ansi & ul standard

4
Data Bulletin ANSI ® C37 Standard and UL ® 489 Standard Comparison Bulletin No. 0613DB9902 June 1999 Cedar Rapids, IA USA © 1999 Square D All Rights Reserved Since Ben Franklin discovered electricity, people have been struggling to harness its energy and use it safely. As the use of electricity spread into residences and commercial businesses, the need for personal safety and protection against fires became clear. People needed products that were safe to use and afforded protection against the hazards of fire. They used electricity in their homes and businesses but were not trained to determine the types of products they needed to protect themselves and their property. Underwriters Laboratories Inc. (UL), was set up in the late 1800s to test many products for the insurance industry. Fire safety and prevention were a major concern. UL, working with electrical manufacturers, developed standards for electrical products and provided third-party certification assuring that the products provide safe and intended functionality regardless of manufacturer. The products began as safety switches evolving into circuit breakers and load centers. The molded case circuit breakers designed for this market are Listed to the UL 489 Standard. UL 489 requires that these circuit breakers meet specific construction and testing requirements to provide necessary protection while requiring little or no maintenance. One important feature of these types of circuit breakers is the enclosed molded case which provides personal safety as well as assuring proper dielectric clearances. As the need and dependence on electricity grew, power generation along with large industrial users and continuous process industries became a large part of our industrial complex. Safety and fire prevention were major considerations but continuity of service and equipment performance were also primary requirements. These users had highly trained staffs that worked with manufacturers and the International Electrical and Electronics Engineers, Inc. (IEEE ® ) committee to design, test and produce electrical equipment that provided the safety, performance and continuity of service they required. The American National Standards Institute (ANSI) compiled these accumulated design and test documents, provided by IEEE and manufacturers, into ANSI Standards. These standards then became the basis for designing and testing low-voltage power circuit breakers (LVPCBs) and switchgear. Switchgear is designed with strict standards for compartmentalization, drawout construction and steel barriers between circuit breaker, bus and instrument compartments. Because of the compartmentalization and barriers, LVPCBs were designed with an open construction to allow for strength, heat dissipation and maintenance that was necessary for long service life. UL incorporated ANSI Standard C37 into the UL 1558 Standard for switchgear in 1982 and into the UL 1066 standard for low-voltage power circuit breakers in 1985. These two UL standards provide the basis for third-party witnessing and certification to the ANSI Standard. UL 489 ANSI C37.13 and C37.50 or UL 1066 UL67 Panelboards UL 891 Switchboards ANSI Switchgear or UL1558 Switchgear or UL 891 Switchboards EVOLUTION OF PRODUCTS AND MARKETS Underwriters Laboratories Inc. ® (UL ® ) The American National Standards Institute ® (ANSI ® ) CIRCUIT BREAKER AND EQUIPMENT STANDARDS Circuit Breaker Standards Equipment Standards

Upload: anas-memon

Post on 24-Oct-2014

157 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Ansi & Ul Standard

Data Bulletin

ANSI® C37 Standard and UL ® 489 Standard Comparison

Bulletin No. 0613DB9902June 1999

Cedar Rapids, IA USA

© 1999 Square D All Rights Reserved

Since Ben Franklin discovered electricity, people have been struggling toharness its energy and use it safely. As the use of electricity spread intoresidences and commercial businesses, the need for personal safety andprotection against fires became clear.

People needed products that were safe to use and afforded protection againstthe hazards of fire. They used electricity in their homes and businesses butwere not trained to determine the types of products they needed to protectthemselves and their property.

Underwriters Laboratories Inc. (UL), was set up in the late 1800s to test manyproducts for the insurance industry. Fire safety and prevention were a majorconcern. UL, working with electrical manufacturers, developed standards forelectrical products and provided third-party certification assuring that theproducts provide safe and intended functionality regardless of manufacturer.The products began as safety switches evolving into circuit breakers and loadcenters.

