Amendment No. 1
to
AS 2118.1—2006
Automatic fire sprinkler systems
Part 1: General systems
REVISED TEXT
The 2006 edition of AS 2118.1 is amended as follows; the amendments should be inserted in the appropriate
places.
SUMMARY: This Amendment applies to Clauses 1.3, 1.4.14, 1.4.24, 2.2, 2.3.2.3, 2.3.2.4, 2.3.2.5, 2.3.3.2.1,
2.3.3.3, 3.3.2, 3.3.3, 3.5.2.1, 4.1.2, 4.2.1, 4.2.2.2, 4.3.1.1, 4.3.1.5, 4.3.2.2, 4.3.4.1, 5.5.3, 5.7.2, 7.9.3, 7.10.2.1,
7.10.2.2, .13.1.3, 8.1.2, 9.3.2, 10.3.2, 11.4.1.1, 11.5.5, 11.5.1.2.4, 11.5.12.5, 11.7.5.1, 11.7.6.3, 11.7.7.4,
11.7.8.5, 11.7.8.9, 11.8.3 and 12.10, Tables 5.5.2, 11.5.12.2, 11.6.3(B), 11.6.3(C), 11.6.3(D), 11.6.3(E),
11.6.4(M), 11.4.6(N), 11.6.2, 11.6.3(B), 11.6.3(C), 11.6.3(D), 11.6.3(E), 11.6.4(M),, 11.6.4(N), 11.6.4(O),
11.6.4(P), 11.6.4(Q), 11.6.4(R) and 12.10(C), Figures 4.2.2.2(B), 11.6.2, 11.6.5 and 11.7.2.6 and 10 and
Appendices A, B, C, D, E and F.
Published on 23 August 2010.
Clause 1.3
1 Delete 1668.1 (under AS/NZS listing) and replace with the following:
1668 The use of ventilation and airconditioning in buildings
1668.1 Part 1: Fire and smoke control in multi-compartment buildings2 Delete ‘1999’ from the last item ‘NFPA 13’.
Clause 1.4.14
Delete ‘(sprinkler)’ from the title and replace with ‘(nominal)’.
Clause 1.4.24
Delete the duplicated commentary text (outside the borders).
Clause 2.2
In Item (c)(iii), delete ‘A4.2.3’ and replace with ‘A4.3’.
Clause 2.3.2.3
Delete the fourth paragraph, excluding Items (a) and (b), and replace with the following:
‘Alternate wet and dry systems shall be so designed that the water transit times from valve
trip to discharge of water at the most remote sprinkler shall not exceed 60 s. The maximum
floor area, including mezzanine floor areas, controlled by one control assembly, including
tail-end extensions (see Clauses 2.3.2.8 and 2.3.2.9), shall not exceed the following:’
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
2/35
Clause 2.3.2.4
1 Delete the third paragraph and replace with the following:
‘The water transit time limitation and the floor area controlled by one control
assembly in a dry system shall comply with Clause 2.3.2.3 for alternate wet and dry
systems.’
2 In the last paragraph, delete ‘piping shall be arranged with slope for drainage’ and
replace with ‘Piping shall be galvanized and arranged with slope for drainage’.
Clause 2.3.2.5
Delete the second last paragraph and replace with the following:
‘Piping shall be galvanized and, where subject to freezing, it shall be arranged with slope
for drainage (see Clause 7.5) and standard sprinklers shall be installed in the upright
position above the line of pipe.’
Clause 2.3.3.2.1
Delete the second paragraph.
Clause 2.3.3.3
Delete the NOTE and replace with the following:
NOTE: Except as modified by this Standard, systems using Factory Mutual design requirements
and limitations for the particular ESFR sprinkler selected should also comply with the Factory
Mutual Data Sheets 2.0, 8.9 and other ‘eight series’ data sheets. Systems using the Underwriters
Laboratories (UL) sprinkler listing requirements and limitations for the selected ESFR sprinkler
should also comply with the ESFR requirements of NFPA 13.
Clause 3.2.2
Delete Items (c), (d) and (e) and replace with the following:
(c) Pendent sidewall (WP)—mounted pendent and oriented to direct the spray towards
the window or wall.
(d) Pendent sidewall (WP)—mounted horizontally and oriented to direct the spray
downwards and parallel to the window or wall.
(e) Horizontal sidewall (WH)—mounted pendent and oriented to direct the spray
downwards and parallel to the window or wall.
Clause 3.3.2
Insert the following second paragraph (text transposed from Clause 3.3.3).
The following requirements shall apply (see Clause 8.13.4):
(a) Where control assemblies are grouped in a single location, and each is fitted with a
manually resettable ‘system operated’ indicating device, at least one alarm signal
shall be provided to the monitoring centre.
(b) Where control assemblies are distributed in several locations on the one premise,
individual alarms to the monitoring centre shall be provided. Where activation of
distributed control assemblies is indicated at a single point within the premises, a
single signal may be provided to the monitoring centre.
(c) For multiple installations identification, signage shall be provided in accordance with
Clause 8.1.1(l).
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
3/35
(d) A permanent and securely affixed notice shall be located in close proximity to the
control assemblies to indicate that there is a direct alarm connection to the monitoring
centre (see Clause 8.3).
(e) Prior to testing, where an alarm signal is to be transmitted, the monitoring service
provider shall be advised that a test is to be conducted. On completion of the test, the
alarm monitoring service provider shall confirm that the system has been restored tonormal.
NOTE: Advice may be by configuring the alarm signall ing equipment into a test mode.
Clause 3.3.3
Delete the second paragraph, including Items (a) to (e); (text transposed to Clause 3.3.2).
Clause 3.5.2.1
Delete the first paragraph and replace with the following:
‘Class A fault monitoring devices shall be installed except where the monitored componentsare located within a ceiling space, a secure area or a room with access restricted by means
of a security device or system, where Class B devices may be used.’
Clause 4.1.2
Delete the second paragraph and replace with the following:
‘Calculations for the sprinkler system design shall be based on the residual pressure
available to the premises from the source of supply at the required flow. Where the
acceptable source of supply is a town main, the residual pressure shall take into account the
effect of the required flow on the water supply system.
The residual pressure shall be—
(a) determined from local water agency modelling confirming that the pressure can be
maintained for 95% of the time; and
(b) a minimum pressure obtained or calculated from local water agency records adjusted
for the effect of the system demand (excluding the pressures on the 5% of days
having the lowest pressures); or
(c) determined by testing the water supply system using a method approved by the water
supply agency.
