cable manaement prestige 2com - mk electric
TRANSCRIPT
mkelectric.co.uk
622
CA
BLE
MA
NA
GE
ME
NT
PERI
MET
ER A
ND
DIST
RIBU
TION
Prestige 2ComTechnical
PRODUCT APPLICATIONPRESTIGE 3D DADO CABLE MANAGEMENT
Prestige 3D Dado Cable Management installed with Part M Compliant Graphite Logic Plus Socket Outlets with Outboard Rockers, alongside USB Outlets for convenient charging of mobile phones and other portable devices.This system is an ideal specification for a project with high sustainability credentials. Prestige 3D extrusions are manufactured from 100% recycled content* and the whole system is made in the UK. Logic Plus Socket Outlets are also made in the UK offering a much reduced carbon footprint when compared to some imported products.
To find out more visit www.mkelectric.co.uk
*Based on 2014 Consumption
PR
OD
UC
T
AP
PL
ICA
TIO
N
Technical Hotline +44 (0)1268 563720
CA
BLE
MA
NA
GE
ME
NT
PERIMETER AND
DISTRIBUTION
623
Standards and ApprovalsThe Prestige 2com trunking is a symmetrical two compartment system offering a Cat 7 flexible solution to routing data cabling whilst maintaining a slow bend radius of 50mm, with a separate compartment for power cables.
The trunking is normally surface mounted at dado or skirting height but may also be used vertically. The covers are of the snap-on type with the option of screw fixing for added security against vandalism. Special accessories include adaptors for connection to the full range of MK Ega Mini Trunking.
TECHNICAL SPECIFICATION
MATERIALSAll components are manufactured from PVCu. Carriers, covers and cable dividers are extruded. Carrier couplers, corner carriers, stop ends and accessory boxes are formed by injection moulding.
COLOURSThe system is available in a standard white colour.
OUTLETSThe system is designed to accommodate the complementary range of Logic Plus switches and sockets. Other MK wiring devices may also be used.
Classifications to BS EN 50085-1:2005 and BS EN 50085-2-1:2006 available on request.
FEATURES
l System bend radius 50mm Exceeds Cat 5e, 6 and 7 data cable requirements
l Attractive styling complementary to Logic Plus
l Aesthetic one piece fitting covers with carriers
l Two equal compartments – maximises wiring compartment capacity
l Accessory mounting in either or both compartments – giving flexibility/ versatility
l Unobtrusive screw fixing covers to maximise security against tampering
l Ease of installation – butt jointed construction, no mitring required
l Economical – cost effective 3 components (2 x lids, 1 base)
l Suitable for skirting or dado mounting
l Pre-drilled base – ease/speed of installation
l Accommodates matching MK and other BS switches and sockets
l Interfaces with MK Premier, Ega Industrial and Ega Mini Trunking and Conduit Systems
l Strong PVCu sections are resistant to impact
l Manufactured to high precision standards
l Full range of components, spares and accessories
l Mounting frames for LJU6C and Euro data outlets – cost effective, minimum space requirement (for mounting in SELV compartment only)s
l All extrusions manufactured from 100% recycled material*
For a full range of corresponding products,
see pages 311-316 in the product selector.
Prestige 2ComTechnical
* Based on 2014 consumption
DescriptionThe Prestige 2com trunking is a symmetrical two compartment system offering a Cat 7 flexible solution to routing data cabling whilst maintaining a slow bend radius of 50mm, with a separate compartment for power cables. The trunking is normally surface mounted at dado or skirting height but may also be used vertically. The covers are of the snap-on type with the option of screw fixing for added security against vandalism. Special accessories include adaptors for connection to the full range of MK Ega Mini Trunking.
