basics of lv switchboard-presentation
DESCRIPTION
SwitchgearTRANSCRIPT
![Page 1: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/1.jpg)
Power Center Factory
Basic of LV Switchboard (IEC-61439-2)
Presented by yEng. Nooruddin Khan
18 Dec 2013
![Page 2: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/2.jpg)
Switchboard: Definition? A Switchboard is a point in an electrical network at which an A Switchboard is a point in an electrical network at which an
incoming-power supply divides into separate circuits, each of which is controlled and protected by the fuses or switchgear of the switchboardswitchboard.
![Page 3: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/3.jpg)
Switchboard: A distribution switchboard is divided A distribution switchboard is divided
into a number of functional units, each comprising all the electrical and mechanical elements thatand mechanical elements that contribute to the fulfillment of a given function. It represents a key li k i th d d bilit h ilink in the dependability chain.
Distribution switchboards are Distribution switchboards are critical to the dependability of an electrical installation. They must comply with well-defined standards Picture: Switchboard panel with open-type comply with well-defined standards governing the design and construction of LV switchgear assemblies
knife switches is an Edison DC type. from The Frick Power House, 1904 A.D.
assemblies.
![Page 4: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/4.jpg)
Switchboard Parameters:
Rated Operational Voltage (Ue) : This is the maximum continuous voltage at which equipment may be used.
Rated Insulation Voltage (Ui) : The highest operating voltage that will not cause a dielectric strength failure. The rated insulation voltage is used as a parameter for dielectric strength tests and forvoltage is used as a parameter for dielectric strength tests and for the creepage distance. The rated insulation voltage must always be higher than the rated operating voltage (Ue).
Rated Impulse Voltage (Uimp) : The peak value of an impulse voltage of which the circuit of an assembly is capable of withstanding without failurewithstanding without failure.
Rated current (In) : Maximum current that the device can carry continuously without abnormal temperature risecontinuously without abnormal temperature rise.
![Page 5: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/5.jpg)
Switchboard Parameters:
Rated short time withstand current (Icw) : Maximum short time withstand current that the equipment can carry without damage.
Rated Peak withstand current (Ipk) : The rated peak withstand current of a circuit of an assembly is the value of peak currentcurrent of a circuit of an assembly is the value of peak current assigned to that circuit by the manufacturer which that circuit can withstand satisfactorily.
Rated short-circuit making capacity (Icm) Maximum current (peak) a device can make at its rated voltage according to the (p ) g gconditions of standard. Devices without protection like switches, must be able to withstand short-circuit current with a value & duration resulting from action of the associated protection device.duration resulting from action of the associated protection device.
![Page 6: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/6.jpg)
Switchboard Parameters:
Rated ultimate short-circuit breaking capacity (Icu) : This is the maximum short-circuit current value that a circuit breaker can break t i lt d h l ( ϕ) Th t t t dat a given voltage and phase angle (cos ϕ). The tests are executed
according to the sequence O - t - CO. O represents an automatic break operation, t a time interval and CO a make operation followed by an automatic break operation. Following the test, the circuit breaker must continue to provide a minimum level of safety (isolation, dielectric strength).( g )
Rated service short-circuit breaking capacity (Ics) : This is the al e e pressed as a percentage of Ic It ill be one of thevalue expressed as a percentage of Icu. It will be one of the
following values: 25% (category A only), 50%, 75% or 100%. The circuit breaker must be capable of operating normally after breaking the Ics current several times using the sequence O-t-CO-t-CO.
![Page 7: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/7.jpg)
LV Switchboard: Standard International Standard IEC-61439-1 & 2 (Old Standard IEC-60439-1 International Standard IEC 61439 1 & 2 (Old Standard IEC 60439 1
is still valid for KSA market till 2014). Certified switchboard is called “Verified assembly” or in old std. “Type Tested Assembly”
American Standard ANSI-C37.20.1 or IEEE, UL-508 (Out of Power Center Scope) p )
![Page 8: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/8.jpg)
MV Switchgear: Standard
![Page 9: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/9.jpg)
IEC-61439-2: Verification
![Page 10: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/10.jpg)
Switchboard: Customer Inquiry Customer send his inquiry in different ways(1) Single Line Diagram (Example)
![Page 11: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/11.jpg)
Switchboard: Customer Inquiry(2) Load Schedule (Example)
![Page 12: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/12.jpg)
Switchboard: Customer Inquiry(3) Main/Branch CB Size Listing (Example)
![Page 13: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/13.jpg)
Switchboard: Customer Inquiry(4) Drawings (Example)
![Page 14: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/14.jpg)
Specification: Additional information with inquiry: Customer specification should
be attached with SLD/Schedule/drawing etc.
![Page 15: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/15.jpg)
Request For Quotation (RFQ) Please send all inquiry
to PC with filled RFQ.
![Page 16: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/16.jpg)
Switchboard: Main Components
Housing (Enclosure)
Bus-bar
Incoming CB/Fuse/Switchg
Outgoing CB/Fuse/Switch
Metering & Indication
Control & Accessories etc Control & Accessories etc.
![Page 17: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/17.jpg)
Housing (Enclosure)
![Page 18: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/18.jpg)
Enclosure: Function?
Protection of switchgear, i t h i l i tagainst mechanical impacts,
vibrations and other external influences (EMI, dust, moisture, vermin, etc.)
