caledonian câbles offshore & marine norme nek606
DESCRIPTION
NEK 606-2004,IEC 60092-350,IEC 60092-351,IEC 60092-352,IEC 60092-353,IEC 60092-354,IEC 60092-359,IEC 60092-375,IEC 60092-376,IEC 60228,IEC 60331-11/12/21/25/31,IEC 60332-1/3,IEC 60446,IEC 60754-1/2,IEC 60811,IEC 61034-1/2,Mud Résistant,Résistance à l’huile,Résistance Au Feu,Ignifugation,Hydrocarbures (HCF) résistant au feu,Émission de fumée,Contenu de l’halogène,Résistance conducteur,Notes de court-circuit,Réactance,Impédance,Identification de baseTRANSCRIPT
Caledonian Câbles Offshore & Marine
NORME NEK606
www.caledonian-cables.co.ukwww.caledonian-cables.fr
Caledonian
ROYAUME-UNI
Marchants Centre industriel,Mill Lane, Laughton, Lewes,East Sussex, BN8 6AJ, UKTel: 44 (0) 207 419 5087Fax: 44 (0) 207 831 9489Email: [email protected]
HONG KONG
Unité B 22 / F CMA bâtiment,64-66 Connaught Road Central, Hong KongTel: 852 36527508Fax: 852 35834834Email: [email protected]
Copyright@ Caledonian Câbles Offshore & Marine
Caledonian, créé en 1978, offre l'une des gammes les plus complètes de solutions de fibres et de systèmes de câblage cuivre avec plus de centaines de produits différents systèmes de câblage. Nos produits de qualité supérieure fournissent pointe au sein de chaque série du câble et pour chaque application.
Parmi les normes nationales et internationales avec lesquelles nos câbles pourraient se conformer sont: BS - British Standard; LPCB incendie Performance Standard, la norme ISO etc. Câbles Caledonian propose un stock complet de câbles et de produits de câblage à travers son réseau national de revendeurs et de distributeurs. Câbles calédoniens a continuellement élargi sa présence internationale en Europe et en Asie.
Caledonian & Addison, produit une large gamme de câbles de communication, la puissance et l'électronique dans ses usines primaires au Royaume-Uni, Italie et Espagne. Pour rester à l'avant, nous gardons toujours l'expansion de nos capacités de fabrication dans plusieurs régions à faible coût tels que la Roumanie, Taiwan, la Malaisie, etc. Ce faible coût des installations de fabrication nous permettent de fournir un système global souple, évolutive qui offre une performance opérationnelle supérieure et des résultats optimaux pour nos clients.
Notre vaste réseau mondial d'installations de fabrication nous donne grande échelle et la flexibilité pour répondre à nos exigences du client. Cette présence mondiale fournit des solutions de conception et de conseil qui sont combinés avec la fabrication de câble de base, les services logistiques, et verticalement intégrés avec nos technologies de commerce électronique, afin d'optimiser les opérations des clients en réduisant les coûts et en réduisant les délais de commercialisation.
Caledonian & Addison a été respecté pour ses normes élevées de qualité, un excellent niveau de service, des prix compétitifs et un esprit unique et novateur. Avec nos dernières technologies, nous sommes à la fois inspirés et bien positionnés pour répondre aux besoins changeants de nos clients. Nous avons les ressources pour diversifier et de renforcer nos lignes de produits et services. Nous comprenons le besoin de changement et avec notre planification précise, nous sommes prêts pour l'avenir et la promesse de nouvelles possibilités de commercialisation. Notre tradition de la croissance grâce à l'excellence est assurée.
Nos centres de conception travaillent en étroite collaboration avec les clients afin d'améliorer constamment sa gamme standard de produits et de technologies et de développer sur mesure, des pays et des solutions spécifiques à l'industrie. Caledonian & Addison a établi un vaste réseau de conception, de fabrication, et de logistique dans les principaux marchés du monde pour répondre aux besoins d'externalisation croissants des clients multinationaux et régionaux.
Copyright@ Caledonian Câbles Offshore & Marine
1ADDISONwww.addison-cables.com
P1 ou P1/P8 RFOU/TFOU 0.6/1KV ......................................................................3P18 RU 0.6/1kV ....................................................................................................8P15 UX 0.6/1kV ..................................................................................................12
CONTENU
Moyenne Tension Câbles D’alimentation
Puissance De Feu Résistant Et Câbles De Commande
Résistant Au Feu Moyenne Tension Câbles
Câbles Instrumentation
P5 ou P5/P12 BFOU 0.6/1KV .............................................................................14P17 BU 0.6/1 kV .................................................................................................19P34 BFOU-HCF 0.6/1 kV ....................................................................................23
P2 ou P2/P9 RFOU/TFOU 3.6/6KV ...................................................................26P3 ou P3/P10 RFOU/TFOU 6/10KV ...................................................................29P4 ou P4/P11 RFOU/TFOU 8.7/15KV ................................................................32P19 ou P19/P21 RFOU 12/20KV ........................................................................35
P6 ou P6/P13 BFOU 3.6/6kV .............................................................................38P7 ou P7/P14 BFOU 6/10kV .............................................................................41P30 RFOU-HCF / TFOU-HCF 6/10(12) kV .........................................................44
S1 ou S1/S5 RFOU(i) 250V ................................................................................47S2 ou S2/S6 RFOU(c) 250V ...............................................................................53P16 IFLI 250 V ...................................................................................................59S11 RU(i) 250 V ..................................................................................................61S12 RU(c) 250 V .................................................................................................64
Résistant Au Feu Instrumentation Câbles
S3 ou S3/S7 BFOU(i) 250V ................................................................................67S4 ou S4/S8 BFOU(c) 250V ...............................................................................73S13 BU(i) 250 V .................................................................................................79
Pouvoir Et De Contrôle CâblesCopyright@
Caledonian Câbles Offshore & Marine
Pouvoir et de contrôle Câbles
2 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
RG6 Câble Coaxial Blindé ................................................................................105RG11 Câble Coaxial Blindé ..............................................................................107RG59 Câble Coaxial Blindé ..............................................................................109RG58 Câble Coaxial Blindé .............................................................................. 111RG213 Câble Coaxial Blindé ............................................................................ 113Câble Composite résistant à la boue ................................................................ 115
Câbles De Télécommunications
Câbles De Données
Câbles Coaxiaux
S9 IYXI(c) 60 V ...................................................................................................89S10 IYOI(c) 60 V .................................................................................................91
S14 BU(c) 250 V ................................................................................................82S15 BFOU-HCF(i) 250 V ...................................................................................85S16 BFOU-HCF(c) 250 V ..................................................................................87
F1 QFCI .............................................................................................................93F5 QFCB ............................................................................................................95F6 AICI ...............................................................................................................97
Cat5E UTP/FTP Blindé câble de données .........................................................99Cat6 UTP/FTP Blindé câble de données ..........................................................102
Cable Code Désignation ................................................................................... 117Normes et Tests .... ........................................................................................... 118Caractéristiques du câble ................................................................................ 119Des données électriques ..................................................................................121Identification de base .......................................................................................123
Informations Techniques
Câbles Fibre Optique
Copyright@ Caledonian Câbles Offshore & Marine
Pouvoir et de contrôle Câbles
3ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
P1 ou P1/P8 RFOU/TFOU 0.6/1KV
Applications
Câbles marines sont ignifuge, sans fumée, halogène gratuits résistant à la boue, utilisé pour les systèmes d'éclairage de contrôle et de puissance.
Normes
IEC 60092-353 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs : Étamé recuite cuivre multibrins IEC 60228 classe 2. Isolation: Sans halogène EPR. XLPE peut être proposé en option (pour le câble
TFOU) Literie: Composé sans halogène. Armour: Fil de cuivre étamé tresse. Gaine extérieure: Sans halogène composés thermodurcissables, SHF2 (de TYPE
P1). Halogène gratuit, résistant à la boue thermodurcissable composé, boue de la SHF (de TYPE P1/P8), de couleur noire.
Caractéristiques électriques
Cross Section Nominale Zone mm² 1.5 2.5 4 6 10 16 25 35 50 70Chef d’orchestre Diamètre nominal mm 1.6 2.1 2.6 3.2 4.0 5.1 6.5 7.4 8.7 10.3Resistant@20℃ DC maximale Ω/km 12.2 7.56 4.7 3.11 1.84 1.16 0.734 0.529 0.391 0.27
Fil De Cuivre Ètamé
Halogène Gratuit Isolation EPR/XLPE
Literie Sans Halogène
Conducteur En Cuivre Multibrins
SHF2/SHF Gaine De Boue
Copyright@ Caledonian Câbles Offshore & Marine
Pouvoir et de contrôle Câbles
4 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Courant Nominal Continu@45℃ 1 Core A 23 30 40 52 72 96 127 157 196 242
Courant Nominal Continu@45℃ 2 Core A 20 26 34 44 61 82 108 133 167 206
Courant Nominal Continu@45℃ 3&4 Core A 16 21 28 36 50 67 89 110 137 169
1s courant de court circuit A 210 360 570 860 1430 2290 3580 5010 7150 10020Tension de fonctionnement KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1
Cross Section Nominale Zone mm² 95 120 150 185 240 300 400 500 630Chef d’orchestre Diamètre nominal mm 12.2 13.8 15.1 17.0 19.6 21.9 24.6 27.6 32.5Resistant@20℃ DC maximale Ω/km 0.195 0.154 0.126 0.1 0.0762 0.0607 0.0475 0.0369 0.0286Courant Nominal Continu@45℃ 1 Core A 293 339 389 444 522 601 690 780 890Courant Nominal Continu@45℃ 2 Core A 249 288 331 444 444 511 587 663 757Courant Nominal Continu@45℃ 3&4 Core A 205 237 272 311 365 421 483 546 623
1s courant de court circuit A 13590 17170 21460 26470 34340 42930 57230 71540 90140Tension de fonctionnement KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1
Remarque : Pour plus de 4 cœurs, les notations actuelles peuvent être calculées par la formule ,I1= L a note actuelle pendant 1-coeure, N = Nombre de conducteurs.
Facteurs de Correction de la température ambianteFacteurs de Correction de la température ambiante 35 40 45 50 55 60 65 70 75 80
Facteur Note 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47
Propriétés mécaniques et thermiques
Rayon de cintrage: 8×OD (lors de l’installation); 6×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids Construction
de no des carottes × coupe
transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
1×1.5 1.0 1.1 1.1 8.9 1351×2.5 1.0 1.1 1.1 9.3 1501×4 1.0 1.1 1.1 9.9 1801×6 1.0 1.1 1.1 10.4 2051×10 1.0 1.1 1.2 12.2 2951×16 1.0 1.1 1.2 13.5 385
Copyright@ Caledonian Câbles Offshore & Marine
Pouvoir et de contrôle Câbles
5ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des
carottes × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
1×25 1.2 1.1 1.2 15.4 5251×35 1.2 1.1 1.3 16.9 6851×50 1.4 1.1 1.4 18.7 8701×70 1.4 1.1 1.4 20.4 11051×95 1.6 1.1 1.5 22.8 14351×120 1.6 1.2 1.6 24.9 17451×150 1.8 1.2 1.6 26.8 20551×185 2.0 1.2 1.7 29.3 25601×240 2.2 1.2 1.8 32.5 31901×300 2.4 1.2 1.9 35.2 39351×400 2.4 1.4 2.1 40.5 50601×500 2.4 1.4 2.2 44.0 61801×630 2.4 1.4 2.3 48.0 76202×1.5 1.0 1.1 1.2 13.6 2952×2.5 1.0 1.1 1.2 14.4 3352×4 1.0 1.1 1.3 16.1 4452×6 1.0 1.1 1.3 17.1 5202×10 1.0 1.1 1.4 19.3 6802×16 1.0 1.1 1.5 21.7 9552×25 1.2 1.2 1.6 25.9 13352×35 1.2 1.2 1.7 27.9 15952×50 1.4 1.2 1.9 31.9 22502×70 1.4 1.2 2.1 35.8 27952×95 1.6 1.2 2.3 41.2 37802×120 1.6 1.4 2.4 44.8 45602×150 1.8 1.4 2.6 49.2 55002×185 2.0 1.4 2.7 53.8 66752×240 2.2 1.6 3.0 61.0 86052×300 2.4 1.6 3.2 67.0 105103×1.5 1.0 1.1 1.2 14.2 3203×2.5 1.0 1.1 1.3 15.6 4153×4 1.0 1.1 1.3 16.8 5003×6 1.0 1.1 1.4 18.1 6053×10 1.0 1.1 1.4 20.3 7953×16 1.0 1.1 1.5 22.8 11253×25 1.2 1.2 1.6 27.5 16203×35 1.2 1.2 1.7 29.6 19553×50 1.4 1.2 1.9 33.9 27303×70 1.4 1.4 2.0 38.4 36553×95 1.6 1.4 2.2 43.8 4885
Copyright@ Caledonian Câbles Offshore & Marine
Pouvoir et de contrôle Câbles
6 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des
carottes × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
3×120 1.6 1.4 2.3 47.6 60003×150 1.8 1.6 2.5 52.4 73003×185 2.0 1.6 2.7 58.6 89603×240 2.2 1.8 2.9 66.1 116103×300 2.2 1.8 3.4 71.9 134904×1.5 1.0 1.1 1.3 15.7 3504×2.5 1.0 1.1 1.3 16.6 4254×4 1.0 1.1 1.4 18.1 5904×6 1.0 1.1 1.4 19.5 7254×10 1.0 1.1 1.5 22.1 9554×16 1.0 1.2 1.6 25.2 13754×25 1.2 1.2 1.7 30.0 19654×35 1.2 1.2 1.8 32.4 24104×50 1.4 1.4 2.0 37.3 33654×70 1.4 1.4 2.2 42.1 45804×95 1.6 1.4 2.4 48.2 6020
4×120 1.6 1.6 2.5 52.7 74404×150 1.8 1.6 2.9 58.3 88004×185 2.0 1.6 3.1 64.0 107604×240 2.2 1.8 3.4 72.4 138904×300 2.4 1.8 3.7 79.8 174055×1.5 1.0 1.1 1.3 16.7 4206×1.5 1.0 1.1 1.3 17.8 4957×1.5 1.0 1.1 1.3 17.8 5408×1.5 1.0 1.1 1.5 20.3 6459×1.5 1.0 1.1 1.5 21.5 67510×1.5 1.0 1.1 1.5 21.8 70512×1.5 1.0 1.1 1.5 22.5 80514×1.5 1.0 1.1 1.6 23.6 86016×1.5 1.0 1.1 1.7 24.9 94019×1.5 1.0 1.1 1.7 26.0 110020×1.5 1.0 1.1 1.7 27.2 113023×1.5 1.0 1.1 1.8 29.3 128524×1.5 1.0 1.1 1.8 30.0 130527×1.5 1.0 1.1 1.9 30.8 146030×1.5 1.0 1.1 1.9 31.8 152033×1.5 1.0 1.2 2.0 33.5 167037×1.5 1.0 1.2 2.0 34.6 184044×1.5 1.0 1.2 2.2 39.2 22105×2.5 1.0 1.1 1.4 18.0 555
Copyright@ Caledonian Câbles Offshore & Marine
Pouvoir et de contrôle Câbles
7ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des
carottes × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
6×2.5 1.0 1.1 1.4 19.2 5907×2.5 1.0 1.1 1.4 19.2 6558×2.5 1.0 1.1 1.5 21.8 7759×2.5 1.0 1.1 1.6 23.3 78510×2.5 1.0 1.1 1.6 23.6 86512×2.5 1.0 1.1 1.6 24.5 95514×2.5 1.0 1.1 1.7 25.5 107016×2.5 1.0 1.1 1.7 26.7 115519×2.5 1.0 1.1 1.8 28.2 136020×2.5 1.0 1.1 1.8 29.5 141023×2.5 1.0 1.1 1.9 31.8 161024×2.5 1.0 1.2 2.0 33.2 169027×2.5 1.0 1.2 2.0 33.9 181530×2.5 1.0 1.2 2.0 34.9 196033×2.5 1.0 1.2 2.1 36.7 219037×2.5 1.0 1.2 2.1 38.0 237044×2.5 1.0 1.2 2.3 42.6 2795
Remarque : Pour un câble XLPE isolé, une mince épaisseur de l'isolation est appliquée.
Copyright@ Caledonian Câbles Offshore & Marine
Pouvoir et de contrôle Câbles
8 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
P18 RU 0.6/1kV
Applications
Ces câbles sont ignifuge, sans fumée, halogène gratuits résistant à la boue, utilisé pour les systèmes d'éclairage de contrôle et de puissance.
Normes
IEC 60092-353 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Étamé recuite cuivre multibrins IEC 60228 classe 2. Isolation: Sans halogène EPR. Gaine extérieure: Halogène composé thermodurcissable libre, SHF2, de couleur
noire.
Caractéristiques électriques
Cross Section Nominale Zone mm² 1.5 2.5 4 6 10 16 25 35Chef d’orchestre Diamètre nominal mm 1.6 2.1 2.6 3.2 4 5.1 6.5 7.4Resistant@20℃ DC maximale Ω/km 12.2 7.56 4.7 3.11 1.84 1.16 0.734 0.529Courant Nominal Continu@45℃ 1 Core A 23 30 40 52 72 96 127 157Courant Nominal Continu@45℃ 2 Core A 20 26 34 44 61 82 108 133Courant Nominal Continu@45℃ 3&4 Core A 16 21 28 36 50 67 89 110
1s courant de court circuit A 210 360 570 860 1430 2290 3580 5010Tension de fonctionnement KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1
Isolation EPR Gratuit Halogène
Conducteur En Cuivre Multibrins
SHF2 Gaine
Copyright@ Caledonian Câbles Offshore & Marine
Pouvoir et de contrôle Câbles
9ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Cross Section Nominale Zone mm² 50 70 95 120 150 185 240 300Chef d’orchestre Diamètre nominal mm 8.7 10.3 12.2 13.8 15.1 17.0 19.6 21.9Resistant@20℃ DC maximale Ω/km 0.391 0.27 0.195 0.154 0.126 0.1 0.0762 0.0607Courant Nominal Continu@45℃ 1 Core A 196 242 293 339 389 444 522 601Courant Nominal Continu@45℃ 2 Core A 167 206 249 288 331 444 444 511Courant Nominal Continu@45℃ 3&4 Core A 137 169 205 237 272 311 365 4211s courant de court circuit A 7150 10020 13590 17170 21460 26470 34340 42930Tension de fonctionnement KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1
Remarque : Pour plus de 4 cœurs, les notations actuelles peuvent être calculées par la formule , I1= La note actuelle pendant 1-coeure, N = Nombre de conducteurs.
Facteurs de Correction de la température ambiante
Facteurs de Correction de la température ambiante 35 40 45 50 55 60 65 70 75 80
Facteur Note 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47
Propriétés mécaniques et thermiques
Rayon de cintrage: 8×OD (lors de l’installation); 6×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des carottes × coupe
transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
1×1.5 1.0 1.0 6.0 601×2.5 1.0 1.0 6.5 801×4 1.0 1.0 7.1 1101×6 1.0 1.0 7.6 1301×10 1.0 1.1 8.5 1651×16 1.0 1.1 9.8 2351×25 1.2 1.2 11.7 3551×35 1.2 1.2 12.8 4551×50 1.4 1.3 14.4 5951×70 1.4 1.4 16.3 8051×95 1.6 1.5 18.7 10901×120 1.6 1.5 20.3 13451×150 1.8 1.6 22.4 16351×185 2.0 1.7 24.9 2075
Copyright@ Caledonian Câbles Offshore & Marine
Pouvoir et de contrôle Câbles
10 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des carottes × coupe
transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
1×240 2.2 1.8 28.1 26601×300 2.4 1.9 30.8 33402×1.5 1.0 1.1 9.7 1452×2.5 1.0 1.1 10.5 1752×4 1.0 1.2 11.6 2252×6 1.0 1.2 12.9 2952×10 1.0 1.3 14.8 4202×16 1.0 1.4 17.2 6052×25 1.2 1.5 21.3 9402×35 1.2 1.6 23.3 11852×50 1.4 1.8 26.9 15852×70 1.4 1.9 31.9 22802×95 1.6 2.1 36.9 30902×120 1.6 2.2 40.3 37802×150 1.8 2.4 44.7 46402×185 2.0 2.6 49.5 57502×240 2.2 2.8 56.1 74602×300 2.4 3.0 62.0 92653×1.5 1.0 1.1 10.3 1653×2.5 1.0 1.2 11.1 2053×4 1.0 1.2 12.5 2803×6 1.0 1.3 13.6 3603×10 1.0 1.3 16.0 5303×16 1.0 1.4 18.5 7703×25 1.2 1.6 22.9 12003×35 1.2 1.7 25.0 15253×50 1.4 1.8 28.7 20303×70 1.4 2.0 32.6 27653×95 1.6 2.2 37.6 37453×120 1.6 2.3 41.2 46403×150 1.8 2.5 45.7 56753×185 2.0 2.7 51.2 72003×240 2.2 3.0 57.5 93003×300 2.4 3.2 66.8 120804×1.5 1.0 1.2 11.2 2004×2.5 1.0 1.2 12.4 2554×4 1.0 1.3 13.7 3404×6 1.0 1.3 15.2 4554×10 1.0 1.4 17.5 6654×16 1.0 1.5 20.4 9704×25 1.2 1.7 25.5 15304×35 1.2 1.8 27.8 19554×50 1.4 2.0 31.9 2600
Copyright@ Caledonian Câbles Offshore & Marine
Pouvoir et de contrôle Câbles
11ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des carottes × coupe
transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
4×70 1.4 2.1 36.3 35404×95 1.6 2.4 42.0 48154×120 1.6 2.5 46.0 59654×150 1.8 2.7 53.5 77204×185 2.0 2.9 59.2 95704×240 2.2 3.2 67.3 124804×300 2.4 3.5 74.6 158705×1.5 1.0 1.2 13.1 2456×1.5 1.0 1.3 14.4 2757×1.5 1.0 1.3 14.4 2858×1.5 1.0 1.4 16.9 3809×1.5 1.0 1.4 18.1 39510×1.5 1.0 1.4 18.4 43512×1.5 1.0 1.4 19.0 48514×1.5 1.0 1.5 20.2 56516×1.5 1.0 1.5 21.3 61519×1.5 1.0 1.6 22.6 71520×1.5 1.0 1.6 23.8 78023×1.5 1.0 1.7 25.9 90524×1.5 1.0 1.7 26.6 92027×1.5 1.0 1.7 27.2 98530×1.5 1.0 1.8 28.4 111033×1.5 1.0 1.8 29.5 119037×1.5 1.0 1.9 30.8 131544×1.5 1.0 2.0 34.8 15605×2.5 1.0 1.3 14.3 3056×2.5 1.0 1.3 15.6 3607×2.5 1.0 1.3 15.6 3908×2.5 1.0 1.4 18.4 4959×2.5 1.0 1.5 19.9 50510×2.5 1.0 1.5 20.2 57012×2.5 1.0 1.5 20.9 62514×2.5 1.0 1.5 21.9 73516×2.5 1.0 1.6 23.3 81019×2.5 1.0 1.6 24.6 93520×2.5 1.0 1.7 26.1 103523×2.5 1.0 1.8 28.4 120524×2.5 1.0 1.8 29.2 122027×2.5 1.0 1.8 29.9 129530×2.5 1.0 1.9 31.1 147533×2.5 1.0 1.9 32.3 158537×2.5 1.0 2.0 33.8 173044×2.5 1.0 2.2 38.4 2100
Copyright@ Caledonian Câbles Offshore & Marine
Pouvoir et de contrôle Câbles
12 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
P15 UX 0.6/1kV
Applications
Ces câbles sont ignifuge, sans fumée et halogènes, utilisé pour la mise à la terre et les services de liaison.
Normes
IEC 60092-353 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Tresse cuivre multibrins recuit à la CEI 60228 classe 2 ou classe 5. Isolation: Composé de thermodurcissable, SHF2 sans halogène. Lorsqu’il est utilisé
comme fil conducteur de protection (PE), les câbles de couleur jaune/vert. Lorsqu’il est utilisé comme seul fil, les câbles de couleur blanc cassé, noir, rouge ou bleu.
Caractéristiques électriques
Cross Section Nominale Zone mm² 10 16 25 35 50 70Chef d’orchestre Diamètre nominal mm 4 5.1 6.5 7.4 8.7 10.3Resistant@20℃ DC maximale Ω/km 1.84 1.16 0.734 0.529 0.391 0.27Courant nominal continu@45℃ 1 Coeur A 72 96 127 157 196 2421s courant de court circuit A 1430 2290 3580 5010 7150 10020Tension de fonctionnement KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1
Cross Section Nominale Zone mm² 95 120 150 185 240 300Chef d’orchestre Diamètre nominal mm 12.2 13.8 15.1 17.0 19.6 21.9
SHF2 Isolation
Conducteur En Cuivre Multibrins
Copyright@ Caledonian Câbles Offshore & Marine
Power and Control Cables
13ADDISONwww.addison-cables.com
NEK606 Caledonian Offshore & Marine Cables
www.caledonian-cables.co.uk
Resistant@20℃ DC maximale Ω/km 0.195 0.154 0.126 0.1 0.0762 0.0607Courant nominal continu@45℃ 1 Coeur A 293 339 389 444 522 6011s courant de court circuit A 13590 17170 21460 26470 34340 42930Tension de fonctionnement KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1
Propriétés mécaniques et thermiques
Rayon de cintrage: 8×OD (lors de l’installation); 6×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des carottes × coupe
transversale(mm²)
Épaisseur D'isolation Nominale
mm
Diamètre nominal globalmm
Poids nominalkg/km
1×10 2.0 8.2 160
1×16 2.1 9.4 230
1×25 2.4 11.3 350
1×35 2.4 12.4 450
1×50 2.7 14.4 600
1×70 3.0 16.7 840
1×95 3.0 18.6 1110
1×120 3.1 20.3 1360
1×150 3.4 22.4 1660
1×185 3.7 24.9 2080
1×240 4.0 28.1 2690
1×300 4.3 31.0 3330
Copyright@ Caledonian Câbles Offshore & Marine
Puissance De Feu Résistant Et Câbles De Commande
14 ADDISON www.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
P5 ou P5/P12 BFOU 0.6/1KV
Applications
Ces câbles sont résistants au feu, retardateur de flamme, faible dégagement de fumée, sans halogène et résistants boue, utilisé pour les systèmes de contrôle, de puissance et d'éclairage.
