steel 400 N/mm2

    Density of concrete 25 kN/m3

    Density of soil 16 kN/m3

    Clear cover to bottom reinf 50 mm

    Lever arm 1.6 m

    Self weight of pilecap

    Self weight of pilecap 106 kN

    Self weight of pedestal 18 kN

    Total wt. of foundation 124 kN

    Factored wt. of foundation 155 kN

    Design of pile cap for module 34-IF

  • 8/2/2019 Anchor Bolts Before

    59/117

    0.5

    1.3

    0.5

    0.5 1.3 0.5

    ONE WAY SHEAR RESISTANCE (As per cl.15.5.3 of CSA std.A23.3-94)

    Main reinf. Diameter (db) 20 mm

    Effective depth of pile cap (d) 0.62 m

    (d =tpc-ep-cover-1.5db)

    Location of critical section 1.07 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 0.812 m

    If section falls beyond pile

    then no shear

    0.5*(Sp+Dp)< S No shear on the section

    ONE WAY SHEAR RESISTANCE (As per cl.13.4.6.2 of CSA std.A23.3-94)

    Parameters :

    l 1

    fc 0.6

    fs 0.85

    Critical shear section along 0.310 m

    a line located d/2 from the corner pile

    One way shear force (Vf) 575 kN

    from the corner pile

    Length of critical section bw 2.36 m

    2(d/2+Dp/2)+2* sqrt.(ed2+ed

    2)

    Vc1 =(260/(1000+d)).l.fc.sqrt.fc'.bw.d 1248.5 kN cl.11.3.5.2 of CSA std.A23.3-94

    Vc2=0.1.l.fc.sqrt.fc'.bw.d 480.5 kN

    Factored one way shear (Vr) 1248.5 kN Vr>Vf

    resistance w/o shear reinf.

    Max. of Vc1 & Vc2

    Pile cap is safe in one way shear

    d/2

    TWO-WAY SHEAR

    TWO-WAY SHEAR

    ONE WAY SHEAR - N/A

    ONE-WAY SHEAR

  • 8/2/2019 Anchor Bolts Before

    60/117

    TWO WAY SHEAR RESISTANCE (As per cl. 13.4.3.1 of CSA std.A23.3-94)

    Parameters:

    as for interior column 4

    as for exterior column 3

    p 3.14

    Critical section @ d/2 from pedestal face

    Length of critical shear section bo 6.08 m

    bo=2(b+d+l+d)

    Fraction of unbalanced moment

    transferred by eccentricity of shear

    gvx = 1-1/(1+2/3.sqrt.((b+d)/(l+d)) 0.4 cl.13.4.5.3 of CSA std.A23.3-94

    Polar moment of inertia of the critical 1.089E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    sect. About its centroidal axis (Jx)

    (b+d)d3/6+(b+d)

    3d/6+d(l+d)(b+d)

    2/2

    Polar moment of inertia of the critical 1.089E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    sect. About its centroidal axis (Jy)

    (l+d)d3/6+(l+d)3d/6+d(b+d)(l+d)2/2

    Distance from NA to extreme 0.76 m

    compression ex=(l+d)/2

    Distance from NA to extreme 0.76 m

    compression ey=(b+d)/2

    Location of critical section 0.76 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 0.812 m

    If section falls beyond or inside pile No shear on the section

    then no shear

    Factored shear stress (Vf) 0.537 N/mm2

    cl.13.4.5.5 of CSA std.A23.3-94

    Vf=K(Vf/bod+(gvMfe/J)x+(gvMfe/J)y)

    Factored shear resistance,Vr Smallest of Vc1,Vc2,Vc3

    w/o shear reinf.

    Vc1=(1+2/bc).0.2.l.fc.sqrt.(fc') 1.97 N/mm

    Vc2=(as.d/bo+0.2).l.fc.sqrt.(fc') 2.0 N/mm

    Vc3 =0.4lfc.sqrt.(fc'

    1.31 N/mm

    Vr = min(Vc) 1.31 N/mm Vr>Vf

    Pile cap is safe in two way shear

  • 8/2/2019 Anchor Bolts Before

    61/117

    TWO WAY SHEAR RESISTANCE (As per cl. 13.4.3.1 of CSA std.A23.3-94)

    Critical section @d/2 from corner pile

    Two way shear from corner pile Vf 575 kN

    length of critical section bo 1.74 m

    bo=p(Dp+d)/4+2ed

    Factored shear resistance,Vr Smallest of Vc1,Vc2,Vc3

    w/o shear reinf.

