arras maxei oil treatment - wordpress.com · control panel arras maxei oil treatment plant type mas...
TRANSCRIPT
PREAMBLE The efficient and reliable use of dielectric fluids in trans-formers, circuit breakers and other types of electrical equipments depends upon some of their basic character-istics, which in service may be affected, resulting in re-duced operating efficiency of the electrical equipments. In order to act as an insulant, a coolant and an extinguish-ing medium, dielectric fluids must have some basic proper-ties, and especially a high dielectric strength. Now, in service, the dielectric fluids basic properties may be affected by oxidation, con-densation and other contami-nants such as dissolved gases and solid impurities. Working on the principles of filtration, dehydration, and vacuum degasification,
MAXEI Industries Electri-ques oil treatment plants are particularly recom-mended to maintain, dry and fill your transformers and circuit- breakers. By removing solid impuri-ties, dissolved moisture and gases from insulating and cooling oils, they indeed enable to restore the oil dielectric properties, and thus to extend the useful life of your electrical equip-ment. Used and reknowned all over the world for their perform-ance, reliability and ease of operation, our standard plants have been enriched with the latest technological achievements in order to develop a complete range of plants meant to treat live / operating transformers. As their operation principle has been approved further to
tests performed in our Quality and Control platform, ARRAS MAXEI treatment plants meant to treat live / operating transformers ensure a reliable and safe treatment of the transformer. Available with various auto-mation levels, the MAS 4000 TEC and MAS 2000 TEC plants can operate not only on live / operating trans-formers, but also on non-energized transformers ei-ther for their filling-up or for their traditional mainte-
MAS 4000 TEC on a skid
Principle of operation 2
Main characteristics 2
Components of the plant 2
Description of the plant 3
Flow diagram 4
Options 5
SUMMARY:
TECHNICAL DESCRIPTION OF THE OIL TREATMENT PLANT MEANT TO TREAT LIVE / OPERATING TRANSFORMERS
TYPE MAS 4000 TEC
ARRAS MAXEI OIL TREATMENT
I–BETH09GB_E page 1/6
MAS 4000 TEC
ARRAS MAXEI MAS 4000 TEC plant has been especially designed to carry out the operations of filtration, dehydration and ab-sorption of dissolved gases on a transformer that is under current or operating. Then, the transformer is totally available during the treatment operations that are necessary for its efficient and safe operation. Furthermore, the transformer does not need to be stopped at all during connection with the plant if the security distance between the transformer’s connections and the terminals can be re-spected. ARRAS MAXEI MAS 4000 TEC plant has been designed to treat dielectric oil with a 50 ppm moisture content and a dissolved gas
content of approx. 10% by volume before being treated. Once the optimal treatment conditions have been reached, the clean treated oil goes out after 1 pass at a maxi-mum temperature of 70°C with a moisture content below 5 ppm* and a dissolved gas content of approximately 0.1% by vol-ume*. This restores the oil dielectric strength to a value in excess of 75 kV after treatment. An oil at 20 ppm will go out at 3 ppm* after 1 pass. These charac-teristics are given for a distillation curve of 1.10-2 mbar at 80°C. For a treatment of the active parts of transformer, these data can vary in function of the state of the transformer.
Type of transformer to be treated Up to 220 kV
Max. oil quantity 100 000 litres
Treatment of live / operating transformers with MAS 4000 TEC Co mparis o n be twenn vapo r and liquid phas es o f mo is ture and die lec tric o il
0 , 0 10 , 1110
10 010 0 0
T °C
WATEROIL
0
10
20
30
40
50
60
70
80
90
14:33:15 14:49:50 15:06:30 15:23:10 15:39:50 15:56:30 16:13:10 16:29:50 16:46:30 17:03:10 17:19:50 17:36:300,10
1,00
10,00
100,00
1 000,00
vide
Teneur en eau
Température en entrée
Régulation de température
Température en sortie
°C et % d'eau mbars
The pre-filtered dielectric fluid enters the plant through an inlet strainer, and then passes through an inlet oil pump and into an oil heater, where it is heated by im-mersion heaters. After a first filtration 7 µm absolute through cartridge filter, the dielectric fluid is sprayed into a vacuum chamber on a basket of degassing rings. Finally, after elimination of the air bub-bles and filtration 1µm absolute, the clean treated fluid flows through the out-let oil pump.
Principle of operation
- 1 Inlet oil motor-pump. - 1 Direct electrical heater. - 2 Cartridge filters 6µ absolute. - 1 Dehydration tank. - 1 Outlet oil vacuum motor-pump. - 1 Trap system of free gases. - 1 Cartridge filter 1µ absolute. - 1 Single-staged vacuum motor-pump. - 1 Set measuring, controlling, alarming and regulating apparatus. - 1 Control panel with display and PLC. - 1 Set pipes, valves and accessories for the connection of the plant to the transformer. - 1 Set of 6 hoses with flanges (5 hoses ∅40 , length : 10 m and 1 hose ∅40 , length : 2 m ). In standard presentation, the oil treatment plant is installed on a section iron plate with reten-tion tray and maintenance wheels.
