POWER ENTRY 330.2mm[13"] WIDE x 177.8mm[7"] HIGH ORIGIN CONTROL PANEL BOTTOM DETAIL NOTES: 1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING SNOW, FOR WINTER OPERATION) OR AIR RE-CIRCULATION ENSURES RATED PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE. SITE RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW, RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE DIMINISHED PERFORMANCE. JOHNSON CONTROLS UNIT CONTROLS WILL OPTIMIZE OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT. HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL PERFORMANCE DEGRADATION. 1.1. RECOMMENDED MINIMUM CLEARANCES: 1.1.1. SIDE TO WALL - 1828.8mm[6'] 1.1.2. REAR TO WALL - 1828.8mm[6'] 1.1.3. CONTROL PANEL TO WALL - 1828.8mm[6'] 1.1.4. TOP - NO OBSTRUCTIONS ALLOWED. 1.1.5. DISTANCE BETWEEN ADJACENT UNITS - 3048mm[10'] 1.1.6. NO MORE THAN ONE ADJACENT WALL MAY BE HIGHER THAN UNIT. 2. WEIGHT AND CENTER OF GRAVITY - REFER TO AVM REPORT. 3. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN ACCOMMODATIONS IN CHILLED WATER PIPING NEAR THE EVAPORATOR. 4. NUMBER OF COMPRESSORS MAY VARY FROM DRAWING. 4.1. REFER TO YORKworks REPORTS. 5. OVERALL HEIGHT OF UNIT IS 2394.6mm-[94.27"] ON MONTERREY, MEXICO AND SAN ANTONIO, TEXAS BUILDS. 6. OVERALL HEIGHT OF UNIT IS 2507.0mm-[98.70"] ON SABADELL, SPAIN BUILDS. 7. FOR MONTERREY, MEXICO, SAN ANTONIO, TEXAS AND SABADELL, SPAIN BUILDS ONLY. 1177.2mm [46.35"] 20.7mm [.81"] 15.9mm[5/8"] DIA MOUNTING HOLES (TYP.) OVERALL HEIGHT DEPENDS ON BUILD LOCATION REFER TO NOTES 5 AND 6 ABOVE. 3" VICTAULIC OUTLET 3" VICTAULIC INLET (OPTIONAL HEAT RECOVERY UNIT) 140.8mm-288.0mm [5.54"]- [11.34"] - DIMENSION VARIES BASED ON CHILLER MODEL SELECTED 4" VICTAULIC OUTLET 4" VICTAULIC INLET 4" VICTAULIC OUTLET 4" VICTAULIC INLET 2251.4mm [88.64"] 2242.0mm [88.27"] 2254.4mm [88.76"] 588.3mm [23.16"] 1256.1mm [49.45"] 2061.5mm [81.16"] 885.9mm [34.88"] 1151.3mm [45.33"] 4731.4mm [186.28"] 4768.9mm [187.75"] 254.4mm [10.02"] 685.7mm [27"] 822.4mm [32.38"] 1085.1mm [42.72"] 1275.7mm [50.22"] 136.7mm [5.38"] 82.9mm [3.26"] 2077.3mm [81.78"] 194.6mm [7.66"] 1753.2mm [69.03"] 1917.9mm [75.51"] 36.4mm [1.43"] DRAWING NUMBER "ALL PROPRIETARY RIGHTS IN THE SUBJECT MATTER HEREOF ARE RESERVED AND NO PERMISSION IS GRANTED TO REPRODUCE THIS PRINT IN WHOLE OR IN ANY PART, OR DISCLOSE ANY OF THE INFORMATION UPON IT TO OTHERS WITHOUT WRITTEN RELEASE BY JOHNSON CONTROLS INCORPORATED" REVISION DATE EC NUMBER DRAWN BY CHECKED BY ENGINEERED BY JOHNSON CONTROLS - BUILDING EFFICIENCY 507 EAST MICHIGAN STREET, MILWAUKEE, WI 53202 USA SCALE: ENG: CHKD: MODELER: DRAWN: OF 2 B A 1 3 4 5 6 7 8 9 10 11 12 13 C D E F G H 2 1 3 4 5 6 7 8 9 10 11 12 13 B A C D E F G H YLAA 8-FAN 50&60Hz w/OPTIONAL HEAT RECOVERY UNITS 035-24059-010 10 13 DO NOT SCALE ETE 11/06/2013 3/8"=1' NONE REVIEW - DX13-0527 N/A N/A - ORIG 66935 N/A A3 THIS DRAWING PERTAINS TO THE FOLLOWING MODELS: YLAA 0125 HE YLAA 0155 SE YLAA 0136 SE YLAA 0456 HE YLAA 0142 HE YLAA 0516 HE YLAA 0150 SE Appendix A1

Upload: doanthuy

Post on 10-Apr-2018

216 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Appendix A1 - Cloud Object Storage | Store & Retrieve … Temp. 95F EER: 15.96 65KVA Unit Short Circuit Withstand Circuit Breaker 1.5” Armaflex Insulation on all Cold Parts BacNet

POWER ENTRY

330.2mm[13"] WIDE x 177.8mm[7"] HIGH

ORIGIN

CONTROL PANEL BOTTOM DETAIL

NOTES:

1. PLACEMENT ON A LEVEL SURFACE FREE OF OBSTRUCTIONS (INCLUDING

SNOW, FOR WINTER OPERATION) OR AIR RE-CIRCULATION ENSURES RATED

PERFORMANCE, RELIABLE OPERATION AND EASE OF MAINTENANCE. SITE

RESTRICTIONS MAY COMPROMISE MINIMUM CLEARANCES INDICATED BELOW,

RESULTING IN UNPREDICTABLE AIR FLOW PATTERNS AND POSSIBLE

DIMINISHED PERFORMANCE. JOHNSON CONTROLS UNIT CONTROLS WILL

OPTIMIZE OPERATION WITHOUT NUISANCE HIGH PRESSURE SAFETY CUTOUT.