    Vc1=(1+2/bc).0.2.l.fc.sqrt.(fc') 1.97 N/mm

    2

    Vc2=(as.d/bo+0.2).l.fc.sqrt.(fc') 4.2 N/mm

    Vc3 =0.4lfc.sqrt.(fc')

    1.31 N/mm

    vr = min(Vc) 1.31 N/mm2

    Vr=vr.bo.d 1419.0 kN Vr>Vf

    Pile cap is safe in two way shear

    MOMENT RESISTANCE OF PILECAP

    Critical section @ face of pedestal

    Max.factored moment @ face of

    pedestal

    Mf = 2.Vmax(Sp/2-b/2) 230.1 kN.m

    resistance factor Kr =Mf/1000.d2

    0.60 N/mm2

    p.2-4 of CPCA Concrete Design Handbook

    Ratio of average stress in rectangular

    compression block to the specified

    concrete strength

    a1=0.85-0.0015fc'

    0.805 >0.67 cl.10.1.7(c) of CSA std.A23.3-94

    Required ratio of tension reinforcement

    r = a1fcfc/fs.fy.(1-sqrt.(1-(2Kr/a1.fc.fc'))) 0.0018 P.no.123 of Reinforced Concrete Design -Pillai

    Required area of

    tension reinforcement As reqd. 1115 mm2/m

    Minimum area of tension reinforcement

    As min = 0.002*1000*(D-ep) 1400 mm /m cl.7.8.1 of CSA std.A23.3-94

    Try 20M @ 200 mm :Bottom,E.W.

    area of tension reinforcement 1800 mm2/m o.k.

    Provide 20M @ 200 mm @ bottom e.w.

    Provide 16M @ 200 mm @ top e.w.

  • 8/2/2019 Anchor Bolts Before

    62/117

    ADFREEZE AND FROST HEAVE FOR PILE CAP

    Length of pile 16 m

    Area of pilecap A=L.B 5.29 m2

    Perimeter of pile cap =2(L+B) 9.2 m

    Compressive strength of Geospan Cs 40 kN/m2

    p. no. 35 of 38 in soil report

    Adfreeze value to be applied to sides 30 kN/m2

    p. no. 36 of 38 in soil report

    Allowable static skin friction below 10 m 75 kN/m2

    Table 5.1 of soil report

    Max. uplift due to adfreeze =A.Cs 212 kN

    Max. uplift from sides due to adfreeze 220.8 kN

    Total uplift 432 kN

    Dead load from structure 746 kN Refer S Dle in support reactions

    Skin friction beyond 10 m resisting uplift 915.6 kN

    Total resisting force 1661.6 kN >Total uplift

    No need of bond break around the pile cap

    4d

    =1

    300

    4d = 1300500500

    500

    500

    2300

    2300

    800

    Fz (-ve)

    Fy (+ve)

    300

    600

    M20 @ 200 c/c e.w.M16 @ 200 c/c e.w.

    324 mm dia x 9.52 mm WT pile 16.0m length

  • 8/2/2019 Anchor Bolts Before

    63/117

    Data

    No. of piles 6

    Pile diameter (Dp) 0.324 m

    Length of pile cap (L) 3.6 m

    Width of pile cap (B) 2.3 m

    Thickness of pile cap (D) 0.8 m

    C/C of piles (Sp) 1.3 m = 4d

    Edge distance (ed) 0.5 mPile embedment in pilecap (ep) 0.1 m

    Bottom of pilecap below GL 1.6 m

    Depth of soil on pilecap 0.6 m

    Width of pedestal (b) 0.9 m

    Length of pedestal ( l ) 0.9 m

    Height of pedestal above GL 0.3 m

    Total height of pedestal 0.90 m

    Grade of concrete 30 N/mm2

    Grade of steel 400 N/mm2

    Density of concrete 25 kN/m3

    Density of soil 16 kN/m3

    Clear cover to bottom reinf 50 mm

    Lever arm 1.6 m

    Self weight of pilecap

    Self weight of pilecap 166 kN

    Self weight of pedestal 18 kN

    Total wt. of foundation 184 kN

    Factored wt. of foundation 230 kN

    m 0.5

    1.3

    1.3

    0.5

    0.5 1.3 1.3 0.5

    ONE WAY SHEAR RESISTANCE (As per cl.15.5.3 of CSA std.A23.3-94)

