Notice

This document contains information protected by copyright. All rights are reserved. The owner of the equipment forwhich this manual is written may photocopy the contents of this manual for internal use only. No part of this docu-ment may be photocopied, reproduced, or translated into another language for use by anyone other than the ownerof the equipment for which this manual is written without the prior written consent of Stulz Air Technology Systems,Inc. (SATS).

This document contains confidential and proprietary information of Stulz Air Technology Systems, Inc. Distributing orphotocopying this document for external distribution is in direct violation of U.S. copyright laws and is strictlyprohibited without the express written consent of SATS.

Unpublished — rights reserved under the copyright laws of the United States and of other countries.Other brands and tradenames are trademarks of their respective owners.

Copyright 2007 by Stulz Air Technology Systems, Inc.Printed in the United States of America.All rights reserved.

Stulz Air Technology Systems, Inc.1572 Tilco DriveFrederick, MD 21704USA

06/07

Project: _____________________SATS Model: _____________________SATS Serial #: _____________________SATS Job#: _____________________

Page 3: C-Tech-10 Operation Manual - STULZ USAats.stulz.com/fileadmin/US_STULZ_USA/documents/PDF/controllers/... · (©June, 2007) C-Tech-10 Operation Manual Air Technology Systems, Inc

(©June, 2007)

C-Tech-10 Operation Manual

Air Technology Systems, Inc.

1

SETTING THE PARAMETERS• Press the SET button to enter the modifying mode of the DIRECT Level parameters.

⇒ Press the SET button to enter the modifiable field.⇒ Use the and buttons to change the parameter’s value.⇒ Press the SET button to confirm change.

• Press the SET + MODE buttons and hold for 3 to 5 seconds to enter the modifying mode of the FACTORYLevel parameters. Enter the code 177 and press the SET button to access the modifiable parameters.

• For the above quick references, press the HOLD button to accept all changes. Press the RESUME button notto accept any changes.

SETTING THE CLOCK• Press the CLOCK button repeatedly to access the hours, minutes, and day of the week. Use the and

buttons to modify the value. Press the CLOCK button again to accept the new value.

CLEARING & MUTING THE ALARM• Press the RESUME button to silence the alarm. Press the RESUME button for 3 seconds to reset any active

alarms. Note the alarm will not be cleared until the alarm condition has been eliminated.

SETTING THE TEMPERATURE SETPOINT• There are 3 operating modes that are relevant to the temperature control: UNOCCUPIED, COMFORT, and

NIGHT-TIME- . Press the SET button to enable modification of the above 3 modes. Use the and

buttons to change the setpoint. Note the symbol being modified will be in the bottom-right hand corner ofthe display during modification. Press the HOLD button to accept all the changes. Press the RESUME buttonnot to accept any changes.

SETTING THE HUMIDITY SETPOINT• Press the SET button for 3 seconds, the word “set” will appear in the upper-right hand corner of the screen and

the actual humidity reading will become the humidity setpoint. Use the and buttons to change thesetpoint. Press the HOLD button to accept all the changes. Press the RESUME button not to accept anychanges.

Page 4: C-Tech-10 Operation Manual - STULZ USAats.stulz.com/fileadmin/US_STULZ_USA/documents/PDF/controllers/... · (©June, 2007) C-Tech-10 Operation Manual Air Technology Systems, Inc

(©June, 2007)

C-Tech-10 Operation Manual

Air Technology Systems, Inc.

2

ALARMS AND TROUBLESHOOTING

The detection of an alarm brings about:· The activation of the buzzer, if present and enabled (parameter P1 not equal to 0), depending on the type of alarm.· The display of the alarm code and the letters ‘AL’, alternating with the display of the temperature· The de activation of some or all the outputs, depending on the type of alarm· The activation of the alarm relay, if present (parameter H2=1), depending on the type of alarm (WARNING: alarm relay refersonly to Stand Alone models)

Note, when more than one alarm is detected at the same time, the display automatically scrolls through the occurred alarms.

Resetting the alarms

Muting the buzzer:Pressing the RESUME button for less than 3 seconds, whenever an alarm is detected, mutes the buzzer, while the outputsdeactivated by the alarm in question remain de energized. The alarm code continues to be displayed, alternating with themeasured temperature value.

Automatic reset:Some alarms are automatically reset when the cause is no longer present, that is, they are deactivated: relevant messageon the display, buzzer and alarm relay.

Manual reset:Pressing the RESUME button for more than 3 seconds, if the alarm conditions have been removed, the instrument returns tothe normal operation and the alarm relay is de-energized. If, on the other hand, the alarm conditions persist, the alarmsituation in progress remains.

