ba profibus dlt6100 en[1]

92
Description of the PROFIBUS connection FMS / VMS ETAMATIC / ETAMATIC OEM FA1 Sensors and Systems for Combustion Engineering

Upload: chabane148549

Post on 25-Nov-2015

86 views

Category:

Documents


5 download

TRANSCRIPT

  • Description of the FMS / VMS TIC / ETAMATIC OEM

    FA1

    Sensors and Systems

    for Combustion EngineeringPROFIBUS connection ETAMA

  • Table of ContentsTable of Contents

    1 HISTORY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

    1.1 Version History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    2 GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

    2.1 For Your Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    2.2 Attention to the German Law on Device Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    2.3 Validity of these Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

    3 DESCRIPTION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

    3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    3.2 Physical Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    3.3 Device Master File GSD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    4 OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13

    4.1 Connection of the Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    4.2 Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    4.3 Connecting Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154.3.1 PROFIBUS at ETAMATIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154.3.2 PROFIBUS at FMS/VMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    4.4 Installation Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    5 PARAMETER. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18

    5.1 Systembus-Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    5.2 PROFIBUS-Parameter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195.2.1 Parameter Table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195.2.2 Parameter Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    6 OUTPUT DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21

    6.1 Output Data Table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    6.2 Internal Load . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256.2.1 Internal Load Output Bytes 0-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256.2.2 Controller Actual Value Output Bytes 2-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256.2.3 Actual Value Channel 1-5 Output Bytes 4-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

    6.3 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276.3.1 Fault Codes Bytes 14-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276.3.2 Operating Modes Output Bytes 16-17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 272

  • Table of Contents6.4 Direct Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286.4.1 RegisterNo. Output Bytes 18-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286.4.2 Register Value Output Bytes 20-21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

    6.5 UserDiagnose Bytes 22-23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

    6.6 O2-Setpoint Bytes 24-25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

    6.7 Digital Outputs Bytes 26-27 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

    6.8 Oxygen O2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336.8.1 O2-Setpoint Output Bytes 24-25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336.8.2 O2-Actual Value Output Bytes 28-29 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 336.8.3 O2-Measured Value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

    6.9 Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346.9.1 Value 1 Output Bytes 30-31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346.9.2 Value 2 Bytes 32-33 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346.9.3 Value 3 Bytes 34-35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346.9.4 Value 4 Bytes 36-37 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346.9.5 Value 5 Bytes 38-39 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346.9.6 Value 6 Bytes 40-41 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346.9.7 Value 7 Bytes 42-43 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346.9.8 Value 8 Bytes 44-45 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356.9.9 Value 9 Bytes 46-47 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356.9.10 Value 10 Bytes 48-49 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 356.9.11 Register 1-8 Handshake-IN Byte 92. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

    6.10 LT1/LT2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 366.10.1 O2-Measured Value LT1/LT2 Output Bytes 50-51 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 366.10.2 Operating mode Bytes 52-53 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 366.10.3 Faults Bytes 54-55 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 386.10.4 Warning Bytes 56-59 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 396.10.5 Absolute Pressure LT1 or Inner Resistance Probe LT2 bytes 60-61 . . . . . . . . . . . . . . 406.10.6 Application specific measured value bytes 62-69. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 406.10.7 Reserve Output Bytes 70-77 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

    6.11 LSB-Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 416.11.1 Status LSB-Output-Modules Output Byte 78 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 416.11.2 Status PID-Regulator-Digital-Outputs Output Bytes 78-80. . . . . . . . . . . . . . . . . . . . . . 41

    6.12 LSB-Output Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 426.12.1 Status LSB Module Output Byte 81 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 426.12.2 Module 16 Bytes 82-89. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

    6.13 LSB Digital Input Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 436.13.1 Module 1-2-13-14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 436.13.2 Register Handshake_IN Output Byte 92 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

    6.14 NEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 446.14.1 Device Status Output Byte 93 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 446.14.2 Handshake IN Output Byte 94 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 446.14.3 Indication Information Byte 95-105. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 456.14.4 Input Status bytes 106-111. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 453

  • Table of Contents7 INPUT DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47

    7.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 477.1.1 Input Data Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

    7.2 Controlword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 507.2.1 Controlword Bytes 0-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

    7.3 Analogue value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 517.3.1 Analogue value 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

    7.4 Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 537.4.1 Digital Controlword (input-bytes 6-7) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 537.4.2 Digital Inputs 1 Bytes 8-9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 547.4.3 Digital Inputs 2-Bytes 14-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

    7.5 Access to Directly Addressed Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 637.5.1 Register Number Bytes 10-11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

    7.6 Access to Indirectly Addressed Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 647.6.1 RegisterNo. 1-10 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 657.6.2 Handshake-OUT Byte 66 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

    7.7 LSB-Output Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 677.7.1 Module-11 Bytes 40-47 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 677.7.2 Module-6 and 7 Byte 56 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 677.7.3 Module-12 Bytes 48-55 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

    7.8 Reserve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 687.8.1 Free Input Bytes 57 - 65 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

    7.9 Indirectly Addressed Register . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

    7.10 NEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 697.10.1 Handshake-OUT and Device-No. Byte 67 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 697.10.2 NEMS-Device Number Byte 67 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 697.10.3 NEMS-Relay 1...16 Bytes 68-69. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 707.10.4 LSB Time Set Byte 70-75 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

    8 REGISTER TABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72

    8.1 Special Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

    8.2 Standard Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

    9 APPENDIX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .87

    9.1 NEMS Handshake . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 874

  • 1 History1 History

    1.1 Version History

    *1) Communication processor - Version K2p001 24.08.01 and GSD-File 663P7N01.gsd

    *2) Communication processor - Version K2x001 13.12.01 and GSD-File 663P7N02.gsd

    *3) Communication processor - Version K2x001 13.12.01 and GSD-File 663P7N02.gsd

    *5) Communication processor - Version K4k001 04.09.03 and GSD-File 663P7N05.gsd

    *6) Communication processor - Version K4w001 14.05.04 and GSD-File 663P7N06.gsd

    LT1 Version 4V24, LT2 Version 1V30a, FMS/VMS/ETAMATIC Version 4.100 and higher

    *8) Communication processor - Version A5f001 11.11.05 and GSD-File 663P7N07.gsd

    LT1 Version 4V24, LT2 Version 1V30a, FMS/VMS/ETAMATIC Version 4.100 and higher

    **) Future extensions, realization open yet5

  • 2 General Information2 General Information

    2.1 For Your Safety

    In this operating instructions, the following symbols are used as important safety instructions to the user. These symbols appear wherever there is a need for this information in a particular section. It is essential to note and comply with the safety instructions, particularly the warnings.

    DANGER!Indicates possible danger to personnel, particularly with regard to electrical equipment

    WARNING!Indicates possible danger to personnel if the system components are not handled correctly.

    CAUTION!Indicates danger to system components or possible impairment of functionality.

    NOTICE!Contains important additional information for the user concerning the system or system com-ponents and provides helpful tips

    Contained in texts that provide information on how to perform tasks.In performing all tasks, the operator is requested to observe all statutory safety regulations and to do everything possible, according to the circumstances, to prevent injury to persons or damage to equipment6

  • 2 General Information2.2 Attention to the German Law on Device Safety

    The German Law on Device Safety regulates the following:Note the instructions for use! Use the device only in compliance with the instructions, which are contained in this document for PROFIBUS (publication no. DLT6100-10-aEN-047).If this document is a supplement, use it only in combination with the basic manuals.

    Use the devices only for the purpose described in this documentation.

    Used by trained personnel only. Only persons whose knowledge and training qualifies them to do so, are allowed to operate and service the device . Note the safety provisions of the burner manufacturer.

    To be used only in a grounded power line network!

    Electrical connection with devices that are not mentioned in this operating instructions - only after consultation with the manufactorers or an authorized expert.Liability for the function of the device shall be transferred to the owner or user. Liability for the function of the device shall be borne by the owner or user insofar as the device has been used by persons without the necessary knowledge, has been improperly used, serv-iced or repaired or has been handled in a manner that does not conform to proper use.Modifications to the device render the type approval null and void. Inputs and outputs of the device and associated modules may only be connected as indicated in this manual.LAMTEC GmbH & Co. KG is not liable for damages occurring as a result of non-compliance with the above instructions. Compliance with the above instructions shall not entail any ex-tension to the warranty and liability provisions of LAMTEC GmbH & Co. KG's terms of sale and delivery.Insofar as reference is made to laws, regulations and standards, the basis for these shall be the law of the Federal Republic of Germany.7

  • 2 General Information2.3 Validity of these Instructions

    This supplementary manual applies to the PROFIBUS It is only valid in combination with the basic documents of the following devices:

    ETAMATIC / ETAMATIC S, ETAMATIC OEM / ETAMATIC S OEM, ETAMATIC V / ETAMATIC VS, Burner Control FA1

    the Combustion-Management-SystemFMS 4 / FMS 5

    and the Fuel and Air Ratio ControlVMS4 / VMS5

    in any configuration.8

  • 3 Description3 Description

    3.1 General

    Communication to the PROFIBUS is carried out on a master/slave basis. With the customer side always being considered the master.LAMTEC burner control units with the PROFIBUS interface offer many advantages in relation to use and integration into a PROFIBUS network:Configurable processor data module with preconfigured data content or parameters that can be freely set Quick transmission of processor values Direct reading and writing of inputs and outputs Forcing of inputs Back-up controller function Acyclic services for parameter transfer

    3.2 Physical Properties

    Interface:cable medium RS485 (copper)Network:linear bus with active bus termination at both ends.Transfer medium:shielded dual-wire, twisted cable. The bus cable properties are specified in IEC 61158.The cable type shown below can be used

    Cable length:The maximum length of cable is dependent on the master.

    DANGER!Stub cables must be avoided

    Baud rates:The baud rate is defined and fixedAddressing:Addressing is set up using parameter 887.

