c15 · ® c15 diesel generator sets media number: lehe1637-00 ... additional ratings may be...
TRANSCRIPT
Cat® C15 DIESEL GENERATOR SETS
Engine Model Cat® C15 ACERT In-line 6, 4-cycle diesel
Bore x Stroke 137mm x 171mm (5.4in x 6.8in)
Displacement 15.2 L (928 in³)
Compression Ratio 16.1:1
Aspiration Turbocharged Air-to-Air Aftercooled
Fuel Injection System MEUI
Governor Electronic ADEM™ A4
1/2
Model Standby Prime Emission Strategy
DE500E0 500 kVA, 400 ekW 450 kVA, 360 ekW Non-Certified
Emissions
Performance Standby Prime
Frequency 50 Hz 50 Hz
Genset Power Rating 500 kVA 450 kVA Gen set power rating with fan @ 0.8 power factor 400 ekW 360 ekW Fuelling strategy Non-Certified Emissions Non-Certified Emissions
Performance Number DM8491 DM8490
Fuel Consumption
100% load with fan 103.7 L/hr 27.4 gal/hr 94.5 L/hr 25.0 gal/hr
75% load with fan 77.9 L/hr 20.6 gal/hr 71.8 L/hr 19.0 gal/hr
50% load with fan 55.3 L/hr 14.6 gal/hr 51.5 L/hr 13.6 gal/hr
25% load with fan 33.4 L/hr 8.8 gal/hr 31.6 L/hr 8.3 gal/hr
Cooling System1
Radiator air flow restriction (system) 0.12 kPa, 0.48 in. Water 0.12 kPa, 0.48 in. Water
Radiator air flow 476 m3/min, 16809 cfm 476 m3/min, 16809 cfm
Engine coolant capacity 20.8 L, 5.5 gal 20.8 L, 5.5 gal
Radiator coolant capacity 37 L, 9.7 gal 37 L, 9.7 gal
Total coolant capacity 57.8 L, 15.2 gal 57.8 L, 15.2 gal
Inlet Air
Combustion air inlet flow rate 29.3 m³/min 1036.4 cfm 27.3 m³/min 965.0 cfm
Max. Allowable Combustion Air Inlet Temp 48 ° C 118 ° F 46 ° C 114 ° F
Exhaust System
Exhaust stack gas temperature 523.6 ° C 974.4 ° F 515.3 ° C 959.5 ° F
Exhaust gas flow rate 79.4 m³/min 2802.2 cfm 73.1 m³/min 2580.2 cfm
Exhaust system backpressure (maximum allowable) 10.0 kPa, 40.0 in. water 10.0 kPa, 40.0 in. water Heat Rejection
Heat rejection to jacket water 151 kW 8583 Btu/min 139 kW 7923 Btu/min
Heat rejection to exhaust (total) 377 kW 21425 Btu/min 344 kW 19561 Btu/min
Heat rejection to aftercooler 71 kW 4053 Btu/min 61 kW 3450 Btu/min
Heat rejection to atmosphere from engine 44 kW 2477 Btu/min 42 kW 2396 Btu/min Heat Rejection to Atmosphere from Generator 28 kW 1592 Btu/min 22 kW 1251 Btu/min
PACKAGE PERFORMANCE
Standby & Prime: 50Hz; 380, 400V & 415V
LEHE1637-00
Cat® C15 DIESEL GENERATOR SETS
Media Number: LEHE1637-00
APPLICABLE CODES AND STANDARDS:
AS1359, CSA C22.2 No100-04, UL142, UL489, UL869, UL2200, NFPA37, NFPA70, NFPA99, NFPA110, IBC, IEC60034-1, ISO3046, ISO8528, NEMA MG1-22, NEMA MG1-33, 2006/95/EC, 2006/42/EC, 2004/108/EC.
Note: Codes may not be available in all model configurations. Please consult your local Cat Dealer representative for availability.
STANDBY: Output available with varying load for the duration of the interruption of the normal source power. Average power output is 70% of the standby power rating. Typical operation is 200 hours per year, with maximum expected usage of 500 hours per year.
PRIME: Output available with varying load for an unlimited time. Average power output is 70% of the prime power rating. Typical peak demand is 100% of prime rated ekW with 10% overload capability for emergency use for a maximum of 1 hour in 12. Overload operation cannot exceed 25 hours per year
RATINGS: Ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO3046 standard conditions.
Fuel Rates are based on fuel oil of 35º API [16º C (60º F)] gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb) when used at 29º C (85º F) and weighing 838.9 g/litre (7.001 lbs/U.S. gal.). Additional ratings may be available for specific customer requirements, contact your Caterpillar representative for details. For information regarding Low Sulfur fuel and Biodiesel capability, please consult your Cat dealer.
DEFINITIONS AND CONDITIONS
1 For ambient and altitude capabilities consult your Cat dealer. Air flow restriction (system) is added to existing restriction from factory.
2 Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D & E and ISO8178-1 for measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of 77° F, 28.42 in HG and number 2 diesel fuel with 35° API and LHV of 18,390 BTU/lb. The nominal emissions data shown is subject to instrumentation, measurement, facility and engine to engine variations. Emissions data is based on 100% load and thus cannot be used to compare to EPA regulations which use values based on a weighted cycle.