HOWEVER, THE SYSTEM DESIGNER MUST CONSIDER POTENTIAL

PERFORMANCE DEGRADATION.

1.1. RECOMMENDED MINIMUM CLEARANCES:

1.1.1. SIDE TO WALL - 1828.8mm[6']

1.1.2. REAR TO WALL - 1828.8mm[6']

1.1.3. CONTROL PANEL TO WALL - 1828.8mm[6']

1.1.4. TOP - NO OBSTRUCTIONS ALLOWED.

1.1.5. DISTANCE BETWEEN ADJACENT UNITS - 3048mm[10']

1.1.6. NO MORE THAN ONE ADJACENT WALL MAY BE HIGHER THAN UNIT.

2. WEIGHT AND CENTER OF GRAVITY - REFER TO AVM REPORT.

3. INSTALLING CONTRACTOR MUST INCLUDE VENT AND DRAIN

ACCOMMODATIONS IN CHILLED WATER PIPING NEAR THE EVAPORATOR.

4. NUMBER OF COMPRESSORS MAY VARY FROM DRAWING.

4.1. REFER TO YORKworks REPORTS.

5. OVERALL HEIGHT OF UNIT IS 2394.6mm-[94.27"] ON MONTERREY, MEXICO AND

SAN ANTONIO, TEXAS BUILDS.

6. OVERALL HEIGHT OF UNIT IS 2507.0mm-[98.70"] ON SABADELL, SPAIN BUILDS.

7. FOR MONTERREY, MEXICO, SAN ANTONIO, TEXAS AND SABADELL, SPAIN

BUILDS ONLY.

1177.2mm

[46.35"]

20.7m

m

[.81"]

15.9mm[5/8"] DIA

MOUNTING HOLES (TYP.)

OV

ER

ALL H

EIG

HT

D

EP

EN

DS

O

N B

UILD

LO

CA

TIO

N

RE

FE

R T

O N

OT

ES

5 A

ND

6 A

BO

VE

.

3" VICTAULIC

OUTLET

3" VICTAULIC

INLET

(OPTIONAL HEAT

RECOVERY UNIT)

140.8mm-288.0mm

[5.54"]- [11.34"] - DIMENSION VARIES BASED

ON CHILLER MODEL SELECTED

4" VICTAULIC OUTLET

4" VICTAULIC

INLET

4" VICTAULIC

OUTLET

4" VICTAULIC

INLET

2251.4m

m

[88.64"]

2242.0mm

[88.27"]

2254.4mm

[88.76"]

588.3mm

[23.16"]

1256.1mm

[49.45"] 2061.5mm

[81.16"]

885.9mm

[34.88"]1151.3mm

[45.33"]

4731.4mm

[186.28"]

4768.9mm

[187.75"]

254.4m

m

[10.02"]

685.7m

m

[27"]

822.4m

m

[32.38"]

1085.1m

m

[42.72"]

1275.7m

m

[50.22"]

136.7mm

[5.38"]

82.9m

m

[3.26"]

2077.3m

m

[81.78"]

194.6mm

[7.66"]

1753.2mm

[69.03"]

1917.9mm

[75.51"]

36.4m

m

[1.43"]

DRAWING NUMBER

"ALL PROPRIETARY RIGHTS IN

THE SUBJECT MATTER HEREOF

ARE RESERVED AND NO

PERMISSION IS GRANTED TO

REPRODUCE THIS PRINT IN

WHOLE OR IN ANY PART, OR

DISCLOSE ANY OF THE

INFORMATION UPON IT TO

OTHERS WITHOUT WRITTEN

RELEASE BY JOHNSON

CONTROLS INCORPORATED®"

REVISION DATE EC NUMBER DRAWN BY CHECKED BY ENGINEERED BY

JOHNSON CONTROLS - BUILDING EFFICIENCY

507 EAST MICHIGAN STREET, MILWAUKEE, WI 53202 USA

SCALE:

ENG:

CHKD:

MODELER:

DRAWN:

OF

2

B

A

1345678910111213

C

D

E

F

G

H

2 1345678910111213

B

A

C

D

E

F

G

H

YLAA 8-FAN 50&60Hz

w/OPTIONAL HEAT RECOVERY

UNITS

035-24059-010

10 13

DO NOT SCALE

ETE 11/06/2013

3/8"=1' NONE REVIEW

- DX13-0527

N/A

N/A

-

ORIG

66935

N/A

A3

THIS DRAWING PERTAINS TO THE FOLLOWING MODELS:

YLAA 0125 HE YLAA 0155 SE

YLAA 0136 SE YLAA 0456 HE

YLAA 0142 HE YLAA 0516 HE

YLAA 0150 SE

Appendix A1

Page 2: Appendix A1 - Cloud Object Storage | Store & Retrieve … Temp. 95F EER: 15.96 65KVA Unit Short Circuit Withstand Circuit Breaker 1.5” Armaflex Insulation on all Cold Parts BacNet

EQUIPMENT SUBMITTAL FOR APPROVAL

PROJECT: FPL Lake City Data

LOCATION: Lake City, FL

DX Air Cooled Scroll Chiller

EQUIPMENT YLAA - Air Cooled ChillerUNIT TAGS CH-1, CH-2QUANTITY 2

SOLD TO:Florida Power and Light

CONSULTING ENGINEER:Not available

PREPARED BY:Roger M. Coll

DATE:Friday, August 05, 2016

REVISION:1

Page 3: Appendix A1 - Cloud Object Storage | Store & Retrieve … Temp. 95F EER: 15.96 65KVA Unit Short Circuit Withstand Circuit Breaker 1.5” Armaflex Insulation on all Cold Parts BacNet

BILL OF MATERIAL DATA

EQUIPMENT YLAA - Air Cooled ChillerUNIT TAGS CH-1,CH-2

QTY 2

Actual Tonnage at Design Conditions 128.6 Tons460/3/60Scroll Compressor R410a RefrigerantEvaporator EWT/LWT: 55/44FFlow: 303 GPMAmbient Temp. 95FEER: 15.9665KVA Unit Short Circuit Withstand Circuit Breaker1.5” Armaflex Insulation on all Cold PartsBacNet Interface BoardCondenser Coil Coating by Factory Low Ambient Option (provides controls and capability to operate down to 0F Ambient Temperatures)Acoustical Sound Compressor Blankets and Low Sound Fans (Unit Sound Pressure 70dba at 10ft)5 Year Parts and Labor and Refrigerant Warranty Factory testing for efficiency 1 point with report Start-Up by Factory Technician and Owner Training Flow Detection by: Thermal Dispersion Device and Differential Pressure Note: unit is selected to perform with 30% ethylene glycol mixture in water.

