catalog et b1 • 2009/2010 en - siemens · 7kt1 14 e-counters siemens et b1 · 10/2008 12/3 12 ......

12
Siemens ET B1 · 10/2008 12 12 12/2 Product overview 12/3 7KT1 14 E-counters 12/5 7KT1 11, 7KT1 12 digital measuring devices 12/7 7KT1 0 analog measuring devices 12/8 7KT5 8 time and pulse counters 12/10 7KT5 5, 7KT5 6 time counters for front-panel mounting BETA Measuring Single-Phase Measuring Devices © Siemens AG 2008 © Siemens AG 2008

Upload: lebao

Post on 26-Feb-2019

226 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Catalog ET B1 • 2009/2010 EN - Siemens · 7KT1 14 E-counters Siemens ET B1 · 10/2008 12/3 12 ... 7KT1 140 Standards EN 62053-31, EN 50740-1, EN 50470-3 Supply † Rated control

Siemens ET B1 · 10/2008

12

12

12/2 Product overview

12/3 7KT1 14 E-counters

12/5 7KT1 11, 7KT1 12 digital measuring devices

12/7 7KT1 0 analog measuring devices

12/8 7KT5 8 time and pulse counters

12/10 7KT5 5, 7KT5 6 time counters for front-panel mounting

BETA MeasuringSingle-Phase Measuring Devices

ET_B1_2009_en.book Seite 1 Freitag, 12. Dezember 2008 9:47 09

© Siemens AG 2008© Siemens AG 2008

Page 2: Catalog ET B1 • 2009/2010 EN - Siemens · 7KT1 14 E-counters Siemens ET B1 · 10/2008 12/3 12 ... 7KT1 140 Standards EN 62053-31, EN 50740-1, EN 50470-3 Supply † Rated control

BETA MeasuringSingle-Phase Measuring Devices

Product overview

12/2 Siemens ET B1 · 10/2008

12

■ Overview

Devices Page Field of application Standards Used in

Non

-res

iden

tial

bui

ldin

gs

Res

iden

tial

bui

ldin

gs

Ind

ustr

y

7KT1 14 E-counters 12/3 For the measurement of kWh in single-phase systems, e.g. in industrial plants, offices and apartments in apartment houses

EN 50740-1, EN 50470-3, EN 62053-31

✓ ✓ ✓

7KT1 11, 7KT1 12 digital measuring devices

12/5 Voltage and current measurement with large 3-digit LEDs for monitoring incoming and outgoing currents as well as device currents in order to prevent plant overload.

DIN 43751-1, DIN 43751-2

✓ -- ✓

7KT1 0 analog measuring devices 12/7 Voltage and current measurement for monitoring incoming and outgoingcurrents as well as device currents in order to prevent plant overload.

IEC 60051-2,EN 60051-2

✓ -- ✓

7KT5 8 time and pulse counters 12/8 For monitoring operating hours and starting operations for planning preventative maintenance tasks and preventing sudden shutdowns

IEC 60255-6,EN 60255-6, (VDE 0435-301), UL 94

✓ ✓ ✓

7KT5 5, 7KT5 6 time counters for front-panel mounting

12/10 For monitoring operating hours and starting operations for planning preventative maintenance tasks and preventing sudden shutdowns.

IEC 60255-6,EN 60255-6 (VDE 0435-301)

✓ ✓ ✓

ET_B1_2009_en.book Seite 2 Freitag, 12. Dezember 2008 9:47 09

© Siemens AG 2008© Siemens AG 2008

Page 3: Catalog ET B1 • 2009/2010 EN - Siemens · 7KT1 14 E-counters Siemens ET B1 · 10/2008 12/3 12 ... 7KT1 140 Standards EN 62053-31, EN 50740-1, EN 50470-3 Supply † Rated control

BETA MeasuringSingle-Phase Measuring Devices

7KT1 14 E-counters

12/3Siemens ET B1 · 10/2008

12

■ Overview

E-counters serve the measurement of kWh in single-phase systems, e.g. in industrial plants, offices and apartments in apartment houses.

■ Benefits

• The accuracy class 1 according to EN 50470-3 ensures that you always have the correct measured value

• The drum-type register in digit size 3.8 mm × 1.5 mm enables easy reading

• The short-circuit resistant pulse output protects the device if it is assembled incorrectly.

