building service chapter 1

44
PSMZA Course Note (Chapter 1) Ver. 1 (MSH-Jun2013): CC608 Building Services 1 1.0 ELECTRICAL INSTALLATION SYSTEM IN THE BUILDING Electrical wiring in general refers to insulated conductors used to carry electricity, and associated devices. Electrical wiring as used to provide power in buildings and structures, commonly referred to as building wiring. 1.1 Basic Concept of Electrical Power Supply Electricity generation is the process of generating electrical power from other sources of primary energy. The fundamental principles of electricity generation were discovered during the 1820s and early 1830s by the British scientist Michael Faraday. His basic method is still used today: electricity is generated by the movement of a loop of wire, or disc of copper between the poles of a magnet. For electric utilities, it is the first process in the delivery of electricity to consumers. The other processes, electricity transmission, distribution, and electrical power storage and recovery using pumped-storage methods are normally carried out by the electric power industry. Electricity is most often generated at a power station by electromechanical generators, primarily driven by heat engines fueled by chemical combustion or nuclear fission but also by other means such as the kinetic energy of flowing water and wind. Other energy sources include solar photo-voltaic and geothermal power. There are seven fundamental methods of directly transforming other forms of energy into electrical energy: i. Static electricity, from the physical separation and transport of charge. ii. Electromagnetic induction, where an electrical generator, dynamo or alternator transforms kinetic energy (energy of motion) into electricity. This is the most used form for generating electricity and is based on Faraday's law. iii. Electrochemistry, the direct transformation of chemical energy into electricity, as in a battery, fuel cell or nerve impulse iv. Photoelectric effect, the transformation of light into electrical energy, as in solar cells v. Thermoelectric effect, the direct conversion of temperature differences to electricity, as in thermocouples, thermopiles, and thermionic converters. vi. Piezoelectric effect, from the mechanical strain of electrically anisotropic molecules or crystals. vii. Nuclear transformation, the creation and acceleration of charged particles. Static electricity was the first form discovered and investigated, and the electrostatic generator is still used even in modern devices such as the Van de Graaff generator. Charge carriers are separated and physically transported to a position of increased electric potential. Almost all commercial electrical generation is done using electromagnetic induction, in which mechanical energy forces an electrical generator to rotate. There are many different methods of developing the mechanical energy, including heat engines, hydro, wind and tidal power.

Upload: izam-lukman

Post on 18-Jul-2015

204 views

Category:

Engineering


24 download

TRANSCRIPT

Page 1: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 1

1.0 ELECTRICAL INSTALLATION SYSTEM IN THE BUILDING Electrical wiring in general refers to insulated conductors used to carry electricity, and

associated devices. Electrical wiring as used to provide power in buildings and structures, commonly referred to as building wiring.

1.1 Basic Concept of Electrical Power Supply Electricity generation is the process of generating electrical power from other sources of

primary energy.

The fundamental principles of electricity generation were discovered during the 1820s and early 1830s by the British scientist Michael Faraday. His basic method is still used today: electricity is generated by the movement of a loop of wire, or disc of copper between the poles of a magnet.

For electric utilities, it is the first process in the delivery of electricity to consumers. The other processes, electricity transmission, distribution, and electrical power storage and recovery using pumped-storage methods are normally carried out by the electric power industry.

Electricity is most often generated at a power station by electromechanical generators, primarily driven by heat engines fueled by chemical combustion or nuclear fission but also by other means such as the kinetic energy of flowing water and wind. Other energy sources include solar photo-voltaic and geothermal power.

There are seven fundamental methods of directly transforming other forms of energy into electrical energy:

i. Static electricity, from the physical separation and transport of charge. ii. Electromagnetic induction, where an electrical generator, dynamo or alternator

transforms kinetic energy (energy of motion) into electricity. This is the most used form for generating electricity and is based on Faraday's law.

iii. Electrochemistry, the direct transformation of chemical energy into electricity, as in a battery, fuel cell or nerve impulse

iv. Photoelectric effect, the transformation of light into electrical energy, as in solar cells v. Thermoelectric effect, the direct conversion of temperature differences to electricity,

as in thermocouples, thermopiles, and thermionic converters. vi. Piezoelectric effect, from the mechanical strain of electrically anisotropic molecules or

crystals. vii. Nuclear transformation, the creation and acceleration of charged particles.

Static electricity was the first form discovered and investigated, and the electrostatic

generator is still used even in modern devices such as the Van de Graaff generator. Charge carriers are separated and physically transported to a position of increased electric potential.

Almost all commercial electrical generation is done using electromagnetic induction, in which mechanical energy forces an electrical generator to rotate. There are many different methods of developing the mechanical energy, including heat engines, hydro, wind and tidal power.

Page 2: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 2

The direct conversion of nuclear potential energy to electricity by beta decay is used only on a small scale. In a full-size nuclear power plant, the heat of a nuclear reaction is used to run a heat engine. This drives a generator, which converts mechanical energy into electricity by magnetic induction.

Most electric generation is driven by heat engines. The combustion of fossil fuels supplies most of the heat to these engines, with a significant fraction from nuclear fission and some from renewable sources. The modern steam turbine (invented by Sir Charles Parsons in 1884) currently generates about 80% of the electric power in the world using a variety of heat sources.

Figure 1.1: Source of Energy

Figure 1.2: Stage of electricity

Page 3: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 3

1.1.1 Electrical Distribution There are a few stages to distribute the electric to consumer from generation plant. The

explanation must be referring to the numbers of stage at figure 1.2. 1. The Power Plant: The electricity that used at home starts its journey at the power

plant. Normally, the power plant will use a spinning electrical generator to produce its power, though what spins the generator (water, diesel, gas, or steam) varies. Steam turbines, powered by burning natural gas or coal, are the most common generators. Regardless of what type of generator is used, the energy produced is called 3-phase AC power.

2. The Transmission Substation: The 3-phase power travels from the generator to a nearby transmission substation. Here, the substation converts the generator’s voltage, which is on the order of thousands, up to the levels needed for long distance travel, which is on the scale of hundreds of thousands, using large transformers.

3. The Transmission Lines: Once the voltage is increased to the appropriate levels, electricity runs along transmission lines for up to 3000 km.

4. The Distribution Substation: However, before the electricity is usable in a home or business the voltage must be reduced to manageable levels, which is accomplished at a distribution substation. This substation also has a “distribution bus” that splits the power in multiple directions, and breakers that can disconnect it from the transmission lines and/or specific distribution lines.

5. Into Your Home/Factory: From the distribution substation power runs through regulator banks (which prevents overcharges), taps (which separate out the phases), and finally into a transformer drum on top of a power pole outside your house. The transformer drum’s job is to reduce the voltage from 7,200 volts to 240 volts/415volts which is what most houses/factory use. From there the power travels through your meter and into home/factory.

1.2 Electrical Power Supply: Single Phase and Three Phase The phase voltage is a voltage between any one conductor and ground. Electricity

supply for domestic consumers, according to MS IEC 60038 standards, meets the following specifications:

i. Single phase supply with nominal voltage of 230V, range +10%, -6% ii. Three phase supply with nominal voltage of 400V, range +10%, -6% iii. Permitted frequency is 50Hz +1% iv. Earthing system type (TT System) as in Figure 1.3 and figure 1.4.