Not Including: Rigging, Pumps, Valves, or Item not mentioned above

Page 4: Appendix A1 - Cloud Object Storage | Store & Retrieve … Temp. 95F EER: 15.96 65KVA Unit Short Circuit Withstand Circuit Breaker 1.5” Armaflex Insulation on all Cold Parts BacNet

AVM Report

Project Name Unit Tag Date Chiller TypeCH-1 2016-07-19 Air Cooled Scroll Chillers

PIN VersionYLAA0142HE46XFBBCXXHXXBLXCXX44XEXXXXHXDXYAXXPXXXBXXLXXH5XXXX E.16.3.0-D.35.0033

MLP Date:2016-02-15Generated on 2016-07-29 E.16.3.0-D.35.0033(REV. v7_05.idd) AVM Location SpecificationUnit Folder: CH-1 Software Version: YW16.03a Page_1_of_1

LOCATION X Distance (in) Y Distance (in)JCI PART NUMBER

SAP NUMBER COLOUROperating

Weights (lb)R1 7.6 1.4 N/A N/A N/A 540R2 76.6 1.4 N/A N/A N/A 1190R3 152.1 1.4 N/A N/A N/A 891L1 7.6 86.9 N/A N/A N/A 932L2 76.6 86.9 N/A N/A N/A 1892L3 152.1 86.9 N/A N/A N/A 999

Total Weight (lb) Centre of Gravity (in)Operating 6444 Xg 83.0Shipping 6333 Yg 52.1

Page 5: Appendix A1 - Cloud Object Storage | Store & Retrieve … Temp. 95F EER: 15.96 65KVA Unit Short Circuit Withstand Circuit Breaker 1.5” Armaflex Insulation on all Cold Parts BacNet

MLP Date:2016-02-15Generated on 2016-07-29 E.16.3.0-D.35.0033(REV. v7_05.idd) Smart SpecificationUnit Folder: CH-1 Software Version: YW16.03a Page_1_of_5

Air Cooled Scroll Liquid Chiller -YORK YLAA R410A 50Hz & 60Hz

1. GENERAL

1.01. GENERAL REQUIREMENTS

The requirements of this Section shall conform to the general provisions of the Contract, including General and Supplementary Conditions, Conditions of the Contract, and Contract Drawings.

1.02. SCOPE

Provide Microprocessor controlled, multiple scroll compressor, air-cooled, liquid chillers of the scheduled capacities as shown and indicated on the Drawings, including but not limited to:

1. Chiller package

2. Charge of refrigerant and oil

3. Electrical power and control connections

4. Chilled liquid connections

5. Manufacturer start-up

1.03. QUALITY ASSURANCE

A. Products shall be Designed, Tested, Rated and Certified in accordance with, and Installed in compliance with applicable sections of the following Standards and Codes:

1. AHRI 550/590 – Water Chilling Packages Using the Vapor Compression Cycle

2. AHRI 370 – Sound Rating of Large Outdoor Refrigerating and Air-Conditioning Equipment

3. ANSI/ASHRAE 15 – Safety Code for Mechanical Refrigeration

4. ANSI/ASHRAE 34 – Number Designation and Safety Classification of Refrigerants

5. ASHRAE 90.1 – Energy Standard for Buildings Except Low-Rise Residential Buildings

6. ANSI/NFPA 70 – National Electrical Code (N.E.C.)

7. ASME Boiler and Pressure Vessel Code, Section VIII, Division 1

8. OSHA – Occupational Safety and Health Act

9. Manufactured in facility registered to ISO 9001

10. Conform to Intertek Testing Services for construction of chillers and provide ETL/cETL Listed Mark

B. Factory Run Test: Chiller shall be pressure-tested, evacuated and fully charged with refrigerant and oil, and shall be factory operational run tested with water flowing through the vessel.

C. Chiller manufacturer shall have a factory trained and supported service organization.

D. Warranty: Manufacturer shall Warrant all equipment and material of its manufacture against defects in workmanship and material for a period of eighteen (18) months from date of shipment or twelve (12) months from date of start-up, whichever occurs first.

1.04. DELIVERY AND HANDLING

A. Unit shall be delivered to job site fully assembled with all interconnecting refrigerant piping and internal wiring ready for field installation and charged with refrigerant and oil by the Manufacturer.

Page 6: Appendix A1 - Cloud Object Storage | Store & Retrieve … Temp. 95F EER: 15.96 65KVA Unit Short Circuit Withstand Circuit Breaker 1.5” Armaflex Insulation on all Cold Parts BacNet

MLP Date:2016-02-15Generated on 2016-07-29 E.16.3.0-D.35.0033(REV. v7_05.idd) Smart SpecificationUnit Folder: CH-1 Software Version: YW16.03a Page_2_of_5

B. Provide protective covering over vulnerable components for unit protection during shipment. Fit nozzles and open ends with plastic enclosures.

