balanced three-phase circuits osman parlaktuna osmangazi university eskisehir, turkey
TRANSCRIPT
BALANCED THREE-PHASE CIRCUITS
Osman ParlaktunaOsmangazi University
Eskisehir, TURKEY
Circuit Analysis II Spring 2005 Osman Parlaktuna
BALANCED THREE-PHASE VOLTAGES
A set of balanced three-phase voltages consists of three sinusoidalvoltages that have identical amplitudes and frequencies but are out ofphase with each other by exactly 1200. The phases are referred to as a, b, and c, and usually the a-phase is taken as the reference.
abc (positive) phase sequence: b-phase lags a-phase by 1200,and c-phase leads a-phase by 1200.
Va
Vc
Vb
V
V
V
a m
b m
c m
V
V
V
-120
+120
00
0
0
Circuit Analysis II Spring 2005 Osman Parlaktuna
acb (negative) phase sequence: b-phase leads a-phase by 1200,and c-phase lags a-phase by 1200.
Va
Vc
Vb
V
V
V
a m
b m
c m
V
V
V
+120
-120
00
0
0
Another important characteristic of a set of balanced three-phase voltages is that the sum of the voltages is zero.
V V Va b c 0
Circuit Analysis II Spring 2005 Osman Parlaktuna
THREE-PHASE VOLTAGE SOURCES
A three-phase voltage source is a generator with three separatewindings distributed around the periphery of the stator.
The rotor of the generator is an electro-magnet driven at synchronous speed bya prime mover. Rotation of the electro-magnet induces a sinusoidal voltagein each winding.The phase windings are designed so thatthe sinusoidal voltages induced in them are equal in amplitude and out of phasewith each other by 1200. The phase windings are stationary with respect tothe rotating electromagnet.
Circuit Analysis II Spring 2005 Osman Parlaktuna
There are two ways of interconnecting the separate phase windingsto form a 3-phase source: in either a wye (Y) or a delta ().
Circuit Analysis II Spring 2005 Osman Parlaktuna
ANALYSIS OF THE Y-Y CIRCUIT
V V V V V V VN N a n
A a ga
N b n
B b gb
N c n
C c gcZ Z Z Z Z Z Z Z Z Z0 1 1 1
0
Circuit Analysis II Spring 2005 Osman Parlaktuna
BALANCED THREE-PHASE CIRCUIT
The voltage sources form a set of balanced three-phase voltages, this means Va
,n, Vb
,n, Vc
,n are a set of
balanced three-phase voltages. The impedance of each phase of the voltage source
is the same: Zga=Zgb=Zgc. The impedance of each line conductor is the same:
Z1a=Z1b=Z1c. The impedance of each phase of the load is the
same: ZA=ZB=ZC
There is no restriction on the impedance of the neutral line, its value has no effect on the system.
Circuit Analysis II Spring 2005 Osman Parlaktuna
If the circuit is balanced, the equation can be written as
VV V V
Na n b n c n
A a ga B b gb C c gc
Z Z Z
Z Z Z Z Z Z Z Z Z Z
( )1 1
0
1 1 1
Since the system is balanced,
V V V V a n b n c n N0 0 and
This is a very important result. If VN=0, there is no potential differencebetween n and N, consequently the current in the neutral line is zero.Hence we may either remove the neutral line from a balanced Y-Y circuit (I0=0) or replace it with a perfect short circuit between n and N(VN=0). Both are convenient to use when modeling balanced 3-phase circuits.
Circuit Analysis II Spring 2005 Osman Parlaktuna
When the system is balanced, the three line currents are
I I IaAa n
bBb n
cCc n
Z Z Z V V V
, ,
The three line currents from a balanced set of three-phase currents,that is, the current in each line is equal in amplitude and frequencyand is 1200 out of phase with the other two line currents. Thus, ifwe calculate IaA and know the phase sequence, we can easily writeIbB and IcC.
Circuit Analysis II Spring 2005 Osman Parlaktuna
SINGLE-PHASE EQUIVALENT CIRCUITWe can use line current equations to construct an equivalent circuitfor the a-phase of the balanced Y-Y circuit. Once we solve this circuit,we can easily write the voltages and currents of the other two phases.Caution: The current in the neutral conductor in this figure is IaA, which is not the same as the current in the neutral conductor of thebalanced three-phase circuit, which is I0=IaA+IbB+IcC
Circuit Analysis II Spring 2005 Osman Parlaktuna
LINE-TO-LINE AND LINE-TO-NEUTRAL VOLTAGES
The line-to-line voltages are VAB, VBC, andVCA. The line-to-neutral voltages are VAN,VBN, and VCN. Using KVL
V V V
V V V
V V V
AB AN BN
BC BN CN
CA CN AN
For a positive (abc) phase sequence wherea-phase taken as reference
V V
V
AN BN
CN
V V
V
-120
+120
00 0
0
Circuit Analysis II Spring 2005 Osman Parlaktuna
V
V
V
AB
BC
AB
V V V
V V V
V V V
0 -120 30
-120 120 - 90
120 0 150
0 0 0
0 0 0
0 0 0
3
3
3
• The magnitude of the line-to-line voltage is3 times the magnitude of the line-to-neutralvoltage.• The line-to-line voltages form a balanced three-phase set of voltages.•The set of line-to-line voltages leads the setof line-to-neutral voltages by 300
•For a negative sequence, the set of line-to-linevoltages lags the set of line-to-neutral voltagesby 300
Circuit Analysis II Spring 2005 Osman Parlaktuna
EXAMPLEA balanced three-phase Y-connected generator with positive sequencehas an impedance of 0.2+j0.5 Ω/ and an internal voltage of 120V/ .The generator feeds a balanced three-phase Y-connected load having an impedance of 39+j28 Ω/. The line connecting the generator to theload is 0.8+j1.5 Ω/. The a-phase internal voltage of the generator is specified as the reference phasor.
