Eng and dng fans

application ENG and DNG marine centrifugal fans are used in the ventilation system of seagoing ships with unrestricted cruising area as well as offshore objects.The fans can be used as exhaust or supply fans and be installed inside the compartment. The 1-phase drives (ENG) can be adjusted directly. The 3-phase drives (DNG) can be adjusted by a converter.

Casing

drive All drive motors employed are designed for continual operation and comply with the valid VDE regulations, Euro-norms and accident prevention regulations.

Employed as standard:• Split-pole motors 230 V, 50 Hz• Single-phase alternating-current motors 230 V,

50 Hz with operating capacitor

• Rotary-current motors 230/400 V, 50 Hz• Broad-voltage-range motors 202-306/350-

530 V, 50/60 Hz• ATEX motors in the types of protection EEX“e“

or EEX“de“

Type of protection “d“ flameproof enclosureType of protection in which the parts that could ignite an explosive atmosphere are enclosed in a casing.

“e“ increased safetyType of protection in which measures are taken to provide a higher level of safety, preventing inadmissibly high temperatures and the occurrence of sparks and electrical arcs in the interior or exterior parts of electrical equipment, where these do not occur in normal operation (EN 50019).

Zone

Explosion Groups:Group I : Mining (not available)Group II: Everything other than mining

Temperature classes:

To offer complete operational

security to those who ensure

ours

“ “

Options Accessoires

• 50/60Hzoperation• Specialvoltages,

protectionandinsultationclasses

• Change-poledrives• Fanswithoutcasings• ATEXfansforzone1,2,

21and22,inthetypesofprotectionEEx”e”orEEx”de”

• Rotaryspeedandfrequency-adjustablefans

• Fanswithdirect-currentdrives

• Stainless-steelfans• Lloydtypes• CSA/ULdrives• Track-compatibletypes

• Intake filters• Connectors• Connection flanges• Sound insultation cabinets• Motor brackets• Pressure switches• Cable• Pipe sound absorbers• Motors with frequency

converter• Speed regulators• Temperature guards

Gas Dust

Zone 0Zone 1Zone 2

Zone 20Zone 21Zone 21

T1 T2 T3 T4 T5 T6

4500C 3000C 2000C 1350C 1000C 850C

Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

Page 3: Centrifugal ENG and DNG Fans

Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

Impeller speed All employed fan impellers are dynamically balanced in two planes. The balance quality is according to DIN ISO 1940.With the low-pressure fans, fans with split-pole motors and external rotors, forward-curved drum-type rotors (DNG 9-30) or backward-curved high-performance impellers are employed. The standard material is galvanized-steel plate.

With the middle-pressure fans (DMV), forward-curved middle-pressure impellers from aluminum or coated-steel plate are employed.Backward-curved middle-pressure high-performance impellers are employed with the DMV models.

All fan impellers are generally available in stainless steel (1.4301).

direction of rotation The direction of rotation is defined in relation to the suction side of the fan. The standard design is clockwise rotation. Unless otherwise specified in the order, the motor is mounted at:• clockwise rotation: foot R90, terminal box RO• anticlockwise rotation: foot R90, terminal box RO

Other positions for the foot, terminal box or condensate drain holes must defined separately.

Air performance curves and sound level information are available on request.

Specifications are subject to change. The selection is as accurate as possible, but the dimension, weight or type may change.

4 All the technical data is according to basic engineering, deviations are possible if custom made

Curve Type Performance of air

Pressure differential

Voltage Current Power out

Speed Frequency Protection mode

Noise level

Weight

m3/h Pa V A kW min-1 Hz IP dB(A) kg 1 ENG 1-0,65 27 70 ┴ 230 0,12 0,009 2550 50 43 44 0,9 2 ENG 1-0,8 42 65 ┴ 230 0,12 0,011 2550 50 43 45 0,9 3 ENG 1-1,2 72 105 ┴ 230 0,2 0,023 2600 50 20 50 1 4 ENG 1-1,6 96 125 ┴ 230 0,2 0,024 2600 50 20 45 1,1 5 ENG 1-2,6 126 160 ┴ 230 0,34 0,037 2350 50 20 52 1,6 6 ENG 2-2,8 150 220 ┴ 230 0,39 0,056 2440 50 20 58 2,2