    Example

    Wave impedance 135 ... 165 at 3 ... 20 MHzOperating capacity (pf/m) < 30

    Loop impedance (/km) < 110Wire diameter (mm) > 0.64

    Wire cross-section (mm2) > 0.349

  • 3 Description3.3 Device Master File GSD

    The DMD is an ASCII text file in which the general and device-specific communication char-acteristics of a PROFIBUS device from the manufacturer of PROFIBUS components can be described using obligatory and optional keywords.The DMD file describes all important parameters for cyclical communication.Extract from our DMD file for ETAMATIC:Vendor_Name = "LAMTECGmbH"Model_Name = "KomProzessor"Revision = "N07"Ident_Number = 0x73649.6_supp = 119.2_supp = 193.75_supp = 1187.5_supp = 1500_supp = 11.5M_supp = 1Module = "Geraet 38 Wort A 56 Wort E" 0xC0, 0x65, 0x77EndModule

    NOTICE!The LAMTEC communications processor only serves PROFIBUS DP (decentralised periph-erals)You can see the current status of the DMD file on the enclosed CD or request it from our Sup-port Hotline on (0049) 06227 6052 33 or by email [email protected]

    Fig. 3-1 Display without communications processor

  • 3 DescriptionFig. 3-2 Selection of a communications processor

    Fig. 3-3 Installing the DMD file11

  • 3 DescriptionFig. 3-4 Display with communications processor12

  • 4 Operation4 Operation

    4.1 Connection of the Interface

    The PROFIBUS module is mounted on the top hat rail in the control cabinet. The connection is made using a 9 pin sub-D PB-X1 socket and a 9 pin PB-X2 socket connected to the module.The physical signals of the serial interface conform to RS485 specification.The user is to set up the cables. In doing so, the general cable specifications in accordance with IEC61158 are to be adhered to.

    Item number for FMS/VMS 663 R 0401

    ETAMATIC 663 R0 401ETA

    PB-X1, PB-X2 connection PROFIBUS DP input/output

    LED LED1 green: Continuous light in normal operation:Display of operation voltage of the electrically isolated PROFIBUS interface

    LED2 green: PROFIBUS Tx-LED to the PROFIBUS master

    LED3 yellow: PROFIBUS Rx LED from the PROFIBUS master

    LED4 red: shows PROFIBUS transmit/receive switching of the RS-485 driver (Tx enable)

    LED5 yellow: shows PROFIBUS status "data exchange":- switched of if: "data exchange"- continuous light if: No "data exchange" (statuses: GET_CONFIG, GET_PARAMETER, or all other statuses13

  • 4 Operation4.2 Wiring

    When laying cables, the instructions provided by the manufacturer of the master subassembly for laying cables are to be adhered to. Cable routing inside buildings (inside and outside the control cabinets) Cable laying outside of buildings Potential equalisation Shielding of cables Lengths of cables

    NOTICE!In the technical guidelines "Set Up Guidelines for PROFIBUS DP / FMS" (publisher:PROFI-BUS PNO user organisation) the laying of PROFIBUS cables is described in more detail14

  • 4 Operation4.3 Connecting Diagrams

    The connection diagrams show LAMTEC burner control units that are connected directly to the communications processor. Further LAMTEC devices (such as NEMS, LT...) must be con-nected to the communications processor by means of the LAMTEC SYSTEM BUS (LSB).You can find connection plans for this in the documentation on LSB (DLT no. 6059).

    4.3.1 PROFIBUS at ETAMATIC

    Fig. 4-1 PROFIBUS at ETAMATIC15

  • 4 Operation4.3.2 PROFIBUS at FMS/VMS16

    Fig. 4-2 PROFIBUS at FMS

  • 4 Operation4.4 Installation Notes

    To ensure trouble free and reliable functioning of the PROFIBUS interface and thus guarantee communication between the slave and master, please note the following installation instruc-tions: Measurement and data cables must be laid separately from control cables: Sensor measurement cables must be laid as a shielded cable twisted in pairs. Connected contactors, relays, motors etc. must be equipped with an RC protective circuit

    as stated by the manufacturer: The device may not be installed close to strong electric or magnetic fields:

    WARNING!The device is not suitable for installation in explosive areas

    CAUTION!A missing connection could lead to the destruction of the device

    WARNING!The device may only be used in the environment with the permitted type of protection

    CAUTION!In equipment where transient overvoltages can occur, the devices are to be equipped with ad-ditional overvoltage filters or limiters.

    CAUTION!The device contains components subject to ESD

    WARNING!The user must ensure that no inappropriate predetermined measurement values outside of the measurement area are transferred to the controller. If necessary, analogue input values with limiting functions are to be monitored and functions for switching off and safety are to be wired in.17

  • 5 Parameter5 Parameter

    5.1 Systembus-Parameter

    DEV = FMS/VMS, ETAMATIC/ETAMATIC=EM, FA1

    DEV BUS Description Default-Values Value Range

    845 1 Systembus-Family 1846 2 LSB-Modules-Occupancy-Configuration 6 With versions *1) ... *5) you may insert a

    customer specific value from 0 to 5For versions *6) and higher this value must be = 6

    847 3 LSB-Device-Number 1848 4 LSB-Analog-Modules-Input-Output-

    Range-Configuration0 see separate description

    849 5 reserved 018

  • 5 Parameter5.2 PROFIBUS-Parameter

    5.2.1 Parameter Table

    DEV = FMS/VMS, ETAMATIC/ETAMATIC OEM, FA1

    DEV BUS Description Default Values Description

    886 1 reserved 1

    887 2 PROFIBUS-Slave-Address

    888 3 Behaviour of FMS/VMS/ETAMATIC after an interrupt of the PROFIBUS communi-cation or after disconnecting the Commu-nication Processor.Remark: Parameter 888 is used only for FMS/VMS/ETAMATIC internal. The Communi-cation Processor does not use this parameter.

    0 The input data will be erased after 5 sec. It results in no fault condition and does not switch off burner.1 After 5 sec. the burner switches OFF due to fault condition.2 No reaction. The input data still exists > 2 = time-value in [sec] up to the response, which means:a) for even numbers the input data will be erased, it results in no fault condition and does not shut OFF the burnerb) for odd numbers it results in a fault con-dition and the burner switches OFF

    889 4 Time-out value of the Com. - Processor in units of 25 ms (after that time the data are set to non valid, time in which no commu-nication via PROFIBUS exists to FMS/VMS/ETAMATIC)

    100(100 * 25ms = 2,5s)

    0... 65000(x * 25 ms = 0... 1625 s)

    890 5 Analog Value1 Configuration 1 0-not configured1-load input2-outside temperature set point3-correction value 14-correction value 25-mixing signal for mixed-firing

    891 6 Analog Value2 Configuration 2 0-not configured1-load input2-outside temperature set point3-correction value 14-correction value 25-mixing-signal for mixed-firing

    892 7 Analog Value3 Configuration *6) 3 0-not configured1-load input2-outside temperature set point3-correction value 14-correction value 25-mixing signal for mixed-firing

    893 8 Analog Value4 Configuration *6) 4 0-not configured1-load input2-outside temperature set point3-correction value 14-correction value 25-mixing-signal for mixed-firing

    894 9 reserved

    895 10 reserved for customer specific value19

  • 5 Parameter5.2.2 Parameter Description

    Addressing 887

    The PROFIBUS slave address is set with parameter 887.

    Time-Out 888/889

    The behaviour of the device in the event of bus failure or the bus stopping is regulated using the PROFIBUS parameter 888.The following settings are possible:

    Analogue Value 890-893

    The content of these variables can be used an analogue input signal. According to the value of parameter 890 in FMS/VMS/ETAMATIC, the firing rate value, the outside temperature, one of the two correction channels or the mixing signal for the mixed combustion to are transferred to FMS/VMS/ETAMATIC used there instead of the value at the input terminal

    The analogue values 3 and 4 are only available from the following versions:Communications processor vers. K4w001 14.05.04 and DMD file "663P7N06.gsdLT1 from version 4V24, LT2 on version 1V30a, FMS/VMS/ETAMATIC from version 4.100

    Value Procedure

    4 Default value

    2...124 Freely selectable value area to set the address

    Value Procedure

    0 The input data is deleted after 5 seconds. There is no fault shutdown

    1 There is a fault shutdown after 5 seconds

    2 No reaction. The input data remains present

    >2 The value set gives the time in [s], which elapses until there is a reaction.In doing so, the input data is deleted for even figures and no fault shutdown takes place.There is a fault shutdown for uneven numbers

    0 Procedure

    1 Value is switched off

    2 Regular firing rate input

    3 Predetermined outside temperature

    4 Correction value 1

    5 Correction value 2

    6 Mixing signal for mixed combustion20

  • 6 Output Data6 Output Data

    6.1 Output Data Table

    NOTICE!Output data will be transferred from FMS/VMS/ETAMATIC to PROFIBUS master. You have to mask every free bit position in PROFIBUS master, to permit compatibility to new firmware ver-sions.

    All unsigned int-Values are transmitted first Byte X: High-Byte, second Byte X+1: Low Byte.

    Outputbytes

    Data Type Value Range(hex)

    Definition Description

    0,1 unsigned int 0000...0064 load value load value in%0% = base load100% = max.load

    2, 3 unsigned int 0000... 03E7 actual value controller actual value of controller(boiler temperature)

    4, 5 unsigned int 0000... 0064 actuator pos. of channel 1 actuator position of channel 1 in%0% = positioning element at low range100% = positioning element at high range Note: The actual values of low/high range are transferred from FMS with the values:KPR_uiMinWert_Kanal_1 and KPR_uiMaxWert_Kanal_1only if the FMS is incrementing the KPR_uiRefreshParameter!

    6, 7 unsigned int 0000... 0064 actuator pos. of channel 2 actuator pos. of channel 2 in% (see above)

    8, 9 unsigned int 0000... 0064 actuator pos. of channel 3 actuator pos. of channel 3 in% (see above)

    10, 11 unsigned int 2710... 0064 actuator pos. of channel 4 actuator pos. of channel 4 in% (see above)

    12, 13 unsigned int 0000... 0064 actuator pos. of channel 5 actuator pos. of channel 5 in% (see above)

    14, 15 unsigned int 0000 03E7 actual fault code indicating the last fault code, resp. the actual fault code

    16, 17 unsigned int 0000 FFFF mode of operation bit pattern of mode of operation

    18, 19 unsigned int 2710 FFFF register-no. after polling of a register value, the response indicates here the register no. (should be com-pared with the original request)

    20, 21 unsigned int 0000 FFFF register-value content value of the register

    22, 23 unsigned int 0000 0001 user diagnose 0 - data not valid (respect. not actual)1 - data received from the FMS/VMS

    *1) 24, 25 unsigned int 0000 03E7 O2-setpoint O2-setpoint, value - in a tenth of percent

    *1) 26,27 unsigned int 0000 FFFF digital outputs digital outputs, bit coded

    *1) 28,29 unsigned int 0000 03E7 O2-actual value O2-actual value, in a tenth of percent

    *3) 30, 31 unsigned int 0000 FFFF Modbus-Register-Value 1 value of Modbus-Register 1 (see input data and appendix A)

    *3) 32,33 unsigned int 0000 FFFF Modbus-Register-Value 2 value of Modbus-Register 2(see input data and appendix A)