■ Technical specifications

7KT1 140

Standards EN 62053-31, EN 50740-1, EN 50470-3

Supply

• Rated control voltage Un V AC 230

• Operating range V 184 ... 276

• Rated frequency Hz 50/60

• Operating frequency range Hz 45 ... 65

• Rated power dissipation Pv W ≤ 0.6

Measuring inputs

• Connection type Direct

• Voltage V 230

• Operating range voltage V 184 ... 276

• Current A 75

• Operating range current Direct connection A 0.025 ... 75

• Minimum operational current mA 25

• Frequency Hz 50/60

• Operating frequency range- Distortion factor ≤ 3 %; symmetric sinus curve Hz 45 ... 65

Overload capability

• Voltage Ue Continuous: phase/N V 276Short-time (1 s) V 300

• Current Ie Continuous A 75Short-time (10 ms) A 2250

Display

• Rate 1 rate

• Active energy Drum-type register H × W: mm × mm 3.8 × 1.57-digit with 1 decimal 0 ... 999999.9

Measuring accuracy At 23 °C ±1 °C

Active energy Acc. to EN 50470-3 % ±1

Safety Acc. to EN 62052-11

• Separation of current and voltage circuit Electrical

• Rated insulation voltage V 300

• Rated impulse withstand voltage 1.2/50 μs kV 6

• Overvoltage category 4

Pulse output

• S0 interface acc. to EN 62053-31 IR test output LED Imp/kWh 1000Terminals, output Imp/kWh 10Pulse duration ms 100 ±5

Minimum interval between 2 pulses ms 125Required voltage V DC 5 ... 30Permissible current mA 90

Terminals

• Main current paths ± screw (Pozidriv) 2

• S0 interface/control terminals Blade for slotted screw mm 0.8 × 3.5

• Conductor cross-sections,main current paths

Rigid mm2 1.5 ... 35Flexible, with end sleeve mm2 1.5 ... 35

• Conductor cross-sections S0 interface/control terminals

Rigid mm2 0.14 ... 2.5Flexible, with end sleeve mm2 0.14 ... 1.5

Ambient conditions

• Temperature Storage °C -25 ... +70Operation °C -10 ... +55

• Relative air humidity Storage % ≤ 80Operation % ≤ 80

• Maximum vibration Sinus amplitude at 50 Hz mm ±0.075

• Degree of protection IP20, with connected conductors

ET_B1_2009_en.book Seite 3 Freitag, 12. Dezember 2008 9:47 09

© Siemens AG 2008© Siemens AG 2008

Page 4: Catalog ET B1 • 2009/2010 EN - Siemens · 7KT1 14 E-counters Siemens ET B1 · 10/2008 12/3 12 ... 7KT1 140 Standards EN 62053-31, EN 50740-1, EN 50470-3 Supply † Rated control

BETA MeasuringSingle-Phase Measuring Devices

7KT1 14 E-counters

12/4 Siemens ET B1 · 10/2008* You can order this quantity or a multiple thereof.

12

■ Selection and ordering data

■ Dimensional drawings

■ Schematics

Uc Ie Ue MW DT Order No. Priceper PU

PG PU PS*/P. unit

Weightper PUapprox.

V AC A AC V AC Unit(s) Unit(s) kg

E-counters for active energy

With 7-digit drum-type register, with S0 interface, for single-phase operation

Direct connection, single rate

230 63 230 2 B 7KT1 140 027 1 1 0.400

7KT1 140

45 90

I2_1

6002

6444636

1 3

L1 L1 N

7KT1 140

1 3

L1 N

L1N

63 A

L1

I2_1

6003

kWh

T1

230 V AC

ET_B1_2009_en.book Seite 4 Freitag, 12. Dezember 2008 9:47 09

© Siemens AG 2008© Siemens AG 2008

Page 5: Catalog ET B1 • 2009/2010 EN - Siemens · 7KT1 14 E-counters Siemens ET B1 · 10/2008 12/3 12 ... 7KT1 140 Standards EN 62053-31, EN 50740-1, EN 50470-3 Supply † Rated control

BETA MeasuringSingle-Phase Measuring Devices

7KT1 11, 7KT1 12 digital measuring devices

12/5Siemens ET B1 · 10/2008

12

■ Overview

These devices for measuring voltages and currents can be used for monitoring input and output currents or device currents in electric plants. They are suitable for direct connection in a single-phase system or for three-phase systems when used in conjunction with a measuring selector switch.