All electrical equipment used must be suitable for operation with the stated

electricity supply specifications.

Figure 1.3: Single phase power Figure 1.4: Three phase power

Page 4: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 4

1.2.1 Single Phase Power Supply Single-phase wire has three wires located within the insulation. Two hot wires and one

neutral wire provide the power. Each hot wire provides 120 volts of electricity. The neutral is tapped off from the transformer. A two-phase circuit probably exists because most water heaters, stoves and clothes dryers require 240 volts to operate. These circuits are fed by both hot wires, but this is just a full phase circuit from a single-phase wire.

Every other appliance is operated off of 120 volts of electricity, which is only using one hot wire and the neutral. The type of circuit using hot and neutral wires is why it is commonly called a split-phase circuit. The single-phase wire has the two hot wires surrounded by black and red insulation, the neutral is always white and there is a green grounding wire.

1.2.2 Three Phase Power Supply A continuous series of three overlapping AC cycles offset by 120 degrees. Three-phase

power is used for all large scale distribution systems. The most common form of AC power for distribution. Three-phase power has three overlapping AC cycles offset by 120 degrees.

In electrical engineering, three-phase electric power systems have at least three conductors carrying alternating current voltages that are offset in time by one-third of the period. A three-phase system may be arranged in delta (∆) or star (Y) (also denoted as wye in some areas). A wye system allows the use of two different voltages from all three phases, such as a 230/400V system which provides 230V between the neutral (centre hub) and any one of the phases, and 400V across any two phases.

A delta system arrangement only provides one voltage magnitude, however it has a

greater redundancy as it may continue to operate normally with one of the three supply windings offline, albeit at 57.7% of total capacity. Harmonic currents in the neutral may become very large if non- linear loads are connected.

Figure 1.5: Home wiring

Page 5: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 5

1.2.3 The Differences between Single and Three Phase Power Supply The difference between three phase and single phase is primarily in the voltage that is

received through each type of wire. There is no such thing as two-phase power, which is a surprise to some people. Some ways to determine whether three-phase wire or single-phase wire.

Table 1.1: Differences between single phase and three phase

No Item Single Phase Three Phase

1 Phase name

Commonly called "split-phase." It’s called three phase

2 Suitable Suitable for low electricity load More efficient than single-phase power

3 Cable Two cables power supply Four cables power supply

4 Connecting One hot wire and one neutral Three hot wires and one neutral

5 Cable color Other once red/blue/black chose for

hot wire. Red, blue and black connecting for hot

wire

6 Voltage Carry 240 Volts Carry 415 Volts

7 Wave shape

8 Power supply

connection

Figure 1.6: One voltage cycle of a three phase system

Page 6: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 6

1.3 Electrical Wiring System Electrical wiring in general refers to insulated conductors used to carry electricity, and

associated devices. This article describes general aspects of electrical wiring as used to provide power in buildings and structures, commonly referred to as building wiring. Regulation 11(1) of the Electricity Regulations 1994 states that all wiring or rewiring of an installation or extension to an existing installation, which shall be carried out by an Electrical Contractor or a Private Wiring Unit, have to obtain the approval in writing from a licensee or supply authority.

Electrical wiring composes of electrical equipment such as cables, switch boards, main switches, miniature circuit breakers (MCB) or fuses, residual current devices (RCD), lighting points, power points, lightning arrestors.

Figure 1.7: Single phase wiring schematic

Page 7: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 7

1.3.1 Consumer Unit Wiring Circuit System

A consumer unit is a type of distribution board (a component of an electrical power system within which an electrical power feed provides supply to subsidiary circuits). A particular type of distribution board comprising a type-tested coordinated assembly for the control and distribution of electrical energy, principally in domestic premises, incorporating manual means of double-pole isolation on the incoming circuit(s) and an assembly of one or more fuses, circuit breakers, residual current operated devices or signaling and other devices proven during the type-test of the assembly as suitable for use.

Figure 1.8: Three phase wiring schematic

Page 8: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 8

See on figure 1.9 above, in an example typical new town house wiring system, there have: i. Live & Neutral tails from the electricity meter to the CU. ii. A split load CU. iii. Ring circuits from 32A MCBs in the CU supplying mains sockets. 2 such rings is typical

for a 2 up 2 down, larger houses have more. iv. Radial lighting circuits from 6A CU MCBs. 2 or more circuits typical. v. Earth connection from incomer to CU. vi. 10mm² main equipotential bond to other incoming metal services (gas, water, oil).

Systems often have some of the following as well: i. Dedicated circuit MCB & cable supplying cooker. ii. Dedicated high current circuit MCB & cable supplying shower iii. 2 way lighting switching for stairs, large rooms & walk through rooms iv. Outdoor lighting supplied by a 6A MCB, often via a PIR motion detector switch. v. 16A MCB and cable supplying hot water immersion heater. vi. A high current MCB supplying storage heater. Sometimes these are run from the main

CU, but often from a time-switch controlled dedicated CU (with either a separate "off peak" electricity meter, or a dual tariff meter).

The radial lighting circuit has 3 common wiring options, which may be mixed at will: i. "Loop-in". The circuit is fed to each lamp fitting in turn, and a separate cable connects

from the fitting to the switch. (this is the most common method). ii. Switch loop through (the circuit connects to each switch in turn, and a separate cable

goes from the switch to each lamp). iii. Junction box loop in, where the termination and feed connection are done at junction

boxes, and cables run to switches and lamps from there.

The diagram is shown with 6A lighting fuse and 32A ring circuit MCB. Other options are also possible: 20A radial socket circuits and 10A lighting circuits are occasionally used

Figure 1.9: Consumer circuit

Page 9: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 9

i. Plug A fitting, commonly with two metal prongs for insertion in a fixed socket, used to

connect an appliance to a power supply. AC power plugs and sockets are devices that allow electrically operated equipment to be connected to the primary alternating current (AC) power supply in a building. Electrical plugs and sockets differ in voltage and current rating, shape, size and type of connectors. The types used in each country are set by national standards,

Generally the plug is the movable connector attached to an electrically operated

device's mains cable, and the socket is fixed on equipment or a building structure and connected to an energized electrical circuit. The plug has protruding prongs, blades, or pins (referred to as male) that fit into matching slots or holes (called female) in the sockets. Sockets are designed to prevent exposure of bare energized contacts. Sockets may also have protruding exposed contacts, but these are used exclusively for earthing (grounding).