    *3) 34, 35 unsigned int 0000... FFFF Modbus-Register-Value 3 value of Modbus-Register 3(see input data and appendix A)

    *3) 36, 37 unsigned int 0000... FFFF Modbus-Register-Value 4 value of Modbus-Register 4(see input data and appendix A)21

  • 6 Output Data*3) 38, 39 unsigned int 0000... FFFF Modbus-Register-Value 5 value of Modbus-Register 5(see input data and appendix A)

    *3) 40, 41 unsigned int 0000... FFFF Modbus-Register-Value 6 value of Modbus-Register 6(see input data and appendix A)

    *3) 42, 43 unsigned int 0000... FFFF Modbus-Register-Value 7 value of Modbus-Register 7(see input data and appendix A)

    *3) 44, 45 unsigned int 0000... FFFF Modbus-Register-Value 8 value of Modbus-Register 8(see input data and appendix A)

    *3) 46, 47 unsigned int 0000... FFFF Modbus-Register-Value 9 value of Modbus-Register 9(see input data and appendix A)

    *3) 48, 49 unsigned int 0000... FFFF Modbus-Register-Value 10 value of Modbus-Register 10(see input data and appendix A)

    *5) 50, 51 unsigned int 0000... FFFF O2 Value LT1 or LT2 O2-value in units of 1/10%*5)52, 53 unsigned int 0000... FFFF Operating mode of LT1 or

    LT2bit-coded value of operating mode of LT1 or LT2, see table below

    *5) 54, 55 unsigned int 0000... FFFF Faults states of LT1 or LT2 bit-coded value of fault states of LT1 or LT2, see table below

    *5) 56, 57 unsigned int 0000... FFFF Warnings 1 of LT1 or LT2 bit-coded value of warning-word of LT1 or LT2, see table below

    *5) 58, 59 unsigned int 0000... FFFF Warnings 2 of LT1 or LT2 bit-coded value of warning-word of LT1 or LT2, see table below

    *5) 60, 61 unsigned int 0000... FFFF absolute pressure value of LT1 or internal resistance of probe LT2

    absolute pressure value of LT1 in mbar or inter-nal resistance of probe LT2 in units of 0.1 Ohm, the meaning of this LT-value can be selected by parameter 1302 in the LT

    *5) 62, 63 unsigned int 0000... FFFF LT1/LT2: Application spe-cific measured value 1

    application specific measured value 1. The meaning of this LT-value can be selected by parameter 1303 in the LT

    *5) 64, 65 unsigned int 0000... FFFF LT1/LT2: Application spe-cific measured value 2

    application specific measured value 2. The meaning of this LT-value can be selected by parameter 1304 in the LT

    *5) 66, 67 unsigned int 0000... FFFF LT1/LT2: Application spe-cific measured value 3

    application specific measured value 3. The meaning of this LT-value can be selected by parameter 1305 in the LT

    *5) 68, 69 unsigned int 0000... FFFF LT1/LT2: Application spe-cific measured value 4

    application specific measured value 4. The meaning of this LT-value can be selected by parameter 1306 in the LT

    *5) 70, 71 unsigned int 0000... FFFF LT1/LT2: reserved reserved for future expansions

    *5) 72, 73 unsigned int 0000... FFFF LT1/LT2: reserved reserved for future expansions

    *5) 74, 75 unsigned int 0000 FFFF

    LT1/LT2: reserved reserved for future expansions

    *5) 76, 77 unsigned int 0000... FFFF LT1/LT2: reserved reserved for future expansions

    *6) 78 unsigned char

    00 . FF Status LSB-Output-Mod-ules and **) PID-Regulator-Analog-Outputs

    Status-Bits (0 => Offline, 1 => Online):Bit 0: LSB-Analog-Output-Module-11Bit 1: LSB-Analog-Output-Module-12Bit 2: LSB-Digital-Output-Module-6Bit 3: LSB-Digital-Output-Module-7Bit 4...7: PID-Regulator-Analog-Output. **)

    *6) 79 unsigned char

    00 .7F **) Status PID-Regulator-Digital-Outputs

    Status-Bits (0 => Offline, 1 =>Online):Bit 0 ... 6: PID-Regulator-Digital-Out. **)

    Outputbytes

    Data Type Value Range(hex)

    Definition Description22

  • 6 Output Data*6) 80 unsigned char

    00 . FF reserved

    *6) 81 unsigned char

    00.... F7 Status LSB-Analog-Input-Modules and LSB-Digital-Output-Modules

    Status-Bits (0=> Offline, 1 => Online):Bit 0: reservedBit 1: LSB-Analog-Input-Module-14Bit 2: LSB-Analog-Input-Module-15Bit 3: LSB-Analog-Input-Module-16Bit 4: LSB-Analog-Input-Module-1Bit 5: LSB-Analog-Input-Module-3Bit 6: LSB-Analog-Input-Module-13Bit 7: LSB-Analog-Input-Module-14

    *6) 82, 83 unsigned int 0000... 03E7 LSB-AnalogInput-Module-16.1

    LSB-Analog-Input-Module-16Input-Value 1

    *6) 84, 85 unsigned int 0000... 03E7 LSB-AnalogInput-Module-16.2

    LSB-Analog-Input-Module-16Input-Value 2

    *6) 86, 87 unsigned int 0000... 03E7 LSB-AnalogInput-Module-16.3

    LSB-Analog-Input-Module-16Input-Value 3

    *6) 88, 89 unsigned int 0000 03E7 LSB-AnalogInput-Module-16.4

    LSB-Analog-Input-Module-16Input-Value 4

    *6) 90,91 unsigned int 0000 FFFF LSB-DigitalInput-Module-1-3-13-14

    Bit 0 ... 3: LSB-Digital-Input-Module-1Bit 4 ... 7: LSB-Digital-Input-Module-3Bit 8 ... 11: LSB-Digital-Input-Module-13Bit 12 ...15: LSB-Digital-Input-Module-14

    *6) 92 unsigned char

    00.... FF Modbus-Register-1...8 Handshake-IN

    Modbus-Register Handshake-IN:Bit 0: ModbusReg-1-Data Valid...Bit 7: ModbusReg-8-DataValid

    *6) 93 unsigned char

    00.... FF NEMS-Device-Status() Bit 0: Device 1 (0 => Offline, 1 => On)...Bit 7: Device 8 (0 => Offline, 1=> On)

    *6) 94 unsigned char

    NEMS-Hand-shake-IN

    NEMS-Handshake-IN NEMS-handshake-INBit 0: NewData (new Message)Bit 1: DeviceNrRead (DeviceNr read)Bit 2: InputStatusValid (InputStatus 2.0 is valid)

    *6) 95 unsigned char

    00.... FF NEMS-MessageInfo NEMS-MessageInfo-Bits:Bit 0: reserved Bit 1: TimeStamp valid = 1 / not valid = 0Bit 2: Input unstable = 1 / stable = 0Bit 3: Not confirmed = 1 / confirmed = 0Bit 4: Link-Input = 1 / Not a Link-Input = 0Bit 5: FirstValue = 1 / NewValue = 0Bit 6: Arrived = 1 / Gone = 0Bit 7: Process signal = 1 / Fault signal = 0

    *6) 96, 97 unsigned int 0001 .... 0400 NEMS-Message-Num Message-Number 1...1024

    *6) 98 BCD 01 . 31 NEMS-Day Message-Time-Stamp Day

    *6) 99 BCD 01 . 12 NEMS-Month Message-Time-Stamp-Month

    *6) 100 BCD 00 . 99 NEMS-Year Message-Time-Stamp-Year

    *6) 101 BCD 00 . 23 NEMS-Hour Message-Time-Stamp-Hour

    *6) 102 BCD 00 . 59 NEMS-Minute Message-Time-Stamp-Minute

    *6) 103 BCD 00 . 59 NEMS-Second Message-Time-Stamp-Second

    *6) 104, 105

    unsigned int 0000 . 03E7 NEMS-Millisecond Message-Time-Stamp-Millisecond

    Outputbytes

    Data Type Value Range(hex)

    Definition Description23

  • 6 Output Data*6) 106, 107

    unsigned int 0000 . FFFF NEMS-Input-Status2 Status2 of Inputs 1-16(Bit 0: Inp.1...Bit 15: Inp.16) of Device-Num. x (selected in Input-Byte 67)

    *6) 108, 109

    unsigned int 0000 . FFFF NEMS-Input-Status1 Status1 of Inputs 1-16(Bit 0: Inp.1...Bit 15: Inp.16) of Device-Num. x (selected in Input-Byte 67)

    *6) 110, 111

    unsigned int 0000 . FFFF NEMS-Input-Status() Status0 of Inputs 1-16(Bit 0: Inp.1...Bit 15:Inp.16) of Device-Num. x (selected in Input-Byte 67)

    Outputbytes

    Data Type Value Range(hex)

    Definition Description24

  • 6 Output Data6.2 Internal Load

    6.2.1 Internal Load Output Bytes 0-1

    Fig. 6-1 data stream of the internal firing rate

    The output bytes 0 and 1output the load value in.%. 0% corresponds to base load and 100% corresponds to full load.

    6.2.2 Controller Actual Value Output Bytes 2-3

    Fig. 6-2 data stream of the internal load

    The output bytes 2 and 3In d output the controllers actual value (boiler temperature). The unit of the output value depends on the settings of parameter 809:

    Input bytes 2, 3 (p. ex. in digit)

    Value HEX Value% Description

    0000 0% base load

    0064 100% full load

    Parameter 809 = 0 digit= 1 C= 2 bar

    Value HEX Value digit

    0000 0 min.

    03E7 999 max.25

  • 6 Output Data6.2.3 Actual Value Channel 1-5 Output Bytes 4-13

    Fig. 6-3 Data flow of the internal load

    The actual percentage value of the channels 1... 5 is given in the output bytes 4.... 13. Here, 0% corresponds to the lower area limit and 100% to the upper area limit for DPS out-puts. It depends on the configuration for upstream outputs (see table).Output bytes 4.... 13

    Output bytes

    Chan-nel

    Value HEX

    Value% TPS-Output Continuous Output

    0...20 mA 0...20 mA

    4,5 1 0000 0 lower 0mA 4mA

    4,5 1 0064 999 upper 20mA 20mA

    6,7 2 0000 0 lower 0mA 4mA

    6,7 2 0064 999 upper 20mA 20mA

    8,9 3 0000 0 lower 0mA 4mA

    8,9 3 0064 999 upper 20mA 20mA

    10,11 4 0000 0 lower 0mA 4mA

    10,11 4 0064 999 upper 20mA 20mA

    12,13 5 0000 0 lower 0mA 4mA

    12,13 5 0064 999 upper 20mA 20mA26

  • 6 Output Data6.3 Display

    6.3.1 Fault Codes Bytes 14-15

    Fig. 6-4 Data flow of the internal load

    The current or last fault code is displayed in the output bytes 14 and 15. A distinction is made to whether the fault code is given by the main processor or from the watchdog processor as follows.10000 was added to the fault code when given by the main processor.