The measuring ranges of the ammeter are set at the device with a coding switch.

■ Benefits

• The ammeters have 14 measuring ranges from 0 ... 20 A to 0 ... 999 A, which can be set using a coding switch. This ensures universal application.

■ Technical specifications

7KT1 110 7KT1 120

Standards DIN 43751-1, -2

Rated control supply voltage Uc V AC 230

Operating range × Uc 0.9 ... 1.15

Rated frequency Hz 45 ... 65

Rated operational power Ps VA < 2

Measuring range

• Voltage Direct measurement V AC 12 ... 600 --

• Current Direct measurement A AC -- 0.4 ... 20 directTransformer measurement A AC -- 0.1 ... 1000/5

Display 3 LED red; height 10 mm

• Voltage > 600 V H H H --< 12 V -- -- -- --

• Current Direct > 20 A -- H H HTransformer > 5 A -- H H H

Direct < 0.4 A -- -- -- --Transformer < 0.1 A -- -- -- --

Measuring cycle /s 4 times

Measuring accuracy At 23 °C % ±0.5 ±1 digit

Temperature influence %/°C ±0.03

Overload capability

• Voltage Continuous V 720 --Short-time for 1 s V 780 --

• Current Continuous, direct A -- 22Continuous, transformer A -- 5.5

Short-time for 1 s, direct A -- 200Short-time for 1 s, transformer A -- 50

Electrical isolation• Clearances mm ≥ 3 ≥ 1.5• Creepage distances in the device mm ≥ 4.3 ≥ 2.1• Creepage distances on the printed board Printed boards not installed mm ≥ 3.0 ≥ 1.5

Test voltage 50 Hz, 1 min kV 2.2 1.35

Terminals ± screw (Pozidriv) 1

Conductor cross-sections Rigid, max. mm2 1 × 6/2 × 4Flexible, with end sleeve, min. mm2 0.75

Permissible ambient temperature °C -10 ... +55

Degree of protection IP20, with connected conductors

ET_B1_2009_en.book Seite 5 Freitag, 12. Dezember 2008 9:47 09

© Siemens AG 2008© Siemens AG 2008

Page 6: Catalog ET B1 • 2009/2010 EN - Siemens · 7KT1 14 E-counters Siemens ET B1 · 10/2008 12/3 12 ... 7KT1 140 Standards EN 62053-31, EN 50740-1, EN 50470-3 Supply † Rated control

BETA MeasuringSingle-Phase Measuring Devices

7KT1 11, 7KT1 12 digital measuring devices

12/6 Siemens ET B1 · 10/2008* You can order this quantity or a multiple thereof.

12

■ Selection and ordering data

■ Dimensional drawings

■ Schematics

Switching examples

■ More informationRange selector switch for 7KT1 120 digital ammeter

Ue Ie Uc MW DT Order No. Priceper PU

PG PU PS*/P. unit

Weightper PUapprox.