C. Unit shall be stored and handled per Manufacturer’s instructions.

2. PRODUCTS

2.01. CHILLER MATERIALS AND COMPONENTS

A. General: Install and commission, as shown on the schedules and plans, factory assembled, charged, and tested air cooled scroll compressor chiller(s) as specified herin. Chiller shall be designed, selected, and constructed using a refrigerant with Flammability rating of "1", as defined by ANSI/ASHRAE STANDARD 34 Number Designation and Safety Classification of Refrigerants. Chiller shall include not less than two refrigerant circuits above 50 tons (200kW), scroll compressors, direct-expansion type evaporator, air-cooled condenser, refrigerant, lubrication system, interconnecting wiring, safety and operating controls including capacity controller, control center, motor starting components and special features as specified herin or required for safe, automatic operation.

B. Cabinet: External structural members shall be constructed of heavy guage, galvanized steel coated with baked on powder paint which, when subject to ASTM B117, 1000 hour, 5% salt spray test, yields minimum ASTM 1654 rating of "6".

C. Operating Characteristics: Provide low and high ambient temperature control options as required to ensure unit is capable of operation from 30°F to 115°F (-1°C to 46°C) ambient temperature. [Optional: 0°F to 125°F (-18°C to 52°C)

ambient.]

D. Service Isolation valves: Discharge (ball type) isolation valves factory installed per refrigerant circuit. Includes a system high-pressure relief valve in compliance with ASHRAE15.

E. Pressure Transducers and Readeout Capability

1. Discharge Pressure Transducers: Permits unit to sense and display discharge pressure.

2. Suction Pressure Transducers: Permits unit to sense and display suction pressure.

3. High Ambient Control: Allows units to operate when the ambient temperature is above 115°F (46°C). Includes

discharge pressure transducers

2.02. COMPRESSORS

A. Compressors: Shall be hermetic, scroll-type, including:

1. Compliant design for axial and radial sealing.

2. Refrigerant flow through the compressor with 100% suction cooled motor.

3. Large suction side free volume and oil sump to provide liquid handling capability.

4. Compressor crankcase heaters to provide extra liquid migration protection.

5. Annular discharge check valve and reverse vent assembly to provide low-pressure drop, silent shutdown andreverse rotation protection.

6. Initial oil charge.

7. Oil level sight glass.

8. Vibration isolator mouonts for compressors.

9. Brazed-type connections for fully hermetic refrigerant circuits.

10. Compressor Motor overloads capable of monitoring compressor motor current. Provides extra protectionagainst compressor reverse rotation, phase-loss and phase-imbalance.

Page 7: Appendix A1 - Cloud Object Storage | Store & Retrieve … Temp. 95F EER: 15.96 65KVA Unit Short Circuit Withstand Circuit Breaker 1.5” Armaflex Insulation on all Cold Parts BacNet

MLP Date:2016-02-15Generated on 2016-07-29 E.16.3.0-D.35.0033(REV. v7_05.idd) Smart SpecificationUnit Folder: CH-1 Software Version: YW16.03a Page_3_of_5

2.03. REFRIGERANT CIRCUIT COMPONENTS

Each refrigerant circuit shall include: a discharge service ball type isolation valve, high side pressure relief, liquid line shutoff valve with charging port, low side pressure relief device, filter-drier, solenoid valve, sight glass with moisture indicator, thermostatic expansion valves, and flexible, closed-cell foam insulated suction line and suction pressure transducer.

2.04. HEAT EXCHANGERS

A. Evaporator:

1. Evaporator shall be brazed-plate stainless steel construction capable of refrigerant working pressure of 650psig (3103 kPa) and liquid side pressure of 150 psig (1034 kPa) [Option for 300 psig (2068 kPa) available].

2. Brazed plate heat exchangers shall be UL listed.

3. Exterior surfaces shall be covered with 3.4" (19mm), flexible, closed cell insulation, thermal conductivity of0.26k ([BTU/HR-Ft² - °F]/in.) maximum.

4. Water nozzles shall be provided with grooves for field provided ANSI/AWWA C-606 mechanical couplings.

5. Evaporator shall include vent and drain fittings and thermostatically controlled heaters to protect to -20°F (-

29°C) ambient in off-cycle.

6. A 20-mesh, serviceable wye-strainer and mechanical couplings shall be provided for field installation onevaporator inlet prior to startup.

7. Evaporator shall be provided with piping extension kit and mechanical couplings to extend liquid connectionfrom evaporator to edge of unit. Thermal dispersion type flow switch shall be factory installed in the evaporator outlet pipe extension and wired to the unit control panel. Insulation and heat trace on piping shall be responsibility of installing contractor. Extension kit nozzle connections shall be ANSI/AWWA C-606 (grooved).

B. Air-cooled Condenser:

1. Coils: Condenser coils shall be constructed of a single material to avoid galvanic corrosion due to dissimilarmetals. Coils and headers are brazed as one piece. Integral sub cooling is included. Coils shall be designed for a design working pressure of 650 PSIG (45 bar). Condenser coil shall be washable with potable water under 100 psi (7 bar) pressure.

2. Low Sound Fans: Shall be dynamically and statically balanced, direct drive, corrosion resistant glass fiberreinforced composite blades molded into a low noise, full-airfoil cross section, providing vertical air discharge and low sound. Each fan shall be provided in an individual compartment to prevent crossflow during fan cycling. Guards of heavy gauge, PVC (poly- vinylchloride) coated or galvanized steel shall be factory installed.

3. Fan Motors: High efficiency, direct drive, 6 pole, 3 phase, insulation class “F”, current protected, Totally

Enclosed Air-Over (TEAO) , rigid mounted, with double sealed, permanently lubricated, ball bearings.

2.05. CONTROLS

A. General: Automatic start, stop, operating, and protection sequences across the range of scheduled conditions and transients.

B. Power/Control Enclosure: Rain and dust tight NEMA 3R powder painted steel cabinet with hinged, latched, and gasket sealed door.

C. Microprocessor Control Center:

1. Automatic control of compressor start/stop, anti-coincidence and anti-recycle timers, automatic pumpdown atsystem shutdown, condenser fans, evaporator pump, evaporator heater, unit alarm contacts, and chiller operation from 0°F to 125°F (-18°C to 52°C) ambient. Automatic reset to normal chiller operation after power failure.