Components of the plant
Options
Low speed trailer
Road trailer
Options
Tarpaulin
Metallic cover
Options
Remote control
Continuous moisture content measurement
Digital recorder
Main characteristics
* : Approximate value. ** : Consumable cartridge with filtration expressed in absolute µm at 99.9 %. Our plants are all equipped with tropicalized electrical material Power supply 400 Volts 3 phases 50 Hz Auxiliary operation in 220 Volts by transformer.
Nominal flow* during treatment (l/hr) 4 000
Heating power (kW) 78
Total power (kW) 88
Filtration** by cartridge in absolute µm 0,5
Limit vacuum against closed suction (mbar) 0.08
Vacuum during treatment (mbar) 0.5 to 2
I–BETH09GB_E page 2/6 ARRAS MAXEI OIL TREATMENT
MAS 4000 TEC
Description of the plant Inlet oil pump Maximum flow of pump in l/hr 7000
Pump type Centrifugal
Discharge rate in mCE 55
Motor power in kW 2.2
Rotation speed in rpm 1500
Pump construction Cast iron/steel
Connection diameter in mm 40
Oil heating Total heating power in kW 78
Number of thermo-dippers 10
Power of an element in kW 7.8
Auxiliary heating diameter 40
Filtration 6µm absolute Number of cartridges per filter 6
Number of filters 1
Filter construction Cast iron/steel
Clogging control Pressostat
Filtration 1µm absolute Number of cartridges per filter 1
Filter construction Cast iron/steel
Clogging control Pressostat
Vacuum pump Flow in m3/hr 170
Limit vacuum in mbar 0.08
Motor power in kW 4
Rotation speed in rpm 1450
Oil capacity in litres 5
Vacuum measurement Pirani
Auxiliary vacuum connection 50
Outlet oil pump Maximum flow of pump in l/hr 4500
Pump type Centrifugal
Discharge rate in mCE 40
Motor power in kW 3
Rotation speed in rpm 1500
Pump building Cast iron/bronze
Connection diameter in mm 40
Continuous control of the temperature of the plant at oil inlet, before degassing chamber and at oil outlet. Remote control of the overheating through security thermostat. Permanent control of the overpressures in the network thanks to pressostat, security valve and by-pass. Flows display at inlet, before degassing (regulation and mini-mum flow) and outlet of the plant. Continuous control of the oil levels and condensates in the plant. Continuous control of the oil level in the transformer. Automatic regulation of foaming effects. Tri-filtration through strainer (0.8 mm), filtration before de-gassing (7µm absolute) and fine filtration (1µm absolute) at out-let. Remote control of filters clogging with pressostat. Vacuum control with Pirani gauge and manometer. Removal of free gases and air bubbles at the outlet of the plant. Detection and automatic draining of free gases at plant outlet. Running of the plant thanks to an operating system. Self-operating in compressed air by compressor. Vacuum accumulator for draining of transformers’ connections. Secure connections to the transformer.
Filling of the plant. Piping put under vacuum. Filling of the piping. Treatment in closed circuit. Treatment on transformer. Draining of the piping. Draining of the plant. Vacuum in the accumulator for the pipes draining.
Automated and rationalized starting sequences.
I–BETH09GB_E page 3/6 ARRAS MAXEI OIL TREATMENT
MAS 4000 TEC
Comment : MAS 4000 TEC is also equipped with an additive func-tion in order to treat off line transformers, using the MAS TEC safeties. Moreover, you can also use it with the standards safeties used for MAS type treatment plants.
Control panel
ARRAS MAXEI oil treatment plant type MAS 4000 TEC is equipped with a watertight panel of industrial type in painted cast iron, with PLC, contactors, relays, terminal boards, and every cables necessary for the plant operation. On the door of the control panel stand the operating desk, the switches and the warning lights of the different components.