The molded case circuit breakers designed for this market are Listed to theUL 489 Standard. UL 489 requires that these circuit breakers meet specificconstruction and testing requirements to provide necessary protection whilerequiring little or no maintenance. One important feature of these types ofcircuit breakers is the enclosed molded case which provides personal safetyas well as assuring proper dielectric clearances.

As the need and dependence on electricity grew, power generation along withlarge industrial users and continuous process industries became a large partof our industrial complex. Safety and fire prevention were majorconsiderations but continuity of service and equipment performance werealso primary requirements. These users had highly trained staffs that workedwith manufacturers and the International Electrical and Electronics Engineers,Inc. (IEEE®) committee to design, test and produce electrical equipment thatprovided the safety, performance and continuity of service they required.

The American National Standards Institute (ANSI) compiled theseaccumulated design and test documents, provided by IEEE andmanufacturers, into ANSI Standards. These standards then became the basisfor designing and testing low-voltage power circuit breakers (LVPCBs) andswitchgear.

Switchgear is designed with strict standards for compartmentalization,drawout construction and steel barriers between circuit breaker, bus andinstrument compartments. Because of the compartmentalization and barriers,LVPCBs were designed with an open construction to allow for strength, heatdissipation and maintenance that was necessary for long service life.

UL incorporated ANSI Standard C37 into the UL 1558 Standard forswitchgear in 1982 and into the UL 1066 standard for low-voltage power circuitbreakers in 1985. These two UL standards provide the basis for third-partywitnessing and certification to the ANSI Standard.

� UL 489� ANSI C37.13 and C37.50 or UL 1066

� UL67 Panelboards� UL 891 Switchboards� ANSI Switchgear or UL1558 Switchgear or UL 891 Switchboards

EVOLUTION OF PRODUCTS ANDMARKETS

Underwriters Laboratories Inc. ® (UL®)

The American National StandardsInstitute ® (ANSI®)

CIRCUIT BREAKER AND EQUIPMENTSTANDARDS

Circuit Breaker Standards

Equipment Standards

Page 2: Ansi & Ul Standard

© 1999 Square D All Rights Reserved2

ANSI® C37 Standard and UL ® 489 Standard Comparison Bulletin No. 0613DB9902Data Bulletin June 1999

The UL and ANSI Standards differ in four basic areas:

� Philosophy� Construction� Performance testing� Certification

The scope of the UL 489 Molded Case Circuit Breaker Standard includesminiature circuit breakers (MCBs), molded case circuit breakers (MCCBs)and insulated case circuit breakers (ICCBs). These circuit breakers aretypically rated 10–6000 A and up to 600 Vac and 500 Vdc. Circuit breakersdesigned and tested to this standard typically exhibit the followingcharacteristics:

� Sealed molded case� Little or no maintenance� No user replaceable parts� Good performance and reliability� Long service life

The scope of the ANSI C37 Low Voltage Power Circuit Breaker Standardincludes 2- or 3-pole stationary and drawout circuit breakers. Thespecifications of these circuit breakers are 254, 508 or 635 Vac maximum,fused or unfused, and manually- or power-operated with or withoutelectromechanical or electronic trip units. These circuit breakers typicallyexhibit the following characteristics:

� Iron frame—older designs are open, newer designs are closed� Maintainable for long service life� Most parts can be replaced in the field� High performance and reliability� High maintenance costs

The main construction differences between UL 489 Listed and ANSI C37Certified circuit breakers are maintainability, ampere interrupting ratings(AIRs), heat rise and endurance. These construction differences result fromthe design and test philosophies outlined above. These differences will bediscussed under Performance Testing.

UL 489 Listed circuit breakers are sealed and require no maintenance for along service life. ANSI C37 Certified circuit breakers typically requiremaintenance for long life and have been designed with an open case tofacilitate maintenance.

The UL 489 and ANSI C37 Standards require the same basic tests includingthe following:

� Dielectric� Calibration� Overload� Temperature� Endurance� Short circuit

Both the UL 489 and ANSI C37 Standards demonstrate the circuit breaker’sability to protect conductors under overload or short-circuit conditions. Themajor differences in performance testing occur during the details andsequences of the tests for overload, temperature, endurance and short-circuit conditions.

