    30RA/RH 005013

    Air cooled water chillers

    PRO-DIALOG Control

    Service interface

    SERVICE INTERFACE MANUAL

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    2/26

    2

    Contents:

    Ref. Q.ty Description

    1 Service interface 1 Flat cable extension 1 J4 connector 1 Service interface manual 1 Suit-case

    GENERAL LEGEND

    Each of the following drawings is replaced in the whole document by the

    corresponding explanation:

    Start/stop button

    Return key

    Down arrow

    Up arrow

    DELTA T. Example: temperature difference between entering

    and leaving heat exchanger temperatures

    Means character is flashing

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    3/263

    TABLE OF CONTENTS

    1 - SAFETY CONSIDERATIONS..................................................................................................................................................41.1 - General .................................................................................................................................................................................41.2 - Avoid electrocution .............................................................................................................................................................. 4

    2 - GENERAL DESCRIPTION ...................................................................................................................................................... 42.1 - Service interface ................................................................................................................................................................... 42.2 - Pro-Dialog ............................................................................................................................................................................42.2 - Abbreviations used ............................................................................................................................................................... 4

    3 - INTERFACE CONNECTION...................................................................................................................................................53.1 - Functions ON/OFF, cooling/heating and dual set-point .......................................................................................................5

    4 - SETTING UP PRO-DIALOG PLUS CONTROL ...................................................................................................................64.1 - Service interface general features ......................................................................................................................................... 64.2 - Unit start/stop control ........................................................................................................................................................... 7

    4.2.1 - Description ................................................................................................................................................................... 74.3 - Menus ...................................................................................................................................................................................7

    4.3.1 - Selecting a menu .......................................................................................................................................................... 74.3.2 - Selecting a menu item .................................................................................................................................................. 74.3.3 - Modifying the value of a parameter/access to a sub-menu..........................................................................................74.3.4 - Expand display.............................................................................................................................................................84.3.5 - Description of the Information menu......................................................................................................................... 114.3.6 - Description of the Temperatures menu...................................................................................................................... 124.3.7 - Description of the Pressures menu.............................................................................................................................124.3.8 - Description of the Setpoints menu.............................................................................................................................134.3.9 - Description of the Inputs menu.................................................................................................................................. 134.3.10 - Description of the Outputs/Tests menu ...................................................................................................................14

    4.3.10.1 - General ......................................................................................................................................................... 144.3.10.2 - Menu description ......................................................................................................................................... 144.3.10.3 - Manual tests ................................................................................................................................................. 144.3.10.4 - Automatic tests ............................................................................................................................................ 14

    4.3.11 - Description of the configuration menu ....................................................................................................................154.3.11.1 - General ......................................................................................................................................................... 154.3.11.2 - Password ...................................................................................................................................................... 154.3.11.3 - Description of the User 1 configuration sub-menu......................................................................................174.3.11.4 - Description of the User 2 configuration sub-menu......................................................................................17

    4.3.11.5 - Description of the Date and Time configuration sub-menu ........................................................................184.3.11.6 - Description of the Time Schedules sub-menus ...........................................................................................184.3.11.7 - Description of the Holidays sub-menus.......................................................................................................194.3.11.8 - Description of the Broadcast sub-menu.......................................................................................................19

    4.3.12 - Description of the Alarms menu ..............................................................................................................................204.3.13 - Description of the Alarms History menu .................................................................................................................204.3.14 - Runtime menu description ....................................................................................................................................... 20

    4.3.14.1 - Description of the Runtimes 1 menu ...........................................................................................................204.3.14.2 - Maintenance menu description ....................................................................................................................20

    5 - PRO-DIALOG PLUS CONTROL OPERATION ................................................................................................................. 215.1 - Heating/cooling operation .................................................................................................................................................. 22

    5.1.1 - General ....................................................................................................................................................................... 225.2 - Evaporator water pump control .......................................................................................................................................... 22

    5.3 - Evaporator heater control (option) ..................................................................................................................................... 225.4 - Control point....................................................................................................................................................................... 22

    5.4.1 - Active setpoint ........................................................................................................................................................... 225.4.2 - Reset........................................................................................................................................................................... 23

    5.5 - Demand limit ...................................................................................................................................................................... 235.6 - Night mode ......................................................................................................................................................................... 235.7 - Capacity control .................................................................................................................................................................. 235.8 - Head pressure control ......................................................................................................................................................... 235.9 - Defrost function .................................................................................................................................................................. 245.10 - Additional electric heater stage control ............................................................................................................................245.11 - Control of a boiler ............................................................................................................................................................ 245.12 - Controlling Pro-Dialog Plus units with a System Manager .............................................................................................24

    6 - DIAGNOSTICS - TROUBLESHOOTING ............................................................................................................................246.1 - General ............................................................................................................................................................................... 246.2 - Displaying alarms ............................................................................................................................................................... 246.3 - Resetting alarms ................................................................................................................................................................. 246.4 - Alarm codes ........................................................................................................................................................................ 25

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    4/264

    1 - SAFETY CONSIDERATIONS

    1.1 - General

    Installation, start-up and servicing of equipment can be

    hazardous if certain factors particular to the installation are not

    considered: operating pressures, presence of electrical

    components and voltages and the installation site (elevated

    plinths and built-up up structures). Only properly qualified

    installation engineers and highly qualified installers and

    technicians, fully trained for the product, are authorised to

    install and start-up the equipment safely. During all servicing

    operations all instructions and recommendations which appear

    in the installation and service instructions for the product, as

    well as on tags and labels fixed to the equipment and components

    and accompanying parts supplied separ-ately, must be read,

    understood and followed.

    Apply all standard safety codes and practices.

    Wear safety glasses and gloves.

    Use the proper tools to move heavy objects. Move units

    carefully and set them down gently.

    1.2 - Avoid electrocution

    Only personnel qualified in accordance with IEC (Interna-

    tional Electrotechnical Commission) recommendations may be

    permitted access to electrical components. It is particu-larly

    recommended that all sources of electricity to the unit be shut

    off before any work is begun. Shut off the main power supply

    at the main circuit breaker or isolator.

    IMPORTANT: This equipment uses and emits electro-

    magnetic signals. Tests have shown that the equipment

    conforms to all applicable codes with respect to electro-

    magnetic compatibility.

    RISK OF BURNS: Electrical currents cause components to

    get hot either temporarily or permanently. Handle power

    cable, electrical cables and conduits, terminal box covers and

    motor frames with great care.

    2 - GENERAL DESCRIPTION

    2.1 - Service interface

    Service inteface is a command for exclusively use by service

    and installers personnel.

    The purpose of this contol are:

    Diagnostic

    Parameters' configuration

    Note: ON/OFF, COOL/HEAT and dual set-point functions are

    not available on the service interface.

    2.2 - Pro-Dialog

    Pro-Dialog is a system for controlling single circuit 30RA air-

    cooled liquid chillers or air-to-water 30RH heat pumps. Pro-

    Dialog controls compressor start-up needed to maintain the

    desired heat exchanger entering or leaving water temperature. In

    cooling mode it controls the operation of the fans to maintain the

    correct condensing pressure. For heat pump units it controls

    and optimises the defrost cycles in order to minimize the

    heating capacity reduction. Safety devices are constantly

    monitored by Pro-Dialog to ensure their safe operation. Pro-Dialog also gives access to a Quick Test program covering all

    inputs and outputs.

    All PRO-DIALOG Plus control can work in accordance with

    two independent modes:

    Remote mode: the machine is controlled by remote contacts

    volt-free contacts (available simplified control AJRC).

    CCN mode: the machine is controlled by commands from

    the Carrier Comfort Network (CCN). In this case, a data

    communication cable is used to connect the unit to the

    CCN communication bus.

    The operating mode must be chosen with the Start/Stop button

    described in sections 3 and 4.2.1. When the PRO-DIALOG

    Plus system operates autonomously (Remote mode) it retains all

    of its own control capabilities but does not offer any of the

    features of the CCN network.

    2.3 - Abbreviations used

    The following abbreviations are used frequently:CCN : Carrier Comfort Network

    CCn : Operating type: CCN

    LED : Light Emitting Diode

    LOFF : Operating type: Local OffL-On : Operating type: Local On mode

    L-Sc : Operating type: Local On following a time schedule

    rEM : Operating type: by remote contacts

    SCT : Saturated Condensing Temperature

    SIO : Sensor Bus (internal communication bus linking the

    basic board)

    SST : Saturated Suction Temperature

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    5/265

    3 - INTERFACE CONNECTION

    Disconnect the unit fom power supply.

    Remove the electrical panel access door and the top unit

    cover.

    Replace the J4 connector (see fig. 1) with the one supplied

    ref. Connect the service interface to the J10 connector onto

    Pro-Dialog basic board (see fig. 3) using the flat cable

    extension (ref) supplied. Refit the unit top cover, the electrical panel access door

    and reconnect the unit power supply.

    3.1 Functions ON/OFF, cooling/heating and dual set-point

    By connecting the J4 connector (ref.), the unit operates(in cooling mode); disconnecting the J4 connector the unit

    stops.

    To select COOL/HEAT mode or dual set-point, fit

    J4 connector like a connector shown in fig. 2.

    Fig. 3

    Fig. 1

    J4 connector

    Fig. 2

    Cooling Set-point 1 Cooling Set-point 2 Heating Set-point 1 Heating Set-point 2

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    6/266

    Main interfaceIt gives access to all PRO-DIALOG PLUS data and operating

    functions. It consists of: A two-digit display showing the number of the item

    selected.