Data Trunking System
mkelectric.co.uk
624
CA
BLE
MA
NA
GE
ME
NT
PERI
MET
ER A
ND
DIST
RIBU
TION
CABLE CAPACITY
TYPE OF CONDUCTOR SIZE CABLE
FACTOR
COMPARTMENT 1COMPARTMENT 1
WITH 25MMBACK BOX
COMPARTMENT 1WITH 35MMBACK BOX
COMPARTMENT 1EXT CORNER
50MM DATA BEND
Full Term CSA 100% Fill (MM2)
4466 2236 1633 3132
TERM AT 45% FILL (MM2)
2009 1006 734 1409
POWER CABLES NUMBER OF CABLES AT 45% FILL
PVCstranded
1.5mm2 8.6 233 116 85 163
2.5mm2 12.6 159 79 58 111
4mm2 16.6 121 60 44 84
6mm2 21.2 94 47 34 66
DATA CABLESNUMBER OF CABLES AT 45% FILL (A) AND FULL CAPACITY (B)
A B A B A B A B
Cat 5E UTP 5.5mm dia. 30.2 66 147 33 74 24 54 46 103
Cat 5E STP 6.0mm dia. 36.0 55 124 27 62 20 45 39 87
Cat 6 UTP 6.5mm dia. 42.2 47 105 23 52 17 38 33 74
Cat 6 STP 7.0mm dia. 49.0 41 91 20 45 14 33 28 63
Cat7 8.0mm dia. 64 12 27 26 59 4 9 13 30
FLAT ANGLES DIMENSIONS (MM)
LIST NO DESCRIPTION A B C D
VTS2012WHI Flat angle 310 210
VTS2014WHI Flat T details 310 210 410 210
Prestige 2ComTechnical
FLAT ANGLE FLAT TEE
Flat Angles and TeesThese components are fabricated sections and space must be allowed for their inclusion in runs of trunking. All other components snap on over standard trunking profiles.
COMPONENTS
VTS2001WHI main carrier + 2 x VTS5WHI straight covers
WEIGHT:
2.41 Kg/m
WALL THICKNESS:
VTS2001WHI = 2.5mm, 2.0m VTS5WHI = 1.7mm
60
210
1
1
A
A
B
B
C
B
D
A
Data Trunking System
Dimensions (mm)
Technical Hotline +44 (0)1268 563720
625
CA
BLE
MA
NA
GE
ME
NT
PERIMETER AND
DISTRIBUTIONPrestige 2Com
Technical
15mm*to wall
34mm*
118mm*
34mm*
118mm*
15mm*
15mm*
190mm*
* Minimum distance
Data Trunking System
Component Selection Guide
VTS2001WHI
VTS5WHI
VTS5WHI
END CAP ASSEMBLYVTS2006WHI
EXTERNAL CORNER ASSEMBLYVTS2004WHI
EXTERNAL CORNER FIXING SCREW AND COVERVTS2019WHI
INTERNAL CORNER ASSEMBLYVTS2003WHI
INTERNAL CORNER FIXING SCREW AND COVER (SPARE)VTS2018WHI
COUPLER ASSEMBLYVTS2005WHI
FLAT TEEVTS2014WHI
FLAT ANGLEVTS2012WHI
mkelectric.co.uk
626
CA
BLE
MA
NA
GE
ME
NT
PERI
MET
ER A
ND
DIST
RIBU
TION Prestige 2Com
Technical
34mm
13mm
118mm
100mm max
100mm max
34mm
210mm
34mm
500mm max
47mmwide
70mmwide56mm
deep
34mm
deep
1
2
3
5
Planning the InstallationIt is important to spend some time planning the installation, before starting. Time spent on planning the layout at this stage can avoid mistakes later on. The installation is designed for a non-conductive substrate, if you have any queries please contact: MK Technical Sales Service Department. Telephone 01268 563720.
1. Surface to which the trunking is to be installed should be flat and prepared for decorating.
2. Establish the layout of the trunking run with particular attention to the following: -
a. Changes in direction of the trunking.
b. The position of any feeds to or from the system.
c. The position of any connections with existing trunking/wiring systems.
d. Allow for minimum distances between corners, couplers, screw fixings, angles and tees (please see individual technical sections for details).
e. When installing at skirting level, ensure room is also allowed for future floor coverings to be fitted below trunking.