Description of the alarmsDetection is immediate for all alarms except the high and low temperature alarms, which are activated after a period set byparameter P5. When the machine is turned OFF, probe alarms are detected only. The alarms which can be detected aredescribed in the following table:

HI T: High temperature alarmWhen the temperature measured by probe B1 rises above the value specified by the parameter P3 for a period longer thanparameter P5, the buzzer and the high temperature alarm message, HI T, are activated. The alarm relay is not energized.

LO T: Low temperature alarmWhen the temperature measured by probe B1 falls below the value specified by parameter P4 for a period longer thanparameter P5, the buzzer and the low temperature alarm signal, LO T, are activated. The alarm relay is not energized.

CODE TYPE OF ALARM EXPLANATIONHI T High temperature alarm The temperature measured by probe B1 has exceeded the value of parameter P3LO T Low temperature alarm The temperature measured by probe B1 has fallen below the value of parameter P4E ID Alarm from digital input ID3 Digital input ID3 is openE FL Alarm from digital input ID1 Digital input ID1 is openEE EEPROM error Read/write error in non-volatile internal memoryE SR Terminal communication error The terminal doesn’t receive data from the power boardE ST Power board communication error The power board doesn’t receive data from the terminalE1 B1 probe error Ambient temperature regulation B1 probe errorE2 B2 probe error Humidity/auxiliary temperature active B2 probe errorLO H Low ambient humidity alarm The humidity measured by probe B2 is over the value of parameter P8HI H High ambient humidity alarm The humidity measured by probe B2 is below the value of parameter P7

Page 5: C-Tech-10 Operation Manual - STULZ USAats.stulz.com/fileadmin/US_STULZ_USA/documents/PDF/controllers/... · (©June, 2007) C-Tech-10 Operation Manual Air Technology Systems, Inc

(©June, 2007)

C-Tech-10 Operation Manual

Air Technology Systems, Inc.

3

E ID: Alarm from digital inputThe unit is able to detect external alarms through digital input ID3. When this is detected as being open, the system waitsfor the delay time P6 then the buzzer and the alarm message E ID are activated. If parameter P2=0 (non serious alarm),there are no other effects; if P2=1 (serious alarm), the alarm relay is energized and there are two types of reaction: ifdigital input ID1 is connected to the fan thermal cut-off , E ID switches off the outputs but not the fan, otherwise it switchesoff the outputs and the fan. When considered to be a non serious alarm (P2=0), Aria resets automatically when the causeis no longer valid. If P2=1 (serious alarm) and, again, the cause that generated the alarm is removed, the RESUME buttonmust be pressed for more than 3 seconds (manual reset).

E FL: Filter alarmThe unit is able to detect a possible filter alarm through digital input ID1 (if H3=2). When this is detected as being openthe alarm message E FL (filter alarm) is activated. The alarm is reset automatically when its cause is removed.

EE: EEPROM alarmSignals a read and/or write error in the non-volatile internal memory (EEPROM), thus highlighting a problem in thestorage of the parameters. If this occurs, try switching the controller off and on again: If the problem persists, pleasecontact the local service.

E SR: Terminal communication errorSignals an error in the serial communication between the terminal and the power board: the terminal does not receive thedata. The alarm message E SR is displayed, the buzzer is activated and all outputs are de energized. The LED on thepower board blinks 3 times (normally once) in 3 seconds. The alarm is reset automatically, that is when communicationis established again. If the alarm occurs, check the two-lead serial connection between the terminal and the powerboard.

E ST: Power board communication errorSignals an error in the serial communication between the terminal and the power board: the power board does notreceive the data. The alarm signal E ST is displayed, the buzzer is activated and all outputs are de energized. The LED onthe power board blinks twice (normally once) in 3 seconds. The alarm is reset automatically, that is when communica-tion is established again. If the alarm occurs, check the two-lead serial connection between the terminal and the powerboard.

E1: B1 temperature regulation probe errorSignals the malfunctioning of the temperature probe used for temperature regulation (B1). Also check the positionof jumper J1. In the case of an alarm, the controller provides the alarm message E1, the buzzer and the alarm relayare activated and all outputs are de-energized, except for the supply fan. The fan stays on to allow air circulation inpublic areas. The alarm is reset automatically, that is when communication is established again.

E2: B2 auxiliary probe errorSignals the malfunctioning of the B2 active probe. Also check the position of jumper J2. In the case of an alarm,the control provides the alarm message E2, the buzzer and the alarm relay are activated and the humidification anddehumidification functions are suspended. The alarm is reset automatically, that is when the sensor starts workingcorrectly.

HI H: High humidity alarmWhen the humidity measured by probe B2 rises above the value specified by parameter P8 for a time greater thanP5, the high humidity alarm signal HI H is activated. The alarm relay and the buzzer are not activated

LO H: Low humidity alarmWhen the humidity measured by probe B2 falls below the value specified by parameter P7 for a time greater thanP5, the low humidity alarm signal LO H is activated. The alarm relay and the buzzer are not activated.

