carrier advantage automatic standby generators product catalog product cat.pdf · 2016. 5. 26. ·...

2
A member of the United Technologies Corporation family. Stock Symbol UTX. © Carrier Corporation 2009 01-08AS-PA36-25 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice or without incurring obligations. www.carrier.com 1-800-CARRIER Automatic Standby Generators Product Catalog New Revolutionary Designs Willis Carrier invented air conditioning in 1902. Over 100 years later, we’re proud to say Carrier systems are trusted in more homes than any other brand. Carrier continues to be on the forefront of innovative engineering and unsurpassed standards of excellence. So when choosing a home comfort system, you’ll want to turn to the experts. Your Carrier dealer will evaluate your home, such as window placement and size, ductwork, other structural specifics and lifestyle to provide a customized indoor comfort plan designed specifically for you. And when you have an expert helping you make an educated decision, you’re going to feel more comfortable. Turn to the Experts Are You Prepared to Handle a Power Outage? Most people are not. Don’t take your power for granted, be prepared with a Carrier automatic standby generator. Carrier automatic standby generators take the worry out of power outages. Carrier provides peace of mind for home and business owners. No one else in the industry can compare. Whether you’re at home or away, your Carrier standby generator is ready to assume control of your electrical needs when a power outage occurs. Within sec- onds, back-up electricity is provided to your home or business, restoring essential items such as lights, climate control, refrigeration, etc. Unlike a portable generator, you don’t have to go outside, run a maze of extension cords or bother with gasoline, because an automatic standby generator operates on your LP or natural gas supply. Plus, when utility power returns, the generator automatically shuts down and waits for the next outage. Owning a Carrier standby generator has never been more convenient or afford- able. Contact your local Carrier Dealer for pricing information. How It Works Once your standby generator has been installed outside of your home or business, the automatic transfer switch is installed next to your main distribution panel. With an air-cooled system, you identify the circuits you want to protect, then you match those circuits on your distribution panel to the transfer switch’s load center. Larger generators may protect all circuits with an appropriate transfer switch. The system provides monitoring of incoming voltage from the utility line around the clock. When utility power is interrupted, the transfer switch senses the problem and signals for the generator to start. The automatic transfer switch will then safely close off the utility line and open a new power line from the generator. Within seconds, your home standby system will supply electricity to your pre-selected circuits. When utility line voltage returns, the transfer switch will re-transfer the electrical load back to the utility source and resume monitoring for subsequent utility loss. Carrier Advantage Keep heating, air conditioning, sump pumps, refrigerators and water heaters operating Keep lines of com- munication open (telephone, televi- sion and Internet) Keep lights, security systems and cash registers running Peace of Mind

Upload: others

Post on 18-Sep-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Carrier Advantage Automatic Standby Generators Product Catalog PRODUCT CAT.pdf · 2016. 5. 26. · Rated Power LPG/NG kW 20 25 35 45 60 70 80 100 100 130 150 Rated Amps @ 60Hz 120/240V,

A member of the United Technologies Corporation family.

Stock Symbol UTX.

© Carrier Corporation 2009 01-08AS-PA36-25

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs withoutnotice or without incurring obligations.

www.carrier.com 1-800-CARRIER

Automatic Standby Generators

Product Catalog

New Revolutionary Designs

Willis Carrier invented air conditioning in 1902. Over 100 years later, we’re proud to say Carrier systems are trusted in more

homes than any other brand.

Carrier continues to be on the forefront of innovative engineering and unsurpassed standards of excellence. So when

choosing a home comfort system, you’ll want to turn to the experts. Your Carrier dealer will evaluate your home, such as

window placement and size, ductwork, other structural specifics and lifestyle to provide a customized indoor comfort plan

designed specifically for you. And when you have an expert helping you make an educated decision, you’re going to feel

more comfortable.

Turn to the Experts

Are You Prepared to Handle a Power Outage?

Most people are not.

Don’t take your power for granted, be prepared with a Carrier automatic standby

generator.

Carrier automatic standby generators take the worry out of power outages.

Carrier provides peace of mind for home and business owners. No one else in

the industry can compare.

Whether you’re at home or away, your Carrier standby generator is ready to

assume control of your electrical needs when a power outage occurs. Within sec-

onds, back-up electricity is provided to your home or business, restoring essential

items such as lights, climate control, refrigeration, etc.

Unlike a portable generator, you don’t have to go outside, run a maze of extension

cords or bother with gasoline, because an automatic standby generator operates

on your LP or natural gas supply. Plus, when utility power returns, the generator

automatically shuts down and waits for the next outage.

Owning a Carrier standby generator has never been more convenient or afford-

able. Contact your local Carrier Dealer for pricing information.

How It Works

Once your standby generator has been installed outside of your home or business,

the automatic transfer switch is installed next to your main distribution panel.