    A four-digit display showing the contents of the item

    selected.

    LEDs and buttons for unit start/stop, menu selection,

    menu item selection and value adjustment.

    4 - SETTING UP PRO-DIALOG PLUS CONTROL

    4.1 - Service interface general features

    The service interface enables a number of operating parameters to

    be displayed and modified.

    The interface consists of two distinct parts: the main interface

    (left hand section) and the summary interface (right hand

    section).

    MAIN INTERFACE MENU LED'S

    LED NAME DESCRIPTION

    INFORMATION menu Displays the general operat ing parameters for the unit .

    TEMPERATURES menu Displays the unit operating temperatures.

    PRESSURES menu Displays the unit operating pressures.

    SETPOINTS menu Displays the unit setpoints and enables them to be modified.

    INPUTS menu Displays the status of the unit digital and analogue inputs.

    OUTPUTS/TESTS menu Displays the status of the unit outputs and enables them to be tested.

    CONFIGURATIONS menu Displays the unit configuration and enables it to be modified.

    ALARMS menu Displays active alarms.

    ALARMS HISTORY menu Displays the history of the alarms.

    OPERATING LOG menu Displays the operating times and number of starts for the unit and the compressors.

    kPa

    MAIN INTERFACE

    BUTTON NAME DESCRIPTION

    Menu Permits the selection of a main menu. Each main menu is represented by an icon. The icon is lit if active.

    Up arrow Permits scrolling through the menu items (in the two-digit display). If the modification mode is active this button authorisesincrease of the value of any parameter.

    Down arrow Permits scrolling through the menu items (in the two-digit display). If the modification mode is active this button authorisesdecrease of the value of any parameter.

    Enter Gives access to the modification mode, validates a modification or displays expanded item description.

    Start/stop Authorises start or stop of the chiller in local mode or modification of its operating type.

    MAIN INTERFACE SUMMARY INTERFACE

    MENU BLOCK

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    7/267

    kPa

    The summary interface (right hand section) includes a mimic

    diagram of the unit, together with push-buttons and LEDs. It

    gives quick access to the main operating parameters of the unit.

    SUMMARY INTERFACE LED'S

    LED INDICATION WHEN LIT

    Green LED:

    The unit is authorised to start or is already running

    Red LED: Lit: circuit A or unit shut down by alarm

    Flashing: circuit A or unit running with alarm presentRed LED:

    Water flow switch default or user safety lock open.

    Green LED:The evaporator pump is running.

    First Yellow LED:Start/stop status of compressor.Flashing LED indicates that the circuit is in theprotection or defrost mode.

    Green LED:

    The unit operates in heating mode.

    Green LED:

    The unit operates in cooling mode.

    SUMMARY INTERFACE PUSH BUTTONS

    BUTTON DISPLAY

    Blue button: evaporator leaving or entering water temperature in C

    Gray button: outdoor air temperature in C

    Control point (setpoint + reset) in C

    Press 1: circuit A discharge pressure in kPaPress 2: circuit A saturated condensing temperature in C

    4.2 - Unit start/stop control

    4.2.1 - DescriptionThe unit start/stop can be controlled by one of the following

    methods:

    By remote control with the aid of user contacts (remotecontrol type)

    By CCN control with the aid of the CCN (CCN control

    type)

    The service interface includes a Start/Stop button which cannot

    be used to stop or start the unit in the local operating type but

    to select the remote or CCN operating type.

    See CCN clock board instructions kit.

    The available operating types are described in the following

    table.

    OPERATING TYPES

    4 DIGIT DISPLAY DESCRIPTION

    CCN* CCN. The unit is controlled by CCN commands. This

    is displayed if the unit is equipped with an optionalCCN clock board. See section 3.1.

    rEM* Remote. The unit is controlled by remote control

    contacts.

    Legend

    * Displayed if the configuration requires it.

    4.3 - Menus

    4.3.1 - Selecting a menuThe MENU button authorises you to select a menu from the 10

    main menus that are available. Each time you press this button

    one of the 10 LEDs lights up in turn alongside each of the

    icons representing a main menu. The active menu is the one

    against which the LED is lit. If a menu is empty then its LED is

    not lit. To scroll quickly through the menus, hold the MENU

    button down.

    4.3.2 - Selecting a menu itemThe up and down Arrow buttons let you scroll through the

    menu items. Menu item numbers are displayed in the two-digit

    display. The item number increases or decreases every time you

    press the up or down Arrow button. The menu items that are not

    in use or incompatible with the configuration are not displayed.

    The value or status associated with the active item is displayed

    in the four-digit display. To scroll quickly through the items,

    hold the up or down Arrow button down.

    The following example shows how to access item 3 in the

    Pressures menu.

    SELECTING A MENU ITEM

    OPERATION PRESS MENU LED ITEM NUMBER

    BUTTON 2-DIGITDISPLAY

    Press the MENU button until theLED marked PRESSURE lights. 0

    0

    Press one of the Arrow buttons 1

    until the two-digit display shows 3(item number 3).

    2

    3

    4.3.3 - Modifying the value of a parameter/access to a sub-menuPress the Enter button for more than 2 seconds to enter the

    modification mode or to select a sub-menu. This lets you correct

    the value of an item or select a sub-menu with the aid of the up

    and down Arrow buttons (if you are authorised to overwrite the

    item concerned). When modification mode is activated, the LED

    for the main menu to which the item belongs flashes in menu

    block. Once the required value is obtained, press the Enter

    button again to validate the change or to access the sub-menu.

    The LED for the menu to which the item belongs then stops

    flashing, indicating that modification mode no longer applies.

    In modification mode, the value to be modified increases or

    decreases in steps of 0.1 every time you press the Arrow

    buttons. Holding one of these buttons down increases the rate

    of increase or decrease.

    NOTE: The access to a sub-menu may require entering a

    password. This is automatically requested. See section

    4.3.11.2.

    kPa

    kPa

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    8/268

    0

    0

    1

    1 6.0

    1 6.0

    1 5.9

    1 5.8

    1 5.7

    1 5.7

    MODIFYING THE VALUE OF A PARAMETER

    OPERATION PRESS BUTTON MENU LED ITEM NUMBER ITEM VALUE2-DIGIT DISPLAY 4-DIGIT DISPLAY

    Hold on the MENU button until the LED for SETPOINT lights.

    Press one of the Arrow buttons until the two-digit display shows 1(item number 1- cooling setpoint 2).The value for setpoint 2 is displayed in the four-digit display (6.0C in thisexample).

    Press the Enter button for more than 2 seconds to enable the value associatedwith item 1 to be modified.The Setpoint menu LED flashes indicating that modification mode is active.

    Keep pressing the Down Arrow button until the value 5.7 is displayed in the four-digit display. The Setpoint menu LED keeps flashing.

    Press the Enter button again to validate the change. The new setpoint is 5.7C.The Setpoint menu LED stops flashing, indicating that modification mode no

    longer applies.

    The example below shows how to modify the value of item 1 in

    the Setpoint menu.

    4.3.4 - Expand displayPressing the Enter button causes a 23 character text expansion to

    be scrolled across the four-digit display. All user menus provide

    an expansion of the current displayed parameters. If the

    expansion is complete the four-digit display reverts to item

    value. This function can be inhibited through the User

    Configuration menu.

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    9/269

    STATUS

    TEMPERATURES

    PRESSURES

    SETPOINT

    S

    INPUTS

    OUTPUTS

    C

    ONFIGURATION

    ALARMS

    ALARMSHISTORY

    ALARMS

    USER

    [USEr]

    SERVICE

    [SErviCE]

    FACTORY

    [FACtorY]

    RUNTIME

    [RuntiME]

    MAINTENANCE

    [MAintEnAnCE]

    PERIOD

    3

    [PEriod3]

    PERIOD

    4

    [PEriod4]

    PERIOD

    5

    [PEriod5]

    PERIOD

    6

    [PEriod6]

    PERIOD

    7

    [PEriod7]

    PERIOD

    8

    [PEriod8]

    PERIOD

    1

    [PEriod1]

    PERIOD

    2

    [PEriod2]

    USER

    1

    [USEr1]

    USER

    2

    [USEr2]

    SCHEDULE1

    [SCHEduLE1]

    SCHEDULE2

    [SCHEduLE2]

    HOLIDAYS

    [HoLidAy]

    HOUR

    +DATE

    [dAtE]

    BROADCAST

    [brodCASt]

    SERVICE1

    [SErviCE1]

    SERVICE2

    [SErviCE2]

    HMS

    [HMS]

    PERIOD

    3

    [PEriod3]

    PERIOD

    4

    [PEriod4]

    PERIOD

    5

    [PEriod5]

    PERIOD

    6

    [PEriod6]

    PERIOD

    7

    [PEriod7]

    PERIOD

    8

    [PEriod8]

    PERIOD

    1

    [PEriod1]

    PERIOD

    2

    [PEriod2]

    HOLIDAYS3

    [HoLidAy3]

    HOLIDAYS4

    [HoLidAy4]

    HOLIDAYS5

    [HoLidAy5]

    HOLIDAYS6

    [HoLidAy7]

    HOLIDAYS7

    [HoLidAy7]

    HOLIDAYS8

    [HoLidAy8]

    -

    -

    -

    -

    -

    -

    -

    -

    -

    HOLIDAYS15

    [HoLidAy15]

    HOLIDAYS16

    [HoLidAy16]

    HOLIDAYS1

    [HoLidAy1]

    HOLIDAYS2

    [HoLidAy2]

    MAIN

    MENU

    S

    SUB-MENUS

    SUB-SUB-MENUS

    SUB-SUB-SUB-MENUS

    MENU STRUCTURE

    NOTE:Theitem

    sinbracketsshowwhatis

    displayedontheuserinterface.

