    Switc hg ear Type SIMOPRIME A4 up to 24 kV, Air -Insulat e dTested according to IEC 62271-200

    Medium-V oltage Circuit-breaker

    Switc hgear

    Catalog

  • 8/18/2019 Catalogue 24 kV Switchgear_Simoprime A4.pdf

    2/11

    Circuit-Breaker Switchgear Type SIMOPRIME A4 up to 24kV, Air-Insulated

    Cont ents Application

    Page Benefits, typical uses

    Application Benefits (see also page 10 for details) Benef its 2 • Saves livesTypica l uses 2 and 3

    Technical Data Ratings 4Classif ication, dimensions, 4 r oom planning

    • Peace of mind• Increases productivity • Saves money

    Product RangePanels 5

    Design Panel design 6

    Compar tments, interlock s, 7operationBenef its and f eatur es 8

    The cir cuit-br eak er switc hgear type SIMOPRIME A4 is a factor y-assembled, type-t este d switchgear f or indoo r installatio n acc or ding toIEC 62 271-200 and VDE 0670-6.

    Standards Standar ds, specif ications, 9 guidelines

    Notes Notes 10

    SIMOPRIME A4 panel Maximum r atings 24 kV / 25 kA / 2500 A

    Typical usesTypical usesTypical usesTypical uses The SIMOPRIME A4 cir cuit-br eake r switchgear can be used in transformer and switching substatio ns, e.g.:

    Application: Power supply system Application: Power supply system Application: Power supply system Application: Power supply system! Power supply com panies

    Applic ation: Industry ! Power stations

    ! Cement industr y

    ! Automobile industr y

    ! Iron and steel works

    ! Rolling mills

    ! Mining industr y

    ! Textile, paper and f ood industries

    ! Chemical industr y

    ! Petr oleum industr y

    ! Pipeline installatio ns

    ! Of fsho r e installatio ns

    ! Electr ochemic a l plants

    ! Petr ochemic a l plants

    ! Shipbuilding industr y

    ! Diesel po we r plants

    ! Emer gency po wer supply

    installatio ns ! Lignit e open-c ast mines

    ! Traction po wer supplies

    2 Printed by Siemens

  • 8/18/2019 Catalogue 24 kV Switchgear_Simoprime A4.pdf

    3/11

    Circuit-Breaker Switc hge ar Type SIMOP RIME A4 up to 24 kV, Air-Insulat ed

    Application

    Typical uses

    Application

    Industr y

    R-HA26-012.tif

    Application Public pow er supply system

    SIMOPRIME A4 switchgear

    Application Industr y

    Printed by Siemens 3

  • 8/18/2019 Catalogue 24 kV Switchgear_Simoprime A4.pdf

    4/11

    Circuit-Br eaker Switc hge ar Type SIMOP RIME A4up to 24 kV, Air-Insulat ed

    Technical Data

    Ratings, Classification, dimensions, room planning

    Electrical data (maximum values) of SIMOPRIME A4

    Ratings Rated values(max.) Switc hgear up to 24k V

    Rated voltage 24kV 24 kVRated f r equency 50/60 HzRated shor t-duration power -fr equency withstand voltag e 50 kVRated lightning impulse wit hst and voltage 1 25 kVRated shor t-time withst and current, 3 s 25 kARated peak wit hst and current at 50/60 Hz 63 kARated shor t-cir cuit br eaking current 25 kARated shor t-cir cuit making current at 50/60 Hz 63 kARated normal current of busbar 2500 ARated normal current of f eeder s

    – with cir cuit-br eak er 2500 A

    – w

    ith

    fused load breakswitch As per fuse

    Classification of the SIMOPRIME A4 switchgear according to IEC 62 271-200

    Resistance to internal arcs Classification IAC

    Accessibility

    Construction and desig n Class of par titions Ser vice continuity catego r y

    PM LSC2B

    – Front – Rear – Lateral

    Type A Type A Type A

    Compar tment accessibility (standar d) – Busbar compartment – Switching-device compartment

    Tool-basedInterlock-based

    Test current k A 25 Test duration s 1.0

    – Low-voltage compartment – Connection compartment

    – Front connection

    – Rear connection *

    Tool-based

    Interlock-based and Tool-basedTool-based

    Dimensions

    * Contact factory for rear connection option Room planning (Minimum ro om height W 2850 mm)