Normes
IEC 60092-353 IEC 60092-351 IEC 60092-359 IEC 60331-21 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Étamé recuit échoué cuivre compacté à la norme IEC 60228 classe 2.. Isolation: Ruban Mica + Halogène EPR libre/Ruban Mica + XLPE. Literie: Composé sans halogène. Armour: Fil de cuivre étamé tresse. Gaine extérieure: Sans halogène composés thermodurcissables, SHF2 (pour TYPE
P5). Halogène gratuit, résistant à la boue thermodurcissable composé, boue de la SHF (de TYPE P5/P12), de couleur noire.
Caractéristiques électriques
Cross Section Nominale Zone mm² 1.5 2.5 4 6 10 16 25 35 50Chef d’orchestre Diamètre nominal mm 1.6 2.1 2.6 3.2 4 5.1 6.5 7.4 8.7Resistant@20℃ DC maximale Ω/km 12.2 7.56 4.7 3.11 1.84 1.16 0.734 0.529 0.391
Fil De Cuivre Ètamé
Bande De Mica + HFEPR/XLPE Isolation
Literie Sans Halogène
Conducteur En Cuivre Multibrins
SHF2/SHF Gaine De BOUE
Copyright@ Caledonian Câbles Offshore & Marine
Puissance De Feu Résistant Et Câbles De Commande
15ADDISONwww.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Courant Nominal Continu@45℃ 1 Core A 23 30 40 52 72 96 127 157 196Courant Nominal Continu@45℃ 2 Core A 20 26 34 44 61 82 108 133 167Courant Nominal Continu@45℃ 3&4 Core A 16 21 28 36 50 67 89 110 1371s courant de court circuit A 210 360 570 860 1430 2290 3580 5010 7150Tension de fonctionnement KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1
Cross Section Nominale Zone mm² 70 95 120 150 185 240 300 400 630
Chef d’orchestre Diamètre nominal mm 10.3 12.2 13.8 15.1 17.0 19.6 21.9 24.6 32.5
Resistant@20℃ DC maximale Ω/km 0.27 0.195 0.154 0.126 0.1 0.0762 0.0607 0.0475 0.0286
Courant Nominal Continu@45℃ 1 Core A 242 293 339 389 444 522 601 690 890Courant Nominal Continu@45℃ 2 Core A 206 249 288 331 444 444 511 587 757Courant Nominal Continu@45℃ 3&4 Core A 169 205 237 272 311 365 421 483 623
1s courant de court circuit A 10020 13590 17170 21460 26470 34340 42930 57230 90140Tension de fonctionnement KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1
Remarque : Pour plus de 4 cœurs, les notations actuelles peuvent être calculées par la formule , I1= La note actuelle pendant 1-coeure, N = Nombre de conducteurs.
Facteurs de Correction de la température ambiante
Facteurs de Correction de la température ambiante 35 40 45 50 55 60 65 70 75 80
Facteur Note 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47
Propriétés mécaniques et thermiques
Rayon de cintrage: 8×OD (lors de l’installation); 6×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des carottes × coupe
transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
1×1.5 1.0 1.1 1.1 9.3 1451×2.5 1.0 1.1 1.1 9.7 1601×4 1.0 1.1 1.1 10.4 2201×6 1.0 1.1 1.1 10.9 2501×10 1.0 1.1 1.2 12.7 310
Copyright@ Caledonian Câbles Offshore & Marine
Puissance De Feu Résistant Et Câbles De Commande
16 ADDISON www.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des carottes × coupe
transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
1×16 1.0 1.1 1.2 13.9 3901×25 1.2 1.1 1.3 16.3 5851×35 1.2 1.1 1.3 17.2 6901×50 1.4 1.1 1.4 19.0 8901×70 1.4 1.1 1.4 20.6 11101×95 1.6 1.1 1.5 23.1 14401×120 1.6 1.2 1.6 25.0 17351×150 1.8 1.2 1.7 27.0 20601×185 2.0 1.2 1.7 29.4 25451×240 2.2 1.2 1.8 32.6 31701×300 2.4 1.2 1.9 35.3 39101×400 2.4 1.4 2.1 41.0 51001×630 2.8 1.4 2.3 48.5 76602×1.5 1.0 1.1 1.2 14.2 3102×2.5 1.0 1.1 1.3 15.1 3602×4 1.0 1.1 1.3 16.6 4702×6 1.0 1.1 1.4 17.9 5552×10 1.0 1.1 1.4 19.9 7052×16 1.0 1.1 1.5 22.5 9852×25 1.2 1.2 1.6 26.4 13602×35 1.2 1.2 1.7 28.4 16202×50 1.4 1.2 1.9 32.4 22902×70 1.4 1.2 2.1 38.0 32602×95 1.6 1.2 2.3 41.6 39102×120 1.6 1.4 2.4 45.3 47102×150 1.8 1.4 2.6 49.7 56702×185 2.0 1.4 2.7 54.3 68402×240 2.2 1.6 3.0 61.5 87902×300 2.4 1.6 3.2 67.8 106303×1.5 1.0 1.1 1.3 14.8 3453×2.5 1.0 1.1 1.3 16.2 4453×4 1.0 1.1 1.3 17.4 5303×6 1.0 1.1 1.4 18.7 6353×10 1.0 1.1 1.5 21.1 8303×16 1.0 1.1 1.5 23.7 11603×25 1.2 1.2 1.7 28.1 16403×35 1.2 1.2 1.8 30.2 19803×50 1.4 1.2 2.0 34.3 27503×70 1.4 1.2 2.2 39.0 36753×95 1.6 1.4 2.4 44.7 4955
Copyright@ Caledonian Câbles Offshore & Marine
Puissance De Feu Résistant Et Câbles De Commande
17ADDISONwww.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des carottes × coupe
transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
3×120 1.6 1.4 2.5 48.3 60353×150 1.8 1.4 2.7 53.2 73553×185 2.0 1.6 2.9 59.5 90253×240 2.2 1.6 3.2 66.5 115903×300 2.4 1.8 3.4 72.6 137404×1.5 1.0 1.1 1.3 16.4 4004×2.5 1.0 1.1 1.3 17.3 5054×4 1.0 1.1 1.4 18.8 6204×6 1.0 1.1 1.4 20.1 7504×10 1.0 1.1 1.5 22.7 9854×16 1.0 1.2 1.6 25.9 14004×25 1.2 1.2 1.8 30.7 19954×35 1.2 1.2 1.9 33.1 24404×50 1.4 1.4 2.0 38.2 34304×70 1.4 1.4 2.2 42.7 46004×95 1.6 1.6 2.4 49.4 61354×120 1.6 1.6 2.5 53.6 75154×150 1.8 1.6 2.9 59.0 90104×185 2.0 1.6 3.1 64.7 110004×240 2.2 1.8 3.4 73.1 141604×300 2.4 1.8 3.7 80.7 175505×1.5 1.0 1.1 1.4 17.7 5106×1.5 1.0 1.1 1.4 19.0 5457×1.5 1.0 1.1 1.4 19.0 5908×1.5 1.0 1.1 1.5 21.8 7159×1.5 1.0 1.1 1.6 23.3 72010×1.5 1.0 1.1 1.6 23.6 79012×1.5 1.0 1.2 1.6 24.3 88014×1.5 1.0 1.2 1.7 25.5 96516×1.5 1.0 1.2 1.7 26.7 103519×1.5 1.0 1.2 1.7 27.4 118520×1.5 1.0 1.2 1.8 29.5 126023×1.5 1.0 1.2 1.9 31.8 143524×1.5 1.0 1.2 2.0 33.2 151027×1.5 1.0 1.2 2.0 33.9 161530×1.5 1.0 1.2 2.0 34.9 173532×1.5 1.0 1.4 2.0 35.5 180033×1.5 1.0 1.4 2.0 36.7 194037×1.5 1.0 1.4 2.0 38.0 209044×1.5 1.0 1.4 2.3 42.6 2460
Copyright@ Caledonian Câbles Offshore & Marine
Puissance De Feu Résistant Et Câbles De Commande
18 ADDISON www.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des carottes × coupe
transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
5×2.5 1.0 1.1 1.4 18.8 5956×2.5 1.0 1.1 1.4 20.4 6507×2.5 1.0 1.1 1.4 20.4 7008×2.5 1.0 1.1 1.5 23.5 7909×2.5 1.0 1.1 1.6 25.1 86010×2.5 1.0 1.1 1.6 25.4 95512×2.5 1.0 1.2 1.6 26.1 104514×2.5 1.0 1.2 1.7 27.3 116016×2.5 1.0 1.2 1.8 28.8 126519×2.5 1.0 1.2 1.8 29.6 144520×2.5 1.0 1.2 1.9 31.8 154523×2.5 1.0 1.4 2.0 34.7 180524×2.5 1.0 1.4 2.0 35.8 185027×2.5 1.0 1.4 2.0 35.4 197030×2.5 1.0 1.4 2.1 38.1 223533×2.5 1.0 1.4 2.2 39.6 239037×2.5 1.0 1.4 2.3 41.2 261044×2.5 1.0 1.4 2.4 46.2 3075
Remarque : Pour un câble XLPE isolé, une mince épaisseur de l'isolation est appliquée.
Copyright@ Caledonian Câbles Offshore & Marine
Puissance De Feu Résistant Et Câbles De Commande
19ADDISONwww.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
P17 BU 0.6/1 kV
Applications
Ces câbles sont résistants au feu, retardateur de flamme, faible dégagement de fumée et sans halogène, utilisé pour les systèmes de contrôle, de puissance et d'éclairage.
Normes
IEC 60092-353 IEC 60092-351 IEC 60092-359 IEC 60331-21 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-2 NEK 606:2004
Construction
Conducteurs: Étamé recuite cuivre multibrins IEC 60228 classe 2. Isolation: Ruban Mica + Halogène EPR libre. Gaine extérieure: Halogène composé thermodurcissable libre, SHF2, de couleur
noire.
Caractéristiques électriques
Cross Section Nominale Zone mm² 1.5 2.5 4 6 10 16 25 35Chef d’orchestre Diamètre nominal mm 1.6 2.1 2.6 3.2 4 5.1 6.5 7.4Resistant@20℃ DC maximale Ω/km 12.2 7.56 4.7 3.11 1.84 1.16 0.734 0.529Courant Nominal Continu@45℃ 1 Core A 23 30 40 52 72 96 127 157Courant Nominal Continu@45℃ 2 Core A 20 26 34 44 61 82 108 133Courant Nominal Continu@45℃ 3&4 Core A 16 21 28 36 50 67 89 110
Ruban Mica + HFEPR Isolation
Conducteur En Cuivre Multibrins
SHF2 Gaine
Copyright@ Caledonian Câbles Offshore & Marine
Puissance De Feu Résistant Et Câbles De Commande
20 ADDISON www.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
1s courant de court circuit A 210 360 570 860 1430 2290 3580 5010Tension de fonctionnement KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1
Cross Section Nominale Zone mm² 50 70 95 120 150 185 240 300Chef d’orchestre Diamètre nominal mm 8.7 10.3 12.2 13.8 15.1 17.0 19.6 21.9Resistant@20℃ DC maximale Ω/km 0.391 0.27 0.195 0.154 0.126 0.1 0.0762 0.0607Courant Nominal Continu@45℃ 1 Core A 196 242 293 339 389 444 522 601Courant Nominal Continu@45℃ 2 Core A 167 206 249 288 331 444 444 511Courant Nominal Continu@45℃ 3&4 Core A 137 169 205 237 272 311 365 4211s courant de court circuit A 7150 10020 13590 17170 21460 26470 34340 42930Tension de fonctionnement KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1
Remarque : Pour plus de 4 cœurs, les notations actuelles peuvent être calculées par la formule , I1= La note actuelle pendant 1-coeure, N = Nombre de conducteurs.
Facteurs de Correction de la température ambiante
Facteurs de Correction de la température ambiante 35 40 45 50 55 60 65 70 75 80
Facteur Note 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47
Propriétés mécaniques et thermiques
Rayon de cintrage: 8×OD (lors de l’installation); 6×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des carottes × coupe
transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
1×1.5 1.0 1.0 6.4 651×2.5 1.0 1.0 6.8 751×4 1.0 1.0 7.4 951×6 1.0 1.0 7.9 1201×10 1.0 1.1 8.8 1701×16 1.0 1.1 10.2 2401×25 1.2 1.2 12.0 3601×35 1.2 1.2 13.1 4551×50 1.4 1.3 14.7 6001×70 1.4 1.4 16.6 8051×95 1.6 1.5 19.0 10951×120 1.6 1.5 20.6 1345
Copyright@ Caledonian Câbles Offshore & Marine
Puissance De Feu Résistant Et Câbles De Commande
21ADDISONwww.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des carottes × coupe
transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
1×150 1.8 1.6 22.7 16351×185 2.0 1.7 25.2 20701×240 2.2 1.8 28.4 26551×300 2.4 1.9 31.1 33352×1.5 1.0 1.1 10.3 1552×2.5 1.0 1.2 11.0 1902×4 1.0 1.2 12.3 2502×6 1.0 1.3 13.4 3102×10 1.0 1.3 15.6 4452×16 1.0 1.4 18.2 6352×25 1.2 1.6 22.0 9702×35 1.2 1.7 24.0 12152×50 1.4 1.8 27.4 16152×70 1.4 1.9 32.6 23352×95 1.6 2.1 37.6 31552×120 1.6 2.3 41.2 38752×150 1.8 2.4 45.4 47252×185 2.0 2.6 50.2 58452×240 2.2 2.8 56.8 75702×300 2.4 3.1 63.0 93953×1.5 1.0 1.2 10.9 1803×2.5 1.0 1.2 11.9 2303×4 1.0 1.2 13.1 2953×6 1.0 1.3 14.2 3753×10 1.0 1.4 16.5 5503×16 1.0 1.5 19.3 7953×25 1.2 1.6 23.5 12203×35 1.2 1.7 25.6 15453×50 1.4 1.9 29.5 20753×70 1.4 2.0 33.2 27753×95 1.6 2.2 38.5 38003×120 1.6 2.4 42.0 46853×150 1.8 2.5 46.3 56853×185 2.0 2.7 51.8 72153×240 2.2 3.0 58.0 93203×300 2.4 3.2 67.6 122804×1.5 1.0 1.2 12.1 2254×2.5 1.0 1.2 13.0 2754×4 1.0 1.3 14.5 3654×6 1.0 1.4 15.8 4904×10 1.0 1.4 18.4 6954×16 1.0 1.5 21.5 10054×25 1.2 1.7 26.1 15504×35 1.2 1.8 28.5 1970
Copyright@ Caledonian Câbles Offshore & Marine
Puissance De Feu Résistant Et Câbles De Commande
22 ADDISON www.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des carottes × coupe
transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
4×50 1.4 2.0 32.8 26454×70 1.4 2.2 36.9 35454×95 1.6 2.4 42.8 48504×120 1.6 2.6 46.5 59654×150 1.8 2.8 54.6 80204×185 2.0 3.0 60.3 99304×240 2.2 3.3 68.4 129204×300 2.4 3.5 75.5 159955×1.5 1.0 1.3 14.3 2656×1.5 1.0 1.3 15.6 3057×1.5 1.0 1.3 15.6 3208×1.5 1.0 1.4 18.4 4259×1.5 1.0 1.5 19.9 44010×1.5 1.0 1.5 20.2 49512×1.5 1.0 1.5 20.9 53014×1.5 1.0 1.6 21.9 63016×1.5 1.0 1.6 23.3 69019×1.5 1.0 1.6 24.6 79020×1.5 1.0 1.7 26.1 88023×1.5 1.0 1.8 28.4 103024×1.5 1.0 1.8 29.2 103527×1.5 1.0 1.8 29.9 108030×1.5 1.0 1.9 31.1 125033×1.5 1.0 1.9 32.3 133537×1.5 1.0 2.0 33.8 144544×1.5 1.0 2.2 38.4 17655×2.5 1.0 1.3 14.5 3406×2.5 1.0 1.4 17.0 3957×2.5 1.0 1.4 17.0 4208×2.5 1.0 1.5 20.0 5359×2.5 1.0 1.5 21.5 56010×2.5 1.0 1.5 21.8 62012×2.5 1.0 1.6 22.7 68014×2.5 1.0 1.6 23.9 81016×2.5 1.0 1.7 25.4 89519×2.5 1.0 1.7 26.8 100020×2.5 1.0 1.8 28.4 114023×2.5 1.0 1.9 30.9 132524×2.5 1.0 1.9 31.8 134027×2.5 1.0 1.9 32.5 139530×2.5 1.0 2.0 33.9 162033×2.5 1.0 2.0 35.2 173537×2.5 1.0 2.1 36.8 186544×2.5 1.0 2.3 41.8 2295
Copyright@ Caledonian Câbles Offshore & Marine
Puissance De Feu Résistant Et Câbles De Commande
23ADDISONwww.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
P34 BFOU-HCF 0.6/1 kV
Applications
Ces câbles sont résistants au feu, retardateur de flamme, faible dégagement de fumée et sans halogène, utilisé pour les systèmes de contrôle d'urgence, alimentation et d'éclairage qui doivent être opérationnels pendant un feu d'hydrocarbures 1100 ℃.
Normes
IEC 60092-353 IEC 60092-351 IEC 60092-359 IEC 60331-21 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Étamé recuit échoué cuivre compacté à la norme IEC 60228 classe 2.. Isolation: Ruban Mica + Halogène EPR libre/XLPE. Literie: Composé sans halogène. Armour: Fil de cuivre étamé tresse. Gaine extérieure1: Halogène composé thermodurcissable libre, SHF2. HC-Protection Contre L’incendie: Extruded thermoplastic fire protection compound. Enregistrement :Ruban de fibre de verre rodé. Gaine extérieure2: Ignifuge sans halogène thermoplastique composé, SHF1, couleur
noir. .
SHF2 Gaine
Ruban Mica + HFEPR/XLPE IsolationLiterie Sans Halogène
Conducteur En Cuivre Multibrins
SHF1 Gaine
HC-Protection Contre L'incendie+Ruban AdhésifFil De Cuivre Ètamé
Copyright@ Caledonian Câbles Offshore & Marine
Puissance De Feu Résistant Et Câbles De Commande
24 ADDISON www.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Caractéristiques électriques
Cross Section Nominale Zone mm² 1.5 2.5 4 6 16 35Chef d’orchestre Diamètre nominal mm 1.6 2.1 2.6 3.2 5.1 7.4Resistant@20℃ DC maximale Ω/km 12.2 7.56 4.7 3.11 1.16 0.529Courant Nominal Continu@45℃ 1 Core A 23 30 40 52 96 157Courant Nominal Continu@45℃ 2 Core A 20 26 34 44 82 133Courant Nominal Continu@45℃ 3&4 Core A 16 21 28 36 67 1101s courant de court circuit A 210 360 570 860 2290 5010Tension de fonctionnement KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1
Cross Section Nominale Zone mm² 50 70 95 120 150 185 240 300Chef d’orchestre Diamètre nominal mm 8.7 10.3 12.2 13.8 15.1 17.0 19.6 21.9Resistant@20℃ DC maximale Ω/km 0.391 0.27 0.195 0.154 0.126 0.1 0.0762 0.0607Courant Nominal Continu@45℃ 1 Core A 196 242 293 339 389 444 522 601Courant Nominal Continu@45℃ 2 Core A 167 206 249 288 331 444 444 511Courant Nominal Continu@45℃ 3&4 Core A 137 169 205 237 272 311 365 4211s courant de court circuit A 7150 10020 13590 17170 21460 26470 34340 42930Tension de fonctionnement KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1
Remarque : Pour plus de 4 cœurs, les notations actuelles peuvent être calculées par la formule , I1= La note actuelle pendant 1-coeure, N = Nombre de conducteurs.
Facteurs de Correction de la température ambiante
Facteurs de Correction de la température ambiante 35 40 45 50 55 60 65 70 75 80
Facteur Note 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47
Propriétés mécaniques et thermiques
Rayon de cintrage: 20×OD (lors de l’installation); 12×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Copyright@ Caledonian Câbles Offshore & Marine
Puissance De Feu Résistant Et Câbles De Commande
25ADDISONwww.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Dimensions et poids
Construction de no des
carottes × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Diamètre nominal cours Literie
mm
Diamètre nominal sur gaine1
mm
Diamètre nominal global mm
Poids nominalkg/km
1×50 1.4 15.0 18.5 45.5 29001×70 1.4 16.5 20.5 47.5 33001×95 1.6 18.5 23.0 50.5 38001×120 1.6 20.5 25.0 52.5 42601×150 1.8 23.0 27.0 54.5 47501×185 2.0 25.0 29.5 57.5 53801×240 2.2 28.0 32.5 66.0 70501×300 2.4 30.5 35.5 68.0 80002×1.5 1.0 10.0 13.0 40.5 18902×2.5 1.0 11.0 14.5 42.0 20803×1.5 1.0 10.5 14.0 42.0 21403×2.5 1.0 11.5 15.0 42.5 22003×4 1.0 13.0 16.5 43.0 24003×6 1.0 14.0 18.0 45.0 26003×16 1.0 18.5 23.0 50.0 35003×35 1.2 25.0 29.5 57.5 48403×70 1.4 33.0 39.0 72.0 81503×120 1.6 41.0 48.0 81.5 113003×150 1.8 46.0 54.5 88.5 133004×2.5 1.0 12.5 16.5 44.0 23004×6 1.0 15.5 19.5 47.5 28704×16 1.0 20.5 25.0 53.5 38307×1.5 1.0 14.0 17.5 44.5 255012×1.5 1.0 18.5 22.5 50.0 314027×1.5 1.0 26.5 31.0 64.5 50707×2.5 1.0 15.0 19.0 46.0 276012×2.5 1.0 20.5 24.5 52.0 3500
Remarque : Pour un câble XLPE isolé, une mince épaisseur de l'isolation est appliquée.
Copyright@ Caledonian Câbles Offshore & Marine
Moyenne Tension Câbles D'alimentation
26 ADDISON www.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
P2 ou P2/P9 RFOU/TFOU 3.6/6KV
Applications
Ces câbles sont ignifuges, faible dégagement de fumée, sans halogène et résistants boue, utilisé pour l'installation fixe pour moyenne tension.
Normes
IEC 60092-354 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Circulaire cuivre recuit étamé brin CEI 60228 classe 2. Écran du conducteur: Semi en matériau conducteur. Isolation: Sans halogène EPR. XLPE peut être proposé en option (pour le câble
TFOU). Écran d’isolation: Semi matériau conducteur et étamé tresse de fils de cuivre. Literie: Composé sans halogène. Armour: Fil de cuivre étamé tresse. Gaine extérieure: Halogène composé thermodurcissable libre, SHF2 (pour le TYPE
P2), ou un halogène boue sans composé thermodurcissable résistant, SHF MUD (pour le TYPE P2/P9), de couleur rouge.
Caractéristiques électriques
Cross Section Nominale Zone mm² 16 25 35 50 70 95 120
Fil De Cuivre Ètamé
HFEPR/XLPE Isolation
Literie Sans HalogèneConducteur En Cuivre Multibrins
SHF2/SHF Gaine De BOUEÉcran D’isolationÉcran Du Conducteur
Copyright@ Caledonian Câbles Offshore & Marine
Moyenne Tension Câbles D'alimentation
27ADDISONwww.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Chef d'orchestre Diamètre nominal mm 5.1 6.5 7.4 8.7 10.3 12.2 13.8Resistant@20℃ DC maximale Ω/km 1.16 0.734 0.529 0.391 0.27 0.195 0.154Courant Nominal Continu@45℃ 1 Core A 96 127 157 196 242 293 339Courant Nominal Continu@45℃ 3 Core A 67 89 110 137 169 205 2371s courant de court circuit A 2290 3580 5010 7150 10020 13590 17170Tension de fonctionnement KV 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6
Cross Section Nominale Zone mm² 150 185 240 300 400 500 630Chef d’orchestre Diamètre nominal mm 15.1 17.0 19.6 21.9 24.6 27.6 32.5Resistant@20℃ DC maximale Ω/km 0.126 0.1 0.0762 0.0607 0.0475 0.0369 0.0286Courant Nominal Continu@45℃ 1 Core A 389 444 522 601 690 780 890Courant Nominal Continu@45℃ 3 Core A 272 311 365 421 483 546 6231s courant de court circuit A 21460 26470 34340 42930 57230 71540 90140Tension de fonctionnement KV 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6
Facteurs de Correction de la température ambiante
Facteurs de Correction de la température ambiante
35 40 45 50 55 60 65 70 75 80
Facteur Note 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47
Propriétés mécaniques et thermiques
Rayon de cintrage: 15×OD (lors de l’installation); 9×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des
carottes × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
1×16 2.5 1.4 1.1 22.8 7801×25 2.5 1.5 1.1 24.0 10201×35 2.5 1.5 1.2 25.1 11551×50 2.5 1.6 1.2 26.3 13201×70 2.5 1.6 1.3 28.2 15951×95 2.5 1.7 1.3 30.0 1905
Copyright@ Caledonian Câbles Offshore & Marine
Moyenne Tension Câbles D'alimentation
28 ADDISON www.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des
carottes × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
1×120 2.5 1.8 1.4 31.8 22351×150 2.5 1.8 1.4 33.5 25501×185 2.5 1.9 1.5 35.4 30151×240 2.6 2.0 1.5 38.8 37251×300 2.8 2.1 1.6 42.3 46251×400 3.0 2.2 1.7 46.6 54201×500 3.2 2.4 1.8 50.8 66101×630 3.2 2.5 1.9 55.1 81703×16 2.5 2.2 1.6 44.9 29303×25 2.5 2.3 1.7 45.4 33903×35 2.5 2.4 1.8 47.6 38203×50 2.5 2.5 1.9 50.9 44953×70 2.5 2.7 2.0 54.8 55853×95 2.5 2.8 2.1 58.9 67653×120 2.5 3.0 2.2 63.5 81653×150 2.5 3.1 2.3 67.4 94953×185 2.5 3.3 2.4 75.8 106603×240 2.6 3.5 2.5 82.3 116603×300 2.8 3.8 2.7 89.3 12940
Remarque : Pour un câble XLPE isolé, une mince épaisseur de l'isolation est appliquée.
