PLUGS AND RECEPTACLES: NEC/CEC HAZARDOUS LOCATION Visit our website at www.emerson.com or contact us at (800) 621-1506. © November 2017 425 NEC/CEC: Class I, Division 1 and 2, Groups B, C, D Class II, Division 1 and 2, Groups F, G Class III NEMA 3, 3R, 4, 4X, 7CD, 9FG Applications Locations where receptacles are used with stationary or portable electrically operated devices such as: — Lighting systems — Conveyors — Heaters — Motor-generator sets — Air conditioners — Compressors — Pumps Locations where damp or corrosive conditions exist Class I: classified locations such as: — Petrochemical plants — Petroleum refineries — Paint and chemical plants — Any location where ignitable vapors or gases are present Class II: classified locations such as: — Process industries where there are dust hazards from handling such products as flour, grain and starch or any location where ignitable amounts of dust are present or amounts which would adversely affect performance Features Large housing provides ample wiring room. Style 2 (shell and extra pole) grounding. Spring door keeps dust out of receptacle when plug is not in use. Brass contacts exert constant pressure along entire contact surface and provide superior electrical contact. Contacts have beryllium copper wire springs. Insulators provide superior dielectric and mechanical strength and lowest arc tracking. Tapped NPT conduit openings at top and bottom: 30 Amp 3/4”, 60 Amp 1-1/2”, 100 Amp 2”. Interlocked” Disconnect Switch” provides safe connect and disconnect operation at 30, 60 or 100 Amp, 600 Vac maximum, three pole, non-fused motor circuit switch. FSQC permits safe operation in Class I, Group B as well as Class I, Groups C and D, Class II, Groups F, G, and Class III. To operate, insert plug and turn receptacle face to ON” position. To remove plug, turn to OFF position and pull plug out. ACP Powertite™ Series plug fits hazardous location FSQC receptacles. Both flip and screw covers are provided. Standard Materials Receptacle and mounting box: copperfree (4/10 of 1% max.) aluminum ACP plugs: copperfree (4/10 of 1% max.) aluminum housings Insulating blocks: fiber glass reinforced polyester Standard Finishes Receptacles, mounting boxes, cord connector housings and caps: epoxy powder coat Options Special Polarization: Prevents plug insertion in a receptacle or connector wired for a different voltage. In installations where there are different line voltages, the special polarization option is desirable. This allows only plugs and receptacles wired for the same line voltage to be mated together. The receptacle or connector interior is positioned 22-1/2°, relative to the polarization rivet, to the right (as specified) of standard, and plug is polarized to correspond. This option can be added to receptacles using the Powertite™ Plug. Add suffix -P4 to receptacle or plug. Auxilary contacts 1NO + 1NC. Add suffix -AUX to receptacle. NEC/CEC Cetifications and Compliances UL Standard: UL 1010 (UL 1203), UL 894, UL 1682, UL 1686 UL Listed: E10784 CSA Standard: C22.2 No. 25, C22.2 No. 30, C22.2 No. 159 CSA Certified: 025875 30 Amp Shown with Flip Lid Cover 60 Amp Shown with Screw Cap Cover 100 Amp Shown with Flip Lid Cover FSQC 30, 60 and 100 Amp Series Receptacles and Powertite Plugs NEMA 3, 3R, 4 and 4X Rated Interlocked Disconnect Switch 600 Vac Max. 250 Vdc Max. Receptacle is rated NEMA 4 when mated with a Powertite™ Plug. When not mated, leave the flip cover installed for NEMA 3, 3R rating, or install screw cover for NEMA 4, 4X rating. Classified by UL and Certified by CSA for use in specific combinations with Crouse-Hinds Arktite. Arktite is a registered trademark of Cooper Crouse-Hinds.