V AC A AC V AC Unit(s) Unit(s) kg

Digital voltmeters

230 600 2 B 7KT1 110 027 1 1 0.190

Digital ammeters for direct and transformer connection

230 0 ... 20 transformer /5

2 B 7KT1 120 027 1 1 0.200

7KT1 110, 7KT1 120

45 90

I2_0

7806

b

64447

1 2 3 4 5

36

Digital voltmeters Digital ammeters

7 KT1 110

I2_0

7833

b

1 2 3 4 5

L N230 V AC

7 KT1 110

I2_0

7834

c

1 2 3 4 5

L1 N L2 N230 V AC max. 600 V AC

L N

7 KT1 120

I2_0

7835

c

1 2 3 4 5

N

Direct connectionup to 20 A

230 V AC NL1 N

7 KT1 120

1 2 3 4 5

L2

I2_0

7836

c

230 V AC

Direct connectionof different phasesup to 20 A

L1 N

7 KT1 120

1 2 3 4 5

L2

I2_0

7837

c

230 V AC

Transformer connectionTransformer …/5 A

1 2 3 4

0

1I2_00183c

1 2 3 4

0 0 0 0

1 0 0 0 25/5 A AC

20 A AC

40/5 A AC50/5 A AC60/5 A AC80/5 A AC

100/5 A AC150/5 A AC 999/5 A AC

800/5 A AC600/5 A AC500/5 A AC400/5 A AC250/5 A AC200/5 A AC0 0 0 1

1 0 0 10 1 0 11 1 0 10 0 1 11 0 1 10 1 1 1

0 1 0 0

0 0 1 01 0 1 00 1 1 01 1 1 0

1 1 0 0

Direct measurement

Transformer measurement

ET_B1_2009_en.book Seite 6 Freitag, 12. Dezember 2008 9:47 09

© Siemens AG 2008© Siemens AG 2008

Page 7: Catalog ET B1 • 2009/2010 EN - Siemens · 7KT1 14 E-counters Siemens ET B1 · 10/2008 12/3 12 ... 7KT1 140 Standards EN 62053-31, EN 50740-1, EN 50470-3 Supply † Rated control

BETA MeasuringSingle-Phase Measuring Devices

7KT1 0 analog measuring devices

12/7Siemens ET B1 · 10/2008* You can order this quantity or a multiple thereof.

12

■ Overview

These devices for measuring voltages and currents can be used for monitoring input and output currents or device currents in electric plants. They are suitable for direct connection in asingle-phase system or for three-phase systems when used in conjunction with a measuring selector switch.

■ Benefits

• The 7KT1 020 ammeters can be equipped with changeable scales for primary currents of 60, 150 or 400 A AC, depending on the transformer ratio of the installed current transformer. The changeable scales are included in delivery. This ensures universal application

• Permanent overload up to 20 % does not damage the device. Protection for your plant.

■ Technical specifications

■ Selection and ordering data

■ Dimensional drawings ■ Schematics

Terminals

7KT1 000 7KT1 01. 7KT1 020

Standards EN 60051-2

Measuring ranges• Direct measurement V AC 0 ... 500 -- --

A AC -- 0 ... 25 --A AC -- 0 ... 40 --A AC -- 0 ... 60 --

• Transformer measurement A AC -- -- 0 ... 150/5

Max. permissible measuring frequency Hz 45 ... 65

Display Pointer

Measuring accuracy At 23 ±1 °C % ±1.5 ±3 ±1.5

Rated operational power Ps VA < 2 < 1.1

Temperature influence %/°C ±0.03

Overload capability Continuous 1.2 × Umeas 1.2 × ImeasShort-time for 1 s 2 × Umeas 10 × Imeas

Test voltage 50 Hz, 1 min kV > 2

Terminals ± screw (Pozidriv) 1 2 1

Conductor cross-sections Rigid, max. mm2 1 × 6/2 × 4 1 × 25/2 × 16 1 × 6/2 × 4Flexible, with end sleeve, min. mm2 0.75 0.75

Permissible ambient temperature °C -10 ... +55

Degree of protection IP20, with connected conductors

Umeas Imeas MW DT Order No. Priceper PU

PG PU PS*/P. unit

Weightper PUapprox.

V AC A AC Unit(s) Unit(s) kg

Analog voltmeters

500 4 B 7KT1 000 027 1 1 0.105

Analog ammeters for direct connection

25 4 B 7KT1 010 027 1 1 0.11040 B 7KT1 011 027 1 1 0.12560 B 7KT1 012 027 1 1 0.135

Analog ammeters for transformer connection with 3 different interchangeable scales

0 ... 60 A,0 ... 150 A and0 ... 400 A

0 ... 60/5 0 ... 150/5 0 ... 400/5

4 B 7KT1 020 027 1 1 0.105

7KT1 000 7KT1 01., 7KT1 020

45 86

I2_1

1611

b

64446

6 7

70

5 7

70

7KT1 000 7KT1 01., 7KT1 020

ET_B1_2009_en.book Seite 7 Freitag, 12. Dezember 2008 9:47 09

© Siemens AG 2008© Siemens AG 2008

Page 8: Catalog ET B1 • 2009/2010 EN - Siemens · 7KT1 14 E-counters Siemens ET B1 · 10/2008 12/3 12 ... 7KT1 140 Standards EN 62053-31, EN 50740-1, EN 50470-3 Supply † Rated control

BETA MeasuringSingle-Phase Measuring Devices

7KT5 8 time and pulse counters

12/8 Siemens ET B1 · 10/2008

12

■ Overview

Time and pulse counters are used for the reliable monitoring of production and service times, which enables the exact planning and monitoring of production sequences, maintenance cycles and warranty times.