These are the three colour wires, what they mean and where they are in the opened

plug. a. Blue – Neutral (found on the left side) b. Yellow and green – Earth (found at the top) c. Brown – Live – (Found on the right and the one the fuse is connected too) An older appliance the wires may be different as so: a. Black – Neutral (found on the left side) b. Green – Earth (found at the top) c. Red – Live (Found on the right and the one the fuse is connected too)

Figure 1.10: Plug

Page 10: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 10

ii. Socket Sockets may be wired on ring circuits or radial circuits. Mostly rings are used, as they

use less copper for most circuit layouts, they have safety advantages over radial circuits (sometimes debated), can provide more power, and cover more floor area per circuit. The types of socket circuits were:

a. Ring

Sockets are on 32A ring circuits in most house installations. These use a ring of cable (ie a loop), so that at the CU 2 cables are connected to the MCB instead of 1. An unlimited number of sockets may be connected on each ring. One ring circuit per floor is a fairly common arrangement, but by no means the only option. Larger houses generally have more rings. Its also common to have a ring dedicated just for sockets in the kitchen since that is where you will find many of the highest power consuming appliances in a modern house. 2.5mm² cable is usually used for ring circuits. 4mm² is used when cable will be under insulation or bunched with other cables.

b. Spurs Spurs are permitted, but sockets should be included in the ring rather than spurred wherever practical. Spurring is best only used for later additions to circuits. Rules apply to the loading and number of sockets allowed on the end of a spur.

Spurring sockets prevents the easy later addition of more sockets in some positions, as a spur may not be spurred off a spur. Spurs also prevent the addition of more sockets at existing spurred positions, whereas a practically unlimited number of sockets can be added where a socket is in the ring. Bear in mind the number of sockets wanted has risen greatly over the years, and can only be expected to rise further.

c. Radial Radial socket circuits are used less often. These use a single cable from CU to socket, then a single cable to the next socket along the line etc. Radials use more copper on most circuits, though less cable on physically long narrow shaped circuits. Connection faults have greater consequences than with ring circuits. (Confusion over the relative safety of ring & radial circuits is widespread.)20A radials use 2.5mm² or 4mm² cable. 32A radials use 4mm² cable.

Figure 1.11: T-junction outlet socket

Page 11: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 11

iii. Lighting circuit Suruhanjaya Tenaga Malaysia was suggested the lighting circuit at the consumer circuit

must be referring to table 1.2 below.

Table 1.2: Examples of single –phase schematic circuit for lamp

No Types of switch and lamp Diagram

1 1 lamp control by 1 switch

1-way switch

2 2 lamp control by 1 switch

1-way switch

3 2 lamp control by 2 location

1-way switch

4 1 lamp control by 2 switch

2-way switch

5

3 lamp control by 2 switch

2-way switch and intermediate switch

6

1 lamp fluorescent control by 1 switch

1-way switch

Page 12: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 12

1.3.2 Electrical Wiring Installation Factors

To choose the type of wiring to be use has considered a few factors. The factors were: i. Types of place to installation: to determine the routing of wiring, connections and

terminations. ii. Types of electrical load: the installed capacity of electric cables must be compatible with

electrical load iii. Cost: overall cost of a wiring and financing capabilities. iv. Neatness: identifies whether the installation of the wiring system suitable for surface or

concealed wiring. v. Safety and approval by LLN/JKR: installation routing paths taking into account the

situation and circumstances that can prevent from potential danger. vi. Effectiveness: power supplies can be distributed to electrical appliances with the

appropriate voltage. vii. Flexibility to the system: can change the position and orientation of the equipment as well

as machinery and temporary buildings. viii. Ambient temperature: taking into account the type of installation if the boiler room or

assembly heat treatment. ix. Installation Method - protection against possible mechanical requirements and height at

work. x. Durability: the long life span of the installation. xi. Environment: made an assessment of the environment so that the owner obtain the

optimum value from the electrical installation. xii. Installation period: with short installation period, it will save you the cost of installation. xiii. Easy for wiring extension if there are building renovation for the future.

Figure 1.12: Electrical wiring illustration

Page 13: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 13

1.3.3 Types of Electrical Wiring System There are a few types of wiring system to install in the building. It’s were: i. Open/Surface Wiring System

A network of electrical wiring that is not concealed by the structure of a building, but is protected by cleats, flexible tubing, knots, and tubes, which also support its insulated conductors. Surface wiring system is a system where the cables used in an installation that is installed on the wall or ceiling without any additional protection. The features of open/surface wiring system were: i. Single-phase supply voltage ii. Buildings is made of wood or stone iii. Low the installation cost iv. Less of cable in the final circuit to be installed v. Minimized cause of mechanical lacking damage vi. Less time to complete the installation vii. Suitable for low electrical consumer load

ii. Hidden Wiring System Circuit cables installed in walls or ceilings and are not visible directly, but the end of

the cable used to connect to the terminal. The features of hidden wiring system were: i. Single-phase supply voltage ii. Building is made of brick or cement iii. Neatness and beautiful buildings required iv. Mechanical damage can be minimized v. Less of cable in the final circuit to be installed vi. Longer cable resistance required vii. Suitable for low electrical consumer load

Clip

Meranti wood

Limited to12

cables

Figure 1.13: Surface wiring system

Figure 1.14: Hidden wiring system

Page 14: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 14

iii. Conduit Wiring System Use a system-conduit and conduit will be installed into the wall or the like and in it will

be channeled cable. a. There are too much cause of mechanical breakdown on a building b. Need a good grounding or earthing system c. Need the new addition circuits for the future if there are building extension d. Suitable for 1 phase and 3 phase supply voltage e. The power rate installed was greater than electrical load

iv. Overhead Catenaries Wiring Support System Overhead Catenaries supporters wiring system is a system that is rarely used today.

But in a situation of this system is still needed. The features of this system were: a. When the building or hall ceiling is too high b. There are center of wiring in the building c. Also installed at the livestock barn d. Supply cable connection between the two buildings e. There are outdoor obstruction areas

Figure 1.14: Conduit wiring system

Figure 1.15: Overhead canaries wiring support system

Page 15: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 15

v. Trunking Wiring System Trunking wiring system is a system that uses mains metal or insulating materials are

usually rectangular and mounted vertically or horizontally on the wall or the metal frame of the building. The features for this system were: a. Suitable for single phase and 3 phase supply voltage b. Used foe large buildings and multi-storey c. A lot of cable required d. Need the new addition circuits for the future if there are building extension e. Greater cable safety and mechanical protection required

vi. Ducting Wiring System Ducting wiring system is a system that uses a metal duct or insulating material and

mounted under the floor during the construction of the building. The features were: i. Suitable for single phase and 3 phase supply voltage ii. A lot of cable required iii. Need the new addition circuits for the future if there are building extension iv. Allowed the possibility of making changes in the load position in the future v. Requires regular arrangement of devices or straight of tables vi. Need a neatness and good finishing installation vii. Greater cable safety and mechanical protection required

Figure 1.16: Trunking wiring system

Figure 1.17: Ducting wiring system

Page 16: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 16

1.4 Conductor, Insulator and Protection in the Electrical Wiring System

1.4.1 Conductor In physics and electrical engineering, a conductor is an object or type of material which

permits the flow of electric charges in one or more directions. In metals such as copper or aluminum, the movable charged particles are electrons. Positive charges may also be mobile, such as the cationic electrolyte(s) of a battery, or the mobile protons of the proton conductor of a fuel cell. Insulators are non-conducting materials with few mobile charges and which support only insignificant electric currents.

All conductors contain electrical charges, which will move when an electric potential difference (measured in volts) is applied across separate points on the material. This flow of charge (measured in amperes) is what is meant by electric current. In most materials, the direct current is proportional to the voltage (as determined by Ohm's law), provided the temperature remains constant and the material remains in the same shape and state.