Upload: others

Post on 21-Feb-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Appleton™ FSQC 30, 60 and 100 Amp Series Receptacles and ... · When not mated, leave the flip cover installed for NEMA 3, 3R rating, or install screw cover for NEMA 4, 4X rating

Plugs and RecePtacles: nec/cec HazaRdous location

Visit our website at www.emerson.com or contact us at (800) 621-1506. © November 2017

425

NEC/CEC: Class I, Division 1 and 2, Groups B, C, D Class II, Division 1 and 2, Groups F, G Class III NEMA 3, 3R, 4, 4X, 7CD, 9FG

Applications•   Locations where receptacles are used with stationary or 

portable electrically operated devices such as:— Lighting systems— Conveyors— Heaters— Motor-generator sets— Air conditioners— Compressors— Pumps

•   Locations where damp or corrosive conditions exist•   Class I: classified locations such as:

— Petrochemical plants— Petroleum refineries— Paint and chemical plants— Any location where ignitable vapors or gases are present

•  Class II: classified locations such as: — Process industries where there are dust hazards from 

handling such products as flour, grain and starch or any location where ignitable amounts of dust are present or amounts which would adversely affect performance

Features•   Large housing provides ample wiring room.•  Style 2 (shell and extra pole) grounding.•   Spring door keeps dust out of receptacle when plug is not in 

use. •   Brass contacts exert constant pressure along entire contact 

surface and provide superior electrical contact.•   Contacts have beryllium copper wire springs.•   Insulators provide superior dielectric and mechanical strength 

and lowest arc tracking.•   Tapped NPT conduit openings at top and bottom: 30 Amp 3/4”, 

60 Amp 1-1/2”, 100 Amp 2”.•   “Interlocked” Disconnect Switch” provides safe connect and 

disconnect operation at 30, 60 or 100 Amp, 600 Vac maximum, three pole, non-fused motor circuit switch. FSQC permits safe operation in Class I, Group B as well as Class I, Groups C and D, Class II, Groups F, G, and Class III.

•   To operate, insert plug and turn receptacle face to “ON” position. To remove plug, turn to OFF position and pull plug out.

•   ACP Powertite™ Series plug fits hazardous location FSQC receptacles. 

•   Both flip and screw covers are provided. 

Standard Materials•   Receptacle and mounting box: copperfree (4/10 of 1% max.) 

aluminum•   ACP plugs: copperfree (4/10 of 1% max.) aluminum housings•   Insulating blocks: fiber glass reinforced polyester

Standard Finishes•   Receptacles, mounting boxes, cord connector housings and 

caps: epoxy powder coat

Options •  Special Polarization: Prevents plug insertion in a receptacle or 

connector wired for a different voltage. In installations where there are different line voltages, the special polarization option is desirable. This allows only plugs and receptacles wired for the same line voltage to be mated together. The receptacle or connector interior is positioned 22-1/2°, relative to the polarization rivet, to the right (as specified) of standard, and plug is polarized to correspond. This option can be added to receptacles using the Powertite™ Plug. Add suffix -P4 to receptacle or plug.

•  Auxilary contacts 1NO + 1NC. Add suffix -AUX to receptacle.

NEC/CEC Cetifications and Compliances•   UL Standard: UL 1010 (UL 1203), UL 894, UL 1682, UL 1686•  UL Listed: E10784•   CSA Standard: C22.2 No. 25, C22.2 No. 30, C22.2 No. 159•  CSA Certified: 025875

30 AmpShown with Flip Lid

Cover

60 AmpShown with Screw

Cap Cover

100 AmpShown with Flip Lid

Cover

FSQC 30, 60 and 100 Amp Series Receptacles and Powertite™ PlugsNEMA 3, 3R, 4 and 4X Rated Interlocked Disconnect Switch600 Vac Max. 250 Vdc Max.

Receptacle is rated NEMA 4 when mated with a Powertite™ Plug. When not mated, leave the flip cover installed for NEMA 3, 3R rating, or install screw cover for NEMA 4, 4X rating.

Classified by UL and Certified by CSA for use in specific combinations with Crouse-Hinds Arktite. Arktite is a registered trademark of Cooper Crouse-Hinds.