The protection of human life The protection of human life against the possibility of direct and indirect electric
![Page 19: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/19.jpg)
Enclosure: Selection Criteria Application: Indoor/Outdoor
Degree of Protection: IP Rating, IP-31, IP-42 or IP-55g g, ,
Mechanical Strength (IK) Rating
Material: Mild Steel/Stainless Steel/Polyester/GRP
Certification: Type Tested/Universal Certification: Type Tested/Universal
Form of Separation: Form-1/2a/2b/3a/3b/4a/4b
Entry: Top/Bottom
Access: Front/Rear
![Page 20: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/20.jpg)
IP Rating as per IEC-60529
![Page 21: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/21.jpg)
IK Rating as per IEC-62262
![Page 22: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/22.jpg)
Form of Separation:
![Page 23: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/23.jpg)
Bus-bar Bus bar is a conductor of electricity e.g. strip or bar of copper, brass
or aluminum that conducts electricity within a switchboard, distribution board substation battery bank or other electricaldistribution board, substation, battery bank or other electrical apparatus etc.
Cu-ETP (Electrolytic-Tough-Pitch) R240 grade of bus bar is specified in switchboard application as per EN 1650
![Page 24: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/24.jpg)
Bus-bar Selection Criteria Thumb Rule: 1.5A/mm2 (Not Accurate & just for rough estimation)
S l t it bl i f t bl d l d b CDA Select suitable size from tables developed by CDA.
Tables Developed by switchboard manufacturers Tables Developed by switchboard manufacturers
Using Formula
Using Software
![Page 25: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/25.jpg)
Switchgear & CB A Switchgear is the combination of electrical disconnect switches,
fuses or circuit breakers used to control, protect and isolate electrical equipment
A Circuit Breaker is a manually or automatically operated electrical switch designed to protect an electrical circuit fromelectrical switch designed to protect an electrical circuit from damage caused by overload or short circuit.
![Page 26: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/26.jpg)
Overload Protection
![Page 27: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/27.jpg)
Short Circuit Protection
![Page 28: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/28.jpg)
Insulation Fault Protection
![Page 29: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/29.jpg)
Electrical Hazard
![Page 30: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/30.jpg)
LV & MV Switchgear
![Page 31: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/31.jpg)
Type of LV Circuit Breaker There are three types of LV Circuit Breakers in market
1 MCB (Miniature Circuit Breaker) in two frame size upto 63A/upto1. MCB (Miniature Circuit Breaker) in two frame size upto 63A/upto120A (Schneider Electric iC60 & iC120 range)
2 MCCB (Molded Case Circuit Breaker) available normally upto2. MCCB (Molded Case Circuit Breaker) available normally upto1600A (Schneider Electric MCCB NSX/Easypact range upto 630A & NS from 630A upto 3200A)
3. ACB (Air Circuit Breaker) available upto 6300A (Schneider Electric NT range upto 1600A & NW range upto 6300A)
![Page 32: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/32.jpg)
Selection Criteria of LV CBWhat are the characteristics for choosing a circuit breaker? Current parameter: In – Icu – Ics – Icm
Voltage parameters: Ue – Ui – Uimp
Fixed or withdrawable
Standard
T f t i it Type of trip unit
Number of poles
Need for discrimination
![Page 33: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/33.jpg)
Metering & Indication Lamps
Normally Metering consists of Digital multimeter or Analog Ammeters & Voltmeters 72X72 or 96X96 size with selector switch, Current transformers & control fuses/fuse holders
Indication Lamps consist of three in Indication Lamps of 22mm Indication Lamps consist of three in Indication Lamps of 22mm diameter with Red/Yellow/Blue colors for all phases
![Page 34: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/34.jpg)
Types of Switchboard
Switchboard or Main Distribution Board (Example: Blokset, Prisma Plus-P)
Motor Control Center (Example: Blokset, Prisma Plus-P) Panelboard or Sub Main Distribution Board (Example: Prisma
Plus P & GPlus-P & G Loadcenters or Final Distribution Board (Example: Prisma
Pack, Disbo)
![Page 35: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/35.jpg)
Technology in Switchboard
Traditional distribution switchboards: Switchgear and fuse gear, etc. are normally located on a chassis at the rear of the enclosure. Required careful designing having knowledge of dimension of all components. (Example: Universal Enclosure panels)p )
Functional distribution switchboards: Made up of functional d l th t i l d it h d i t th ithmodules that include switchgear devices together with
standardized accessories for mounting & connections, ensuring a high level of reliability & a great capacity for last-minute and future changes.
![Page 36: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/36.jpg)
Product Range Switchboards up-to 6300A & up-to Form-4b Panel-boards
L d C t Load Centers MCC (DOL/Y-∆/VFD/Soft-starter) Auto & Manual Synchronizing Panels Auto. & Manual Synchronizing Panels ATS & MTS Lighting Control Panels PFC Panels (Capacitor Bank)
![Page 37: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/37.jpg)
Product Characteristics
![Page 38: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/38.jpg)
Designing Tools (Software)E di l f di i d f l i l k Ecodial for coordination study of electrical network
Rapsody for design Prisma Plus switchboard Rapsody for design Prisma Plus switchboard.
Schneider online “Electrical Calculation Tools”
![Page 39: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/39.jpg)
Basic Calculation
![Page 40: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/40.jpg)
Basic Calculation
![Page 41: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/41.jpg)
Basic Calculation
![Page 42: Basics of LV Switchboard-Presentation](https://reader034.vdocument.in/reader034/viewer/2022050721/55cf9a10550346d033a05097/html5/thumbnails/42.jpg)
Questions