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    10/2610

    Menu tree structure

    Leg

    en

    d

    *

    Displaye

    diftheconfiguratio

    nrequiresit

    **

    Displayedifthealar m

    exists

    -

    Notinuse

    ITEM

    0 1 2 3 4 5 6 7 8 9 10

    11

    12

    13

    14

    15

    S

    TATUS

    D

    efaultdisplay

    M

    ode

    C

    hilleroccupied

    m

    ode*

    M

    inutesleft

    C

    ooling/heating

    s

    tatus*

    C

    ompressor

    s

    tatus

    -- -

    -- -

    -- -

    -

    TEMP

    Evaporatorwater

    enteringte

    mp.

    Evapo

    ratorwater

    leavingtemp.

    Outdoortempera-

    ture

    Saturated

    discharg

    e

    temperature

    Sa

    turatedsuction

    temperature

    Defrost

    temperature

    - - - - - - - - - -

    PRESSU

    RES

    Dischar g

    e

    pressure

    Suction

    pr e

    ssure

    - - - - - - - - - - - - - -

    SETPO

    INTS

    Coo

    lingsetpoint1

    Cooling

    setpoint2

    He

    atingsetpoint1*

    Heatingsetpoint2*

    Heati

    ngsetpoint3*

    Cooling-

    zeroreset

    threshold*

    Coo

    ling-fullreset

    threshold*

    Coo

    ling-fullreset

    value*

    Heating-ze

    roreset

    threshold*

    Heatin

    g-fullreset

    threshold*

    Heating-f u

    llreset

    value*

    - - - - -

    INPUTS

    Contact1

    :on/off/

    status

    Contact2:on

    /off/

    heat i

    ng/cooling*

    Contact

    3:

    dualsetpoint

    status

    Con

    tact4:CCN

    modeselect

    sta

    tus

    Contact5:

    interlockstatus

    Faultcontact,c

    om-

    press

    or,circuitA

    - - - - - - - - - -

    OUTPUT

    S

    Comp

    ressor

    status

    Two-speed

    fan

    status

    Wate

    rpump1

    status*

    Waterheat

    exchanger+

    airheat

    exc

    hangerheater

    status

    Alarmr e

    lays

    Boilerstatus

    *

    Revers

    ing

    valve

    Status

    ,

    heater

    stage

    s*#1

    Status,

    heaterstages*#2

    Screent e

    stfor

    localinterface

    Automatic

    qui c

    ktest

    - - - - -

    CONFI G

    SU

    B-MENU:User

    Configuratio

    n(U

    SEr)

    SUB-M

    ENU:

    ServiceConfiguratio

    n

    (SErviCE)

    SU

    B-MENU:

    FactoryConfig u

    ration

    (FAC

    torY)

    - - - - - - - - - - - - -

    ALARMS

    Number

    ofactive

    alarms/resets**

    Activealarm

    code1**

    Activea

    larmcode2**

    Ac

    tivealarmcode3**

    Activealarmcode

    4**

    Active

    alarmcode5**

    - - - - - - - - - -

    ALARMS

    HIST

    Histor i

    calarmco

    de

    1**

    Historical a

    rmco

    de

    2**

    Histo

    ricalarm

    code3**

    Historicalarmco

    de

    4**

    Historicalarmc o

    de

    5**

    His

    toricalarmco

    de

    6**

    Histor i

    calarmco

    de

    7**

    Histo

    ricalarmco

    de

    8**

    Historicalarm

    co

    de

    9**

    Historic

    alarmco

    de

    10**

    - - - - - -

    RUNT

    IMES

    SU

    B-MENU:

    Runtimes

    SUB-M

    ENU:

    Maintenance

    - - - - - - - - - - - - - -

    MENU

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    11/2611

    4.3.5 - Description of the Information menu

    INFORMATION MENU (3)

    ITEM FORMAT UNITS

    0

    nn.n C

    CCn -rEM -

    OFF -rEADY -

    dELAY -

    StOPPing -running -triPout -OvErridE -dEFrOSt -

    OCCUPIEd -UNOCCUPIEd -

    COOL -HEAT -

    BotH -

    ALArM -ALErt -

    1 [1] nn

    -

    2 [2] -occu

    unocForc

    3 nn.n minutes

    4 [2]HEAt -COOL -

    both -Forc -

    5 [2] nnn -

    6 [2] -occu

    unocForc

    7 nn.n C

    8 nn.n

    Forc C

    9 nn.n C

    Legend

    1 This item is masked when nil.2 This item is displayed in certain unit configurations only.

    3 Access to this menu is read-only except for item 10 that can be forced when the unit is in Local operating type.

    DESCRIPTION

    Automatic display mode. It cycles through the following displays:

    1: Controlled water temperature:temperature of the water that the unit tries to maintain at the control point.

    2: Unit operating typeCCN Control. Displayed if the CCN/clock board is installed.Remote Control

    3: Unit status

    Off: Unit is stopped and not authorised to start.Ready: Unit is authorised to start

    Delay: Unit is in delay at start-up. This delay is active after the unit has been switched on. The delay can beconfigured in the User Configuration menu.

    Stopping: Unit is currently stopping.On: Unit is running or authorised to start.Fault shutdown.Limit: The operating conditions do not allow total unit operation.Defrost: One circuit is in defrost mode.

    4. Unit occupied/unoccupied statusOccupied: Unit in occupied modeUnoccupied: Unit in unoccupied mode

    5. Heating/cooling operating mode

    Cooling: Unit operates in cooling modeHeating: Unit operates in heating mode

    Both: The unit operates in cooling (compressors) and heating (boiler). Only with HSM operation.

    6: Alarm modeAlarm: Unit is totally stopped because of failure.Alert: Unit is in failure but not completely stopped.

    Active mode codes.Each active mode is displayed in turn. This Item is masked when nil. Pressing the enter button when a modecode is displayed causes a character text expansion to be scrolled accross the four-digit display. See the description in the following

    table

    This item indicates the current unit occupied/unoccupiedmode. Displayed if the CCN/clock board is installed.Occupied

    UnoccupiedThe value is displayed in turn with 'Forc' when the unit is in CCN control and if this variable if forced through CCN.

    Start-up delay.This item indicates the minutes left before the unit can be started. This delay at start-up is always active after the unithas been switched on. The delay can be configured in the User Configuration 1 menu.

    Heating/cooling mode.This item indicates whether the unit is in cooling or heating. Displayed if the unit controls a boiler.HeatingCooling

    Both: The unit operates in cooling (compressors) and heating (boiler). Only with HSM operation.The value is displayed in turn with 'Forc' when the unit is in CCN control and if this variable if forced through CCN.

    Compressor status. ON - OFF

    Setpoint occupied mode.Displayed if the CCN/clock board is installed.Occupied: cooling setpoint 1 is active

    Unoccupied: cooling setpoint 2 is activeThe value shall be displayed in turn with 'Forc' when the unit is in CCN control and if this variable if forced through CCN.

    Active setpoint.This is the current cooling/heating setpoint: it refers to cooling setpoint 1 or cooling/heating setpoint 2. See section5.4.1.

    Control point.This is the setpoint used by the controller to adjust the temperature of the leaving or entering water (according to

    configuration).Control point = active setpoint + reset. See section 5.4

    The value is displayed in turn with 'Forc' when the unit is in CCN control and if this variable if forced through CCN.

    Controlled water temperature.Water temperature that the unit tries to maintain at the control point.

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    12/2612

    4.3.6 - Description of the Temperatures menu

    TEMPERATURES MENU [2]

    ITEM FORMAT UNITS COMMENTS

    0 nn.n C Water heat exchanger entering water

    temperature

    1 nn.n C Water heat exchanger leaving water tempera-

    ture

    2 nn.n C Outdoor temperature

    3 nn.n C Saturated discharge temperature, circuit A

    4 nn.n C Saturated suction temperature, circuit A

    5 [1] nn.n C Defrost temperature, circuit A

    Legend1 This item is displayed in certain unit configurations only2 Access to this menu is read-only.

    4.3.7 - Description of the Pressures menu

    PRESSURES MENU [1]

    ITEM FORMAT UNITS COMMENTS

    0 [1] nnnn kPa Discharge pressure.

    Relative pressure.

    1 [1] nnn kPa Suction pressure.

    Relative pressure.

    Legend1 Access to this menu is read-only

    DESCRIPTION OF OPERATING MODES (ITEM 1 OF THE INFORMATION MENU)

    MODE # MODE NAME

    1 Delay at start-up active

    2 2nd cooling/heating setpoint active

    3 3rd heating setpoint active

    4 Setpoint reset active

    5 Water or air heat exchanger

    heater active

    6 Evaporator pump periodic start

    7 Night condensing mode

    8 Low suction temperature protection

    9 High pressure protection

    10 Defrost

    11 Low water entering temperatureprotection in heating mode

    12 Hot gas protection in heating mode

    13 Low suction temperature protectionin heating mode

    14 Boiler active

    15 Electric heating stages active

    16 Unit in SM control

    DESCRIPTION

    The delay at start-up operates after the unit has been switched on. If the delay has not expired, the mode is active.The delay is configured in the User Configuration 1 menu.

    The second cooling/heating setpoint is active. See section 5.4.1

    The third heating setpoint is active. See section 5.4.1

    In this mode, the unit uses the reset function to adjust the leaving water temperature setpoint. See section 5.4.