Copyright@ Caledonian Câbles Offshore & Marine
Moyenne Tension Câbles D'alimentation
29ADDISONwww.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
P3 ou P3/P10 RFOU/TFOU 6/10KV
Applications
Ces câbles sont ignifuges, faible dégagement de fumée, sans halogène et résistants boue, utilisé pour l'installation fixe pour moyenne tension.
Normes
IEC 60092-354 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Circulaire cuivre recuit étamé brin CEI 60228 classe 2. Écran du conducteur: Semi en matériau conducteur. Isolation: Sans halogène EPR. XLPE peut être proposé en option (pour le câble
TFOU). Écran d’isolation: Semi matériau conducteur et étamé tresse de fils de cuivre. Literie: Composé sans halogène. Armour: Fil de cuivre étamé tresse. Gaine extérieure: Halogène composé thermodurcissable libre, SHF2 (pour le TYPE
P3), ou un halogène boue sans composé thermodurcissable résistant, SHF MUD (pour le TYPE P3/P10), de couleur rouge.
Caractéristiques électriques
Cross Section Nominale Zone mm² 16 25 35 50 70 95 120
Fil De Cuivre Ètamé
HFEPR/XLPE Isolation
Literie Sans HalogèneConducteur En Cuivre Multibrins
SHF2/SHF Gaine De BOUEÉcran D’isolationÉcran Du Conducteur
Copyright@ Caledonian Câbles Offshore & Marine
Moyenne Tension Câbles D'alimentation
30 ADDISON www.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Chef d’orchestre Diamètre nominal mm 5.2 6.5 7.4 8.7 10.3 12.2 13.8Resistant@20℃ DC maximale Ω/km 1.16 0.734 0.529 0.391 0.27 0.195 0.154Courant Nominal Continu@45℃ 1 Core A 96 127 157 196 242 293 339Courant Nominal Continu@45℃ 3 Core A 67 89 110 137 169 205 2371s courant de court circuit A 2290 3580 5010 7150 10020 13590 17170Tension de fonctionnement KV 6/10 6/10 6/10 6/10 6/10 6/10 6/10
Cross Section Nominale Zone mm² 150 185 240 300 400 500 630Chef d’orchestre Diamètre nominal mm 15.1 17.0 19.6 21.9 24.5 27.5 32.3Resistant@20℃ DC maximale Ω/km 0.126 0.1 0.0762 0.0607 0.0475 0.0369 0.0286Courant Nominal Continu@45℃ 1 Core A 389 444 522 601 690 780 890Courant Nominal Continu@45℃ 3 Core A 272 311 365 421 483 546 6231s courant de court circuit A 21460 26470 34340 42930 57230 71540 90140Tension de fonctionnement KV 6/10 6/10 6/10 6/10 6/10 6/10 6/10
Facteurs de Correction de la température ambianteFacteurs de Correction de la température ambiante 35 40 45 50 55 60 65 70 75 80
Facteur Note 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47
Propriétés mécaniques et thermiques
Rayon de cintrage: 15×OD (lors de l’installation); 9×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des
carottes × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
1×16 3.4 1.5 1.1 24.0 9001×25 3.4 1.5 1.2 26.0 11401×35 3.4 1.6 1.2 26.9 12651×50 3.4 1.6 1.2 28.3 14601×70 3.4 1.7 1.3 30.0 17101×95 3.4 1.8 1.3 32.0 20601×120 3.4 1.8 1.4 33.8 23801×150 3.4 1.9 1.4 35.3 27001×185 3.4 2.0 1.5 37.8 3225
Copyright@ Caledonian Câbles Offshore & Marine
Moyenne Tension Câbles D'alimentation
31ADDISONwww.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des
carottes × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
1×240 3.4 2.1 1.6 41.0 39901×300 3.4 2.2 1.6 43.7 47601×400 3.4 2.3 1.7 45.5 59001×500 3.4 2.4 1.8 49.5 73501×630 3.4 2.6 1.9 54.5 87503×16 3.4 2.3 1.7 46.0 33003×25 3.4 2.4 1.8 50.1 39053×35 3.4 2.5 1.8 52.2 43603×50 3.4 2.6 1.9 55.1 51853×70 3.4 2.7 2.0 58.9 61253×95 3.4 2.9 2.1 63.5 75003×120 3.4 3.0 2.2 67.6 87753×150 3.4 3.2 2.3 71.7 102353×185 3.4 3.4 2.4 74.0 113003×240 3.4 3.6 2.6 79.5 133003×300 3.4 3.8 2.7 85.0 16300
Remarque : Pour un câble XLPE isolé, une mince épaisseur de l'isolation est appliquée.
Copyright@ Caledonian Câbles Offshore & Marine
Moyenne Tension Câbles D'alimentation
32 ADDISON www.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
P4 ou P4/P11 RFOU/TFOU 8.7/15KV
Applications
Ces câbles sont ignifuges, faible dégagement de fumée, sans halogène et résistants boue, utilisé pour l'installation fixe pour moyenne tension.
Normes
IEC 60092-354 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Circulaire cuivre recuit étamé brin CEI 60228 classe 2. Écran du conducteur: Semi en matériau conducteur. Isolation: Sans halogène EPR. XLPE peut être proposé en option (pour le câble
TFOU). Écran d’isolation: Semi matériau conducteur et étamé tresse de fils de cuivre. Literie: Composé sans halogène. Armour: Fil de cuivre étamé tresse. Gaine extérieure: Halogène composé thermodurcissable libre, SHF2 (pour le TYPE
P4), ou un halogène boue sans composé thermodurcissable résistant, SHF MUD (pour le TYPE P4/P11), de couleur rouge.
Caractéristiques électriques
Cross Section Nominale Zone mm² 25 35 50 70 95 120
Fil De Cuivre Ètamé
HFEPR/XLPE Isolation
Literie Sans HalogèneConducteur En Cuivre Multibrins
SHF2/SHF Gaine De BOUEÉcran D’isolationÉcran Du Conducteur
Copyright@ Caledonian Câbles Offshore & Marine
Moyenne Tension Câbles D'alimentation
33ADDISONwww.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Chef d’orchestre Diamètre nominal mm 6.5 7.4 8.7 10.3 12.2 13.8Resistant@20℃ DC maximale Ω/km 0.734 0.529 0.391 0.27 0.195 0.154Courant Nominal Continu@45℃ 1 Core A 127 157 196 242 293 339Courant Nominal Continu@45℃ 3 Core A 89 110 137 169 205 2371s courant de court circuit A 3580 5010 7150 10020 13590 17170Tension de fonctionnement KV 8.7/15 8.7/15 8.7/15 8.7/15 8.7/15 8.7/15
Cross Section Nominale Zone mm² 150 185 240 300 400 500 630Chef d’orchestre Diamètre nominal mm 15.1 17.0 19.6 21.9 24.5 27.5 32.3Resistant@20℃ DC maximale Ω/km 0.126 0.1 0.0762 0.0607 0.0475 0.0369 0.0286Courant Nominal Continu@45℃ 1 Core A 389 444 522 601 690 780 890Courant Nominal Continu@45℃ 3 Core A 272 311 365 421 483 546 6231s courant de court circuit A 21460 26470 34340 42930 57230 71540 90140Tension de fonctionnement KV 8.7/15 8.7/15 8.7/15 8.7/15 8.7/15 8.7/15 8.7/15
Facteurs de Correction de la température ambiante
Facteurs de Correction de la température ambiante 35 40 45 50 55 60 65 70 75 80
Facteur Note 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47
Propriétés mécaniques et thermiques
Rayon de cintrage: 15×OD (lors de l’installation); 9×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des
carottes × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur1×25 4.5 1.6 1.2 28.4 13051×35 4.5 1.6 1.3 29.3 14301×50 4.5 1.7 1.3 30.7 16201×70 4.5 1.8 1.3 32.4 19001×95 4.5 1.8 1.4 34.4 22501×120 4.5 1.9 1.5 36.6 26251×150 4.5 2.0 1.5 38.1 2940
Copyright@ Caledonian Câbles Offshore & Marine
Moyenne Tension Câbles D'alimentation
34 ADDISON www.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des
carottes × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur1×185 4.5 2.0 1.5 40.6 35451×240 4.5 2.1 1.6 43.4 42201×300 4.5 2.2 1.7 46.3 50701×400 4.5 2.4 1.8 50.2 57601×500 4.5 2.5 1.8 53.6 68801×630 4.5 2.6 1.9 57.9 84603×25 4.5 2.6 1.9 55.3 47253×35 4.5 2.7 2.0 57.5 52153×50 4.5 2.8 2.0 60.6 59603×70 4.5 2.9 2.1 64.4 70353×95 4.5 3.1 2.2 68.7 83703×120 4.5 3.2 2.3 72.7 97453×150 4.5 3.4 2.4 76.8 111403×185 4.5 3.6 2.6 84.2 134903×240 4.5 3.8 2.7 90.6 158603×300 4.5 4.0 2.9 96.6 18320
Remarque : Pour un câble XLPE isolé, une mince épaisseur de l'isolation est appliquée.
Copyright@ Caledonian Câbles Offshore & Marine
Moyenne Tension Câbles D'alimentation
35ADDISONwww.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
P19 ou P19/P21 RFOU 12/20KV
Applications
Ces câbles sont ignifuges, faible dégagement de fumée, sans halogène et résistants boue, utilisé pour l'installation fixe pour moyenne tension.
Normes
IEC 60092-354 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Circulaire cuivre recuit étamé brin CEI 60228 classe 2. Écran du conducteur: Semi en matériau conducteur. Isolation: Sans halogène EPR. XLPE peut être proposé en option (pour le câble
TFOU). Écran d’isolation: Semi matériau conducteur et étamé tresse de fils de cuivre. Literie: Composé sans halogène. Armour: Fil de cuivre étamé tresse. Gaine extérieure: Halogène composé thermodurcissable libre, SHF2 (pour le TYPE
P19), ou un halogène boue sans composé thermodurcissable résistant, SHF MUD (pour le TYPE P19/P21), de couleur rouge.
Facultatif
P20 ou P20/P22 RFOU/TFOU 18/30(36) kV
Fil De Cuivre Ètamé
HFEPR/XLPE Isolation
Literie Sans HalogèneConducteur En Cuivre Multibrins
SHF2/SHF Gaine De BOUEÉcran D’isolationÉcran Du Conducteur
Copyright@ Caledonian Câbles Offshore & Marine
Moyenne Tension Câbles D'alimentation
36 ADDISON www.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Caractéristiques électriques
Cross Section Nominale Zone mm² 16 25 35 50 70 95Chef d’orchestre Diamètre nominal mm 5.2 6.5 7.4 8.7 10.3 12.2Resistant@20℃ DC maximale Ω/km 1.16 0.734 0.529 0.391 0.27 0.195Courant Nominal Continu@45℃ 1 Core A 96 127 157 196 242 293Courant Nominal Continu@45℃ 3 Core A 67 89 110 137 169 2051s courant de court circuit A 2290 3580 5010 7150 10020 13590Tension de fonctionnement KV 12/20 12/20 12/20 12/20 12/20 12/20
Cross Section Nominale Zone mm² 120 150 185 240 300Chef d’orchestre Diamètre nominal mm 13.8 15.1 17.0 19.6 21.9Resistant@20℃ DC maximale Ω/km 0.154 0.126 0.1 0.0762 0.0607Courant Nominal Continu@45℃ 1 Core A 339 389 444 522 601Courant Nominal Continu@45℃ 3 Core A 237 272 311 365 4211s courant de court circuit A 17170 21460 26470 34340 42930Tension de fonctionnement KV 12/20 12/20 12/20 12/20 12/20
Facteurs de Correction de la température ambiante
Facteurs de Correction de la température ambiante 35 40 45 50 55 60 65 70 75 80
Facteur Note 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47
Propriétés mécaniques et thermiques
Rayon de cintrage: 15×OD (lors de l’installation); 9×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des
carottes × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur1×16 5.5 1.4 1.2 28 12001×25 5.5 1.5 1.2 31.6 15301×35 5.5 1.8 1.3 32.3 1595
Copyright@ Caledonian Câbles Offshore & Marine
Moyenne Tension Câbles D'alimentation
37ADDISONwww.addison-cables.com
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des
carottes × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur1×50 5.5 1.8 1.4 33.8 17951×70 5.5 1.9 1.4 34.6 20701×95 5.5 2.0 1.5 37.0 24701×120 5.5 2.0 1.5 38.8 28101×150 5.5 2.1 1.6 40.7 32451×185 5.5 2.2 1.6 42.9 37651×240 5.5 2.3 1.7 45.8 45101×300 5.5 2.4 1.8 48.5 53153×16 5.5 1.8 2.0 55.5 49503×25 5.5 1.9 2.0 62.2 57053×35 5.5 2.9 2.1 62.6 59903×50 5.5 3.0 2.2 65.4 67403×70 5.5 3.1 2.3 69.1 77903×95 5.5 3.3 2.4 73.0 91503×120 5.5 3.4 2.5 77.4 105803×150 5.5 3.6 2.6 81.9 121453×185 5.5 3.8 2.7 89.5 122653×240 5.5 4.0 2.9 96.1 147253×300 5.5 4.2 3.0 101.9 17190
Remarque : Pour un câble XLPE isolé, une mince épaisseur de l'isolation est appliquée.
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Moyenne Tension Câbles
38 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
P6 ou P6/P13 BFOU 3.6/6kV
Applications
Ces câbles sont résistants au feu, retardateur de flamme, faible dégagement de fumée, sans halogène et résistants boue, utilisé pour l'installation fixe pour moyenne tension.
Normes
IEC 60092-354 IEC 60092-351 IEC 60092-359 IEC 60331-21 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Circulaire cuivre recuit étamé brin CEI 60228 classe 2. Écran du conducteur: Semi en matériau conducteur. Isolation: Ruban Mica + Halogène EPR libre. Écran d’isolation: Semi matériau conducteur et étamé tresse de fils de cuivre. Literie: Composé sans halogène. Armour: Fil de cuivre étamé tresse. Gaine extérieure: Halogène composé thermodurcissable libre, SHF2 (pour le TYPE
P6), ou un halogène boue sans composé thermodurcissable résistant, SHF MUD (pour le TYPE P6/P13), de couleur rouge.
Fil De Cuivre Ètamé
Ruban Mica + HFEPR Isolation
Literie Sans HalogèneConducteur En Cuivre Multibrins
SHF MUD Gaine De BOUEÉcran D’isolationÉcran Du Conducteur
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Moyenne Tension Câbles
39ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Caractéristiques électriques
Cross Section Nominale Zone mm² 25 35 50 70 95 120 150Chef d’orchestre Diamètre nominal mm 6.5 7.4 8.7 10.3 12.2 13.8 15.1Resistant@20℃ DC maximale Ω/km 0.734 0.529 0.391 0.27 0.195 0.154 0.126Courant Nominal Continu@45℃ 1 Core A 127 157 196 242 293 339 389Courant Nominal Continu@45℃ 3 Core A 89 110 137 169 205 237 2721s courant de court circuit A 3580 5010 7150 10020 13590 17170 21460Tension de fonctionnement KV 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6 3.6/6
Cross Section Nominale Zone mm² 185 240 300 400 500 630Chef d’orchestre Diamètre nominal mm 17.0 19.6 21.9 24.5 27.5 32.3Resistant@20℃ DC maximale Ω/km 0.1 0.0762 0.0607 0.0475 0.0369 0.0286Courant Nominal Continu@45℃ 1 Core A 444 522 601 690 780 890Courant Nominal Continu@45℃ 3 Core A 311 365 421 483 546 6231s courant de court circuit A 26470 34340 42930 57230 71540 90140Tension de fonctionnement KV 3.6/6 3.6/6 3.6/6 8.7/15 8.7/15 8.7/15
Facteurs de Correction de la température ambiante
Facteurs de Correction de la température ambiante 35 40 45 50 55 60 65 70 75 80
Facteur Note 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47
Propriétés mécaniques et thermiques
Rayon de cintrage: 15×OD (lors de l’installation); 9×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des
carottes × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
1×16 2.5 1.5 1.2 24.8 9501×25 2.5 1.6 1.2 26.3 1110
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Moyenne Tension Câbles
40 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des
carottes × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
1×35 2.5 1.6 1.2 27.6 12601×50 2.5 1.7 1.3 29.1 14601×70 2.5 1.7 1.3 30.9 17401×95 2.5 1.8 1.4 33.2 21101×120 2.5 1.9 1.4 34.9 24301×150 2.5 1.9 1.4 36.9 28901×185 2.5 2.0 1.5 39.1 33701×240 2.6 2.1 1.6 42.2 41001×300 2.8 2.2 1.6 44.7 48101×400 3.0 2.3 1.7 48.1 58101×500 3.2 2.5 1.8 52.1 70301×630 3.2 2.6 1.9 56.5 86303×16 2.5 2.3 1.7 48.2 35503×25 2.5 2.5 1.8 51.5 41803×35 2.5 2.6 1.9 54.7 48203×50 2.5 2.7 1.9 57.4 54903×70 2.5 2.8 2.0 61.6 65903×95 2.5 3.0 2.1 66.2 79203×120 2.5 3.1 2.2 70.1 91503×150 2.5 3.3 2.3 74.0 104603×185 2.5 3.4 2.4 78.6 120103×240 2.6 3.7 2.6 86.3 146903×300 2.8 3.9 2.8 92.3 17130
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Moyenne Tension Câbles
41ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
P7 ou P7/P14 BFOU 6/10kV
Applications
Ces câbles sont résistants au feu, retardateur de flamme, faible dégagement de fumée, sans halogène et résistants boue, utilisé pour l'installation fixe pour moyenne tension.
Normes
IEC 60092-354 IEC 60092-351 IEC 60092-359 IEC 60331-21 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Circulaire cuivre recuit étamé brin CEI 60228 classe 2. Écran du conducteur: Semi en matériau conducteur. Isolation: Ruban Mica + Halogène EPR libre. Écran d’isolation: Semi matériau conducteur et étamé tresse de fils de cuivre. Literie: Composé sans halogène. Armour: Fil de cuivre étamé tresse. Gaine extérieure: Halogène composé thermodurcissable libre, SHF2 (pour le TYPE
P7), ou un halogène boue sans composé thermodurcissable résistant, SHF MUD (pour le TYPE P7/P14), de couleur rouge.
Fil De Cuivre Ètamé
Ruban Mica + HFEPR Isolation
Literie Sans HalogèneConducteur En Cuivre Multibrins
SHF MUD Gaine De BOUEÉcran D’isolationÉcran Du Conducteur
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Moyenne Tension Câbles
42 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Caractéristiques électriques
Cross Section Nominale Zone mm² 25 35 50 70 95 120 150Chef d’orchestre Diamètre nominal mm 6.5 7.4 8.7 10.3 12.2 13.8 15.1Resistant@20℃ DC maximale Ω/km 0.734 0.529 0.391 0.27 0.195 0.154 0.126Courant Nominal Continu@45℃ 1 Core A 127 157 196 242 293 339 389Courant Nominal Continu@45℃ 3 Core A 89 110 137 169 205 237 2721s courant de court circuit A 3580 5010 7150 10020 13590 17170 21460Tension de fonctionnement KV 6/10 6/10 6/10 6/10 6/10 6/10 6/10
Cross Section Nominale Zone mm² 185 240 300 400 500 630Chef d’orchestre Diamètre nominal mm 17.0 19.6 21.9 24.5 27.5 32.3Resistant@20℃ DC maximale Ω/km 0.1 0.0762 0.0607 0.0475 0.0369 0.0286Courant Nominal Continu@45℃ 1 Core A 444 522 601 690 780 890Courant Nominal Continu@45℃ 3 Core A 311 365 421 483 546 6231s courant de court circuit A 26470 34340 42930 57230 71540 90140Tension de fonctionnement KV 6/10 6/10 6/10 8.7/15 8.7/15 8.7/15
Facteurs de Correction de la température ambiante
Facteurs de Correction de la température ambiante 35 40 45 50 55 60 65 70 75 80
Facteur Note 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47
Propriétés mécaniques et thermiques
Rayon de cintrage: 15×OD (lors de l’installation); 9×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des
carottes × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
1×16 3.4 1.5 1.2 25.6 9901×25 3.4 1.6 1.2 27.1 1150
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Moyenne Tension Câbles
43ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des
carottes × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
1×35 3.4 1.7 1.2 28.5 13201×50 3.4 1.7 1.3 29.9 15001×70 3.4 1.8 1.3 31.9 18101×95 3.4 1.8 1.4 34.0 21601×120 3.4 1.9 1.4 36.1 26101×150 3.4 2.0 1.5 38.1 29901×185 3.4 2.0 1.5 39.9 34401×240 3.4 2.2 1.6 43.1 41801×300 3.4 2.3 1.7 45.9 49301×400 3.4 2.4 1.7 49.0 59001×500 3.4 2.5 1.8 52.5 70701×630 3.4 2.7 1.9 57.0 86903×16 3.4 2.4 1.8 50.2 37803×25 3.4 2.5 1.8 53.2 43803×35 3.4 2.6 1.9 56.4 50403×50 3.4 2.7 2.0 59.3 57403×70 3.4 2.9 2.1 63.7 69003×95 3.4 3.1 2.2 68.4 82703×120 3.4 3.2 2.3 72.1 94703×150 3.4 3.3 2.4 76.0 108003×185 3.4 3.5 2.5 80.8 123703×240 3.4 3.7 2.7 88.2 150403×300 3.4 3.9 2.9 94.0 17450
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Moyenne Tension Câbles
44 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
P30 RFOU-HCF / TFOU-HCF 6/10(12) kV
Applications
Ces câbles sont résistants au feu, retardateur de flamme, faible dégagement de fumée et sans halogène, utilisé pour les systèmes de contrôle d'urgence, alimentation et d'éclairage qui doivent être opérationnels pendant un feu d'hydrocarbures 1100 ℃.
Normes
IEC 60092-354 IEC 60092-351 IEC 60092-359 IEC 60331-21 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Circulaire cuivre recuit étamé brin CEI 60228 classe 2. Écran du conducteur: Semi en matériau conducteur. Isolation: Sans halogène EPR. XLPE peut être proposé en option. Écran d’isolation: Semi matériau conducteur et étamé tresse de fils de cuivre. Literie: Composé sans halogène. Armour: Fil de cuivre étamé tresse. Gaine extérieure1: Halogène composé thermodurcissable libre, SHF2, de couleur
rouge. Protection contre l’incendie-HC :Protection contre l’incendie thermoplastique
composé des profilés extrudés.. Enregistrement :Ruban de fibre de verre rodé.
Fil De Cuivre Ètamé
HFEPR/XLPE Isolation
Literie Sans HalogèneConducteur En Cuivre Multibrins
SHF2 GaineÉcran D’isolationÉcran Du Conducteur
SHF1 Gaine
HC-Protection Contre L'incendie+Ruban Adhésif
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Moyenne Tension Câbles
45ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Gaine extérieure2: Ignifuge sans halogène thermoplastique composé, SHF1, de couleur rouge..
