batching manual update eng new-2

Upload: lcdamptech-linh

Post on 07-Apr-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/4/2019 Batching Manual Update Eng New-2

    1/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________

    1. System Menu Bin Dischage

    Click right to show menu bindischarge detail as below;

    - Manual Operate = To panel manual system.- Reset Error = To reset error.

    -Under Repair = To not use this bin discharge.

    - Parameter = To set Bin Parameter- Bin Inventory = To set Bin Inventory

    Page 1 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    2/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________2. BIN PARAMETER

    When you right click on the Popup menu, this will show the

    BIN PARAMETER, select this field.

    Page 2 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    3/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________

    Bin Code Number of Bin that you need to edit. (wecan use Alphabets or Numbers)

    IngredientCode

    Code of the material to be packed insidethe bin.

    Pre-CutWeight

    Weight on change bin dischage to stepjoging mode

    Free FallWeight

    Weight increases after the systemcommands the Stop Bin Feeder.

    Very HighTolerance

    Weight is over the limit but is stillacceptable. (if weight is over thelimit, the system will show an alarm ofOver Weight)

    Very LowTolerance

    Weight is not complete but it is stillacceptable. (if the weight is morethan the value you set, the systemwill jog for 6 times. After jogging, andthe weight is still below the requiredweight, it will show an alarm windowUnder Weight)

    Jog Time(s)

    This is the time wherein the system worksin Jogging Mode to open the BinFeeder.

    Note: time of Jogging can be set at ScaleConfiguration and Jogging Max

    Speed Jog(%)

    % rate for Joging

    SpeedHigh(%)

    % rate for maximum speed joging

    Page 3 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    4/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________

    SpeedLow(%)

    % rate for minimum speed joging

    Active Bin The system checks if this Bin can be used.

    SubFeeder

    Set RESERVE Bin

    Main and Sub are used in the systemsupport to open more than 1 Binsimultaneously (max of 5 bins), this iscalledMulti-Bin Draw. When the

    required weight is almost completed,the system stops the Sub-Feeder andruns the Main Feeder until it iscomplete. This method reduces thetime of Scaling but increasescorrectness.

    Bin Code Number of Bin that you need to edit. (wecan use Alphabets or Numbers)

    AutoCalculateFreeFall

    The System automatically calculates forthe Free Fall weight.

    Auto-FixFreeFall in

    LastBatch

    The system to use Free Fall Weight in lastbatch on next production(formula).

    3. Manual Operate

    Page 4 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    5/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________

    Page 5 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    6/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________

    3.1 Jogging Mode- Set Jog Speed, Jog Time

    3.2 Manual- Set Jog Speed and click mouse down to jog and mouse

    up to stop jog.

    Page 6 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    7/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________4. System Menu Scale

    System Menu after click mouse right to show menu detail as

    below:

    - Auto = To set auto mode- Manul = To set manual mode- Start Batch = To set new batch (Active Formul)- Formula Monitoring = To monitoring formula activeweight ingredient by item

    Page 7 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    8/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________on scale.

    - Change Batch Preset = To change batch preset on actualformual

    - Reset Batch Queue = To reset batch queue after setBatch Queue- Parameter = To set parameter scale.- Hold slide = To set Hold/UnHold slide scale.

    5. Scale Parameter

    Page 8 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    9/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________Flow Time This is the time when the ingredient flows

    after starting the Feeder. If the time is =flowtime and the ingredient does now

    flow, (the Scale does not increase) theprogram shows an alarm Ingredient NotFlow.

    Settle Time This is the time when the system waitsuntil the Scale stops. After a commandstops the Feeder.

    Delay Time This is the time when the system waits foran open Slide. After completely weighingevery ingredient, it is now ready to send itto the next procedure (in case that wehave 2 scales that go to the same Mixer,only one slide can be open at a time).

    Empty Weight Weight of ingredient that can be acceptedto remain in the Scale after Discharge.(not more than 1% of the Scalescapacity)

    DischargeTime

    Shows the time to open the Slide of theScale for discharging the ingredients forthe next procedure. When the discharge

    time is complete, the system closes theSlide. The machine is not interested indischarging if the ingredient is not enough(normally set to 0.0 for this parameter,its used to check for an empty weight,but not if the parameter is unstable).