As well as the proven electromechanical time and pulse counters for mounting in distribution boards, we also supply digital time and pulse counters.

The fields of application for both counter types are very diverse, such as the recording of operating hours of machines, systems or building management systems, as well as pulse counting for general volume flow counting, registration of starting frequencies, starting cycles or production quantities in systems and machines.

■ Benefits

• Time and pulse counters help to plan maintenance intervals and ensure high plant availability

• Versions without zero position and with electric or manual zero position for all applications

• Flexible application of the digital counters for power supplies of 12 to 150 V DC and 24 to 240 V AC in a single device.

■ Technical specifications

7KT5 801 7KT5 802 7KT5 803 7KT5 804 7KT5 806 7KT5 807

Standards DIN VDE 0435-110; EN 60255-6; UL 863Approved acc. to UL 863, UL File No. E300537, CSA C22.2 No. 6 and 55

Rated control supply voltage Uc V AC -- 24 115 230 115 230V DC 12 ... 24 --

Operating range At 50/60 Hz × Uc 0.9 ... 1.1

Rated frequency Hz -- 50 60

Rated power dissipation Pv VA < 1 < 2

Method of operation Counting of Hours

Display Drum-type register h 00000.00

Terminals ± screw (Phillips) 1

Conductor cross-sections Rigid mm2 1.5 Flexible, with end sleeve, min. mm2 0.75

Permissible ambient temperature °C -10 ... +70

Degree of protection Acc. to EN 60529 IP20, with connected conductors

Safety class Acc. to EN 61140/VDE 0140-1 II

Permissible humidity % < 80

7KT5 811 7KT5 812 7KT5 814 7KT5 821 7KT5 822 7KT5 823 7KT5 833

Standards DIN VDE 0435-110; EN 60255-6; UL 863Approved acc. to UL 863, UL File No. E300537, CSA C22.2 No. 6 and 55

Rated control supply voltage Uc V AC -- 24 230 24 ... 240V DC 12 ... 24 -- -- 12 ... 150

Operating range At 50/60 Hz × Uc 0.9 ... 1.1

Rated frequency Hz -- 50/60

Rated power dissipation Pv VA < 1 < 2 < 1

Method of operation Counting of Pulses Hours Pulses

Display Drum-type register 0000000 -- --LCD h -- 000000.0 --

-- -- 0000000

Counting frequency Hz 10 -- 10

Pulse duration ms 50 -- 50

Resetting Electrical -- YesMechanical -- Yes

Terminals ± screw (Phillips) 1

Conductor cross-sections Rigid mm2 1.5Flexible, with end sleeve, min. mm2 0.75

Permissible ambient temperature °C -10 ... +70

Degree of protection Acc. to EN 60529 IP20, with connected conductors

Safety class Acc. to EN 61140/VDE 0140-1 II

Permissible humidity % < 80

ET_B1_2009_en.book Seite 8 Freitag, 12. Dezember 2008 9:47 09

© Siemens AG 2008© Siemens AG 2008

Page 9: Catalog ET B1 • 2009/2010 EN - Siemens · 7KT1 14 E-counters Siemens ET B1 · 10/2008 12/3 12 ... 7KT1 140 Standards EN 62053-31, EN 50740-1, EN 50470-3 Supply † Rated control

BETA MeasuringSingle-Phase Measuring Devices

7KT5 8 time and pulse counters

12/9Siemens ET B1 · 10/2008* You can order this quantity or a multiple thereof.

12

■ Selection and ordering data

■ Dimensional drawings ■ Schematics

Terminals

■ More information

Time counters count the time in hours with an accuracy of two decimal places (hundredths of an hour). The pulse counter sums up the number of pulses, e.g. the making operations of devices.

A power supply is required at terminals 1 and 3 of the electronic counters so that the device can constantly display the measured values. Once terminal 3 is supplied with voltage (for DC "+"), the counting procedure starts. If terminal 4 is supplied short-time with voltage (for DC "+"), the counter is reset.

In the case of electronic counters, the counting result is saved indefinitely in the event of a power failure (EEPROM). On recovery of the power, the counting is continued from the saved value. As well as a modern design, the electronic counter has a 7-digit LCD, which can be reset electrically or manually.

