Building Operator
Certification – Level I
A Partnership of the CUNY Institute for Urban Systems
Building Performance Lab, the CUNY School of Professional
Studies, and the New York State Energy Research & Development
Authority
2
Building Operator Certification Level I (BOCI)
Building Systems: Electrical
CUNY School of Professional Studies
CUNY Building Performance Lab
The BOC
Motors: Lesson 4
3
Lesson 3 Review
4
Motors
Lesson Objectives
Be able to
Apply principles of motor construction and operation to improve efficiency and life of motors
Inventory motors with detailed characteristics from nameplate data
Calculate motor load factors and energy consumption
Describe the benefits of efficiently-running motors and a motor maintenance program
5
Agenda for Session
Importance of Motors and their energy implications (30 min) Basics of Motor Construction, Operation and Maintenance (90 min) Understanding Motor Sizing, Loading and Calculating Motor Energy Usage (60 min)
6
Motors are among the biggest energy users in a facility. They consume 30- 35% of the electricity used in commercial and institutional facilities in the U.S.
Because motors are one of a facilities biggest energy users, their efficient operation can greatly influence the energy budget. It is important to understand how motors work, how they draw power and the factors that influence how much power they consume. A motor performs more efficiently when properly maintained.
Motors are used for everything that has motion, as well as part of processes, like the HVAC system for compressors and fans.
Consider: Where are there motors in your facility?
Motors and Energy Use
7
Energy Efficient Motors
8
Energy Efficient Motors, Continued When you buy a car, you may make an effort to select a car with high efficiency to save on the cost of gas. You should do this to a much greater extent for the purchase of a motor. The cost of gas is a relatively small part of the cost of ownership of a car. 15,000 miles/yr / 25 GPM = 600 gal/yr x $4/gal = $2400/yr This is 10% of the cost of the car $24,000 A motor can use 10 times the “cost of the motor” in the cost of electricity over its life time. Savings = $4600 Cost = $460 What kind of motor selection strategy do these figures suggest?
9
Motor Efficiency
Motor Efficiency is a measure of the Work Output to the Energy Input
Eff = Output / Input
83 - 88% “Standard”
>90% Premium, 94% for larger motors
(larger motors built to higher efficiency range)
Manufacturers must test and publish their motor efficiencies – available in catalogs, spec sheets and on unit nameplates
Baseline efficiencies are required by federal law (see next slide)
10
Motor Efficiency
11
Benefits of Energy Efficient Motors
• Reduced heat load on building air conditioning system • Lower operating expenses
• Environmental benefits – Reduction in Greenhouse Gas
emissions
• Reduced current on customer's distribution system
• Utility rebates and tax credits may be available to change and maintain high efficiency motors
12
Standard vs. Energy Efficient Motors
Std Efficiency Motors, Average Efficiency Replace with EPAct Motors
% Eff. At 75% load Annual Energy Use (kWh), cost
Purchase Price (35% disc)
% Eff. at 75% load
Annual Energy Use (kWh), cost
Annual Saving kWh, cost
Payback Period
HP
5 84.00% 26,644 $233 88.2% 25,374 1,270 2.44
$1,998 $1,903 $95 10 86.75% 51,653 $375 90% 49,773 1,919 2.6
$3,874 $3,730 $144 15 87.55% 76,771 $562 91% 73,780 2,991 2.5
$5,758 $5,534 $224 20 89.30% 100,206 $666 92.6% 96,626 3,579 2.48
$7,515 $7,247 $268 25 89.90% 124,457 $800 93.10% 119,952 4,505 2.36
$9,334 $8,996 $338 50 91.60% 244,211 $1,617 93.9% 238,027 6,185 3.48
$18,316 $17,852 $464
13
BREAK
14
Basic Principle of Electric Motors How it works: • Motor with a permanently
magnetized stator
• Electricity applied to the rotor creates a strong magnetic field in rotor
• Force in the rotor will rotate the rotor
Applications: • Used in small equipment
• Preferred for tools for easier adjustment of motor speed
15
Basic Principle of Electric Motors, cont’d
Video 1: How an Electric Motor Works 5a 4:45 min www.ehow.com/video_4951184_electric-motor-work_.html
16
There are many different kinds of motors, that work on same principles but components configured differently.
The AC single-phase and three-phase induction motors are the most common.
DC powered motors less common
Typical Electric Motor Construction
17
AC Induction Motor Stator
High production of heat from electric current. Heat must be removed or windings will fail prematurely.
The stationary “windings” where electro-magnetic field is induced. Windings are wiring wrapped around a metal core.