    A pending fault is shown by the operation mode (AB 16,17) in bit 9 (0x0200).

    6.3.2 Operating Modes Output Bytes 16-17

    Operating Modes bytes 16,17

    Fig. 6-5 Data flow of the internal load

    The output bytes 16 and 17 show the operating mode of the connected device.The operating modes are coded by bit pattern.

    Fault code Error message Processor

    211 H211 Main processor fault no. 211

    10211 U211 Watchdog processor fault no. 211

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 HEX Description

    X 0x0001 Power ONX 0x0002 OFF

    X 0x0004 ReadyX 0x0008 Pre ventilation

    X 0x0010 Start to move to igni-tion position

    X 0x0020 IgnitionX 0x0040 Base load

    X 0x0080 Control / regulateX 0x0100 Post ventilation

    X 0x0200 FaultX 0x0300 reserved

    X 0x0400 reservedX 0x1000 O2 Setting

    X 0x2000 ParameterisationX 0x4000 Setting27

    X 0x8000 Clear memory

  • 6 Output DataBit-no. 10-15 are to take out. These bits are used for representation of sub-modes(i.e.: Adjustment).You must highlight the relevant bits when you analyse the read data. This prevents customers to use a new version without any changes by the customer after LAMTEC has enhanced func-tionality. You must set all bits to ZEROS equivalently.

    6.4 Direct Register

    Fig. 6-6 Direct register data flow

    6.4.1 RegisterNo. Output Bytes 18-19

    If a register is read in via the input data, the register number that has been read in appears in the output bytes 18 and 19 as an answer. This output must now be compared to the number read in. Only once the value output corresponds to the register number entered does the reg-ister value in the output bytes 20 and 21 also correspond to the desired contents.The respective processes are carried out asynchronously. For this reason, it can take some time until the corresponding response is transferred (see also description of the input bytes 10 and 11).Extract from the register table of the FMS/VMS/ETAMATIC

    Decimal register no. Hexadecimal register no.

    Designation Description

    30075 757B uiDigitalIn Digital input signals

    30105 7599 ucAktBrennstoff Current curve set selection 07

    30122 75AA Akt_sollwert Burner firing rate controller setpoint

    50100 C3B4 uiFlammIntensitaet Flame intensity

    30004 7534 uiKorrSollwertK1 Channel 1 setpoint

    30010 753A uiKorrSollwertK2 Channel 2 setpoint

    30016 7540 uiKorrSollwertK3 Channel 3 setpoint

    30022 7546 uiKorrSollwertK3 Channel 4 setpoint

    30028 754C uiKorrSollwertK5 Channel 5 setpoint28

  • 6 Output Data6.4.2 Register Value Output Bytes 20-21

    In the output bytes 20 and 21, the content for the register numbers given in the output bytes 18 and 19 is displayed.

    WARNING!For safety reasons, you must check the following:The register number of the requested number must also be contained in the output bytes 18 and 19. Only then does the register value in the output bytes 20 and 21 also correspond to the contents of the desired register.

    6.5 UserDiagnose Bytes 22-23

    Fig. 6-7 Data flow of the internal load

    In the output bytes. 22 and 23 is shown if the communication between the communications processor and the device (FMS / VMS / ETAMATIC / FA1) is functioning. If no communication is possible between the components, this is displayed with the value 0x0000 in this field. If communication is functional, the value 0x0001 is displayed in this field.Output bytes 22, 23

    6.6 O2-Setpoint Bytes 24-25

    see chapter 6.8.1 O2-Setpoint Output Bytes 24-25

    Value (HEX) Communication

    0x000 No

    0x001 Yes29

  • 6 Output Data6.7 Digital Outputs Bytes 26-27

    Fig. 6-8 Data flow of the internal load

    In the output bytes 26 and 27, the digital outputs from the devices are given in bit-coded form.(output-bytes 26, 27)

    Source of bit 10 0x0200 (ignition position reached) Logic AND from KPR_uiSynchron:

    Source of Bit 11 0x0400 (high fire position reached) Logic AND from KPR_uiSynchron:

    Source of Bit 12 0x0800 (manual operation) Logic OR from KPR_uiAcHandmodus:

    13 12 11 10 9 8 7 6 5 4 3 2 1 0 HEX Description

    X 0x0001 Oil valveX 0x0002 Ignition valve

    X 0x0004 OIL / GASX 0x0008 Pre-ventilation finished

    X 0x0010 Gas valve 1X 0x0020 Ignition transformer

    X 0x0040 Gas valve 2X 0x0080 Fault relay

    X 0x0100 Fan ONX 0x0200 Ignition position reached

    X 0x0400 High fire position reachedX 0x0800 Manual given load

    X 0x1000 Curve set changingX 0x2000 Mixed combustion relays

    PQ_ZP_HP 0x0001PQ_ZP_UE 0x0002

    PQ_GL_HP 0x0004PQ_GL_UE 0x0008

    0x0001 Compound regulator adjustment via front plate0x0002 O2 adjustment via front plate0x0004 Given load under control mode operation via front plate0x0100 Given load for compound regulator adjustment by Remote Software0x0200 Given load for O2 adjustment by Remote Software0x0400 External manual given load0x0800 External manual given load0x1000 Manual given load under control mode operation by Remote Software30

  • 6 Output DataOutput-bytes 26, 27 VMS

    Source of bit 10 0x0200 (ignition position reached) Logic AND from KPR_uiSynchron:

    Source of Bit 11 0x0400 (high fire position reached) Logic AND from KPR_uiSynchron:

    Source of Bit 12 0x0800 (manual operation) Logic OR from KPR_uiAcHandmodus:

    13 12 11 10 9 8 7 6 5 4 3 2 1 0 HEX Description

    X 0x0001 Ignition position HPX 0x0002 Fault HP

    X 0x0004 Mixed combustion Fuel A releaseX 0x0008 Mixed combustion Gas release

    X 0x0010 Fault PX 0x0020 High fire position reached

    X 0x0040 Ignition position PX 0x0080 Mixed-combustion oil release

    X 0x0100 Burner ONX 0x0200 Ignition position reached

    X 0x0400 High fire position reachedX 0x0800 Manual given load

    X 0x1000 Curve set changingX 0x2000 Mixed-combustion relays

    PQ_ZP_HP 0x0001 Ignition position main processor (HP) reachedPQ_ZP_UE 0x0002 Ignition position watchdog processor (P) reached

    PQ_GL_HP 0x0004 High fire position main processor reachedPQ_GL_UE 0x0008 High fire position watchdog processor reached

    0x0001 Compound regulator adjustment via front plate0x0002 O2 adjustment via front plate0x0004 Given load under control mode operation via front plate0x0100 Given load for compound regulator adjustment by Remote Software0x0200 Given load for O2 adjustment by Remote Software0x0400 External manual given load0x0800 External manual given load0x1000 Manual given load under control mode operation by Remote Software31

  • 6 Output DataOutput-bytes 26, 27 ETAMATIC

    Source of bit 10 0x0200 (ignition position reached) Logic AND from KPR_uiSynchron:

    Source of Bit 11 0x0400 (high fire position reached) Logic AND from KPR_uiSynchron:

    Source of Bit 12 0x0800 (manual operation) Logic OR from KPR_uiAcHandmodus:

    13 12 11 10 9 8 7 6 5 4 3 2 1 0 HEX Description

    X 0x0001 Oil valveX 0x0002 Ignition valve

    X 0x0004 OIL / GASX 0x0008 Pre-ventilation finished

    X 0x0010 Gas valve 1X 0x0020 Ignition transformer

    X 0x0040 Gas valve 2X 0x0080 Fault relay

    X 0x0100 Fan ONX 0x0200 Ignition position reached

    X 0x0400 High fire position reachedX 0x0800 Manual given load

    X 0x1000 Curve set changingX 0x2000 reserved

    PQ_ZP_HP 0x0001 Ignition position main processor (HP) reachedPQ_ZP_UE 0x0002 Ignition position watchdog processor (P) reached

    PQ_GL_HP 0x0004 High fire position main processor reachedPQ_GL_UE 0x0008 High fire position watchdog processor reached

    0x0001 Compound regulator adjustment via front plate0x0002 O2 adjustment via front plate0x0004 Given load under control mode operation via front plate0x0100 Given load for compound regulator adjustment by Remote Software0x0200 Given load for O2 adjustment by Remote Software0x0400 External manual given load0x0800 External manual given load0x1000 Manual given load under control mode operation by Remote Software32

  • 6 Output Data6.8 Oxygen O2

    6.8.1 O2-Setpoint Output Bytes 24-25

    Fig. 6-9 Data flow of the internal load

    In the output bytes 24, 25, the O2 setpoint of the devices is displayed in tenths of a percent if an O2 controller is active.Output bytes 24, 25

    6.8.2 O2-Actual Value Output Bytes 28-29

    Fig. 6-10 Data flow of the internal load

    In the output bytes 28, 29, the O2 setpoint of the devices is displayed in 1/100ths of a percent if an O2 controller is active.From communications processor vers. K2p001 from 24/08/01 and DMD file 663P7N01.gsd

    NOTICE!The O2 setpoint must be initialised by the O2 analyser on the LSB (LAMTEC SYSTEM BUS). The O2 setpoint is read by the FMS/VMS/ETAMATIC, however it is not initialised.

    6.8.3 O2-Measured Value

    Fig. 6-11 Data flow of the internal load

    O2 measured value in 1/10 percentThese values are only available if an O2 analyser (LT1 or LT2) is connected via LAMTEC SYS-TEM BUS. The meaning of some values differs depending on whether and LT1 or LT2 is con-nected.

    Value (%) Value (hex) Description

    0 0000 min

    2091 0001 20.9 vol.% O2999 03E7 max.33

  • 6 Output Data6.9 Register

    Fig. 6-12 Data flow of indirectly addressable registers

    6.9.1 Value 1 Output Bytes 30-31

    If a register number is entered into the output bytes 16.... 35, then the values from the corre-sponding registers are given here, in output bytes 30... 49.

