Carbex AB • Box 115 • 592 22 Vadstena • Sweden • Tel +46 (0)143-294 40 • [email protected] • www.carbex.se 1/10
PRODUCT INFORMATION
ANTI-CONDENSATION HEATERS
Anti-condensation heaters prevent the occurrence of condensation in electric plant and equipment such aselectric motors and generators. Their compact design facilitates easy installation, even in small engines with restricted space. The anti-condensation heateris mounted around the two outer ends of the statorwindings before impregnation.
• Mounted for constant connection to the mains orvia relay for automatic disconnection when in operation. • Available for 230V and 110V power supply as standard • Power 10 – 100 W as stock items• Many versions, including EX and EX/UL variants
Properties• Available in EX and EX/UL versions• Available as 230 and 110V versions as standard• Available with 10 – 100 W power as standard• Compact design facilitates easy installation at both ends of windings • Designed for impregnation during motor production• Also for retrofitting (even when the best thermal transfer results are attained when anti-condensation heaters are impregnated against the windings) • Anti-condensation heaters are usually dimensioned so that at least 70% of the stator’s perimeter is covered. If an anti-condensation heater is chosen with a perimeter larger than the stator’s perimeter, it is very important that the part of the anti-condensation heater which overlaps is kept apart from the other by at least 5 mm, otherwise so-called ”hot spots” are formed as a result thereof.
Anti-condensation heaters prevent the occurrence of condensation in electric plant and equip-ment such as electric motors and generators. Their compact design facilitates easy installation, even in small engines with restricted space. The anti-condensation heater is mounted around the two outer ends of the stator windings before impregnation
Typical applicationsMotors, generators, slip ring units and other electrical equipment where a risk of condensation exists. Examples of bran-ches where they find use include offshore sector, shipbuilding industry, marine equipment, port/harbour cranes, pump installations and other applications where plant and equipment are exposed to damp conditions. All outdoor installa-tions in tropical environments or environments where the temperature is such that condensation is formed, for example, Nordic climates. A cheap insurance against unnecessary downtime and the rewinding of motors and generators as moisture and frost damage can lead to creep currents and short circuits in the longer term,
Composition/FunctionAn anti-condensation heater is usually connected when the equipment is not in use in order to constantly keepthe temperature at a level where condensation is notformed. It is then disconnected via a relay when theengine, motor or generator is operational and self-heating prevents any condensation forming.
• The inner conductor consists of an insulated heating conductor wound around a glassfiber core.• The heating conductor is connected to ”cold” terminal cables usually 500mm long for mounting to the terminal box. Anti-condensation heaters can be manufactured with terminal cables in each end of the heater or with both cables at the same end which often facilitates assembly. • External insulation of glassfiber braid for flat type anti-condensation heaters • External insulation of silicone or PTFE for round type anti-condensation heaters depending on the version
Packaging• Stocked items sold individually (see item list)• Other versions and MOQ on request
Product information for which Carbex bears no responsibility is provided by the manufacturer.
Carbex AB • Box 115 • 592 22 Vadstena • Sweden • Tel +46 (0)143-294 40 • [email protected] • www.carbex.se 2/10
Product information for which Carbex bears no responsibility is provided by the manufacturer.