Uc Frequency MW DT Order No. Priceper PU

PG PU PS*/P. unit

Weightper PUapprox.

V Hz Unit(s) Unit(s) kg

Time counters

Mechanical counting mechanism, display 00000.00 h without zero position

12 ... 24 DC -- 2 A 7KT5 801 027 1 1 0.095

24 AC 50 A 7KT5 802 027 1 1 0.095115 AC B 7KT5 803 027 1 1 0.095230 AC A 7KT5 804 027 1 1 0.095

115 AC 60 B 7KT5 806 027 1 1 0.095230 AC B 7KT5 807 027 1 1 0.095

Pulse counters

Mechanical counting mechanism, display 0000000 without zero position

12 ... 24 DC -- 2 B 7KT5 811 027 1 1 0.095

24 AC 50/60 B 7KT5 812 027 1 1 0.095230 AC B 7KT5 814 027 1 1 0.095

Electronic time counters

LCD 000000.0 h without zero position

12 ... 150 DC, 24 ... 240 AC

--50/60

2 B 7KT5 821 027 1 1 0.080

With electrical zero positioning

12 ... 150 DC, 24 ... 240 AC

--50/60

B 7KT5 822 027 1 1 0.080

With electrical and mechanical zero positioning

12 ... 150 DC, 24 ... 240 AC

--50/60

B 7KT5 823 027 1 1 0.080

Electronic pulse counters

LCD 0000000

With electrical and mechanical zero positioning

12 ... 150 DC, 24 ... 240 AC

--50/60

2 B 7KT5 833 027 1 1 0.080

7KT5 80. 7KT5 81.

7KT5 82. 7KT5 833

I2_1

1289

a

2 3

36

1 2 3 4

36 4464

6

45

7KT5 801 7KT5 802 7KT5 803 7KT5 804 7KT5 806 7KT5 807

7KT5 811 7KT5 812 7KT5 814

7KT5 821 7KT5 822, 7KT5 823, 7KT5 833

��

� �

���

��� 3(-)

2(+)

3(N)

2(L)

L1(+) N(–)

1 2 3 4

K1

I2_1

1616

b

+/~ –/~

Count

L1(+) N(–)

1 2 3 4

K1 K2

I2_1

1288

b

+/~ –/~

Count Reset

ET_B1_2009_en.book Seite 9 Freitag, 12. Dezember 2008 9:47 09

© Siemens AG 2008© Siemens AG 2008

Page 10: Catalog ET B1 • 2009/2010 EN - Siemens · 7KT1 14 E-counters Siemens ET B1 · 10/2008 12/3 12 ... 7KT1 140 Standards EN 62053-31, EN 50740-1, EN 50470-3 Supply † Rated control

BETA MeasuringSingle-Phase Measuring Devices7KT5 5, 7KT5 6 time counters for front-panel mounting

12/10 Siemens ET B1 · 10/2008

12

■ Overview

Time and pulse counters for control cabinets, control and mechanical engineering are used, e.g. in boilers, machine tools or compressors. The pulse counters count the starting frequencies. This supports planning for preventative maintenance.

In-time and regular maintenance is the best protection against unexpected shutdowns. Time counters count the time in hours with an accuracy of two decimal places (hundredths of an hour).

■ Benefits

• Time and pulse counters help to plan maintenance intervals and ensure high plant availability.

■ Technical specifications

7KT5 500 7KT5 501 7KT5 502 7KT5 503 7KT5 504 7KT5 505

Standards DIN VDE 0435-110; EN 60255-6

Rated control supply voltage Uc V AC -- 115 230 115 230 24V DC 10 ... 80 --

Operating range × Uc 0.9 ... 1.1

Rated frequency Hz -- 50 60 50

Rated power dissipation Pv VA < 1 0.2 1.8 0.9 1.8 0.2

Method of operation Counting of Hours

Display Drum-type register h 00000.00

Pulse duration Pulse length, pulse interval ms 50

Front-panel mounting Switchboard cutout• Without cover 55 mm × 55 mm mm × mm 45.2 × 45.2+0.3

• With cover 55 mm × 55 mm Ø mm 50.2+0.3

Terminals ± screw (Phillips) 1

Conductor cross-sections Rigid mm2 1.5Flexible, with end sleeve, min. mm2 0.75

Permissible ambient temperature °C -10 ... +70

Degree of protection Acc. to EN 60529• Front panel IP65• Installation with seal IP43• Terminals IP20, with connected conductors