NOTE: The water supply agency may nominate a residual pressure limit at the point of
connection to the town main, below which draw-off is not permitted.’
Clause 4.2.1
In Item (b)(ii), delete the word ‘pumps’ and replace with ‘pump’.
Clause 4.2.2.2
Insert the following note after Item (b); (note transposed from Clause 4.2.2.4):
NOTE: Where there are two or more installations in one building, it is permitted to have the
second and subsequent installation supplied by a single pipe taken downstream of the
interconnection of the two supplies [see Figure 4.2.2.2(B)].
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
4/35
Figure 4.2.2.2(B)
Delete the figure and replace with the following:
Proper ty boundary
Typical towns
mains water supply
arrangements to be
in accordance with
the requirements
of the local water
supply author i tyBui lding
Town main B
T o w n
m a i n
A
Sprinkler
control
assembl ies
Al te rnati ve
connect ion
FIGURE 4.2.2.2(B) DUAL TOWN WATER MAIN WATER SUPPLIES—UNBOOSTED
Clause 4.2.2.4
Delete Note (transposed to Clause 4.2.2.2).
Clause 4.3.1.1
In the first paragraph, delete the words ‘whichever is the lesser’.
Clause 4.3.1.5 (new)
Add a new clause as follows:
4.3.1.5 Shared water supplies
Sprinkler systems under separate ownership shall not share private water supplies, nor shall
they share connections to public water supplies.
Sprinkler system piping (with the exception of water supply connections to town mains)
shall not traverse ground that is not under the control of the owner.
C4.3.1.5 Water supplies, other than those parts under the control of the water supply
authority, should be under the control of the owner of the building containing the
installation.
Where there is a ring main or loop within the premises it is desirable to provideisolating stop valves, so situated as to maintain the maximum possible service in the
event of fracture or, if it is necessary, to close down part of the ring main.
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
5/35
Clause 4.3.2.2
Add the following commentary:
C4.3.2.2 Water conservation recommendations
(f)
To conserve water during periodic run and load testing of pumps drawing from atown main supply, a recirculation tank and associated piping [see
Figure C4.3.2.2(A)], may be provided to permit re-use of water during pump
testing. In use the circulation tank is filled as required, the town main supply is
isolated and test water is recirculated via the tank. On completion of the test run,
the town main supply is restored. Tank capacity and dimensions are selected to
accommodate maximum pump duty flow and to prevent turbulence from tank return
lines. See HB 233,Fire Protection Systems Testing, Water Conservation Handbook .
D
E
Recirculat ion
tank
Control
assembly
Flowmeter
As per meter
manufacturer’s
recommendat ions
T o w n m
a i n
FIGURE C4.3.2.2(A) TYPICAL RECIRCULATION TANK ARRANGEMENT
(g) Where a recirculation tank as in Figure C4.3.2.2(A) above cannot be provided, a
less acceptable means of conserving water during periodic run and partial load
testing of pumps drawing from a town main supply may involve piping for closed
circuit metering. A typical recirculation loop piping arrangement is shown in
Figure C4.3.2.2(B). Means for air release should be provided if air can be trapped
in the loop. Turbulence in the water entering the pump should be avoided to
prevent cavitation.
It should be noted that—
(i) prolonged recirculation can cause heat build-up unless some water iswasted; and
(ii) this arrangement cannot serve as the annual flow test facility (see
Clause 4.4.)
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
6/35
T o w n
m a i n
D
E
To control
assembly
( ies)
Air cock
5 diameters min.
Throttle valve
FIGURE C4.3.2.2(B) TYPICAL RECIRCULATION LOOP ARRANGEMENT
(h) If neither of the foregoing options is practicable, specifying pumpsets
incorporating variable speed pressure limiting control, that is, a speed control
system designed to limit the total discharge head by reducing the pump driver
speed (the speed duty point). This acts to eliminate or reduce the discharge of
water from the pressure relief valve during periodic pump run tests. Requirements
for variable speed control systems are set out in AS 2941.
(i)
Where discharge of some water is unavoidable, it should be captured and returnedto the sprinkler installation or redirected to another use. This may be accomplished
through the use of temporary on-site recirculating storage tank, grey water
recycling plant where it exists on site, or discharge directly to a tanker for off-site
use in council gardens and the like.
Clause 4.3.4.1
Add the following commentary:
C4.3.4.1 To conserve water at time of tank maintenance, the provision of dual
compartment (sectional) tanks or two half-capacity tanks is strongly recommended.Such a tank arrangement not only permits conservation of half the stored water at time
of tank draining for maintenance (by pumping from one compartment or tank to the
other) but also ensures that at least half the required stored capacity is available
during tank maintenance.
Clause 5.3.3
Add a new Item (j) as follows:
(j) In the case of partial suspended ceiling panels, full protection is required above and
below the panels. Sprinklers suspended on droppers between ceiling panels shall be
positioned to comply with the requirements of Items (e), (f) and (h) above.
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
7/35
Table 5.5.2
Delete the table and replace with the following:
TABLE 5.5.2
CLEARANCES FROM OBSTRUCTIONS—STANDARD SPRINKLERS
Dimension B—Maximum height of deflector above obstruction/beam
Dimension AConventional
upright
Conventional
pendent
12 m2
SSU/SSP
21 m2
SSU/SSP
100 Not permitted Not permitted 0 0
200 Not permitted −20 20 0
300 Not permitted −10 40 15
400 Not permitted 0 60 30
500 Not permitted 15 85 45
600 Not permitted 30 115 60
700 Not permitted 45 145 85
800 Not permitted 60 180 110
900 Not permitted 80 215 140
1000 −200 100 250 170
1100 −185 120 290 200
1200 −170 140 320 230
1300 −145 165 370 265
1400 −120 190 410 300
1500 −75 225 450 335
1600 −30 260 — 370
1700 70 325 — 410
1800 170 390 — —
NOTE: Where the sprinkler def lector i s required to be below the obstruction, Dimension B is
shown as negative (−ve).
Clause 5.7.2
Add the following at the end of Item (a):
‘Pipework in hoist and lift shafts shall be galvanized.’
Clause 7.9.3
In the third line, delete ‘1.4 MPa’ and replace with ‘1.6 MPa’.
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
8/35
Clause 7.10.2.1
Delete the Clause and replace with the following:
‘7.10.2.1 Pipes above ground
Except in the case of dry pipe and pre-action system piping, which shall be galvanized
medium steel tube, pipes above ground shall be at least equivalent to medium steel tubecomplying with the requirements of—
(a) AS 1074;
(b) AS 1579; or
(c) AS 4041.