18
AC Motors: Single-and Three-Phase
Single Phase power: 120 V, typical for smaller motors, < 5 HP < 1 HP are called “fractional HP”, common on smaller circulation pumps
3-Phase power: 208/240 V and higher • Phases must be in BALANCE (close to equal voltage and
amperage) or overheating and premature failure • Shaft can rotate in wrong direction if leads reversed. Check
rotation after any work!
Motors must have proper power supply at rated voltage. Amperage will vary based on load. Motors can tolerate limited duration under-voltage or over-loading but will eventually over-heat and fail.
19
NEMA Nameplate Data Standardization
* type and frame
* Horsepower output.
* Time rating
* Maximum ambient temperature for which motor is designed.
* Insulation system designation.
* RPM at rated load.
* Frequency.
* Number of phases.
* Rated load current: LRA and RLA
* Voltage.
* Code letter for locked rotor kVA. (See MG 1-10.37.)
* Design letter for medium motors. (See MG 1-1.16.)
* NEMA nominal efficiency when required by MG 1- 12.55
* Service factor if other than 1.0.
* For motors equipped with thermal protectors, the words "thermally protected" if the motor provides all the protection described in MG 1-12.52. (See MG 1-1.71 and MG 1-1.72.)
* For motors rated above 1 hp equipped with over-temperature devices or systems, the words OVER TEMP. PROT.-." A type number as described in MG 1- 12.53 inserted in the blank would identify the protection type.
Motor manufacturers have agreed on motor characterization so that data is readily available to know motor equivalencies.
20
Generic Nameplate
21
Electric Motor Nameplate Data HP - mechanical work produced at the shaft
1 HP = 746 watts
Required Voltage for motor operation, Phases (single or 3-phase)
Rated Amps LRA - Locked Rotor Amps – Motor is not turning RLA – Rated Load Amps – Running at Rated HP
Efficiency 83 - 88% Standard, >90% Premium
Type (torque characteristics in relation to current) Type B - general duty, most common Type B limits inrush of current (Type A does not, which can cause
problems with sizing the starter)
Frame NEMA dimensions for replacement across mfrers (The frame size sets
important mounting dimensions such as foot hole mounting pattern, shaft diameter, and shaft height. NEMA standards do not set some dimensions that can turn out to be important if the motor must fit into a confined space.)
22
What Do All Those Things on an AC Motor Nameplate Mean?
Have you ever ordered a motor on power, speed, and enclosure? PO says maybe "5 hp, 1,800 rpm, TEFC." New-motor nameplate says "HP 5, RPM 1748, Enclosure TEFC, Des B, Frame 184T, Amps 7.0, PH 3, HZ 60, Duty Cont, Volts 460, Type P, Amb 40 C, SF 1.15, INS CL F, EFF 82.5, P.F. 80, DE bearing 35BC02JGG30A26, ODE bearing 3OBC02JGG3OA26."
Should you reject the motor because it is not rated at 1,800 rpm? What does all that extra information on the nameplate mean? Do you care? The answers are "maybe," "we'll discuss it in a minute," and "you probably should."
23
Electric Motor Nameplate Data (Continued) We are teaching this for 2 reasons:
1. So you understand motors and their ratings
2. You have to get the information off of one nameplate of a motor at your facility. Preferably a large motor
Important: A motor with an efficiency of 84% is “average to low” efficiency. On the low end of the “average scale”
Important: Calculate the amount of power that a motor draws
We know: Power = Volts x Current (Watts= Volts x Amps)
The maximum power a motor can draw = Volts x Maximum Current
What do you need from the Nameplate?
Answer: Rated Voltage and Rated Current
24
Motors Starting and Protection
• Current Inrush – short duration high amperage (LRA).
• Safely connect and disconnect motor circuit on control signal
• Need to protect motor from extreme overheating, from any of various sources: • Rotor jammed (alignment, bearings) • Excess load • Load (pump or fan) bound • Shaft bound • Under-voltage
Motor Starter
25
Motors Starter Provides start relaying from controls
Power circuit “pulls in” via electromagnetic coil on call from lower voltage control circuit
Regulates starting power inrush larger motors (“soft-start” and solid-
state) Soft start starts a motor gently;
regulates power “rushing” into motor so as not to be abrupt. This reduces motor wear and power usage
Protects against thermal overloads Excessive load conditions Low-voltage conditions (P = A x V) Transients
Motor Starter
26
Motor Starters, Continued
3 leads of electricity to a motor
From left to right – symbols:
Lead connection – 3 phases
Contacts of breaker
Contacts of overload device
Temp sensor of overload device
The motor
27
Belts: Common Cause of Energy Waste
• Pulley and sheave need to be in good alignment
• Loose belts slip, so power is not delivered to load – wastes energy. • Adjust to
proper tension. • Consider “low-
slip” belts.