    Front connection

    H

    Front

    Single-row arrangement (plan view)For dimensions B (width) and T (depth) refer to table on this page 1) For panel replacement: Control aisle W 2000 mm

    B T 2) Minimum distance to wall W 150mm

    Dimensions All panel types in mmWidth B For 1250 A vacuum circuit-breaker 800

    For 2500 A vacuum circuit-breaker 10 00 For load-break switch 5 00

    Height H With standard low-voltage compartment 2250

    Depth T

    Standard

    1900

    4 Printed by Siemens

  • 8/18/2019 Catalogue 24 kV Switchgear_Simoprime A4.pdf

    5/11

    Circuit-Breaker Switc hge ar Type SIMOP RIME A4 up to 24 kV, Air-Insulat ed

    Product Range

    Panels

    Circuit-breaker panel Disconnecting panel Bus sectionalizer (mirror-image Metering panelInstallation also possible)

    Load-break switch panel

    Com pone nts

    Cur r ent transf ormer

    Voltage transf ormer without primary f uses

    Voltage transf ormer with primary f uses

    Capacit ive volt age detection system

    Withdra wable voltage transf ormer with primary f uses

    Mak e-proof

    earthing switch

    Disconnecting link or dummy truck

    Cable sealing ends 1) max. 4 x 500 mm 2 per phase

    HV HRC f use

    3AH5 vacuum circuit-break er

    Three-positionSwitch-disconnector

    Surge arresstor

    1) The de t ails r e f er to conv entional RXS single-cor e sealing ends f or XLPE cables or other makes with similar dimensions.

    5 Printed by Siemens

  • 8/18/2019 Catalogue 24 kV Switchgear_Simoprime A4.pdf

    6/11

    Circuit-Br eaker Switc hge ar Type SIMOP RIME A4 up to 24 kV, Air-Insulat ed

    Design

    Panel design

    Legend for panel design : 1111 Door of low-voltage

    compartment2222 Opening for locking or

    unlocking the low-voltagecompartment door

    3333 High-voltage door of switching-device compartment

    4444 Inspection window for checkingthe switching-device truck

    5555 Opening for locking orunlocking the high-voltage door

    6666 Opening for mechanical char-ging of circuit-breaker closingspring

    7777 Openings for manual opera-tion (ON/OFF) of the circuit-

    breaker 8888 Inspection window for readingthe indicators

    9999 Door handle11110000 Openings for switching-device

    truck operation11111111 Opening for earthing-switch

    operation11112222 Pressure relief duct11113333 Busbars11114444 Bushings11115555 Post insulators16161616 Block-type current transformer17171717 Option: Make-proof earthing

    swtich

    Basic panel design (example)

    11118888 Cable sealing ends19191919 Option: Voltage transformer22220000 Earthing busbar22221111 Low-voltage plug connector22222222 Vacuum interrupters22223333 Switching-device truck

    CircuitCircuitCircuitCircuit----breaker panelbreaker panelbreaker panelbreaker panel Design :Connection from front with block current transformer

    A A A llllll ooo ppp eee r r r aaa tttiiiooo nnn sss bbb eee hhh iiinnn ddd ccc lllooo sss eee ddd ddd ooo ooo r r r

    6 Printed by Siemens

  • 8/18/2019 Catalogue 24 kV Switchgear_Simoprime A4.pdf

    7/11

    Circuit-Breaker Switc hge ar Type SIMOP RIME A4up to 24 kV, Air-Insulat ed

    Design

    Compartments, interlocks, operation

    SwitchingSwitchingSwitchingSwitching- ---devicedevicedevicedeviceccccoooommmmppppartmentartmentartmentartment• All switching operations with

    high-voltage door closed• Pressure relief upwards• Panel powder-coated with

    epoxy resin• Shutter operating mecha-

    nisms separately for – Busbar bushings – Connection bushings• Metallic, earthed shutters and

    partitions ensure partitionclass PM

    • High-voltage door pressure-

    resistant in the event of internal arcs in the panel• Metallic ducts for laying

    control cables• Interlocking between

    high-voltage door andcircuit-breaker truck ensuresinterlock-based access

    • Switching-device compart -ment to accommodate com -ponents for implementingvarious panel versions with

    – Vacuum circuit-breaker withor without voltage trans-formers on the truck

    – Disconnector truck – Metering truck

    Busbar compartmentBusbar compartmentBusbar compartmentBusbar compartment • Pressure relief upwards

    and through rear pressurerelief duct.