Facultatif
P31 RFOU-HCF / TFOU-HCF 8.7/15kVP32 RFOU-HCF / TFOU-HCF 12/20(24) kVP33 RFOU-HCF / TFOU-HCF 18/30(36) kV
Caractéristiques électriques
Cross Section Nominale Zone mm² 70 95 120 150 185 240 300Chef d’orchestre Diamètre nominal mm 10.3 12.2 13.8 15.1 17.0 19.6 21.9Resistant@20℃ DC maximale Ω/km 0.27 0.195 0.154 0.126 0.1 0.0762 0.0607Courant Nominal Continu@45℃ 1 Core A 242 293 339 389 444 522 601Courant Nominal Continu@45℃ 3 Core A 169 205 237 272 311 365 4211s courant de court circuit A 10020 13590 17170 21460 26470 34340 42930Tension de fonctionnement KV 6/10 6/10 6/10 6/10 6/10 6/10 6/10
Facteurs de Correction de la température ambianteFacteurs de Correction de la température ambiante 35 40 45 50 55 60 65 70 75 80
Facteur Note 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47
Propriétés mécaniques et thermiques
Rayon de cintrage: 20×OD (lors de l’installation); 12×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des
carottes × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Diamètre nominal cours Literie
mm
Diamètre nominal sur gaine1
mm
Diamètre nominal globalmm
Poids nominalkg/km
1×70 3.4 23.5 30.0 62.0 52201×95 3.4 25.5 32.0 64.5 59001×120 3.4 27.5 34.0 66.5 63401×150 3.4 28.5 35.0 67.5 6670
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Moyenne Tension Câbles
46 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des
carottes × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Diamètre nominal cours Literie
mm
Diamètre nominal sur gaine1
mm
Diamètre nominal globalmm
Poids nominalkg/km
1×185 3.4 30.5 36.5 69.0 73201×240 3.4 33.0 39.0 72.0 82501×300 3.4 35.0 41.5 74.5 92803×50 3.4 47.0 55.0 89.0 109703×95 3.4 54.0 62.5 97.0 14230
3×150 3.4 60.0 70.5 106.0 17400
Remarque : Pour un câble XLPE isolé, une mince épaisseur de l'isolation est appliquée.
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Instrumentation
47ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
S1 ou S1/S5 RFOU(i) 250V
Applications
Ces câbles sont ignifuge, sans fumée, halogènes libres et résistant à la boue, util isé pour l ' instrumentation, de communication, de contrôle et d'alarme.
Normes
IEC 60092-376 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Fil recuit circulaire conserves brin de cuivre CEI 60228 classe 2. Isolation: Halogène composé EPR libre. Jumelage : Code couleurs carottes torsadés ensemble. Blindage individuel : Chaque paires/triples sont examinées par ruban de polyester
soutenue en cuivre en contact avec un fil de drain en cuivre étamé toronné et enveloppé avec du ruban adhésif polyester. Couples/triples sont numérotés avec un ruban numéroté ou par numéros imprimés directement sur les conducteurs isolés.
Literie: Composé sans halogène. Armour: Fil de cuivre étamé tresse. Gaine extérieure: Halogène composé thermodurcissable libre, SHF2 (pour le TYPE
S1). Gratuit composé thermodurcissable résistant à la boue halogène, boue de la SHF (pour TYPE S1/S5), de couleur gris (bleu pour sécurité intrinsèque).
Fil De Cuivre Ètamé
HFEPR Isolation
Literie Sans Halogène
Conducteur En Cuivre Multibrins
SHF2/SHF Gaine De BOUE
Ruban De Cuivre/Polyester+Fil De Drain
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Instrumentation
48 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Caractéristiques électriques
Cross Section Nominale Zone mm² 0.75 1.0 1.5 2.5Chef d’orchestre Diamètre nominal mm 1.1 1.3 1.6 2.0Maximum résistant@20℃ Ω/km 26.3 19.3 12.9 8.02Capacité mutuelle nF/km 90 100 110 120Nominal Inductance@1KHz MH/km 0.686 0.649 0.637 0.598Maximum L/R@1KHz μH/Ω 20 25 35 50Tension de fonctionnement V 250 250 250 250
Propriétés mécaniques et thermiques
Rayon de cintrage: 8×OD (lors de l’installation); 6×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des éléments × non. des
carottes en élément × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
1×2×0.75 0.6 1.1 1.1 10.9 2102×2×0.75 0.6 1.1 1.3 13.2 3254×2×0.75 0.6 1.1 1.3 16.2 4807×2×0.75 0.6 1.1 1.4 19.0 6708×2×0.75 0.6 1.1 1.4 20.4 7559×2×0.75 0.6 1.1 1.5 22.6 83510×2×0.75 0.6 1.1 1.5 23.5 87512×2×0.75 0.6 1.1 1.5 24.1 101014×2×0.75 0.6 1.1 1.6 25.3 104015×2×0.75 0.6 1.1 1.6 26.9 112016×2×0.75 0.6 1.1 1.6 27.3 116518×2×0.75 0.6 1.1 1.7 28.7 127019×2×0.75 0.6 1.1 1.7 29.0 136020×2×0.75 0.6 1.1 1.7 30.1 142021×2×0.75 0.6 1.1 1.8 31.0 149023×2×0.75 0.6 1.1 1.8 31.5 159524×2×0.75 0.6 1.2 1.8 33.4 172027×2×0.75 0.6 1.2 1.9 34.0 177030×2×0.75 0.6 1.2 1.9 35.1 1910
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Instrumentation
49ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des éléments × non. des
carottes en élément × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
32×2×0.75 0.6 1.2 2.0 36.1 206033×2×0.75 0.6 1.2 2.0 36.9 216037×2×0.75 0.6 1.2 2.0 38.0 23301×3×0.75 0.6 1.1 1.2 11.3 2252×3×0.75 0.6 1.1 1.3 16.4 4903×3×0.75 0.6 1.1 1.4 17.2 5204×3×0.75 0.6 1.1 1.4 18.5 6105×3×0.75 0.6 1.1 1.5 19.8 7206×3×0.75 0.6 1.1 1.5 21.7 8357×3×0.75 0.6 1.1 1.5 21.7 8708×3×0.75 0.6 1.1 1.6 23.5 9509×3×0.75 0.6 1.1 1.6 24.6 106510×3×0.75 0.6 1.1 1.7 26.4 109512×3×0.75 0.6 1.1 1.7 27.3 127514×3×0.75 0.6 1.1 1.8 28.5 132015×3×0.75 0.6 1.1 1.8 29.3 139516×3×0.75 0.6 1.1 1.8 30.1 146518×3×0.75 0.6 1.1 1.9 31.6 160019×3×0.75 0.6 1.1 1.9 31.9 165520×3×0.75 0.6 1.2 2.0 33.2 182021×3×0.75 0.6 1.2 2.0 33.8 189023×3×0.75 0.6 1.2 2.0 35.1 205024×3×0.75 0.6 1.2 2.0 36.0 222027×3×0.75 0.6 1.2 2.1 37.9 233530×3×0.75 0.6 1.2 2.2 39.7 255532×3×0.75 0.6 1.2 2.2 40.7 2690
1×2×1.0 0.6 1.1 1.2 11.4 2302×2×1.0 0.6 1.1 1.3 14.5 3703×2×1.0 0.6 1.1 1.3 16.6 5154×2×1.0 0.6 1.1 1.4 17.4 5955×2×1.0 0.6 1.1 1.4 19.1 6856×2×1.0 0.6 1.1 1.5 20.7 7907×2×1.0 0.6 1.1 1.5 20.7 8208×2×1.0 0.6 1.1 1.6 21.6 8759×2×1.0 0.6 1.1 1.6 23.8 99510×2×1.0 0.6 1.1 1.6 24.8 101012×2×1.0 0.6 1.1 1.7 25.6 119514×2×1.0 0.6 1.1 1.7 26.7 121015×2×1.0 0.6 1.1 1.8 28.5 132016×2×1.0 0.6 1.1 1.8 29.0 137518×2×1.0 0.6 1.1 1.9 30.5 150019×2×1.0 0.6 1.1 1.9 30.8 1555
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Instrumentation
50 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des éléments × non. des
carottes en élément × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
20×2×1.0 0.6 1.1 1.9 31.9 168021×2×1.0 0.6 1.2 2.0 33.3 179023×2×1.0 0.6 1.2 2.0 33.7 192024×2×1.0 0.6 1.2 2.0 35.2 201527×2×1.0 0.6 1.2 2.1 36.5 218530×2×1.0 0.6 1.2 2.1 37.7 236533×2×1.0 0.6 1.2 2.2 39.2 257037×2×1.0 0.6 1.2 2.2 40.4 27751×3×1.0 0.6 1.1 1.2 11.8 2502×3×1.0 0.6 1.1 1.4 17.3 5553×3×1.0 0.6 1.1 1.4 17.9 5904×3×1.0 0.6 1.1 1.4 19.4 7005×3×1.0 0.6 1.1 1.5 20.7 8256×3×1.0 0.6 1.1 1.6 23.0 9757×3×1.0 0.6 1.1 1.6 23.0 9908×3×1.0 0.6 1.1 1.6 24.4 10959×3×1.0 0.6 1.1 1.7 26.4 124510×3×1.0 0.6 1.1 1.8 28.0 126512×3×1.0 0.6 1.1 1.8 28.9 150014×3×1.0 0.6 1.1 1.8 30.0 154515×3×1.0 0.6 1.1 1.9 31.1 165516×3×1.0 0.6 1.1 1.9 31.8 187018×3×1.0 0.6 1.2 2.0 33.9 193519×3×1.0 0.6 1.2 2.0 34.2 204020×3×1.0 0.6 1.2 2.0 35.1 215021×3×1.0 0.6 1.2 2.1 35.9 224523×3×1.0 0.6 1.2 2.1 37.6 252524×3×1.0 0.6 1.2 2.1 38.7 268527×3×1.0 0.6 1.2 2.2 40.3 278530×3×1.0 0.6 1.2 2.3 42.1 305032×3×1.0 0.6 1.2 2.3 43.2 32151×2×1.5 0.7 1.1 1.2 12.4 2702×2×1.5 0.7 1.1 1.4 15.8 4953×2×1.5 0.7 1.1 1.4 17.9 6404×2×1.5 0.7 1.1 1.5 19.5 7155×2×1.5 0.7 1.1 1.5 21.5 8506×2×1.5 0.7 1.1 1.6 23.3 9907×2×1.5 0.7 1.1 1.6 23.3 10308×2×1.5 0.7 1.1 1.7 24.8 11309×2×1.5 0.7 1.1 1.7 26.9 123010×2×1.5 0.7 1.1 1.8 28.2 127012×2×1.5 0.7 1.1 1.8 29.3 1375
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Instrumentation
51ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des éléments × non. des
carottes en élément × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
14×2×1.5 0.7 1.1 1.8 30.2 152015×2×1.5 0.7 1.2 1.9 32.7 168516×2×1.5 0.7 1.2 2.0 33.4 177518×2×1.5 0.7 1.2 2.0 35.0 192019×2×1.5 0.7 1.2 2.0 35.3 199020×2×1.5 0.7 1.2 2.1 37.2 225521×2×1.5 0.7 1.2 2.1 38.2 234523×2×1.5 0.7 1.2 2.2 39.0 254024×2×1.5 0.7 1.2 2.2 40.7 261027×2×1.5 0.7 1.2 2.3 41.7 277530×2×1.5 0.7 1.2 2.3 43.1 300533×2×1.5 0.7 1.4 2.4 45.1 348037×2×1.5 0.7 1.4 2.5 46.7 36001×3×1.5 0.7 1.1 1.2 13.0 3002×3×1.5 0.7 1.1 1.4 17.5 5103×3×1.5 0.7 1.1 1.5 20.1 7404×3×1.5 0.7 1.1 1.5 21.8 8705×3×1.5 0.7 1.1 1.6 23.3 10456×3×1.5 0.7 1.1 1.7 25.9 12307×3×1.5 0.7 1.1 1.7 26.0 12658×3×1.5 0.7 1.1 1.8 27.8 14059×3×1.5 0.7 1.1 1.8 29.5 158510×3×1.5 0.7 1.1 1.9 31.8 168012×3×1.5 0.7 1.2 2.0 33.1 195014×3×1.5 0.7 1.2 2.0 34.6 202015×3×1.5 0.7 1.2 2.0 35.6 214516×3×1.5 0.7 1.2 2.1 36.6 245018×3×1.5 0.7 1.2 2.2 39.2 258019×3×1.5 0.7 1.2 2.2 39.5 267520×3×1.5 0.7 1.2 2.2 40.5 287521×3×1.5 0.7 1.2 2.3 41.5 300023×3×1.5 0.7 1.2 2.3 43.0 326024×3×1.5 0.7 1.4 2.4 44.9 331027×3×1.5 0.7 1.4 2.4 46.4 363530×3×1.5 0.7 1.4 2.5 48.5 398032×3×1.5 0.7 1.4 2.6 50.0 42251×2×2.5 0.7 1.1 1.2 13.3 3202×2×2.5 0.7 1.1 1.4 17.5 5303×2×2.5 0.7 1.1 1.5 20.2 7804×2×2.5 0.7 1.1 1.5 21.5 9005×2×2.5 0.7 1.1 1.6 23.4 10606×2×2.5 0.7 1.1 1.7 25.4 1235
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Instrumentation
52 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des éléments × non. des
carottes en élément × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
7×2×2.5 0.7 1.1 1.7 25.4 12908×2×2.5 0.7 1.1 1.7 27.5 14009×2×2.5 0.7 1.1 1.8 29.4 149510×2×2.5 0.7 1.1 1.9 30.9 159512×2×2.5 0.7 1.1 1.9 31.6 175514×2×2.5 0.7 1.2 2.0 33.6 199015×2×2.5 0.7 1.2 2.1 36.0 216516×2×2.5 0.7 1.2 2.1 36.9 235018×2×2.5 0.7 1.2 2.2 38.9 256519×2×2.5 0.7 1.2 2.2 39.3 266520×2×2.5 0.7 1.2 2.2 40.8 288021×2×2.5 0.7 1.2 2.3 42.1 302023×2×2.5 0.7 1.2 2.3 42.7 325524×2×2.5 0.7 1.4 2.4 45.2 333027×2×2.5 0.7 1.4 2.4 46.1 361530×2×2.5 0.7 1.4 2.5 47.8 395033×2×2.5 0.7 1.4 2.6 49.7 430037×2×2.5 0.7 1.4 2.6 51.2 46701×3×2.5 0.7 1.1 1.3 13.9 3552×3×2.5 0.7 1.1 1.5 20.9 8403×3×2.5 0.7 1.1 1.5 21.6 9454×3×2.5 0.7 1.1 1.6 23.3 11155×3×2.5 0.7 1.1 1.7 25.4 13156×3×2.5 0.7 1.1 1.8 28.3 15557×3×2.5 0.7 1.1 1.8 28.3 16408×3×2.5 0.7 1.1 1.8 30.2 17809×3×2.5 0.7 1.2 1.9 32.6 205510×3×2.5 0.7 1.2 2.0 35.1 208012×3×2.5 0.7 1.2 2.1 36.8 243514×3×2.5 0.7 1.2 2.1 38.3 270015×3×2.5 0.7 1.2 2.2 39.7 289516×3×2.5 0.7 1.2 2.2 40.8 305018×3×2.5 0.7 1.2 2.3 42.9 333519×3×2.5 0.7 1.2 2.3 43.3 347020×3×2.5 0.7 1.4 2.4 44.9 378521×3×2.5 0.7 1.4 2.4 45.8 393523×3×2.5 0.7 1.4 2.5 47.7 415024×3×2.5 0.7 1.4 2.5 48.6 430027×3×2.5 0.7 1.4 2.6 51.1 476530×3×2.5 0.7 1.4 2.7 53.5 523532×3×2.5 0.7 1.6 2.8 55.5 5620
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Instrumentation
53ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
S2 ou S2/S6 RFOU(c) 250V
Applications
Ces câbles sont ignifuge, sans fumée, halogènes libres et résistant à la boue, util isé pour l ' instrumentation, de communication, de contrôle et d'alarme.
Normes
IEC 60092-376 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Fil recuit circulaire conserves brin de cuivre CEI 60228 classe 2. Isolation: Halogène composé EPR libre. Jumelage : Code couleurs carottes torsadés ensemble. Collectives Blindage: Paires / triples sont layed et collectivement projetés par le
cuivre soutenu polyester bande en contact avec un fil de continuité étamé en cuivre brin. Paires / triples sont numérotés avec du ruban numéroté ou par des numéros imprimés directement sur les conducteurs isolés.
Literie: Composé sans halogène. Armour: Fil de cuivre étamé tresse. Gaine extérieure: Sans halogène composés thermodurcissables, SHF2 (de TYPE
S2). Gratuit composé thermodurcissable résistant à la boue halogène, boue de la SHF (de TYPE S2/S6), de couleur gris (bleu pour sécurité intrinsèque).
Fil De Cuivre Ètamé
HFEPR Isolation
Literie Sans Halogène
Conducteur En Cuivre Multibrins
SHF2/SHF Gaine De BOUE
Ruban De Cuivre/Polyester+Fil De Drain
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Instrumentation
54 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Caractéristiques électriques
Cross Section Nominale Zone mm² 0.75 1.0 1.5 2.5Chef d’orchestre Diamètre nominal mm 1.1 1.3 1.6 2.0Maximum résistant@20℃ Ω/km 26.3 19.3 12.9 8.02Capacité mutuelle nF/km 80 90 100 110Nominal Inductance@1KHz MH/km 0.682 0.645 0.632 0.593Maximum L/R@1KHz μH/Ω 20 25 35 50Tension de fonctionnement V 250 250 250 250
Propriétés mécaniques et thermiques
Rayon de cintrage: 8×OD (lors de l’installation); 6×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des éléments × non. des
carottes en élément × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
1×2×0.75 0.6 1.1 1.1 11.1 2002×2×0.75 0.6 1.1 1.3 15.0 2953×2×0.75 0.6 1.1 1.3 15.6 3554×2×0.75 0.6 1.1 1.3 16.4 3905×2×0.75 0.6 1.1 1.4 17.8 5406×2×0.75 0.6 1.1 1.4 19.1 6107×2×0.75 0.6 1.1 1.4 19.1 6258×2×0.75 0.6 1.1 1.5 20.7 6809×2×0.75 0.6 1.1 1.5 21.8 74510×2×0.75 0.6 1.1 1.6 22.9 76012×2×0.75 0.6 1.1 1.6 23.4 81014×2×0.75 0.6 1.1 1.6 24.5 87515×2×0.75 0.6 1.1 1.7 26.1 96016×2×0.75 0.6 1.1 1.7 26.5 101018×2×0.75 0.6 1.1 1.8 27.9 108019×2×0.75 0.6 1.1 1.8 28.2 111520×2×0.75 0.6 1.1 1.8 29.2 121021×2×0.75 0.6 1.1 1.8 30.0 125523×2×0.75 0.6 1.1 1.9 30.6 135524×2×0.75 0.6 1.1 1.9 31.9 1370
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Instrumentation
55ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des éléments × non. des
carottes en élément × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
27×2×0.75 0.6 1.2 1.9 32.9 148030×2×0.75 0.6 1.2 2.0 34.1 160533×2×0.75 0.6 1.2 2.0 35.3 172537×2×0.75 0.6 1.2 2.1 36.9 19501×3×0.75 0.6 1.1 1.2 11.7 2302×3×0.75 0.6 1.1 1.3 14.5 3603×3×0.75 0.6 1.1 1.3 16.2 4154×3×0.75 0.6 1.1 1.4 17.6 5405×3×0.75 0.6 1.1 1.4 19.1 6456×3×0.75 0.6 1.1 1.5 21.1 7557×3×0.75 0.6 1.1 1.5 21.1 7808×3×0.75 0.6 1.1 1.6 22.6 8459×3×0.75 0.6 1.1 1.6 23.9 94510×3×0.75 0.6 1.1 1.7 25.7 96012×3×0.75 0.6 1.1 1.7 26.4 108014×3×0.75 0.6 1.1 1.7 27.5 115015×3×0.75 0.6 1.1 1.8 28.5 123016×3×0.75 0.6 1.1 1.8 29.2 131018×3×0.75 0.6 1.1 1.9 30.7 140519×3×0.75 0.6 1.1 1.9 31.0 147520×3×0.75 0.6 1.1 1.9 31.8 156021×3×0.75 0.6 1.2 1.9 32.7 164023×3×0.75 0.6 1.2 2.0 34.1 179524×3×0.75 0.6 1.2 2.0 34.6 183027×3×0.75 0.6 1.2 2.1 36.8 204030×3×0.75 0.6 1.2 2.1 38.3. 221032×3×0.75 0.6 1.2 2.2 39.5 2345
1×2×1.0 0.6 1.1 1.2 11.7 2252×2×1.0 0.6 1.1 1.3 13.4 3353×2×1.0 0.6 1.1 1.3 16.3 4704×2×1.0 0.6 1.1 1.4 17.4 5355×2×1.0 0.6 1.1 1.4 18.7 6106×2×1.0 0.6 1.1 1.5 20.2 7007×2×1.0 0.6 1.1 1.5 20.2 7208×2×1.0 0.6 1.1 1.5 21.8 7759×2×1.0 0.6 1.1 1.6 23.2 85010×2×1.0 0.6 1.1 1.6 24.1 88012×2×1.0 0.6 1.1 1.6 24.7 98014×2×1.0 0.6 1.1 1.7 26.0 103015×2×1.0 0.6 1.1 1.8 27.8 112516×2×1.0 0.6 1.1 1.8 28.2 117518×2×1.0 0.6 1.1 1.8 29.5 125519×2×1.0 0.6 1.1 1.8 29.8 1295
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Instrumentation
56 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des éléments × non. des
carottes en élément × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
20×2×1.0 0.6 1.1 1.9 31.1 142021×2×1.0 0.6 1.1 1.9 31.9 147523×2×1.0 0.6 1.2 1.9 32.7 161024×2×1.0 0.6 1.2 2.0 34.3 162027×2×1.0 0.6 1.2 2.0 35.0 174530×2×1.0 0.6 1.2 2.1 36.7 198033×2×1.0 0.6 1.2 2.1 38.0 213037×2×1.0 0.6 1.2 2.2 39.3 23051×3×1.0 0.6 1.1 1.2 12.0 2502×3×1.0 0.6 1.1 1.4 17.0 5203×3×1.0 0.6 1.1 1.4 17.4 5404×3×1.0 0.6 1.1 1.4 18.7 6255×3×1.0 0.6 1.1 1.5 20.2 7456×3×1.0 0.6 1.1 1.6 22.4 8757×3×1.0 0.6 1.1 1.6 22.4 9058×3×1.0 0.6 1.1 1.6 23.8 9809×3×1.0 0.6 1.1 1.7 25.4 108010×3×1.0 0.6 1.1 1.7 27.1 115012×3×1.0 0.6 1.1 1.8 28.1 126514×3×1.0 0.6 1.1 1.8 29.2 135515×3×1.0 0.6 1.1 1.8 30.1 144016×3×1.0 0.6 1.1 1.9 31.1 157018×3×1.0 0.6 1.2 1.9 32.8 167519×3×1.0 0.6 1.2 2.0 33.3 175020×3×1.0 0.6 1.2 2.0 34.1 188021×3×1.0 0.6 1.2 2.0 34.8 195023×3×1.0 0.6 1.2 2.1 36.6 221524×3×1.0 0.6 1.2 2.1 37.3 220027×3×1.0 0.6 1.2 2.2 39.2 242530×3×1.0 0.6 1.2 2.2 40.8 263032×3×1.0 0.6 1.2 2.3 42.1 27901×2×1.5 0.7 1.1 1.2 12.7 2602×2×1.5 0.7 1.1 1.4 15.4 4203×2×1.5 0.7 1.1 1.4 17.6 5854×2×1.5 0.7 1.1 1.4 18.8 6355×2×1.5 0.7 1.1 1.5 21.1 7706×2×1.5 0.7 1.1 1.6 22.8 8907×2×1.5 0.7 1.1 1.6 22.8 9258×2×1.5 0.7 1.1 1.6 23.7 9759×2×1.5 0.7 1.1 1.7 26.3 106010×2×1.5 0.7 1.1 1.7 27.4 113012×2×1.5 0.7 1.1 1.8 28.3 127014×2×1.5 0.7 1.1 1.8 29.5 1325
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Instrumentation
57ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des éléments × non. des
carottes en élément × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
15×2×1.5 0.7 1.1 1.9 31.6 144516×2×1.5 0.7 1.1 1.9 32.1 157518×2×1.5 0.7 1.2 2.0 34.2 167019×2×1.5 0.7 1.2 2.0 34.5 176520×2×1.5 0.7 1.2 2.1 36.0 189521×2×1.5 0.7 1.2 2.1 37.3 205023×2×1.5 0.7 1.2 2.1 37.9 218524×2×1.5 0.7 1.2 2.2 39.8 220027×2×1.5 0.7 1.2 2.2 40.6 239030×2×1.5 0.7 1.2 2.3 42.1 260033×2×1.5 0.7 1.2 2.3 43.6 280537×2×1.5 0.7 1.4 2.4 45.4 30801×3×1.5 0.7 1.1 1.2 13.2 2952×3×1.5 0.7 1.1 1.4 17.0 4903×3×1.5 0.7 1.1 1.5 19.5 6854×3×1.5 0.7 1.1 1.5 20.9 7855×3×1.5 0.7 1.1 1.6 21.0 8206×3×1.5 0.7 1.1 1.7 22.8 9607×3×1.5 0.7 1.1 1.7 25.1 11358×3×1.5 0.7 1.1 1.7 27.0 12709×3×1.5 0.7 1.1 1.8 28.9 144510×3×1.5 0.7 1.1 1.9 31.1 145012×3×1.5 0.7 1.1 1.9 31.5 171014×3×1.5 0.7 1.2 2.0 33.8 181515×3×1.5 0.7 1.2 2.0 34.8 193016×3×1.5 0.7 1.2 2.1 36.0 211018×3×1.5 0.7 1.2 2.1 38.1 230519×3×1.5 0.7 1.2 2.2 38.6 237520×3×1.5 0.7 1.2 2.2 39.6 258021×3×1.5 0.7 1.2 2.2 40.4 268023×3×1.5 0.7 1.2 2.3 42.0 292524×3×1.5 0.7 1.2 2.3 42.7 314027×3×1.5 0.7 1.4 2.4 45.3 325030×3×1.5 0.7 1.4 2.5 47.4 355532×3×1.5 0.7 1.4 2.5 48.6 37451×2×2.5 0.7 1.1 1.2 13.5 3002×2×2.5 0.7 1.1 1.4 18.9 6503×2×2.5 0.7 1.1 1.5 19.9 7204×2×2.5 0.7 1.1 1.5 21.1 8205×2×2.5 0.7 1.1 1.6 23.0 9656×2×2.5 0.7 1.1 1.6 24.8 11057×2×2.5 0.7 1.1 1.6 24.8 11508×2×2.5 0.7 1.1 1.7 27.0 1255
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Instrumentation
58 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des éléments × non. des
carottes en élément × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
9×2×2.5 0.7 1.1 1.8 28.8 138510×2×2.5 0.7 1.1 1.8 30.0 143012×2×2.5 0.7 1.3 1.9 31.0 154514×2×2.5 0.7 1.2 1.9 32.7 173015×2×2.5 0.7 1.2 2.0 35.0 188516×2×2.5 0.7 1.2 2.0 35.6 197018×2×2.5 0.7 1.2 2.1 37.9 223519×2×2.5 0.7 1.2 2.1 38.3 231520×2×2.5 0.7 1.2 2.2 39.9 253021×2×2.5 0.7 1.2 2.2 41.0 263023×2×2.5 0.7 1.2 2.3 41.8 275024×2×2.5 0.7 1.2 2.3 43.7 285027×2×2.5 0.7 1.4 2.4 45.1 315030×2×2.5 0.7 1.4 2.5 46.8 343533×2×2.5 0.7 1.4 2.5 48.5 371537×2×2.5 0.7 1.4 2.6 50.2 40401×3×2.5 0.7 1.1 1.3 14.3 3602×3×2.5 0.7 1.1 1.5 20.5 7853×3×2.5 0.7 1.1 1.5 21.2 8754×3×2.5 0.7 1.1 1.6 22.9 10355×3×2.5 0.7 1.1 1.6 24.8 12056×3×2.5 0.7 1.1 1.8 27.8 14307×3×2.5 0.7 1.1 1.8 27.8 15058×3×2.5 0.7 1.1 1.8 29.6 16259×3×2.5 0.7 1.1 1.9 31.7 185510×3×2.5 0.7 1.2 2.0 34.4 189012×3×2.5 0.7 1.2 2.0 35.5 211014×3×2.5 0.7 1.2 2.1 37.6 244515×3×2.5 0.7 1.2 2.2 38.9 262016×3×2.5 0.7 1.2 2.2 40.0 275518×3×2.5 0.7 1.2 2.3 42.0 301019×3×2.5 0.7 1.2 2.3 42.4 312520×3×2.5 0.7 1.2 2.3 43.5 336021×3×2.5 0.7 1.4 2.4 44.9 355523×3×2.5 0.7 1.4 2.5 46.7 388524×3×2.5 0.7 1.4 2.5 47.5 387027×3×2.5 0.7 1.4 2.6 50.0 428030×3×2.5 0.7 1.4 2.7 52.3 469532×3×2.5 0.7 1.4 2.7 53.8 4960
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Instrumentation
59ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
P16 IFLI 250 V
Applications
Ces câbles sont retardateur de flamme, faible dégagement de fumée et sans halogène, utilisé pour les zones de vie, trimestre et de bureau.