    DischargeSettle Time

    The scale discharges until the weight isless than the specified empty weight. Thesystem will wait until it is time for the

    discharge to be complete.Delay to StartNext Batch (s)

    The time the system waits after closingthe Slide Scale, before we can continuewith the process.

    Max Weight Maximum capacity of scale.Time to HoldConveyor

    Time in holding the Conveyor.

    Page 9 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    10/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________Jog Max Times to joging

    Suspend

    WeightTime(s)

    Time to stop scale system after mixer

    discharging.

    5. System Menu Mixer

    System Menu after click mouse right to show menu detail asbelow:

    - Auto = To set mode auto- Manual = To set mode manul- Formula Monitoring = To monitoring formula weight

    ingredient by item on mixer. (HandAdd, Liquid, etc.)- Parameter = To set parameter mixer.- Hold slide = To hold/unhold slide gate mixer.

    Page 10 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    11/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________

    7. Mixer Parameter.

    Dry MixTime

    Mixing the ingredients without liquids.Example, no water or oil.

    Page 11 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    12/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________Wet Mix

    Time

    Start time for mixing and how long to mix withliquids.

    Acture

    time (s)Time AfterLiquid

    After wet mix, the machine will hold the

    ingredients before discharging. The process ofmixing the ingredients is completed.

    DischargeTime

    Time of discharge, the Mixers gate is open.

    CycleDelayTime

    A gap between the batching process.

    DelaySurgeLow

    Waiting time for the Mixer Surge Low signal(hopper is empty) and before the Mixerdischarges the ingredients to the Hopper whenthe mixing process is complete.

    8. System Menu Liquid.

    Page 12 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    13/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________

    System Menu after click mouse right to show menu detail asbelow:

    - Manual Operate = To set manual liquid from ManualOperate Panel.

    - Reset Error = To reset error.- Under Repair = To not use pump liquid.- Reset Pluse = To reset pluse on liquid system by item.- Parameter = To set parameter liquid.

    Page 13 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    14/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________9. Liquid Parameter.

    Page 14 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    15/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________

    IngredientCode

    Code of the material to be packed insidethe bin.

    Flow Rate Number of pules per kilo / Time. (belowoption Liquid Pules/Time

    Jog Time Times to joging mode.

    Free FallWeight

    Weight increases after the systemcommands the Stop Bin Feeder.

    Very High

    Tolerance

    Weight is over the limit but is still

    acceptable. (if weight is over the limit,the system will show an alarm of OverWeight)

    Very LowTolerance

    Weight is not complete but it is stillacceptable. (if the weight is more thanthe value you set, the system will jogfollow Jog Max. After jogging, and theweight is still below the requiredweight, it will show an alarm windowUnder Weight)

    Jog Max This is the time wherein the system worksin Jogging Mode to open the BinFeeder.

    Note: time of Jogging can be set at ScaleConfiguration and Jogg Max

    Delat Time(s) Time to delay liquid to spuirt after startmixing time.

    Flow Time(s) Time to check liquid pluse no flow afterstart motor. System show alarmLIQUID NOT FLOW

    Page 15 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    16/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________

    Liquid FlushTime(s)

    Time to fluse liquid line.

    LiquidCompleteTime(s)

    Time to check liquid completed .

    OPTION

    Active Liquid = Check Active Liquid whento use.

    Auto-Cal Free Fall = Set system auto calculate free

    fall.Liquid Pules/Time = Set system to use flow rate kilo

    per 1 pules or kilo per 1 sec.Liquid Flush Every Batch = Set system to auto flush

    line every batch.Liquid Flush Every Last Batch = Set System to auto

    flush line every in last batch.

    10. System Menu HandAdd

    Page 16 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    17/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________- Manual Open = To open slide handadd- Manual Close = To close slide handadd- Reset Error = To reset error

    -Under Repair = To not openslide handadd

    - Parameter = To set parameter handadd5. HANDADD PARAMETER.