    The water or air heat exchanger heater is active. See section 5.3.

    The unit is stopped and the pump is started each day at 14.00 p.m. for two seconds. This function needs to beconfigured in the User Configuration 1 menu. See section 5.2 & 4.3.11.4.

    The night mode is active. Fan runs at low speed (if permitted by operating conditions) and unit capacity can belimited. See section 4.3.11.4.

    Protection for evaporator low suction temperature circuit is active. In this mode, circuit capacity is not authorised torise and the circuit can be unloaded.

    The unit is in cooling mode.The circuit is in high pressure protection mode because the HP protection threshold has been exceeded.Circuit has been unloaded and the circuit capacity is not authorised to rise. See section 5.7.

    The unit is in heating mode, and the defrost sequence is active on the relevant circuit.

    The unit is in heating mode and compressor start is not authorised, as the entering water temperature is below

    10C.

    The unit is in heating protection mode and hot gas discharge protection is active. In this mode, the circuit capacitycannot increase, and the circuit may be unloaded or go into defrost mode.

    The unit is in heating mode and low suction temperature protection is active. In this mode, circuit capacity is notauthorised to rise and the circuit can be unloaded or go into defrost mode.

    The unit controls a boiler and this is operating. See section 5.10.

    The unit controls additional electric heating stages, and these are operating. See section 5.10.

    Unit is in control of a System Manager (FSM, CSM III or HSM).

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    13/2613

    SETPOINTS MENU [2]

    ITEM FORMAT UNITS RANGE

    0 nn.n C See table below

    1 nn.n C See table below

    2 nnn C See table below

    3 [1] nnn C See table below

    4 [1] nn.n C See table below

    5 [1] nn.n C See table below

    6 [1]

    nn.n

    C See table below7 [1] nn.n C See table below

    8 [1] nn.n C See table below

    9 [1] nn.n C See table below

    10 [1] nn.n C -16 to 16

    4.3.8 - Description of the Setpoints menu

    1 This item is displayed in certain unit configurations only.2 All points contained in this table can be modified.

    * Those setpoints can be used for entering or leaving water temperature control. By default the unit controls the evaporator entering fluid temperature.Leaving fluid temperature control requires a parameter modification in the Service Configuration menu.

    ** These parameters are only accessible when reset based on OAT or delta T has been selected in the User Configuration 1 menu. See section 4.3.11.3 & 5.6.2.

    COMMENTS

    This item lets you display and modify Cooling setpoint 1*

    This item lets you display and modify Cooling setpoint 2*

    This item lets you display and modify Heating setpoint 1*, only displayed for heat pumps.

    This item lets you display and modify Heating setpoint 2*, only displayed for heat pumps.

    This item lets you display and modify Heating setpoint 3*, only displayed for heat pumps.

    Zero reset threshold, cooling mode**

    Full reset threshold, cooling mode**Full reset value, cooling mode**

    Zero reset threshold, heating mode**

    Full reset threshold, heating mode**

    Full reset value, heating mode**

    LEAVING WATER TEMPERATURE CONTROL (LWT_OPT=YES)

    SETPOINT - C R-410A

    Minimum cooling value

    Water 3.9Maximum cooling value 17.8

    Feedback setpoint, cooling 7.0Minimum heating value 20.6

    Maximum heating value 50.0Default setpoint heating 50.0

    ENTERING WATER TEMPERATURE CONTROL (LWT_OPT=NO)

    SETPOINT - C R-410A

    Minimum cooling valueWater 10.0

    Maximum cooling value 23.9

    Feedback setpoint, cooling 12.0Minimum heating value 14.4

    Maximum heating value 43.9Default setpoint heating 45.0

    RESET THRESHOLDS IN COOLING OR HEATING MODE

    Reset threshold Zero FullReset based on outdoor -10 to 51.7 C -10 to 51.7 Cair temperature

    Reset based on 0 to 11.1 C 0 to 11.1 CDelta T

    INPUTS MENU [2]

    ITEM FORMAT UNITS

    0 oPEn/CLoS -

    1 [1] oPEn/CLoS -

    2 oPEn/CLoS -

    3 [1] oPEn/CLoS -

    4 b1 -

    4.3.9 - Description of the Inputs menu

    1: This item is displayed in certain unit configurations only2: Access to this menu is read-only.

    COMMENTS

    Remote contact 1 status.If the auto cooling/heating changeover function is not selected (User Configuration 1), this contact is used to startand stop the unit. If the auto cooling/heating changeover function is selected, this contact is multiplexed with contact

    2 to permit starting and stopping the unit and the selection of heating/cooling/auto. This contact is only valid, if theunit is in the remote operating control (rEM) mode. See section 3.6 for the description of the connections of thiscontact.

    Remote contact 2 status.If the auto cooling/heating changeover function is not selected (User Configuration 1), this contact is used to select

    the heating or cooling mode. If the auto cooling/heating changeover function is selected, this contact is multiplexedwith contact 1 to permit starting and stopping the unit and the selection of heating/cooling/auto. This contact is only

    valid, if the unit is in the remote operating control (rEM) mode. See section 3.6 for the description of the connectionsof this contact.

    Remote contact 3 status.Dual set point: CSP1=Open; CSP2=Closed

    CCN contact status.

    This contact is only used for dual-circuit units: this contact is multiplexed with contact 6 to permit selection of asetpoint. This contact is only active in the remote operating control mode. See section 3.6.6 for the description of this

    contact and section 5.6.1 for the description of the setpoint selection function.Compressor feedbackcontacts

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    14/2614

    1 : This item is displayed in certain unit configurations only.2 : Testing authorised only if the unit is in Local Off and all compressors are off.

    3 : Password needed only for testing.Test: displayed in turn with the item value during tests.

    4.3.10.3 - Manual testsThis function allows the user to test the outputs individually, if

    the machine is completely shut down (LOFF). To carry out a

    manual test use the arrow keys to access the output to be tested

    and press the Enter key (longer than 2 seconds) to activate the

    modification mode. The password is automatically requested, if it

    has not previously been verified. The Outputs/Test LED on the

    user interface begins to flash. Enter the desired test value andagain press Enter to start the test. 'TESt' is displayed on the

    4-digit display alternately with the value tested. The Outputs/

    Test LED stops flashing. Press the Enter key or an arrow key to

    stop the test.

    4.3.10 - Description of the Outputs/Tests menu

    4.3.10.1 - GeneralThis menu displays the status of the controller outputs. Moreo-

    ver, when the machine is fully stopped (LOFF) the outputs can

    be activated for manual or automatic tests (the access to the

    tests is password controlled).

    4.3.10.2 - Menu description

    OUTPUTS STATUS & TESTS MENU [2] [3]

    ITEM FORMAT UNITS0 b

    1

    tESt

    FAILGood -

    1 StoPLOW

    HIGHtESt -

    2 [1] On

    OFFtESt

    FAILGood

    Forc -

    3 On

    OFFtESt -

    4 b1

    tESt -

    5 [1] OnOFF

    tESt -

    6 [1] nnn

    tESt %7 [1] b1

    tESt

    8 [1] b1b

    2

    tESt

    9 [1] YES -no -

    tESt %

    10 Auto tESt -

    DESCRIPTIONCompressor, command status

    b1= compressor

    In test mode, the Arrow buttons display ON/OFF in succession, so as to force the status of the compressor outputs in turn.

    During the test phase, power to the compressor is switched on for 10 seconds only. It is then not possible to restart thecompressor for a further 30 seconds. When the test is completed the following is displayed:- Fail: displayed if the test has failed because the compressor was not started or run in reverse rotation.- Good: displayed if test was successful

    Two-speed fan statusStop = fan is stopped

    Low = fan is in low speedHigh = fan is in high speed

    Evaporator water pumpcommand status. Not displayed if the unit does not control a pump.

    On: pump is runningStop: pump is stopped

    Forc: this item is displayed only when the unit is stopped locally (LOFF). selecting this item authorises turning on thepump with no delay and for an unlimited length of time. The pump will remain on until any button of the user interface is

    pressed: it is then immediately stopped. If the unit is in CCN control, then the pump status is displayed in turn with "Forc"if the pump status if forced through CCN.

    During the test phase, power to the pump is switched on for 10 seconds only. When the test is completed the following isdisplayed:

    - Fail: displayed if the test has failed because the pump was not started- Good: displayed if the test was successful

    Water heat exchanger heater command status

    See sections 5.3

    Alarm output command status

    b1= alarmIn test mode, the Arrow buttons display ON and OFF in succession, so as to force each alarm output status in turn.

    Boilercommand status. Displayed if the unit controls a boiler. See section 5.11.

    Variable fan speed. Displayed if the unit controls a variable-speed fan.

    4-way reversing cycle valve status.In test mode, the arrow keys successively display 01 and 10, in order to authorise thetest for each valve in turn.

    b1= valve

    This item is only displayed for heat pump units.

    Additional heating stage status.

    b1= stage 1

    b2= stage 2

    In test mode the arrow keys successively display 0001, 0010, 0100 and 1000 to force the status of each electric heatingstage in turn.This item is only displayed for heat pump units controlling additional electric heater stages. See section 5.10.

    Used for local interface testonly. Lights or flashes all LEDs and blocks, so as to check that they are working properly.

    Automatic test.Selecting this item activates the automatic test function.

    4.3.10.4 - Automatic testsThe automatic test function verifies the integrity of the analo-

    gue entries and activates the outputs in sequence. For each test

    't XX' is displayed on the user interface. 'xx' indicates the

    number of the test in progress. When a test has been completed,

    the following test is automatically activated.