Normes
IEC 60092-376 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Fil de cuivre brin circulaire CEI 60228 classe 2. Isolation: XLPE. Literie: Composé thermoplastique sans halogène. Écran métallique: Ruban aluminium longitudinal, une épaisseur de 0,2 mm en contact
avec un conducteur de terre en cuivre brin. Gaine extérieure: Gratuit composé thermoplastique d’halogène, SHF1, couleur gris.
Caractéristiques électriques
Cross Section Nominale Zone mm² 2.5Maximum résistant@20℃ Ω/km 7.41Courant Nominal Continu@45℃ 2 Core A 261s courant de court circuit A 360Tension de fonctionnement V 250
XLPE Isolation
Conducteur En Cuivre Multibrins
SHF1 Gaine
Halogène Gratuit Literie Thermoplastique
Ruban Aluminium + Conducteur De Terre
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Instrumentation
60 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Propriétés mécaniques et thermiques
Rayon de cintrage: 8×OD (lors de l’installation); 6×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des éléments × non. des
carottes en élément × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
Intérieure Extérieur
2×1×2.5 0.7 1.1 1.2 10.0 180
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Instrumentation
61ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
S11 RU(i) 250 V
Applications
Ces câbles non armés sont ignifuge, sans fumée et halogènes, utilisés pour les systèmes d'instrumentation, de communication, de contrôle et d'alarme.
Normes
IEC 60092-376 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Fil recuit circulaire conserves brin de cuivre CEI 60228 classe 2. Isolation: Halogène composé EPR libre. Jumelage : Code couleurs carottes torsadés ensemble. Blindage individuel : Chaque paires/triples sont examinées par ruban de polyester
soutenue en cuivre en contact avec un fil de drain en cuivre étamé toronné et enveloppé avec du ruban adhésif polyester. Couples/triples sont numérotés avec un ruban numéroté ou par numéros imprimés directement sur les conducteurs isolés.
Gaine extérieure: Composés thermodurcissables libre d’halogène, SHF2, couleur gris (bleu pour sécurité intrinsèque).
Caractéristiques électriques
Cross Section Nominale Zone mm² 0.75 1.0 1.5 2.5Chef d’orchestre Diamètre nominal mm 1.1 1.3 1.6 2.0
HFEPR Isolation
Conducteur En Cuivre Multibrins
SHF2 Gaine
Ruban De Cuivre/Polyester+Fil De Drain
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Instrumentation
62 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Maximum résistant@20℃ Ω/km 26.3 19.3 12.9 8.02Capacité mutuelle nF/km 90 100 110 120Nominal Inductance@1KHz MH/km 0.686 0.649 0.637 0.598Maximum L/R@1KHz μH/Ω 20 25 35 50Tension de fonctionnement V 250 250 250 250
Propriétés mécaniques et thermiques
Rayon de cintrage: 8×OD (lors de l’installation); 6×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des éléments × non. des carottes en élément ×
coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gaine
mm
Diamètre nominal globalmm
Poids nominalkg/km
1×2×0.75 0.6 1.0 7.6 952×2×0.75 0.6 1.1 9.7 1804×2×0.75 0.6 1.2 12.1 2557×2×0.75 0.6 1.3 14.4 3808×2×0.75 0.6 1.3 15.6 425
12×2×0.75 0.6 1.5 19.0 61016×2×0.75 0.6 1.5 21.0 78519×2×0.75 0.6 1.6 22.4 89524×2×0.75 0.6 1.7 25.6 113532×2×0.75 0.6 1.8 28.4 14401×3×0.75 0.6 1.0 8.0 1102×3×0.75 0.6 1.2 11.0 1803×3×0.75 0.6 1.2 12.7 2654×3×0.75 0.6 1.2 13.8 3257×3×0.75 0.6 1.4 16.7 5008×3×0.75 0.6 1.4 18.0 540
12×3×0.75 0.6 1.6 22.2 81516×3×0.75 0.6 1.6 24.7 104519×3×0.75 0.6 1.7 26.2 120524×3×0.75 0.6 1.9 30.5 1545
1×2×1.0 0.6 1.0 8.1 1102×2×1.0 0.6 1.1 10.4 2154×2×1.0 0.6 1.2 12.9 3107×2×1.0 0.6 1.4 15.5 4758×2×1.0 0.6 1.4 17.0 540
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Instrumentation
63ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des éléments × non. des carottes en élément ×
coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gaine
mm
Diamètre nominal globalmm
Poids nominalkg/km
12×2×1.0 0.6 1.5 20.5 76016×2×1.0 0.6 1.5 22.9 99519×2×1.0 0.6 1.7 24.1 113524×2×1.0 0.6 1.8 27.8 145032×2×1.0 0.6 1.9 30.8 18501×3×1.0 0.6 1.0 8.5 1253×3×1.0 0.6 1.3 13.4 3204×3×1.0 0.6 1.3 14.8 3957×3×1.0 0.6 1.5 17.9 61512×3×1.0 0.6 1.6 23.7 99016×3×1.0 0.6 1.7 26.5 129519×3×1.0 0.6 1.8 28.0 147524×3×1.0 0.6 2.0 32.6 19001×2×1.5 0.7 1.0 9.1 1402×2×1.5 0.7 1.2 11.7 2804×2×1.5 0.7 1.3 14.9 4107×2×1.5 0.7 1.5 18.0 6358×2×1.5 0.7 1.5 19.7 72012×2×1.5 0.7 1.6 23.8 101516×2×1.5 0.7 1.6 26.6 133019×2×1.5 0.7 1.9 28.3 152524×2×1.5 0.7 2.0 32.6 194532×2×1.5 0.7 2.2 36.1 24751×3×1.5 0.7 1.0 9.5 1602×3×1.5 0.7 1.3 14.0 2853×3×1.5 0.7 1.3 15.5 4254×3×1.5 0.7 1.3 17.0 5257×3×1.5 0.7 1.6 20.9 8308×3×1.5 0.7 1.6 22.5 90012×3×1.5 0.7 1.8 27.6 134016×3×1.5 0.7 1.9 31.1 177019×3×1.5 0.7 2.0 32.8 202024×3×1.5 0.7 2.2 38.4 26101×2×2.5 0.7 1.0 9.8 1751×3×2.5 0.7 1.2 10.4 205
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Instrumentation
64 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
S12 RU(c) 250 V
Applications
Ces câbles non armés sont ignifuge, sans fumée et halogènes, utilisés pour les systèmes d'instrumentation, de communication, de contrôle et d'alarme.
Normes
IEC 60092-376 IEC 60092-351 IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Fil recuit circulaire conserves brin de cuivre CEI 60228 classe 2. Isolation: Halogène composé EPR libre. Jumelage : Code couleurs carottes torsadés ensemble. Collectives Blindage: Paires / triples sont layed et collectivement projetés par le
cuivre soutenu polyester bande en contact avec un fil de continuité étamé en cuivre brin. Paires / triples sont numérotés avec du ruban numéroté ou par des numéros imprimés directement sur les conducteurs isolés.
Gaine extérieure: Composés thermodurcissables libre d’halogène, SHF2, couleur gris (bleu pour sécurité intrinsèque).
Caractéristiques électriques
Cross Section Nominale Zone mm² 0.75 1.0 1.5Chef d’orchestre Diamètre nominal mm 1.1 1.3 1.6
HFEPR Isolation
Conducteur En Cuivre Multibrins
SHF2 Gaine
Ruban De Cuivre/Polyester+Fil De Drain
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Instrumentation
65ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Maximum résistant@20℃ Ω/km 26.3 19.3 12.9Capacité mutuelle nF/km 80 90 100Nominal Inductance@1KHz MH/km 0.682 0.645 0.632Maximum L/R@1KHz μH/Ω 20 25 35Tension de fonctionnement V 250 250 250
Propriétés mécaniques et thermiques
Rayon de cintrage: 8×OD (lors de l’installation); 6×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des éléments × non. des carottes en élément ×
coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gaine
mm
Diamètre nominal globalmm
Poids nominalkg/km
2×2×0.75 0.6 1.1 9.4 1604×2×0.75 0.6 1.1 11.5 2157×2×0.75 0.6 1.3 13.6 3008×2×0.75 0.6 1.3 14.7 34012×2×0.75 0.6 1.4 17.6 46516×2×0.75 0.6 1.5 19.7 59519×2×0.75 0.6 1.5 20.7 66524×2×0.75 0.6 1.7 24.1 85032×2×0.75 0.6 2.0 26.7 10652×3×0.75 0.6 1.1 11.0 1703×3×0.75 0.6 1.1 12.1 2354×3×0.75 0.6 1.2 13.1 2807×3×0.75 0.6 1.4 15.7 4108×3×0.75 0.6 1.4 17.5 49012×3×0.75 0.6 1.5 20.6 64516×3×0.75 0.6 1.6 23.1 83519×3×0.75 0.6 1.7 24.3 94024×3×0.75 0.6 1.8 28.2 1210
2×2×1.0 0.6 1.1 9.9 1904×2×1.0 0.6 1.1 12.3 2557×2×1.0 0.6 1.3 14.7 3708×2×1.0 0.6 1.3 15.7 41012×2×1.0 0.6 1.5 18.9 56516×2×1.0 0.6 1.6 21.1 73019×2×1.0 0.6 1.7 22.5 830
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Instrumentation
66 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des éléments × non. des carottes en élément ×
coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gaine
mm
Diamètre nominal globalmm
Poids nominalkg/km
24×2×1.0 0.6 1.8 25.9 105032×2×1.0 0.6 2.1 28.7 13153×3×1.0 0.6 1.1 12.9 2804×3×1.0 0.6 1.3 14.0 3357×3×1.0 0.6 1.5 16.9 50012×3×1.0 0.6 1.6 22.1 79516×3×1.0 0.6 1.6 24.8 102519×3×1.0 0.6 1.8 26.3 117524×3×1.0 0.6 2.0 30.4 14902×2×1.5 0.7 1.2 11.3 2504×2×1.5 0.7 1.2 14.1 3457×2×1.5 0.7 1.4 17.2 5158×2×1.5 0.7 1.4 18.4 57512×2×1.5 0.7 1.6 22.4 81016×2×1.5 0.7 1.7 25.0 104519×2×1.5 0.7 1.8 26.4 117524×2×1.5 0.7 1.9 30.7 150532×2×1.5 0.7 2.2 33.9 18902×3×1.5 0.7 1.2 13.5 2653×3×1.5 0.7 1.2 14.9 3804×3×1.5 0.7 1.3 16.3 4657×3×1.5 0.7 1.5 19.8 7058×3×1.5 0.7 1.5 21.5 82012×3×1.5 0.7 1.7 26.2 114016×3×1.5 0.7 1.8 29.4 147519×3×1.5 0.7 1.9 30.9 167524×3×1.5 0.7 2.1 36.2 2160
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
67ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
S3 ou S3/S7 BFOU(i) 250V
Applications
Ces câbles sont résistants au feu, retardateur de flamme, faible dégagement de fumée, sans halogène et résistants boue, utilisé pour les systèmes d'instrumentation, de communication, de contrôle et d'alarme.
Normes
IEC 60092-376 IEC 60092-351 IEC 60092-359 IEC 60331-21 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Fil recuit circulaire conserves brin de cuivre CEI 60228 classe 2. Isolation: Ruban Mica + Halogène composé EPR libre. Jumelage : Code couleurs carottes torsadés ensemble. Blindage individuel : Chaque paires/triples sont examinées par ruban de polyester
soutenue en cuivre en contact avec un fil de drain en cuivre étamé toronné et enveloppé avec du ruban adhésif polyester. Couples/triples sont numérotés avec un ruban numéroté ou par numéros imprimés directement sur les conducteurs isolés.
Literie: Composé sans halogène. Armour: Fil de cuivre étamé tresse. Gaine extérieure: Halogène composé thermodurcissable libre, SHF2 (pour le TYPE
S3). Halogène MUD gratuitement composé thermodurcissable résistant, SHF MUD (pour le TYPE S3/S7), de couleur grise (de bleu pour sécurité intrinsèque).
Fil De Cuivre Ètamé
Ruban Mica + HFEPR Isolation
Literie Sans Halogène
Conducteur En Cuivre Multibrins
SHF2 Gaine
Ruban De Cuivre/Polyester+Fil De Drain
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
68 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Caractéristiques électriques
Cross Section Nominale Zone mm² 0.75 1.0 1.5 2.5Chef d’orchestre Diamètre nominal mm 1.1 1.3 1.6 2.0Maximum résistant@20℃ Ω/km 26.3 19.3 12.9 8.02Capacité mutuelle nF/km 85 95 100 110Nominal Inductance@1KHz MH/km 0.731 0.691 0.673 0.629Maximum L/R@1KHz μH/Ω 20 25 35 55Tension de fonctionnement V 250 250 250 250
Propriétés mécaniques et thermiques
Rayon de cintrage: 8×OD (lors de l’installation); 6×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des éléments × non. des carottes en élément ×
coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal global
mm
Poids nominalkg/km
Intérieure Extérieur
1×2×0.75 0.6 1.1 1.2 12.1 2252×2×0.75 0.6 1.1 1.3 16.7 4053×2×0.75 0.6 1.1 1.4 17.5 5404×2×0.75 0.6 1.1 1.4 18.6 6105×2×0.75 0.6 1.1 1.5 20.2 7056×2×0.75 0.6 1.1 1.5 21.7 8057×2×0.75 0.6 1.1 1.5 21.7 8308×2×0.75 0.6 1.1 1.6 23.6 9059×2×0.75 0.6 1.1 1.7 25.1 100010×2×0.75 0.6 1.1 1.7 26.2 103012×2×0.75 0.6 1.1 1.7 26.8 114514×2×0.75 0.6 1.1 1.8 28.2 120515×2×0.75 0.6 1.1 1.8 30.0 130516×2×0.75 0.6 1.1 1.9 30.6 141518×2×0.75 0.6 1.1 1.9 32.1 147519×2×0.75 0.6 1.2 1.9 32.7 157520×2×0.75 0.6 1.2 2.0 34.1 1700
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
69ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des éléments × non. des carottes en élément ×
coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal global
mm
Poids nominalkg/km
Intérieure Extérieur
21×2×0.75 0.6 1.2 2.0 35.0 176523×2×0.75 0.6 1.2 2.0 35.5 189524×2×0.75 0.6 1.2 2.1 37.7 198027×2×0.75 0.6 1.2 2.2 38.7 216530×2×0.75 0.6 1.2 2.2 39.9 233533×2×0.75 0.6 1.2 2.3 41.5 253537×2×0.75 0.6 1.2 2.3 42.7 27251×3×0.75 0.6 1.1 1.1 11.9 2452×3×0.75 0.6 1.1 1.4 15.5 4203×3×0.75 0.6 1.1 1.4 18.4 5804×3×0.75 0.6 1.1 1.4 19.7 6757×3×0.75 0.6 1.1 1.6 23.6 9608×3×0.75 0.6 1.1 1.7 25.0 980
12×3×0.75 0.6 1.3 1.8 29.6 143516×3×0.75 0.6 1.4 1.9 32.6 177019×3×0.75 0.6 1.4 2.1 34.4 198524×3×0.75 0.6 1.8 2.2 39.6 25801×2×1.0 0.6 1.1 1.2 12.5 2452×2×1.0 0.6 1.1 1.4 17.6 4503×2×1.0 0.6 1.1 1.4 18.3 6004×2×1.0 0.6 1.1 1.4 19.3 6255×2×1.0 0.6 1.1 1.5 21.1 9206×2×1.0 0.6 1.1 1.6 22.8 9507×2×1.0 0.6 1.1 1.6 22.8 8608×2×1.0 0.6 1.1 1.6 24.7 9859×2×1.0 0.6 1.1 1.7 26.3 113510×2×1.0 0.6 1.1 1.7 27.4 117012×2×1.0 0.6 1.1 1.8 28.3 130014×2×1.0 0.6 1.1 1.8 29.5 138015×2×1.0 0.6 1.1 1.9 31.6 151016×2×1.0 0.6 1.1 1.9 32.1 162018×2×1.0 0.6 1.2 2.0 34.2 174519×2×1.0 0.6 1.2 2.0 34.5 183020×2×1.0 0.6 1.2 2.1 36.0 197521×2×1.0 0.6 1.2 2.1 37.3 213523×2×1.0 0.6 1.2 2.1 37.9 229524×2×1.0 0.6 1.2 2.2 39.8 233527×2×1.0 0.6 1.2 2.2 40.6 250030×2×1.0 0.6 1.2 2.3 42.1 272033×2×1.0 0.6 1.2 2.3 43.6 2940
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
70 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des éléments × non. des carottes en élément ×
coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal global
mm
Poids nominalkg/km
Intérieure Extérieur
37×2×1.0 0.6 1.4 2.4 45.4 32301×3×1.0 0.6 1.1 1.2 12.6 2752×3×1.0 0.6 1.1 1.4 18.8 6403×3×1.0 0.6 1.1 1.5 19.3 6654×3×1.0 0.6 1.1 1.5 20.9 7755×3×1.0 0.6 1.1 1.6 22.8 9656×3×1.0 0.6 1.1 1.7 25.4 11357×3×1.0 0.6 1.1 1.7 25.4 11808×3×1.0 0.6 1.1 1.7 27.0 12709×3×1.0 0.6 1.1 1.8 28.9 1450
10×3×1.0 0.6 1.1 1.9 31.1 145512×3×1.0 0.6 1.1 1.9 32.0 168514×3×1.0 0.6 1.2 2.0 33.8 182015×3×1.0 0.6 1.2 2.0 34.8 193516×3×1.0 0.6 1.2 2.1 36.0 210518×3×1.0 0.6 1.2 2.1 38.1 231019×3×1.0 0.6 1.2 2.2 38.6 235520×3×1.0 0.6 1.2 2.2 39.6 259021×3×1.0 0.6 1.2 2.2 40.4 268523×3×1.0 0.6 1.2 2.3 42.0 293524×3×1.0 0.6 1.2 2.3 42.8 314527×3×1.0 0.6 1.4 2.4 45.3 325530×3×1.0 0.6 1.4 2.5 47.4 356532×3×1.0 0.6 1.4 2.5 48.6 37551×2×1.5 0.7 1.1 1.2 13.5 2952×2×1.5 0.7 1.1 1.4 19.2 5453×2×1.5 0.7 1.1 1.5 20.2 7254×2×1.5 0.7 1.1 1.5 21.5 7705×2×1.5 0.7 1.1 1.6 23.4 9756×2×1.5 0.7 1.1 1.7 25.4 11307×2×1.5 0.7 1.1 1.7 25.4 11708×2×1.5 0.7 1.1 1.7 27.5 12259×2×1.5 0.7 1.1 1.8 29.4 1405
10×2×1.5 0.7 1.1 1.9 30.9 144012×2×1.5 0.7 1.1 1.9 31.6 168014×2×1.5 0.7 1.2 2.0 33.6 175015×2×1.5 0.7 1.2 2.1 36.0 191016×2×1.5 0.7 1.2 2.1 36.9 205518×2×1.5 0.7 1.2 2.2 38.9 226019×2×1.5 0.7 1.2 2.2 39.3 2395
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
71ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des éléments × non. des carottes en élément ×
coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal global
mm
Poids nominalkg/km
Intérieure Extérieur
20×2×1.5 0.7 1.2 2.2 40.8 254021×2×1.5 0.7 1.2 2.3 42.1 266023×2×1.5 0.7 1.2 2.3 42.7 286524×2×1.5 0.7 1.4 2.4 45.2 308027×2×1.5 0.7 1.4 2.4 46.1 315530×2×1.5 0.7 1.4 2.5 47.8 344032×2×1.5 0.7 1.4 2.6 49.0 368533×2×1.5 0.7 1.4 2.6 49.7 374037×2×1.5 0.7 1.4 2.6 51.2 40401×3×1.5 0.7 1.1 1.3 13.6 3252×3×1.5 0.7 1.1 1.5 18.5 5603×3×1.5 0.7 1.1 1.5 21.4 8004×3×1.5 0.7 1.1 1.6 23.7 9755×3×1.5 0.7 1.1 1.7 25.4 11956×3×1.5 0.7 1.1 1.8 28.3 14057×3×1.5 0.7 1.1 1.8 28.3 14708×3×1.5 0.7 1.1 1.8 30.2 15859×3×1.5 0.7 1.2 1.9 32.6 1835
10×3×1.5 0.7 1.2 2.0 35.1 193512×3×1.5 0.7 1.2 2.1 36.8 211514×3×1.5 0.7 1.2 2.1 38.3 236015×3×1.5 0.7 1.2 2.2 39.7 253016×3×1.5 0.7 1.2 2.2 40.8 277518×3×1.5 0.7 1.2 2.3 42.9 290519×3×1.5 0.7 1.2 2.3 43.3 320020×3×1.5 0.7 1.4 2.4 44.9 330521×3×1.5 0.7 1.4 2.4 45.8 343023×3×1.5 0.7 1.4 2.5 47.7 375524×3×1.5 0.7 1.4 2.5 48.6 392527×3×1.5 0.7 1.4 2.6 51.1 411530×3×1.5 0.7 1.4 2.7 53.5 451032×3×1.5 0.7 1.6 2.8 55.5 48501×2×2.5 0.7 1.1 1.3 14.0 3402×2×2.5 0.7 1.1 1.5 18.5 5603×2×2.5 0.7 1.1 1.5 21.6 8654×2×2.5 0.7 1.1 1.6 23.2 10105×2×2.5 0.7 1.1 1.7 25.3 11856×2×2.5 0.7 1.1 1.7 27.4 13707×2×2.5 0.7 1.1 1.7 27.4 14308×2×2.5 0.7 1.1 1.8 29.9 1560
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
72 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des éléments × non. des carottes en élément ×
coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal global
mm
Poids nominalkg/km
Intérieure Extérieur
9×2×2.5 0.7 1.1 1.9 31.9 178010×2×2.5 0.7 1.2 2.0 33.8 177512×2×2.5 0.7 1.2 2.0 34.6 196514×2×2.5 0.7 1.2 2.1 36.9 227515×2×2.5 0.7 1.2 2.2 39.5 248016×2×2.5 0.7 1.2 2.2 40.1 259018×2×2.5 0.7 1.2 2.3 42.3 282519×2×2.5 0.7 1.2 2.3 42.7 293020×2×2.5 0.7 1.4 2.4 44.8 324021×2×2.5 0.7 1.4 2.4 46.1 337523×2×2.5 0.7 1.4 2.5 46.9 356024×2×2.5 0.7 1.4 2.5 49.1 366027×2×2.5 0.7 1.4 2.6 50.3 400030×2×2.5 0.7 1.4 2.7 52.2 437033×2×2.5 0.7 1.4 2.7 54.1 473537×2×2.5 0.7 1.6 2.8 56.4 52251×3×2.5 0.7 1.1 1.2 14.5 3802×3×2.5 0.7 1.1 1.6 22.5 9503×3×2.5 0.7 1.1 1.6 23.4 10554×3×2.5 0.7 1.1 1.7 25.3 12505×3×2.5 0.7 1.1 1.7 27.4 14606×3×2.5 0.7 1.1 1.9 30.7 17357×3×2.5 0.7 1.1 1.9 30.7 18308×3×2.5 0.7 1.2 2.0 33.3 20259×3×2.5 0.7 1.2 2.0 35.4 2290
10×3×2.5 0.7 1.2 2.2 38.8 240512×3×2.5 0.7 1.2 2.2 40.0 268514×3×2.5 0.7 1.2 2.3 41.9 300015×3×2.5 0.7 1.2 2.3 43.1 319016×3×2.5 0.7 1.4 2.4 44.9 342018×3×2.5 0.7 1.4 2.5 47.2 374019×3×2.5 0.7 1.4 2.5 47.6 388520×3×2.5 0.7 1.4 2.5 48.9 418521×3×2.5 0.7 1.4 2.6 50.0 437023×3×2.5 0.7 1.4 2.7 52.1 476024×3×2.5 0.7 1.4 2.7 53.0 478527×3×2.5 0.7 1.6 2.8 56.2 533530×3×2.5 0.7 1.6 2.9 58.8 585532×3×2.5 0.7 1.6 3.0 60.6 6215
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
73ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
S4 ou S4/S8 BFOU(c) 250V
Applications
Ces câbles sont résistants au feu, retardateur de flamme, faible dégagement de fumée, sans halogène et résistants boue, utilisé pour les systèmes d'instrumentation, de communication, de contrôle et d'alarme.