Belts are most common form of connecting motor shaft to load (pump or fan). Pulley and sheave sizes provide means of setting motor speed.
How do you check alignment? Tension?
28
Motors: Common causes of early failure • Bearings (lubrication)
• Shaft Alignment, belts
• Movement and vibration (supports)
• Extended over-load (high amperage)
• Excessive start-stop (load short-cycling)
• poor air flow/blockage (from dirt, dust)
• phase imbalance, low voltage
• loose connections
Biggest enemy is over-heating, that can be from various sources – mechanical and/or electrical
29
Discuss: Common causes of early failure and what you see in the field
What kinds of problems do you experience with motors?
What kinds of routine observations, adjustments and maintenance do you perform?
Do you have regularly scheduled maintenance? Maintenance triggered by certain observations? Do you have a maintenance check-list?
30
Checklist of Maintenance Practices for Motors
Check for over-loading. Periodically check and record Amps with a multi-meter.
Lubricate. Manufacturers provide recommendations for how and when to lubricate. Noise can indicate binding from misalignment or bearing failure.
Inspect electrical connections at the motor and starter to be sure that they are clean and tight. (Thermograph scan)
Check shaft and belts for alignment, tension.
Provide good ventilation to dissipate heat. Remember: for every 20°F increase in motor operating temperature, motor life is estimated to be halved
31
Motor Maintenance Knowledge Check
Check for rated ‘Amps’ – Use a Clamp On Ammeter to check the current to the motor does not exceed the rated ‘Amps’ of the motor.
Ask: What happens to a motor that is blocked with dust or has no air circulation through it?
32
Good Checklist – Found at http://www1.eere.energy.gov/femp/pdfs/OM_9.pdf
33
Motors Schedule – Manage Your Motors
• Collect motor information to help you understand your facility’s largest energy users (Big Loads) and your Peak Demand
• Collect motor information to help you select the best motors when a replacement is needed ; will help you develop inventory of building motors to speed replacement
• Motor Master – Free software to select the best motors: www.eere.energy.gov
LOAD LOCATION, DESCRIPTION HP V A Ph KW, connected TIME OF OPER KW, on-
peak OPER HRS/YR KWH /YR
34
Exercise: Create a Motor Schedule from the following facility description
Rooftop exhaust fans: 5, each with 0.5 HP motor
4 Air Handlers: each with 20 HP fan motor
Boiler with 5 HP burner fan motor and 1.5 HP oil pump motor
Hot Water Circulator: 2 pumps, each 10 HP, alternated
Chilled Water: 2 pumps, each 10 HP, alternated
Condenser Loop: 2 pumps, each 10 HP, lead-lag
Cooling Tower: 3 cells, each fan with 5 HP motor, lead-lag
Water Pressurization: 3-pump station, 1.5 HP (lead) + 2 – 5 HP
Hot Water Re-circulation: 1 – 1.5 HP pump
35
MotorMaster (type it into Google and go to page on www.eere.energy.gov) o Free software o Database of 25,000 available electric motors,
efficiencies and prices o User enters current motor inventory and utility rates o MotorMaster recommends replacement units based on
lifecycle savings, added resources at • Link to Motor Payback Calculator (online tool)
Motor Replacement Plan
36
BREAK
37
Motor Sizing and its Implications
Motors are typically over-sized, for their loads (pumps, fans). Further, Pumps or fans are typically over-sized for their loads. The result is significant motor over-sizing. This has implications for efficiency, power consumption, and possibilities for motor speed reduction.
38
Motor Efficiency vs. Load
Motor efficiency drops off at part-loads, but not severely until very light loads Larger motors generally hold their efficiencies better at part loads.
39
Load Factor • Indicates how much of Rated Output (HP), the motor is
actually doing to satisfy its load.
• Can be measured by motor “slip” (rpm) or by amperage.
• A motor draws only as much power as it needs to satisfy its load. So, if we use a clamp-on amp meter on a motor rated for 10 amps and the meter reads 7 amps, the motor is running at a 70% load factor.
• Because of this, using Rated Output or Rated Power to calculate motor energy can significantly over-estimate actual usage (and potential savings). It is important to establish Load Factors when assessing large motors. Question for discussion: What happens if a motor is run
without Load?