    A message may appear, asking the operator for a validationwith the Enter key, if the control cannot automatically verify a

    sensor value or an output status. If the value read or the output

    status is incorrect, the operator must press a different key (not

    the Enter key) to cancel the automatic test procedure.

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    15/2615

    If a test fails, an error message and an error code are dis-

    played. The automatic test procedure is interrupted.

    When all tests have been completed, an end-of-test message

    appears.

    The table below describes the messages shown on the user

    interface during the automatic test sequence.

    The table below describes the different sequences of the

    automatic test.

    TEST NUMBER

    0

    1

    2

    3, 4

    5, 6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    18

    DESCRIPTION

    Outdoor temperature sensor test

    Pressure sensor test

    Defrost sensor test (heat pumps only)

    Water flow switch test and primary pump test

    Entering and leaving water temperature sensor test

    Entering and leaving water temperature sensor delta test

    Water flow switch test

    Test compressor

    4-way reversing valve test (heat pumps only)

    Low-speed test, fan (units not equipped with Varifan)

    High-speed test, fan (units not equipped with Varifan)

    Air heat exchanger condensate heater test (dual-circuit heat pumps only)

    Boiler output activation (if unit controls a boiler)

    Additional electric heating stage 1 activation (if unit controls electric heating stages)

    Additional electric heating stage 2 activation (if unit controls electric heating stages)

    Alarm output A activation

    Automatic test completed

    CONFIRMATION

    yes

    no

    no

    no

    no

    no

    no

    no

    no

    yes

    yes

    yes

    yes

    yes

    yes

    yes

    -

    TEXT DESCRIPTION

    Thermistor test failed [XX] Test number XX of the thermistor has failed

    Pressure test failed [XX] Test number XX of the pressure sensor hasfailed

    Output test failed [XX] Output test number XX has failed

    Input test failed [XX] Input test number XX has failed

    Press enter if test [XX] correct Request for the operator to validate test XX

    OAT [value] press enter if Request for the operator to validate thetest [XX] correct outdoor air temperature value displayed.

    Test number XX

    Auto test completed Automatic test completed

    The table below describes the faults that can be displayed

    during the automatic test.

    4.3.11- Description of the configuration menu

    4.3.11.1- GeneralThis menu can be used to display and modify all configurations:

    Factory, Service and User. Only the User Configuration can be

    modified by the end-user. The Factory, Service and master/slave

    configurations are not described in this document. A configu-

    ration can only be modified if the unit is fully stopped (LOFF).

    The menus User 1 [USEr 1] and User 2 [USEr 2] are pass-

    word-protected. The other menus are directly accessible, except

    if item 6 of the User 1 menu (password for all con-figurations)

    has been validated.

    4.3.11.2 - PasswordA password must be entered in order to access the test function

    or to modify a configuration. It is automatically requested, if

    necessary: 'EntEr PASS' is displayed on the 4-digit display and

    the configuration menu LED flashes, indi-cating that the

    modification mode is active. Press the arrow keys until the

    value '11' is displayed on the 4-digit display. Press Enter to

    validate this. The configuration menu LED stops flashing. If the

    password is correct, 'Good' is displayed. If the password is

    incorrect, 'PASS incorrEct' is displayed. The User password has

    a default value of 11.

    This value can be modified through the Service configuration.

    The password can be entered if the unit is fully stopped,otherwise 'ACCES dEniEd' (access denied) will be displayed on

    the 4-digit display. The controller automatically deacti-vates

    the password after 5 minutes without activity (i.e. no buttons

    pressed) or after powering up.

    TEST FAULT DESCRIPTION

    1 Outdoor air thermistor outside range

    2 Outdoor air value read not validated by operator

    3 Low pressure transducer, outside range4 High pressure transducer, outside range

    5 Defrost thermistor, outside range

    6 Water flow switch not open

    7 Primary pump not started or water flow switch not

    closed

    8, 9, 10, 11, 12 Water entering temperature sensor outside range13, 14, 15, 16, 17 Water leaving temperature sensor outside range

    18 Temperature difference between entering andleaving water sensors too high

    19 Water flow switch not opened or primary pump notstopped

    20 Compressor start fault; pressure difference (delta P)

    between head and suction low

    21 Command fault, 4-way reversing valve

    22 Low-speed test, fan not validated by the operator

    23 High-speed test, fan not validated by the operator

    24 Air heat exchanger condensate heater, notvalidated by the operator

    25 Boiler activation test not validated by the operator

    26 Electric heating stage 1 activation test notvalidated by the operator

    27 Electric heating stage 2 activation test notvalidated by the operator

    28 Alarm relay output activation test, not validated by

    the operator

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    16/2616

    SUB-MENU USER CONFIGURATION

    Legend:

    *: only displayed if configuration requires.: The holiday function is not activated if no holiday is configurated.

    NOTE: The items in brackets show what is displayed on the

    user interface.

    SCHEDULE 1

    [ScHEduLE 1MEnu]*

    Return to previous menu

    SUB-MENU:Period 1 [PErIod 1]

    SUB-MENU:

    Period 2 [PErIod 2]

    SUB-MENU:Period 3 [PErIod 3]

    SUB-MENU:

    Period 4 [PErIod 4]

    SUB-MENU:

    Period 5 [PErIod 5]SUB-MENU:

    Period 6 [PErIod 6]

    SUB-MENU:Period 7 [PErIod 7]

    SUB-MENU:

    Period 8 [PErIod 8]

    -

    -

    -

    -

    -

    -

    -

    -

    -

    DATE

    [dAtE]*

    Return to previous

    menu

    Hour*

    Day of the week*

    Day and month*

    Year*

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    -

    SCHEDULE 2

    [ScHEduLE 2 MEnu]*

    Return to previous

    menu

    SUB-MENU:Start period hrs

    SUB-MENU:

    End period hrs

    SUB-MENU:Period 1 [PErIod 1]

    SUB-MENU:

    Period 2 [PErIod 2]

    SUB-MENU:

    Period 3 [PErIod 3]SUB-MENU:

    Period 4 [PErIod 4]

    SUB-MENU:Period 5 [PErIod 5]

    SUB-MENU:

    Period 6 [PErIod 6]

    SUB-MENU:Period 7 [PErIod 7]

    SUB-MENU:

    Period 8 [PErIod 8]

    -

    -

    -

    -

    -

    -

    -

    HOLIDAYS

    [HOLidAy MEnu]*

    Return to previous menu

    SUB-MENU:Holidays 1 [HOLidAy 1]

    SUB-MENU:

    Holidays 2 [HOLidAy 2]

    SUB-MENU:Holidays 3 [HOLidAy 3]

    SUB-MENU:

    Holidays 4 [HOLidAy 4]

    SUB-MENU:

    Holidays 5 [HOLidAy 5]

    SUB-MENU:

    Holidays 6 [HOLidAy 6]

    SUB-MENU:Holidays 7 [HOLidAy 7]

    SUB-MENU:

    Holidays 8 [HOLidAy 8]

    SUB-MENU:Holidays 9 [HOLidAy 9]

    SUB-MENU:

    Holidays 10 [HOLidAy 10]

    SUB-MENU:Holidays 11 [HOLidAy 11]

    SUB-MENU:

    Holidays 12 [HOLidAy 12]

    SUB-MENU:Holidays 13 [HOLidAy 13]

    SUB-MENU:

    Holidays 14 [HOLidAy 14]

    SUB-MENU:

    Holidays 15 [HOLidAy 15]SUB-MENU:

    Holidays 16 [HOLidAy 16]

    -

    BROADCAST

    [BrodCASt]*

    Return to previous menu

    Broadcast acknowledgerselection

    Broadcast activation

    Outdoor temperaturebroadcast bus

    Outdoor temperature

    broadcast element

    Start month daylight

    saving timeStart day daylight saving

    time

    Start hour daylight savingtime

    Minutes to add

    End month daylight savingtime

    End day daylight saving

    time

    End hour daylight savingtime

    Minutes to subtract

    -

    -

    -

    -

    -

    USER 2

    [USER2]*

    Return to previous

    menu*

    Periodic pump start-up*

    Night mode - start

    hour*

    Night mode - endhour*

    -

    Number clock 1*

    Number clock 2*

    CCN address *

    CCN bus*

    -

    -

    -

    -

    -

    -

    -

    -

    -

    USER 1

    [USER1]

    Return to previous menu

    Start-up delay*

    Set point selected on

    remote control

    Set point reset selection;cooling mode

    Set point reset selection;

    heating mode

    Boiler selection

    Boiler selection

    threshold

    Electric heating stageoperating threshold

    Electric heating

    safety stage + threshold

    Electric heatingstage operation schedule

    Extended display

    selection

    Password for all userconfiguration

    Software version

    number

    -

    -

    -

    -

    -

    ITEM

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    SUB-MENU PERIOD CONFIGURATION*

    Item PERIOD 1 to 8[PEriod X MEnu]*

    0 Return to previous menu

    1 Start of occupied period

    2 End of occupied period

    3 Selection Monday

    4 Selection Tuesday

    5 Selection Wednesday

    6 Selection Thursday

    7 Selection Friday

    8 Selection Saturday

    9 Selection Sunday

    10 Selection holidays

    SUB-MENU HOLIDAY CONFIGURATION*

    Item HOLIDAYS 1 to 16[HoLidAy X MEnu]*

    0 Return to previous menu

    1 Start month holidays

    3 Start day holidays

    4 Number of days, holidays

    Legend

    *: only displayed if configuration requires.