Normes
IEC 60092-376 IEC 60092-351 IEC 60092-359 IEC 60331-21 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Fil recuit circulaire conserves brin de cuivre CEI 60228 classe 2. Isolation: Ruban Mica + Halogène composé EPR libre. Jumelage : Code couleurs carottes torsadés ensemble. Collectives Blindage: Paires / triples sont layed et collectivement projetés par le
cuivre soutenu polyester bande en contact avec un fil de continuité étamé en cuivre brin. Paires / triples sont numérotés avec du ruban numéroté ou par des numéros imprimés directement sur les conducteurs isolés.
Literie: Composé sans halogène. Armour: Fil de cuivre étamé tresse. Gaine extérieure: Sans halogène composés thermodurcissables, SHF2 (pour TYPE
S4). Gratuit composé thermodurcissable résistant à la boue halogène, boue de la SHF (pour TYPE S4/S8), de couleur gris (bleu pour sécurité intrinsèque).
Fil De Cuivre Ètamé
Ruban Mica + HFEPR Isolation
Literie Sans Halogène
Conducteur En Cuivre Multibrins
SHF2/SHF Gaine De BOUE
Ruban De Cuivre/Polyester+Fil De Drain
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
74 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Caractéristiques électriques
Cross Section Nominale Zone mm² 0.75 1.0 1.5 2.5Chef d’orchestre Diamètre nominal mm 1.1 1.3 1.6 2.0Maximum résistant@20℃ Ω/km 26.3 19.3 12.9 8.02Capacité mutuelle nF/km 75 80 85 95Nominal Inductance@1KHz MH/km 0.727 0.686 0.667 0.623Maximum L/R@1KHz μH/Ω 20 25 35 55Tension de fonctionnement V 250 250 250 250
Propriétés mécaniques et thermiques
Rayon de cintrage: 8×OD (lors de l’installation); 6×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des éléments × non. des carottes en élément
× coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal global
mm
Poids nominalkg/km
Intérieure Extérieur
1×2×0.75 0.6 1.1 1.2 12.1 2302×2×0.75 0.6 1.1 1.3 16.4 3403×2×0.75 0.6 1.1 1.4 17.2 4954×2×0.75 0.6 1.1 1.4 18.2 5555×2×0.75 0.6 1.1 1.5 19.8 6406×2×0.75 0.6 1.1 1.5 21.2 7257×2×0.75 0.6 1.1 1.5 21.2 7408×2×0.75 0.6 1.1 1.6 23.1 8059×2×0.75 0.6 1.1 1.6 24.3 880
10×2×0.75 0.6 1.1 1.7 25.6 90012×2×0.75 0.6 1.1 1.7 26.2 95014×2×0.75 0.6 1.1 1.7 27.3 103515×2×0.75 0.6 1.1 1.8 29.2 113016×2×0.75 0.6 1.1 1.8 29.7 117518×2×0.75 0.6 1.1 1.9 31.3 127519×2×0.75 0.6 1.1 1.9 31.6 131520×2×0.75 0.6 1.2 2.0 33.3 147521×2×0.75 0.6 1.2 2.0 34.1 153023×2×0.75 0.6 1.2 2.0 34.6 163524×2×0.75 0.6 1.2 2.1 36.8 173027×2×0.75 0.6 1.2 2.1 37.5 1850
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
75ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des éléments × non. des carottes en élément
× coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal global
mm
Poids nominalkg/km
Intérieure Extérieur
30×2×0.75 0.6 1.2 2.2 38.9 196533×2×0.75 0.6 1.2 2.2 40.3 215537×2×0.75 0.6 1.2 2.3 41.7 23251×3×0.75 0.6 1.1 1.2 12.6 2552×3×0.75 0.6 1.1 1.4 17.7 5453×3×0.75 0.6 1.1 1.4 18.3 5854×3×0.75 0.6 1.1 1.5 19.7 6705×3×0.75 0.6 1.1 1.5 21.2 7706×3×0.75 0.6 1.1 1.6 23.5 9007×3×0.75 0.6 1.1 1.6 23.5 9358×3×0.75 0.6 1.1 1.7 25.2 10159×3×0.75 0.6 1.1 1.7 26.7 113510×3×0.75 0.6 1.1 1.8 28.7 114012×3×0.75 0.6 1.1 1.8 29.6 123014×3×0.75 0.6 1.1 1.9 31.0 137515×3×0.75 0.6 1.1 1.9 31.9 145516×3×0.75 0.6 1.2 2.0 33.3 154518×3×0.75 0.6 1.2 2.0 34.8 169019×3×0.75 0.6 1.2 2.0 35.1 175020×3×0.75 0.6 1.2 2.1 36.6 198521×3×0.75 0.6 1.2 2.1 37.3 205523×3×0.75 0.6 1.2 2.2 38.8 221524×3×0.75 0.6 1.2 2.2 39.5 224527×3×0.75 0.6 1.2 2.3 41.5 243530×3×0.75 0.6 1.2 2.3 43.3 264532×3×0.75 0.6 1.4 2.4 44.9 28401×2×1.0 0.6 1.1 1.2 12.5 2452×2×1.0 0.6 1.1 1.4 17.2 3753×2×1.0 0.6 1.1 1.4 17.9 5504×2×1.0 0.6 1.1 1.4 19.0 6155×2×1.0 0.6 1.1 1.5 20.6 7106×2×1.0 0.6 1.1 1.6 22.4 8207×2×1.0 0.6 1.1 1.6 22.4 8458×2×1.0 0.6 1.1 1.6 24.1 9059×2×1.0 0.6 1.1 1.7 25.7 99510×2×1.0 0.6 1.1 1.7 26.8 103512×2×1.0 0.6 1.1 1.7 27.4 109514×2×1.0 0.6 1.1 1.8 28.9 119515×2×1.0 0.6 1.1 1.9 30.9 130516×2×1.0 0.6 1.1 1.9 31.4 135518×2×1.0 0.6 1.2 2.0 33.4 150019×2×1.0 0.6 1.2 2.0 33.7 1550
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
76 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des éléments × non. des carottes en élément
× coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal global
mm
Poids nominalkg/km
Intérieure Extérieur
20×2×1.0 0.6 1.2 2.0 35.0 168521×2×1.0 0.6 1.2 2.1 36.5 185023×2×1.0 0.6 1.2 2.1 37.0 197524×2×1.0 0.6 1.2 2.2 38.9 199027×2×1.0 0.6 1.2 2.2 39.6 213530×2×1.0 0.6 1.2 2.2 40.9 230033×2×1.0 0.6 1.2 2.3 42.5 249537×2×1.0 0.6 1.4 2.4 44.3 27351×3×1.0 0.6 1.1 1.2 13.0 2802×3×1.0 0.6 1.1 1.4 18.0 5503×3×1.0 0.6 1.1 1.4 18.7 6004×3×1.0 0.6 1.1 1.5 20.0 6905×3×1.0 0.6 1.1 1.6 22.4 8806×3×1.0 0.6 1.1 1.6 24.6 10207×3×1.0 0.6 1.1 1.6 24.6 10608×3×1.0 0.6 1.1 1.7 26.4 11509×3×1.0 0.6 1.1 1.8 28.2 1305
10×3×1.0 0.6 1.1 1.8 30.2 129012×3×1.0 0.6 1.1 1.9 31.3 143514×3×1.0 0.6 1.2 1.9 32.9 160515×3×1.0 0.6 1.2 2.0 34.0 172016×3×1.0 0.6 1.2 2.0 35.0 176518×3×1.0 0.6 1.2 2.1 37.2 205019×3×1.0 0.6 1.2 2.1 37.5 212020×3×1.0 0.6 1.2 2.2 38.7 230021×3×1.0 0.6 1.2 2.2 39.4 238023×3×1.0 0.6 1.2 2.2 40.8 251524×3×1.0 0.6 1.2 2.3 41.7 257527×3×1.0 0.6 1.2 2.3 43.7 281530×3×1.0 0.6 1.4 2.4 46.1 312532×3×1.0 0.6 1.4 2.5 47.5 33101×2×1.5 0.7 1.1 1.3 14.3 3352×2×1.5 0.7 1.1 1.5 20.5 7403×2×1.5 0.7 1.1 1.5 21.2 8054×2×1.5 0.7 1.1 1.6 22.9 9455×2×1.5 0.7 1.1 1.6 24.8 10956×2×1.5 0.7 1.1 1.8 27.8 13007×2×1.5 0.7 1.1 1.8 27.8 13558×2×1.5 0.7 1.1 1.8 29.6 14559×2×1.5 0.7 1.1 1.9 31.7 1660
10×2×1.5 0.7 1.1 2.0 34.4 168012×2×1.5 0.7 1.1 2.0 35.5 1855
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
77ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des éléments × non. des carottes en élément
× coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal global
mm
Poids nominalkg/km
Intérieure Extérieur
14×2×1.5 0.7 1.2 2.1 37.6 215015×2×1.5 0.7 1.2 2.2 38.9 230016×2×1.5 0.7 1.2 2.2 40.0 241518×2×1.5 0.7 1.2 2.3 42.0 263019×2×1.5 0.7 1.2 2.3 42.4 272520×2×1.5 0.7 1.2 2.3 43.5 294021×2×1.5 0.7 1.2 2.4 44.9 311023×2×1.5 0.7 1.2 2.5 46.7 340024×2×1.5 0.7 1.2 2.5 47.5 336027×2×1.5 0.7 1.4 2.6 50.0 371030×2×1.5 0.7 1.4 2.7 52.3 406032×2×1.5 0.7 1.4 2.7 53.8 428533×2×1.5 0.7 1.4 2.5 48.5 324537×2×1.5 0.7 1.4 2.6 50.2 35151×3×1.5 0.7 1.1 1.3 14.3 3352×3×1.5 0.7 1.1 1.5 20.5 7403×3×1.5 0.7 1.1 1.5 21.2 8054×3×1.5 0.7 1.1 1.6 22.9 9455×3×1.5 0.7 1.1 1.6 24.8 10956×3×1.5 0.7 1.1 1.8 27.8 13007×3×1.5 0.7 1.1 1.8 27.8 13558×3×1.5 0.7 1.1 1.8 29.6 14559×3×1.5 0.7 1.1 1.9 31.7 1660
10×3×1.5 0.7 1.2 2.0 34.4 168012×3×1.5 0.7 1.2 2.0 35.5 185514×3×1.5 0.7 1.2 2.1 37.6 215015×3×1.5 0.7 1.2 2.2 38.9 230016×3×1.5 0.7 1.2 2.2 40.0 240518×3×1.5 0.7 1.2 2.3 42.0 263019×3×1.5 0.7 1.2 2.3 42.4 271020×3×1.5 0.7 1.2 2.3 43.5 294021×3×1.5 0.7 1.4 2.4 44.9 311023×3×1.5 0.7 1.4 2.5 46.7 340024×3×1.5 0.7 1.4 2.5 47.5 343027×3×1.5 0.7 1.4 2.6 50.0 371030×3×1.5 0.7 1.4 2.7 52.3 406032×3×1.5 0.7 1.4 2.7 53.8 42851×2×2.5 0.7 1.1 1.3 14.5 3352×2×2.5 0.7 1.1 1.5 20.4 7403×2×2.5 0.7 1.1 1.5 21.3 8004×2×2.5 0.7 1.1 1.6 22.8 9305×2×2.5 0.7 1.1 1.6 24.7 1075
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
78 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des éléments × non. des carottes en élément
× coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal global
mm
Poids nominalkg/km
Intérieure Extérieur
6×2×2.5 0.7 1.1 1.7 26.9 12457×2×2.5 0.7 1.1 1.7 26.9 12908×2×2.5 0.7 1.1 1.8 29.3 14059×2×2.5 0.7 1.1 1.9 31.3 1585
10×2×2.5 0.7 1.2 2.0 33.2 160512×2×2.5 0.7 1.2 2.0 34.0 174514×2×2.5 0.7 1.2 2.0 35.6 192015×2×2.5 0.7 1.2 2.2 38.8 220516×2×2.5 0.7 1.2 2.2 39.4 223018×2×2.5 0.7 1.2 2.3 41.5 250019×2×2.5 0.7 1.2 2.3 41.9 259020×2×2.5 0.7 1.2 2.3 43.5 281521×2×2.5 0.7 1.4 2.4 45.2 299023×2×2.5 0.7 1.4 2.4 45.8 321524×2×2.5 0.7 1.4 2.5 48.2 327027×2×2.5 0.7 1.4 2.6 49.4 351530×2×2.5 0.7 1.4 2.6 51.0 381033×2×2.5 0.7 1.4 2.7 53.1 414537×2×2.5 0.7 1.4 2.8 54.9 45001×3×2.5 0.7 1.1 1.3 15.1 3852×3×2.5 0.7 1.1 1.5 22.0 8803×3×2.5 0.7 1.1 1.6 23.0 9904×3×2.5 0.7 1.1 1.6 24.6 11505×3×2.5 0.7 1.1 1.7 26.9 13506×3×2.5 0.7 1.1 1.8 30.0 15957×3×2.5 0.7 1.1 1.8 30.0 16708×3×2.5 0.7 1.1 1.9 32.2 18209×3×2.5 0.7 1.2 2.0 34.8 2105
10×3×2.5 0.7 1.2 2.1 37.9 219012×3×2.5 0.7 1.2 2.2 39.2 245514×3×2.5 0.7 1.2 2.2 40.9 271515×3×2.5 0.7 1.2 2.3 42.3 290516×3×2.5 0.7 1.2 2.3 43.5 306018×3×2.5 0.7 1.4 2.4 46.1 338019×3×2.5 0.7 1.4 2.5 46.7 353020×3×2.5 0.7 1.4 2.5 47.9 380021×3×2.5 0.7 1.4 2.5 48.9 395023×3×2.5 0.7 1.4 2.6 50.9 429024×3×2.5 0.7 1.4 2.6 51.8 432527×3×2.5 0.7 1.4 2.7 54.5 474530×3×2.5 0.7 1.6 2.9 57.7 530032×3×2.5 0.7 1.6 2.9 59.3 5595
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
79ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
S13 BU(i) 250 V
Applications
Ces câbles sont résistants au feu, retardateur de flamme, faible dégagement de fumée et sans halogène, utilisé pour les systèmes d'instrumentation, de communication, de contrôle et d'alarme.
Normes
IEC 60092-376 IEC 60092-351 IEC 60092-359 IEC 60331-21 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Fil recuit circulaire conserves brin de cuivre CEI 60228 classe 2. Isolation: Ruban Mica + Halogène composé EPR libre. Jumelage : Code couleurs carottes torsadés ensemble. Blindage individuel : Chaque paires/triples sont examinées par ruban de polyester
soutenue en cuivre en contact avec un fil de drain en cuivre étamé toronné et enveloppé avec du ruban adhésif polyester. Couples/triples sont numérotés avec un ruban numéroté ou par numéros imprimés directement sur les conducteurs isolés.
Gaine extérieure: Composés thermodurcissables libre d’halogène, SHF2, couleur gris (bleu pour sécurité intrinsèque).
Ruban Mica + HFEPR Isolation
Conducteur En Cuivre Multibrins
SHF2 Gaine
Ruban De Cuivre/Polyester+Fil De Drain
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
80 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Caractéristiques électriques
Cross Section Nominale Zone mm² 0.75 1.0 1.5 2.5Chef d’orchestre Diamètre nominal mm 1.1 1.3 1.6 2.0Maximum résistant@20℃ Ω/km 26.3 19.3 12.9 8.02Capacité mutuelle nF/km 85 95 100 110Nominal Inductance@1KHz MH/km 0.731 0.691 0.673 0.629Maximum L/R@1KHz μH/Ω 20 25 35 55Tension de fonctionnement V 250 250 250 250
Propriétés mécaniques et thermiques
Rayon de cintrage: 8×OD (lors de l’installation); 6×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des éléments × non. des carottes en élément ×
coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gaine
mm
Diamètre nominal globalmm
Poids nominalkg/km
1×2×0.75 0.6 1.0 8.2 1052×2×0.75 0.6 1.2 10.5 2054×2×0.75 0.6 1.2 13.2 2907×2×0.75 0.6 1.4 16.0 4458×2×0.75 0.6 1.4 17.3 49512×2×0.75 0.6 1.6 21.1 70516×2×0.75 0.6 1.7 23.5 91519×2×0.75 0.6 1.8 24.8 103524×2×0.75 0.6 1.9 28.6 132032×2×0.75 0.6 2.0 31.7 16701×3×0.75 0.6 1.0 8.6 1202×3×0.75 0.6 1.2 12.0 2053×3×0.75 0.6 1.2 13.8 3004×3×0.75 0.6 1.3 15.1 3657×3×0.75 0.6 1.5 18.3 5608×3×0.75 0.6 1.5 19.5 65012×3×0.75 0.6 1.7 24.4 91516×3×0.75 0.6 1.8 27.3 118519×3×0.75 0.6 1.9 29.0 136024×3×0.75 0.6 2.1 33.7 1750
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
81ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des éléments × non. des carottes en élément ×
coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gaine
mm
Diamètre nominal globalmm
Poids nominalkg/km
1×2×1.0 0.6 1.0 8.6 1252×2×1.0 0.6 1.2 11.1 2404×2×1.0 0.6 1.3 14.0 3457×2×1.0 0.6 1.5 16.9 5258×2×1.0 0.6 1.5 18.5 600
12×2×1.0 0.6 1.6 22.3 84016×2×1.0 0.6 1.6 24.9 109519×2×1.0 0.6 1.8 26.5 125524×2×1.0 0.6 1.9 30.5 160532×2×1.0 0.6 2.0 33.8 20301×3×1.0 0.6 1.0 9.1 1403×3×1.0 0.6 1.3 14.7 3604×3×1.0 0.6 1.3 16.1 4407×3×1.0 0.6 1.6 19.7 695
12×3×1.0 0.6 1.7 26.0 111516×3×1.0 0.6 1.8 29.2 145519×3×1.0 0.6 1.9 31.0 167524×3×1.0 0.6 2.1 36.1 21451×2×1.5 0.7 1.0 9.6 1552×2×1.5 0.7 1.3 12.6 3104×2×1.5 0.7 1.4 16.1 4507×2×1.5 0.7 1.6 19.4 6908×2×1.5 0.7 1.6 21.3 780
12×2×1.5 0.7 1.7 25.7 110016×2×1.5 0.7 1.9 28.9 145019×2×1.5 0.7 2.0 30.5 164524×2×1.5 0.7 2.2 35.3 211532×2×1.5 0.7 2.3 39.1 26801×3×1.5 0.7 1.1 10.1 1752×3×1.5 0.7 1.3 14.5 3203×3×1.5 0.7 1.3 16.8 4704×3×1.5 0.7 1.4 18.4 5807×3×1.5 0.7 1.7 22.6 9108×3×1.5 0.7 1.7 23.5 1030
12×3×1.5 0.7 1.9 30.0 147516×3×1.5 0.7 2.0 33.6 192519×3×1.5 0.7 2.1 35.7 221024×3×1.5 0.7 2.4 41.7 28551×2×2.5 0.7 1.1 10.5 1901×3×2.5 0.7 1.3 11.0 220
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
82 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
S14 BU(c) 250 V
Applications
Ces câbles non blindés sont résistants au feu, retardateur de flamme, faible dégagement de fumée et sans halogène, utilisé pour les systèmes d'instrumentation, de communication, de contrôle et d'alarme.
Normes
IEC 60092-376 IEC 60092-351 IEC 60092-359 IEC 60331-21 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Fil recuit circulaire conserves brin de cuivre CEI 60228 classe 2. Isolation: Ruban Mica + Halogène composé EPR libre. Jumelage : Code couleurs carottes torsadés ensemble. Collectives Blindage: Paires / triples sont layed et collectivement projetés par le
cuivre soutenu polyester bande en contact avec un fil de continuité étamé en cuivre brin. Paires / triples sont numérotés avec du ruban numéroté ou par des numéros imprimés directement sur les conducteurs isolés.
Gaine extérieure: Composés thermodurcissables libre d’halogène, SHF2, couleur gris (bleu pour sécurité intrinsèque).
Ruban Mica + HFEPR Isolation
Conducteur En Cuivre Multibrins
SHF2 Gaine
Ruban De Cuivre/Polyester+Fil De Drain
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
83ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Caractéristiques électriques
Cross Section Nominale Zone mm² 0.75 1.0 1.5Chef d’orchestre Diamètre nominal mm 1.1 1.3 1.6Maximum résistant@20℃ Ω/km 26.3 19.3 12.9Capacité mutuelle nF/km 75 80 85Nominal Inductance@1KHz MH/km 0.727 0.686 0.667Maximum L/R@1KHz μH/Ω 20 25 35Tension de fonctionnement V 250 250 250
Propriétés mécaniques et thermiques
Rayon de cintrage: 8×OD (lors de l’installation); 6×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des éléments × non. des carottes en élément ×
coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gaine
mm
Diamètre nominal globalmm
Poids nominalkg/km
2×2×0.75 0.6 1.1 10.2 1854×2×0.75 0.6 1.2 12.5 2407×2×0.75 0.6 1.4 15.0 3508×2×0.75 0.6 1.4 16.3 395
12×2×0.75 0.6 1.5 19.5 54016×2×0.75 0.6 1.6 21.8 69019×2×0.75 0.6 1.7 23.2 78024×2×0.75 0.6 1.8 26.7 98532×2×0.75 0.6 2.1 29.6 12252×3×0.75 0.6 1.2 12.0 2053×3×0.75 0.6 1.2 13.1 2654×3×0.75 0.6 1.3 14.4 3207×3×0.75 0.6 1.3 17.4 4758×3×0.75 0.6 1.5 19.5 590
12×3×0.75 0.6 1.6 22.9 74516×3×0.75 0.6 1.7 25.6 96519×3×0.75 0.6 1.8 27.2 109524×3×0.75 0.6 2.0 31.6 14052×2×1.0 0.6 1.1 10.7 210
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
84 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Construction de no des éléments × non. des carottes en élément ×
coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gaine
mm
Diamètre nominal globalmm
Poids nominalkg/km
4×2×1.0 0.6 1.1 13.3 2857×2×1.0 0.6 1.4 16.0 4158×2×1.0 0.6 1.4 17.3 465
12×2×1.0 0.6 1.6 20.8 64516×2×1.0 0.6 1.7 23.3 82519×2×1.0 0.6 1.8 24.7 94024×2×1.0 0.6 1.9 28.8 120032×2×1.0 0.6 2.3 31.8 14953×3×1.0 0.6 1.2 14.0 3104×3×1.0 0.6 1.4 15.3 3807×3×1.0 0.6 1.6 18.6 570
12×3×1.0 0.6 1.6 24.4 90016×3×1.0 0.6 1.7 27.3 116019×3×1.0 0.6 1.9 29.0 132524×3×1.0 0.6 2.1 33.7 17002×2×1.5 0.7 1.2 12.1 2754×2×1.5 0.7 1.3 15.2 3807×2×1.5 0.7 1.5 18.4 5658×2×1.5 0.7 1.5 20.0 640
12×2×1.5 0.7 1.7 24.3 89516×2×1.5 0.7 1.8 27.2 115019×2×1.5 0.7 1.9 28.6 129524×2×1.5 0.7 2.1 33.5 167032×2×1.5 0.7 2.3 37.0 20952×3×1.5 0.7 1.3 15.0 3103×3×1.5 0.7 1.3 16.0 4204×3×1.5 0.7 1.4 17.7 5157×3×1.5 0.7 1.6 21.5 7858×3×1.5 0.7 1.6 23.5 930
12×3×1.5 0.7 1.8 28.5 125516×3×1.5 0.7 1.9 31.9 163019×3×1.5 0.7 2.0 33.8 185524×3×1.5 0.7 2.2 39.3 2375
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
85ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
S15 BFOU-HCF(i) 250 V
Applications
Ces câbles sont résistantes au feu, retardateur de flamme, sans fumée et halogènes, utilisé pour les systèmes d'instrumentation, de communication, de contrôle et d'alarme d'urgence nécessitant d'être opérationnel durant une 1100 ℃ feu d'hydrocarbures.