With an air-cooled system, you identify the circuits you want to protect, then you

match those circuits on your distribution panel to the transfer switch’s load center.

Larger generators may protect all circuits with an appropriate transfer switch.

● The system provides monitoring of

incoming voltage from the utility line

around the clock.

● When utility power is interrupted, the

transfer switch senses the problem

and signals for the generator to

start.

● The automatic transfer switch will

then safely close off the utility line

and open a new power line from the

generator.

● Within seconds, your home standby

system will supply electricity to your

pre-selected circuits. When utility

line voltage returns, the transfer

switch will re-transfer the electrical

load back to the utility source and

resume monitoring for subsequent

utility loss.

Carrier Advantage

● Keep heating, air

conditioning, sump

pumps, refrigerators

and water heaters

operating

● Keep lines of com-

munication open

(telephone, televi-

sion and Internet)

● Keep lights, security

systems and cash

registers running

Peace of Mind

Page 2: Carrier Advantage Automatic Standby Generators Product Catalog PRODUCT CAT.pdf · 2016. 5. 26. · Rated Power LPG/NG kW 20 25 35 45 60 70 80 100 100 130 150 Rated Amps @ 60Hz 120/240V,

Rated Power LPG/NG kW 20 25 35 45 60 70 80 100 100 130 150Rated Amps @ 60Hz 120/240V, 1ø, 1.0pf N/A N/A N/A N/A 250 292 333 417 417 542 625120/208V, 3ø, 0.8pf 70 87 122 156 208 243 278 347 347 452 521277/480V, 3ø, 0.8pf N/A N/A 53 68 90 105 120 151 151 196 226Engine/Alternator RPM 3600/3600 3600/3600 3600/3600 3600/3600 3600/3600 1800/1800 3600/3600 3600/3600 2300/1800 3000/1800 3600/3600Engine 1.5L 1.6L 2.4L 2.4L 3.0L 6.8L 4.6L 5.4L 6.8L 6.8L 6.8LFuel ConsumptionLiquid propane cu. ft/hr (gal/hr) 125 (3.44) 183 (5.0) 222.3 (6.1) 286 (7.86) 376.3 (10.34) 411 (11.3) 442 (12.1) 553 (15.2) 507 (13.80) 719 (19.8) 830 (22.8)Natural gas cu. ft/hr 315 442 560 720 960 1020 1100 1374 1260 1786 2061Dimensions (L”xW”XH”)* 71x29.5x36 71x29.5x36 77x34x45 77x34x45 89x34x48* 116x37x55 116x37x55* 116x37x55* 116x37x55* 116x37x55* 116x37x55*Generator Weight (lbs.) Steel 1020 1025 1393 1414 1650 2185 2010 2311 2705 2873 2666

Aluminum 930 935 1276 1297 1513 2040 1836 2137 2531 2699 2492Required Transfer Switch RTS 100-200 RTS 100-200 RTS 100-200 RTS 100-200 RTS 100-200 HTS 150-400 HTS 150-400 HTS 200-600 HTS 200-600 HTS 200-600 HTS 300-800

*Height does not include measurement of exhaust stack.

Air-Cooled

Residential / 8, 10, 14 and 16 circuits

7-17kW

Pre-packaged system includes: 100 Amp automatic transfer

switch with load center, outdoor connection box, pre-wired

harness in conduit, flexible fuel line, composite mounting pad

and installation guide.

Sizing a Generator

When choosing the right generator, you must first decide how

many circuits or rooms in your home or small business you

should protect. The more circuits that require protection, the

larger the generator you need.

The automatic transfer switch in pre-packaged, air-cooled

systems allows you to match the system’s load center circuits

to the amperage in your home’s main distribution panel. (See

Fig. A). Simply determine which circuits to protect during an

outage and choose a generator.

For whole-house protection, Carrier’s liquid-cooled

residential / light commercial models range from 22-48kW.

To get accurate sizing requirements of a liquid-cooled gener-

ator, a licensed electrician will need to apply an amp meter to

the circuits and appliances that are intended to operate on

backup power.

Carrier air-cooled standby generators are designed to supply electricity to pre-selected circuits that supply a home’s

essential items in the event of a utility power outage. The pre-wired, pre-packaged system makes installation easy

and affordable.

● Breakthrough Design: Generates high starting power

to run the items that matter most.

● Circuit Coverage: Protects 16, 14, 10 or 8 circuits of

your home (17, 14, 10 and 8kW models respectively.)

● Industrial Engine: The longest life design and most

horsepower in its class.

● Superior Paint: Tough textured paint finish for

unmatched durability.

● Enclosure: Durable steel construction.

● Safe Design: UL listed / automatic voltage regulation

for sensitive electronics.

● Continuous Fuel: Models run on natural gas or liquid

propane gas.