    NOTE: The items in brackets show what is displayed on the

    user interface.

    USER

    [USEr]

    CONFIGURATION

    PERIOD 1

    PERIOD 2

    PERIOD 3

    PERIOD 4

    PERIOD 5

    PERIOD 6

    PERIOD 7

    PERIOD 8

    PERIOD 1

    PERIOD 2

    PERIOD 3

    PERIOD 4

    PERIOD 5

    PERIOD 6

    PERIOD 7

    PERIOD 8

    HOLIDAY 1

    HOLIDAY 2

    HOLIDAY 3

    HOLIDAY 4

    HOLIDAY 5

    HOLIDAY 6

    HOLIDAY 7

    HOLIDAY 8

    HOLIDAY 16

    HOLIDAY 15

    ...

    ...

    ...

    USER2[USEr 2]

    SCHEDULE 1[SCHEduLE 1]*

    SCHEDULE 2[SCHEduLE 2]*

    HOLIDAYS[HOLIDAYS]*

    HOUR + DATE[dAtE]*

    BROADCAST[broAdCASE]*

    USER1[USEr 1]

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    17/2617

    4.3.11.3 - Description of the User 1 Configuration sub-menu

    Legend

    1 This item shall be masked when not used.2 Access to menu is read/write.

    USER 1 CONFIGURATION SUB-MENU [2]

    ITEM FORMAT UNITS DEFAULT COMMENTS

    0 USEr MEnu - - When selected this item authorises return to the previous menu.

    1 1 to 15 min 1 Delay at start-up. This value is reinitialised after power-up or when both circuits are halted by local, remote orCCN command. No compressor will be started up until this pause has expired. However, the evaporator pump

    command will be activated immediately. The safety lockout loop will not be checked until the pause has expired.

    2 [1] 0/1 - 0 Contact 3 select0 = dual setpoint is activated through remote control

    1 = dual setpoint is activated through programming operating time via CCNDetermines whether contact 3 is used for remote demand limit or dual setpoint control. For single-circuit units only.

    3 0/1/2 - 0 Cooling setpoint reset select. See section 5.4.2.0 = reset not selected1 = reset based on outdoor temperature2 = reset based on return water temperature

    4 [1] 0/1/2 - 0 Heating setpoint reset select.See section 5.4.2

    0 = reset not selected1 = reset based on outdoor temperature

    2 = reset based on return water temperature

    5 YES/no - no Boiler control selectYes = boiler controlled by the unitNo = boiler not controlled

    6 [1] -15 to 0 C -10 Boiler threshold.Outdoor air temperature limit; if the temperature is lower, the heat pump is stopped or only

    the boiler is used for hot water production. Only for heat pumps controlling an additional boiler.

    7 [1] -5 to 21 C 5 Electric heating stage threshold.Maximum outdoor air temperature threshold for the use of electric heatingstages. Only for heat pumps, equipped with optional additional electric heating stages.

    8 [1] YES/no - no Electric heating safety stage.In this configuration the last electric heating stage is only activated in the

    safety mode (in case of a unit fault that prevents unit operation in heat pump mode). The other electricheating stages operate normally. See section 5.10.

    9 [1] 0 to 60 minutes Electric heating stage operation schedule.Permits configuration of a start-up delay after unit start-upduring which the electric heater stages are not allowed to start.

    10 YES/no - yes Extended menu selectYes = menu description availableNo = menu description not availableThis item authorises activating or inhibiting the menu item expanded display.

    11 YES/no - no Password for all User Configurations

    Yes = password required for all User Configurations (Date, Time Schedule, Broadcast)No = password require for User menu only

    When this item is validated, the User Password will be required for all configurations accessible by the User.

    12 nn.n - - Software version numberThis item shows the number of the software version used by this controller. Access is read only.

    4.3.11.4 - Description of the User 2 Configuration sub-menuThis menu is only accessible if the unit is equipped with an

    optional CCN/clock board

    USER 1 CONFIGURATION SUB-MENU

    ITEM FORMAT UNITS DEFAULT COMMENTS

    0 USEr 2 Menu When selected this item authorises return to the previous menu.

    1[1] YES/no - no Periodic pump quick-start of the water pump(s)Yes = the pump is started periodically when the unit is manually stopped.

    No = periodic pump start is disabledWhen the unit is manually stopped (e.g. during the winter season) the pump is started each day at 14.00

    hours for 2 seconds. If two pumps are available, pump #1 is started on odd days and pump #2 on even days.

    2 n1n2n3n4 Night control mode - start time*00:00 to 23:59 - 00:00 Authorises entering the t ime of day at which the night control mode starts. During this period the fan runs at

    low speed (to reduce fan noise) if permitted by operating conditions, and unit capacity is limited to themaximum night values.

    3 n1n

    2n

    3n

    4Night control mode - end time*

    00:00 to 23:59 - 00:00 Authorises entering the time of day at which the night control mode ends.

    4 [1] 0 or 65 to 99 - 0 Schedule 1 clock number(for unit on/off schedule, see section 4.3.11.6).

    0 = schedule in local operating mode65 to 99 = schedule in CCN operating mode

    5 [1] 0 or 65 to 99 - 0 Schedule 2 clock number(schedule for setpoint selection, see section 4.3.11.6).

    0 = schedule in local operating mode65 to 99 = schedule in CCN operating mode

    6 [1] 1 to 239 - 1 CCN element address.

    No two network elements can have the same element number and bus number at the same time.7 [1] 0 to 239 - 0 CCN bus number.

    No two network elements can have the same element number and bus number at the same time.

    Legend* n

    1n

    2: hours (00 to 23). The first time the Enter button is continuously pressed, the first two characters in the 4-digit display flash so that hours can be adjusted.

    n3n

    4: minutes (00 to 59). Continuous pressing of the Enter key again causes the last two characters to flash so that minutes can be adjusted.

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    18/2618

    Starts at Ends at Active on

    P1: period 1, 0h00, 3h00, MondayP2: period 2, 7h00, 18h00, Monday and TuesdayP3: period 3, 7h00, 21h00, WednesdayP4: period 4, 7h00, 17h00, Thursday and Friday

    P5: period 5, 7h00, 12h00, SaturdayP6: period 6, 20h00, 21h00, Public holidaysP7: period 7, Not used in this exampleP8: period 8, Not used in this example

    4.3.11.6 - Description of the Time Schedules sub-menusThe control provides two timer programs: schedule 1 and

    schedule 2 that can be activated if the unit is equipped with an

    optional CCN/clock board (if the CCN/clock board is not

    installed, the two schedules are permanently in occupied

    mode).

    The first timer program (schedule #1) provides a means to

    automatically switch the unit from an occupied mode to an

    unoccupied mode: the unit is started during occupied periods.

    The second timer program (schedule #2) provides a means to

    automatically switch the active setpoint from an occupied

    setpoint to an unoccupied setpoint: cooling setpoint 1 is used

    during occupied periods, cooling or heating setpoint 2 during

    unoccupied periods. Heating setpoint 3 is activated during

    holiday periods. For additional information on set-point

    activation see section 5.4.1.

    Each schedule consists of eight time periods set by the

    operator. These time periods can be flagged to be in effect ornot in effect on each day of the week plus a holiday period (see

    section 4.3.11.7 on public holidays). The day begins at 00.00

    hours and ends at 24.00 hours.

    Program is in unoccupied mode unless a schedule time period

    is in effect. If two periods overlap and are both active on the

    same day, the occupied mode takes priority over the

    period.

    Each of the eight periods can be displayed and changed with

    the aid of a sub-sub-menu. The table below shows how to

    access the period configuration. Method is the same for thetime schedule #1 or the time schedule #2.

    4.3.11.5 - Description of Date and Time configuration sub-menuThis menu is only accessible, if the unit is equipped with an

    optional CCN/clock board.

    DATE & TIME CONFIGURATION SUB-MENU

    ITEM FORMAT COMMENTS

    0 dAtE MEnu When selected this item authorises return to theprevious menu.

    1 n1n

    2n

    3n

    4Current timesetting.

    00:00 to 23:59 n1n2: hours (00 to 23). The first time the Enter button iscontinuously pressed, the first two characters in the

    4-digit display flash so that hours can be adjusted.n

    3n

    4: minutes (00 to 59). Continuous pressing of the

    Enter key again causes the last two characters to flashand minutes can be adjusted.

    2 Current day of weeksetting.

    Mon MondaytUe Tuesday

    uEd WednesdaytHu Thursday

    FrI FridaySAt Saturday

    Sun Sunday

    3 n1n

    2n

    3n

    4Current day and monthsetting.

    01:01 to 31:12 n1n

    2:day (01 to 31). The first time the Enter button is

    continuously pressed, the first two characters in the 4-digit display flash so that day can be adjusted.n

    3n

    4:month (01 to 12). Continuous pressing of the

    Enter key again causes the last two characters to flash

    so that month can be adjusted.

    4 nnnn Current year setting.

    PERIOD X CONFIGURATION SUB-MENUS (X = 1 TO 8)

    ITEM # FORMAT COMMENTS

    0 Period X Menu Indicates the period (X) you are going toconfigure. When selected this item authorises areturn to the main menu.

    1 n1n

    2n

    3n

    4Occupied period - Start time*.

    00:00 to 24:00 Authorises entering the time of day at which theoccupied period starts.

    2 n1n2n3n4 Occupied period - End time*.00:00 to 24:00 Authorises entering the time of day at which the

    occupied period ends.