    6.9.2 Value 2 Bytes 32-33

    see chapter 6.9.1 Value 1 Output Bytes 30-31

    6.9.3 Value 3 Bytes 34-35

    see chapter 6.9.1 Value 1 Output Bytes 30-31

    6.9.4 Value 4 Bytes 36-37

    see chapter 6.9.1 Value 1 Output Bytes 30-31

    6.9.5 Value 5 Bytes 38-39

    see chapter 6.9.1 Value 1 Output Bytes 30-31

    6.9.6 Value 6 Bytes 40-41

    see chapter 6.9.1 Value 1 Output Bytes 30-31

    6.9.7 Value 7 Bytes 42-43

    see chapter 6.9.1 Value 1 Output Bytes 30-3134

  • 6 Output Data6.9.8 Value 8 Bytes 44-45

    see chapter 6.9.1 Value 1 Output Bytes 30-31

    6.9.9 Value 9 Bytes 46-47

    see chapter 6.9.1 Value 1 Output Bytes 30-31

    6.9.10 Value 10 Bytes 48-49

    see chapter 6.9.1 Value 1 Output Bytes 30-31

    6.9.11 Register 1-8 Handshake-IN Byte 92

    The validity bit for registers 1 to 8 is set in this byte.

    NOTICE!Here, up to 10 of the numerous indirectly addressable registers can be entered (for register list, see appendix A) and their contents can be read in the corresponding output data byte 30...49.35

  • 6 Output Data6.10 LT1/LT2

    Fig. 6-13 Data flow of the internal load

    6.10.1 O2-Measured Value LT1/LT2 Output Bytes 50-51

    see chapter 6.9.3 Value 3 Bytes 34-35

    6.10.2 Operating mode Bytes 52-53

    The operating mode of the LT1 will be displayed in output byte 52, 53. The operating mode is bit-coded, combinations of several bits are possible.

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 HEX Description

    X 0x0001 MeasurementX 0x0002 Calibration

    X 0x0004 MaintenanceX 0x0008 Heating active

    X 0x0010 Cold startX 0x0020 Standby

    X 0x0040 At least one warning active

    X 0x0080 At least one fault activeX 0x0100 Manual calibration active

    X 0x0200 reservedX 0x0400 reserved

    X 0x0800 reservedX 0x1000 Limit value 1 active

    X 0x2000 Limit value 2 activeX 0x4000 Limit value 3 active

    X 0x8000 Limit value 4 active36

  • 6 Output DataThe operating mode of the LT2 will be displayed in output byte 52, 53. The operating mode is bit-coded, combinations of several set bits are possible.

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 HEX Description

    X 0x0001 Measurement X 0x0002 Calibration

    X 0x0004 MaintenanceX 0x0008 reserved

    X 0x0010 Cold startX 0x0020 Standby

    X 0x0040 At least one warning active

    X 0x0080 At least one fault activeX 0x0100 reserved

    X 0x0200 reservedX 0x0400 reserved

    X 0x0800 reservedX 0x1000 Limit value 1 active

    X 0x2000 Limit value 2 activeX 0x4000 Limit value 3 active

    X 0x8000 Limit value 4 active37

  • 6 Output Data6.10.3 Faults Bytes 54-55

    The faults are bit-coded, combination of several set bits are possible.

    * Parameter 51 can be used to read-out the probe current at the last calibration.Output bytes 54 and 56 display LT errors. The faults are bit-coded, combinations of several sets are possible.

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 HEX Description

    0x0000 No warning / fault active

    X 0x0001 Probe defectiveX 0x0002 Flow throughput to low Is <

    200 mA

    X 0x0004 Failure vacuum pressure (measuring gas pump)

    X 0x0008 Defective probe heaterX 0x0010 Probe broken wire

    X 0x0020 Current input of pump too high

    X 0x0040 Probe: no constant current (dI/dT is not small enough)

    X 0x0080 Fault test gas (check with test gas failed)

    X 0x0100 Probe dynamic is missingX 0x0200 Dirty pre-filter (sintered metal

    preliminary filter dirty)

    X 0x0400 Error analog outputX 0x0800 Error parameters

    X 0x1000 Error analog inputsX 0x2000 Error O2-controller (see

    parameter 4002)

    X 0x4000 provided for expansionsX 0x8000 provided for expansions

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 HEX Description

    X 0x0001 Probe voltage

  • 6 Output Data6.10.4 Warning Bytes 56-59

    The warnings of the LT1 will be displayed in the output bytes 56, 57 and in the output bytes 58, 59. The warnings are bit-coded, combinations of several bits are possible.Output-bytes 56, 57 (Warnings 1-16)

    *at the probe current, at the last calibration** Option in course of preparation

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 HEX Description

    0x0000 No warning

    X 0x0001 Probe heating control defec-tive, heating with fixed volt-age

    X 0x0002 Dirty pre-filter-heating (filter SEA blocked)

    X 0x0004 Flow throughput too low, Is must be replaced

    X 0x0010 Leakage of flue gas pipingX 0x0020 Defective MEV-heating

    X 0x0040 Defective pre-filter heatingX 0x0080 n.n.

    X 0x0100 Pressure at measuring point outside the permissible range (too high/too low)

    X 0x0200 Temperature at measuring point outside the permissible range (too high/too low)

    X 0x0400 Error analogue outputX 0x0800 Parameter error

    X 0x1000 Error analogue inputX 0x2000 Error O2-controller (see

    parameter 4002)

    X 0x4000 Probe current limit activeX 0x8000 Line voltage too high or too

    low39

  • 6 Output DataOutput-bytes 58, 59 (Warnings 17-32)

    6.10.5 Absolute Pressure LT1 or Inner Resistance Probe LT2 bytes 60-61

    6.10.6 Application specific measured value bytes 62-69

    Special measured value in the Lambda transmitter, which is freely configurable.The measured value is given on the display.Four measured values can be freely configured

    NOTICE!These values are only available if an O2 analyser (LT1 or LT2) is connected via LAMTEC SYS-TEM BUS. The meaning of some values differs depending on whether and LT1 or LT2 is con-nected.

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 HEX Description

    X 0x0001 Running time definition of flue gas pump active, measuring value deviations possible

    X 0x0002 No constant probe current while calibration

    X 0x0004 Value of analogue input 1 too high/low

    X 0x0008 Value of analogue input 2 too high/low

    X 0x0010 Value of analogue input 3 too high/low

    X 0x0020 Value of analogue input 4 too high/low

    X 0x0040 Configuration error analogue outputs

    X 0x0080 Service warning 1X 0x0100 Service warning 2

    X 0x0200 Probe dynamic is missingX 0x0400 Probe dynamic test activated

    X 0x0800 reservedX 0x1000 reserved

    X 0x2000 reservedX 0x4000 reserved

    X 0x8000 reserved

    Bytes Description

    62, 63 Measured value 1

    64, 65 Measured value 2

    66, 67 Measured value 3

    68, 69 Measured value 440

  • 6 Output Data6.10.7 Reserve Output Bytes 70-77

    Bytes reserved for future LT expansions

    6.11 LSB-Module

    Fig. 6-14 data stream LSB module

    6.11.1 Status LSB-Output-Modules Output Byte 78

    Fig. 6-15 Data flow recognition of LSB module

    The master uses output byte 78 to recognise whether LSB analogue output modules 11 and 12 and the LSB digital output modules 6 and 7 on the LAMTEC SYSTEM BUS are connected.

    6.11.2 Status PID-Regulator-Digital-Outputs Output Bytes 78-80

    6 5 4 3 2 1 0 Description Address

    X Analogue output module 11 43X Analogue output module 12 47

    X Digital output module 6 23X Digital output module 7 2741

  • 6 Output Data6.12 LSB-Output Module

    6.12.1 Status LSB Module Output Byte 81

    Fig. 6-16 Data flow of the LSB Modules recognition

    The device master recognises with output byte 81, wether LSB analogue input modules 14, 15 and 16 and LSB digital input modules 1, 3, 13 and 14 are connected to LAMTEC SYSTEM BUS.

    6.12.2 Module 16 Bytes 82-89

    Fig. 6-17 LSB data flow - PROFIBUS

    Corresponding to this, the process with the values at analogue inputs 2,3 and 4 is as follows:

    This process provides 4 additional analogue inputs for the PROFIBUS master.

    7 6 5 4 3 2 1 0 Description Address

    X reservedX LSB-Analog-Input-Module 14 55

    X LSB-Analog-Input-Module 15 59X LSB-Analog-Input-Module 16 63

    X LSB-Digital-Input-Module 1 3X LSB-Digital-Input-Module 3 11

    X LSB-Digital-Input-Module 13 51X LSB-Digital-Input-Module 14 55

    Fig. 6-18 Current output

    The analogue value that is present at analogue input 1 of the LSB analogue input mode with the LSB address 63 is written in the out-put bytes 82 and 83 and then transferred to the PROFIBUS master.

    Analogue input Analogue output bytes

    1 82,83

    2 84,85

    3 86,87

    4 88,8942

  • 6 Output Data6.13 LSB Digital Input Modules

    Fig. 6-19 data stream LSB module

    6.13.1 Module 1-2-13-14

    The four Input-Bits of LSB-Digital-Input-Module-1 (LSB-Module-address 3) are sent to the Bits 0 ... 3 of this value.

    The four Input-Bits of LSB-Digital-Input-Module-3 (LSB-Module-address 11) are sent to the Bits 4 ... 7 of this value.

    The four Input-Bits of LSB-Digital-Input-Module-13 (LSB-Module-address 51) are sent to the Bits 8 ... 11 of this value.

    The four Input-Bits of LSB-Digital-Input-Module-14 (LSB-Module-address 55) are sent to the Bits 12 ... 15 of this value.

    6.13.2 Register Handshake_IN Output Byte 92

    see chapter 6.11 LSB-Module43

  • 6 Output Data6.14 NEMS

    Fig. 6-20 NEMS data flow

    6.14.1 Device Status Output Byte 93

    The device status is updated on an ongoing basis and displays which NEMS devices are ac-tive on the bus.

    6.14.2 Handshake IN Output Byte 94

    It shows all specified data of a new message and is updated via a handshaking from the com-munication processor. Handshaking-Flowchart for the Message-Window between communication processor (KP) and PROFIBUS-Master (PM):

    NOTICE!Time-out:A new message in the Message-Window (NewData = 1) must be read by the PROFIBUS-Master (PM) before 10 sec. have been passed, otherwise the possibly following messages are cleared in the NEMS-Devices, until this message is read by the PROFIBUS-Master (PM).