Dimension

Type A B C D TkE F G H I ENG 1-0,65 103 56,5 32 49 84 36,5 54 30 36 ENG 1-0,8 103 56,5 46 49 84 36,5 54 44 38 ENG 1-1,2 103 57 46 67 84 36,5 95 42 36 ENG 1-1,6 126 63 60 70 95 48,5 95 56 43 ENG 1-2,6 126 63 60 80 95 48,5 95 56 43 ENG 2-2,8 144 79 60 88 116 51 95 56 52

4 All the technical data is according to basic engineering, deviations are possible if custom made

Curve Type Performance of air

Pressure differential

Voltage Current Power out

Speed Frequency Protection mode

Noise level

Weight

m3/h Pa V A kW min-1 Hz IP dB(A) kg 1 ENG 1-0,65 27 70 ┴ 230 0,12 0,009 2550 50 43 44 0,9 2 ENG 1-0,8 42 65 ┴ 230 0,12 0,011 2550 50 43 45 0,9 3 ENG 1-1,2 72 105 ┴ 230 0,2 0,023 2600 50 20 50 1 4 ENG 1-1,6 96 125 ┴ 230 0,2 0,024 2600 50 20 45 1,1 5 ENG 1-2,6 126 160 ┴ 230 0,34 0,037 2350 50 20 52 1,6 6 ENG 2-2,8 150 220 ┴ 230 0,39 0,056 2440 50 20 58 2,2

Dimension

Type A B C D TkE F G H I ENG 1-0,65 103 56,5 32 49 84 36,5 54 30 36 ENG 1-0,8 103 56,5 46 49 84 36,5 54 44 38 ENG 1-1,2 103 57 46 67 84 36,5 95 42 36 ENG 1-1,6 126 63 60 70 95 48,5 95 56 43 ENG 1-2,6 126 63 60 80 95 48,5 95 56 43 ENG 2-2,8 144 79 60 88 116 51 95 56 52

Page 4: Centrifugal ENG and DNG Fans

Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

Curve Type Performance of air

Pressure differential

Voltage Current Power out

Speed Frequency Protection mode

Noise level

Weight

A m3/h Pa V A kW min-1 Hz IP dB(A) kg

1 ENG 1-0,65 27 70 ┴ 230 0.12 0.009 2550 50 43 44 0.9

2 ENG 1-0,8 42 65 ┴ 230 0.12 0.011 2550 50 43 45 0.9

3 ENG 1-1,2 72 105 ┴ 230 0.2 0.023 2600 50 20 50 1

4 ENG 1-1,6 96 125 ┴ 230 0.2 0.024 2600 50 20 45 1.1

5 ENG 1-2,6 126 160 ┴ 230 0.34 0.037 2350 50 20 52 1.6

6 ENG 2-2,8 150 220 ┴ 230 0.39 0.056 2440 50 20 58 2.2

Dimension (in mm)

Type A B C D TkE F G H I

ENG 1-0,65 103 56.5 32 49 84 36.5 54 30 36

ENG 1-0,8 103 56.5 46 49 84 36.5 54 44 38

ENG 1-1,2 103 57 46 67 84 36.5 95 42 36

ENG 1-1,6 126 63 60 70 95 48.5 95 56 43

ENG 1-2,6 126 63 60 80 95 48.5 95 56 43

ENG 2-2,8 144 79 60 88 116 51 95 56 52

Page 5: Centrifugal ENG and DNG Fans

Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

Curve Type Performance of air

Pressure differential

Voltage Current Power out

Speed Frequency Protection mode

Noise level

Weight

A m3/h Pa V A kW min-1 Hz IP dB(A) kg

1 ENG 3-4 A 220 330 ┴ 230 0.4 0.075 1750 50 44 55 3

2 ENG 4-6 A 460 395 ┴ 230 0.75 0.165 2160 50 44 69 4

3 ENG 5-10 A 580 650 ┴ 230 1.18 0.26 2100 50 44 70 5

Dimension (in mm)