40
Quantification of Motor Energy Performance
• This section deals with calculating: • Load Factor • HP to KW • KWs/KWHs • Savings resulting from reduced operation • Determining load, if you have other info
• A most useful conversion factor is
>1 HP = 746 watts = .746 KW
40
41
MOTOR CALCULATION FORMULAE 1 HP = .746 KW Motor KW = [rated HP x .746 x Load Factor] / motor Efficiency Motor Load Factor (%)
“Slip Method” LF (%) = [(Synchronous speed – Tested Speed) / (Synch Speed – Rated Speed)] x 100
(synchronous speeds, 1800 4-pole, 3600 2-pole)
“Amperage Method”
LF (%) = Tested amperage / Rated amperage
Motor KW from Amperage and Voltage Measurement (use if HP is not available) KW = [V x A x Power Factor / 1,000 (single-phase) KW = [V x A x Power Factor x 1.73 / 1,000 (three-phase)
Assume Power Factor = .80 if no other information is available
Motor Energy Consumption KWH= Motor KW x Operating Hours
Herzog simplified formula: Motor KW = HP x .55
load factor = .6 Efficiency = .8
.55 = (.746 x .6) / .8
42
Quantification - Motors Example of Savings from reduction of operating hours
> Assume 170 days per year, 100 heating-days per year
Motors: 20 HP fan motor, 62% load factor, 84% efficiency Shut-down for 2 hours per day (1 hp = 0.55 kW)
Energy Saved = Rate of Use x Reduction of Hours of Use Energy Saved = kilo-Watts x Reduction of Hours of Use
= [ 20 HP x .55 ] x 2 x 170 = 3,740 KWH
42
There are 3 basic steps to solve this problem: Convert HP to kW Energy = kW x hours = kW-hrs Find the savings in kW-hrs
43
Load Factor and Motor Size Reduction
Low load factor indicates that motor can probably be down-sized. Reducing HP yields equivalent energy savings. Be careful that the load is not variable.
Conduct a load study to determine if a motor can be down-sized. The load study should include the driven-device (fan, pump) loading as well. It may also be possible to “trim” the pump impeller, reducing flow and motor load.
Re-sizing should be part of any planned approach to change-out of motors for higher efficiency.
44
Motor Size Reduction vs Speed Control
Slowing down a driven-device and its motor is another way to address over-sizing.
Look for throttled pumps or fans as for speed control. • If continuously throttled, belt-driven equipment can be slowed down
by changing the pulleys and sheaves. • If the load varies, then control speed by application of Variable
Frequency Drive (VFD), a solid-state control addition.
Energy reduction is a cubic function of speed reduction, so energy saving potential is very large.
• VFD and the calculation of their energy savings is considered as a BOC Level-2 topic.
• But see the handy chart in Herzog, page XX
45
SUGGESTION FOR PROJECT #4
Identify one or more significant motors in your facility.
Develop a plan to measure key operating characteristics and calculate (baseline) energy usage.
Identify a strategy for improving motor energy performance (simply changing to higher efficiency models without confirming sizing and operating hours is not sufficient)
Calculate the savings associated with the changes you identify.
46
Closing: Some Guidelines for efficient motor operations in HVAC systems. From: FEMP 9.10.5 • Turn off unneeded motors
• Reduce motor system usage • Reducing load in building
• For example, reducing solar load on a building will reduce the amount of time the air handler motors would need to operate
• Efficiency of mechanical systems affects run-time of motors. For example, • Check ventilation systems for excessive air
• Repair duct leaks • Re-sheave fan if air is excessive
• Improve compressed air systems • Locate and repair compressed air leaks
47
FEMP 9.10.5 - Guidelines for efficient Motor operations (cont’d) • Sizing motors is important – Do not assume an existing
motor is properly sized for its load, especially when replacing motors. • Identify actual motor loading. There are several ways to
estimate actual motor loading -See MotorMaster software (MotorMaster www.eere.energy.gov)
• Downsize motors, if possible Many motors operate most efficiently at 75% to 85% of full load rating. Under-sizing or over-sizing reduces efficiency.
• Replace motors with an energy-efficient version
48
Lessons to Take Home to Your Facility
• Even a seemingly modest (small) increase in motor efficiency can lead to measurable (often large) reductions in energy use and costs.
• Overheating is the largest contributing factor for premature motor failure – make every effort to ensure your motors do not overheat.
• Are my motor maintenance practices up to snuff? Should I be adding procedures?
• Do I have or should I consider creating a motor schedule for my facility?
49