    Main reinf. Diameter (db) 20 mm

    Effective depth of pile cap (d) 0.62 m

    (d =tpc-ep-cover-1.5db)

    Location of critical section 1.07 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 0.812 m

    If section falls beyond pile

    then no shear

    0.5*(Sp+Dp)< S No shear on the section

    Design of pile cap for module 34-35 TB

    TWO-WAY SHEAR

    TWO-WAY SHEAR

    ONE WAY SHEAR - N/A

    ONE WAY SHEAR

    d/2

  • 8/2/2019 Anchor Bolts Before

    64/117

    ONE WAY SHEAR RESISTANCE (As per cl.13.4.6.2 of CSA std.A23.3-94)

    Parameters :

    l 1

    fc 0.6

    fs 0.85

    Critical shear section along 0.310 m

    a line located d/2 from the corner pile

    One way shear force (Vf) 427 kN

    from the corner pile

    Length of critical section bw 2.36 m

    2(d/2+Dp/2)+2* sqrt.(ed2+ed

    2)

    Vc1 =(260/(1000+d)).l.fc.sqrt.fc'.bw.d 1248.5 kN cl.11.3.5.2 of CSA std.A23.3-94

    Vc2=0.1.l.fc.sqrt.fc'.bw.d 480.5 kN

    Factored one way shear (Vr) 1248.5 kN Vr>Vfresistance w/o shear reinf.

    Max. of Vc1 & Vc2

    Pile cap is safe in one way shear

  • 8/2/2019 Anchor Bolts Before

    65/117

    TWO WAY SHEAR RESISTANCE (As per cl. 13.4.3.1 of CSA std.A23.3-94)

    Parameters:

    as for interior column 4

    as for exterior column 3

    p 3.14

    Critical section @ d/2 from pedestal face

    Length of critical shear section bo 6.08 m

    bo=2(b+d+l+d)

    Fraction of unbalanced moment

    transferred by eccentricity of shear

    gvx = 1-1/(1+2/3.sqrt.((b+d)/(l+d)) 0.4 cl.13.4.5.3 of CSA std.A23.3-94

    Polar moment of inertia of the critical 1.089E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    sect. About its centroidal axis (Jx)

    (b+d)d3/6+(b+d)

    3d/6+d(l+d)(b+d)

    2/2

    Polar moment of inertia of the critical 1.089E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    sect. About its centroidal axis (Jy)

    (l+d)d3/6+(l+d)

    3d/6+d(b+d)(l+d)

    2/2

    Distance from NA to extreme 0.76 m

    compression ex=l+d/2

    Distance from NA to extreme 0.76 m

    compression ey=b+d/2

    Location of critical section 0.76 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 0.812 m

    Factored shear stress (Vf) 0.563 N/mm cl.13.4.5.5 of CSA std.A23.3-94

    Vf=K(Vf/bod+(gvMfe/J)x+(gvMfe/J)y)

    Factored shear resistance,Vr Smallest of Vc1,Vc2,Vc3

    w/o shear reinf.

    Vc1=(1+2/bc).0.2.l.fc.sqrt.(fc') 1.97 N/mm

    Vc2=(as.d/bo+0.2).l.fc.sqrt.(fc') 2.0 N/mm

    Vc3 =0.4lfc.sqrt.(fc'

    1.31 N/mm

    Vr = min(Vc) 1.31 N/mm Vr>Vf

    Pile cap is safe in two way shear

  • 8/2/2019 Anchor Bolts Before

    66/117

    TWO WAY SHEAR RESISTANCE (As per cl. 13.4.3.1 of CSA std.A23.3-94)

    Critical section @d/2 from corner pile

    Two way shear from corner pile Vf 427 kN

    length of critical section bo 1.74 m

    bo=p(Dp+d)/4+2ed

    Factored shear resistance,Vr Smallest of Vc1,Vc2,Vc3

    w/o shear reinf.