Type A B C D TkE F G H I

ENG 3-4 A 199 94 84 15.5 144 78 134 79 65

ENG 4-6 A 228 107 100 x 157 86 x 93 90

ENG 5-10 A 265 11 87 75 175 101.5 120 78 99

Page 6: Centrifugal ENG and DNG Fans

Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

Curve Type Performance of air

Pressure differential

Voltage Current Power out

Speed Frequency Protection mode

Noise level

Weight

m3/h Pa V A kW min-1 Hz IP dB(A) kg

1 ENG 1-1,5 150 170 ┴ 230 0.25 0.03 2760 50 54 55 2.6

1 DNG 1-1,5 150 170 ∆ 202-306 Y 350-530

0.19/0.11 0.045 2750 50 54 55 2.6

1 DNG 1-1,5 WS 150-155 165 ∆ 202-306 0.19/0.11 0.045 2750 50 54 57 2.6

1 DNG 1-1,5 WS 165-180 240 Y 350-530 0.16/0.09 0.07 3255 60 54 60 2.6

2 ENG 2-2,5 190 230 ┴ 230 0.25 0.03 2760 50 54 62 2.8

2 DNG 2-2,5 190 230 ∆ 202-306 Y 350-530

0.19/0.11 0.045 2750 50 54 62 2.8

2 ENG 2-2,5 Ex 190 230 ┴ 230 1.07 0.12 2790-2860 50 54 65 5.4

2 DNG 2-2,5 Ex 170-195 230 ∆/Y 230/400 0.73/0.42 0.12 2775-2855 50 55 65 5.4

2 DNG 2-2,5 WS 190/220 225-230 325-335

∆ 202-306 Y 350-530

0.19/0.11 0.16/0.09

0.045 0.07

2750 3255

50 60

54 54

61 61

2.8 2.8

3 ENG 2-4,8 295 290 ┴ 230 0.45 0.05 2750 50 54 60 2.9

3 DNG 2-4,8 295 290 ∆ 202-306 Y 350-530

0.36/0.21 0.065 2760 50 54 60 2.9

3 ENG 2-4,8 Ex 295 290 ┴ 230 1.07 0.12 2790-2860 50 54 60 5.4

3 DNG 2-4,8 Ex 295 290 ∆/Y 230/400 0.73/0.42 0.12 2775-2855 50 55 60 5.4

4 DNG 2-4,8 WS 280-305 310-350

285 410-415

∆ 202-306 Y 350-530

0.36/21 0.33/19

0.065 0.08

2760 3300

50 60

54 54

62 64

3 3

4 ENG 3-2 170 285 ┴ 230 0.25 0.03 2760 50 54 59 3.6

4 DNG 3-2 170 285 ∆ 202-306 Y 350-530

0.19/0.11 0.045 2750 50 54 59 3.6

4 ENG 3-2 Ex 170 285 ┴ 230 1.07 0.12 2790-2860 50 54 59 6

4 DNG 3-2 Ex 170 285 ∆/Y 230/400 0.73/0.42 0.12 2775-2855 50 55 59 6

4 DNG 3-2 WS 165-180 170-210

280-285 390-40

∆ 202-306 Y 350-530

0.19/0.11 0.16/0.09

0.045 0.07

2750 3255

50 60

54 54

59 61

3.6 3.6

ATEX-Design II 2 G c T4

ATEX-Design II 2 G c T4

ATEX-Design II 2 G c T4

Page 7: Centrifugal ENG and DNG Fans

Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

Curve Type Performance of air

Pressure differential

Voltage Current Power out

Speed Frequency Protection mode

Noise level

Weight

m3/h Pa V A kW min-1 Hz IP dB(A) kg

5 ENG 3-3,5 180 395 ┴ 230 0.25 0.03 2760 50 54 62 3.8

5 DNG 3-3,5 180 395 ∆ 202-306 Y 350-530

0.19/0.11 0.045 2750 50 54 62 3.8

5 ENG 3-3,5 Ex 180 395 ┴ 230 1.07 0.12 2790-2860 50 54 62 6.2

5 DNG 3-3,5 Ex 180 395 ∆/Y 230/400 0.73/0.42 0.12 2775-2855 50 55 62 6.2

5 DNG 3-3,5 WS 170-190 165-220

390-410 535-580

∆ 202-306 Y 350-530

0.19/0.11 0.16/0.09

0.045 0.07

2750 3255

50 60

54 54

61 63

3.8 3.8

6 ENG 3-4,5 285 536 ┴ 230 0.4 0.065 2750 50 54 63 4

6 DNG 3-4,5 285 536 ∆/Y 230/240V 0.27/0.16 0.06 2750 50 54 63 4

6 ENG 3-4,5 Ex 285 536 ┴ 230 1.07 0.12 2790-2860 50 54 64 6.3