Page 8: Appendix A1 - Cloud Object Storage | Store & Retrieve … Temp. 95F EER: 15.96 65KVA Unit Short Circuit Withstand Circuit Breaker 1.5” Armaflex Insulation on all Cold Parts BacNet

MLP Date:2016-02-15Generated on 2016-07-29 E.16.3.0-D.35.0033(REV. v7_05.idd) Smart SpecificationUnit Folder: CH-1 Software Version: YW16.03a Page_4_of_5

2. Software stored in non-volatile memory, with programmed setpoints retained in lithium battery backed real-time-clock (RTC) memory for minimum 5 years.

3. Forty character liquid crystal display, descriptions in English (or Spanish, French, Italian, or German), numericdata in English (or Metric) units. Sealed keypad with sections for Setpoints, Display/Print, Entry, Unit Options & clock, and On/Off Switch.

4. Programmable Setpoints (within Manufacturer limits): display language; chilled liquid temperature setpoint andrange, remote reset temperature range, daily schedule/holiday for start/stop, manual override for servicing, low and high ambient cutouts, low liquid temperature cutout, low suction pressure cutout, high discharge pressure cutout, anti-recycle timer (compressor start cycle time), and anti-coincident timer (delay compressor starts).

5. Display Data: Return and leaving liquid temperatures, low leaving liquid temperature cutout setting, lowambient temperature cutout setting, outdoor air temperature, English or metric data, suction pressure cutout setting, each system suction pressure, liquid temperature reset via a 4-20milliamp or 0-10 VDC input, anti-recycle timer status for each compressor, anti-coincident system start timer condition, compressor run status, no cooling load condition, day, date and time, daily start/stop times, holiday status, automatic or manual system lead/lag control, lead system definition, compressor starts/operating hours (each), status of hot gas valves, evaporator heater and fan operation, run permissive status, number of compressors running, liquid solenoid valve status, load & unload timer status, water pump status.

6. System Safeties: Shall cause individual compressor systems to perform auto shut down; manual reset requiredafter the third trip in 90 minutes. System Safeties include: high discharge pressure, low suction pressure, high pressure switch, and motor protector. Compressor motor protector shall protect against damage due to high input current or thermal overload of windings.

7. Unit Safeties: Shall be automatic reset and cause compressors to shut down if low ambient, low leaving chilledliquid temperature, under voltage, and flow switch operation.

8. Alarm Contacts: Low ambient, low leaving chilled liquid temperature, low voltage, low battery, and (percompressor circuit): high discharge pressure, and low suction pressure.

9. BAS Communications: YORKTalk 2, BACnet MS/TP, Modbus and N2 communication capabilities arestandard.

D. Manufacturer shall provide any controls not listed above, necessary for automatic chiller operation. Mechanical Contractor shall provide field control wiring necessary to interface sensors to the chiller control system.

2.06. POWER CONNECTION AND DISTRIBUTION

A. Power Panels:

1. NEMA 3R/12 rain/dust tight, powder painted steel cabinets with hinged, latched, and gasket sealed outerdoors. Provide main power connection(s), control power connections, compressor and fan motor start contactors, current overloads, and factory wiring.

2. Power supply shall enter unit at a single location, be 3 phase of scheduled voltage, and connect to individualterminal blocks per compressor. Separate disconnecting means and/or external branch circuit protection (by Contractor) required per applicable local or national codes.

B. Compressor, control and fan motor power wiring shall be located in an enclosed panel or routed through liquid tight conduit.

2.07. ACCESSORIES AND OPTIONS

Some accessories and options supersede standard product features. Your Johnson Controls representative will be pleased to provide assistance.

A. Microprocessor controlled, Factory installed Across-the-Line type compressor motor starters as standard.

Page 9: Appendix A1 - Cloud Object Storage | Store & Retrieve … Temp. 95F EER: 15.96 65KVA Unit Short Circuit Withstand Circuit Breaker 1.5” Armaflex Insulation on all Cold Parts BacNet

MLP Date:2016-02-15Generated on 2016-07-29 E.16.3.0-D.35.0033(REV. v7_05.idd) Smart SpecificationUnit Folder: CH-1 Software Version: YW16.03a Page_5_of_5

B. Outdoor Ambient Temperature Control

C. Power Supply Connections:

D. Condenser Coil Environmental Protection:

1. Post-Coated Dipped: Dipped-cured coating on condenser coils for seashore and other corrosive applications(with the exception of strong alkalis, oxidizers, and wet bromine, chlorine and fluorine in concentrations greater than 100 ppm).

E. Thermal Dispersion Flow Switch (Factory installed and wired in piping extension kit): Normally open, 30bar pressure rating, stainless steel 316L construction, IP67, -4°F to 158°F ambient rating.

F. Evaporator options:

1. Provide 1-1/2”” evaporator insulation in lieu of standard 3/4”.

G. Low Temperature Process Glycol: Leaving chilled liquid setpoint range 10°F to 50°F (-12°C to 10°C)

H. Sound Reduction (Factory installed):

1. Ultra Quiet - Low speed, reduced noise fans

2. Compressor Acoustic Sound Blankets

3. EXECUTION

3.01. INSTALLATION

A. General: Rig and Install in full accordance with Manufacturer’s requirements, Project drawings, and Contract

documents.

B. Location: Locate chiller as indicated on drawings, including cleaning and service maintenance clearance per Manufacturer instructions. Adjust and level chiller on support structure.

C. Components: Installing Contractor shall provide and install all auxiliary devices and accessories for fully operational chiller.

D. Electrical: Coordinate electrical requirements and connections for all power feeds with Electrical Contractor (Division 16).

E. Controls: Coordinate all control requirements and connections with Controls Contractor.

F. Finish: Installing Contractor shall paint damaged and abraded factory finish with touch-up paint matching factory finish.