    Hand Add

    Delay Time

    Time to hold slide handadd to open after

    slide scale opened.Hand AddDischarge

    Time

    Time to open slide handadd after HandAddAckownlage

    11. System Alarm.

    System Alarm

    Page 17 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    18/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________Alarm Cause Repair

    HandAdd

    not Acknow.

    - Hand Add

    Acknowledge switchis not pushed.- PLC is notreceiving signal(Hand AddAcknowledgesignal).- PLC. Input to be

    damaged.

    - Tell Hand Add Station to push

    the switch.- Change switch.- Check Cable, check LampHand Add Acknowledge PanelBoard.- See PLC Input and Output

    Topic.

    HandAddnotcomplete.

    - HandAddComplete switch isnot pushed.- PLC is notreceiving signalfrom Hand AddComplete.- PLC Input to bedemaged.

    - Tell HandAdd Station to pushthe switch.- Change switch.- Check Cable, check LampHand Add Complete PanelBoard- See PLC Input and Outputtopic.

    Slide

    HandAddNot Open.

    - Slide Hand Add is

    not working.- Air Valve not open.- Solenoid ofPneumatic systemis broken.- PLC Output forControl CoilSolenoid not work.- Slide is open but

    Limit Slide Open isnot working.- PLC Input signal itreceives from theLimit Open is error.

    - Check the Air System of the

    Slide H.A.because the slide is jammed

    by dust. Youcan use oil to make the Slide

    work again.- Open Air Valve, check AirPressure.- Check the resistance of thecoil if it is an open circuit. Check

    the electric line.- Check Limit Switch.- See PLC Input and Outputtopic.

    Page 18 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    19/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________Alarm Cause Repair

    Slide

    HandAddNot Close.

    - Slide HandAdd is

    not working.- Air Valve is notclosed.- PLC Output forControl CoilSolenoid is notworking.- Slide is closed butLimit Slide Close isnot working.- PLC Input Error.

    - Check the Air System of the

    SlideHandAdd because the Slide isjammed

    by dust.- Open Air Valve, check Air

    Pressure.- Check the resistance of the

    coil if it is aclosed circuit. Check the

    electric line.- Check Limit Switch Close.- See PLC Input and Output

    topic.Mix routenot ready.

    - the way oftransport fromMixer to somemachines does notwork.- the PLC Output

    makes the CoilSolenoid work, orthe Motor Starterdoes not work.- PLC Input error.

    - Check the Limit Switch of theMotor Conveyor System and theMotor Starter, to see if thetransport from mixer is correct.- See PLC Input and Output

    Topic.

    Discharge inhold. (Mixersystem)

    - Slide hold- Switch is notpushed but LED ofInput PLC is shown.

    - release Switch Hold Mixer.

    Page 19 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    20/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________Alarm Cause Repair

    Slides Gate

    Mixer is notOpen.

    - Slide in not

    working.- Air Valve is notopen.- Solenoid ofPneumatic Systemis broken.- the PLC Outputthat makes the CoilSolenoid work is notworking.- Slide is open butLimit Slide Open isnot working (LampSlide Open is notshown on the Panel)- PLC Input error.

    - check the Air System of the

    Slide Bin because the Slide maybe jammed by dust. Use oil intothe Air System.- open the Air Valve and checkthe Air Pressure.- check resistance of the CoilCircuit. If it is not complete,check the wire or change theCoil Solenoid.- change the Limit Switch atSlide Open position or LimitSwitch touching position.- See PLC Input and Output

    Topic.

    Slides GateMixer is notClose.

    - Slide is notworking.- Air Valve is not

    closed.- Slide is closed butLimit Slide Close isnot working (nosignal Lamp SlideClose on Panel)- PLC Input Error.

    - Check the Air System of theSlide Bin because the Slide maybe jammed by dust. Use oil into

    the Air System.- Open the Air Valve and checkthe Air Pressure.- Change the Limit Switch atSlide Open position or LimitSwitch touching position.- See PLC Input and Output

    Topic.