● Ultra Quiet Mode (17kW only): Patent-pending self-test

feature allows the generator to exercise at reduced

rpm, decreasing sound output significantly.

Liquid-Cooled

Larger Residential / Light Commercial

22-48kW

Broadest line of generators on the market.

Higher wattage requirements need larger generators. This line of

standby generators is built for larger homes and small business.

Featuring automotive style, liquid-cooled engines and the exclusive

Ultra Quiet Mode feature, their greater power output and quiet

design makes for more complete and peaceful coverage during

an electrical outage.

● High Output: Liquid-cooled engine based models

produce more electricity for greater needs.

● Ultra Quiet Mode: Patent-pending self-test feature

allows the generator to exercise at reduced rpm,

decreasing sound output significantly.

● Enclosure Options: Steel or corrosion-resistant

aluminum enclosure for coastal communities.

● Superior Paint: Tough textured paint finish for

unmatched durability.

● Safe Design: UL listed / automatic voltage regulation

and electronic governor for sensitive electronics.

● Continuous Fuel: Models run on natural gas or liquid

propane gas.

● Transfer Switches: See transfer switch section for

selection of 100 and 200 Amp, single-phase switch

gear.

17-20kW

The system includes: composite mounting pad and installation guide.

Breakthrough Design

The exclusive Ultra Quiet Mode feature allows the generator to

exercise at reduced rpm, decreasing sound output significantly.

● Breakthrough Design: Generates high starting power

to run the items that matter most.

● Ultra Quiet Mode: Patent-pending self-test feature

allows the generator to exercise at reduced rpm,

decreasing sound output significantly.

● Industrial Engine: The longest life design and most

horsepower in its class.

● Enclosure: Corrosion-resistant aluminum enclosure.

● Application Flexibility: Gives the option of complete

back-up or load management system.

● Superior Paint: Tough textured paint finish for

unmatched durability.

● Safe Design: UL listed / automatic voltage regulation

and electronic governor for sensitive electronics.

● Continuous Fuel: Models run on natural gas or liquid

propane gas.

● Transfer Switches: See transfer switch section for

selection of 100 and 200 Amp, single-phase

switch gear.

Bedroom

Bedroom

Family Room

Deck

Kitchen

Garage

Bath

Master

Bedroom

Dining

Room

Utility

Room

Walk-In

Closet

Master

Bath

Circuit

Bath

A/C Unit Circuit

(up to 5 ton)

Furnace

Water Heater

Sump Pump

Home Office

(in basement)

Commercial Series

Commercial / Light Industrial

20-150kW

Continuous standby power for every application.

Carrier commercial series standby generators offer

restaurants, gas stations, offices and other businesses

maximum blackout protection for minimal investment.

Models range in output from 20 to 150kW and offer a

choice of voltage outputs with higher amperage

transfer switches. Transfer switches sold separately.

See required transfer switches in the chart below.

● Ultra Quiet Mode: Patent-pending self-test feature

allows the generator to exercise at reduced rpm,

decreasing sound output significantly.

● Superior Paint: Tough textured paint finish for

unmatched durability.

● Safe Design: UL listed / automatic voltage regula-

tion and electronic governor for sensitive elec-

tronics.

● Continuous Fuel: Models run on natural gas or

liquid propane gas.

Transfer Switches

100-200 AMP (Single-phase)

● No service disconnect

● Installations with sub panel

● Custom installations

● Aluminum enclosure

100-200 AMP (Single-phase)

● With service disconnect

● Service entrance rated

● Economical installation

● Aluminum enclosure

For Carrier commercial models.

100-400 AMP - Designed for applications

requiring up to 400 Amps.

HTS 200-800 AMP - Designed for simple

monitoring, operation and maintenance.

Removable and adjustable components

for serviceability.

20-25kW

35-45kW

60kW

80-150kW

KGAT

KGALT

HTS-N

70kW

Figure B is an example of the circuits that can be protected

with a 16kW (16 circuits) pre-packaged air-cooled generator.

Note: Rooms and appliances are shown as example only. You may choose other items that

better fit your needs. Due to the cycling nature of some appliances, all items may not be able

to run simultaneously.

* A 240V 2-pole circuit breaker is equal to two circuits.