Copper is the most common material used for electrical wiring. But silver is the best conductor, but it is expensive. Because gold does not corrode, it is used for high-quality surface-to-surface contacts. However, there are also many non-metallic conductors, including graphite, solutions of salts, and all plasmas. There are even conductive polymers.

Figure 1.18: Flow of electric charge in conductor

Figure 1.18: Conductor

Page 17: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 17

Table 1.3: The resistivity and conductivity of selected 16 materials at 20 °C

No. Material Resistivity

ρ (Ω•m) at 20 °C Conductivity

σ (S/m) at 20 °C

1 Silver 1.59×10-8 6.30×107

2 Copper 1.68×10-8

5.96×107

3 Annealed copper 1.72×10-8

5.80×107

4 Gold 2.44×10-8

4.10×107

5 Aluminium 2.82×10-8

3.50×107

6 Calcium 3.36×10-8

2.98×107

7 Tungsten 5.60×10-8

1.79×107

8 Zinc 5.90×10-8

1.69×107

9 Nickel 6.99×10-8

1.43×107

10 Lithium 9.28×10-8

1.08×107

11 Iron 1.00×10-7

1.00×107

12 Platinum 1.06×10-7

9.43×106

13 Tin 1.09×10-7

9.17×106

14 Carbon steel (1010) 1.43×10-7

6.99×106

15 Lead 2.20×10-7

4.55×106

16 Titanium 4.20×10-7

2.38×106

Table 1.4: Conductor size and circuit breaker capacity

Capacity (A) Main conductor size

mm2 (copper)

Earth conductor size mm

2 (copper)

Circuit breaker capacity

Up to 600 W 1.5 1.5 5A

600-1200 W 1.5/2.5 1.5 10A

1200-1800 W 2.5/4.0 2.5 15 A

Ring circuit (floor area 100 m

2)

4.0 4.0 30/32A

A2 Radial Circuit (floor area 50 m

2)

4.0 4.0 30/32A

A3 Radial Circuit (floor area 20 m

2)

2.5 2.5 20 A

Air conditioner (1.5 ton) 6.0 6.0 30/32A

Cooker 6.0 6.0 30/32A

Water Heater 4.0 4.0 20A

Page 18: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 18

1.4.2 Insulator An electrical insulator is a material whose internal electric charges do not flow freely, and

which therefore does not conduct an electric current, under the influence of an electric field. A perfect insulator does not exist, but some materials such as glass, paper and teflon, which have high resistivity, are very good electrical insulators. A much larger class of materials, even though they may have lower bulk resistivity, are still good enough to insulate electrical wiring and cables. Examples include rubber-like polymers and most plastics. Such materials can serve as practical and safe insulators for low to moderate voltages.

Insulators are used in electrical equipment to support and separate electrical conductors without allowing current through themselves. An insulating material used in bulk to wrap electrical cables or other equipment is called insulation. The term insulator is also used more specifically to refer to insulating supports used to attach electric power distribution or transmission lines to utility poles and transmission towers.

Electrical insulation is the absence of electrical conduction. Electronic band theory (a

branch of physics) says that a charge will flow if states are available into which electrons can be excited. This allows electrons to gain energy and thereby move through a conductor such as a metal. If no such states are available, the material is an insulator.

Most insulators have a large band gap. This occurs because the "valence" band

containing the highest energy electrons is full, and a large energy gap separates this band from the next band above it. There is always some voltage (called the breakdown voltage) that will give the electrons enough energy to be excited into this band. Once this voltage is exceeded the material ceases being an insulator, and charge will begin to pass through it. However, it is usually accompanied by physical or chemical changes that permanently degrade the material's insulating properties.

Materials that lack electron conduction are insulators if they lack other mobile charges as

well. For example, if a liquid or gas contains ions, then the ions can be made to flow as an electric current, and the material is a conductor. Electrolytes and plasmas contain ions and will act as conductors whether or not electron flow is involved.

Insulator material were :

i. Glass ii. Rubber iii. Oil iv. Asphalt v. Fiberglas vi. Porcelain vii. Ceramic viii. Quartz ix. Dry cotton x. Dry paper xi. Dry wood xii. Plastic xiii. Air xiv. Diamond xv. Pure water

Figure 1.19: Illustration of cable

Page 19: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 19

1.4.3 Electrical Protection System i. The Lighting

One of the most esoteric topics among electrical engineers is the Lightning Protection Systems, more specific lightning rods already mentioned lightings are a very complex natural phenomenon therefore is it difficult to establish and unified criteria, for this reason is that there exists a lot of opinions and strange myths that brings as result wrong lightning protection designs.

Air is not a perfect isolating media, given that

its dielectric resistance is around 30kV/cm, when a potential difference is reach between tow electrical conductor points a spark will occur inevitably (family size, the one we call Lightning).

Depending of the polarization, the lightings are

classified on negatives (electrons or negative charge ions) or positives (positive charged ions), according to its origin figure 1.21 there are inside lightning (inside the cloud), intercloud (from cloud to cloud), clout – earth lightning (80% percent of the lightning produced and therefore the most important to us) and at last earth to cloud lightning.

Despite the short duration that they have (microseconds), lightning’s have a huge

destructive potential given that they carry current around 30 kA typically, up to 300 kA have been register, therefore the necessity of protecting installations and ourselves.

a. Lightning Formation

The lightning (this point forward it will be considered as and cloud to earth and negative) is produced by the union of the ion leaders figure 1.22 the ascendant - up streamer. The descendent - stepped leader, they precisely are the ones that make a ionize row which is used by the lightning to go through figure 1.23. The lightning produces when the ion leaders touch each other as seen in figure 1.24. When a Lightning takes place it drains the negative charge of the cloud, it can occur a several times in a row, that why sometimes it looks like blinking in the sky.

Figure 1.20: The lightning

Figure 1.21: Types of lightning Figure 1.22: Ascendant and descendent

Leader

Page 20: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 20

b. Protection against Atmospheric Discharges Given that a lightning is a natural phenomenon and as one it is unpredictable, it is impossible to avoid its incidence on the structures or people 100% of the times, what a protection system does is attract the lightning that otherwise will strike in an undesired area. The most costumed way to do so is by using lightning rods, the simplest systems consist on a captor element of cooper or one with and equivalent resistance, connected solid to earth trough a isolated download wire.

Figure 1.23: Ionize row for by the ascendant and leader Figure 1.24: Lightning formed

Figure 1.25: Lightning protection

Page 21: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 21

ii. Earthing In electricity supply systems, an earthing system defines the electrical potential of the

conductors relative to the Earth's conductive surface. The choice of earthing system can affect the safety and electromagnetic compatibility of the power supply, and regulations can vary considerably among countries. Most electrical systems connect one supply conductor to earth (ground). If a fault within an electrical device connects a "hot" (unearthed) supply conductor to an exposed conductive surface, anyone touching it while electrically connected to the earth (e.g., by standing on it, or touching an earthed sink) will complete a circuit back to the earthed supply conductor and receive an electric shock.

A Protective Earth (PE), known as an equipment grounding conductor in the US National

Electrical Code, avoids this hazard by keeping the exposed conductive surfaces of a device at earth potential. To avoid possible voltage drop no current is allowed to flow in this conductor under normal circumstances, but fault currents will usually trip or blow the fuse or circuit breaker protecting the circuit. A high impedance line-to-ground fault insufficient to trip the overcurrent protection may still trip a residual-current device if one is present.