Painting ARRAS MAXEI oil treatment plant type MAS 4000 TEC is painted in white (RAL9002). Approximate dimensions
I–BETH09GB_E page 4/6 ARRAS MAXEI OIL TREATMENT
MAS 4000 TEC
Machine length in mm
Width
in mm
Heigh
in mm
Total length in mm
Plant on a platform with tarpaulin 3450 2150 2350 Ø
Plant on a platform with metallic cover
3450 2150 2250 Ø
Plant on a skid with tarpaulin 3250 2150 2250 Ø
Plant on a low speed trailer with tarpaulin
3250 2000 2650 4250*
Plant on a low speed trailer with metallic cover
3300 2150 2450 4250*
Plant on a road trailer with tarpau-lin
3400 2150 2850 5250*
Plant on a skid with metallic cover 3450 2150 2150 Ø
Weight
in kg 2800
3100
2800
3100
3000
3300
3100
Plant on a road trailer with metallic cover
3450 2150 2650 5250* 3500
* : Dimension with the draw bar
Nou
s nou
s rés
ervo
ns le
dro
it de
mod
ifier
les c
arac
téri
stiq
ues t
echn
ique
s san
s pré
avis
NH
RT
NBR
T
Rés
erve
d'hu
ile
V16
G4
Bag
ue té
flon
isola
nte
Van
ne à
ouve
rture
pilo
tée
Racc
ord
guill
emin
ant
i-des
serre
men
t
Van
ne h
aute
tran
sform
ateu
r
T2
B4 (J
N4)
Con
tact
d'a
larm
ebu
chho
lz :
NO
Con
tact
ala
rme
MAS
400
0 TE
C: N
O
VP12
Racc
ord
guill
emin
ant
i-des
serre
men
t
Vann
e ba
sse
trans
form
ateu
r
B1 (J
T1,C
I1)VP
1
G1
RAO
1
V1
VP2
B6
(JT6
,CI6
)
G2
RAO
25
V25
B7
(JN
7)
B2
(JN
2)
T1
B8
(JN
8)
V23
CdC
B5 (J
N5)
Filtr
atio
n 1
µm a
bsol
u
Niv
eau
d'hu
iletra
nsfo
rmat
eur
V20
VP11
CAR
2VP4
F2
VP3
B3 (J
N3)
V2G3
M1
P1
T°1
VP9
V18
CAR
1
M3D
PS2
VP8
V17
T°2
VP10
CAR
3
SCD
V3
CH
BP
V28
SG
Reg
SS1
V4
F1
PS1
TS
V13 V1
4'
P2
M2
SCAB
SCN
B
SCAH
SCN
H
V15
DEG
AZ
VP5
IC
V5V8
TE
V10
Man
o 1
V10'
ID
DM
PT1
Niv
eau
d'hu
ileda
ns g
atte
du
MAS
NH
G
Cla
p
V11
RAS
CH
VP6
NH
CS
PV
PIR
Man
o 2
ACC
U
RAO
13
V14
Tres
se c
ondu
ctric
e
Man
o 4
Opt
ion
: ten
eur e
n ea
u en
lign
e
Filtr
atio
n à
6 µm
abs
olu
Entré
e au
xilia
ire d
e re
mpl
issa
ge d
u M
AS p
ar fû
tou
ent
rée
pour
trai
tem
ent t
radi
tionn
el
Sorti
e au
xilia
ire d
e vi
dang
e du
MAS
par
fût
ou s
ortie
pou
r tra
item
ent t
radi
tionn
el
VP7
V15
V19
V19'
V15
All c
hara
cter
istic
s may
be
mod
ified
with
out a
ny p
rior
not
ice.
I–BETH09GB_E page 5/6 ARRAS MAXEI OIL TREATMENT
MAS 4000 TEC
1) LOW SPEED TRAILER The oil treatment can be installed on a low speed trailer with full tyres (max. speed : 20 km/hr). 2) ROAD TRAILER The oil treatment plant can be installed on a road trailer. The trailer is equipped with rear lights in accordance with the EU regula-tions of road code. The whole installation is commissioned by the French government vehicle testing service to be allowed to circu-late in France and in the European countries. 3) TARPAULIN PROTECTION The plant can be equipped with a protection type tarpaulin, which protects it from bad weather. The tarpaulin can be opened on the four sides thanks to its panels to enable the access to all the components of the plant. 4) METALLIC COVER PROTECTION The plant can be equipped with a metallic cover type protection, which protects it from bad weather. It is made of aluminium and the frame is made of iron steel. The side panels open horizontally, close per key and are maintained thanks to gas jacks. The panels en-able the access to the components of the plant.
Presentations
Options AUTOMATIC DRAINING OF THE VALVE This option enables an optimal protection of the vacuum net of the plant.
VOLTMETER / AMMETER This option will enable you to visualize the power supply of the plant, as well as the strength developed in order to protect the net and equipment.
REMOTE CONTROL The remote control enables to be informed of the plant operation through an internal phone line, a TELECOM phone line, or through the GSM network. RECORDER This option enables to record the physical parameters of the degassing process like temperature and vacuum level.
CONTINUOUS MOISTURE CONTENT MEASURING This option has been designed to carry out on-line moisture content measurement, that means continuously during the oil treatment. Then you reduce the errors linked to the sampling method and the risks due to hot oil handling.
REGENERATION This option enables to regenerate the oil and to decrease its acidity thanks to absorbent and colloidal properties product.
Process controls
Low speed trailer with tarpaulin Skid with tarpaulin Road trailer with metallic cover
I–BETH09GB_E page 6/6 ARRAS MAXEI OIL TREATMENT
MAS 4000 TEC
GSM remote control
Digital recorder