bus box terminal connection point details 24 mar 2014

1
Bus Bar B Bus bar C Bus bar A Insulation Insulation This side coming from the Wire Gutter This side coming going to the Existing Main Breaker This side coming going to new MDP Notes: 1. The busbar connection shall be rated at 800amps or higher. 2. The size and supports used in this terminal box must be referred to the panelboard manufacturer. 3. The dimension of the terminal bus must be sized correctly to accommodate the following: a. Incoming cables from the existing wire gutter ( an ocular inspection is needed). b. The outgoing cables of: Existing cable going to the existing MDP(ocular inspection is needed) New cables going to MDP( for 2 x 3-100mm2) 4. The panelboard manufacturer shall consider the actual condition and the proposed transition wireway for the new MDP.

Upload: mcmillet

Post on 01-Oct-2015

215 views

Category:

Documents


2 download

DESCRIPTION

Electrical

TRANSCRIPT

  • Bus Bar B

    Bus bar C

    Bus bar A

    Insulation

    Insulation

    This side comingfrom the Wire

    Gutter

    This side cominggoing to theExisting Main

    Breaker

    This side cominggoing to newMDP

    Notes:

    1. The busbar connection shall berated at 800amps or higher.

    2. The size and supports used inthis terminal box must bereferred to the panelboardmanufacturer.

    3. The dimension of the terminalbus must be sized correctly toaccommodate the following:a. Incoming cables from the

    existing wire gutter ( anocular inspection isneeded).

    b. The outgoing cables of: Existing cable going to

    the existing MDP(ocularinspection is needed)

    New cables going toMDP( for 2 x 3-100mm2)

    4. The panelboard manufacturershall consider the actualcondition and the proposedtransition wireway for the newMDP.