NOTE: This does not preclude the use of corrosion-resistant pipe such as stainless steel or copper
alloy of equivalent pressure rating.’
Clause 7.10.2.2
In the first line of the first paragraph, delete ‘Clause 1.5’ and replace with ‘Clause 1.3’.
Clause 7.13.1.3
In the second line of the first paragraph, delete ‘Clause 1.5’ and replace with ‘Clause 1.3’.
Clause 8.1.2
In the first line of the first paragraph, correct ‘mutiple’ to read ‘multiple’.
Clause 9.3.2
1 After the sentence beginning ‘subject to the provision .... the reduction within
30 min’, which follows Item (b), add the following new sentence:
‘Notwithstanding any calculated storage requirement, the minimum of any tank
supply shall be 25 000 L, and no two tanks for a dual supply system shall have a
combined capacity of less than 50 000 L.’
2 After the sentence beginning ‘The storage capacity of ... for the reduced tank
capacity’, which is immediately before C9.3.2, add the following new sentence:
‘Notwithstanding any calculated storage requirement, the minimum of any tank
supply shall be 25 000 L, and no two tanks for a dual supply system shall have a
combined capacity of less than 100 000 L.’
Clause 10.3.2
1 After the sentence beginning ‘subject to the provision .... the reduction within
60 min’, which follows Item (b), add the following new sentence:
‘Notwithstanding any calculated storage requirement, the minimum of any tank
supply shall be 25 000 L, and no two tanks for a dual supply system shall have a
combined capacity of less than 50 000 L.’
2 After the sentence beginning ‘The storage capacity of ... for the reduced tank
capacity’, which is immediately before C10.3.2, add the following new sentence:
‘Notwithstanding any calculated storage requirement, the minimum of any tank
supply shall be 25 000 L, and no two tanks for a dual supply system shall have acombined capacity of less than 100 000 L.’
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
9/35
Clause 11.4.1.1
Delete the first paragraph and replace with the following:
‘Roof/ceiling sprinklers for process occupancies or categorized commodities shall be
15 mm or 20 mm orifice standard response spray type, extra large orifice (ELO) or control
mode sprinklers defined by K factor (see Clause 1.4.14).’
Clause 11.5.5
Third line, delete ‘Clause 5.8.1 and 5.8.3’ and replace with ‘Clauses 5.6.1 and 5.6.3’.
Table 11.5.12.2
In the headings of the fourth and fifth columns, correct ‘Minium’ to read ‘Minimum’.
Clause 11.5.12.4
Delete the first paragraph and replace with the following:
‘Where the clearance between roof/ceiling sprinklers and the top of rack storage exceeds
6.1 m and design criteria are not provided within the relevant area/density tables, one of the
following four options shall be applied:’
Commentary 11.5.12.5
In the second paragraph of the commentary, delete ‘Clause 5.8’ and replace with
‘Clause 5.6’.
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
10/35
Figure 11.6.2
Delete the Figure and replace with the following:
WS S
PS S
SS
11.6.4(A)
11.6.4(B)
11.6.4(C)
Cat. 1
WS S
PS SSS
11.6.4(D)
11.6.4(E)11.6.4(F)
Cat. 2
WS S
PS S
SS
11.6.4(G)
11.6.4(H)
11.6.4(I)
Cat. 3
WS S
PS S
SS
11.6.4(J)
11.6.4(K)
11.6.4(L)
Cat. 4
WS S
PS S
SS
11.6.4(M)
11.6.4(N)
11.6.4(O)
Cat. 5
WS S
PS S
SS
11.6.4(P)
11.6.4(Q)
11.6.4(R)
Cat. 6
11.6.5(C)
WSS,
PSS,SS
Cat.
1 to 5
11.6.5(D)
Cat. 6WSS,
PSS,SS
SRR
SRR
11.6.5(C)
MRR
11.6.5(E)
DRR
11.6.5(F)
11.6.5(F)
11.6.5(C)
11.6.5(D)
11.6.5(C)
11.6.5(E)
11.6.5(F)
11.6.5(F)
Table no.
11.6.5(A) 11.6.5(A)
Figure no.
11.6.5(A) 11.6.5(A)
SP,P,ShS
storage
Pal let ised
rack
storage
BB
storage
11.6.3(D)
11.6.3(E)
11.6.3(A)
Cat. 5
Cat. 6
11.6.3(C)
11.6.3(B)
Cat. 6
Cat. 5
Cat. 1 to 4
MRR
DRR
11.6.5(D) 11.6.5(D)
11.6.5(B)
11.6.5(C) 11.6.5(C)
11.6.5(B)
Ais le
1.2 m
Ais le
1.2 m
Ais le
1.2 m
Ais le
1.2 m
Ais le
1.2 m
Ais le
1.2 m
Ais le
1.2 m
Depth
2.7 m
Depth
2.7 m
Ais le
1.2 m
Depth
2.7 m
Depth
2.7 m
Depth
2.7 m
Depth
2.7 m
Height
7.6 m
Height
7.6 m
FIGURE 11.6.2 CATEGORIZED COMMODITIES DESIGN DECISION TREE
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
11/35
Table 11.6.3(B)
Delete the Table and replace with the following:
TABLE 11.6.3(B)
DESIGN CRITERIA—CATEGORY 5—SOLID PILE,PALLETIZED AND SHELF STORAGE
5
Maximum roof/ceiling height
up to 4.6 m 4.7 to 6.1 m 6.2 to 7.6 m 7.7 to 9.1 m 9.2 to 10.7 m 10.8 to 12.2 m
Maximum
storage
height,
m rDD rDA rDD rDA rDD rDA rDD rDA RDD rDA rDD rDA
1.5 8.0 230 12.0 185 12.0 185 18.0 230 24.0 230 Note 2
1.6 8.0 230 12.4 188 12.4 188 18.0 230 24.0 230 Note 2
1.8 8.0 230 13.2 194 13.2 194 18.0 230 24.0 230 Note 2
2.0 8.0 230 14.0 200 14.0 200 18.0 230 24.0 230 Note 2
2.2 8.0 230 14.8 206 14.8 206 18.0 230 24.0 230 Note 2
2.4 8.0 230 15.6 212 15.6 212 18.0 230 24.0 230 Note 2
2.6 8.0 230 16.4 218 16.4 218 18.0 230 24.0 230 Note 2
2.8 8.0 230 17.2 224 17.2 224 18.0 230 24.0 230 Note 2
3.0 8.0 230 18.0 230 18.0 230 18.0 230 24.0 230 Note 2
3.2 12.1 230 18.8 230 18.8 230 18.8 230 24.0 230 Note 2
3.4 16.2 230 19.5 230 19.5 230 19.5 230 24.0 230 Note 2
3.6 20.3 230 20.3 230 20.3 230 20.3 230 24.0 230 Note 2
3.8 n/p 21.0 230 21.0 230 21.0 230 24.0 230 Note 2
4.0 n/p 21.8 230 21.8 230 21.8 230 24.0 230 Note 2
4.2 n/p 22.5 230 22.5 230 22.5 230 24.0 230 Note 2
4.4 n/p 23.3 230 23.3 230 23.3 230 24.0 230 Note 2
4.6 n/p 24.0 230 24.0 230 24.0 230 24.0 230 Note 2
4.8 n/p 24.0 230 24.0 230 24.0 237 Note 2 Note 2
5.0 n/p 24.0 230 24.0 230 24.0 244 Note 2 Note 2
5.2 n/p 24.0 230 24.0 251 Note 2 Note 2
5.4 n/p 24.0 230 24.0 259 Note 2 Note 2
5.6 n/p 24.0 230 24.0 266 Note 2 Note 2
5.8 n/p 24.0 230 24.0 273 Note 2 Note 2
6.0 n/p 24.0 230 24.0 280 Note 2 Note 2
6.1 n/p 24.0 230 24.0 280 — — — —
Table 11.6.3(B) design constraints
Delete Item (f) and replace with the following:
(f) Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).
