CAUSE← EFFECT↓ SIGNAL TYPE ALARM INDICATION & BUZZER IN MFACP ACTIVATION OF VOICE EVACUATION ACTUATE EVACUATION SIGNAL DISPLAY/ PRINT CHANGE OF STATUS ACTIVATION OF SMOKE DETECTOR@1 ST FLR FIRE X X X X ACTIVATION OF SMOKE DETECTOR@GND. FLR. FIRE X X X X ACTIVATION OF DUCT DETECTOR@1 ST FLR FIRE X X X X ACTIVATION OF DUCT DETECTOR@GND. FLR. FIRE X X X X ACTIVATION OF HEAT DETECTOR@1 ST FLR FIRE X X X X ACTIVATION OF HEAT DETECTOR@GND. FLR. FIRE X X X X ACTIVATION OF MANUAL CALL POINT@1 ST FLR FIRE X X X X ACTIVATION OF MANUAL CALL POINT@GND. FLR. FIRE X X X X OTHER STATUS ELECTRIC FIRE PUMP - RUN FAULT X X LOOP OPEN CIRCUIT FAULT X LOOP SHORT CIRCUIT FAULT X MASTER ALARM OPEN CIRCUIT FAULT X MASTER ALARM SHORT CIRCUIT FAULT X EARTH FAULT FAULT X FIRE PUMP SYSTEM LOW BATTERY FAULT X FIRE PUMP POWER FAILURE FAULT X FIRE PUMP PHASE REVERSAL FAULT X X SPRINKLER CONTROL VALVE- LVL. ROOF FAULT X X SPRINKLER CONTROL VALVE- LVL.1 FAULT X X SPRINKLER CONTROL VALVE-LVL. GRND FAULT X X WATER FLOW- LVL. ROOF FAULT X X WATER FLOW - LVL.1 FAULT X X WATER FLOW -LVL. GRND FAULT X X Fire Alarm Sequence of operations 1.The fire alarm system shall operate as follows: A. Manual Operation - operation of manual fire alarm pull station shall: 1) Identify the individual station on the system control panel and sound the alarm bell at the control panel and rem FIRE ALARM SYSTEM CAUSE & E ANNUNCIATION NO

Upload: anju-ann-mathews

Post on 21-May-2017

213 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Cause&Effect Matrix

CA

USE←

EFF

ECT↓

SIG

NA

L TY

PE

ALA

RM

IND

ICA

TIO

N &

BU

ZZER

IN

MFA

CP

AC

TIV

ATI

ON

OF

VO

ICE

EVA

CU

AT

ION

AC

TUA

TE E

VA

CU

AT

ION

SIG

NA

L

DIS

PLA

Y/

PR

INT

CH

AN

GE

OF

STA

TUS

ACTIVATION OF SMOKE DETECTOR@1ST FLR FIRE X X X X

ACTIVATION OF SMOKE DETECTOR@GND. FLR. FIRE X X X X

ACTIVATION OF DUCT DETECTOR@1ST FLR FIRE X X X X

ACTIVATION OF DUCT DETECTOR@GND. FLR. FIRE X X X X

ACTIVATION OF HEAT DETECTOR@1ST FLR FIRE X X X X

ACTIVATION OF HEAT DETECTOR@GND. FLR. FIRE X X X X

ACTIVATION OF MANUAL CALL POINT@1ST FLR FIRE X X X X

ACTIVATION OF MANUAL CALL POINT@GND. FLR. FIRE X X X X

OTHER STATUS

ELECTRIC FIRE PUMP - RUN FAULT X X

LOOP OPEN CIRCUIT FAULT X

LOOP SHORT CIRCUIT FAULT X

MASTER ALARM OPEN CIRCUIT FAULT X

MASTER ALARM SHORT CIRCUIT FAULT X

EARTH FAULT FAULT X

FIRE PUMP SYSTEM LOW BATTERY FAULT X

FIRE PUMP POWER FAILURE FAULT X

FIRE PUMP PHASE REVERSAL FAULT X X

SPRINKLER CONTROL VALVE- LVL. ROOF FAULT X X

SPRINKLER CONTROL VALVE- LVL.1 FAULT X X

SPRINKLER CONTROL VALVE-LVL. GRND FAULT X X

WATER FLOW- LVL. ROOF FAULT X X

WATER FLOW - LVL.1 FAULT X X

WATER FLOW -LVL. GRND FAULT X X

Fire Alarm Sequence of operations

1.The fire alarm system shall operate as follows:

A. Manual Operation - operation of manual fire alarm pull station shall:

1) Identify the individual station on the system control panel and sound the alarm bell at the control panel and remote alarm panel.

