ASTM E 1886 and ASTM E 1996 TEST REPORT
Report No.: A7795.01‐109‐44
Rendered to:
LEED‐HIMMEL INDUSTRIES, INC. Hamden, Connecticut
INSULPANE OF CT INC. Hamden, Connecticut
PRODUCT TYPE: Curtain Wall System
SERIES/MODEL: 250
Test Date: 04/05/11 Report Date: 05/25/11 Test Record Retention End Date: 04/05/15
Architectural Testing
Test Report No.: A7795.01‐109‐44 Report Date: 05/25/11
Test Record Retention End Date: 04/05/15 Page 1 of 7
1.0 Report Issued To: Leed‐Himmel Industries, Inc. 76 Leeder Hill Drive Hamden, Connecticut 06517
Insulpane of CT Inc. 30 Edmond Street Hamden, Connecticut 06517
2.0 Test Laboratory: Architectural Testing, Inc. 130 Derry Court York, Pennsylvania 17406‐8405 717‐764‐7700
3.0 Project Summary:
3.1 Product Type: Curtain Wall System
3.2 Series/Model: 250
3.3 Compliance Statement: Results obtained are tested values and were secured by using the designated test method(s). The samples tested met the performance requirements set forth in the referenced test procedures for a ±2394 Pa (±50.0 psf) Design Pressure with missile impacts corresponding to Missile Level D and Wind Zone 3.
3.4 Test Date: 04/05/11
3.5 Test Location: Architectural Testing, Inc. test facility in York, Pennsylvania.
3.6 Test Sample Source: The test specimen was provided by the client. Representative samples of the test specimen(s) will be retained by Architectural Testing for a minimum of four years from the test completion date.
3.7 Drawing Reference: The test specimen drawings have been reviewed by Architectural Testing and are representative of the test specimen(s) reported herein. Test specimen construction was verified by Architectural Testing per the drawings located in Appendix C. Any deviations are documented herein or on the drawings.
3.8 List of Official Observers:
Name Company Adam Stern Leed‐Himmel Industries, Inc. John Harris Leed‐Himmel Industries, Inc. Scott A. Garner Architectural Testing, Inc. Michael D. Stremmel, P.E. Architectural Testing, Inc. Eric M. Brennan Architectural Testing, Inc.
www.archtest.com
Test Report No.: A7795.01‐109‐44 Report Date: 05/25/11
Test Record Retention End Date: 04/05/15 Page 2 of 7
4.0 Test Specification(s):
ASTM E 1886‐05, Standard Test Method for Performance of Exterior Windows, Curtain Walls, Doors and Storm Shutters Impacted by Missile(s) and Exposed to Cyclic Pressure Differentials. ASTM E 1996‐05, Standard Specification for Performance of Exterior Windows, Glazed Curtain Walls, Doors and Storm Shutters Impacted by Wind Borne Debris in Hurricanes.
5.0 Test Specimen Description:
5.1 Product Sizes:
Width Height Overall Area: 7.4 m² (80.0 ft2) millimeters inches millimeters Inches Overall size 2438 96 3048 120 5.2 Frame Construction: Frame Member Material Description All frame members Aluminum Extruded
Joinery Type Detail
Vertical/horizontal intersections
Square‐cut and butted
All horizontal members were secured to the vertical members with an extruded aluminum shear block/anchor clip. The shear block was secured to the vertical member with three #14 x 1‐1/2" long self‐tapping hex head screws. The horizontal members were secured to the shear block with two #8 x 1" long flat head screws. The shear blocks on either side of the center vertical member at the center horizontals were secured to each other with two 3/8 x 4" long bolts through the center vertical member.
Pressure plates N/A
All pressure plates were secured to the main frame members with 1/4" x 1" long hex head screws spaced 16" on center. All pressure plates utilized a snap‐fit aluminum cover.
www.archtest.com
Test Report No.: A7795.01‐109‐44 Report Date: 05/25/11
Test Record Retention End Date: 04/05/15 Page 3 of 7
5.0 Test Specimen Description: (Continued)
5.3 Weatherstripping:
Description Quantity Location Kerf‐mounted custom shaped, hollow vinyl bulb gasket 1 Row Glazing legs of the exterior pressure
plate.