In contrast, a functional earth connection serves a purpose other than shock protection,

and may normally carry current. The standard terminology an earthing distinguishes three families of earthing arrangements, using the two-letter codes TN, TT, and IT.

The first letter indicates the connection between earth and the power-supply equipment

(generator or transformer): a. T -Direct connection of a point with earth (Latin: terra) b. I -No point is connected with earth (isolation), except perhaps via a high impedance. The second letter indicates the connection between earth and the electrical device being supplied: a. T -Direct connection of a point with earth b. N -Direct connection to neutral at the origin of installation, which is connected to the

earth

Figure 1.26: Earthing illustration

Page 22: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 22

Table 1.5: Types of earthing circuit

The important of earthing were:

a. In power systems it helps to maintain the voltage of any part of the network at a

definite potential with respect to earth. b. And it allows enough current to flow fast enough under earth fault conditions to

operate the protective devices installed in the circuits. c. Preventing exposed conductive parts of the equipment from rising in potential for a

period sufficient to cause danger from electrocution.

For normal installation practice, earthing is to connect together the exposed conductive parts of various items of the equipment and to a common terminal (main earthing terminal). This in turn is connected by the earthing conductor to an earth electrode, buried in the mass of earth. The earth installation must be capable of carrying the prospective fault currents without danger and without excessive heat. It must have low resistance at all times with good resistance to corrosion.

No Network Circuit

1 TN

TN-S TN-C TN-C-S

Separate protective earth (PE) and neutral (N) conductors from transformer

to consuming device, which are not connected together at any point after the

building distribution point.

Combined PE and N conductor all the way from the transformer to the

consuming device.

Combined PEN conductor from transformer to building distribution

point, but separate PE and N conductors in fixed indoor wiring

and flexible power cords.

2 TT

The protective earth connection of the consumer is provided by a local connection to earth, independent of any earth connection at the generator. Commonly code used in Malaysia country

3 IT

The electrical distribution system has no connection to earth at all, or it has only a high impedance connection. In such systems, an insulation monitoring device is used to monitor

the impedance.

Page 23: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 23

The most important part of the earthing system is the electrodes. Earth electrodes are made from a number of materials like cast iron, steel, copper or stainless steel, and they may be in the from of plates, tubes , rods or strips. The most favored material is copper. It has good conductivity, is corrosion resistance to many of the salts that exist in the soil and it is a material that easily worked.

The earth resistance depends on soil resistivity and characteristics. The types of soil suitable for earth electrode are: -

a. Wet marshy ground b. Clay, loam soil, arable land c. Clayey soil, loam mixed with small quantity of sand d. Damp and wet sand

The site should not be well drained and without flowing water which will wash away the

salt in the soil. Achieving a good earth will depend on local soil condition. Three factors that affect the soil resistivity are:-

a. Moisture content of the soil b. Chemical composition of the soil

iii. Fuses A fuse is a type of low resistance resistor that acts as a sacrificial device to provide

overcurrent protection, of either the load or source circuit. It’s essential component is a metal wire or strip that melts when too much current flows, which interrupts the circuit in which it is connected. Short circuit, overloading, mismatched loads or device failure are the prime reasons for excessive current.

A fuse interrupts excessive current (blows) so that further damage by overheating or

fire is prevented. Wiring regulations often define a maximum fuse current rating for particular circuits. Overcurrent protection devices are essential in electrical systems to limit threats to human life and property damage. The time and current operating characteristics of fuses are used to provide adequate protection without needless

Figure 1.27: Earthing system

Page 24: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 24

interruption. Slow blow fuses are designed to allow harmless short term higher currents but still clear on a sustained overload.

Fuses are manufactured in a wide range of current and voltage ratings to protect

wiring systems and electrical equipment. Self-resetting fuses automatically restore the circuit after the overload has cleared; these are useful, for example, in aerospace or nuclear applications where fuse replacement is impossible. There are three types of fuse, refer table 1.6 below.

Most fuses are marked on the body or end caps with markings that indicate their

ratings. Surface-mount technology "chip type" fuses feature few or no markings, making identification very difficult.

Similar appearing fuses may have significantly different properties, identified

by their markings. Fuse markings will generally convey the following information, either explicitly as text, or else implicit with the approval agency marking for a particular type:

a. Ampere rating of the fuse b. Voltage rating of the fuse c. Time-current characteristic; i.e. fuse speed. d. Approvals by national and international standards agencies e. Manufacturer/part number/series f. Breaking capacity Fuses come in a vast array of sizes and styles to serve in many applications,

manufactured in standardized package layouts to make them easily interchangeable. Fuse bodies may be made of ceramic, glass, plastic, fiberglass, molded mica laminates, or molded compressed fiber depending on application and voltage class.

Cartridge (ferrule) fuses have a cylindrical body terminated with metal end caps.

Some cartridge fuses are manufactured with end caps of different sizes to prevent accidental insertion of the wrong fuse rating in a holder, giving them a bottle shape.

Fuses for low voltage power circuits may have bolted blade or tag terminals which are

secured by screws to a fuse holder. Some blade-type terminals are held by spring clips. Blade type fuses often require the use of a special purpose extractor tool to remove them from the fuse holder.

Renewable fuses have replaceable fuse elements, allowing the fuse body and

terminals to be reused if not damaged after a fuse operation. Fuses designed for soldering to a printed circuit board have radial or axial wire leads. Surface mount fuses have solder pads instead of leads.

High-voltage fuses of the expulsion type have fiber or glass-reinforced plastic tubes

and an open end, and can have the fuse element replaced. Semi-enclosed fuses are fuse wire carriers in which the fusible wire itself can be

replaced. The exact fusing current is not as well controlled as an enclosed fuse, and it is extremely important to use the correct diameter and material when replacing the fuse wire, and for these reasons these fuses are slowly falling from favor. Current ratings refer tble 1.7 below.

Page 25: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 25

Table 1.6: Types of fuse

No. Type of fuse Diagram

1 Wire

2 Domestic

Cartridge

Over current fuse

Miniature time delay

fuse

3 High voltage

Page 26: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 26

Some types of circuit breakers must be maintained on a regular basis to ensure their mechanical operation during an interruption. This is not the case with fuses, which rely on melting processes where no mechanical operation is required for the fuse to operate under fault conditions. In a multi-phase power circuit, if only one fuse opens, the remaining phases will have higher than normal currents, and unbalanced voltages, with possible damage to motors. Fuses only sense overcurrent, or to a degree, over-temperature, and cannot usually be used independently with protective relaying to provide more advanced protective functions, for example, ground fault detection. Some manufacturers of medium-voltage distribution fuses combine the overcurrent protection characteristics of the fusible element with the flexibility of relay protection by adding a pyrotechnic device to the fuse operated by external protective relays.