NOTES to Table 11.6.3(B)
Delete Note 2 replace with the following:
2
For excessive clearances, see Clause 11.5.12.4.
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
12/35
Table 11.6.3(C)
Delete the Table and replace with the following:
TABLE 11.6.3(C)
DESIGN CRITERIA—CATEGORY 6—SOLID PILE, PALLETIZED AND SHELF STORAGE
6
Maximum roof/ceiling height
up to 4.6 m
4.7 to
6.1 m 6.2 to 7.6 m 7.7 to 9.1 m 9.2 to 10.7 m 10.8 to 12.2 m
Maximum
storage
height,
m rDD rDA rDD rDA RDD rDA rDD rDA rDD rDA rDD rDA
1.50 12.0 186 12.0 186 12.0 186 24.0 280 24.0 465 Note 2
1.60 12.8 188 12.8 192 12.8 192 24.0 280 24.0 465 Note 2
1.80 14.4 191 14.4 205 14.4 205 24.0 280 24.0 465 Note 2
2.00 16.0 194 16.0 217 16.0 217 24.0 280 24.0 465 Note 2
2.20 17.6 197 17.6 230 17.6 230 24.0 280 24.0 465 Note 2
2.40 19.2 200 19.2 242 19.2 242 24.0 280 24.0 465 Note 2
2.60 20.8 204 20.8 255 20.8 255 24.0 280 24.0 465 Note 2
2.80 22.4 207 22.4 267 22.4 267 24.0 280 24.0 465 Note 2
3.00 24.0 210 24.0 280 24.0 280 24.0 280 24.0 465 Note 2
3.20 24.0 242 24.0 289 24.0 303 24.0 303 24.0 465 Note 2
3.40 24.0 274 24.0 298 24.0 326 24.0 326 24.0 465 Note 2
3.60 24.0 306 24.0 306 24.0 349 24.0 349 24.0 465 Note 2
3.80 n/p 24.0 315 24.0 373 24.0 373 24.0 465 Note 2
4.00 n/p 24.0 324 24.0 396 24.0 396 24.0 465 Note 2
4.20 n/p 24.0 333 24.0 419 24.0 419 24.0 465 Note 2
4.40 n/p 24.0 341 24.0 442 24.0 442 24.0 465 Note 2
4.60 n/p 24.0 350 24.0 465 24.0 465 24.0 465 Note 2
Table 11.6.3(C) design constraints
Delete Item (f) and replace with the following:
(f) Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).
NOTES to Table 11.6.3(C)
Delete Note 2 replace with the following:
2
For excessive clearances, see Clause 11.5.12.4.
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
13/35
Table 11.6.3(D)
Delete the Table and replace with the following:
TABLE 11.6.3(D)
DESIGN CRITERIA—CATEGORY 5—BIN BOX STORAGE
Maximum roof/ceiling height
up to 4.6 m. 4.7 to 6.1 m. 6.2 to 7.6 m. 7.7 to 9.1 m. 9.2 to 10.7 m. 10.8 to 12.2 m.
Maximum
storage
height,
m rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA
1.50 8.0 230 12.0 185 12.0 185 12.0 230 18.0 230 24.0 230
1.60 8.0 230 12.0 188 12.0 188 12.0 230 18.0 230 24.0 230
1.80 8.0 230 12.0 194 12.0 194 12.0 230 18.0 230 24.0 230
2.00 8.0 230 12.0 200 12.0 200 12.0 230 18.0 230 24.0 230
2.20 8.0 230 12.0 206 12.0 206 12.0 230 18.0 230 24.0 230
2.40 8.0 230 12.0 212 12.0 212 12.0 230 18.0 230 24.0 230
2.60 8.0 230 12.0 218 12.0 218 12.0 230 18.0 230 24.0 230
2.80 8.0 230 12.0 224 12.0 224 12.0 230 18.0 230 24.0 230
3.00 8.0 230 12.0 230 12.0 230 12.0 230 18.0 230 24.0 230
3.20 13.4 230 12.8 230 12.8 230 12.8 230 18.0 230 24.0 230
3.40 18.9 230 13.5 230 13.5 230 13.5 230 18.0 230 24.0 230
3.60 14.3 230 14.3 230 14.3 230 14.3 230 18.0 230 24.0 230
3.80 n /p 15.0 230 15.0 230 15.0 230 18.0 230 24.0 230
4.00 n /p 15.8 230 15.8 230 15.8 230 18.0 230 24.0 2304.20 n /p 16.5 230 16.5 230 16.5 230 18.0 230 24.0 230
4.40 n /p 17.3 230 17.3 230 17.3 230 18.0 230 24.0 230
4.60 n /p 18.0 230 18.0 230 18.0 230 18.0 230 24.0 230
4.80 n /p 18.0 230 18.0 230 18.9 230 18.9 230 24.0 230
5.00 n /p 18.0 230 18.0 230 19.7 230 19.7 230 24.0 230
5.20 n/p 18.0 230 20.6 230 20.6 230 24.0 230
5.40 n/p 18.0 230 21.4 230 21.4 230 24.0 230
5.60 n/p 18.0 230 22.3 230 22.3 230 24.0 230
5.80 n/p 18.0 230 23.1 230 23.1 230 24.0 230
6.00 n/p 18.0 230 24.0 230 24.0 230 24.0 230
6.20 n/p 20.0 230 24.0 230 n/p
6.40 n/p 22.0 230 24.0 230 n/p
6.60 n/p 24.0 230 24.0 230 n/p
6.80 n/p 24.0 230 n/p
7.00 n/p 24.0 230 n/p
7.20 n/p 24.0 230 n/p
7.40 n/p 24.0 230 n/p
7.60 n/p 24.0 230 n/p
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
14/35
Table 11.6.3(D) design constraints
Delete Item (e) and replace with the following:
(e) Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).