    Handshake Bit:NewData

    Handshake Bit:DataRead

    Source: KP (OB 94 Bit 0) Source: PM /(IB 67 Bit 4)

    0 0 Normal state(KP can write a new message into the Message-Window)

    1 0 KP has written a new Message into the Message-Window (Output bytes 95 ... 105) and sets then NewData = 1

    1 1 PM sets DataRead = 1

    0 1 PM reads the new message from the Message-Window (Out-put bytes 95 ... 105); KP sets NewData = 0

    0 0 When PM has read the complete message, then PM checks if NewData = 0 and if yes it sets DataRead = 044

  • 6 Output Data6.14.3 Indication Information Byte 95-105

    Here, all specified data of a new indication is displayed and updated by the communications processor by means of hand shaking.

    6.14.4 Input Status bytes 106-111

    If the Handshake-IN-Bit2 (InputStatusValid) is set, in the NEMS-Input-Status-Window the cur-rent status of the 16 NEMS-Inputs of the NEMS-Device (selected in Input byte 67) is shown with the following coding and is updated continuously:Coding of NEMS-Input-Status2...0 (bit 0: NEMS-Input 1...Bit 15: NEMS-Input 16):

    Example: NEMS-Input-Status2 = 0x0002, NEMS-Input-Status1 = 0x0000, NEMS-Input-Status0 = 0x0003: NEMS-Input1: Fault-State-Input is active NEMS-Input2: Process-State-Input is activeHandshaking-Flowchart for the NEMS-Input-Status-Window between communication processor (KP) and PROFIBUS-Master (PM):

    Handshake bit:DataRead

    96 Indication no.

    97 Indication no.

    98 Day

    99 Month

    100 Year

    101 Hour

    102 Minute

    103 Second

    104 Millisecond

    Output bytes Input Status

    106-107 Input-Status-2

    108-109 Input-Status-1

    110-111 Input-Status-0

    Status2 Bit x Status1 Bit x Status0 Bit x Status of the related NEMS-Input x

    0 0 0 Process-State-/Fault-State-Input is not active

    0 0 1 Fault-State-Input is active

    0 1 0 Input bypassed and Input is not active

    0 1 1 Input bypassed and Input is active

    1 0 0 Input unstable

    1 0 1 Process-State-Input is active

    1 1 0 reserved

    1 1 1 reserved45

  • 6 Output DataWARNING!The data in the NEMS-Input-Status-Window are only valid if:GerteNrRequest = 0 and GerteNrRead = 0 and InputStatusValid = 1, because only then the data in the NEMS-Input-Status-Window relate to the device which is selected in Input-Byte 67.If there are messages waiting in the Message-Window (New Data = 1), the InputStatusValid-Bit will be held to = 0, if this device is currently selected in Input-Byte 67, to guarantee the con-sistency of the data. The Handshake-Protocol is not time-dependent, this means that no waiting loops have to be inserted between the different states of the flowchart above.

    HandshakeBit:GerteNrRequest

    HandshakeBit:GerteNrRead

    HandshakeBit:InputStatusValid

    Statusof the related NEMS-Input x

    Source: PM IB 67 Bit 5 Source: KP OB 94 Bit 1 Source: KP OB 94 Bit 2

    0 0 1 Data in NEMS-Input-Status-Window are valid (Output bytes 106 ... 111)

    1 0 1 PM has selected a new device in Input-Byte 67 and sets then DeviceNrRequest = 1

    1 1 0 KP sets InputStatusValid = 0KP reads new Device-Num. from Input-Byte 67 and sets then DeviceNumRead = 1

    0 1 0 PM wait till DeviceNumRead = 1 and sets then DeviceNrRequest = 0

    0 0 0 KP sets DeviceNum.Read = 0

    0 0 1 Data in NEMS-Input-Status-Window are validKP writes continuously the current NEMS-Input-Status (of the device selected in Input-Byte 67) into the Out-put bytes 106...11146

  • 7 Input Data7 Input Data

    7.1 Overview

    7.1.1 Input Data Table

    NOTICE!The PROFIBUS master sends the input data to FMS/VMS/ ETAMATIC. All unused bit items must be filled with zeros to enable compatibility with new versions of firmware.

    Fig. 7-1 Burner control unit data flow entry

    Input-Bytes Data-Type Value Range(Hexadecimal)

    Definition Description

    0, 1 unsigned int 0000.... 00FF Control word marking of these values which will be transmit-ted to the FMS/VMS/ETAMATIC respectively for what these are used

    2, 3 unsigned int 0000.... 03E7 Analog-Value1 see following explanation below

    4, 5 unsigned int 0000.... 03E7 Analog-Value2 see following explanation below

    6, 7 unsigned int 0000.... 00FF DigitalControl word marking of relevant bits of the digital inputs

    8, 9 unsigned int 0000.... 00FF DigitalInputs definition of the non safety relevant input ter-minals via the Bus

    10, 11 unsigned int 2710.... FFFF RegisterNo to read and write the FMS/VMS/ETAMATIC-register variables with register no.xxxx

    12, 13 unsigned int 0000.... FFFF reserved

    *2) 14, 15 unsigned int 0000 . FFFF DigitalInputs-2 Curve set selection and FAT_Standby etc.

    *3) 16, 17 unsigned int 0000 . 20CF Modbus-RegisterNo.1 Modbus-Register-Value 1 output, in output data bytes 30, 31 (see Appendix A)

    *3) 18, 19 unsigned int 0000 . 20CF Modbus-RegisterNo.2 Modbus-Register-Value 2 output, in output data bytes 32, 33 (see Appendix A)

    *3) 20, 21 unsigned int 0000 . 20CF Modbus-RegisterNo.3 Modbus-Register-Value 3 output, in output data bytes 34, 35 (see Appendix A)

    *3) 22, 23 unsigned int 0000 . 20CF Modbus-RegisterNo.4 Modbus-Register-Value 4 output, in output data bytes 36, 37 (see Appendix A)

    *3) 24, 25 unsigned int 0000 . 20CF Modbus-RegisterNo.5 Modbus-Register-Value 5 output, in output data bytes 38, 39 (see Appendix A)

    *3) 26,27 unsigned int 0000 . 20CF Modbus-RegisterNo.6 Modbus-Register-Value 6 output, in output data bytes 40, 41 (see Appendix A)

    *3) 28,29 unsigned int 0000 . 20CF Modbus-RegisterNo.7 Modbus-Register-Value 7 output, in output data bytes 42, 43 (see Appendix A)

    *3) 30, 31 unsigned int 0000 . 20CF Modbus-RegisterNo.8 Modbus-Register-Value 8 output, in output data bytes 44, 45 (see Appendix A)47

  • 7 Input Data*3) 32,33 unsigned int 0000 . 20CF Modbus-RegisterNo.9 Modbus-Register-Value 9 output, in output data bytes 46, 47 (see Appendix A)

    *3) 34, 35 unsigned int 0000 . 20CF Modbus-RegisterNo.10 Modbus-Register-Value 10 output, in output data bytes 48, 49 (see Appendix A)

    *6) 36, 37 unsigned int 0000.... 03E7 Analog-Value3 see description below

    *6) 38, 39 unsigned int 0000.... 03E7 Analog-Value4 see description below*6) 40, 41 unsigned int 0000.... 03E7 LSB-Analog-Output-

    Module-11.1LSB-Analog-Output-Module-11Output 1

    *6) 42, 43 unsigned int 0000.... 03E7 LSB-Analog-Output-Module-11.2

    LSB-Analog-Output-Module-11Output 2

    *6) 44, 45 unsigned int 0000.... 03E7 LSB-Analog-Output-Module-11.3

    LSB-Analog-Output-Module-11Output 3

    *6) 46, 47 unsigned int 0000.... 03E7 LSB-Analog-Output-Module-11.4

    LSB-Analog-Output-Module-11Output 4

    *6) 48, 49 unsigned int 0000.... 03E7 LSB-Analog-Output-Module-12.1

    LSB-Analog-Output-Module-12Output 1

    *6) 50, 51 unsigned int 0000.... 03E7 LSB-Analog-Output-Module-12.2

    LSB-Analog-Output-Module-12Output 2

    *6) 52, 53 unsigned int 0000.... 03E7 LSB-Analog-Output-Module-12.3

    LSB-Analog-Output-Module-12Output 3

    *6) 54, 55 unsigned int 0000.... 03E7 LSB-Analog-Output-Module-12.4

    LSB-Analog-Output-Module-12Output 4

    *6) 56 unsigned char 00.... FF LSB-Digital-Output-Module-6 and -7

    Bit 0 ... 3: LSB-Digital-Output-Module-6Bit 4 ... 7: LSB-Digital-Output-Module-7

    *6) 57 unsigned char 00.... FF **) PID-Regulator-Dig-ital-Outputs

    see description below

    *6) 58, 59 unsigned int 0000.... 03E7 **) PID-Regulator-Anal-ogOutput-1

    see description below

    *6) 60, 61 unsigned int 0000.... 03E7 **) PID-Regulator-Anal-ogOutput-2

    see description below

    *6) 62, 63 unsigned int 0000.... 03E7 **) PID-Regulator-Anal-ogOutput-3

    see description below

    *6) 64, 65 unsigned int 0000.... 03E7 **) PID-Regulator-Anal-ogOutput-4

    see description below

    *6) 66 unsigned char 00.... FF Modbus-Register-1 ... 8 Handshake-OUT

    Modbus-Register Handshake-OUT:Bit 0: ModbusReg-1-Request...Bit 7: ModbusReg-8-Request

    *6) 67 unsigned char 01.... 38 NEMS-Handshake-Out and NEMS-Device-Num. from Inputstatus Window

    NEMS-Device-Num. from Inputstatus-Win-dowsBit 0 ... 3: NEMS-Device-Num. 1 ... 8NEMS-Device-Num. selection of Input-Status in NEMS-Input-Status-Window.NEMS-Handshake-Out:Bit 4: DataRead (new Message reading)Bit 5: DeviceNumRequest (NEMS-Input-Sta-tus Request of another DeviceNum.)