    • Option: Busbar transversepartition between panels

    • Busbars made of flat copper,bolted from panel to panel

    - For rated normal currents upto 2500 A

    - Option: Insulated busbars• Bolted top covers provide

    tool-based access• Option: Coupling electrode

    for capacitive voltagedetection system

    • Optio ns: Possibility of install-ing the following components

    - Voltage transformers- Busbar earthing switch- Current transformers in the

    run of busbars

    Connection compartmentConnection compartmentConnection compartmentConnection compartment

    Pressure relief upwardsthrough rear pressure reliefduct

    • Suitable for connection of- Single-core cables- Three-core cables• Independent opening shutters

    to permit cable testing• Earthing busbar• Connection from front• Use of block-type current

    transformers• Interlocked high-voltage door

    and bolted partitions betweenconnection compartment andswitching-device compartmentprovide interlock-based andtool-based access for panelswith connection from front

    • Option: Connection from rear Components at the pane lconnection (option)• Single-core XLPE cables

    up to max. 4 x 500 mm2per phase

    • Three-core XLPE cablesup to max. 3 x 300 mm2

    per phase• Coupling electrode for

    capacitive voltage detectionsystem

    • Voltage transformers – Cast-resin insulated – Max. 3 x 1-pole – Fixed-mounted, without

    primary fuses• Make-proof earthing switch – With manual operating

    mechanism – In addition to standard inter-

    locking of earthing switch/circuit-breaker truck,optionally lockable or withelectromagnetic interlock

    • Surge arresters – Surge arresters for protecting

    the switchgear against exter-nal overvoltages

    InterlocksInterlocksInterlocksInterlocks •

    Interlocking conditions are

    satisfied according toIEC 62 271-200 / VDE0670-6

    • Earthing switch can only beoperated with circuit-breaker truck in test position

    • Circuit-breaker truck canonly be moved with circuit-breaker

    “OPEN” and earthing switch

    “OPEN”• Mechanical coding on the

    circuit-breaker truck prevents

    insertion of similar circuit-breaker trucks for lower ratednormal currents into panelswith higher rated normal cur-rents

    • Interlocking of high-voltagedoor against circuit-breakertruck

    • The high-voltage door canonly be opened when thecircuit-breaker truck is in testposition

    • Option: Electromagneticinterlocks

    LowLowLowLow----voltage compartmentvoltage compartmentvoltage compartmentvoltage compartment •

    Accommodates equipmentfor protection, control,measuring and metering

    • Separated from the high-voltage part of the panel,safe-to-touch

    LowLowLowLow----voltage cablesvoltage cablesvoltage cablesvoltage cables • Control cables of the panel

    are flexible and havemetallic covers

    • Connection between switch-ing device truck and panelwiring to low-voltage com-partment via 64-pole coded

    plug connectors• Option: Fire-resistance

    control wiring

    Printed by Siemens 7

  • 8/18/2019 Catalogue 24 kV Switchgear_Simoprime A4.pdf

    8/11

    Circuit-Br eaker Switc hge ar Type SIMOP RIME A4 up to 24 kV, Air-Insulat ed

    Design

    Benefits and f eatures

    Benef its Featur es

    • Saves lives • All switching operations including emergency manual operationswith high-voltage door closed

    • Interlocking between high-voltage door and switching devices

    • Rack-in, rack-out operations of the circuit-breaker truck with high-voltage door closed

    • Metallic, earthed shutters and partitions, partition class: PM

    • Internal arc tested design up to 25 kA, 1 s, according to IEC 62 271-200, Annex A

    • Use of vacuum circuit-breakers

    • Peace of mind • Factory-assembled, type-tested switchgear according to IEC 62 271-200• Type testing of the circuit-breaker inside the panel

    • Use of standard, worldwide available components

    • Use of maintenance-free vacuum circuit-breakers

    • Quality management according to DIN EN ISO 9001• Design based on global best practice sharing and experience

    • Increases productivity • Use of metallic, earthed shutters and partitions between the compartments ensures highest service

    continuity of the switchgear (LSC2B according to IEC 62 271-200) during maintenance • Use of maintenance-free vacuum circuit-breakers

    • Saves money • Use of maintenance-free vacuum circuit-breakers

    Truck-type design

    8 Printed by Siemens

  • 8/18/2019 Catalogue 24 kV Switchgear_Simoprime A4.pdf

    9/11

    Cir cuit-Br eaker Switc hge ar Type SIMOP RIME A4 up to 24 kV, Air -Insulat ed

    St andar ds

    Standards, specifications, guidelines

    StandardsStandardsStandardsStandards

    The switchg ear

    complies

    w

    ith

    the r elev ant st andar ds and spec ificatio ns applic able at the t ime o f t ype t est s.