NOTES to Table 11.6.3(D)
Delete Note 2 replace with the following:
2
For excessive clearances, see Clause 11.5.12.4.
-
8/17/2019 As 2118.1-2006 Amendment1-2010
15/35
Table 11.6.3(E)
Delete the Table and replace with the following:
TABLE 11.6.3(E)
DESIGN CRITERIA—CATEGORY 6—BIN BOX STORAGE
Maximum roof/ceiling height
up to 4.6 m 4.7 to 6.1 m 6.2 to 7.6 m 7.7 to 9.1 m 9.2 to 10.7 m 10.8 to 12.2 m
Max.
storage
height,
m rDD rDA rDD rDA RDD rDA rDD rDA rDD rDA rDD rDA
1.50 8.0 230 12.0 230 12.0 230 12.0 230 18.0 230 24.0 230
1.60 8.0 230 12.0 230 12.0 230 12.0 230 18.0 230 24.0 230
1.80 8.0 230 12.0 230 12.0 230 12.0 230 18.0 230 24.0 230
2.00 8.0 230 12.0 230 12.0 230 12.0 230 18.0 230 24.0 230
2.20 8.0 230 12.0 230 12.0 230 12.0 230 18.0 230 24.0 230
2.40 8.0 230 12.0 230 12.0 230 12.0 230 18.0 230 24.0 230
2.60 8.0 230 12.0 230 12.0 230 12.0 230 18.0 230 24.0 230
2.80 8.0 230 12.0 230 12.0 230 12.0 230 18.0 230 24.0 230
3.00 8.0 230 12.0 230 12.0 230 12.0 230 18.0 230 24.0 230
3.20 12.5 229 12.8 230 12.8 230 12.8 230 18.0 230 24.0 230
3.40 13.0 223 13.5 230 13.5 230 13.5 230 18.0 230 24.0 230
3.60 14.0 217 14.3 230 14.3 230 14.3 230 18.0 230 24.0 230
3.80 n/p 15.0 230 15.0 230 15.0 230 18.0 230 24.0 230
4.00 n/p 15.8 230 15.8 230 15.8 230 18.0 230 24.0 2304.20 n/p 16.5 230 16.5 230 16.5 230 18.0 230 24.0 230
4.40 n/p 17.3 230 17.3 230 17.3 230 18.0 230 24.0 230
4.60 n/p 18.0 230 18.0 230 18.0 230 18.0 230 24.0 230
4.80 n/p 18.0 230 18.0 230 18.9 230 18.9 230 24.0 230
5.00 n/p 18.0 230 18.0 230 19.7 230 19.7 230 24.0 230
5.20 n/p 18.0 230 20.6 230 20.6 230 24.0 230
5.40 n/p 18.0 230 21.4 230 21.4 230 24.0 230
5.60 n/p 18.0 230 22.3 230 22.3 230 24.0 230
5.80 n/p 18.0 230 23.1 230 23.1 230 24.0 230
6.00 n/p 18.0 230 24.0 230 24.0 230 24.0 230
6.20 n/p 24.0 230 24.0 230 n/p
6.40 n/p 24.0 230 24.0 230 n/p
6.60 n/p 24.0 230 24.0 230 n/p
6.80 n/p 24.0 230 n/p
7.00 n/p 24.0 230 n/p
7.20 n/p 24.0 230 n/p
7.40 n/p 24.0 230 n/p
7.60 n/p 24.0 230 n/p
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
16/35
Table 11.6.3(E) design constraints
Delete Item (e) and replace with the following:
(e) Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).
NOTES to Table 11.6.3(E)
Delete Note 2 replace with the following:
2
For excessive clearances, see Clause 11.5.12.4.
Table 11.6.4(M)
Delete the Table and replace with the following:
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
17/35
-
8/17/2019 As 2118.1-2006 Amendment1-2010
18/35
Table 11.6.4(M) design constraints
Delete Item (e) and replace with the following:
(e) Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).
NOTES to Table 11.6.4(M)
Delete Note 2 replace with the following:
2
For excessive clearances, see Clause 11.5.12.4.
Table 11.6.4(N)
Delete the Table and replace with the following:
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
19/35
-
8/17/2019 As 2118.1-2006 Amendment1-2010
20/35
Table 11.6.4(N) design constraints
Delete Item (e) and replace with the following:
(e) Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).
NOTES to Table 11.6.4(N)
Delete Note 2 replace with the following:
2
For excessive clearances, see Clause 11.5.12.4.
Table 11.6.4(O)
Delete the Table and replace with the following:
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
21/35
TABLE 11.6.4(O)
DESIGN CRITERIA—CATEGORY 5—RACK STORAGE HEIGHT UP TO 7
SOLID SHELVES GREATER THAN 5.9 m2
Maximum roof/ceiling height
up to 4.6 4.7 to 6.1 m 6.2 to 7.6 m 7.7 to 9.1 m 9.2 to 10.7 m
IRS levels IRS levels IRS levels IRS levels IRS levels I
1 ET 1 ET 1 ET 1 ET 1
Max.
storage
height,
m
rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA
3.1 12.0 185 n/r 12.0 185 n/r 12.0 185 n/r 12.0 185 n/r 12.0 185
7.6 n/p 12.0 185 12.0 185
Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on netwo
-
8/17/2019 As 2118.1-2006 Amendment1-2010
22/35
Table 11.6.4(O) design constraints
Delete Item (e) and replace with the following:
(e) Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).
NOTES to Table 11.6.4(O)
Delete Note 2 replace with the following:
2
For excessive clearances, see Clause 11.5.12.4.