    Vc1=(1+2/bc).0.2.l.fc.sqrt.(fc') 1.97 N/mm

    2

    Vc2=(as.d/bo+0.2).l.fc.sqrt.(fc') 4.2 N/mm

    Vc3 =0.4lfc.sqrt.(fc')

    1.31 N/mm

    vr = min(Vc) 1.31 N/mm2

    Vr=vr.bo.d 1419.0 kN Vr>Vf

    Pile cap is safe in two way shear

    MOMENT RESISTANCE OF PILECAP

    Critical section @ face of pedestal

    Max.factored moment @ face of

    pedestal

    Mf = 3.Vmax(Sp/2-b/2) 256.0 kN.m

    resistance factor Kr =Mf/1000.d2

    0.666 N/mm2

    p.2-4 of CPCA Concrete Design Handbook

    Ratio of average stress in rectangular

    compression block to the specified

    concrete strength

    a1=0.85-0.0015fc'

    0.805 >0.67 cl.10.1.7(c) of CSA std.A23.3-94

    Required ratio of tension reinforcement

    r = a1fcfc/fs.fy.(1-sqrt.(1-(2Kr/a1.fc.fc' 0.0020 P.no.123 of Reinforced Concrete Design -Pillai

    Required area of

    tension reinforcement As reqd. 1244 mm2/m

    Minimum area of tension reinforcement

    As min = 0.002*1000*(D-ep) 1400 mm /m cl.7.8.1 of CSA std.A23.3-94

    Try 20M @ 200 mm :Bottom,E.W.

    area of tension reinforcement 1800 mm2/m o.k.

    Provide 20M @ 200 mm @ bottom e.w.

    Provide 16M @ 200 mm @ top e.w.

  • 8/2/2019 Anchor Bolts Before

    67/117

    ADFREEZE AND FROST HEAVE FOR PILE CAP

    Length of pile 16 m

    Area of pilecap A=L.B 8.28 m2

    Perimeter of pile cap =2(L+B) 11.8 m

    Compressive strength of Geospan C 40 kN/m p. no. 35 of 38 in soil report

    Adfreeze value to be applied to sides 30 kN/m2

    p. no. 36 of 38 in soil report

    Allowable static skin friction below 10 75 kN/m2

    Table 5.1 of soil report

    Max. uplift due to adfreeze =A.Cs 331 kN

    Max. upl ift from sides due to adfreeze 283.2 kN

    Total uplift 614 kN

    Dead load from structure 772 kN Refer S Dle in support reactions

    Skin friction beyond 10 m resisting upli 915.6 kN

    Total resisting force 1687.6 kN >Total uplift

    No need of bond break around the pile cap

    4d = 1300

    4d

    =1

    300

    4d = 1300 500500

    2300

    3600

    500

    500

    800

    Fz (-ve)Fy (+ve)

    300

    600

    M20 @ 200 c/c e.w.M16 @ 200 c/c e.w.

    324mm dia x 9.52 mm WT pile 16.0m length

  • 8/2/2019 Anchor Bolts Before

    68/117

    Data

    No.of piles 4

    Pile diameter (Dp) 0.324 m

    Length of pile cap (L) 2.3 m

    Width of pile cap (B) 2.3 m

    Thickness of pile cap (D) 0.8 m

    C/C of piles (Sp) 1.3 m = 4dEdge distance (ed) 0.5 m

    Pile embedment in pilecap (ep) 0.1 m

    Bottom of pilecap below GL 1.6 m

    Depth of soil on pilecap 0.6 m

    Width of pedestal (b) 0.9 m

    Length of pedestal ( l ) 0.9 m

    Height of pedestal above GL 0.3 m

    Total height of pedestal 0.9 m

    Grade of concrete 30 N/mm2

    Grade of steel 400 N/mm2

    Density of concrete 25 kN/m3

    Density of soil 16 kN/m3

    Clear cover to bottom reinf 50 mm

    Lever arm 1.6 m

    Self weight of pilecap

    Self weight of pilecap 106 kN

    Self weight of pedestal 18 kN

    Total wt. of foundation 124 kN

    Factored wt. of foundation 155 kN

    Design of pile cap for module 35-IF

  • 8/2/2019 Anchor Bolts Before

    69/117

    0.5

    1.3

    0.5

    0.5 1.3 0.5

    ONE WAY SHEAR RESISTANCE (As per cl.15.5.3 of CSA std.A23.3-94)

    Main reinf. Diameter (db) 20 mm

    Effective depth of pile cap (d) 0.62 m

    (d =tpc-ep-cover-1.5db)

    Location of critical section 1.07 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 0.812 m

    If section falls beyond pile

    then no shear

    0.5*(Sp+Dp)< S No shear on the section

    ONE WAY SHEAR RESISTANCE (As per cl.13.4.6.2 of CSA std.A23.3-94)

    Parameters :

    l 1

    fc 0.6

    fs 0.85

    Critical shear section along 0.310 m

    a line located d/2 from the corner pile

    One way shear force (Vf) 576 kN

    from the corner pile

    Length of critical section bw 2.36 m

    2(d/2+Dp/2)+2* sqrt.(ed2+ed

    2)

    Vc1 =(260/(1000+d)).l.fc.sqrt.fc'.bw.d 1248.5 kN cl.11.3.5.2 of CSA std.A23.3-94

    Vc2=0.1.l.fc.sqrt.fc'.bw.d 480.5 kN

    Factored one way shear (Vr) 1248.5 kN Vr>Vf

    resistance w/o shear reinf.