    Input-Bytes Data-Type Value Range(Hexadecimal)

    Definition Description48

  • 7 Input Data*6) 68, 69 unsigned char 0000.... FFFF NEMS-Relais 1 ... 16 Bit 0: NEMS-Relays 1 DeviceNo. 1 Family 1Bit 1: NEMS-Relays 2 DeviceNo. 1 Family 1Bit 2: NEMS-Relays 1 DeviceNo. 2 Family 1Bit 3: NEMS-Relays 2 DeviceNo. 2 Family 1Bit 4: NEMS-Relays 1 DeviceNo. 3 Family 1Bit 5: NEMS-Relays 2 DeviceNo. 3 Family 1Bit 6: NEMS-Relays 1 DeviceNo. 4 Family 1Bit 7: NEMS-Relays 2 DeviceNo. 4 Family 1Bit 8: NEMS-Relays 1 DeviceNo. 5 Family 1Bit 9: NEMS-Relays 2 DeviceNo. 5 Family 1Bit 10: NEMS-Relays 1 DeviceNo. 6 Family 1Bit 11: NEMS-Relays 2 DeviceNo. 6 Family 1Bit 12: NEMS-Relays 1 DeviceNo. 7 Family 1Bit 13: NEMS-Relays 2 DeviceNo. 7 Family 1Bit 14: NEMS-Relays 1 DeviceNo. 8 Family 1Bit 15: NEMS-Relays 2 DeviceNo. 8 Family 1

    *6) 70 BCD 01.... 31 LSB-Time setting NEMS-Day in BCDNEMS-Month in BCDNEMS-Year in BCDNEMS-Hour in BCDNEMS-Minute in BCDNEMS-Second in BCD

    Input-Bytes Data-Type Value Range(Hexadecimal)

    Definition Description49

  • 7 Input Data7.2 Controlword

    Fig. 7-2 Input of the burner control device

    7.2.1 Controlword Bytes 0-1

    The bit-orientated controlword defines, which of the input values are sent to FMS/VMS/ETA-MATIC. The values of the input bytes are read and transferred not before the corresponding bit is set.Control word (bytes 0, 1)

    Bit 3 and Bit 11-15 are currently not in used (reserved)

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

    X X X X X X X X X X

    Bit Value (HEX) Description EB

    0 0001 Analogvalue1, will be transmitted to FMS/VMS/ETAMATIC 2, 3

    1 0002 Analogvalue2, will be transmitted to FMS/VMS/ETAMATIC 4, 5

    2 0004 The value of the variable RegisterNo, will be transmitted to FMS/VMS/ETAMATIC

    10, 11

    3 0008 reserved

    4 0010 The evaluation of bit 0...3 in DigitalInput2 (Input bytes 14, 15):- curve sets 1...4 will be transmitted to FMS/VMS/ETAMATIC

    14, 15

    5 0020 The evaluation of bit 4...7 in DigitalInput2 (Input bytes 14, 15):- curve sets 5...8 will be transmitted to FMS/VMS/ETAMATIC

    14, 15

    6 0040 The evaluation of bit 8...11 of DigitalInput2 (Input bytes 14, 15):- O2-Controller ON/OFF- CO-Controller ON/OFF- Oil pump ON/OFFare transferred to the FMS/VMS.

    14, 15

    7 0080 The evaluation of bit 8...11 of DigitalInput2 (Input bytes 14, 15):- FAT_Standby- FAT_Continuous ventilatingare transferred to the FMS or- VMS Continuous ventilatingare transferred to the VMS

    14, 15

    8 0100 Analogvalue3, will be transmitted to FMS/VMS/ETAMATIC 36, 37

    9 0200 Analogvalue4, will be transmitted to FMS/VMS/ETAMATIC 38, 39

    10 0400 The edge 0 -> 1 will set the LSB-Time of the Inputbytes 58...63 as new LSB-System-Time, see description below

    70....75

    11 0800 reserved

    12 1000 reserved

    13 2000 reserved

    14 4000 reserved

    15 8000 reserved50

  • 7 Input DataExample:The following information is to be transferred:Analogue value -1Analogue value -2Register variable with device register no.

    The hexadecimal value that is transferred in this example is 0113.

    7.3 Analogue value

    7.3.1 Analogue value 1-4

    Fig. 7-3 Data flow of analogue inputs

    Control word assignment (input byte 0, 1)

    Analogue value -1 (input bytes 2, 3)The content of these variables can be used an analogue input signal.In PROFIBUS Parameter 890, the value that is transferred to FMS/VMS/ETAMATIC is set:0 >> value off1 >> regular firing rate input2 >> predetermined outside temperature3 >> correction value 14 >> correction value 25 >> mixing signal for mixed combustionThis value is then used at the FMS/VMS/ETAMATIC instead of the signal at the input terminal.Analogue value -2 (input bytes 4, 5)The content of these variables can be used an analogue input signal.In PROFIBUS Parameter 891, the value that is transferred to FMS/VMS/ETAMATIC is set:0 >> value off1 >> regular firing rate input

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

    X X X X

    Bit Value (HEX) Description

    0 0001 Analogue value -1 is transferred

    1 0002 Analogue value -2 is transferred

    4 0010 The curve sets 1...4 are transferred

    8 0100 Analogue value 3 is transferred

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

    X X X X

    Bit Value (HEX) Description

    0 0001 Analogue value -1 is transferred

    1 0002 Analogue value -2 is transferred

    8 0100 Analogue value -3 is transferred

    9 0200 Analogue value -4 is transferred51

    2 >> predetermined outside temperature

  • 7 Input Data3 >> correction value 14 >> correction value 25 >> mixing signal for mixed combustionThis value is then used at the FMS/VMS/ETAMATIC instead of the signal at the input terminal.Analogue value -3 (input bytes 36, 37)The content of these variables can be used an analogue input signal.In PROFIBUS Parameter 892, the value that is transferred to FMS/VMS/ETAMATIC is set:0 >> value off1 >> regular firing rate input2 >> predetermined outside temperature3 >> correction value 14 >> correction value 25 >> mixing signal for mixed combustionThis value is then used at the FMS/VMS/ETAMATIC instead of the signal at the input terminal.Analogue value -4 (input bytes 38, 39)The content of these variables can be used an analogue input signal.In PROFIBUS Parameter 893, the value that is transferred to FMS/VMS/ETAMATIC is set:0 >> value off1 >> regular firing rate input2 >> predetermined outside temperature3 >> correction value 14 >> correction value 25 >> mixing signal for mixed combustionThis value is then used at the FMS/VMS/ETAMATIC instead of the signal at the input terminal.

    NOTICE!If the FMS/VMS/ETAMATIC is set up in such a way that several analogue values are used for the same analogue value, the further identical analogue values are automatically ignored

    NOTICE!The analogue values 3 and 4 are only available from the following versions:Communications processor version K4w001 15.05.04 and DMD file 663P7N06.gsdLT1 from version 4V24, LT2 from Version IV30aFMS/VMS/ETAMATIC from version 4.10052

  • 7 Input Data7.4 Digital Inputs

    Fig. 7-4 Input of the burner control device

    7.4.1 Digital Controlword (input-bytes 6-7)

    The bits of the digital inputs that are used (input bytes 8, 9) are defined using this word. The control word is coded along the same lines as the coding of the digital inputs.Example 1:Fault releasing is carried out by means of the bus connection.

    The hexadecimal value is 0004Bit 2 of the digital control word is set to "1".Now the value from bit 2 (here "1") of the digital input word (input bytes 8, 9) is read off.If the signal "0" is present at terminal "3" of the FMS, a fault release is triggered.Example 2:Die external ignition position acknowledgement, high firing rate acknowledgement, setpoint changeover and recirculation "ON" are to be given by the BUS:

    The hexadecimal value is 4C20The bits 5, 11 and 14 of the digital control word must be set to "1".Now the values from the bits 5, 11 and 14 (each "1" here) of the digital input words (input bytes 8, 9) are read off. The predefined actions can be carried out.

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

    X

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

    X X X53

  • 7 Input Data7.4.2 Digital Inputs 1 Bytes 8-9

    Digital Inputs ETAMATIC/ETAMATIC S (input bytes 8, 9)

    The input bytes 0, 6 and 11 are not used (reserved).

    NOTICE!If the bus presetting is marked with "No", it is an input with safety relevant functions. The pre-setting via BUS will be ignored. If the bus presetting is marked with "Yes", it is an input without safety relevant functions. If the terminal has a signal, the BUS presetting will be ignored (OR)

    NOTICE!Fault release is edge-triggered. Only a change from 0 to 1 triggers the fault release.

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

    X X X X X X X X X X X X X

    Position (bit-no.)

    Bit pattern (HEX)

    Terminal Input-no. FMS/ETAMATIC

    Description Trans-mission via BUS

    0 0001 reserved Yes

    1 0002 58 Burner "ON" Yes

    2 0004 57 Fault release Yes

    3 0008 56 Control release No

    4 0010 55 Safety interlock chain gas Yes

    5 0020 54 Recirculation "ON" */ pilot flame

    * If you want to control the pilot flame flame with terminal 54 and recirculation ON with PROFIBUS: Function : 788 set to 1 (pilot flame on terminal 54) 762 set to 1 setzen (recirculation ON via PROFIBUS)As long as the recirculation ON bit in PROFIBUS control word 6,7 is not set to 1, recirculation ON remains set to 1 internally.As soon as the recirculation On bit recirculation ON bit 0x0020 in PROFIBUS control word 6,7 is set, re-circulation can be spre-set in bit 0x0020 in PROFIBUS byte 8,9.You may not use this function in a security relevant context.

    Yes / No

    6 0040 reserved

    7 0080 53 Flame signal No

    8 0100 52 Safety interlock chain boiler No

    9 0200 51 Safety interlock chain oil No

    10 0400 50 Setpoint switching Yes

    11 0800 reserved

    12 1000 48 Air pressure monitor No

    13 2000 47 Gas pressure > min No

    14 4000 46 External ignition position acknowledge-ment

    Yes

    15 8000 49 Fuel selection Yes54

  • 7 Input DataDigital Inputs ETAMATIC OEM/ETAMATIC S OEM (input bytes 8, 9)

    The input bytes 0, 6 and 11 are not used (reserved).

    NOTICE!If the bus presetting is marked with "No", it is an input with safety relevant functions. The pre-setting via BUS will be ignored. If the bus presetting is marked with "Yes", it is an input without safety relevant functions. If the terminal has a signal, the BUS presetting will be ignored (OR)

    NOTICE!Fault release is edge-triggered. Only a change from 0 to 1 triggers the fault release.

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

    X X X X X X X X X X X X X

    Position (bit-no.)

    Bit pattern (HEX)

    Terminal Input-no. FMS/ETAMATIC

    Description Trans-mission via BUS

    0 0001 reserved

    1 0002 58 Burner "ON" Yes

    2 0004 57 Fault release Yes

    3 0008 56 Control release Yes

    4 0010 55 Safety interlock chain gas No

    5 0020 54 Gas pressure max / pilot flame No

    6 0040 reserved

    7 0080 53 Flame signal No

    8 0100 52 Safety interlock chain boiler No

    9 0200 51 Safety interlock chain oil No10 0400 50 Setpoint switching Yes

    11 0800 reserved

    12 1000 48 Air pressure monitor No

    13 2000 47 Gas pressure > min leakage test No

    14 4000 46 Oil pressure min atomiser air pressure No

    15 8000 49 Fuel selection Yes55

  • 7 Input DataDigital Inputs ETAMATIC V / ETAMATIC VS (input bytes 8, 9)

    The input bytes 0, 4, 6, 9 and 11....14 are not used (reserved).