Table 1.7: Fuse rating versus wire diameter

Fuse wire rating (A) Cu Wire diameter (mm)

3 0.15

5 0.2

10 0.35

15 0.5

20 0.6

25 0.75

30 0.85

45 1.25

60 1.53

80 1.8

100 2

Page 27: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 27

iv. Circuit breaker A circuit breaker is an automatically operated electrical switch designed to protect an

electrical circuit from damage caused by overload or short circuit. Its basic function is to detect a fault condition and interrupt current flow.

Unlike a fuse, which operates once and then must be replaced, a circuit breaker can

be reset (either manually or automatically) to resume normal operation. Circuit breakers are made in varying sizes, from small devices that protect an individual household appliance up to large switchgear designed to protect high-voltage circuits feeding an entire city. Types of circuit breaker:

a. Low-voltage circuit breakers - Molded Case Circuit Breaker –MCCB 2500A - Miniature Circuit Breaker – MCB 100A

b. Magnetic circuit breakers c. Thermal magnetic circuit breakers d. Common trip breakers e. Medium-voltage circuit breakers f. High-voltage circuit breakers g. Residual-current device RCD or Residual Current Circuit Breaker (RCCB) h. Residual current breaker with over-current protection (RCBO) i. Earth leakage circuit breaker (ELCB) The sample design miniature circuit breaker components above: 1. Actuator lever - used to manually trip and reset the circuit breaker. Also indicates

the status of the circuit breaker (On or Off/tripped). Most breakers are designed so they can still trip even if the lever is held or locked in the "on" position. This is sometimes referred to as "free trip" or "positive trip" operation.

2. Actuator mechanism - forces the contacts together or apart. 3. Contacts - Allow current when touching and break the current when moved apart. 4. Terminals 5. Bimetallic strip. 6. Calibration screw - allows the manufacturer to precisely adjust the trip current of

the device after assembly. 7. Solenoid 8. Arc divider/extinguisher

Figure 1.28: Two-poll miniature circuit breaker

Page 28: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 28

1.4.4 Standard Graphic Symbol In Wiring System

Table 1.8: Types of electrical symbol

No Name Graphic symbol

1 1-fit

Fluorescent

2 Double

Fluorescent

3 1-fit Wall

Fluorescent

4 Double Wall Fluorescent

5 Circle

Fluorescent

6 Filament lamp

7 Glob lamp

8 Wall glob

lamp

9 Wall lamp

10 Double wall

lamp

11 Chandelier

lamp

12 Spotlight

13 1 Way switch

14 2 way switch

15 Intermediation

lamp

16 Pull lamp

17 Dimmer light

switch

18 5A 3 pin

outlet socket

19 13A 3 pin

outlet socket

20 15A 3 pin

outlet socket

21 Telephone

socket outlet

22 TV antenna

socket

23 Electric bell

24 Distribution

board

25 Ceiling fan

26 Exhaust fan

27 Wall fan

28 Fan regulator

29 Hot unit control

30 Water heater

point

31 Air conditioner

unit

32 Cook control

unit

33 Circuit breaker

34 Miniature

circuit breaker

35 Current

balance circuit breaker

36 Fuse

37 Switch fuse

38 Neutral

connection

39 Kilo-Watt/hour

Meter

40 Earthing

41 Lightning collector

42 Connector box

Page 29: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 29

1.5 Safety Procedures and Rules for Electrical Installation System The Health and Safety at Work etc. Act 1974 sets out the general health and safety duties

of employers, employees and the self-employed. The Electricity at Work Regulations 1989, which were made under the Act, require precautions to be taken against the risk of death or personal injury from electricity in work activities.

Duties are placed on employers to ensure, amongst other things, that employees

engaged in such work activities on or near electrical equipment, implement safe systems of work, have the technical knowledge, training or experience to carry out the work safely, and are provided with suitable tools, test equipment and personal protective equipment appropriate to the work they are required to carry out.

Under the Health and Safety at Work etc. Act employees are required to co-operate with

their employer to enable the requirements of the regulations to be met. This includes complying with any instructions given on matters such as safe systems of work. The Electricity at Work Regulations 1989 requires that employees themselves comply with the regulations.

The Management of Health and Safety at Work Regulations 1999 require employers to

make a suitable and sufficient assessment of the risks to the health and safety both of their employees and of other persons arising out of, or in connection with, the conduct of their undertakings. Where five or more persons are employed, the employer must record the significant findings of these risk assessments.

In the context of risks arising from live work, regulation 14 of the Electricity at Work

regulations 1989 requires that: No person shall be engaged in any work activity on or so near any live conductor (other than one suitably covered with insulating material so as to prevent danger) that danger may arise unless; i. It is unreasonable in all the circumstances for it to be dead ii. It is reasonable in all the circumstances for him to be at work on or near it while it is

live iii. Suitable precautions (including where necessary the provision of suitable protective

equipment) are taken to prevent injury

1.5.1 Institution of Electrical Engineer (IEE) Standard for Electrical Installation

i. Legal requirements

a. In accordance with Regulation 12 (1) and (2) of the Electricity Regulations 1994 states that every wiring in an installation must be supervised by Wireman with phase restrictions Single or Three Phase Restrictions. Once completed, Wireman shall certify Supervision and a Certificate of Completion

b. In accordance with Regulation 13 (1) and (2) of the Electricity Regulations 1994 states that the installation Wiring shall be tested by the restriction or by Wireman Single Phase with Restrictions Phase Three authorized to test any installation, and to be Test Certificate to verify the installation

c. In accordance with Regulation 14 (1) of the Electricity Regulations 1994 states Supervision Certificate and Certificate of Completion and Testing in regulations 12 and 13 shall be respectively in Form G and H are specified in the First Schedule

ii. Testing Upon completion of the wiring, some testing of wiring installations should

performed for confirmation of wiring and equipment operating safely installed to be used. Before testing was conducted the inspection shall be made. Decision inspection / supervision and testing must use. For confirmation of the Test Certificate Form applied, the following tests should be performed:

Page 30: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 30

a. Continuity test b. Insulation Resistance Test c. Polarity test d. Earth Electrode Resistance Test e. Testing Residual Current Devices

Table

1.9

: S

tan

dard

of

ele

ctr

ical w

irin

g

Page 31: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 31

1.5.2 Safety Procedure and Regulation To comply with regulation 14 of the Electricity at Work Regulations 1989 (work on or near

live conductors), dead working should be the normal method of carrying out work on electrical equipment and circuits.

Live working, which includes not only working on live uninsulated conductors but also

working so near live uninsulated conductors that there is a risk of injury, should only be carried out in circumstances where it is unreasonable to work dead.

Typically this would include some types of fault finding and testing (including the live

testing requirements of BS 7671 – Requirements for Electrical Installations (IEE Wiring Regulations)), but only where the risks are acceptable and where suitable precautions are taken against injury, including the provision of adequate training and personal protective equipment (PPE).

Pressure to carry out live work is becoming more common in areas such as construction

sites, high cost manufacturing and in retail outlets operating twenty-four hours per day, seven days a week.

Irrespective of these pressures, the requirements of the regulations still apply in such

situations and live working should only be carried out when justified using the criteria explained in HSG85. For systems where the supply has been cut off to allow dead working, regulation 13 of the Electricity at Work Regulations 1989 applies as follows:

Adequate precautions shall be taken to prevent electrical equipment, which has been

made dead in order to prevent danger while work is carried out on or near that equipment, from becoming electrically charged during that work if danger may thereby arise.