Kerf‐mounted rubber gasket 1 Row Frame exterior, under the pressure plate.
5.4 Glazing: Glass Type
Spacer Type
Interior Lite
Exterior Lite
Glazing Method
1/8" tempered
1/8" tempered
0.090" PVB interlayer
0.090" PVB interlayer
1" IG Aluminum box
1/8" tempered
1/8" tempered
The glass was exterior glazed against an EPDM gasket and a bed of silicone and secured with an exterior mounted aluminum pressure plate with a gasket against the glass.
Daylight Opening
Location Quantity millimeters inches
Glass Bite
Fixed daylight opening 4 1124 x 1422 44‐1/4 x 56 1/2"
5.5 Drainage: No drainage was utilized.
5.6 Hardware: No hardware was utilized.
5.7 Reinforcement: No reinforcement was utilized.
6.0 Installation: The specimen was installed into a Spruce‐Pine‐Fir wood buck. The rough opening allowed for a 1/4" shim space. The exterior perimeter of the window was sealed with sealant. Location Anchor Description Anchor Location
Vertical member ends 1/2" x 3" long lag bolts
Two anchors were utilized through each shear block/anchor clip into the wood buck at the end of each vertical member (Reference Testing Mock‐up Drawing, Sheet 1).
www.archtest.com
Test Report No.: A7795.01‐109‐44 Report Date: 05/25/11
Test Record Retention End Date: 04/05/15 Page 4 of 7
7.0 Test Results: The results are tabulated as follows:
ASTM E 1886, Large Missile Impacts
Conditioning Temperature: 21°C (70°F) Missile Weight: 4169 g (9.19 lbs) Missile Length: 2.4 m (7' 11‐3/4") Muzzle Distance from Test Specimen: 5.2 m (17'0")
Test Unit #1: Orientation within ±5° of horizontal
Impact #1: Missile Velocity: 15.4 m/s (50.5 fps)
Impact Area: Center of glass of upper left lite
Observations: Missile hit target area and fractured the laminate glass
Results: Pass
Impact #2: Missile Velocity: 15.7 m/s (51.5 fps) Impact Area: Upper right corner of glass of lower left lite
Observations: Missile hit target area and fractured the laminate glass
Results: Pass
Impact #3: Missile Velocity: 15.4 m/s (50.4 fps) Impact Area: Lower left corner of upper right lite
Observations: Missile hit target area and fractured the laminate glass
Results: Pass
Note: See Architectural Testing Sketch #1 for impact locations.