Page 10: Appendix A1 - Cloud Object Storage | Store & Retrieve … Temp. 95F EER: 15.96 65KVA Unit Short Circuit Withstand Circuit Breaker 1.5” Armaflex Insulation on all Cold Parts BacNet

Design Conditions Datasheet

MLP Date:2016-02-15Generated on 2016-07-29 E.16.3.0-D.35.0033(REV. v7_05.idd) Datasheet SpecUnit Folder: CH-1 Software Version: YW16.03a Page_1_of_2

Unit Tag Qty Model NoNet Cooling

Capacity (ton.R)Nominal Voltage Refrigerant Type

CH-1 2 YLAA0142HE46XFBBCXX 128.6 460-3-60.0 R410A

PIN:YLAA0142HE 46XFBBCXXH XXBLXCXX44 XEXXXXHXDX YAXXPXXXBX XLXXH5XXXX....5...10 ....5...20 ....5...30 ....5...40 ....5...50 ....5...60 ....5...70 ....5...80 ....5...90

Evaporator Data Evaporator Data (Cont.) Performance DataEWT (°F) 55.00 Fluid Volume (USGAL) 13.21 EER (EER) 10.15LWT (°F) 44.00 Min. Flow Rate (USGPM) 150.0 NPLV.IP (EER) 15.96Design Flow Rate (USGPM) 303.0 Max. Flow Rate (USGPM) 625.0

Evap. Press. Drop (ft H2O) 10.7 Condenser Data Physical Data

FluidEthylene

Glycol (%)30 Ambient Temp. Design (°F) 95.0 Rigging Wt. (lb) 6333

Strainer Press. Drop (ft H2O) 0.000 Altitude (ft) 0.000 Operating Wt. (lb) 6444Ext. Kit Press. Drop (ft H2O) 0.000 Compressor Type Scroll - Hermetic Refrigerant Charge (lb) 155.9Total Press. Drop (ft H2O) 10.7Fouling Factor (h.ft².F/Btu) 0.0001000

Electrical DataCircuit 1 2 3 4Compressor RLA 53 / 53 / 53 27 / 27 / 27Fan QTY/FLA (each) 5 / 12 3 / 12High LRA Current 290 / 290 / 290 180 / 180 / 180

Single PointMin. Circuit Ampacity 285Full Load Ampacity 272Recommended Fuse/CB Rating 300Max. Inverse Time CB Rating 300

Max. Dual Element Fuse Size (A) 300 Operating Condition Electrical DataUnit Short Circuit Withstand (STD) 65 [kA] Compressor kW 138.6Wire Lugs Per Phase 2 + 1 Total Fan kW 13.44

Wire Range (Lug Size)#3/0 AWG - 250 kcmil +

250 - 500 kcmilTotal kW 152.1

Starter Type Across The Line

Notes:

Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Using Vapor Compression Cycle Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Unit containing freeze protection fluids in the condenser or in the evaporator with a leaving chilled fluid temperature above 32 DEG F [0 DEG C] is certified when rated per the Standard with water. Certified units may be found in the AHRI Directory at www.ahridirectory.org. Auxiliary components included in total KW - Oil heaters, Chiller controls. Auxiliary power is already included in the compressor and fan power

Page 11: Appendix A1 - Cloud Object Storage | Store & Retrieve … Temp. 95F EER: 15.96 65KVA Unit Short Circuit Withstand Circuit Breaker 1.5” Armaflex Insulation on all Cold Parts BacNet

Design Conditions Datasheet

MLP Date:2016-02-15Generated on 2016-07-29 E.16.3.0-D.35.0033(REV. v7_05.idd) Datasheet SpecUnit Folder: CH-1 Software Version: YW16.03a Page_2_of_2

Part Load Rating DataStage Ambient (°F) Capacity (ton.R) Total kW Unit Efficiency

1 95.0 128.6 152.1 10.152 86.1 109.5 103.7 12.663 80.5 97.48 84.85 13.794 66.7 67.92 48.32 16.875 59.1 51.71 33.96 18.276 55.0 34.51 21.52 19.25

Average Sound Pressure Levels at 10 Feet (Derived from AHRI 370 Sound Power using Parallelepiped Method)

StageAmbient

(°F)63 125 250 500 1K 2K 4K 8K LpA

1 95.0 -4 -5 -9 -9 -13 -17 -20 -23 702 86.1 -4 -5 -9 -9 -13 -17 -20 -23 703 80.5 -4 -5 -9 -9 -13 -17 -20 -23 704 66.7 -6 -7 -11 -11 -15 -19 -22 N/A 685 59.1 -7 -8 -12 -12 -16 -20 -23 N/A 676 55.0 N/A N/A N/A N/A N/A N/A N/A N/A 50

Note: Unit is equipped with Acoustic Sound Blanket and Ultra Quiet Fans.

Performance at AHRI ConditionsEvaporator Data Condenser Data Performance Data

EWT (°F) 54.00 Ambient Temp. (°F) 95.0 EER (EER) 10.20LWT (°F) 44.00 Altitude (ft) 0 IPLV.IP (EER) 15.90

Flow Rate (USGPM) 309.2Net Cooling Capacity (ton.R)

128.6

Pressure Drop (ft H2O) 9.80Fluid WaterFouling Factor (h.ft².F/Btu) 0.0001000Fluid Volume (USGAL) 13.21

Page 12: Appendix A1 - Cloud Object Storage | Store & Retrieve … Temp. 95F EER: 15.96 65KVA Unit Short Circuit Withstand Circuit Breaker 1.5” Armaflex Insulation on all Cold Parts BacNet

Project: FPL Lake City Data 1 SubmittalBid: A

RECEIVING / RIGGING INSTRUCTIONS

The installing contractor is responsible to provide Johnson Controls / YORK with a contact to coordinate the delivery of the equipment in this submittal. Please fill out theinformation requested in the Submittal Approval Form section in the back of this submittal.