Calculate the line currents IaA, IbB, IcC
I
I
I
aA
bB
cC
A
A
A
1202 4 36 87
2 4 156 87
2 4
0
0
0
40 + j30
83.13
0
0
. .
. .
.
Circuit Analysis II Spring 2005 Osman Parlaktuna
Calculate the three phase voltages at the load VAN, VBN, VCN
V
V
Vj
CN
BN
AN
0
0
00
81.118 22.115
19.121 22.115
19.1 22.115)87.36 4.2)(2839(
V
V
V
Calculate the line voltages VAB, VBC, VCA
V V
V
V
AB AN
BC
CA
V
V
V
( ) .
.
.
3 30 199 58
199 58
199 58
0 28.81
- 91.19
148.81
0
0
0
Circuit Analysis II Spring 2005 Osman Parlaktuna
Calculate the phase voltages at the terminals of the generatorVan, Vbn, Vcn
V
V
Vj
cn
bn
an
0
0
00
68.119 9.118
32.120 9.118
32.0 9.118)87.36 4.2)(5.02.0(120
V
V
V
Calculate the line voltages at the terminals of the generatorVab, Vbc, Vca
V V
V
V
ab an
bc
ca
V
V
V
( ) . .
. .
. .
3 30 20594 29 68
20594 90 32
20594 149 68
0 0
0
0
Backfill: Resistive Delta/Wye Conversion
Circuit Analysis II Spring 2005 Osman Parlaktuna
Delta/Wye continued...
Circuit Analysis II Spring 2005 Osman Parlaktuna
Other way,Wye to Delta...
Circuit Analysis II Spring 2005 Osman Parlaktuna
Circuit Analysis II Spring 2005 Osman Parlaktuna
ANALYSIS OF THE Y- CIRCUIT
If the load in a three-phase circuit is connected in a delta, it can betransformed into a Y by using the to Y transformation. When the loadis balanced, the impedance of each leg of the Y is ZY=Z/3. After thistransformation, the a-phase can be modeled by the previous method.When a load is connected in a delta, the current in each leg of the deltais the phase current, and the voltage across each leg is the phase voltage.
Circuit Analysis II Spring 2005 Osman Parlaktuna
To demonstrate the relationship between the phase currents and linecurrents, assume a positive phase sequence and
I I IAB BC CAI I I -120 120 00 0 0, ,
I I I
I I I
I I I
aA AB CA
bB BC AB
cC CA BC
I I I
I I I
I I I
120 - 30
-120 -150
120 -120 90
0 3
0 3
3
0 0 0
0 0 0
0 0 0
The magnitude of the line currents is times the magnitude of the phase currents and the set of line currents lags the set of phase currents by 300. For the negative sequence, line currents lead thephase currents by 300.
3
Circuit Analysis II Spring 2005 Osman Parlaktuna
Positive sequence Negative sequence
Circuit Analysis II Spring 2005 Osman Parlaktuna
EXAMPLEThe Y-connected load of the previous example feeds a -connected loadthrough a distribution line having an impedance of 0.3+j0.9/. The loadimpedance is 118.5+j85.8 /.
Transforming load into Y and drawing a-phase of the circuit gives
118 5 858
339 5 28 6
. .. . /
jj
Circuit Analysis II Spring 2005 Osman Parlaktuna
Calculate the line currents IaA, IbB, and IcC
I
I I
aA
bB cC
jA
A A
120 0
40 302 4 36 87
2 4 156 87 2 4 8313
00
0 0
. .
. . . .
Calculate the phase voltages at the load terminals:Because the load is connected, the phase voltages are the same asthe line voltages.
V
V V
V V
AN
AB AN
BC CA
j V
V
V V
( . . )( . . ) . .
. .
. . . .
39 5 28 6 2 4 36 87 117 04 0 96
3 30 202 72 29 04
202 72 90 96 202 72 149 04
0 0
0 0
0 0
Circuit Analysis II Spring 2005 Osman Parlaktuna
Calculate the phase currents of the load.
I I
I I
AB aA
BC CA
A
A A
1
330 139 6 87
139 126 87 139 11313
0 0
0 0
=
. .
. . . .
Calculate the line voltages at the source terminals
V
V V
V V
an
ab an
bc ca
j V
V
V V
( . . . . ) .