    3 Mo- 0 or Mo- 1 1 = the period is in effect on Monday.

    0 = period not in effect on Monday4 tu- 0 or tu- 1 1 = the period is in effect on Tuesday.

    0 = period not in effect on Tuesday.

    5 UE-0 or UE- 1 1 = the period is in effect on Wednesday.

    0 = period not in effect on Wednesday.

    6 tH- 0 or tH- 1 1 = the period is in effect onThursday.0 = period not in effect on Thursday.

    7 Fr-0 or Fr- 1 1 = the period is in effect on Friday.0 = period not in effect on Friday.

    8 SA- 0 or SA- 1 1 = the period is in effect on Saturday.0 = period not in effect on Saturday.

    9 Su- 0 or Su- 1 1 = the period is in effect on Sunday.0 = period not in effect on Sunday.

    10 Ho- 0 or Ho- 1 1 = the period is in effect on publicholidays.0 = period not in effect on public holidays.

    Legend* n

    1n

    2: hours (00 to 24). The first time the Enter button is continuously pressed,

    the first two characters in the 4-digit display flash so that hours can beadjusted.n

    3n

    4: minutes (00 to 59). Continuous pressing of the Enter key again causes

    the last two characters to flash so that minutes can be adjusted.

    Typical timer program:

    24

    23

    22

    21

    P6P320

    P319

    P318

    P3P2P217

    P4P4P3P2P216

    P4P4P3P2P215

    P4P4P3P2P214

    P4P4P3P2P213

    P4P4P3P2P212

    P5P4P4P3P2P211

    P5P4P4P3P2P210

    P5P4P4P3P2P29

    P5P4P4P3P2P28

    P5P4P4P3P2P27

    6

    5

    4

    3

    P12

    P11

    P10

    HOLSUNSATFRITHUWESTUEMONTime

    Occupied

    Unoccupied

    MON : MondayTUE : Tuesday

    WED : WednesdayTHU : ThursdayFRI : FridaySAT : Saturday

    SUN : Sunday

    HOL : Public holidays

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    19/2619

    BROADCAST CONFIGURATION SUB-MENU

    ITEM # FORMAT COMMENTS

    0 broAdCASt MEnu When selected this item authorises a return to the main menu.

    1 YES/no Determines whether or not the unit is a broadcast acknowledgerwhen the unit is connected on a CCN network. There must beonly one broadcast acknowledgerin a CCN.

    Warning: if the unit operates in standalone mode (not CCN connected) this choice must be set to Yesif the holiday function is used(see section 4.3.11.6) or if you want to configure the daylight saving time function.

    2 YES/no This item authorises enabling or disabling the Broadcast function. When it is set to Yes, the control will make a periodicbroadcast on the CCN. When it is set to No, the control is not the broadcaster and there is no need to configure the other choice inthis table. There must be only one broadcaster in a CCN and this item should not be configured if any other system element is

    acting as broadcaster.

    Warning: if the unit operates in standalone (not CCN connected) this choice must be set to Yesif the holiday function is used (see

    section 4.3.11.6) or if you want to configure the daylight saving time function.

    3 nnn OAT Broadcaster bus number: it is the bus number of the system that has the outside air temperature sensor connected to it.

    0 to 239 Used for CCN network function only.

    4 nnn OAT Broadcaster element number: it is the element number of the system element that has the outside air temperature sensor0 to 230 connected to it. Used for CCN network function only.

    5 nn Daylight saving start month. In this mode you enter the month in which the broadcaster will adjust its time for the start of1 to 12 daylight saving time.

    6 nn Daylight saving start day. In this mode you enter the day on which the broadcaster will adjust its time for the start of daylight

    1 to 31 saving time.

    7 n1n

    2n

    3n

    4Authorises entering the hours and minutes for saving start . In this mode you enter the time of day when the broadcaster will

    00:00 to 24:00 adjust its time for the start of daylight saving time.

    n1n

    2: hours (00 to 24). The first time the Enter button is continuously pressed, the first two characters in the 4-digit display flash so

    that hours can be adjusted.n

    3n

    4: minutes (00 to 59). Continuous pressing of the Enter key again causes the last two characters to flash so that minutes can be

    adjusted.

    8 nnnn Daylight saving start minutes to add: number of minutes by which the broadcaster will adjust its time for the start of daylight1 to 1440 minutes saving time.

    9 nn Daylight saving stop month. In this mode you enter the month in which the broadcaster will adjust its time for the end of1 to 12 daylight saving time.

    10 nn Daylight saving stop day. In this mode you enter the day on which the broadcaster will adjust its time for the end of daylight1 to 31 saving time.

    11 n1n

    2n

    3n

    4Authorises entering the hours and minutes for saving stop. In this mode you enter the time of day when the broadcaster

    00:00 to 24:00 will adjust its time for the end of daylight saving time.

    n1n2: hours (00 to 24). The first time the Enter button is continuously pressed, the first two characters in the 4-digit display flash sothat hours can be adjusted.n

    3n

    4: minutes (00 to 59). Continuous pressing of the Enter key again causes the last two characters to flash so that minutes can be

    adjusted.

    12 nnnn Daylight saving start minutes to subtract: number of minutes by which the broadcaster will adjust its time for the end of

    1 to 1440 minutes dayl ight saving time.

    HOLIDAY PERIOD X CONFIGURATION SUB-MENUS (X = 1 TO 16)

    ITEM # FORMAT COMMENTS

    0 HoLidAy X Sub-menu When selected this i tem authorises a return

    to the configuration menu.

    1 0 to 12 Start month of public holiday period0 = period not in use

    1 = January, 2 = February, etc.

    2 0 to 31 Start day of public holiday period. 0 periodnot in use.

    3 0 to 99 days Duration of the public holiday period indays.

    Typical programming for public holidays:A public holiday period lasting 1 day on 20th May, for instance, is configured as

    follows: start month = 5, start day = 20, duration = 1A public holiday period lasting 2 day on 25th May, for instance, is configured as

    follows: start month = 5, start day = 25, duration = 2

    4.3.11.8 - Description of the Broadcast sub-menuThe controller provides a broadcast configuration menu which

    you can use to configure the unit to be the CCNs broadcaster,

    responsible for transmitting the time, outdoor temperature, and

    holiday flags to all system elements.

    This menu also authorises setting the date of the daylight

    saving time. There should be only one broadcaster in a CCN, sothis table should not be configured if any other system element

    is acting as broadcaster. These menus are only accessible, if the

    unit is equipped with an optional CCN/clock board.

    ATTENTION: If the unit operates in standalone mode (not

    CCN connected) this menu can also must be used if the holi-

    day function is used or to correct for daylight saving time.

    4.3.11.7 - Description of the Holidays sub-menusThis function is used to define 16 public holiday periods. Each

    period is defined with the aid of three parameters: the month,

    starting day and duration of the public holiday period. During

    these public holidays the controller will be in occu-pied or

    unoccupied mode, depending on the programmed periods

    validated for public holidays (see section 4.3.11.6).

    Each of these public holiday periods can be displayed and changed

    with the aid of a sub-menu. These menus are only accessible,

    if the unit is equipped with an optional CCN/clock board.

    ATTENTION: The broadcast function must be activated to

    utilise the holiday schedule, even if the unit is running in stand-

    alone mode (not connected to CCN). See section 4.3.11.8.

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    20/2620

    ITEM #

    0 [1]

    1 [1]

    2 [1]

    3 [1]

    4 [1]

    5 [1]

    FORMAT

    X ALArMrESEt ALArM

    1 to 55

    1 to 55

    1 to 55

    1 to 55

    1 to 55

    COMMENTS

    X alarms are activeReset of alarms is requested

    To reset all active alarms, continuously pressthe Enter key. rESET ALArMis then displayed.

    Press the select key again: all alarms are reset.

    Current alarm code 1*

    Current alarm code 2*

    Current alarm code 3*

    Current alarm code 4*

    Current alarm code 5*

    4.3.12 - Description of the Alarms menuThis menu is used to display and reset up to 5 active alarms. It

    also permits alarm reset. If no alarm is active this menu is not

    accessible. See section 6 for a complete description of the

    alarm codes and alarm reset.

    1 This item is masked when nilNOTE* Pressing the Enter key when alarm code is displayed causes the following

    message to be scrolled:

    time of alarmdate of alarmfull CCN alarm message- time of alarm: hh-mm

    - date: dd-mm- full CCN alarm message: up to 64 characters

    Time and date are displayed if the unit is equipped with an optional CCN/clock board.

    1 This item is masked when nilNOTE

    * Pressing the Enter key when alarm code is displayed causes the followingmessage to be scrolled:time of alarmdate of alarmfull CCN alarm message

    - time of alarm: hh-mm- date: dd-mm

    - full CCN alarm message: up to 64 charactersTime and date are displayed if the unit is equipped with an optional CCN/

    clock board.

    4.3.13 - Description of the Alarms History menu

    ALARMS MENU

    ITEM #

    1 [1]

    2 [1]

    3 [1]4 [1]

    5 [1]

    6 [1]

    7 [1]

    8 [1]

    9 [1]

    10 [1]

    FORMAT

    1 to 55

    1 to 55

    1 to551 to 55

    1 to 55

    1 to 55

    1 to 55

    1 to 55

    1 to 55

    1 to 55

    COMMENTS

    Alarm history code 1*

    Alarm history code 2*

    Alarm history code 3*Alarm history code 4*

    Alarm history code 5*

    Alarm history code 6*

    Alarm history code 7*

    Alarm history code 8*

    Alarm history code 9*

    Alarm history code 10*

    ALARMS HISTORY MENU

    4.3.14.2 - Maintenance menu descriptionTo be active, the maintenance function must be preset in the

    Service configuration.