Normes
IEC 60092-376 IEC 60092-351 IEC 60092-359 IEC 60331-21 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Fil recuit circulaire conserves brin de cuivre CEI 60228 classe 2. Isolation: Ruban Mica + Halogène composé EPR libre. Jumelage : Code couleurs carottes torsadés ensemble. Blindage individuel : Chaque paires/triples sont examinées par ruban de polyester
soutenue en cuivre en contact avec un fil de drain en cuivre étamé toronné et enveloppé avec du ruban adhésif polyester. Couples/triples sont numérotés avec un ruban numéroté ou par numéros imprimés directement sur les conducteurs isolés.
Literie: Composé sans halogène. Armour: Fil de cuivre étamé tresse. Gaine extérieure1: Halogène composé thermodurcissable libre, SHF2. Protection contre l’incendie-HC :Protection contre l’incendie thermoplastique
SHF2 Gaine
Ruban Mica + HFEPR Isolation
Literie Sans Halogène
Conducteur En Cuivre Multibrins
SHF1 Gaine
HC-Protection Contre L'incendie+Ruban AdhésifFil De Cuivre Ètamé
Ruban De Cuivre/Polyester+Fil De Drain
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
86 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
composé des profilés extrudés.. Enregistrement :Ruban de fibre de verre rodé. Gaine extérieure2: Thermoplastique ignifuge sans halogène composé, tapez SHF1,
couleur gris (bleu pour sécurité intrinsèque).
Caractéristiques électriques
Cross Section Nominale Zone mm² 1.5Chef d’orchestre Diamètre nominal mm 1.6Maximum résistant@20℃ Ω/km 12.9Capacité mutuelle nF/km 100Nominal Inductance@1KHz MH/km 0.673Tension de fonctionnement V 250
Propriétés mécaniques et thermiques
Rayon de cintrage: 20×OD (lors de l’installation); 12×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des éléments × non. des
carottes en élément × coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Diamètre nominal cours
Literiemm
Diamètre nominal sur gaine1
mm
Diamètre nominal globalmm
Poids nominalkg/km
1×2×1.5 0.7 9.0 13.1 39.5 18802×2×1.5 0.7 13.0 16.8 44.5 24504×2×1.5 0.7 15.0 20.7 47.5 28308×2×1.5 0.7 21.0 26.4 54.0 3690
12×2×1.5 0.7 25.0 31.2 63.0 5200
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
87ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
S16 BFOU-HCF(c) 250 V
Applications
Ces câbles sont résistantes au feu, retardateur de flamme, sans fumée et halogènes, utilisé pour les systèmes d'instrumentation, de communication, de contrôle et d'alarme d'urgence nécessitant d'être opérationnel durant une 1100 ℃ feu d'hydrocarbures.
Normes
IEC 60092-376 IEC 60092-351 IEC 60092-359 IEC 60331-21 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Fil de cuivre étamé brin circulaire IEC 60228 classe 2 Isolation: Ruban Mica + Halogène composé EPR libre. Jumelage : Code couleurs carottes torsadés ensemble. Collectives Blindage: Paires / triples sont layed et collectivement projetés par le
cuivre soutenu polyester bande en contact avec un fil de continuité étamé en cuivre brin. Paires / triples sont numérotés avec du ruban numéroté ou par des numéros imprimés directement sur les conducteurs isolés.
Literie: Composé sans halogène. Armour: Fil de cuivre étamé tresse. Gaine extérieure1: Halogène composé thermodurcissable libre, SHF2. Protection contre l’incendie-HC :Protection contre l’incendie thermoplastique
SHF2 Gaine
Ruban Mica + HFEPR Isolation
Literie Sans Halogène
Conducteur En Cuivre Multibrins
SHF1 Gaine
HC-Protection Contre L'incendie+Ruban AdhésifFil De Cuivre Ètamé
Ruban De Cuivre/Polyester+Fil De Drain
Copyright@ Caledonian Câbles Offshore & Marine
Résistant Au Feu Câbles Instrumentation
88 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
composé des profilés extrudés.. Enregistrement :Ruban de fibre de verre rodé. Gaine extérieure2: Thermoplastique ignifuge sans halogène composé, tapez SHF1,
couleur gris (bleu pour sécurité intrinsèque).
Caractéristiques électriques Cross Section Nominale Zone mm² 1.5Chef d’orchestre Diamètre nominal mm 1.6Maximum résistant@20℃ Ω/km 12.9Capacité mutuelle nF/km 85Nominal Inductance@1KHz MH/km 0.667Tension de fonctionnement V 250
Propriétés mécaniques et thermiques
Rayon de cintrage: 20×OD (lors de l’installation); 12×OD (fixes installés) Plage de température: -20℃ ~ +90℃
Dimensions et poids
Construction de no des éléments × non. des carottes en élément ×
coupe transversale(mm²)
Épaisseur D'isolation Nominale
mm
Diamètre nominal cours
Literiemm
Diamètre nominal sur
gaine1mm
Diamètre nominal global
mm
Poids nominalkg/km
2×2×1.5 0.7 13.0 16.4 44.5 24004×2×1.5 0.7 15.0 19.9 46.5 26508×2×1.5 0.7 20.5 25.3 53.0 3570
12×2×1.5 0.7 23.5 29.6 57.0 4160
Copyright@ Caledonian Câbles Offshore & Marine
Câbles De Télécommunications
89ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
S9 IYXI(c) 60 V
Applications
Ces câbles sont retardateur de flamme, faible dégagement de fumée et sans halogène, utilisé pour les télécommunications à l'intérieur.
Normes
IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Solide cuivre étamé, 0.5mm. Isolation: PE composé thermoplastique sans halogène. Jumelage : Codés par couleur noyaux torsadés. Les couples sont croix-brin au câble
fini ou 10 unités de paire. Les unités sont bloqués à 20 ans - 30 - 50 câbles à paires. 2 paire est bloqué comme un quad étoiles.
Emballage:Ruban de polyester. Collectives Blindage: L’âme du câble est projeté par le cuivre soutenu ruban
polyester en contact avec un fil de 0,5 mm de vidange étamé solide. Gaine:Composé thermoplastique sans halogène, le type SHF1, de couleur grise.
Caractéristiques électriques
Chef d’orchestre Diamètre nominal mm 0.5Maximum résistant@20℃ Ω/km 95Nominal Inductance@1KHz MH/km 0.61Capacité mutuelle câble 1 paire nF/km 90
Ruban De Cuivre/Polyester+Fil De Drain
Isolation PE Gratuit Halogène
Ruban D'emballage
Conducteur De Cuivre Massif
SHF1 Gaine
Paire Torsadée
Copyright@ Caledonian Câbles Offshore & Marine
Câbles De Télécommunications
90 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Capacité mutuelle câble 2 paires nF/km 80Capacité mutuelle 4 paires et au-dessus de câble nF/km 70
Tension de fonctionnement V 60
Propriétés mécaniques et thermiques
Rayon de cintrage: 8×OD (lors de l’installation); 6×OD (fixes installés) Plage de température: -10℃ ~ +60℃
Dimensions et poids
Construction de no des éléments × non. des carottes en élément ×
Diamètre du noyau(mm)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gaine
mm
Diamètre nominal globalmm
Poids nominalkg/km
1×2×0.5 0.2 1.2 5.0 302×2×0.5 0.2 1.2 5.5 354×2×0.5 0.2 1.2 7.0 55
10×2×0.5 0.2 1.5 8.5 9020×2×0.5 0.2 1.5 11.0 14830×2×0.5 0.2 1.5 13.5 21050×2×0.5 0.2 1.5 16.0 320
Copyright@ Caledonian Câbles Offshore & Marine
Câbles De Télécommunications
91ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
S10 IYOI(c) 60 V
Applications
Ces câbles sont retardateur de flamme, faible dégagement de fumée et sans halogène, utilisé pour les télécommunications à l'intérieur.
Normes
IEC 60092-359 IEC 60332-1 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: Solide cuivre étamé, 0.5mm. Isolation: PE composé thermoplastique sans halogène. Jumelage : Noyaux Couleur codés tordus ensemble.Les couples sont croix-brin au
câble fini ou 10 unités de paire.Les unités sont bloqués à 20 ans - 30 - 50 câbles à paires.2 paire est bloqué comme un quad étoiles.
Emballage:Ruban de polyester. Collectives Blindage: L’âme du câble est projeté par le cuivre soutenu ruban
polyester en contact avec un fil de 0,5 mm de vidange étamé solide. Literie: Composé thermoplastique sans halogène, le type SHF1, de couleur grise. Armour: Fil De Cuivre Ètamé Gaine extérieure: Composé thermoplastique sans halogène, le type SHF1, de couleur
grise.
Caractéristiques électriques
Chef d’orchestre Diamètre nominal mm 0.5Maximum résistant@20℃ Ω/km 95
Ruban De Cuivre/Polyester+Fil De Drain
Isolation PE Gratuit HalogèneRuban D'emballage
SHF1 Gaine
Conducteur De Cuivre Massif
SHF1 Gaine
Fil De Cuivre Ètamé
Copyright@ Caledonian Câbles Offshore & Marine
Câbles De Télécommunications
92 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Nominal Inductance@1KHz MH/km 0.61Capacité mutuelle câble 1 paire nF/km 90Capacité mutuelle câble 2 paires nF/km 80Capacité mutuelle 4 paires et au-dessus de câble nF/km 70
Tension de fonctionnement V 60
Propriétés mécaniques et thermiques
Rayon de cintrage: 8×OD (lors de l’installation); 6×OD (fixes installés) Plage de température: -10℃ ~ +60℃
Dimensions et poids
Construction de no des éléments × non. des carottes en élément ×
Diamètre du noyau(mm)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal global
mm
Poids nominalkg/km
Intérieure Extérieur1×2×0.5 0.2 1.2 1.2 8.0 952×2×0.5 0.2 1.2 1.2 9.0 1104×2×0.5 0.2 1.2 1.2 10.0 14510×2×0.5 0.2 1.5 1.5 12.0 20020×2×0.5 0.2 1.5 1.5 15.0 33030×2×0.5 0.2 1.5 1.5 17.0 43050×2×0.5 0.2 1.5 1.5 20.0 580
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Fibre Optique
93ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
F1 QFCI
Applications
Ces acier câbles à fibres optiques blindées sont ignifuge, sans fumée, halogènes libres et résistant au feu, utilisé pour la communication et des systèmes d'urgence qui doivent être opérationnelles au cours de l'incendie.
Normes
IEC 60794 IEC 60811-2-1 IEC 60331-25 IEC 60332-3-24 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Élément De Fibre: En vrac conception du cœur du tube. Élément central de la force : Fil d’acier ou de fibre renforcée plastique (FRP). Literie: Halogène composé thermoplastique ignifuge libre et des flammes. Armour: Tresse en acier galvanisé. Gaine extérieure: Sans halogène et retardateur de flamme, composé thermoplastique
stabilisé aux UV, SHF1.
Facultatif
F4 QFCI-HCF: Câbles QFCI-HCF sont composent de lâche élément de fibre de tube, fil d'acier ou de PRF élément de la force centrale, halogène retardateur literie thermoplastique sans flamme et, du fil galvanisé tresse armure d'acier, SHF1 gaine, la protection HC-le-feu, la bande résistant au feu et SHF1 gaine extérieure.
Tresse De Fil D'acier Galvanisé Á
Fil D'acier/ FRP Élément De Force
Literie Sans Halogène
Élément De Fibre
SHF1 Gaine
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Fibre Optique
94 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Caractéristiques électriques
Type de fibre 9/125 50/125 50/125 62.5/125Type de ITU-T G652.D G651 G651 -IEC11801 Classement OS1 & OS2 OM2 OM3 OM1Diamètre du noyau μm 8.7±0.4 50±3.0 50±3.0 62.5±3.0Diamètre de la gaine μm 125 ± 1.0 125 ± 2.0 125 ± 2.0 125 ± 2.0Diamètre de revêtement μm 245 ± 10 245 ± 10 245 ± 10 245 ± 10Atténuation maximale
@850 nm dB/km - 3.0 3.0 3.5@1300 nm dB/km - 1.5 1.0 1.5@1310 nm dB/km 0.36 - - -@1550 nm dB/km 0.22 - - -
Bande passante minimum(OFL*)@850 nm MHz.km - 500 1500 200@1300 nm MHz.km - 500 500 600
Maximum de Dispersion chromatique1285-1330 nm ps/nm⋅km 2.8 - - -1550 nm ps/nm⋅km 18 - - -
Zéro longueur d’onde de Dispersion nm 1300~1324 - - -
Propriétés mécaniques et thermiques
Rayon de cintrage: 20×OD (lors de l’installation); 10×OD (fixes installés) Plage de température: -40℃ ~ +70℃
Dimensions et poids
No. de Fibres
Construction de no. des tubes×No. des fibres dans chaque
tube
Nombre de chargesNominale vrac Tube
Diamètremm
Diamètre nominal globalmm
Poids nominalkg/km
2 1×2 5 2.2 13.9 2444 1×4 5 2.2 13.9 2446 3×2 3 2.2 13.9 2448 2×4 4 2.2 13.9 24410 5×2 1 2.2 13.9 24412 3×4 3 2.2 13.9 24416 4×4 2 2.2 13.9 24420 5×4 1 2.2 13.9 24424 6×4 0 2.2 13.9 24432 4×8 2 2.2 13.9 24440 5×8 1 2.2 13.9 24448 6×8 0 2.2 13.9 244
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Fibre Optique
95ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
F5 QFCB
Applications
Ces acier câbles à fibres optiques blindées sont ignifuge, sans fumée, halogènes libres et résistant au feu, utilisé pour la communication et des systèmes d'urgence qui doivent être opérationnelles au cours de l'incendie.
Normes
IEC 60794 IEC 60811-2-1 IEC 60331-25 IEC 60332-3-24 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Élément De Fibre: En vrac conception du cœur du tube. Élément central de la force : Fil d’acier ou de fibre renforcée plastique (FRP). Literie: Halogène composé thermoplastique ignifuge libre et des flammes. Armour: Tresse en acier galvanisé. Gaine extérieure1: Sans halogène et retardateur de flamme, composé
thermoplastique stabilisé aux UV, SHF1. Gaine extérieure2: Résistant à la boue et halogène thermoplastique composé.
Caractéristiques électriques
Type de fibre 9/125 50/125 50/125 62.5/125Type de ITU-T G652.D G651 G651 -IEC11801 Classement OS1 & OS2 OM2 OM3 OM1
Diamètre du noyau μm 8.7±0.4 50±3.0 50±3.0 62.5±3.0
Tresse De Fil D'acier Galvanisé Á
Fil D'acier/ FRP Élément De ForceLiterie Sans Halogène
Élément De Fibre
SHF1 Gaine
Mud Résistant & Halogène Gaine Gratuit
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Fibre Optique
96 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Diamètre de la gaine μm 125 ± 1.0 125 ± 2.0 125 ± 2.0 125 ± 2.0Diamètre de revêtement μm 245 ± 10 245 ± 10 245 ± 10 245 ± 10Atténuation maximale
@850 nm dB/km - 3.0 3.0 3.5@1300 nm dB/km - 1.5 1.0 1.5@1310 nm dB/km 0.36 - - -@1550 nm dB/km 0.22 - - -
Bande passante minimum(OFL*)@850 nm MHz.km - 500 1500 200@1300 nm MHz.km - 500 500 600
Maximum de Dispersion chromatique1285-1330 nm ps/nm⋅km 2.8 - - -1550 nm ps/nm⋅km 18 - - -
Zéro longueur d’onde de Dispersion nm 1300~1324 - - -
Propriétés mécaniques et thermiques
Rayon de cintrage: 20×OD (lors de l’installation); 10×OD (fixes installés) Plage de température: -40℃ ~ +70℃
Dimensions et poids
No. de Fibres
Construction de no. des tubes×No. des fibres dans chaque
tube
Nombre de chargesNominale vrac Tube
Diamètremm
Diamètre nominal globalmm
Poids nominalkg/km
2 1×2 5 2.2 15.0 2904 1×4 5 2.2 15.0 2906 3×2 3 2.2 15.0 2908 2×4 4 2.2 15.0 29010 5×2 1 2.2 15.0 29012 3×4 3 2.2 15.0 29016 4×4 2 2.2 15.0 29020 5×4 1 2.2 15.0 29024 6×4 0 2.2 15.0 29032 4×8 2 2.2 15.0 29040 5×8 1 2.2 15.0 29048 6×8 0 2.2 15.0 290
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Fibre Optique
97ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
F6 AICI
Applications
Ces câbles à fibres optiques sont résistantes au feu, retardateur de flamme, sans fumée et halogènes, utilisés pour les systèmes d'instrumentation, de données et de communication.
Normes
IEC 60794 IEC 60811-2-1 IEC 60331-25 IEC 60332-3-24 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Élément de fibre : Tamponnée serré fibres. Élément de Force centrale: plastique renforcé de fibres (PRF) et / ou des fils
d’aramide. Literie: Halogène composé thermoplastique ignifuge libre et des flammes. Armour: Tresse en acier galvanisé. Gaine extérieure: Sans halogène et retardateur de flamme, composé thermoplastique
stabilisé aux UV, SHF1.
Caractéristiques électriques
Type de fibre 9/125 50/125 50/125 62.5/125Type de ITU-T G652.D G651 G651 -IEC11801 Classement OS1 & OS2 OM2 OM3 OM1
Diamètre du noyau μm 8.7±0.4 50±3.0 50±3.0 62.5±3.0
Tresse De Fil D'acier Galvanisé Á
Aramide Fils
Literie Sans Halogène
Élément De Fibre
SHF1 Gaine
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Fibre Optique
98 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Diamètre de la gaine μm 125 ± 1.0 125 ± 2.0 125 ± 2.0 125 ± 2.0Diamètre de revêtement μm 245 ± 10 245 ± 10 245 ± 10 245 ± 10Atténuation maximale
@850 nm dB/km - 3.0 3.0 3.5@1300 nm dB/km - 1.5 1.0 1.5@1310 nm dB/km 0.36 - - -@1550 nm dB/km 0.22 - - -
Bande passante minimum(OFL*)@850 nm MHz.km - 500 1500 200@1300 nm MHz.km - 500 500 600
Maximum de Dispersion chromatique1285-1330 nm ps/nm⋅km 2.8 - - -1550 nm ps/nm⋅km 18 - - -
Zéro longueur d’onde de Dispersion nm 1300~1324 - - -
Propriétés mécaniques et thermiques
Rayon de cintrage: 20×OD (lors de l’installation); 10×OD (fixes installés) Plage de température: -40℃ ~ +70℃
Dimensions et poids
No. de FibresRevêtement secondaire
mmDiamètre nominal global
mmPoids nominal
kg/km
2 0.9 7.8 1004 0.9 8.2 1108 0.9 9.4 125
12 0.9 10.3 14524 0.9 12.0 185
Copyright@ Caledonian Câbles Offshore & Marine
Câbles De Données
99ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Cat5E UTP/FTP Blindé câble de données
Applications
Cat5E câble est un câble standard pour Gigabit Ethernet et d'autres protocoles de réseau, adapté aux voix et données de base des installations jusqu'à 100 MHz.En outre, ces câbles sont avec du fil de cuivre tresse boue ignifuge blindé et résistant à la flamme gaine extérieure, offrant une protection mécanique supplémentaire en conservant la flexibilité du câble.
Normes
IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: 24AWG cuivre nu solide. Isolation: HDPE. Jumelage: Deux conducteurs isolés torsadés ensemble de couleurs pour former une
paire. Literie: Polyoléfine ignifuge, peu de fumée et sans halogène, couleur noir. Armour: 0.2/0.3mm fil de cuivre tresse. Gaine extérieure: Faible dégagement de fumée et de polyoléfine sans halogène.
Facultatif
Cat5E F/UTP: Ces câbles ont un blindage collectif de ruban aluminium/Polyester avec fil de drain.
Cat5E SF/UTP: Ces câbles ont blindages doubles collectives de ruban aluminium / polyester et fil de cuivre tresse avec fil de drain.
Fil De Cuivre Ètamé
HDPE Isolation
FRLSZH Literie Polyoléfine
Conducteur De Cuivre Massif
LSZH Gaine Polyoléfine
Paire Torsadée
Copyright@ Caledonian Câbles Offshore & Marine
Câbles De Données
100 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Caractéristiques électriques
AWG 24Chef d’orchestre Diamètre nominal mm 0.53Resistant@20℃ DC maximale Ω/100m 9.38DCR maximale Déséquilibre % 5Capacité maximale mutuelle pF/m 55.8Déséquilibre de capacité maximale pF/100m 330Impédance caractéristique@1-100MHz Ω 100+/-15Maximum Délai de propagation d’obliquité ns/100m 45
FREQMHz
Atténuation maximaledB/100m
Minimale NEXT
dB
Minimale PSNEXT
dB
Minimale ELFEXTdB/100m
Minimale PSELFEXTdB/100m
Minimale RLdB
0.772 1.8 67.0 64.0 66.0 63.0 —1 2.0 65.3 62.3 63.8 60.8 20.04 4.1 56.3 53.3 51.7 48.7 23.08 5.8 51.8 48.8 45.7 42.7 24.510 6.5 50.3 47.3 43.8 40.8 25.016 8.2 47.3 44.3 39.7 36.7 25.020 9.3 45.8 42.8 37.7 34.7 25.025 10.4 44.3 41.3 35.8 32.8 24.3
31.25 11.7 42.9 39.9 33.9 30.9 23.662.5 17.0 38.4 35.4 27.8 24.8 21.5100 22.0 35.3 32.3 23.8 20.8 20.1
Propriétés mécaniques et thermiques
Rayon de cintrage: 8×OD (lors de l’installation); 4×OD (fixes installés) Plage de température: -30℃ ~ +75℃
Fil De Cuivre Ètamé
HDPE Isolation
FRLSZH Literie Polyoléfine
Conducteur De Cuivre Massif
LSZH Gaine Polyoléfine
Ruban De AL/Polyester+Fil De Drain
Copyright@ Caledonian Câbles Offshore & Marine
Câbles De Données
101ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Dimensions et poids
Travaux Nombre d' éléments×Nombre de noyaux dans l'élément×Diamètre du
conducteur(mm)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal global
mm
Poids nominalkg/km
Intérieure Extérieur
4×2×0.53 0.2 0.8 1.14 10.1 179
Copyright@ Caledonian Câbles Offshore & Marine
Câbles De Données
102 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Cat6 UTP/FTP Blindé câble de données
Applications
Câble CAT6 est un câble standard pour Gigabit Ethernet et l'autre protocole réseau utilisable pour 10BaseT, 100BaseTx & 1000BaseT (Gigabit Ethernet). En outre, ces câbles sont avec du fil de cuivre tresse blindée & ignifuge résistant à la boue gaine externe, fournissant supplémentaires mécaniquement protection en conservant la flexibilité du câble.
Normes
IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: 23AWG nu en cuivre massif. Isolation: HDPE. Jumelage: Deux conducteurs isolés torsadés ensemble de couleurs pour former une
paire. Literie: Polyoléfine ignifuge, peu de fumée et sans halogène, couleur noir. Armour: 0.2/0.3mm de fil de cuivre tresse. Gaine extérieure: Faible dégagement de fumée et de polyoléfine sans halogène.
Facultatif
Cat6 F/UTP: Ces câbles ont un blindage collectif de ruban aluminium/Polyester avec fil de drain.
Cat6 SF/UTP: Ces câbles ont blindages doubles collectives de ruban aluminium / polyester et fil de cuivre tresse avec fil de drain.