. .
. . . .
39 8 29 5)(2 4 36 87 118 9
3 30 20594 29 68
20594 90 32 20594 149 68
0
0 0
0 0
- 0.32
0
Circuit Analysis II Spring 2005 Osman Parlaktuna
AVERAGE POWER IN A BALANCED Y LOAD
P
P
P
A AN aA vA iA
B BN bB vB iB
C CN cC vC iC
V I
V I
V I
cos( )
cos( )
cos( )
In a balanced three-phase system, themagnitude of each line-to-neutral voltageis the same as is the magnitude of each phasecurrent. The argument of the cosine functionsis also the same for all three phases.
V
I
AN BN CN
aA bB cC
vA iA vB iB vC iC
V V V
I I I
Circuit Analysis II Spring 2005 Osman Parlaktuna
For a balanced system, the power delivered to each phase of theload is the same
P P P P V I
P P V I
PV
I V I
A B C
T
TL
L L L
cos
cos
( ) cos cos
3 3
33
3
Where PT is the total power delivered to the load.
Circuit Analysis II Spring 2005 Osman Parlaktuna
COMPLEX POWER IN A BALANCED Y LOAD
Q V I
Q Q V IT
sin
sin3 3
S
S P jQ
S S V I
AN aA BN bB CN cC
T L L
V I V I V I V I
V I
* * * *
*
3 3
Reactive power in a balanced system
Complex power in a balanced system
Circuit Analysis II Spring 2005 Osman Parlaktuna
POWER CALCULATIONS IN A BALANCED DELTA LOAD
P
P
P
AB AB AB vAB ivAB
BC BC BC vBC ivBC
CA CA CA vCA ivCA
V I
V I
V I
cos( )
cos( )
cos( )
For a balanced system
V V V
I I I
AB BC CA
AB BC CA
vAB iAB vBC iBC vCA iCA
V
I
cosIVPPPP CABCAB
Circuit Analysis II Spring 2005 Osman Parlaktuna
P P V I
PIV V I
T
TL
L L L
3 3
33
3
cos
( ) cos cos
Q V I
Q Q V IT
sin
sin3 3
S P jQ
S S V IT L L
V I*
3 3
Circuit Analysis II Spring 2005 Osman Parlaktuna
INSTANTANEOUS POWER IN THREE-PHASE CIRCUITS
In a balanced three-phase circuit, the total instantaneous power isinvariant with time. Thus the torque developed at the shaft of a three-phase motor is constant, which means less vibration in machinery powered by three-phase motors.
Considering a-phase as the reference, for a positive phasesequence, the instantaneous power in each phase becomes
p v i V I t t
p v i V I t t
p v i V I t t
p p p p V I
A AN aA m m
B BN bB m m
C CN cC m m
T A B C m m
cos cos( )
cos( )cos( )
cos( )cos( )
. cos
120 120
120 120
15
0 0
0 0
Circuit Analysis II Spring 2005 Osman Parlaktuna
EXAMPLEA balanced three-phase load requires 480 kW at a lagging power factorof 0.8. The line has an impedance of 0.005+j0.025/. The line voltageat the terminals of the load is 600V
Single phase equivalent
Calculate the magnitude of theline current.
600
3160 120 10
577 35 36 87
577 35 36 87
577 35
3
0
0
I
I
I
aA
aA
aA
L
j
A
A
I A
*
*
( )
. .
. .
.
-
Circuit Analysis II Spring 2005 Osman Parlaktuna
Calculate the magnitude of the line voltage at the sending end of the line.
V V I
V
an AN L aA
L an
Z j
V
V V
600
30 005 0 025)(577 35
357 51 157
3 619 23
0
( . . . )
. .
.
- 36.87
0
Calculate the power factor at the sending end of the line
pf
= Lagging
cos[ . ( . )]
cos . .
157 36 87
38 44 0 783
0 0
0
Circuit Analysis II Spring 2005 Osman Parlaktuna
EXAMPLE
Determine all the load currents:
Transforming to Y as 60/3=20, and drawing a-phase of the circuit gives:
Vrms
Arms
AN
aA
00
00
0 90)12)(0 5.7(
0 5.730//204
0 120
V
I
Circuit Analysis II Spring 2005 Osman Parlaktuna
In the original Y connected load
ArmsArms
Arms
CNBN
AN
00
00
012 3 012- 3
0 330
0 90
II
I
For the original delta-connected load
ArmsArms
Arms
Vrms
CABC
AB
AB
00
00
000
150 6.2 90 6.2
30 6.260
30 88.155
30 88.155300 390
II
I
V
35Eeng 224
Unbalanced Three Phase Systems An unbalanced system is due to unbalanced voltage sources or unbalanced load. In a unbalanced system the neutral current is NOT zero.
Unbalanced three phase Y connected load.
Line currents DO NOT add up to zero.
In= -(Ia+ Ib+ Ic) ≠ 0
36Eeng 224
37Eeng 224
Three Phase Power Measurement Two-meter method for measuring three-phase power
38Eeng 224
Residential Wiring
Single phase three-wire residential wiring