    ITEM # FORMAT DESCRIPTION

    0 MAintEnAnCE MEnu When selected this item authorises return to the

    previous menu.

    1[1] 0 to 6,10 Reset maintenance alert.

    2[1] ALErt Water flow rate to low.

    3[1] nnn/ALErt Next primary pump maintenance operation in nnndays. 'ALErt' is displayed, when the delay before

    maintenance has elapsed.4[1] nnn/ALErt Next water filter maintenance operation in nnn

    days. 'ALErt' is displayed, when the delay before

    maintenance has elapsed.

    Legend1 This item is masked when not used.

    4.3.14 - Runtime menu description

    RUNTIMES

    RUNTIMES 1

    [runtiMES 1]

    MAINTENANCE

    [MAintEnAnCE]

    NOTE: The items in brackets show what is displayed on the

    user interface.

    1 This item is masked when not used

    NOTES* Certain values are divided by 10 or by 100, so that number of hours or start-

    ups of less then 10 are displayed as 0.

    When the value is divided by 10 or by 100 it is displayed in turn with M 10orM100.

    ITEM #

    0

    1

    2 [1]

    3 [1]

    4

    5

    6

    7

    8

    9

    10

    11

    12 [1]

    13 [1]

    14 [1]

    FORMAT

    -

    nnnn | M 10 | M100

    nnnn | M 10 | M100

    nnnn | M 10 | M100

    nnnn | M 10 | M100

    nnnn | M 10 | M100

    nnnn | M 10 | M100

    nnnn | M 10 | M100

    nn

    nn

    nn

    nn

    nnnn | M 10 | M100

    nnnn | M 10 | M100

    nnnn | M 10 | M100

    UNITS

    -

    hrs/10 or 100

    hrs/10 or 100

    hrs/10 or 100

    hrs/10 or 100

    hrs/10 or 100

    -/10 or 100

    -/10 or 100

    -

    -

    -

    -

    hrs/10 or 100

    hrs/10 or 100

    hrs/10 or 100

    COMMENTS

    When selected this itemauthorises return to the

    previous menu

    Unit operating hours*

    Unit operating hour in cooling

    mode

    Unit operating hours in heatingmode

    Compressor operatinghours*

    Machine starts*

    Compressor starts*

    Pump #1 operating hours*

    Compressor cycle during

    last hour

    Compressor average cycleduring last 24 hours

    Compressor runtime in hours

    Compressor runtime during

    last 24 hours

    Boiler operating hours

    Electric heating operating

    hours

    Number of defrost cycles

    4.3.14.1 - Description of the Runtimes menu

    RUNTIMES MENU [2]

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    21/2621

    The table below, summarizes the unit ON/OFF and control type status with regard to the following:

    ccn_sw: CCN operation switch selector

    onoff_sw: remote START/STOP when the unit is under remote operating mode

    CHIL_S_S: CCN chiller START/STOP forced command

    chil_occ: chiller occupied status. Used when the clock function is enabled (ccnclock = yes) otherwise chil_occ shall be

    forced occupied all the time

    EMSTOP: CCN emergency stop command

    Alarm shutdown unit totally stopped due to a failure

    5 - USE OF THE PRO-DIALOG CONTROL SYSTEM

    PARAMETERS STATUS Active

    chil_occ Alarm control Unit

    ccn_sw CHIL_S_S onoff_sw state EMSTOP shutdown type state

    - - - - Enabled - - Off

    - - - - - Yes - Off

    Open - Open - - - Remote Off

    Open - - Unoccupied - - Remote Off

    Closed Disabled - - - - CCN Off

    Closed - - Unoccupied - - CCN Off

    Open - Closed Occupied Disabled No Remote On

    Open - Closed Occupied Disabled No Remote OnOpen - Closed Occupied Disabled No Remote On

    Closed Enabled - Occupied Disabled No CCN On

    Note: When switching from one control type (Remote or CCN) to another control type or switching from heating to cooling orvice-versa then, the unit shall do a transition through the OFF state before being allowed to start again. At this time, the

    On to OFF delay is always applied.

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    22/2622

    The following table summarises the possible selections

    depending on the control types (remote or CCN) and the

    following parameters:

    Heating/cooling operating mode Control contact 3:status of control contact 3. Contol contact 3 selection:this selection, indicates if

    contact 3 is used for dual setpoint control or for demand

    limit control (see User Configuration menu, section

    4.3.11).

    Schedule 2 status:schedule for setpoint selection. See

    section 4.3.11.6.

    5.2 - Evaporator water pump controlThe unit controls one evaporator water pump. The evaporator

    water pump is turned on when this option is configured (see

    User configuration) and when the unit is in one of the on modes

    described above or in delay mode. Since the minimum value for

    the delay at start-up is 1 minute (configurable between 1 and 15

    minutes), the pump will run for at least one minute before the

    first compressor starts. The pump is kept running for 20 seconds

    after the unit goes to stop mode. The pump keeps working

    when the unit switches from heating to cooling mode or vice-

    versa. It is turned off if the unit is shut down due to an alarmunless the fault is a frost protection error. The pump can be

    started in particular operating conditions when the evaporator

    heater is active (see section 5.3).

    The control provides a means to automatically start the pump

    each day at 14.00 hours for 2 seconds when the unit is off, if

    configurated. Starting the pump periodically for few seconds

    increases the life-time of the pump bearings and the tightness

    of the pump seal.

    5.1 - Heating/cooling operation

    5.1.1 - GeneralThe heating/cooling selection applies to 30RA (liquid chillers)

    units, controlling a boiler and to 30RH (heat pumps) units.

    Heating/cooling control can be automatic or manual.

    If the unit is in standby it does not cool or heat, and no

    compressor can be activated.

    The table below, summarizes the unit HEAT/COOL mode with

    regard to the following parameters:

    status: unit ON/OFF status

    ctrl_typ: unit control type

    hc_sw: switch control status when the unit is under remote

    operating mode

    HC_SEL: HEAT/COOL select while running in CCN

    control type

    Note: A cooling only unit (A/C) with no boiler option, operatesalways in cooling mode.

    When an heat pump unit (HP) operates in cooling mode or

    it is in defrost cycle, the reversing valve will be powered.

    The valve will not be powered in heating mode.

    Valve position will be modified when unit capacity is 0%.

    Unit status and Parameters Operating control type status mode

    status ctrl_typ hc_sw HC_SEL

    Off - - - Cooling

    On Remote Open - Cooling

    On Remote Closed - Heating

    On CCN - Cooling Cooling

    On CCN - Heating Heating

    On CCN - Both Both

    5.3 - Evaporator heater control (Option)

    The evaporator heater can be energised to protect an evaporator

    that can be damaged by freezing, if the unit is shut down for a

    long time at low outdoor temperature. The evaporator pump

    can be started, if conditions get worse.

    NOTE: Evaporator heater control parameters can be

    modified, using the Service configuration.

    5.4 - Control point

    The control point represents the water temperature that the unit

    must produce. The inlet water is controlled by default, but the

    outlet water can also be controlled (requires a Service

    configuration modification).

    Control point = active setpoint + reset

    5.4.1 - Active setpointTwo setpoints can be selected as active in cooling mode and

    three in heating mode. Usually, the second cooling setpoint isused for unoccupied periods or for ice storage (brine unit). The

    second setpoint in heating mode is used for unoccupied

    periods, and the third heating setpoint is used for holiday

    periods or public holidays. Depending on the current opera-

    tions, the active setpoint can be selected by choosing the item

    in the Information menu, with the users volt-free contacts,

    with network commands or with the setpoint timer program

    (schedule 2).

    HEATING/COOLINGOPERATING MODE

    Cooling

    Cooling

    Heating

    Heating

    Heating

    SCHEDULE 2STATUS

    Occupied

    Unoccupied

    Occupied

    Unoccupied

    Holiday

    ACTIVE SETPOINT

    Cooling setpoint 1

    Cooling setpoint 2

    Heating setpoint 1

    Heating setpoint 2

    Heating setpoint 3

    CCN OPERATING MODE

    PARAMETER STATUS

  • 7/25/2019 Carrier Service-Interface 30RA RH 005-013

    23/2623

    HEATING/COOLINGOPERATING MODE

    Cooling

    Cooling

    Cooling

    Cooling

    Heating

    Heating

    HeatingHeating

    Heating

    CONTROL CONTACT 3SELECTION

    Setpoint

    Setpoint

    Demand limit

    Demand limit

    Setpoint

    Setpoint

    Demand limitDemand limit

    Demand limit

    CONTROL CONTACT 3

    Setpoint 1

    Setpoint 2

    -

    -

    Setpoint 1

    Setpoint 2

    --

    -

    SCHEDULE 2 STATUS

    -

    -

    Occupied

    Unoccupied

    -

    -

    OccupiedUnoccupied

    Holiday

    ACTIVE SETPOINT

    Cooling setpoint 1

    Cooling setpoint 2

    Cooling setpoint 1

    Cooling setpoint 2

    Heating setpoint 1

    Heating setpoint 2

    Heating setpoint 1Heating setpoint 2

    Heating setpoint 3

    REMOTE OPERATING MODE

    PARAMETER STATUS

    %Buildingload

    5.4.2 - ResetReset means that the active setpoint is modified so that less

    machine capacity is required (in cooling mode, the setpoint is

    increased, in heating mode it is decreased). This