bus box terminal connection point details 24 mar 2014
DESCRIPTION
ElectricalTRANSCRIPT
-
Bus Bar B
Bus bar C
Bus bar A
Insulation
Insulation
This side comingfrom the Wire
Gutter
This side cominggoing to theExisting Main
Breaker
This side cominggoing to newMDP
Notes:
1. The busbar connection shall berated at 800amps or higher.
2. The size and supports used inthis terminal box must bereferred to the panelboardmanufacturer.
3. The dimension of the terminalbus must be sized correctly toaccommodate the following:a. Incoming cables from the
existing wire gutter ( anocular inspection isneeded).
b. The outgoing cables of: Existing cable going to
the existing MDP(ocularinspection is needed)
New cables going toMDP( for 2 x 3-100mm2)
4. The panelboard manufacturershall consider the actualcondition and the proposedtransition wireway for the newMDP.