Table 11.6.4(P) Part A
Delete the Table and replace with the following:
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
23/35
TABLE 11.6.4(P)—PART A
DESIGN CRITERIA—CATEGORY 6—RACK STORAGE HEIGHT UP TO 7.6 m,
SOLID SHELVES MAXIMUM ROOF/CEILING HEIGHT UP TO 9.1 m
Maximum roof/ceiling height
up to 7.6 m 7.7 t
IRS levels IRS
0 1 2 3 4 0 1
Max.storageheight,
mrDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD
3.1 24.0 280 12.0 185 — — — — — — 24.0 280 12.0 185 —
3.2 n/p 12.4 185 — — — — — — — 12.4 185 —
3.4 n/p 13.2 185 — — — — — — — 13.2 185 —
3.6 n/p 14.0 185 n/r n/r n/r n/p 14.0 185
3.8 n/p 14.8 185 — — — — — — — 14.8 185 —
4.0 n/p 15.6 185 — — — — — — — 15.6 185 —
4.2 n/p 16.4 185 — — — — — — — 16.4 185 —
4.4 n/p 17.2 185 — — — — — — — 17.2 185 —
4.6 n/p 18.0 185 12.0 185 — — — — — 18.0 185 12.0
4.8 n/p 18.9 185 185 — — — — — 18.9 185 12.9
5.0 n/p 19.7 185 185 — — — — — 19.7 185 13.7
5.2 n/p 20.6 185 185 n/r n/r n/p 20.6 185 14.6
5.4 n/p 21.4 185 185 — — — — — 21.4 185 15.4
5.6 n/p 22.3 185 185 — — — — — 22.3 185 16.3
5.8 n/p 23.1 185 185 — — — — — 23.1 185 17.1
6.0 n/p 24.0 185 18.0 185 — — — — — 24.0 185 18.0
6.2 n/p 24.0 185 18.0 185 n/p 18.8
6.4 n/p 24.0 185 18.0 185 n/p 19.5
6.6 n/p 24.0 185 18.0 185 n/p 20.3
6.8 n/p 21.0
7.0 n/p 21.8
7.2 n/p 22.5
7.4 n/p 23.3
7.6 n/p 24.0
Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on netwo
-
8/17/2019 As 2118.1-2006 Amendment1-2010
24/35
Table 11.6.4(P) Part A design constraints
Delete Item (e) and replace with the following:
(e) Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).
NOTES to Table 11.6.4(P) Part A
Delete Note 2 replace with the following:
2
For excessive clearances, see Clause 11.5.12.4.
Table 11.6.4(P) Part B
Delete the Table and replace with the following:
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
25/35
TABLE 11.6.4(P)—PART B
DESIGN CRITERIA—CATEGORY 6—RACK STORAGE HEIGHT UP TO 7.6 m, WITHOU
MAXIMUM ROOF/CEILING HEIGHT FROM 9.2 m UP TO 13.7 m
Maximum roof/ceiling height
9.2 to 10.7 m 10.8 to 12.2 m
IRS levels IRS levels
1 2 3 ET 1 2 3 ET 2
Max.storageheight,
m
rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rD
3.1 18.0 185 — — — — — — 24.0 185 — — — — — — Note 2
3.2 18.0 185 — — — — — — 24.0 185 — — — — — — 24.0 1
3.4 18.0 185 — — — — — — 24.0 185 — — — — — — 24.0 1
3.6 18.0 185 n/r n/r n/r 24.0 185 n/r n/r n/r 24.0 1
3.8 18.0 185 — — — — — — 24.0 185 — — — — — 24.0 1
4.0 18.0 185 — — — — — — 24.0 185 — — — — — — 24.0 1
4.2 18.0 185 — — — — — — 24.0 185 — — — — — — 24.0 1
4.4 18.0 185 — — — — — — 24.0 185 — — — — 24.0 1
4.6 18.0 185 12.0 185 — — — — 24.0 185 18.0 185 — — — — 24.0 1
4.8 18.9 185 12.9 185 — — — 24.0 185 18.0 185 — — — — 24.0 1
5.0 19.7 185 13.7 185 — — — — 24.0 185 18.0 185 — — — — 24.0 1
5.2 20.6 185 14.6 185 n/r n/r 24.0 185 18.0 185 n/r n/r 24.0 1
5.4 21.4 185 15.4 185 — — — — 24.0 185 18.0 185 — — — — 24.0 1
5.6 22.3 185 16.3 185 — — — — 24.0 185 18.0 185 — — — — 24.0 1
5.8 23.1 185 17.1 185 — — — — 24.0 185 18.0 185 — — — — 24.0 1
6.0 24.0 185 18.0 185 12.0 185 — — 24.0 185 18.0 185 12.0 185 — — 24.0 1
6.2 n/p 18.8 185 12.8 185 — — n/p 18.8 185 12.8 185 — — 24.0 1
6.4 n/p 19.5 185 13.5 185 — — n/p 19.5 185 13.5 185 — — 24.0 1
6.6 n/p 20.3 185 14.3 185 — n/p 20.3 185 14.3 185 — — 24.0 1
6.8 n/p 21.0 185 15.0 185 — — n/p 21.0 185 15.0 185 — — 24.0 17.0 n/p 22.5 185 15.8 185 — n/p 22.5 185 15.8 185 — — 24.0 1
7.2 n/p 23.3 185 16.5 185 — — n/p 23.3 185 16.5 185 — — 24.0 1
7.4 n/p 24.0 185 17.3 185 — — n/p 24.0 185 17.3 185 — — 24.0 1
7.6 n/p 24.0 185 18.0 185 12.0 185 n/p 24.0 185 18.0 185 12.0 185 24.0 1
Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on netwo
-
8/17/2019 As 2118.1-2006 Amendment1-2010
26/35
Table 11.6.4(P) Part B design constraints
Delete Item (e) and replace with the following:
(e) Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).
NOTES to Table 11.6.4(P) Part B
Delete Note 2 replace with the following:
2
For excessive clearances, see Clause 11.5.12.4.