DIFFERENCES BETWEEN THE UL 489STANDARD AND THE ANSI C37STANDARD

Philosophy

UL 489 Standard Design and Test Philosophy

ANSI C37 Standard Design and TestPhilosophy

Construction

Performance Testing

Page 3: Ansi & Ul Standard

3© 1999 Square D All Rights Reserved

Bulletin No. 0613DB9902 ANSI ® C37 Standard and UL ® 489 Standard ComparisonJune 1999 Data Bulletin

UL 489 ANSI C37Power Factor: 0.45–0.50 Power Factor: 0.50

Frame size(A)

Number of operations atrated voltage

Frame size(A)

Number of operationsat rated voltage

50–1600 50 600% current 225–800 50 600% current

1601–2500 25 600% current 1600–2000 38 600% current

2501–6000 3 600% current* >2000 0

*An additional 25 operations at 200% current.

UL 489 ANSI C37Temperature 50°C temperature rise at line and load

terminals55°C temperature rise at line andload terminal bus connectionsand 85°C temperature rise oncircuit breaker contacts

Current Standard circuit breaker:� 100% rated current in open air at 40°C� 80% rated current in smallest enclosure

100% rated current in smallestenclosure

Exceptions 100% rated circuit breaker:� 100% rated current in smallest enclosure� Temperature rise may be 60°C if 90°C

wire is used sized to the 75°C chart (NEC)

Trip unit defeated

UL 489 ANSI C37Power factor: 0.75–0.80 Power factor: 0.85

Maintenance not allowed Maintenance allowed

Max. framesize (A)

Number of operations atrated voltage

Max. framesize (A)

Number of operationsat rated voltage

100 60004000

At rated currentWithout current

225 4000100002500

At rated currentWithout currentBetween maintenance

225 40004000

At rated currentWithout current

600 280097001750

At rated currentWithout currentBetween maintenance

600 10005000

At rated currentWithout current

800 280097001750

At rated currentWithout currentBetween maintenance

800 5003000

At rated currentWithout current

1600 8003200500

At rated currentWithout currentBetween maintenance

2500 5002000

At rated currentWithout current

2000 8003200500

At rated currentWithout currentBetween maintenance

6000 4001100

At rated currentWithout current

3200 4001100250

At rated currentWithout currentBetween maintenance

4000 4001100250

At rated currentWithout currentBetween maintenance

Overload TestingOverload testing is done to demonstrate makingand breaking current values that might beobtained when initially energizing a motor load.Each time the circuit breaker is closed andopened on a high current load (600%), the contactsurfaces are subjected to arcing and heat. Thisaction simulates an accelerated life test to makesure the contacts provide adequate conductivitythrough many operations. The UL 489 Standardtests all circuit breaker ratings with significantoperations to ensure the design is capable of along service life with no maintenance. The ANSIC37 Standard tests circuit breakers rated only upto 2000 A.

Temperature TestingThe UL 489 Standard allows for two types ofratings. Standard circuit breakers cannot exceeda maximum of 50°C temperature rise at the wireterminal connection at 100% current in 40°C openair. 100% rated circuit breakers may have atemperature rise of 60°C at the wire terminalconnection in the smallest allowable enclosure ifthe circuit breakers are connected with wire ratedat 90°C wiring insulation sized to the 75°C chart(Table 310-16, National Electric Code®—NEC®).The ANSI C37 Standard requires a maximum of55°C temperature rise at 100% in the smallestenclosure and a maximum of 85°C temperaturerise on the contacts.

Endurance TestingCircuit breakers tested to the UL 489 Standardmust pass a significant number of operationswithout any maintenance. This test verifies thatthe design is capable of a long service life. TheANSI C37 Standard tests circuit breakers forfurther operations but then allows formaintenance of the circuit breaker at relativelyshort intervals.

NOTE: No manufacturer currently offers 225 A or600 A frame circuit breakers tested to ANSI C37.