This regulation therefore requires that adequate precautions are taken to ensure that

conductors and equipment cannot inadvertently be energised while the work is taking place – this is the process of isolation.

The Electricity at Work Regulations 1989 definition of ‘isolation’ is given in regulation 12

and means the disconnection and separation of the electrical equipment from every source of electrical energy in such a way that this disconnection and separation is secure. In effect this means not just cutting off the supply but also ensuring that the means of disconnection is secure, as described in this Guide. In most instances this will require securing the means of disconnection in the OFF position and it is highly recommended that a caution notice or label is posted at the point of disconnection as described in the Guide under ‘Safe isolation procedures’.

Of equal importance is regulation. This requires that employers ensure that all employees

involved in work on electrical equipment are competent. Employees should be instructed on, and trained in, the implementation of safe systems of work. If they have not received such training and instruction, they should only work under the supervision of a competent person.

For the best of practice guide to safe isolation and control of the working practices on

electrical systems must be consider these aspect, it’s: i. Site safety management ii. Safe isolation procedure

a. When isolating the main source of energy, it is also essential to isolate any secondary sources (such as standby generators, uninterruptible power supplies and micro generators).

b. Where there is no such local means of isolation or where there is a risk of reinstatement of the supply, the circuit or equipment to be worked on should be securely isolated by one of the following methods - Isolation using a main switch or distribution board switch-disconnected - Isolation of individual circuits

Page 32: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 32

c. It is preferable that a final circuit distribution board is not energised until all of its final circuits have been completed, and inspected and tested - Isolation of individual circuits protected by circuit-breakers - Isolation of individual circuits protected by fuses

Note: In TT systems, the incoming neutral conductor cannot reliably be regarded as being at Earth potential. This means that for TT supplies, a multi-pole switching device which disconnects the line and neutral conductors must be used as the means of isolation. For similar reasons, in IT systems, all poles of the supply must be disconnected. In these circumstances, single pole isolation, such as by fuses or single-pole circuit-breakers, is not acceptable.

iii. Electrical permit work iv. Caution notice v. Proving dead isolated equipment or circuits vi. Additional precautions

a. New installation b. Alterations and additions c. Circuits under automatic control d. Neutral conductor e. Protective conductors f. Proving dead unused or unidentified cables

vii. Identification of devices suitable for isolation

Page 33: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 33

Figure 1.29: Steps to safe isolation

Page 34: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 34

Figure 1.30: Pocket guide to isolation procedure

Figure 1.31: Caution notice

Page 35: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 35

1.6 Green Technology on Electrical Installation System What is green electricity? “Green electricity’' means electricity produced from sources which do not cause these impacts upon the environment. Of course, every type of electricity generation will have some impact, but some sources are much greener than others. The cleanest energy sources are those which utilize the natural energy flows of the Earth. These are usually known as renewable energy sources, because they will never run out.

1.6.1 Latest Green Electrical Technology by Wind Technology and Innovation

i. Wind power plant Wind power is the conversion of wind energy into a useful form of energy, such

as using wind turbines to make electrical power, windmills for mechanical power, wind pumps for water pumping or drainage, or sails to propel ships.

Large wind farms consist of

hundreds of individual wind turbines which are connected to the electric power transmission network. Offshore wind is steadier and stronger than on land, and offshore farms have less visual impact, but construction and maintenance costs are considerably higher. Small onshore wind farms provide electricity to isolated locations. Utility companies increasingly buy surplus electricity produced by small domestic wind turbines.

Wind power, as an alternative

to fossil fuels, is plentiful, renewable, widely distributed, clean, produces no greenhouse gas emissions during operation and uses little land. The effects on the environment are generally less problematic than those from other power sources.

Wind power is very consistent

from year to year but has significant variation over shorter time scales. The intermittency of wind seldom creates problems when used to supply up to 20% of total electricity demand, but as the proportion increases, a need to upgrade the grid, and a lowered ability to supplant conventional production can occur.

Power management

techniques such as having excess capacity storage, geographically distributed turbines, dispatch able backing sources, storage such as pumped-storage hydroelectricity, exporting and importing power to neighboring areas or reducing demand when wind production is

Figure 1.32: Wind power plant technology

Page 36: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 36

low, can greatly mitigate these problems. In addition, weather forecasting permits the electricity network to be readied for the predictable variations in production that occur.

A turbine works by converting kinetic energy in wind into mechanical energy.

Energy used directly by machinery, then the machine is referred to as a windmill. The energy converted to electricity, is known as a wind generator. Wind turbine technology is a great thing, because it allows us to still provide enough energy for our modern day needs at our disposal. A turbine makes it electricity by using wind. The wind force turns the blades a wind turbine which are connected to a shaft, and the shaft is connected to a generator which creates the electricity. Turbine's produce from 50-750 kilowatts. Wind turbines can be separated into two types based on the axis about which the turbine rotates.

Turbines that rotate around a horizontal axis are more common. Vertical-axis

turbines are less frequently used. Another way to classify wind turbines is the location. Whether they are used onshore or offshore, or even aerial wind turbines. High-tech turbines equal low environmental impact. Offshore wind turbines are increasing and are by far the largest wind turbine operation. That’s why wind power is gaining public approval and generating increased awareness.

It is also becoming economically competitive with more conventional power

sources a fact that’s greatly improving its prospects as a viable energy source. The process behind wind energy is pretty simple. It starts, of course, with the wind, which is actually a form of energy. Wind is caused by the sun’s heating of the atmosphere, the irregularities of the earth's surface and its rotation.

ii. High Altitude Wind Power with Yo-Yo Kites

Some of the most powerful (and energy-dense) winds on Earth are literally out of reach of conventional wind turbines, but one wind power startup aims to harvest energy from them with giant kites and some yo-yo action.

The Turin-based startup Kite Gen isn't the only one searching for the holy grail of

high altitude wind power, but their approach is a bit different from other methods, which seek to generate power at altitude and then send it down a tether to the ground. The Kite Gen system leaves all of the generating equipment on the ground, saving weight and money in the air, and instead uses the physical traction from the kite's tether to generate electricity.

.

Figure 1.33: Kite gen

Page 37: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 37

Once launched, the company's kites are automatically piloted in a predefined flight path (covering a much larger area than a conventional turbine) using on-board avionic sensors to maximize the power generation. The kites are tethered to the ground unit with Dyneema tethers, and the pull on these tethers is what generates electricity. When the kites reach the end of their tether (while turning spinning drums attached to alternators), the angle of the kites are repositioned to present minimum resistance to the wind and the cables are then rewound to begin another phase of power generation. According to Kite Gen, rewinding the cables does consume energy, but only a fraction of what is produced by the kites.

iii. Invelox wind turbine Invelox wind power generation technology, Sheerwind tests result its turbine

could generate six times more energy than the amount produced by traditional turbines mounted on towers. Besides, the costs of producing wind energy with Invelox are lower, delivering electricity with prices that can compete with natural gas and hydropower.

Invelox takes a novel approach to wind power generation as it doesn’t rely on

high wind speeds. Instead, it captures wind at any speed, even a breeze, from a portal located above ground. The wind captured is then funneled through a duct where it will pick up speed.