ANTI-CONDENSATION HEATERS
Items number Designation Ref size Version Length terminal cable Usual stock item100500102 A-C Heaters 21 cm/10W/230V 00B RSV Round 500 X100500103 A-C Heaters 21 cm/10W/110V 00A RSV Round 500 X100500104 A-C Heaters 30cm/25W/230V 0B RSV Flat 500 X100500105 A-C Heaters 30cm/25W/110V 0A RSV Flat 500 X100500106 A-C Heaters 43 cm/25W/230V 1B RSV Flat 500 X100500107 A-C Heaters 43 cm/25W/110V 1A RSV Flat 500 X100500110 A-C Heaters 68 cm/40W/230V 3B RSV Flat 500 X100500111 A-C Heaters 68 cm/40W/110V 3A RSV Flat 500 X100500112 A-C Heaters 79 cm/26W/230V 4B RSV Flat 500 X100500113 A-C Heaters 79 cm/26W/110V 4A RSV Flat 500 X100500114 A-C Heaters 101 cm/42W/230V 5B RSV Flat 500 X100500115 A-C Heaters 101 cm/42W/110V 5A RSV Flat 500 -‐100500116 A-C Heaters 106 cm/50W/230V 6B RSV Flat 500 X100500117 A-C Heaters 106 cm/50W 110V 6A RSV Flat 500 X100500118 A-C Heaters 147 cm/65W/230V 7B RSV Flat 500 X100500119 A-C Heaters 147 cm/65W/110V 7A RSV Flat 500 X100500120 A-C Heaters 170 cm/100W/230V 8B RSV Flat 500 X100500121 A-C Heaters 170 cm/100W/110V 8A RSV Flat 500 X100500122 A-C Heaters 170 cm/75W/230V RSV Flat 500 X100500123 A-C Heaters 170 cm/75W/110V RSV Flat 500 -‐100500124 A-C Heaters 185 cm/100W/230V RSV Flat 500 X100500125 A-C Heaters 185 cm/100W /110V RSV Flat 500 -‐100500126 A-C Heaters 68 cm/21W/230V 2B RSV Flat 500 X100500127 A-C Heaters 68 cm/21W/110V 2A RSV Flat 500 X100500128 A-C Heaters 106 cm/100W/230V Special HB B (Not EX/UL) 500 -‐100500129 A-C Heaters 106 cm/109W/230V Special HB B (Not EX/UL) 500 -‐100500130 A-C Heaters 68 cm/78W/230V Special HB B (Not EX/UL) 500 -‐100500131 A-C Heaters 101 cm/92W/230V Special HB B (Not EX/UL) 500 -‐100500132 A-C Heaters 106 cm/50W/230V 6B RSV Flat, PTFE terminal cable 500 X100500133 A-C Heaters 43 cm/25W/230V 1B RSV Flat, PTFE terminal cable 500 X100500135 A-C Heaters 106 cm/50W 110V 6A ACH-‐F, spec. UL 500 -‐100500136 A-C Heaters 106 cm/50W/110V 6A RSV Flat, PTFE terminal cable 500 X100500137 A-C Heaters 43 cm/25W/110V 1A RSV Flat, PTFE terminal cable 500 X100500140 A-C Heaters 170 cm/125W/230V Special HB B (Not EX/UL) 500 -‐100500141 A-C Heaters 106 cm/109W/110V Special HB B (Not EX/UL) 500 -‐100500142 A-C Heaters 101 cm/92W/110V Special HB B (Not EX/UL) 500 -‐100500143 A-C Heaters 79 cm/40W/230V Special HB B (Not EX/UL) 500 -‐
Carbex AB • Box 115 • 592 22 Vadstena • Sweden • Tel +46 (0)143-294 40 • [email protected] • www.carbex.se 3/10
ANTI-CONDENSATION HEATERS
Technical data / Dimensions The technical data is a direct extract from the manufacturer’s data sheet in English. See item list
Product information for which Carbex bears no responsibility is provided by the manufacturer.
Technical data anti-condensation heaters
Technical dataRSV Flat RSV Round HB-‐A HB-‐B
Totally silicone-free No No Yes YesInsulation terminal cable Silicone* Silicone* PTFE PTFEExternal insulation heater Glassfiber Silicone PTFE GlassfiberLength terminal cable (standard ca mm) 500 500 500 500Dimensions heater cable max (ca mm) 3 x 11 Ø 4 Ø 4 3 x 14Terminal cable from heater cable’s one side (1)/both sides (2) 1 2 2 1Approvals EX / UL / VDE -‐ **VDE: 40029602 **VDE: 40029602
ATEX: Sira 02ATEX3410U ATEX: IBEU10ATEX1021U ATEX: IBEU10ATEX1021UUL: E325880 UL: E325880
Manufactured for supply voltage 110V/230/440 VAC 110/230 110/230 110/230/440 110/230/440
Technical data Designation/VersionHB-‐C ACH-‐F RCH-‐E ACH-‐N
Totally silicone-free Yes Yes No YesInsulation terminal cable PTFE ETFE ETFE ETFEExternal insulation heater Glassfiber Glassfiber Silicone GlassfiberLength terminal cable (standard ca mm) 500 500 500 500Dimensions heater cable max (ca mm) 3 x 18 3 x 15 Ø 4 3 x 15Terminal cable from heater cable’s one side (1)/both sides (2) 2 2 2 2Approvals EX / UL / VDE **VDE: 40029602
ATEX: IBEU10ATEX1021U ATEX: BAS00ATEX2103U ATEX: BAS02ATEX3153UUL: E325880
Manufactured for supply voltage 110V/230/440 VAC 110/230/440 110/230 110/230 110/230
*Can be ordered with PTFE-¬insulated terminal cable (see item list) ** Cheaper alternatives without ATEX/UL on request
Designation/Version
Carbex AB • Box 115 • 592 22 Vadstena • Sweden • Tel +46 (0)143-294 40 • [email protected] • www.carbex.se 4/10
ANTI-CONDENSATION HEATERS
Length (m) Power (W)
0.30 25
0.43 25
0.68 40
0.79 26
1.01 42
1.06 501.47 651.70 75
1.70 100
1.85 100
Standard models
RSVHeating wire Nickel-Copper or Nickel-Chrome
Heating element insulation Silicon elastomer
External insulation Fibre glass braidDimensions 3 x 11 mm
Permissible surface from - 70°C to + 200°Ctemperature
Tolerances Power: ± 10 %
Connection and end insulation
Fibre glass sheath
Fibre glass sheath
Power cablesilicon elastomer
insulation
Fibre glass braid
Fibre glass sheath
Heating wire
Fibre glass core
silicon elastomerinsulation
Heatingsection
Product information for which Carbex bears no responsibility is provided by the manufacturer.