It is the installing contractor’s responsibility to verify the following prior to signingthe bill of lading presented by the transportation company:

• Ensure everything on the bill of lading was delivered.• Visually perform a thorough inspection of all equipment for any signs of shipping damage

Any short-shipments or shipping damage must be noted on the bill oflading prior to signing.

The transportation company will provide you withinstructions for filing a claim. It is the installing contractor’s responsibility to work directly with the transportation company to resolve any shipping claims.

Page 13: Appendix A1 - Cloud Object Storage | Store & Retrieve … Temp. 95F EER: 15.96 65KVA Unit Short Circuit Withstand Circuit Breaker 1.5” Armaflex Insulation on all Cold Parts BacNet

SERVICE POLICY

LIMITED WARRANTY

ENGINEERED SYSTEMS

EQUIPMENT

Supersedes: 50.05-NM2 (1008) Form 50.05-NM2 (309)

THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES, EXPRESS OR IMPLIED IN LAW OR IN FACT, INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. THE WARRANTIES CONTAINED HEREIN SET FORTH BUYER’S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A DEFECT IN WORKMANSHIP OR MATERIALS. IN NO EVENT SHALL JCI’S LIABILITY FOR DIRECT OR COMPENSATORY DAMAGES EXCEED THE PAYMENTS RECEIVED BY JCI FROM BUYER FOR THE MATERIALS OR EQUIPMENT INVOLVED. NOR SHALL JCI BE LIABLE FOR ANY SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES. THESE LIMITA-TIONS ON LIABILITY AND DAMAGES SHALL APPLY UNDER ALL THEORIES OF LIABILITY OR CAUSES OF ACTION, INCLUDING, BUT NOT LIMITED TO, CONTRACT, WARRANTY, TORT (INCLUDING NEGLIGENCE) OR STRICT LIABILITY. THE ABOVE LIMITATIONS SHALL INURE TO THE BENEFIT OF JCI’S SUPPLIERS AND SUBCONTRACTORS.

POLICY STATEMENT

Johnson Controls, Inc. (JCI) warrants all new Engi-

neered Systems Equipment and materials, or installa-

tion or start-up services performed by JCI in connection

therewith, against defects in workmanship and mate-

rial for a period of eighteen (18) months from date of

shipment or twelve (12) months from date of start-up,

whichever occurs first. This warranty does not extend

to products used for rental chiller duty. Subject to the

exclusions listed below, JCI, at its option, will repair or

replace, FOB point of shipment, such JCI products or

components as it finds defective.

Except for reciprocating replacement compressors,

which JCI warrants for a period of twelve (12) months

from date of shipment, JCI reconditioned or replacement

materials, or installation or start-up services performed

by JCI in connection therewith, warrants against defects

in workmanship and material for a period of ninety (90)

days from date of shipment. Subject to the exclusions

listed below, JCI, at its option, will repair or replace, FOB

point of shipment, such JCI products or components as

it finds defective.

Exclusions:

Unless specifically agreed to in the contract documents,

this warranty does not include the following costs and

expenses:

1. Labor to remove or reinstall any equipment, materials,

or components.

2. Shipping, handling, or transportation charges.

3. Cost of refrigerant.

4. Cost of rental chillers or other temporary cooling

equipment.

No warranty repairs or replacements will be made until

payment for all equipment, materials, or components

has been received by JCI.

ALL WARRANTIES ARE VOID IF:

1. Equipment is used with refrigerants, oil, or antifreeze

agents other than those authorized by JCI.

2. Equipment is used with any material or any equipment

such as evaporators, tubing, other low side equip-

ment, or refrigerant controls not approved by JCI.

3. Equipment has been damaged by freezing because

it is not properly protected during cold weather, or

damaged by fire or any other conditions not” ordinar-

ily encountered.

4. Equipment is not installed, operated, maintained

and serviced in accordance with instructions issued

by JCI.

5. Equipment is damaged due to dirt, air, moisture, or

other foreign matter entering the refrigerant sys-

tem.

6. Equipment is not properly stored, protected, or in-

spected by the customer during the period from date

of shipment to date of initial start-up.

7. Equipment is damaged due to acts of god, abuse,

neglect, sabotage, or acts of terrorists.

Copyright © 2009 Johnson Controls, Inc. Printed in USA 50.05-NM2 (309)

Replaces: 50.05-NM2 (1008)

P.O. Box 423, Milwaukee, WI 53203

www.johnsoncontrols.com

Page 14: Appendix A1 - Cloud Object Storage | Store & Retrieve … Temp. 95F EER: 15.96 65KVA Unit Short Circuit Withstand Circuit Breaker 1.5” Armaflex Insulation on all Cold Parts BacNet

66 months (5 Years) Parts & Labor WarrantyFOR THE ENTIRE UNIT

YORK INTERNATIONAL CORPORATIONENGINEERED SYSTEMS

PRODUCT TYPE: Air Cooled Scroll Chillers COMPRESSOR SERIAL NUMBER(S):YORK CONTRACT NO.: ________________________________UNIT MODEL NUMBER: YLAA0142HE ________________________________UNIT SERIAL NUMBER: ________________________________UNIT TAG ID: CH-1, CH-2 ________________________________UNIT LOCATION: ________________________________

________________________________

PROJECT NAME: ______________INSTALLATION Shipping Date

ADDRESS:,

The term of this agreement is 66 months (5 Years), commencing ____on start up__________ and expires ____TBD________.

LIMITED WARRANTY

WHEN PROPERLY ENDORSED, THIS PROTECTION PLAN BETWEEN YORK INTERNATIONAL CORPORATION (YORK) AND CUSTOMER, WARRANTS, TO THE CUSTOMER NAMED HEREIN, FOR THE . IT DOES NOT COVER REFRIGERANT COST, FREIGHT CHARGES, *** UNASSIGNED ***OR ANY OTHER COSTS.