The resulting kinetic energy will drive the generator on the ground level. By

bringing the airflow from the top of the tower, it’s possible to generate more power with smaller turbine blades.

As to the sixfold output claim, as with many new technologies promising a

performance breakthrough, it needs to be viewed with caution. SheerWind makes the

Figure 1.34: Kite height – high altitude wind

Page 38: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 38

claim based on its own comparative tests, the precise methodology of which is not entirely clear.

Figure 1.35: Invelox turbine

Page 39: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 39

1.6.2 Latest Green Electrical Technology by Solar Technology and Innovation

i. Solar power system Solar power is the conversion of sunlight into electricity, either directly using photovoltaics (PV), or indirectly using concentrated solar power (CSP). Concentrated solar power systems use lenses or mirrors and tracking systems to focus a large area of sunlight into a small beam. Photovoltaics convert light into electric current using the photoelectric effect. Sunlight can be converted: a. Concentrated solar power (also called concentrating solar power, concentrated solar

thermal, and CSP) systems use mirrors or lenses to concentrate a large area of sunlight, or solar thermal energy, onto a small area.

b. Solar thermal energy (STE) is a technology for harnessing solar energy for thermal energy (heat).

Figure 1.36: Power of sun cycle

Page 40: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 40

ii. Solar power product Table 1.10: Product of solar energy

No. Item Picture

1

ER Emergency Ready Solar and Hand-Crank Powered Emergency

LED Flashlight with Radio and Mobile Phone Charger

2 Sunforce 60-Watt Solar Charging Kit

3 Waterproof Dynamo Solar Flashlight

4 Hybrid Solar Cooker Sun Oven

Portable Cooker by Sun BD Corporation

5 Garden Creations Solar-Powered

LED Accent Light, Set of 8

6 SOLARBAK Solar Powered Take Your Power With You Backpack

Page 41: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 41

7 Solar Powered White LED Light

Globe

8 Solar boat

9 Solar roof

10 Brunton Solar Roll Flexible Solar

Module

Page 42: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 42

1.7 Reference

Books Egan M David (1986). The Building Fire Safety Concept. University Technology Malaysia,

Skudai. Fullerton R. L. (1979). Building Construction in Warm Climates. Volume 1, 2, 3. Oxford

University Press, United Kingdom.

Hall F. (2000). Building Services & Equipment. Pearson Limited, England. MS EN 81-1:2012. Malaysian Standard. Safety Rules for the Construction and Installation of

Lift- Part1: electric Lifts (first revision). Department of Standards Malaysia. Nor Rizman (2010). Risk Assessment for Demolition Works In Malaysia. Faculy of Civil

Engineering and Earth Resources, Universiti Malaysia Pahang. Undergraduate thesis.

Prashant A/L Tharmarajan (2007(. The Essential Aspects of Fire Safety Management In Hihg-

Rise Buildings. University Teknologi Malaysia. Degree of master science thesis. Riger W. Haines, Douglas C. Hittle (2006). Control System for Heating, Ventilating and Air

Conditioning. Springer-Verlag, New York. Stein, Benjamin, Reynolds, John S., Grondzik, Walter T., and Alison G. Kwok, (2006).

Mechanical and Electrical Equipment for Buildings. 10th ed. Hoboken, New Jersey: John Wiley and Sons, Inc., 2006.

Tan, C. W. and Hiew, B.K., (2004), “Effective Management of Fire Safety in a High-Rise

Building”, Buletin Ingenieur vol. 204, 12-19.

Journals N.H. Salleh and A.G. Ahmad. (2009). Fire Safety Management In Heritage Buildings: The

Current Scenario In Malaysia. CIPA Symposium Kyoto Japan. UIAM and USM.

Code of Practices Approved Code Of Practice For Demolition: Health And Safety In Employment Act 1992.

Issued And Approved By The Minister Of Labour September 1994.

Code of Practice for Lift Works and Escalator Works. (2002 ed). Code Of Practice For Demolition Of Buildings 2004. Published by the Building Department.

Printed by Taiwan Government Logistics Department. Code Of Practice For Demolition Of Buildings (2009). Malaysia Standard Supersede Ms 282

Part 1: 1975. Technical Committee For Construction Practices Under The Supervision Of Construction Industry Development Board, Malaysia.

Demolition Work Code Of Practice (July 2012). Australian Government. Work Health and Safety (Demolition Work Code of Practice) Approval 2012. Australian

Capital Territory. By Dr Chris Bourke, Minister for Industrial Relations.

Page 43: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 43

Others Publishing

Coby Frampton. Benchmarking World-class maintenance. CMC Charles Brooks Associates,

Inc. Electrical Installation and Systems (2006). Training Package UEE06. Industry Skills Council,

Australia. Fire Safety Manual (2002). Florida Atlantic University USA. Garis panduan Pendawaian Elektrik di bangunan Kediaman (2008). Suruhanjaya Tenaga

Malaysia. Jabatan Keselamatan Elektrik. Laws of Malaysia. Act 341: Fire Services Act 1988. Publish by The Commissioner Of Law

Revision, Malaysia Under The Authority Of The Revision Of Laws Act 1968 In Collaboration With Percetakan Nasional Malaysia Bhd 2006.

Operations & Maintenance Best Practices: A Guide to Achieving Operational Efficiency.

(August 2010). Release 3.0. Principles of Home Inspection: Air Conditioning and Heat Pumps. (2010). Educational Course

Note. Routine Maintenance Modules. Part II. Uniform Building By Law 1984. (1996). MDC Legal Advisers: MDC Publishers Printers Guidelines For Applicants For A Demolition Licence Issued Under The Occupational Safety

And Health Regulations 1996. Occupational Safety And Health Act 198. The Government of Commerce, Western Autralia.

Websites

http://en.wikipedia.org/wiki/Electricity

http://science.howstuffworks.com/electricity.htm

http://en.wikipedia.org/wiki/Electricity_generation

https://en.wikipedia.org/wiki/Fire_safety

http://www.usfa.fema.gov/citizens/home_fire_prev/

https://en.wikipedia.org/wiki/Maintenance,_repair,_and_operations

http://academia.edu/406774/Demolition_Work_in_Malaysia_The_Safety_Provisions

http://www.mbam.org.my/mbam/doc/news/010-05Oct09-COP%20Demolition%20Works-corrected%20on%20%2030th%20sept%202009-1.doc

http://en.wikipedia.org/wiki/Demolition

http://www.safeworkaustralia.gov.au/sites/SWA/about/Publications/Documents/700/Demolitio

n%20Work.pdf

https://en.wikipedia.org/wiki/Air_conditioning

Page 44: Building Service Chapter 1

PSMZA Course Note (Chapter 1)

Ver. 1 (MSH-Jun2013): CC608 Building Services 44

http://www.nasa.gov/topics/earth/features/heat-island-sprawl.html

http://www.projectnoah.org/education

http://unfccc.int/files/methods_and_science/other_methodological_issues/interactions_with_ozone_layer/application/pdf/subgene.pdf

http://www.cibse.org/Docs/barney2.doc

http://en.wikibooks.org/wiki/Building_Services/Vertical_Transportation