Model Amps Volts EnclosureHTS-N-150K 150 277/480V 3ø NEMA 1 or 3R HTS-N-200K 200 277/480V 3ø NEMA 1 or 3RHTS-N-300A 300 120/240V 1ø NEMA 1 or 3RHTS-E-300G 300 120/208V 3ø NEMA 1 or 3RHTS-N-300K 300 277/480V 3ø NEMA 1 or 3RHTS-N-400A 400 120/240V 1ø NEMA 1 or 3RHTS-N-400G 400 120/208V 3ø NEMA 1 or 3RHTS-N-400K 400 277/480V 3ø NEMA 1 or 3RHTS-N-600A 600 120/240V 1ø NEMA 12 or 3RHTS-N-600G 600 120/208V 3ø NEMA 12 or 3RHTS-N-600K 600 277/480V 3ø NEMA 12 or 3RHTS-N-800A 800 120/240V 1ø NEMA 12 or 3RHTS-N-800G 800 120/208V 3ø NEMA 12 or 3RHTS-N-800K 800 277/480V 3ø NEMA 12 or 3R

ModelsTypical Loads Circuits 8kW 10kW 14kW 17kWA/C (4-ton) (40 Amp/240V)* •A/C (3-ton or smaller) (30 Amp/240V)* • •Well Pump or Water Heater (20 Amp/120V) • • • •Family Room (20 Amp/120V) • • • •Master Bedroom (20 Amp/120V) • • •Home Office (20 Amp/120V) • •Garage (20 Amp/120V) • • •Kitchen (#1) (20Amp/120V) • •Kitchen (#2) (15 Amp/120V) • • •Bathroom (15 Amp/120V) • • • •Furnace (15 Amp/120V) • • • •Sump Pump (15 Amp/120V) • • • •Bedrooms (15 Amp/120V) • • • •

Number of Circuits Covered 8 10 14 16

Figure A

Model Amps Volts Enclosure Service DisconnectKGATD0401100 100 120/240V NEMA 3R YesKGATX0201100 100 120/240V NEMA 3R NoKGATD0401200 200 120/240V NEMA 3R YesKGATX0201200 200 120/240V NEMA 3R NoKGATX0101400 400 120/240V NEMA 3R NoKGALT0101200 200* 120/240V NEMA 3R Yes

Model ASPDS1XXA008 ASPDS1XXA010 ASPDS1XXA014 ASPDS1XXA017 ASPDY1XXA017 ASPDY1XXA020 ASPFY1XXL022 ASPFX1XXL025 ASPFY1XXL027 ASPFX1XXL030 ASPFY1XXL036 ASPFX1XXL045 ASPFY1XXL048

Rated Power (LPG/NG) kW 8/7 10/9 14/13 17/16 17/16 20/18 22/22 25/24 27/25 30/29 35/35 45/43 45/42Voltage (single-phase) 120/240V 120/240V 120/240V 120/240V 120/240V 120/240V 120/240V 120/240V 120/240V 120/240V 120/240V 120/240V 120/240VAmps @ 120/240V LPG 66.6/33.3 83.3/41.6 116.6/58.3 141.6/70.8 141.6/70.8 166.6/83.3 184/92 208.3/104.2 224/112 250/125 291.6/145.8 375/187.5 375/187.5Amps @ 120/240V NG 58.3/29.2 75/37.5 108.3/54.2 133.3/66.6 133.3/66.6 150.0/75.0 184/92 208.3/104.2 224/112 241.6/120.8 291.6/145.8 358.3/179.2 358.3/179.2Engine/Alternator RPM 3600/3600 3600/3600 3600/3600 3600/3600 3600/3600 3600/3600 1800/1800 3600/3600 1800/1800 3600/3600 1800/1800 3600/3600 1800/1800Engine OHVI/410cc OHVI/530cc OHVI/992cc OHVI/992cc OHVI/992cc OHVI/999cc In-line 4 cyl. In-line 4 cyl. In-line 4 cyl. In-line 4 cyl. V-6 In-line 4 cyl. V-6 Fuel Consumption @ full loadLiquid Propane cu. ft/hr (gal/hr) 54 (1.47) 70 (1.93) 80 (2.18) 92 (2.51) 92 (2.51) 103.5 (2.85) 120 (3.3) 175 (4.8) 147 (4.1) 209 (5.7) 185 (5.1) 286 (7.86) 240 (6.6)Natural Gas cu. ft/hr 119 156 220 245 245 262 316 437 359 525 485 720 630Ultra Quiet Mode No No No Yes Yes Yes N/A Yes Yes Yes Yes Yes YesAutomatic Transfer Switch 100 Amp 100 Amp 100 Amp 100 Amp N/A N/A N/A 200ALT N/A N/A N/A N/A N/ACircuits Protected 8 10 14 16 N/A N/A N/A N/A N/A N/A N/A N/A N/ADimensions (L”xW”xH”) 48x25x29 48x25x29 48x25x29 48x25x29 48x25x29 48x25x29 62x29x33.5 71x29.5x36 62x29x33.5 62x29x33.5 77x33.5x45 77x33.5x45 77x33.5x45Generator Weight (lbs.) 336 375 425.5 445 414 451 843 1025 891 935 1683 1414 1703Enclosure Steel Steel Steel Steel Aluminum Aluminum Aluminum Steel Aluminum Steel Aluminum Steel Aluminum

* 200A load management with 16 circuit load center.