THIS WARRANTY EXCLUDES IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, AND WE DO NOT ASSUME, OR AUTHORIZE ANY OTHER PERSON TO ASSUME OTHER WARRANTIES FOR US. THIS WARRANTY IS OFFERED AS AN EXTENSION TO THE STANDARD LIMITED WARRANTY (FORM 50.05-NM2) AND IS SUBJECT TO THE SAME LIMITATIONS AND EXCLUSIONS, EXCEPT WHERE NOTED.

THIS PROTECTION PLAN DOES NOT COVER FAILURE OR DAMAGE RESULTING FROM FIRE, FLOOD,ABUSE, OR ACT OF GOD. ALSO EXCLUDED ARE DAMAGES OR FAILURES CAUSED BY INSTALLATION, OPERATION, OR MAINTENANCE CONTRARY TO YORK RECOMMENDATIONS, OR THOSE OF THE MANUFACTURER IF OTHER THAN YORK. IN NO EVENT SHALL YORK BE LIABLE FOR CONSEQUENTIAL, INCIDENTAL, OR INDIRECT DAMAGE, LOSS, OR INJURY. WARRANTY FOR EXCHANGE OR PARTS PROCUREMENT SERVICE SHALL BE AVAILABLE THROUGH THE SERVICER LISTED HEREIN DURING NORMAL WORKING HOURS.

DISTRICT SERVICE OFFICE: __________________________________________________________________

OFFERED BY: __________________________________________________________ ______________York Selling Representative Print/Sign Date

APPROVED BY: __________________________________________________________ ______________York Area Service Manager Print/Sign Date

ACCEPTED BY: __________________________________________________________ ______________

(Manufacturer’s Use Only)Customer Signature Date

AUTHORIZED BY: 2016-07-19Manager, Warranty Administration Date

Product Code Ref: 8523

Page 15: Appendix A1 - Cloud Object Storage | Store & Retrieve … Temp. 95F EER: 15.96 65KVA Unit Short Circuit Withstand Circuit Breaker 1.5” Armaflex Insulation on all Cold Parts BacNet

66 MONTHS (5 YEARS)FOR THE REFRIGERANT

YORK INTERNATIONAL CORPORATIONENGINEERED SYSTEMS

PRODUCT TYPE: AIR COOLED SCROLL CHILLERS COMPRESSOR SERIAL NUMBER(S):YORK CONTRACT NO.: _________________________________UNIT MODEL NUMBER: YLAA0142HE _________________________________UNIT SERIAL NUMBER: _________________________________UNIT TAG ID: CH-1 _________________________________UNIT LOCATION: _________________________________

PROJECT NAME: ______________INSTALLATION Shipping Date

ADDRESS:,

The term of this agreement is 66 months (5 Years), commencing ______________ and expires ____________.

LIMITED WARRANTYWHEN PROPERLY APPROVED AND AUTHORIZED BELOW, YORK INTERNATIONAL CORPORATION (YORK) WARRANTS TO THE CUSTOMER NAMED HEREIN, THAT YORK WILL PROVIDE THE CUSTOMER FREE OF CHARGE, WITH REPLACEMENT REFRIGERANT IN THE CASE OF ANY REFRIGERANT LOSS DUE TO ACCIDENTAL SYSTEM LEAKS. SERVICES TO RECYCLE CONTAMINATED REFRIGERANT ARE ALSO INCLUDED IN THE EVENT OF SYSTEM CONTAMINATION. THIS WARRANTY IS OFFERED ON PACKAGED STATIONARY WATER CHILLERS WITHIN THE EXTENDED WARRANTY PERIOD STATED ABOVE, AND IS TO BE OFFERED IN CONJUNCTION WITH A YORK ‘MAINTENANCE CONTRACT’ OR A YORK ‘REFRIGERANT CONSERVATION SERVICE CONTRACT.’ WE DO NOT AUTHORIZE ANY OTHER ENTITY TO PERFORM WARRANTY SERVICE ON OUR BEHALF. THIS WARRANTY IS OFFERED AS AN EXTENSION TO THE STANDARD LIMITED WARRANTY (FORM 50.05-NM2) AND IS SUBJECT TO THE SAME LIMITATIONSAND EXCLUSIONS STATED THEREIN, WHICH ARE HEREBY INCORPORATED HEREIN BY REFERENCE REMOTE EVAPORATOR, REMOTE CONDENSER, FINNED TUBE, AND MOBILE UNITS ARE EXCLUDED FROM THIS COVERAGE.THIS WARRANTY DOES NOT COVER REFRIGERANT LOSS RESULTING FROM FIRE, FLOOD, ABUSE, OR ACT OF GOD. ALSO EXCLUDED ARE DAMAGES OR FAILURES CAUSED BY OPERATION OR MAINTENANCE CONTRARY TO THE RECOMMENDATIONS OF THE EQUIPMENT MANUFACTURER. IN NO EVENT SHALLYORK BE LIABLE FOR SPECIAL CONSEQUENTIAL, INCIDENTAL, OR INDIRECT DAMAGE, LOSS OR INJURY OF ANY NATURE. WARRANTY SERVICE SHALL BE PROVIDED THROUGH THE SERVICER LISTED HEREIN DURING NORMAL WORKING HOURS AND AFTER SYSTEM FAULTS HAVE BEEN REPAIRED.THE WARRANTY AND LIABILITY SET FORTH ABOVE ARE IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES, EXPRESS OR IMPLIED IN LAW OR IN FACT, INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. THE WARRANTIES CONTAINED HEREIN SET FORTH BUYER’S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A DEFECT IN WORKMANSHIP OR MATERIALS.

DISTRICT SERVICE OFFICE: __________________________________________________________________

OFFERED BY: __________________________________________________________ ______________York Selling Representative Print/Sign Date

APPROVED BY: __________________________________________________________ _______________York Area Service Manager Print/Sign Date

ACCEPTED BY: __________________________________________________________ _______________(Manufacturer’s Use Only)

Customer Signature Date

AUTHORIZED BY: 2016-07-19Manager, Warranty Administration Date

Product Code Ref: 8599