Page 6: C-Tech-10 Operation Manual - STULZ USAats.stulz.com/fileadmin/US_STULZ_USA/documents/PDF/controllers/... · (©June, 2007) C-Tech-10 Operation Manual Air Technology Systems, Inc

(©June, 2007)

C-Tech-10 Operation Manual

Air Technology Systems, Inc.

4

2-Year Standard Limited Warranty:

Stulz Air Technology Systems, Inc., warrants to the original buyer of itsproducts that the goods are free from defects in material and workmanship. Stulz Air Technology Systems, Inc.’s obligation under this warranty is torepair or replace, at its option, free of charge to the customer, any part orparts which are determined by Stulz Air Technology Systems Inc. to bedefective. The warranty is in effect for 24 months from date of shipment if acompleted Warranty Registration and Start Up Form is submitted to Stulz AirTechnology Systems, Inc. within 90 days from shipment. In the event that acompleted start-up form is not received by Stulz Air Technology Systems, Inc.within 90 days from shipment, the company’s obligation will be for a period of12 months from date of shipment. Parts replaced under warranty are war-ranted for a period of 90 days from shipment or for the remainder of the unitwarranty period, whichever is greater.

Stulz Air Technology Systems, Inc.’s warranty does not cover failures causedby improper installation, abuse, misuse, misapplication, improper or lack ofmaintenance, negligence, accident, normal deterioration including wear and tear,or the use of improper parts or improper repair as determined by SATS. Thiswarranty does not include costs for transportation, costs for removal or reinstal-lation of equipment or labor for repairs or replacement made in the field.

THIS OBLIGATION AND LIABILITY OF STULZ AIR TECHNOLOGY SYS-TEMS, INC. UNDER THIS WARRANTY DOES NOT INCLUDE LOSSES,DIRECT OR INDIRECT, FOR INCIDENTAL OR CONSEQUENTIAL DAM-AGES. THIS WARRANY IS IN LIEU OF ALL OTHER WARRANTIES,EXPRESS OR IMPLIED, INCLUDING WARRANTIES OR MERCHANTABIL-ITY AND FITNESS FOR A PARTICULAR PURPOSE, AND THERE ARE NOWARRANTIES THAT EXTEND BEYOND THE DESCRIPTION ON THE FACEHEREOF.

����������������������������������

����������������������������������

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

��

Product Warranty

SATS offers a two year standard limited warranty as stated below.

Page 7: C-Tech-10 Operation Manual - STULZ USAats.stulz.com/fileadmin/US_STULZ_USA/documents/PDF/controllers/... · (©June, 2007) C-Tech-10 Operation Manual Air Technology Systems, Inc

(©June, 2007)

C-Tech-10 Operation Manual

Air Technology Systems, Inc.

5

PRODUCT SUPPORT GROUP

SATS provides its customers with a Product Support Group (PSG) which not only provides technical support andparts but the following additional services, as requested: performance evaluations, start-up assistance and training.

Technical Support

The SATS Product Support Group (PSG) is dedicated to the prompt reply and solution to any problem encoun-tered with a unit. Should a problem develop that cannot be resolved using this manual, you may contact PSG at(240) 529-1399 Monday through Friday from 8:00 a.m. to 5:00 p.m. EST. If a problem occurs after business hours,dial the page number (301) 414-4514 and follow the steps below:

1. Wait for the dial tone.

2. Dial your telephone number (including area code).

3. Press the pound (#) key.

4. Wait for a busy signal.

5. Hang up the telephone.

One of our service technicians will return your call. When calling to obtain support, it is vital to have the followinginformation readily available:

• Unit Model Number (X-XXXX-XX)

• Description of Problem

Obtaining Warranty Parts

Warranty inquires are to be made through the Product Support Group (PSG) at (240) 529-1399 Monday throughFriday from 8:00 a.m. to 5:00 p.m. EST. A service technician at SATS will troubleshoot the system over thetelephone with a field service technician to determine the defect of the part. If it is determined that the part may bedefective a replacement part will be sent UPS ground. If the customer requests that warranty part(s) be sent byany other method than UPS ground the customer is responsible for the shipping charges. If you do not haveestablished credit with SATS you must provide a freight carrier account number.

A written (or faxed) purchase order is required on warranty parts and must be received prior to 12:00 p.m. for sameday shipment. The purchase order must contain the following items:

• Purchase Order Number

• Date of Order

• SATS Stated Part Price (obtained from PSG)

• Customer Billing Address

• Shipping Address

• Customer's Telephone and Fax Numbers

• Contact Name

• Unit Model No. & SATS Item No.

The customer is responsible for the shipping cost incurred for shipping the defective part(s) back to SATS. Returnof defective part(s) must be within 30 days at which time an evaluation of the part(s) is conducted and if the part isfound to have a manufacturing defect a credit will be issued.