Safety class Acc. to EN 61140/ VDE 0140-1 II

Permissible humidity % < 93

7KT5 600 7KT5 601 7KT5 602 7KT5 603 7KT5 604

Standards DIN VDE 0435-110; EN 60255-6

Rated control supply voltage Uc V AC -- 115 230 115 230V DC 10 ... 50 --

Operating range × Uc 0.9 ... 1.1

Rated frequency Hz -- 50 60

Rated power dissipation Pv VA < 1

Method of operation Counting of Hours

Display Drum-type register h 00000.00

Pulse duration Pulse length, pulse interval ms 50

Front-panel mounting Switchboard cutout mm × mm 68+0.5 × 68+0.5

Terminals ± screw (Phillips) 1

Conductor cross-sections Rigid mm2 1.5Flexible, with end sleeve, min. mm2 0.75

Permissible ambient temperature °C -10 ... +70

Degree of protection Acc. to EN 60529• Front panel IP52• Terminals IP00

Safety class Acc. to EN 61140/ VDE 0140-1 II

Permissible humidity % < 93

ET_B1_2009_en.book Seite 10 Freitag, 12. Dezember 2008 9:47 09

© Siemens AG 2008© Siemens AG 2008

Page 11: Catalog ET B1 • 2009/2010 EN - Siemens · 7KT1 14 E-counters Siemens ET B1 · 10/2008 12/3 12 ... 7KT1 140 Standards EN 62053-31, EN 50740-1, EN 50470-3 Supply † Rated control

BETA MeasuringSingle-Phase Measuring Devices

7KT5 5, 7KT5 6 time countersfor front-panel mounting

12/11Siemens ET B1 · 10/2008* You can order this quantity or a multiple thereof.

12

■ Selection and ordering data

■ Dimensional drawings ■ Schematics

Terminals

Uc Frequency MW DT Order No. Priceper PU

PG PU PS*/P. unit

Weightper PUapprox.

V Hz Unit(s) Unit(s) kg

Time counters

Mechanical counting mechanism, display 00000.00 h, For front-panel mounting,front frame 48 mm × 48 mm

10 ... 80 DC – A 7KT5 500 027 1 1 0.045

24 AC 50 A 7KT5 505 027 1 1 0.045115 AC A 7KT5 501 027 1 1 0.045230 AC A 7KT5 502 027 1 1 0.045

115 AC 60 A 7KT5 503 027 1 1 0.045230 AC A 7KT5 504 027 1 1 0.045

For front-panel mounting,front frame 72 mm × 72 mm With narrow frame according to DIN 43700

10 ... 50 DC – 2 B 7KT5 600 027 1 1 0.120

115 AC 50 B 7KT5 601 027 1 1 0.120230 AC A 7KT5 602 027 1 1 0.120

115 AC 60 B 7KT5 603 027 1 1 0.120230 AC B 7KT5 604 027 1 1 0.120

Covers for 7KT5 5 time counters

55 mm × 55 mm B 7KT9 020 027 1 1 0.015

Sealing rings for 7KT9 020 covers

IP43 installation in switchboards,with smooth surfaces

C 7KT9 000 027 1 set 1 set 0.020

(1 set = 5 units)

Terminal covers for 7KT5 6 time counters

Degree of protection, IP20, with connected conductors

B 7KT9 021 027 1 1 0.010

7KT5 5 7KT5 6

48 45

5,5

I2_0

7089

b

34

I2_0

6021

b

72 67,5

44595,5

7KT5 5, 7KT5 6

ET_B1_2009_en.book Seite 11 Freitag, 12. Dezember 2008 9:47 09

© Siemens AG 2008© Siemens AG 2008

Page 12: Catalog ET B1 • 2009/2010 EN - Siemens · 7KT1 14 E-counters Siemens ET B1 · 10/2008 12/3 12 ... 7KT1 140 Standards EN 62053-31, EN 50740-1, EN 50470-3 Supply † Rated control

BETA MeasuringSingle-Phase Measuring Devices

Notes

12/12 Siemens ET B1 · 10/2008

12

ET_B1_2009_en.book Seite 12 Freitag, 12. Dezember 2008 9:47 09

© Siemens AG 2008© Siemens AG 2008