    NOTICE!If the bus presetting is marked with "No", it is an input with safety relevant functions. The pre-setting via BUS will be ignored. If the bus presetting is marked with "Yes", it is an input without safety relevant functions. If the terminal has a signal, the BUS presetting will be ignored (OR)

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

    X X X X X X X X

    Position (bit-no.)

    Bit pattern (HEX)

    Terminal Input-no. FMS/ETAMATIC

    Description Trans-mission via BUS

    0 0001 reserved

    1 0002 58 Burner "ON" / boiler thermostat Yes

    2 0004 57 Pre-ventilation Yes

    3 0008 56 Control release Yes

    4 0010 reserved

    5 0020 54 Recirculation "ON" Yes

    6 0040 reserved

    7 0080 53 Flame signal No

    8 0100 52 Gas (curve set 1) Yes

    9 0200 reserved Yes

    10 0400 50 Setpoint switching Yes

    11 0800 reserved

    12 1000 reserved

    13 2000 reserved

    14 4000 reserved

    15 8000 49 Oil (curve set 2) Yes56

  • 7 Input DataDigital Inputs Burner Control FA1(input bytes 8, 9)

    The input bytes 0, 6 and 11 are not used (reserved).

    NOTICE!If the bus presetting is marked with "No", it is an input with safety relevant functions. The pre-setting via BUS will be ignored. If the bus presetting is marked with "Yes", it is an input without safety relevant functions. If the terminal has a signal, the BUS presetting will be ignored (OR)

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

    X X X X X X X X X X X X X

    Position (bit-no.)

    Bit pattern (HEX)

    Terminal Input-no. FMS/ETAMATIC

    Description Trans-mission via BUS

    0 0001 reserved

    1 0002 58 Burner "ON" / boiler thermostat Yes

    2 0004 57 Fault release Yes

    3 0008 56 Pre-ventilation suppression Yes

    4 0010 55 Safety interlock chain gas No

    5 0020 54 Gas pressure max No

    6 0040 reserved

    7 0080 53 Flame signal No

    8 0100 52 Safety interlock chain general No

    9 0200 51 Safety interlock chain oil No

    10 0400 50 Setpoint switching Yes

    11 0800 reserved

    12 1000 48 Air pressure monitor No

    13 2000 47 Gas pressure > min No

    14 4000 46 Oil pressure min / atomiser air pressure No

    15 8000 49 Fuel selection Yes 57

  • 7 Input DataDigital Inputs FMS (input-bytes 8, 9)

    NOTICE!If the bus presetting is marked with "No", it is an input with safety relevant functions. The pre-setting via BUS will be ignored. If the bus presetting is marked with "Yes", it is an input without safety relevant functions. If the terminal has a signal, the BUS presetting will be ignored (OR)

    NOTICE!Fault release is edge-triggered. Only a change from 0 to 1 triggers the fault release.

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

    X X X X X X X X X X X X X X X XX

    Position (bit-no.)

    Bit-pattern (HEX)

    Terminal Input no. FMS/ETAMATIC

    Description Trans-mission via BUS

    0 0001 1 Pre-ventilation rejection Yes

    1 0002 2 Burner "ON" Yes

    2 0004 3 Fault reset * Yes

    3 0008 4 Control release Yes

    4 0010 5 Safety interlock chain gas No

    5 0020 6 Recirculation "ON" / oil pressure > min Yes

    6 0040 7 Gas pressure < max / pilot flame No

    7 0080 8 Flame signal No

    8 0100 35 boiler safety interlock chain No

    9 0200 69 Safety interlock chain oil No

    10 0400 70 Setpoint switching Yes

    11 0800 71 Extern. high fire posit. acknowledgement Yes

    12 1000 72 Air pressure monitor No

    13 2000 73 Gas pressure < min No

    14 4000 74 Extern. ignition posit. acknowledgement Yes

    15 8000 75 Fuel selection Yes58

  • 7 Input DataDigital Inputs VMS (input-bytes 8, 9)

    NOTICE!If the bus presetting is marked with "No", it is an input with safety relevant functions. The pre-setting via BUS will be ignored. If the bus presetting is marked with "Yes", it is an input without safety relevant functions. If the terminal has a signal, the BUS presetting will be ignored (OR).

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

    X X X X X X X X X X X X X X X X

    Position (bit-no.)

    Bit-pattern (HEX)

    Terminal Input no. FMS/ETAMATIC

    Description Trans-mission via BUS

    0 0001 1 Curve set no. 6 Yes

    1 0002 2 Burner start up Yes

    2 0004 3 Pre ventilation Yes

    3 0008 4 Control release Yes

    4 0010 5 Curve set 3 Yes

    5 0020 6 Recirculation "ON" Yes

    6 0040 7 Curve set 1 Yes

    7 0080 8 Flame signal Yes

    8 0100 35 Curve set 2 Yes

    9 0200 69 Curve set 4 Yes

    10 0400 70 Setpoint switching Yes

    11 0800 71 Curve set 5 Yes

    12 1000 72 VMS Continuous ventilating Yes

    13 2000 73 Curve set 7 Yes

    14 4000 74 Curve set 8 Yes

    15 8000 75 ETAMATIC V curve set1 Yes 59

  • 7 Input Data7.4.3 Digital Inputs 2-Bytes 14-15

    Digital Inputs-2 ETAMATIC/ETAMATIC S (input bytes 14, 15)

    Presetting of the values (z. B. CO controller ON / OFF) has to be released in the bits 6 or 7 of the control word (input bytes 0, 1).The input bits 0.... 7 are used in FMS and VMS only for curve sets 1.... 8. The input bits 11, 14 and 15 are free (Reserve).

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

    X X X X X

    Position (bit-no.)

    Bit pattern (HEX)

    Description Trans-mission via BUS

    0 0001 reserved

    1 0002 reserved

    2 0004 reserved

    3 0008 reserved

    4 0010 reserved

    5 0020 reserved

    6 0040 reserved

    7 0080 reserved

    8 0100 O2-controller ON/OFF Yes

    9 0200 CO-controller ON/OFF Yes

    10 0400 Oil pump ON/OFF Yes

    11 0800 reserved

    12 1000 FAT-standby Yes

    13 2000 FAT-continuous ventilating Yes

    14 4000 reserved

    15 8000 reserved60

  • 7 Input DataDigital Inputs-2 FMS (input bytes 14, 15)

    With these values of bits 0....7 you may choose the curve sets. You may only choose one curve set. If you choose no curve set (all bits set to 0) or you choose more than one curve sets (more than one bit set to 1), a fault shut-down occurs when you start the burner.Contrary to the digital inputs in the input bytes 8 and 9, the input bits 0....7 have no correspond-ing control word.The presetting of the input bits 8....13 (e.g. CO controller ON / OFF) has to be released in the Bits 6 or 7 of the control word (input bytes 0, 1).The input bits 11, 14 and 15 are free (reserve).Curve set selection:If you select a curve set with the FMS, there must be the appropriate fuel selection via input terminal 75 or bit 15 in input bites 8,9 in parallel and at the same time.FMS verifies the selected curve set and the appropriate fuel selection with the fuel allocation in parameter 749. Is the selection not valid, a fault shutdown occurs on start of the burner.

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

    X X X X X X X X X X X X X

    Position (bit-no.)

    Bit pattern (HEX)

    Description Trans-mission via BUS

    0 0001 Curve set 1 Yes

    1 0002 Curve set 2 Yes

    2 0004 Curve set 3 Yes

    3 0008 Curve set 4 Yes

    4 0010 Curve set 5 Yes

    5 0020 Curve set 6 Yes

    6 0040 Curve set 7 Yes

    7 0080 Curve set 8 Yes

    8 0100 O2-controller ON/OFF Yes

    9 0200 CO-controller ON/OFF Yes

    10 0400 Oil pump ON/OFF Yes

    11 0800 reserved

    12 1000 FAT-standby Yes

    13 2000 FAT-continuous ventilating Yes

    14 4000 reserved

    15 8000 reserved61

  • 7 Input DataDigitalInputs-2 VMS (input bytes 14, 15)

    With these values of bits 0....7 you may choose the curve sets. You may only choose one curve set. If you choose no curve set (all bits set to 0) or you choose more than one curve sets (more than one bit set to 1), a fault shut-down occurs when you start the burner.Contrary to the digital inputs in the input bytes 8 and 9, the input bits 0....7have no correspond-ing control word.The presetting of the input bits 8....13 (e.g. CO controller ON / OFF) has to be released in the Bits 6 or 7 of the control word (input bytes 0, 1).The input bits 11, 14 and 15 are free (Reserve).Curve set selection:You may select the curve set in the VMS alternatively with the digital inputs in the input bytes 8 and 9. If you want to select the curve set with the digital input 2, all curve sets of the digital inputs (input byte 8, 9) must be deactivated in the bits of the control word (input byte 6, 7).The ambivalent selection of several curve sets causes a fault shutdown when the burner has started.

    15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

    X X X X X X X X X X X

    Position (bit-no.)

    Bit pattern (HEX)

    Description Trans-mission via BUS

    0 0001 Curve set 1 Yes

    1 0002 Curve set 2 Yes

    2 0004 Curve set 3 Yes

    3 0008 Curve set 4 Yes

    4 0010 Curve set 5 Yes

    5 0020 Curve set 6 Yes

    6 0040 Curve set 7 Yes

    7 0080 Curve set 8 Yes

    8 0100 O2-controller ON/OFF Yes

    9 0200 CO-controller ON/OFF Yes

    13 2000 FAT-continuous ventilating Yes62

  • 7 Input Data7.5 Access to Directly Addressed Register

    7.5.1 Register Number Bytes 10-11

    With indirectly addressed registers you can read a lot of different data out of the FMS/VMS/ETAMATIC. The update time will be longer as with direct data access and it has to be calcu-lated for the used register if necessary. These time will be very long, if different registers are read in multiplex operation. With PROFIBUS you can call different parameters or operating data from FMS/VMS/ETAMA-TIC. Therefor you must insert the appropriate register number in this field and you must set "Register control bit" (bit 2) in the control word (input bytes 0, 1) (refer to the following exam-ples).Therfore you must enter the corresponding register number in this field and you must set the bit RegisterNr-contro