    Max. of Vc1 & Vc2

    Pile cap is safe in one way shear

    d/2

    TWO-WAY SHEAR

    TWO-WAY SHEAR

    ONE WAY SHEAR - N/A

    ONE-WAY SHEAR

  • 8/2/2019 Anchor Bolts Before

    70/117

    TWO WAY SHEAR RESISTANCE (As per cl. 13.4.3.1 of CSA std.A23.3-94)

    Parameters:

    as for interior column 4

    as for exterior column 3

    p 3.14

    Critical section @ d/2 from pedestal face

    Length of critical shear section bo 6.08 m

    bo=2(b+d+l+d)

    Fraction of unbalanced momenttransferred by eccentricity of shear

    gvx = 1-1/(1+2/3.sqrt.((b+d)/(l+d)) 0.4 cl.13.4.5.3 of CSA std.A23.3-94

    Polar moment of inertia of the critical 1.089E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    sect. About its centroidal axis (Jx)

    (b+d)d3/6+(b+d)

    3d/6+d(l+d)(b+d)

    2/2

    Polar moment of inertia of the critical 1.089E+12 mm4

    p.no.5-26 of CSA std.A23.3-94

    sect. About its centroidal axis (Jy)

    (l+d)d3/6+(l+d)

    3d/6+d(b+d)(l+d)

    2/2

    Distance from NA to extreme 0.76 m

    compression ex=(l+d)/2

    Distance from NA to extreme 0.76 m

    compression ey=(b+d)/2

    Location of critical section 0.76 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 0.812 m

    Factored shear stress (Vf) 0.537 N/mm cl.13.4.5.5 of CSA std.A23.3-94

    Vf=K(Vf/bod+(gvMfe/J)x+(gvMfe/J)y)

    Factored shear resistance,Vr Smallest of Vc1,Vc2,Vc3

    w/o shear reinf.

    Vc1=(1+2/bc).0.2.l.fc.sqrt.(fc') 1.97 N/mm

    Vc2=(as.d/bo+0.2).l.fc.sqrt.(fc') 2.0 N/mm

    2

    Vc3 =0.4lfc.sqrt.(fc')

    1.31 N/mm

    Vr = min(Vc) 1.31 N/mm Vr>Vf

    Pile cap is safe in two way shear

  • 8/2/2019 Anchor Bolts Before

    71/117

    TWO WAY SHEAR RESISTANCE (As per cl. 13.4.3.1 of CSA std.A23.3-94)

    Critical section @d/2 from corner pile

    Two way shear from corner pile Vf 576 kN

    length of critical section bo 1.74 m

    bo=p(Dp+d)/4+2ed

    Factored shear resistance,Vr Smallest of Vc1,Vc2,Vc3

    w/o shear reinf.

    Vc1=(1+2/bc).0.2.l.fc.sqrt.(fc') 1.97 N/mm

    2

    Vc2=(as.d/bo+0.2).l.fc.sqrt.(fc') 4.2 N/mm

    Vc3 =0.4lfc.sqrt.(fc')

    1.31 N/mm2

    vr = min(Vc) 1.31 N/mm

    Vr=vr.bo.d 1419.0 kN Vr>Vf

    Pile cap is safe in two way shear

    MOMENT RESISTANCE OF PILECAP

    Critical section @ face of pedestal

    Max.factored moment @ face of

    pedestal

    Mf = 2.Vmax(Sp/2-b/2) 230.4 kN.m

    resistance factor Kr =Mf/1000.d2

    0.60 N/mm2

    p.2-4 of CPCA Concrete Design Handbook

    Ratio of average stress in rectangularcompression block to the specified

    concrete strength

    a1=0.85-0.0015fc'

    0.805 >0.67 cl.10.1.7(c) of CSA std.A23.3-94

    Required ratio of tension reinforcement

    r = a1fcfc/fs.fy.(1-sqrt.(1-(2Kr/a1.fc.fc'))) 0.0018 P.no.123 of Reinforced Concrete Design -Pillai

    Required area of

    tension reinforcement As reqd. 1117 mm2/m

    Minimum area of tension reinforcement

    As min = 0.002*1000*(D-ep) 1400 mm2/m cl.7.8.1 of CSA std.A23.3-94

    Try 20M @ 200 mm :Bottom,E.W.

    area of tension reinforcement 1800 mm2/m o.k.