FIRE ALARM SYSTEM CAUSE & EFFECT MATRIX FOR PRIMARY HEALTH CARE CORPORTATION

ANNUNCIATION NOTIFICATION

Page 2: Cause&Effect Matrix

2) Sound audible alarms and actuate strobes

3) Transmit a signal to the central station

B. Activation of area smoke detector, heat detector and flow switch shall cause the following:

1) Provide operation as described for manual call point.

C. Activation of any supervisory circuit shall cause the following actions and indications:

1) Record the occurrence of the event, the time of occurrence and the device initiating the event.

D. Receipt of a trouble signal at the fire alarm control shall cause the following:

1)Display at the control panel and remote annunciator panels alphanumeric LCD display, the origin or the trouble condition report.

2) Activate trouble, audible and visual signals at the fire control panel and remote annunciator.

3) Record the occurrence of the event, the time of occurrence and the device initiating the event.

Page 3: Cause&Effect Matrix

TRA

NSM

IT F

IRE

ALA

RM

SIG

NA

L

TO S

UP

ERV

ISIN

G S

TATI

ON

TRA

NSM

IT S

UP

ERV

ISO

RY

SIG

NA

L

TO S

UP

ERV

ISIN

G S

TATI

ON

TRA

NSM

IT T

RO

UB

LE S

IGN

AL

TO

SUP

ERV

ISIN

G S

TATI

ON

REL

EASE

ALL

SLI

DIN

G D

OO

R

REL

EASE

MA

GN

ETIC

ALL

Y H

ELD

SMO

KE

DO

OR

S

UN

LOC

K E

GR

ESS

SHU

TDO

WN

ELE

VA

TOR

S

CLO

SE S

MO

KE/

FIR

E D

AM

PER

S IN

RA

TED

WA

LLS

AC

TUA

TE S

MO

KE

EXH

AU

ST

AC

TUA

TE S

UP

PR

ESSI

ON

SY

STEM

PR

EDIS

CH

AR

GE

ALA

RM

S

INIT

IATE

SU

PP

RES

SIN

G S

YST

EM

REL

EASI

NG

SEQ

UEN

CE

X X X X X X

X X X X X X

X X X X

X X X X

X X X X

X X X X

X X X X

X X X X

X X X X

X

X

X

X

X

X

X

X

X

X

X

X X X X X

X X X X X

X X X X X

1) Identify the individual station on the system control panel and sound the alarm bell at the control panel and remote alarm panel.

FIRE ALARM SYSTEM CAUSE & EFFECT MATRIX FOR PRIMARY HEALTH CARE CORPORTATION

NOTIFICATION REQUIRED FIRE SAFETY CONTROL

Page 4: Cause&Effect Matrix

1)Display at the control panel and remote annunciator panels alphanumeric LCD display, the origin or the trouble condition report.

Page 5: Cause&Effect Matrix

AC

TUA

TE G

RA

PH

IC S

YST

EM

DIS

PLA

Y F

LOO

R M

AP

PR

ESSU

RIZ

E ST

AIR

WEL

LS

OTH

ER S

YST

EM S

HU

TDO

WN

PR

OC

ESS

AC

TUA

TE E

XTE

RIO

R S

TRO

BE

RES

PO

NSE

PO

INT

SHU

TDO

WN

AIR

HA

ND

LIN

G U

NIT

X X X

X X X

X X X

X X X

X X X

X X X

X X X

X X X

X

X

X

X

X

X X X

X X X

X X X

SUPPLEMENTARY

FIRE ALARM SYSTEM CAUSE & EFFECT MATRIX FOR PRIMARY HEALTH CARE CORPORTATION