    Type of service locationType of service locationType of service locationType of service locationThe switchgear can be used f or indoo r installatio n in accor dan ce with IEC 61 936(Power installatio ns exceeding1 kV AC) and VDE 0101

    Overv iew of s tanda rd s (August 2004)

    IEC st andard VDE standar d EN st andard curr ent in f utur e current in f utur e current

    Switchg ear IEC 60 694 IEC 62 271-1 VDE 0670-1000 VDE 0671-001 EN 60 694 IEC 62 271-200 IEC 62 271-200 VDE 0670-6 VDE 0671-200 EN 62 271-200

    Devices 1) IEC 62 271 -100 IEC 62 271 -100 VDE 0671-100 VDE 0671-100 EN 62 271-100 2) IEC 62 271-102 IEC 62 271-102 VDE 0671-102 VDE 0671-102 EN 62 271-102 3) IEC 62 265-1 IEC 62 271-103 VDE 0670-301 VDE 0671-103 EN 60 265-1 4) IEC 62 271-105 IEC 62 271-105 VDE 0671-105 VDE 0671-105 EN 62 271-105 5) IEC 61 243-5 IEC 61 243-5 VDE 0682-415 VDE 0682-415 EN 61 243-5 6) IEC 60 282 IEC 60 282 VDE 0670-4 VDE 0670-4 EN 60 282

    • Outside lock able e lectrical ser vice location s a t places

    Deg r ee of pro tection

    IEC 60 529 IEC 60 529 VDE 0470-1 VDE 0470-1 EN 60 529

    whic h ar e no t acc essible to Insulation IEC 60 071 IEC 60 071 VDE 0111 VDE 0111 EN 60 071 the public. Enc losure s of

    switc hgear ca n

    only

    be

    r emo ved with tools. • Inside lockable electrical

    Curr ent transformer s Volt age transformer s

    IEC 60 044-1 IEC 60 044-1 VDE 0414-1 VDE 0414-1 EN 60 044-1

    IEC 60 044-2 IEC 60 044-2 VDE 0414-2 VDE 0414-2 EN 60 044-2

    ser vice location s. A lock able elec tric a l servic e location is a place outdoor s or indoor s that is r e ser ved exclusively f or hou sing elec trica l equip- ment and which is kep t un- der lock and key. Acc ess is

    1) Circuit-br ea ker

    2) Disconnect or and ear thing switch

    TableTableTableTable – –– – InsulatingInsulatingInsulatingInsulating capacitycapacitycapacitycapacity

    Rated voltage (rms value) kV

    3) Switch

    4) Switc h-fuse combination

    24

    5) Voltage de tection systems

    6) HV HRC f uses

    ReReReResistancsistancsistancsistanc eeee ttttoooo inteinteinteinte rnalrnalrnalrnal ararararcccc f ff f aultsaultsaultsaults

    r estrict ed to aut horized per - sonnel and perso ns who hav e been properly instruc ted in elec tric a l engineering. Untrained or unsk illed per -

    so ns may only ent e r under the supervi sion of auth orized per sonnel or pr operly in- struct ed per sons.

    TermsTermsTermsTerms

    “Make-pr oo f ear t hing switches”are ear t hing switches withsh ort-ci rcuit making cap acityaccor ding to –IEC 62 271-102 and

    –VDE 0671-102 /EN 62 271-102

    CurrentCurrentCurrentCurrent- ---carrying capacitycarrying capacitycarrying capacitycarrying capacity

    • According to IEC 60 694 / VDE0670-1000 and IEC 62 271-200current- carrying capacities referto the following ambient tempera-tures:

    – Maximum of24-hour mean +35°C

    – Maximum +40°C• The curr ent-c arry ing capac ity of the panels and busbar s depends on the ambient temperatur e outside the enc losure.• To att ain the maximum rated normal curr ents, the panels ar e pr ovided wit h natural or f or ced ventilatio n.