    Provide 20M @ 200 mm @ bottom e.w.

    Provide 16M @ 200 mm @ top e.w.

  • 8/2/2019 Anchor Bolts Before

    72/117

    ADFREEZE AND FROST HEAVE FOR PILE CAP

    Length of pile 16 m

    Area of pilecap A=L.B 5.29 m2

    Perimeter of pile cap =2(L+B) 9.2 m

    Compressive strength of Geospan Cs 40 kN/m p. no. 35 of 38 in soil report

    Adfreeze value to be applied to sides 30 kN/m2

    p. no. 36 of 38 in soil report

    Allowable static skin friction below 10 m 75 kN/m2

    Table 5.1 of soil report

    Max. uplift due to adfreeze =A.Cs 212 kN

    Max. uplift from sides due to adfreeze 220.8 kN

    Total uplift 432 kN

    Dead load from structure 746 kN Refer S Dle in support reactions

    Skin friction beyond 10 m resisting uplift 915.6 kN

    Total resisting force 1661.6 kN >Total uplift

    No need of bond break around the pile cap

    4d

    =

    1300

    4d = 1300500500

    50

    0

    500

    2300

    2300

    800

    Fz (-ve)

    Fy (+ve)

    300

    600

    M20 @ 200 c/c e.w.M16 @ 200 c/c e.w.

    324 mm dia x 9.52 mm WT pile 16.0m length

  • 8/2/2019 Anchor Bolts Before

    73/117

    Data

    No.of piles 4

    Pile diameter (Dp) 0.324 m

    Length of pile cap (L) 2.3 m

    Width of pile cap (B) 2.3 m

    Thickness of pile cap (D) 0.8 m

    C/C of piles (Sp) 1.3 m = 4d

    Edge distance (ed) 0.5 m

    Pile embedment in pilecap (ep) 0.1 m

    Bottom of pilecap below GL 1.6 m

    Depth of soil on pilecap 0.6 m

    Width of pedestal (b) 0.9 m

    Length of pedestal ( l ) 0.9 m

    Height of pedestal above GL 0.3 m

    Total height of pedestal 0.9 m

    Grade of concrete 30 N/mm2

    Grade of steel 400 N/mm2

    Density of concrete 25 kN/m3

    Density of soil 16 kN/m3

    Clear cover to bottom reinf 50 mm

    Lever arm 1.6 m

    Self weight of pilecap

    Self weight of pilecap 106 kN

    Self weight of pedestal 18 kN

    Total wt. of foundation 124 kN

    Factored wt. of foundation 155 kN

    Design of pile cap for module 36-IF

  • 8/2/2019 Anchor Bolts Before

    74/117

    0.5

    1.3

    0.5

    0.5 1.3 0.5

    ONE WAY SHEAR RESISTANCE (As per cl.15.5.3 of CSA std.A23.3-94)

    Main reinf. Diameter (db) 20 mm

    Effective depth of pile cap (d) 0.62 m

    (d =tpc-ep-cover-1.5db)

    Location of critical section 1.07 m

    from C.L. of pilecap (S)

    0.5*(Sp+Dp) 0.812 m

    If section falls beyond pile

    then no shear

    0.5*(Sp+Dp)< S No shear on the section

    ONE WAY SHEAR RESISTANCE (As per cl.13.4.6.2 of CSA std.A23.3-94)

    Parameters :

    l 1

    fc 0.6

    fs 0.85

    Critical shear section along 0.310 m

    a line located d/2 from the corner pile

    One way shear force (Vf) 576 kN

    from the corner pile

    Length of critical section bw 2.36 m

    2(d/2+Dp/2)+2* sqrt.(ed2+ed

    2)

    Vc1 =(260/(1000+d)).l.fc.sqrt.fc'.bw.d 1248.5 kN cl.11.3.5.2 of CSA std.