Short-circuit TestingThe short-circuit tests reflect differences in thephilosophies between the UL and ANSI circuitbreaker standards. The UL 489 Standard requiresthat the tests be conducted at several values ofshort-circuit current. A separate test sequenceevaluates the maximum interrupting ratingclaimed by the manufacturer. Tests are conductedat the rated voltage(s) of the circuit breaker whichis typically 240, 480 or 600 V.

Page 4: Ansi & Ul Standard

Bulletin No. 0613DB9902 June 1999 © 1999 Square D All Rights Reserved.

Square D and are registered trademarks of Square D/Schneider Electric or related companies.Underwriters Laboratories Inc. and UL are registered trademarks of Underwriters Laboratories Inc.ANSI is a registered trademark of American National Standards Institute, Inc.National Electric Code and NEC are registered trademarks of National Fire Protection Association, Inc.IEEE is a registered trademark of The Institute of Electrical and Electronics Engineers, Inc.All other trademarks are the intellectual property of their respective companies.

Square D CompanyPO Box 3069, 3700 Sixth St. SWCedar Rapids, IA 52406-3069Field Services: 1-800-634-2003www.squared.com

ANSI® C37 Standard and UL ® 489 Standard Comparison Bulletin No. 0613DB9902Data Bulletin June 1999

4

Certification tests to the UL 489 Standard are witnessed by UL engineeringrepresentatives. At the successful completion of the test program, UL permitscircuit breakers to bear a UL Listing mark combined with the product identityof “CIRCUIT BREAKER” or “CIRCUIT BREAKER FRAME.” These circuitbreakers are then required to undergo subsequent follow-up testing on aregular basis: quarterly, semiannually or biannually depending on the circuitbreaker size and quantities produced. All follow-up tests are witnessed by ULfield representatives.

Certification tests to the UL 1066 Standard (which include the requirementsof the ANSI C37 Standard) are witnessed by UL engineering representatives.At the successful completion of both UL test programs, UL permits the circuitbreaker to bear a UL Listing mark combined with the product identity of “LOWVOLTAGE AC POWER CIRCUIT BREAKER” or “LOW VOLTAGE ACPOWER CIRCUIT BREAKER FRAME.” While UL conducts follow-upinspections on the UL 1066 Standard tested products to ensure that theconstruction has not changed from that which was originally tested, they donot require subsequent follow-up testing.

ShortCircuit

UL 489 ANSI C37

Power factor ≤10,000 A10,001–20,000 A≥ 20,000 A

0.45–0.500.25–0.300.15–0.20

0.15 Unfused0.20 Fused

Voltage andcurrent

Rated voltage with low-, medium-and high-level current

Rated current at the three voltagelevels: 254, 508 and 635 Vac

Operations Open—close/open on all threepoles

Open—close/open on all three poles.First open at closing angle to ensurepeak current of 2.3 x rated current inone phase

Open—close/open on eachindividual pole at reduced currentlevel Open—close/open individual pole at

87% of rated current

Short-time withstand—first ON cycle,closing angle must ensure a peakcurrent of 2.3 x rated current in onephase. Circuit breaker remainsclosed, tripping disabled—0.5 sec.ON, 15 sec. OFF, 0.5 sec. ON

Three-pole circuit breakers are tested underthree-phase conditions during the maximuminterrupting ability sequence. Each pole is testedindividually at a reduced current level. The circuitbreaker must safely interrupt the short-circuitcurrent and protect the rated wire in the circuit.

The ANSI C37 Standard requires that a three-pole circuit breaker be tested under three-phaseconditions at the maximum interrupting rating andalso that each individual pole be tested at 87% ofthe maximum interrupting rating. Both the three-phase and the individual-pole tests are conductedat rated maximum voltages of 254, 508 and 635 V.The ANSI C37 Standard also includes a separatesequence to evaluate the short-time withstandcurrent of the circuit breaker. The short-timewithstand current is a high-level current that canbe maintained for 0.5 seconds without damage tothe circuit breaker.

Certification