    Rated shor t-duration power -fr equency withstand voltag e (rms value)

    – Acr oss isolating distances kV 60

    – Be tween phases and to ear th kV 50

    Rated lightning impulse wit hst and voltage (peak value)

    – Acr oss isolating distances kV 145

    – Be tween phases and to ear th kV 125

    Climate and ambient conditiClimate and ambient conditiClimate and ambient conditiClimate and ambient conditionsonsonsons

    The switchg ear may be used, subjec t to possible additional measur es, under the f ollowing ambient conditions and climat e classes:

    Ambient conditions – Natural f or e ign materials – Chemic a lly ac tive pollutants – Small animals

    Climat e classes – 3 K3 – 3 K5

    The climat e classes ar e classi f ied accor ding to IEC 60 721-3-3.

    Protection against solid foreign bodies, electric shock and ingress ofwater SIMOPRIME A4 switchgear fulfills acc. to the standards

    – IEC 62 271-200 – IEC 60 529 – VDE 0470-1 – VDE 0670-6the f ollowing deg r ees of pro tec tion:

    – Enc losure : IP 4X – Compar t men ts: IP 2X

    • Safety of operating perso-nnel ensured by tests toverify resistance tointernal arc faults.

    • Internal ar c tests in accor d- ance with IEC 62 271-200,

    Anne x A.• The switc hgear complies wit h

    cr it eria 1 to 5 spec ified in the mentio ned standar ds f or the basic version up to 25 k A.

    • Definitio ns of the criteria: – Criterion 1

    Corr ec tly sec ur ed door s and cove r s do no t open. Def ormations ar e accep ted conditio nally.

    – Criterion 2No fragmentation of enclosu r es occu r s within the time spec ified f or test. Pr ojection s of smal l par ts up to 60 g ar e acce pted.

    – Criterion 3 Ar cing does no t cause ho les in the acc essible s ides up to a height of 2 m.

    – Criterion 4Indic a tors do no t ignit e due to the e ff ect o f hot gases. Ignition caused by glowing par t icles rather than hot gases is allowed. Ignitio ns as a r esult of paint or stick er burning ar e also excluded.

    – Criterion 5The enc losure r emains connec ted to its ear thing po int.

    Printed by Siemens 9

  • 8/18/2019 Catalogue 24 kV Switchgear_Simoprime A4.pdf

    10/11

    Cir cuit-Br eaker Switc hge ar Type SIMOP RIME A4 up to 24 kV, Air -Insulat ed

    No tes

    NotesNotesNotesNotes

    If no t st a ted otherwise on the individual pag es of this ca talog, we r eser ve the right to include modif ications, espe- cially r egar ding the stat ed val- ues, dimensio ns and weights. Dra wings ar e no t binding.

    All pr oduc t designations used ar e trademark s or pr oduct names of Siemens AG or other suppliers.

    If no t stat ed otherwise, a ll dimensio ns in this ca talog ar e given in mm .

    The inf ormation in this document

    contains general desc ript ions of the technic al op tions available, whic h do not always hav e to be pr esent in individual cases. The r eq uir ed f eatur es should ther efor e be spec if ied in eac h individual case a t the time of closing the contract.

    Responsible f or

    Technic al contents : Thevar Tharmalinga PT Siemens Indonesia , PTD M1

    General editin g: Edmund Chua, Siemens AG, PTD M1Innovasia+

    10 Innovasia Siemens Printed by Siemens

  • 8/18/2019 Catalogue 24 kV Switchgear_Simoprime A4.pdf

    11/11

    IIIIf ff f yyyyoooouuuu hhhhaaaavvvveeee aaaannnnyyyy qqqquuuueeee ssss tiontiontiontionssss aaaaboutboutboutbout

    PPPP oooowwwweeee rrrr TTTTransmissioransmissioransmissioransmission nnn anananandddd DDDDistribution,istribution,istribution,istribution,ouououourrrr CCCCususususttttoooomemememe rrrr SuppoSuppoSuppoSuppor rrrtttt CCCCeeee nnnn tttteeee rrrr iiiissss aaaa vvvvailablailablailablailableeee atatatat

    Tel: +62 21 24555 100Fax: +62 21 24555 543

    E-Mail: Trevor.holden @siemens.com www .siemens.c o.id/ ptd

    Published by PT. Siemens IndonesiaPower Transmission and DistributionMedium Voltage Division

    Jl. A. Yani Kav B 67-68Pulo Mas, Jakarta 13210Indonesia

    www .siemens.com/medium-v oltag e -switc hgear Printed by Siemens