RSV Flat
Carbex AB • Box 115 • 592 22 Vadstena • Sweden • Tel +46 (0)143-294 40 • [email protected] • www.carbex.se 5/10
Product information for which Carbex bears no responsibility is provided by the manufacturer.
ANTI-CONDENSATION HEATERS
HB -C
HB-A
HB-A, -B, -CStandard types: Standard types:
length of bands / m voltage U/V power P/W 0,203 110 8 0,203 230 8 0,305 110 22 0,305 230 25 0,432 110 27 0,432 230 26 0,686 110 21 0,686 230 21 0,686 110 40 0,686 230 40 0,762 110 25 0,762 230 26 1,016 110 39 1,016 230 42 1,067 110 50 1,067 230 54 1,473 110 67 1,473 230 65 1,702 110 103 1,702 230 99
Heater band classes: • length of heater bands from 0.2 m to 2 m for design B
and C • length of heater bands from 0.2 to 7.5 m for design A • heating power from 8 W to 110 W for design B and C • heating power from 4 W to 300 W for design A • rated supply voltage of the heater bands according to
the heating power 230 VAC, 110 VAC or 440 VAC Value of resistance calculated from the requested heating power.
Carbex AB • Box 115 • 592 22 Vadstena • Sweden • Tel +46 (0)143-294 40 • [email protected] • www.carbex.se 6/10
Product information for which Carbex bears no responsibility is provided by the manufacturer.
ANTI-CONDENSATION HEATERS
2 - 5
- Technische Daten
Rated supply voltage 110 VAC/230 VAC 1) 1) several currents available
on demand Insulation of the Teflon (PTFE), resistance winding 52% overlap, Wall thickness 0,20 mm Outer insulation fiber glass hose (mechanical protec-tion)
fiber glass hose, wall thickness about 0.30 mm
Testing of insulation 2,5 kV/50 Hz; optional 8KV (type A) Rated temperature - 55°C bis + 180°C Alloy of the resistance resistance wire NiCr alloy Tolerance ± 10% tolerance of power
Lead-in: • length: variable in mm • Teflon-strand; UL File 1199 • max. operation voltage 600 V • AWG 20/7 • end connections are 10 mm partially bared Insulation of the junction of resistance winding and the lead-in: • Kynar shrink tube; strengthened wall thickness after
shrinking 0.5 mm, self-extinguishing according to UL 224, VW-1; MIL-I-23053/5 class 8; dielectric strength 43 kV/mm
Resistance wire: • NiCr 80/20 pure according to DIN 17470 • material 2.4869 • melting temperature 1400°C Contact: • material: nickeled steel • temperature limit T = 300°C • manufactured according to DIN 46228 T2 B 1,5-7 Carrier material/fiber glass filament: • fiber type E-Glas (Textilglas) • application temperature limit at 450°C • reaction to fire according to DIN 4102 non-
combustible
Standard types: Standard types:
length of bands / m voltage U/V power P/W 0,203 110 8 0,203 230 8 0,305 110 22 0,305 230 25 0,432 110 27 0,432 230 26 0,686 110 21 0,686 230 21 0,686 110 40 0,686 230 40 0,762 110 25 0,762 230 26 1,016 110 39 1,016 230 42 1,067 110 50 1,067 230 54 1,473 110 67 1,473 230 65 1,702 110 103 1,702 230 99
Heater band classes: • length of heater bands from 0.2 m to 2 m for design B
and C • length of heater bands from 0.2 to 7.5 m for design A • heating power from 8 W to 110 W for design B and C • heating power from 4 W to 300 W for design A • rated supply voltage of the heater bands according to
the heating power 230 VAC, 110 VAC or 440 VAC Value of resistance calculated from the requested heating power.