Table 11.6.4(Q) Part A
Delete the Table and replace with the following:
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
27/35
TABLE 11.6.4(Q)—PART A
DESIGN CRITERIA—CATEGORY 6—RACK STORAGE HEIGHT UP TO 7.6 m, SOLID SH
Maximum roof/ceiling height
7.7 to 9.1 m 9.2 to 1
IRS levels IRS le
0 1 2 3 4 1 2
Max.
storage
height,m
rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA
3.1 24.0 280 12.0 185 — — — — — 18.0 185 — —
3.2 — 12.8 185 — — — — — 18.0 185 — —
3.4 — 13.5 185 — — — — — 18.0 185 — —
3.6 — 14.3 185 n/r n/r n/r 18.0 185 n/r
3.8 — 15.0 185 — — — — — 18.0 185 — —
4.0 — 15.8 185 — — — — — 18.0 185 — —
4.2 — 16.5 185 — — — — — 18.0 185 — —
4.4 — 17.3 185 — — — — — 18.0 185 — —
4.6 n/p 18.0 185 12.0 185 — — — 18.0 185 12.0 185
4.8 — 18.9 185 12.9 185 — — — 18.9 185 12.9 185
5.0 — 19.7 185 13.7 185 — — — 19.7 185 13.7 185
5.2 — 20.6 185 14.6 185 — — — 20.6 185 14.6 185
5.4 — 21.4 185 15.4 185 — — — 21.4 185 15.4 185
5.6 — 22.3 185 16.3 185 — — — 22.3 185 16.3 185
5.8 — 23.1 185 17.1 185 — — — 23.1 185 17.1 185
6.0 — 24.0 185 18.0 185 — — n/r 24.0 185 18.0 185
6.2 — 18.4 185 18.8 — — — 18.8 185
6.4 — 19.2 185 19.5 — — — 19.5 185
6.6 — 20.0 185 20.3 — — — 20.3 185
6.8 n/p 20.8 185 21.0 — — n/p 21.0 185
7.0 — 21.6 185 21.8 — — — 21.8 185
7.2 — 22.4 185 22.5 — — — 22.5 185
7.4 — 23.3 185 24.0 — — — 23.3 185
7.6 — 24.0 185 24.0 185 — — 24.0 185
Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on netwo
-
8/17/2019 As 2118.1-2006 Amendment1-2010
28/35
Table 11.6.4(Q) Part A design constraints
Delete Item (e) and replace with the following:
(e) Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).
NOTES to Table 11.6.4(Q) Part A
Delete Note 2 replace with the following:
2
For excessive clearances, see Clause 11.5.12.4.
Table 11.6.4(Q) Part B
Delete the Table and replace with the following:
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
29/35
TABLE 11.6.4(Q)—PART B
DESIGN CRITERIA—CATEGORY 6—RACK STORAGE HEIGHT UP TO 7.6 m, SOLID SH
Maximum roof/ceiling height
10.8 to 12.2 m 12.3 to 13.
IRS levels IRS leve
1 2 3 2 3
Max.
storage
height,m
rDD rDA rDD rDA rDD rDA rDD rDA rDD
3.1 24.0 185 — — — — Note 2 Note 2
3.2 24.0 185 — — — — 24.0 185 18.0
3.4 24.0 185 — — — — 24.0 185 18.0
3.6 24.0 185 — — — — 24.0 185 18.0
3.8 24.0 185 n/r n/r 24.0 185 18.0
4.0 24.0 185 — — — — 24.0 185 18.0
4.2 24.0 185 — — — — 24.0 185 18.0
4.4 24.0 185 — — — — 24.0 185 18.0
4.6 24.0 185 18.0 185 — — 24.0 185 18.0
4.8 24.0 185 18.0 185 — — 24.0 185 18.0
5.0 24.0 185 18.0 185 — — 24.0 185 18.0
5.2 24.0 185 18.0 185 — — 24.0 185 18.0
5.4 24.0 185 18.0 185 — — 24.0 185 18.0
5.6 24.0 185 18.0 185 — — 24.0 185 18.0
5.8 24.0 185 18.0 185 — — 24.0 185 18.0
6.0 24.0 185 18.0 185 12.0 185 24.0 185 18.0
6.2 — 18.8 185 12.8 185 24.0 185 18.0
6.4 — 19.5 185 13.5 185 24.0 185 18.0
6.6 — 20.3 185 14.3 185 24.0 185 18.0
6.8 n/p 21.0 185 15.0 185 24.0 185 18.0
7.0 — 21.8 185 15.8 185 24.0 185 18.0
7.2 — 22.5 185 16.5 185 24.0 185 18.0
7.4 — 23.3 185 17.3 185 24.0 185 18.0
7.6 — 24.0 185 18.0 185 24.0 185 18.0
Licensed to Mr KARAN DHIR on 16 May 2016. Personal use licence only. Storage, distribution or use on netwo
-
8/17/2019 As 2118.1-2006 Amendment1-2010
30/35
Table 11.6.4(Q) Part B design constraints
Delete Item (e) and replace with the following:
(e) Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).
NOTES to Table 11.6.4(Q) Part B
Delete Note 2 replace with the following:
2
For excessive clearances, see Clause 11.5.12.4.
Table 11.6.4(R)
Delete the Table and replace with the following:
TABLE 11.6.4(R)
DESIGN CRITERIA—CATEGORY 6—RACK STORAGE HEIGHT
UP TO 7.6 m, SOLID SHELVES GREATER THAN 5.9 m2
Maximum roof/ceiling height
up to 9.1 m 9.2 to 10.7 m 10.8 to 12.2 m 12.3 to 13.7 m
IRS levels IRS levels IRS levels IRS levels
1 ET 1 ET 1 ET ET
Max.
storage
height,
m
rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA rDD rDA
3.1 12.0 185 n/r 18.0 185 n/r 24.0 185 n/r Note 2
3.2 — 12 185 — 12.0 185 — 18.0 185 24.0 185
3.4 — 12 185 — 12.0 185 — 18.0 185 24.0 185
3.6 — 12 185 — 12.0 185 — 18.0 185 24.0 185
3.8 n/p 12 185 n/p 12.0 185 n/p 18.0 185 24.0 185
4.0 — 12 185 — 12.0 185 — 18.0 185 24.0 185
4.2 — 12 185 — 12.0 185 — 18.0 185 24.0 185
4.4 — 12 185 — 12.0 185 — 18.0 185 24.0 185
4.6 — 12 185 — 12.0 185 — 18.0 185 24.0 185
4.8 — 12 185 — 12.0 185 — 18.0 185 23.1 185
5.0 n/p 12 185 n/p 12.0 185 n/p 18.0 185 22.3 185
5.2 — 12 185 — 12.0 185 — 18.0 185 21.4 185
5.4 — 12 185 — 12.0 185 — 18.0 185 20.6 185
5.6 — 12 185 — 12.0 185 — 18.0 185 19.7 185
5.8 — 12 185 — 12.0 185 — 18.0 185 18.9 185
6.0 n/p 12 185 n/p 12.0 185 n/p 18.0 185 18.0 185
6.2 — 12 185 — 12.0 185 — 17.3 185 17.3 185
6.4 — 12 185 — 12.0 185 — 16.5 185 16.5 185
6.6 — 12 185 — 12.0 185 — 15.8 185 15.8 185
6.8 — 12 185 — 12.0 185 — 15.0 185 15.0 185
7.0 — 12 185 — 12.0 185 — 14.3 185 14.3 185
7.2 n/p 12 185 n/p 12.0 185 n/p 13.5 185 13.5 185
7.4 — 12 185 — 12.0 185 — 12.8 185 12.8 185
7.6 — 12 185 — 12.0 185 — 12.0 185 12.0 185
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
31/35
Table 11.6.4(R) design constraints
Delete Item (e) and replace with the following:
(e) Maximum clearance requirements, from the top of the storage to the underside of the roof/ceiling, may
apply (see Note 2).