    Page 20 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    21/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________Alarm Cause Repair

    Mixer surge

    not low.(Hopperunder theMixer is notempty)

    - Hopper is not

    empty or ingredientsticks to the Sensor.- the Conveyorunder the Mixer isslow.- Set Delay SurgeLow in MixerParameter to beover.

    - In case that the Sensor has a

    problem every time that wechange it, clean the Hopperunder the Mixer and Sensor.- Increase the efficiency of theConveyor- Reduce time of Parameter.

    Scale MeterError.

    - Reader has aproblem.- Signal line fromReader is broken.- If it shows UL, OV,Error on ScaleMeter, check theLoad Cells weight ifit is over or under.- PLC

    CommunicationCard has a problem.

    - Check the Readersparameter.- Check Cable of Reader (WeightIndicator) and PLC.- Check resistance of Load Celland compare it with itsCertificate. Also check thesignal (mV) from Load Cell if it iscorrect.- Check Card and See PLC Input

    Topic..

    Scale notempty(Hopper ofScale is notempty)

    - The weight in theHopper Scale ismore than what wasset in EmptyWeight.- The ScaleParameter set in

    Empty Weight isvery low.- The ingredientsent off fromHopper is very slow.

    - Clean the Hopper Scale ormake a new calibration(recalibrate).- Change Parameter.at EmptyWeight.- Increase Dischage Time inScale Parameter.

    Page 21 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    22/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________Alarm Cause Repair

    Scale over

    shutdown(weight inScale ismore thanwhat wasset)

    - weight in Scale is

    more than the MaxCapacity of Scale inScale Configuration.- ingredient weightin formula is over.

    - Send off ingredient from Scale

    or change the Max Capacity inScale Configuration.- Edit formula for all ingredientswith weight less than the MaxCapacity.

    Slide Scaleis not open.

    - Slide is notworking.- Air Valve is notopen.- Solenoid ofPneumatic isbroken.- Slide is openedbut Limit Slide Openis not working (nosignal Lamp SlideOpen on Panel)- PLC Input or

    Output Error.

    - Check the Air System of theSlide Bin because the Slide maybe jammed by dust. Use oil intothe Air System.- Open the Air Valve and checkthe Air Pressure.- Check resistance of the CoilCircuit. If it is not complete,check the wire or change theCoil Solenoid.- See PLC Input and Output

    Topic.- Change the Limit Switch at

    Slide Open position or LimitSwitch touching position.

    Slide Scaleis not Close

    - Slide is notworking.- Air Valve is notclosed.- Slide is closed butLimit Slide Close is

    not working (nosignal Lamp SlideClose on Panel)- PLC Input/Outputerror.

    - Check the Air System of theSlide Bin because the Slide maybe jammed by dust. Use oil intothe Air System.- Open the Air Valve and checkthe Air Pressure.

    - Change the Limit Switch atSlide Open position or LimitSwitch touching position.- See PLC Input and Output

    Topic.

    Page 22 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    23/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________Alarm Cause Repair

    Ingredient is

    not Flow.

    - Ingredient does

    not flow- Bin dischage is notrunning.- the PLC Outputthat controls theMotor Starter is notworking.- Flow Time in theScale Parameter isvery low.- Scale Motion inthe Weight Indicatoris very low.

    - Check the Conveyor System,

    for the flow and quantity of theingredient in the Bin.- See PLC Input and Output

    Topic.- Check the Motor Starter of theFeeder.- Add value to Flow Time.- Add value to Scale motion.

    Ingredient isOver VeryHigh.

    - Ingredient overweight on targetweight.

    - return some ingredient fromthe Hopper in Scale or Acceptan Alarm Window.

    Ingredient isVery Low

    - Ingredient underweight on target

    weight.

    - Retry to auto jogging orManual Jogging of ingredient

    again.- Set new Jog Time in BinParameter (read in Topic Binparameter, how to set Jog Time)- Add the value of Jogging Maxin Scale Configuration.- In case the ingredient is oftenover weight or under weight,please check the value of Free

    Fall. The change could be:1. Ingredient is very sticky.2. Ingredient is often empty,increase ingredient.3. In case of Scaling Ingredient.