Fil De Cuivre Ètamé
HDPE IsolationFRLSZH Literie Polyoléfine
Conducteur De Cuivre MassifLSZH Gaine Polyoléfine
Paire Torsadée
Copyright@ Caledonian Câbles Offshore & Marine
Câbles De Données
103ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Caractéristiques électriques
AWG 23Chef d’orchestre Diamètre nominal mm 0.58Resistant@20℃ DC maximale Ω/100m 7.5DCR maximale Déséquilibre % 3Capacité maximale mutuelle pF/m 5.6Déséquilibre de capacité maximale pF/100m 330Impédance caractéristique@1-100MHz Ω 100+/-15Maximum Délai de propagation d’obliquité ns/100m 18
FREQMHz
Atténuation maximaledB/100m
Minimale NEXT
dB
Minimale PSNEXT
dB
Minimale ELFEXTdB/100m
Minimale PSELFEXTdB/100m
Minimale RLdB
0.772 1.8 76.0 74.0 70.0 67.0 —1 2.0 74.3 72.3 67.8 64.8 20.04 3.8 65.3 63.3 55.7 52.7 23.08 5.3 60.8 58.8 49.7 46.7 24.5
10 6.0 59.3 57.3 47.8 44.8 25.016 7.6 56.3 54.3 43.7 40.7 25.020 8.5 54.8 52.8 41.7 38.7 25.025 9.5 53.3 51.3 39.8 36.8 24.3
31.25 10.7 51.9 49.9 37.9 34.9 23.662.5 15.4 47.4 45.4 31.8 28.8 21.5100 19.8 44.3 42.3 27.8 24.8 20.1155 25.2 41.5 39.5 23.9 20.9 18.8200 29.0 39.8 37.8 21.7 18.7 18.0250 32.8 38.3 36.3 19.8 16.8 17.3
Fil De Cuivre Ètamé
HDPE Isolation
FRLSZH Literie Polyoléfine
Conducteur De Cuivre Massif
LSZH Gaine Polyoléfine
Ruban De AL/Polyester+Fil De Drain
Copyright@ Caledonian Câbles Offshore & Marine
Câbles De Données
104 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Propriétés mécaniques et thermiques
Rayon de cintrage: 8×OD (lors de l’installation); 4×OD (fixes installés) Plage de température: -30℃ ~ +75℃
Dimensions et poids
Travaux Nombre d' éléments×Nombre de noyaux dans l'élément×Diamètre du
conducteur(mm)
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal global
mm
Poids nominalkg/km
Intérieure Extérieur
4×2×0.58 0.23 0.8 1.14 11.6 214
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Coaxiaux
105ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
RG6 Câble Coaxial Blindé
Applications
Ces câbles coaxiaux 75Ω conviennent à l'installation à bord des navires et des autres milieux marins à l'intérieur.
Normes
IEC 60092-350 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: 18AWG cuivre nu solide. Isolation: Mousse PE. Blindage1: Al/Polyester/Al bande. Blindage2: Tresse en cuivre étamé. Literie: Faible dégagement de fumée et de polyoléfine sans halogène, de couleur
noire. Armour: Fil De Cuivre Ètamé. Gaine extérieure: Faible dégagement de fumée et de polyoléfine sans halogène.
Caractéristiques électriques
AWG 18Chef d’orchestre Diamètre nominal mm 1.0Impédance Ω 75+/-5 Atténuation nominale@100MHz dB/100m 6.9Atténuation nominale@200MHz dB/100m 9.0Atténuation nominale@300MHz dB/100m 11.8Atténuation nominale@400MHz dB/100m 13.1
Fil De Cuivre ÉtaméMousse PE Isolation
Tresse En Cuivre ÉtaméConducteur De Cuivre Massif
LSZH Gaine Polyoléfine
Al/Polyester/Al BandeLSZH Literie Polyoléfine
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Coaxiaux
106 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Atténuation nominale@500MHz dB/100m 15.4Atténuation nominale@900MHz dB/100m 21.5Atténuation nominale@1700MHz dB/100m 29.4Capacitance pF/m 53.5Vitesse de propagation % 83Chef d’orchestre DCR Ω/km 21.4Bouclier DCR Ω/km 7.5Inductance μH/m 0.32Temps de retard ns/m 4
Propriétés mécaniques et thermiques
Rayon de cintrage: 15×OD Plage de température: -30℃ ~ +75℃
Dimensions et poids
Nominaux intérieure Diamètre du conducteur
mm
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
1.0 1.8 1.2 11.2 208
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Coaxiaux
107ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
RG11 Câble Coaxial Blindé
Applications
Ces câbles coaxiaux 75Ω conviennent à l'installation à bord des navires et des autres milieux marins à l'intérieur.
Normes
IEC 60092-350 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: 14AWG cuivre nu solide. Isolation: Mousse PE. Blindage1: Al/Polyester/Al bande. Blindage2: Tresse en cuivre étamé. Literie: Faible dégagement de fumée et de polyoléfine sans halogène, de couleur
noire. Armour: Fil De Cuivre Ètamé. Gaine extérieure: Faible dégagement de fumée et de polyoléfine sans halogène.
Caractéristiques électriques
AWG 14Chef d’orchestre Diamètre nominal mm 1.6Impédance Ω 75+/-5 Atténuation nominale@100MHz dB/100m 4.5Atténuation nominale@270MHz dB/100m 7.6Atténuation nominale@540MHz dB/100m 10.8Atténuation nominale@750MHz dB/100m 12.8
Fil De Cuivre ÉtaméMousse PE Isolation
Tresse En Cuivre ÉtaméConducteur De Cuivre Massif
LSZH Gaine Polyoléfine
Al/Polyester/Al BandeLSZH Literie Polyoléfine
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Coaxiaux
108 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Atténuation nominale@1000MHz dB/100m 14.8Capacitance pF/m 53.5Vitesse de propagation % 83Chef d’orchestre DCR Ω/km 8.5Bouclier DCR Ω/km 12.1Inductance μH/m 0.32Temps de retard ns/m 4
Propriétés mécaniques et thermiques
Rayon de cintrage: 15×OD Plage de température: -30℃ ~ +75℃
Dimensions et poids
Nominaux intérieure Diamètre du conducteur
mm
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
1.6 2.7 1.7 15.0 353
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Coaxiaux
109ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
RG59 Câble Coaxial Blindé
Applications
Ces câbles coaxiaux 75Ω conviennent à l'installation à bord des navires et des autres milieux marins à l'intérieur.
Normes
IEC 60092-350 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: 20AWG cuivre nu solide. Isolation: Mousse PE. Blindage1: Al/Polyester/Al bande. Blindage2: Tresse en cuivre étamé. Literie: Faible dégagement de fumée et de polyoléfine sans halogène, de couleur
noire. Armour: Fil De Cuivre Ètamé. Gaine extérieure: Faible dégagement de fumée et de polyoléfine sans halogène.
Caractéristiques électriques
AWG 20Chef d’orchestre Diamètre nominal mm 0.8Impédance Ω 75+/-5 Atténuation nominale@100MHz dB/100m 7.6Atténuation nominale@270MHz dB/100m 12.5Atténuation nominale@540MHz dB/100m 17.9Atténuation nominale@720MHz dB/100m 20.9
Fil De Cuivre ÉtaméMousse PE Isolation
Tresse En Cuivre ÉtaméConducteur De Cuivre Massif
LSZH Gaine Polyoléfine
Al/Polyester/Al BandeLSZH Literie Polyoléfine
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Coaxiaux
110 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Atténuation nominale@750MHz dB/100m 21.3Atténuation nominale@1000MHz dB/100m 24.9Capacitance pF/m 53.5Vitesse de propagation % 83Chef d’orchestre DCR Ω/km 32.8Bouclier DCR Ω/km 12.5Inductance μH/m 0.318Temps de retard ns/m 4.0
Propriétés mécaniques et thermiques
Rayon de cintrage: 15×OD Plage de température: -30℃ ~ +75℃
Dimensions et poids
Nominaux intérieure Diamètre du conducteur
mm
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
0.8 1.4 1.2 10.0 177
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Coaxiaux
111ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
RG58 Câble Coaxial Blindé
Applications
Ces câbles coaxiaux de 50Ω ne conviennent pas pour l'installation à bord des navires et autres environnements maritimes intérieurs.
Normes
IEC 60092-350 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: 21AWG cuivre étamé. Isolation: PE. Blindage: Tresse en cuivre étamé. Literie: Faible dégagement de fumée et de polyoléfine sans halogène, de couleur
noire. Armour: Fil De Cuivre Ètamé. Gaine extérieure: Faible dégagement de fumée et de polyoléfine sans halogène.
Caractéristiques électriques
AWG 21Chef d’orchestre construction No/diamètre des fils -/mm 19/0.18Chef d’orchestre Diamètre nominal mm 0.89Impédance Ω 50+/-3 Atténuation nominale@100MHz dB/100m 15.7Atténuation nominale@200MHz dB/100m 22.3Atténuation nominale@400MHz dB/100m 32.8Atténuation nominale@700MHz dB/100m 46.6Atténuation nominale@900MHz dB/100m 54.1
Fil De Cuivre Étamé
PE Isolation
Tresse En Cuivre Étamé
Conducteur En Cuivre Multibrins
LSZH Gaine Polyoléfine
LSZH Literie Polyoléfine
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Coaxiaux
112 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Atténuation nominale@1000MHz dB/100m 56.1Capacitance pF/m 101Vitesse de propagation % 66Chef d’orchestre DCR Ω/km 35.4Inductance μH/m 0.246Temps de retard ns/m 5.0
Propriétés mécaniques et thermiques
Rayon de cintrage: 15×OD Plage de température: -30℃ ~ +75℃
Dimensions et poids
Nominaux intérieure Diamètre du conducteur
mm
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
0.89 1.0 1.14 8.6 149
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Coaxiaux
113ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
RG213 Câble Coaxial Blindé
Applications
Ces câbles coaxiaux de 50Ω ne conviennent pas pour l'installation à bord des navires et autres environnements maritimes intérieurs.
Normes
IEC 60092-350 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
Conducteurs: 13AWG cuivre étamé. Isolation: PE. Blindage: Tresse en cuivre étamé. Literie: Faible dégagement de fumée et de polyoléfine sans halogène, de couleur
noire. Armour: Fil De Cuivre Ètamé. Gaine extérieure: Faible dégagement de fumée et de polyoléfine sans halogène.
Caractéristiques électriques
AWG 13Chef d’orchestre construction No/diamètre des fils -/mm 7/0.75Chef d’orchestre Diamètre nominal mm 2.24Impédance Ω 50+/-3 Atténuation nominale@100MHz dB/100m 7.5Atténuation nominale@200MHz dB/100m 10.5Atténuation nominale@400MHz dB/100m 15.1Atténuation nominale@1000MHz dB/100m 29.5Capacitance pF/m 101
Fil De Cuivre Étamé
PE Isolation
Tresse En Cuivre Étamé
Conducteur En Cuivre Multibrins
LSZH Gaine Polyoléfine
LSZH Literie Polyoléfine
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Coaxiaux
114 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Vitesse de propagation % 66Chef d’orchestre DCR Ω/km 5.7Bouclier DCR Ω/km 3.9Inductance μH/m 0.246Temps de retard ns/m 5.0
Propriétés mécaniques et thermiques
Rayon de cintrage: 15×OD Plage de température: -30℃ ~ +75℃
Dimensions et poids
Nominaux intérieure Diamètre du conducteur
mm
Épaisseur D'isolation Nominale
mm
Épaisseur nominale de gainemm
Diamètre nominal globalmm
Poids nominalkg/km
2.24 2.2 1.14 13.9 379
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Coaxiaux
115ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Câble Composite résistant à la boue
Applications
Ces câbles composites sont constitués de câble de données et cat6 câble de câble coaxial et alimentation, avec résistant à fil de cuivre tresse blindée et la flamme du pétrole et de boue retardateur gaine extérieure.
Normes
IEC 60092-359 IEC 60332-3-22 IEC 60754-1,2 IEC 61034-1,2 NEK 606:2004
Construction
1) 4×2×0.57mm U/UTP Cat6 Câble de données: Conducteurs: Fil de cuivre nu solide. Isolation: PE. Jumelage: Deux couleurs fils isolés torsadés pour former une paire. Gaine: LSZH ignifuge, de couleur grise
2) RG59 Câble coaxial: Conducteurs: 0.58mm solide fil de cuivre nu. Isolation: PE. Blindage: Bare tresse de fils de cuivre. Gaine: LSZH ignifuge, de couleur grise
3) 3×1.0mm² Câble d'alimentation: Conducteurs: 7/0.44mm fil de cuivre nu brin. Isolation: XLPE. Coloré Bleu, Marron, vert / jaune. Gaine: LSZH ignifuge, de couleur grise
4) Assemblage de l'élément Remplisseur: PP, PVC, PE ou LSZH Matériel.
Fil De Cuivre Étamé
Polyester RubanÉlément Câble Coaxial
Câble D'alimentation Élément
Flame Retardant LSZH Gaine
Élément De Données Par Câble
Flame Retardant LSZH Literie
Copyright@ Caledonian Câbles Offshore & Marine
Câbles Coaxiaux
116 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Emballage:Ruban de polyester. Literie: Retardateur de flamme LSZH. Armour: Fil de cuivre étamé tresse. Gaine extérieure: Résistant aux huiles et la boue, LSZH ignifuge, de couleur grise
Dimensions
Construction du câbleDiamètre nominal de
câble de données mm
Diamètre nominal de câble coaxial
mm
Diamètre nominal de câble d'alimentation
mm
Diamètre nominal globalmm
4×2×0.57mm + RG59 + 3×1.0mm² 6.0 6.2 6.8 21.0
Remarque: Autres construction peut être offert demande de opon.
Copyright@ Caledonian Câbles Offshore & Marine
Informations Techniques
117ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Cable Code DésignationUn code de câble de 2 lettres ( 1. et 4. ) ou 4 lettres est utilisé pour décrire la construction.Par exemple:
1ère lettre: Isolation :B: Bande résistant au feu + isolation (sans halogène)R: Caoutchouc d'éthylène-propylène - EPR T: Polyéthylène réticulé XLPE I: Composé thermoplastique (sans halogène) U: Composé thermodurcissable sans halogène EMA ou EVA A: Fibre, tampon serréeQ: Fibre dans tube en vrac
2ème lettre:Gaine interne:F: Literie/revêtement intérieur ou de l'enregistrement (sans halogène)Y: écran (évent. avec PE ou PP) I: Composé thermoplastique (sans halogène) SHF1
3ème lettre:Armour/écran :L: Aluminium (feuilleté à gaine extérieure)X: Aucune armour O: Fil de cuivre étamé (tinned ou nu ) A: Membre de la Force de fil C: Tresse en acier galvanisé
4ème lettre:Gaine extérieure:I: Composé thermoplastique (sans halogène) , SHF1 U: Composé thermodurcissable sans halogène, SHF2 U: La boue sans halogène composé thermodurcissable résistant, SHF Vase B*: La boue sans halogène composé thermoplastique résistant *QFCB uniquement des câbles
Abréviation supplémentaire pour les câbles d'instrumentation: (c): écran collective(i): paire individuelle ou triple écran
RFOU(i)
Copyright@ Caledonian Câbles Offshore & Marine
Informations Techniques
118 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Normes et Tests
NEK 606-2004 Câbles pour les installations offshore sans halogène et / ou résistant à la boue
IEC 60092-350 Installations électriques à bord des navires Partie 350: basse tension des câbles d'alimentation de bord
. (Construction générale et les exigences d'essai)IEC 60092-351 Installations électriques à bord des navires Partie 351: Matériaux isolants pour câbles électriques à
bord des naviresIEC 60092-352 Installations électriques à bord des navires Partie 352: Choix et l'installation de câbles électriques pour
les systèmes d'énergie basse tensionIEC 60092-353 Installations électriques à bord des navires Partie 353: Câbles simples et multicœurs à isolement
massif extrudé pour tensions assignées 0,6 / 1 et 1,8 / 3 KVIEC 60092-354 Partie 354: Câbles d'alimentation simples et trois
conducteurs avec isolation solide extrudé pour tensions assignées de 6 KV à 30 KV.
IEC 60092-359 Partie 359: Matériaux de revêtement pour l'alimentation à bord et les câbles de télécommunication
IEC 60092-375 Partie 375: Câbles d'instrumentation générale, contrôle et communication
IEC 60092-376 Partie 376: 150/250 V câbles de contrôle et d'instrumentation Circuits
IEC 60228 Des câbles isolésIEC 60331-11/12/21/25/31 Résistant au feu caractéristiques des câbles électriquesIEC 60332-1/3 Essais des câbles électriques sous condition d'incendie. Partie 1: Essais sur un conducteur ou câble isolé vertical. Partie 3: Essai sur des fils ou câbles en nappes.IEC 60446 Principes fondamentaux et de sécurité pour l'interface
homme-machine, marquage et l'identification. Identification des conducteurs par des couleurs ou des
caractères alphanumériquesIEC 60754-1/2 Essai sur les gaz émis lors de la combustion des câbles
électriques IEC 60811 Méthodes d'essais communes pour les matériaux isolants
et de gainage des câbles électriquesIEC 61034-1/2 Mesure de la densité de la fumée des câbles électriques
brûlant dans des conditions définies. Partie 1: Appareillage d’essai. Partie 2: Méthode d’essai et exigences
Copyright@ Caledonian Câbles Offshore & Marine
Informations Techniques
119ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Caractéristiques Du Câble
Mud Résistant
Les qualités des matériaux de revêtement pour utilisation dans les zones où les câbles sont exposés aux fluides de forage sont fortement dépendante du type de fluide présent. chaque type de liquide contient des additifs qui peuvent avoir un effet délétère sur le matériau de revêtement.
Selon NEK 606, les câbles résistants de boue ont une gaine de boue SHF qui sont conformes aux exigences de la CEI 60092-359 pour SHF2 et ci-dessous indiquée. Les câbles résistants de boue doivent être conçus avec des composés de revêtement appropriés pour l'installation et le fonctionnement en contact avec de la boue, sauf indication contraire.
Les exigences de test de résistance à la MUD pour les composés de gainage SHF Mud sont les suivantes:
Fluide d'essai Température Durée
Résistance à la traction &
Allongement à la rupture Variation
variation du volume d'houle
Poids augmenter la variation
Mineral type d'huile - IRM 903
100℃ 7 d 30% 30% 30%
Bromure de calcium saumure
(à base d'eau)70℃ 56 d 25% 20% 15%
Carbo mer (à base d'huile)
70℃ 56 d 25% 20% 15%
Résistance à l’huileTous les câbles gainés thermodurcissables doivent être adaptés à une installation de
production de pétrole. Les propriétés de résistance à l'huile doit être démontrée par un test selon IEC 60092-359 SHF2.
IgnifugationLes câbles doivent résister à l’épreuve dans la CEI 60332-3-10 spécifiée, -22, -23, -24,
-25. Fils simples, de la terre et de liaison doivent pouvoir résister à l’essai spécifié dans la norme CEI 60332-1 ou à la CEI 60332-2.
Résistance Au FeuCâbles de résistance au feu doivent être testés selon la norme IEC 60331-11, -12, -21, -25
et -31.
Copyright@ Caledonian Câbles Offshore & Marine
Informations Techniques
120 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Hydrocarbures (HCF) résistant au feu
L'acheteur doit spécifier laquelle des courbes ci-dessous dans la figure 1 ou 2 de se conformer à l'épreuve de la FHC.
Le test ne nécessite pas de ventilation pour les 30 ou 60 minutes lorsqu'il est connecté à la tension de fonctionnement. Temps à la dégradation à prendre en considération en accord avec l'autorité de la clientèle ou
Contenu de l’halogène
Tous les câbles doivent être sans halogène selon IEC 60754-1/2.
Émission de fumée
Au cours d’une émission de câble incendie de fumée doit être maintenu à une valeur minimale de 60% selon IEC 61034-1/2.
Fig.1 HC fire curve based on Exxon calcula�ons, which required func�onal security
for 15 minutes
Time in minutes exposed to fire
Fig.2 Interna�onal recognized HC fire curve.
Time in minutes exposed to fire
Tem
pera
ture
in d
eg.C
Tem
pera
ture
in d
eg.C
20
600
820
10001050 1083 1100 1100
20
743
880945
1033 1071 1098 1100
0 10 20 30 40 50 60
0 10 20 30 40 50 60
Copyright@ Caledonian Câbles Offshore & Marine
Informations Techniques
121ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Des données électriques
Résistance conducteur
Formule résistance:
[Ω]
p = résistance spécifique, Ω.mm²/mA = zone de conducteur, mm²L = conducteur longueur, m
Résistance en fonction de la température:
R0= résistance à=20℃t = température du conducteur ℃α= 0.00393 pour le cuivre
Notes de court-circuit
Les courants de court-circuit suivantes sont pour les câbles fonctionnent normalement à une température maximale du conducteur de 90°C.
La température théorique qui se pose dans le conducteur lors d'un court-circuit, qui est utilisée comme base du calcul, est 250℃. EPR et XLPE sont capables de résister à des températures de courte durée jusqu'à 250°C.
Les courants de court-circuit pour conducteurs en cuivre indiqués dans le tableau sont des valeurs pour une seconde, pour d'autres durées du courant peut être calculée à partir de la formule suivante:
It=courant de court-ciricut pour t sec.(Amp)l=courant de court-circuit pour un sec.(Amp)t=courte durée de circuit(sec.)La durée du court-circuit sur la base de ces hypothèses doit être comprise entre 0,2 sec.
et 5 sec.
Copyright@ Caledonian Câbles Offshore & Marine
Informations Techniques
122 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Zone de conducteur
mm²
Actuelles 1 seconde ampères
Zone de conducteur
mm²
Actuelles 1 seconde ampères
Zone de conducteur
mm²
Actuelles 1 seconde ampères
Zone de conducteur
mm²
Actuelles 1 seconde ampères
1.0 140 10 1400 70 9800 240 336001.5 210 16 2240 95 13300 300 420002.5 350 25 3500 120 16800 400 560004 560 35 4900 150 21000 500 700006 840 50 7000 185 25900 630 88200
Réactance
La réactance d'un câble dans un système d'exploitation alternatif dépend de nombreux facteurs, y compris, en particulier, l'espacement axial entre les conducteurs et la proximité et propriétés magnétiques de charpente métallique adjacente. Le premier est connu pour le câble multipaires, mais peut varier pour câbles unipolaires en fonction de la distance entre eux et leur disposition lors de l'installation.
Réactance de câbles à certaines dispositions de la charpente métallique est à distance calculable et est représenté. Les valeurs sont pour des câbles avec des conducteurs.
La valeur pour un conducteur en forme de secteur doit être pris comme 90% de la valeur calculée. Induction de 2-, 3- et 4- câbles conducteurs est donnée par la formule:
[H/m]a = L'espace axial entre les conducteurs en mm.d = Diamètre du conducteur en mm.Réactance de câbles 2-, 3- et 4-conducteurs est donnée par la formule:
[Ω]f = en fréquence HzL = en Induction H/m I = Longueur de câble en m
Impédance
Induction de 2-, 3- et 4- câbles conducteurs est donnée par la formule:
[Ω]R = Résistance au fonctionnement Temperature dans ΩX = Réactance en Ω
Copyright@ Caledonian Câbles Offshore & Marine
Informations Techniques
123ADDISONwww.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Identification de base L'identification des conducteurs isolés (noyaux) pour les câbles 250 V
Élément câble Couleur de noyauxPaire Noir Bleu clairTripler Noir Bleu clair Marron
Paires/triples sont numérotés avec du ruban numéroté ou par des numéros imprimés directement sur les conducteurs isolés
L'identification des conducteurs isolés (noyaux) pour les câbles de 0,6 / 1 kV selon la norme NEK
Nombre de conducteur Couleur de noyauxUnipolaire Off-blanc (gris)
Deux noyaux Off-blanc (gris) NoirTrois noyaux Off-blanc (gris) Noir RougeQuatre cœurs Off-blanc (gris) Noir Rouge Bleu
Dessus de 4 cœurs chiffres noirs sur base blancheconducteur de terre Jaune/vert
L'identification des conducteurs isolés (noyaux) pour les câbles de 0,6 / 1 kV selon la norme HD 308 S2
Câbles avec une âme vert / jauneNombre de conducteur Couleur de noyaux*
Trois noyaux Vert/jaune Bleu MarronQuatre cœurs** Vert/jaune - Marron Noir GrisQuatre cœurs Vert/jaune Bleu Marron NoirCinq noyaux Vert/jaune Bleu Marron Noir Gris
** Pour certaines applications seulement.* Dans ce tableau, un conducteur concentrique non isolée, comme une gaine métallique, armures ou écran fils, est pas considéré comme un noyau. Un conducteur concentrique est identifié par sa position et, par conséquent, ne doivent pas être identifiés par la couleur.
Câbles sans noyau vert / jauneNombre de conducteur Couleur de noyaux*
Deux noyaux Bleu MarronTrois noyaux** - Marron Noir GrisTrois noyaux Bleu Marron NoirQuatre cœurs Bleu Marron Noir GrisCinq noyaux Bleu Marron Noir Gris Noir
** Pour certaines applications seulement.* Dans ce tableau, un conducteur concentrique non isolée, comme une gaine métallique, armures ou écran fils, est pas considéré comme un noyau. Un conducteur concentrique est identifié par sa position et, par conséquent, ne doivent pas être identifiés par la couleur.
L'identification des conducteurs isolés (noyaux) pour le 3,6 / 6 kV, 6 / 10kV, 8,7 / 15 kV, 12 / 20kV et 18 câbles / de 30 kV
Nombre de conducteur Couleur de noyauxUnipolaire blanc cassé isolation + noir semi couches conductrices
Trois noyauxOff-blanc isolation + noir semi couches conductrices identifiées par des fils blanc-noir-rouge
sous et plus l'écran métallique sur chaque noyau individuel.conducteur de terre Jaune/vert
Copyright@ Caledonian Câbles Offshore & Marine
Pouvoir et de contrôle Câbles
124 ADDISON www.caledonian-cables.fr
NEK606 Caledonian Câbles Offshore & Marine
www.caledonian-cables.co.uk
Caledonian Câbles Offshore & Marine
NORME NEK606
www.caledonian-cables.co.ukwww.caledonian-cables.fr
Caledonian
ROYAUME-UNI
Marchants Centre industriel,Mill Lane, Laughton, Lewes,East Sussex, BN8 6AJ, UKTel: 44 (0) 207 419 5087Fax: 44 (0) 207 831 9489Email: [email protected]
HONG KONG
Unité B 22 / F CMA bâtiment,64-66 Connaught Road Central, Hong KongTel: 852 36527508Fax: 852 35834834Email: [email protected]
Copyright@ Caledonian Câbles Offshore & Marine