HB-A, -B, -C
Carbex AB • Box 115 • 592 22 Vadstena • Sweden • Tel +46 (0)143-294 40 • [email protected] • www.carbex.se 7/10
Product information for which Carbex bears no responsibility is provided by the manufacturer.
ANTI-CONDENSATION HEATERS
A. High quality dip soldered joint.B. 80/20 Ni Cr or 56/44 heating element. Glass fibre tape carrier.C. Polyester backed adhesive tape, thermosetting adhesive.D. Glass fibre braid insulation.E. Acrylic adhesive backed glass fibre tape insulation and cold leads reinforcement.F. 500mm ColdLeads 19/0.15 ETFE(Tefzel) insulated equipment wire.
ACH/F Standard RangeACH Ref Length Volts Watts
in mm00a00b0a0b1a1b2a2b3a3b4a4b5a5b6a6b7a7b8a8b
88
121217172727272730304040424258586767
203203305305432432686686686686762762
10161016106710671473147317021702
110220110220110220110220110220110220110220110220110220110220
88
22252726212140402526394250546765
10399
-ACH/F
Carbex AB • Box 115 • 592 22 Vadstena • Sweden • Tel +46 (0)143-294 40 • [email protected] • www.carbex.se 8/10
Product information for which Carbex bears no responsibility is provided by the manufacturer.
ACH/n
Standard sizes
ANTI-CONDENSATION HEATERS
A High quality dip soldered joint. B 80/20 Ni Cr heating element. Glass fibre tape carrier.C Polyester backed adhesive tape insulation.D Glass fibre braid insulation.E Acrylic adhesive backed glass fibre tape, insulation and cold leads reinforcement. F 500mm ColdLeads. 19/0.15 ETFE (Tefzel) insulated equipment wire.
Carbex AB • Box 115 • 592 22 Vadstena • Sweden • Tel +46 (0)143-294 40 • [email protected] • www.carbex.se 9/10
Product information for which Carbex bears no responsibility is provided by the manufacturer.
RCH/E
JOINT DETAILS @ A
ETFE
Silicone Rubber insulation
IZES
ANTI-CONDENSATION HEATERS
Carbex AB • Box 115 • 592 22 Vadstena • Sweden • Tel +46 (0)143-294 40 • [email protected] • www.carbex.se 10/10
Product information for which Carbex bears no responsibility is provided by the manufacturer.
Guidelines for choice of anti-condensation heaters NOTE ! The motor manufacturer’s recommendations should always take precedence.
MotorSize Number* Current
VAC / effekt W
Length ca mm
Ref.-‐size
63 1 230/8 203 00b63 1 115/8 203 00a71 1 230/8 203 00b71 1 115/8 203 00a80 1 230/8 203 00b80 1 115/8 203 00a90 1 230/25 305 0b90 1 115/22 305 0a100 1 230/25 305 0b100 1 115/22 305 0a112 1 230/26 432 1b112 1 115/27 432 1a132 1 230/26 432 1b132 1 115/27 432 1a160 1 230/40 686 3b160 1 115/40 686 3a180 1 230/40 686 3b180 1 115/40 686 3a200 2 230/40 686 3b200 2 115/40 686 3a225 2 230/42 1016 5b225 2 115/39 1016 5a250 2 230/42 1016 5b250 2 115/39 1016 5a280 2 230/54 1067 6b280 2 115/50 1067 6a315 3 230/54 1067 6b315 3 115/50 1067 6a355 3 230/54 1067 6b355 3 115/50 1067 6a
230/21 686 2b115/21 686 2a230/26 762 4b115/25 762 4a230/65 1473 7b115/67 1473 7a230/99 1702 8b115/103 1702 8a
* As an alternative to many standard anti-condensation heaters, versions with greater power and length can also be used
Anti-Condensation Heater
Alternative size
Alternative size
Alternative sizeAlternative sizeAlternative sizeAlternative sizeAlternative sizeAlternative size
ANTI-CONDENSATION HEATERS