    Page 23 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    24/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________Alarm Cause Repair

    Scale is

    hold(Scale willnotdischarge)

    - Slide is on hold - UnHold Scale.

    Scale surgenot Low.(Hopperunder Scaleis notempty)

    - Hopper underScale is not emptyor doesnt have aningredient stick atthe Sensor.- Conveyor underthe Scale worksslowly (in case theMixer is under theScale).- Have aningredient in theMixer.

    - Clean the Hopper under theMixer and Sensor in case theSensor often have problems,please change the Sensor.- Add the efficiency of theConveyor System under theScale.- Checking the Mixing Systemuses more time than the ScalingSystem. But in a normalprocess, the Mixing Systemconsumes lesser time than theScaling System.

    Ingredient is

    Out off Bin.(the Bindoesnthave theingredientin theformula)

    - Ingredient is not

    found inside the BinParameter

    - Check formula or Bin

    Parameter- Change bindischage.

    Page 24 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    25/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________Alarm Cause Repair

    Liquid is not

    flow

    - Liquid is empty.

    - Valve or LiquidPump is notrunning.- The PLC Outputthat controls theValve is notrunning.- Liquid is notflowing.- The Liquid but stillhas an Alarm.- PLC Input/OutputError.- In this case, it isthe same of theLiquid Scale, pleaseconsider the Scale ifit doesnt have anyflow.

    - Check the quantity of the

    Liquid inside the Bin.- Check the PLC Output of theValve Liquid (Pump Liquid) andMotor Starter- See Topic: Check PLC Inputand Output.- Check the flow of Liquid.- Check the Pulse signal fromthe Flow meter, and check thesignal cable from the FlowMeter.

    Page 25 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    26/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________Alarm Cause Repair

    Liquid is

    Over VeryHigh.

    - Liquid is over

    more than targetweight.

    - An acceptable case.

    - In case that the quantity of theLiquid is too much, and cant beaccepted anymore, that batchshould be re-mixed. Find aprotection method to avoid thisfrom happening again.1. Does the Valve Liquid open orclose slowly?2. Flow of Liquid is too highwhen compared to the use of itsquantity.3. Does the Systemcommanding Close Valve shouldstop the Liquid from flowing?4. If the Valve is closed, thePump should stop running too.(dont include in the system aLiquid that doesnt flow;Example: Molasses)

    Liquid isUnder VeryLow.

    - Liquid is lowerthan target weight.

    - Please retry for JoggingSystem.- Press Accept in case theweight is not enough but can beaccepted.- If Under Weight oftenhappens, please check Free FallValue and Jog Time Value inLiquid Parameter. Also include

    Bin Parameter.

    Page 26 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    27/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________Alarm Cause Repair

    Liquid Meter

    Error.

    - Weight Indicator

    wave problem.- Signal cable fromthe weight Indicatoris abnormal.- Have UL, OV, ErrorMessage or ------ onMonitor of weightIndicator, pleasecheck the Load Cellif its weight is toohigh or too low.- PLCCommunicationCard Error.

    - Check the weight Indicator

    Parameter value.- Heck the Cable that isconnected between the weightIndicator and PLC- Check the resistance in LoadCell and compare it with itsCertificate. Also check thesignal (mV) from Load Cell if it iscorrect.- Check Card A1SJ71 LoopBack

    Tester method.

    Liquid notActive(Liquid isnotworking)

    - Liquid Active Flagin Liquid Parameteris not turned On.- System is Refilling.

    - Set Liquid Active in LiquidParameter for On and Savedata.- turn off Switch Liquid RefillRequest.

    Commerror(Communication Error)

    - the signal betweenthe PLC andCOMPUTER is notcomplete.

    - check Cable between PLC andCOMPUTER.- check Switch position on CardA1SJ71C24.- check LED signal on CardA1SJ71C24.- CPU of PLC must RUN.- Loop Back Test on CardAISJ71C24 and PLC.

    - try to Download the Programon the COMPUTER again.

    Page 27 of 28

  • 8/4/2019 Batching Manual Update Eng New-2

    28/28

    TAT ENERGY & ENGINEERING CO., LTD.____________________________________________________________

    _______________________