www.archtest.com
Test Report No.: A7795.01‐109‐44 Report Date: 05/25/11
Test Record Retention End Date: 04/05/15 Page 5 of 7
7.0 Test Results: (Continued)
ASTM E 1886, Air Pressure Cycling Test Unit #1 Design Pressure: ±2394 Pa (±50.0 psf)
POSITIVE PRESSURE
Maximum Deflection at Indicator mm (inches) Pressure Range Pa (psf)
Number of
Cycles
Average Cycle Time (seconds) #1 #2 #3 #4 #5 #6
480 to 1200 (10.03 to 25.07) 3500 2.35 1.5
(0.06) 5.6
(0.22) 1.8
(0.07) 1.3
(0.05) 3.3
(0.13) 5.6
(0.22) 0 to 1440 (0 to 30.08) 300 3.08 1.5
(0.06) 5.8
(0.23) 1.8
(0.07) 1.3
(0.05) 3.3
(0.13) 5.8
(0.23) 1200 to 1920 (25.07 to 40.10) 600 2.38 2.8
(0.11) 8.9
(0.35) 2.5
(0.10) 1.5
(0.06) 5.1
(0.20) 8.9
(0.35) 720 to 2400
(15.04 to 50.13) 100 3.30 3.3 (0.13)
10.7 (0.42)
3.3 (0.13)
1.8 (0.07)
6.1 (0.24)
10.7 (0.42)
Permanent Set mm (inches)
2.5 (0.10)
2.8 (0.11)
1.3 (0.05)
0.8 (0.03)
1.8 (0.07)
2.8 (0.11)
NEGATIVE PRESSURE
Maximum Deflection at Indicator mm (inches) Pressure Range Pa (psf)
Number of
Cycles
Average Cycle Time (seconds) #1 #2 #3 #4 #5 #6
720 to 2400 (15.04 to 50.13) 50 3.57 5.1
(0.20) 12.0 (0.47)
5.1 (0.20)
1.8 (0.07)
3.0 (0.12)
12.0 (0.47)
1200 to 1920 (25.07 to 40.10) 1050 2.36 1.3
(0.05) 6.9
(0.27) 2.3
(0.09)1.5
(0.06) 2.8
(0.11) 6.9
(0.27) 0 to 1440 (0 to 30.08) 50 3.09 0.5
(0.02) 4.3
(0.17) 1.3
(0.05)0.5
(0.02) 2.5
(0.10) 4.3
(0.17) 480 to 1200
(10.03 to 25.07) 3350 2.37 0.5 (0.02)
4.1 (0.16)
1.5 (0.06)
0.8 (0.03)
2.3 (0.09)
4.1 (0.16)
Permanent Set mm (inches)
<0.3 (<0.01)
<0.3 (<0.01)
0.5 (0.02)
0.5 (0.02)
0.3 (0.01)
<0.3 (<0.01)
Observations: No additional damage or deglazing was observed. Result: Pass Note: See Architectural Testing Sketch #2 for indicator locations.
www.archtest.com
Test Report No.: A7795.01‐109‐44 Report Date: 05/25/11
Test Record Retention End Date: 04/05/15 Page 6 of 7
General Note: Upon completion of testing, the specimens met the requirements of Section 7 of ASTM E 1996. 8.0 Test Equipment:
Cannon: Constructed from steel piping utilizing compressed air to propel the missile
Missile: 2x4 Southern Pine
Timing Device: Electronic Beam Type
Cycling Mechanism: Computer controlled centrifugal blower with electronic pressure measuring device
Deflection Measuring Device: Linear transducers
Tape and film were not used to seal against air leakage during structural testing.
www.archtest.com
Test Report No.: A7795.01‐109‐44 Report Date: 05/25/11
Test Record Retention End Date: 04/05/15 Page 7 of 7
The service life of this report will expire on the stated Test Record Retention End Date, at which time such materials as drawings, data sheets, samples of test specimens, copies of this report, and any other pertinent project documentation, shall be discarded without notice. If test specimen contains glazing, no conclusions of any kind regarding the adequacy or inadequacy of the glass in any glazed test specimen(s) can be made. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, Inc. ___________________________________________ ______________________________________________ Eric M. Brennan Michael D. Stremmel, P.E. Technician Senior Project Engineer EMB:dem Attachments (pages): This report is complete only when all attachments listed are included. Appendix‐A: Sketches (2) Appendix‐B: Photograph (1) Appendix‐C: Drawings (3) This report produced from controlled document template ATI 00498, issued 02/28/11.
www.archtest.com
Test Report No.: A7795.01‐109‐44 Report Date: 05/25/11
Test Record Retention End Date: 04/05/15
Appendix A
Sketches
www.archtest.com
Test Report No.: A7795.01‐109‐44 Report Date: 05/25/11
Test Record Retention End Date: 04/05/15
Appendix B
Photograph
Photo No. 1 Front of Unit
www.archtest.com
Test Report No.: A7795.01‐109‐44 Report Date: 05/25/11
Test Record Retention End Date: 04/05/15
Appendix C
Drawings
www.archtest.com