3 UL 2200 Listed packages may have oversized generators with a different temperature rise and motor starting characteristics. Generator temperature rise is based on a 40° C ambient per NEMA MG1-32.
Emissions (Nominal)2
NOx 3458.8 mg/Nm³ 6.8 g/hp-hr 3357.6 mg/Nm³ 6.6 g/hp-hr
CO 171.2 mg/Nm³ 0.3 g/hp-hr 159.3 mg/Nm³ 0.3 g/hp-hr
HC 5.2 mg/Nm³ 0.0 g/hp-hr 6.6 mg/Nm³ 0.0 g/hp-hr
PM 7.8 mg/Nm³ 0.0 g/hp-hr 8.8 mg/Nm³ 0.0 g/hp-hr
Alternator3
Voltages 415V 400V 380V
Motor Starting Capability @ 30% Voltage Dip
1439 skVA 1066 skVA 1207 skVA
Current Standby: 695A | Prime: 626A Standby: 722A | Prime: 650A Standby: 747A | Prime: 650A
Frame Size A2975L4 A2975L4 A2975L4
Excitation SE SE SE
Temperature Rise SB:163°C,
325°F PP: 125°C,
257°F SB:163°C,
325°F PP: 125°C,
257°F SB:163°C,
325°F PP: 125°C,
257°F SB: Standby PP: Prime Power
www.Cat.com/electricpower ©2017 Caterpillar All rights reserved. Materials and specifications are subject to change without notice. CAT, CATERPILLAR, their respective logos, ADEM, S•O•S, BUILT FOR IT, “Caterpillar Yellow”, the “Power Edge” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
2/2
LEHE0377-03 Page 1 of 2
C15 Sound Attenuated Enclosures50 Hz / 60 Hz
These sound attenuated, factory installed enclosures incorporate internally mounted super critical level silencers, designed for safety and aesthetic value on integral fuel tank base or optional dual wall integral fuel tank base for total fluid containment. These enclosures are of extremely rugged construction to withstand exposure to the elements and provide weather protection.Image shown may not reflect actual configuration
Enclosures
Robust / Highly Corrosion Resistant Construction• Factory installed on integral fuel tank base• Environmentally friendly, polyester powder baked paint• 1.6 mm (0.063 in) galvanized steel • All round overhanging base to protect enclosure• High-grade engineering thermoplastic corner posts for protection• Integral lifting frame• Compression door latches giving solid door seal• Zinc plated or black coated stainless steel fasteners• Internally mounted super critical exhaust silencing system
Excellent Access• Large cable entry area for installation ease• Accommodates rear mounted breaker and control panel• Double doors on both sides• Vertically hinged doors with solid bar door stays to hold doors open at 135° rotation• Lube oil and coolant drains pipes to exterior of enclosure and terminated drain valves• Radiator fill cover
Security and Safety• Lockable access doors which give full access to control panel and breaker• Cooling fan and battery charging alternator fully guarded• Fuel fill, oil fill and battery can only be reached via lockable access• Externally mounted emergency stop button• Designed for spreader-bar lifting to ensure safety• Control panel viewing window• Stub-up area is rodent proof
Options• Caterpillar yellow or white paint• Integral dual wall fuel tank base for total fluid containment (fuel, oil and coolant)
Features
Enclosures
Model kVA ekW SB/PP LWA
Sound Pressure Levels dBA
Air Flow Rate
Ambient Capability at 100% Load*1m (3.3 ft) 7m (23 ft)
75% Load
100% Load
75% Load
100% Load m3/s cfm °C °F
50 Hz
DE500E0455 364 PP 98 79 79 69 70 5.7 12078 44 111
500 400 SB 98 79 80 69 70 5.7 12078 45 113
DE550E0500 400 PP 98 79 80 69 70 5.7 12078 40 104
550 440 SB 98 79 80 70 71 5.7 12078 41 106
DE550E3500 400 PP – 82 83 73 74 6.1 12925 54 129
550 440 SB – 83 84 73 75 6.1 12925 52 126
60 Hz
DE450SE0513 410 PP – 81 82 71 72 6.3 13349 47 117
563 450 SB – 82 83 71 73 6.3 13349 49 120
DE500SE0569 455 PP – 82 83 71 73 6.3 13349 43 109
625 500 SB – 82 83 72 73 6.3 13349 45 113
*Ambient capability measured with the Cat extended life coolant at sea level.
Enclosure Package Operating Characteristics
Approximate weight of enclosure package: 5071 kg (11180 lb), **5300 kg (11685 lb) DE550E3. Exact weight is dependent on options. Enclosure weight includes: sound attenuated enclosure, exhaust system, base and generator set.
LEHE0377-03 (10/16)
Materials and specifications are subject to change without notice.CAT, CATERPILLAR, their respective logos, “Caterpillar Yellow”,
the “Power Edge” trade dress as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
www.cat.com/electricpower©2016 Caterpillar
All rights reserved.
1658 4930
2221
**1908 (DE550E3) **4880 (DE550E3)