Page 2: Appleton™ FSQC 30, 60 and 100 Amp Series Receptacles and ... · When not mated, leave the flip cover installed for NEMA 3, 3R rating, or install screw cover for NEMA 4, 4X rating

Plug

s an

d Re

cePt

acle

s: n

ec/c

ec H

azaR

dous

loc

atio

n

Visit our website at www.emerson.com or contact us at (800) 621-1506. © November 2017

426

NEC/CEC: Class I, Division 1 and 2, Groups B, C, D Class II, Division 1 and 2, Groups F, G Class III NEMA 3, 3R, 4, 4X, 7CD, 9FG

AmpHub Size (Inches) ‡ Wire/Poles

Terminal Block Wire Range

Receptacle Catalog Number

Mating Plug Powertite™

30 3/4 or 1 3W, 4P #10 - #8 FSQC3430 ACP3034BC

60 1-1/2 3W, 4P #6 - #4 FSQC5640 ACP6034BC

100 2 3W, 4P #2 - 1/0 FSQC61040 ACP1034CD

ACP Plugs

Wire/Poles Cable Dia. (Inches) 30 Amp 60 Amp 100 Amp

3W, 4P0.500 to 1.250 ACP3034BC ACP6034BC ––

0.875 to 1.906 –– –– ACP1034CD

Maximum Horsepower Ratings of Switch

Phase Amps 120 Vac 240 Vac 480 Vac 600 Vac

Three

30 3 7.5 15 20

60 — 10 25 30

100 10 30 60 75

ACP Plug Dimensions in Millimeters (Inches)

Max. Amp A B C D

30 152.4 (6.00) 120.6 (4.75) 79.5 (3.13) 47.2 (1.86)

60 198.3 (7.81) 125.4 (4.94) 88.9 (3.50) 56.6 (2.23)

100 26.7 (10.50) 168.4 (6.63) 101.6 (4.00) 62.7 (2.47)

Receptacle is rated NEMA 4 when mated with a Powertite™ Plug. When not mated, leave the flip cover installed for NEMA 3, 3R rating, or install screw cover for NEMA 4, 4X rating.

Receptacle insulator and contacts are not serviceable.

FSQC 30, 60 and 100 Amp Series Receptacles and Powertite™ PlugsNEMA 3, 3R, 4 and 4X Rated Interlocked Disconnect Switch600 Vac Max. 250 Vdc Max.

Page 3: Appleton™ FSQC 30, 60 and 100 Amp Series Receptacles and ... · When not mated, leave the flip cover installed for NEMA 3, 3R rating, or install screw cover for NEMA 4, 4X rating

Plugs and RecePtacles: nec/cec HazaRdous location

Visit our website at www.emerson.com or contact us at (800) 621-1506. © November 2017

427

NEC/CEC: Class I, Division 1 and 2, Groups B, C, D Class II, Division 1 and 2, Groups F, G Class III NEMA 3, 3R, 4, 4X, 7CD, 9FG

FSQC 30, 60 and 100 Amp Series Receptacles and Powertite™ PlugsNEMA 3, 3R, 4 and 4X Rated Interlocked Disconnect Switch600 Vac Max. 250 Vdc Max.

FSQC Receptacles — Shown with Flip Lid Cover — Dimensions in Millimeters (Inches)

30 Amp 60 Amp

79.4 mm(3.13”)

127.4 mm (5.02”) 31.8 mm (1.25”)2 Places

Conduit Openings

Ø 0.38”(9.5 mm)

121.2 mm(4.77”)

15

18.6 mm(0.73”)

163.1 mm (6.42”)

262.

1 m

m (1

0.32

”)

127.0 mm (5.00”)

215.9 mm(8.50”)

Ø 10.5 mm(0.42”)(4) MountingHoles

39.5 mm (1.56”)2 Places

Conduit Enterance

18.9 mm(0.74”)

15

175.29 mm (6.90”)

206.4 mm (8.13”)

386.0 mm(15.20”)

100 Amp

182.7 mm (7.19”)

379.

4 m

m (1

4.94

”)

471.

5 m

m (1

8.58

”)

228.6 mm (9.00”)

15

257.5 mm (10.14”)

61.9 mm (2.44”)3 Places

Conduit Openings 6.4 mm (0.25”)

Ø 11.1 mm (0.44”)

234.9 mm (9.25”)

Receptacle is rated NEMA 4 when mated with a Powertite™ Plug. When not mated, leave the flip cover installed for NEMA 3, 3R rating, or install screw cover for NEMA 4, 4X rating.