GENERAL INSTALLATION GUIDELINES
TOOLS AND SUNDRIES REQUIRED FOR INSTALLATION:
1. Fine toothed tenon saw or a hacksaw with a 32 – 26 TPI blade for cutting the trunking, or preferably a circular saw with a 350mm diameter fine tungsten tipped blade (100T approx.)
2. All purpose knife or fine file for trimming of trunking
3. Spirit level, Plumb Bob and chalk line
4. A range of screwdrivers (flat or cross point) to suit fixing screws and Earth Carrier Connectors
5. A 5.5mm Ø drill bit and No.8 Round head or Pan head screws with suitable washers to secure the trunking.
6. Soft faced mallet to aid lid fitting
4
Data Trunking System
Installation Guide
Technical Hotline +44 (0)1268 563720
627
CA
BLE
MA
NA
GE
ME
NT
PERIMETER AND
DISTRIBUTIONPrestige 2Com
Technical
34mm
13mm
118mm
100mm max
100mm max
34mm
210mm
34mm
500mm max
47mmwide
70mmwide56mm
deep
34mm
deep
6
7
8
9a
General NotesPrior to installation strike a line of trunking using a plumb and chalk line for vertical, and spirit levels for horizontal runs.
Drill Holes in supporting walls prior to fixing
When mounting at skirting level allowance should be made for thickness of floor finish
Start Installation at a corner position
Debur all carrier cut ends
Carrier couplers must be placed at all junctions between carriers
Leave a gap of 5mm for expansion in long runs
Fixings require washers and No. 8 Round or Pan head screws
Fixings to be at 500mm centres and also at points within 100mm of each end
Cut trunking to allow for mini trunking / conduit (9a) and box adaptor crossover bridge (9b).
1
2
3
4
5
6
7
8
9
9b
Data Trunking System
mkelectric.co.uk
628
CA
BLE
MA
NA
GE
ME
NT
PERI
MET
ER A
ND
DIST
RIBU
TION Prestige 2Com
Technical
13mm
for jo
int
cove
r
1 gang 76mm2 gang 137mm3 gang 197mmfor outlet boxes
88mmfor mini trunking adaptor
Trunking Covers to be cut 8-10mm shorter than Trunking Base
Cen
tre
12
13
14
15
16
17
10
e
18
Debur all cover cut ends
Insert accessories in the following order
a Box adaptor
b Accessory Boxes
c Appropriate slide (VTS2081 shown)
d Cross over bridge
e External Corner Radius (into the Data/Telecom compartment)
Power Cables
Data / Communication cables
Mark position where mains entry is required
Installation Guide Continued
12
13
14
10
11
Data Trunking System
Technical Hotline +44 (0)1268 563720
629
CA
BLE
MA
NA
GE
ME
NT
PERIMETER AND
DISTRIBUTIONPrestige 2Com
Technical
13mm
for jo
int
cove
r
1 gang 76mm2 gang 137mm3 gang 197mmfor outlet boxes
88mmfor mini trunking adaptor
Trunking Covers to be cut 8-10mm shorter than Trunking Base
Cen
tre
Fit covers by locating them correctly into position and pushing them firmly to snap in
place.
Determine whether corners need to be screw fixed (Fig 1). Continue to locate correctly the
Corner and Joint covers and push them firmly until they snap into place. Fit the appropriate badge to the Corner Covers.
Fit covers by locating them correctly into position and pushing them firmly to snap in
place.
Fit end caps by pushing them on from the front so the clips slide behind the retainers
and engage in the main carrier.
a
b
c
d
16
17
FIGURE 1
15
16
17
18
Data Trunking System
Drill 4.5mm dia.clearance holeto allow fixing of screw.