NOTES to Table 11.6.4(R)
Delete Note 2 replace with the following:
2
For excessive clearances, see Clause 11.5.12.4.
Clause 11.7.5.1
Style the two separate NOTES as follows:
NOTES:
1 Consideration should also be given to the use of large drop sprinklers. Factory Mutual Loss
Prevention Data 8-18 provides design and installation requirements for Large Drop sprinklers
protecting hanging garment storage.
2 A brief description of each of the terms used throughout the requirements for hanging
garments storage can be found in Clause 11.2.
Figure 11.7.5.7(A)
In the caption, correct ‘ERTICAL’ to read ‘VERTICAL’.
Clause 11.7.6.3
Delete the NOTE to Item (c) and replace with the following:
NOTE: Vertical barriers in racks should not be considered as a substi tute for in-rack sprinklers.
The racking shown in Figure 11.7.6.4(A) assumes solid shelving with a minimum 100 mm
transverse flues at rack uprights.
Clause 11.7.8.5
In the NOTES to Item (b), delete the second word ‘ NOTES:’
Clause 11.7.8.9
Delete the second paragraph and replace with the following:
‘Level 2 and Level 3 aerosols, subject to the design prerequisites of Appendix F, shall be
protected in accordance with the requirements of Table 11.7.8.14.’
Clause 11.8.3
Insert the following after the first paragraph (including Notes):
‘Where pumps drawing directly from a town main supply are not permitted by the water
supply authority, pump suction tanks may take the form of break tanks the capacity of
which shall be not less than one third of the quantity ( V min) or 30 000 L, whichever is the
greater. Break tanks shall incorporate the following inflow arrangements:
(a) Inflow shall be via two automatic mechanical float valves and one manually operated
valve, each sized to deliver not less than the maximum system demand (Q max).
(b) Inflow piping shall incorporate means for flow measurement.
(c) Unless a lesser dimension is acceptable to the relevant authority, the outlet of anyinflow piping shall be not less than 3.0 m horizontally from suction piping inlets.
(d) Inflow arrangements shall be accessible for inspection.’
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
32/35
Clause 12.10
Delete the equation and replace with the following:
1.85
2
1.85 4.876.05 10
Q P
C d
= × ×
×
Table 12.10(C)
In the headings of second and fourth columns, place parentheses around the word ‘internal’.
Appendix A, Paragraph A4.1
Delete the title and first paragraph and replace with the following:
‘A4.1 High Hazard— Process occupancies
The following shall be classified as High Hazard Process Occupancies:’
Appendix A, Paragraph A4.2
Delete the title replace with the following:
‘A4.2.1 High Hazard—Storage occupancies’
Appendix A, Paragraph A4.2.1
Delete the first paragraph replace with the following:
‘The sprinkler protection of storage occupancies shall take into consideration the method of
storage, the hazardous nature of the materials being stored and the height of the storage.’
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
33/35
Appendix A, Paragraph A4.2.4
1 Delete the title and text and replace with the following:
‘A4.2.4 Categories of High Hazard storage
High Hazard storage occupancies shall be classified as follows:(a) High Hazard—Storage occupancies—Category 1
Category 1 commodities include non-combustible products stored on wood
pallets, or within single layer cardboard cartons.
(b) High Hazard—Storage occupancies—Category 2
Category 2 commodities include Category 1 products stored in wooden crates
and boxes, or within multiple thickness cardboard cartons on wood pallets.
(c) High Hazard—Storage occupancies—Category 3
Category 3 commodities generally include paper or food products.
(d) High Hazard—Storage occupancies —Category 4
Category 4 goods would include Category 1, 2 and 3 goods containing in them,
or in their packaging, no more than 25% by volume of expanded (foamed)
plastic or polyurethane, or 15% by weight of unexpanded plastics or
polyurethane.
(e) High Hazard—Storage occupancies—Category 5
Category 5 goods include cartoned or uncartoned unexpanded plastics and
cartoned expanded plastics.
(f) High Hazard—Storage occupancies—Category 6
Category 6 goods include uncartoned expanded plastics.
2 Add a second Note as follows:
2 Foamed or cellular (expanded) plastics are those in which the density is reduced by the
presence of numerous small cells throughout their mass.’
Appendix D, Figure D1(b)
Delete the figure and replace with the following:
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
34/35
(b) Pump suction tank as dual supply
Full capacity tank
D E
Appendix D, Figure D2
1 Delete (b) from sub-caption and replace with (a).
2 Delete (c) from sub-caption and replace with (b).
Appendix D, Figure D3
Delete the entire sub-caption (c)
Appendix E, Paragraph E5
In Example 1, Item (i), renumber (A) and (B) to read (i) and (ii) respectively.
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
AMDT
No. 1
AUG
2010
-
8/17/2019 As 2118.1-2006 Amendment1-2010
35/35
Appendix E, Figure E6(C)
Delete the Figure and replace with the following:
50 kPa margin
Max.
f low rate
of the
system
FLOW N 1.85 x 500
P R E S
S U R E
950
900
850
800
75 0
70 0
650
600
550
500
450
400
350
300
25 0
200
15 0
10 0
50
0 7654321 8 9 10 11
1000
LEGEND:
F = Minimum towns main 1 supply at pump
G = Maximum towns main 2 supply at pump
H = Pump character is t ic curve
J = Minimum combined supply ( towns main 1 and pump)
K = Maximum combined water supply ( towns main 2 and pump)
L = Demand curve for most unfavourable des ign area
M = Demand curve for most favourable design area
L
MK
G
H
F
J
1250
1200
1150
1100
1050
1300
FIGURE E6(C) WORKED EXAMPLES—DETERMINATION OFMAXIMUM FLOW RATES
Appendix F, Table F1.3(B)
Row beginning ‘67-56-1’, last column, remove the space between ‘1’ and ‘9’.
Appendix F, Table F1.3(B)
Number Notes from 1 to 7 respectively.
AMDT
No. 1
AUG
2010