6 DNG 3-4,5 Ex 285 536 ∆/Y 230/400 0.73/0.42 0.12 2775-2855 50 55 64 6.3

6 DNG 3-4,5 WS 265-285 285-325

400-410 560-585

∆ 202-306 Y 350-530

0.45/0.26 0.42/0.24

0.09 0.12

2760 3300

50 60

54 54

63 63

4 4

7 ENG 3-6 430 340 ┴ 230 0.76 0.09 2770 50 54 65 4

7 DNG 3-6 430 340 ∆/Y 230/400 0.52/0.3 0.09 2760 50 54 65 4

7 ENG 3-6 Ex 430 340 ┴ 230 1.07 0.12 2790-2860 50 54 65 6.4

7 DNG 3-6 Ex 430 340 ∆/Y 230/400 0.73/0.42 0.12 2775-2855 50 55 65 6.4

7 DNG 3-6 Ex 400-440 430-510

340-345 490-500

∆ 202-306 Y 350-530

0.55/0.32 0.51/0.29

0.15 2785 3310

50 60

54 54

65 69

4 4

8 ENG 3-9,8 500 450 ┴ 230 0.9 0.12 2760 50 54 67 4.5

8 DNG 3-9,8 500 450 ∆ 202-306 Y 350-530

0.55/0.32 0.12 2785 50 54 67 4.5

8 ENG 3-9,8 Ex 500 450 ┴ 230 1.07 0.12 2790-2860 50 54 67 7

8 DNG 3-9,8 Ex 500 450 ∆/Y 230/400 0.73/0.42 0.12 2775-2855 50 55 67 7

8 DNG 3-9,8 WS 460-510 455-575

415-420 590-610

∆ 202-306 Y 350-530

0.55/0.32 0.51/0.29

0.12 0.15

2785 3310

50 60

54 54

65 67

4.5 4.5

ATEX-Design II 2 G c T4

ATEX-Design II 2 G c T4

ATEX-Design II 2 G c T4

ATEX-Design II 2 G c T4

Page 8: Centrifugal ENG and DNG Fans

Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

Dimension (in mm)

Type A B C D TkE F G H I

ENG 1-1,5 126

63

60

96

95

48.5

108

55.5

43DNG 1-1,5

DNG 1-1,5 WS

ENG 2-2,5

144

79

60

90

116

51

108

55.5

52DNG 2-2,5

ENG 2-2,5 Ex

DNG 2-2,5 Ex

DNG 2-2,5 WS

ENG 2-4,8

177

79

62

119

116

69

109

60

60DNG 2-4,8

ENG 2-4,8 Ex

DNG 2-4,8 Ex

DNG 2-4,8 WS

ENG 3-2

199

94

40

94

144

78

108

35

64DNG 3-2

ENG 3-2 Ex

DNG 3-2 Ex

DNG 3-2 WS

ENG 3-3,5

199

94

40

94

144

78

108

35

65DNG 3-3,5

ENG 3-3,5 Ex

DNG 3-3,5 Ex

DNG 3-3,5 WS

ENG 3-4,5

199

199

94

94

52

52

114

133

144

144

78

78

108

109

47

47

65

65

DNG 3-4,5

ENG 3-4,5 Ex

DNG 3-4,5 Ex

DNG 3-4,5 WS

ENG 3-6

199

199

94

94

84

84

125

135

144

144

78

78

109

109

79

79

65

65

DNG 3-6

ENG 3-6 Ex

DNG 3-6 Ex

DNG 3-6 WS

ENG 3-9,8

199

94

84

142

144

78

109

79

65DNG 3-9,8

ENG 3-9,8 Ex

DNG 3-9,8 Ex

DNG 3-9,8 WS

Page 9: Centrifugal ENG and DNG Fans

Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

Curve Type Performance of air

Pressure differential

Voltage Current Power out

Speed Frequency Protection mode

Noise level

Weight

m3/h Pa V A kW min-1 Hz IP dB(A) kg

9 ENG 4-14 850 580 ┴ 230 1.4 0.18 2730 50 55 70 5.2

9 DNG 4-14 850 580 ∆/Y 230/400 1.0/0.6 0.18 2730 50 55 70 5.2

9 ENG 4-14 Ex 850 580 ┴ 230 1.6 0.18 2650 50 55 71 7.2

9 DNG 4-14 Ex 850 580 ∆/Y 230/400 1.06/0.61 0.18 2648 50 55 71 7.2

9

DNG 4-14 WS

780-820

780-945

540

770-785

∆ 202-288 Y 350-500 ∆ 202-306 Y 350-530

∆ 1.23-1.64 Y 0.71-0.94 ∆ 1.68-1.45 Y 0.97-0.84

0.25

0.35

2765/2890

3065/3445

50

60

55

55

70

73

9.8

9.8

10 ENG 5-12,5 620 735 ┴ 230 1.4 0.18 2730 50 55 70 5.8

10 DNG 5-12,5 620 735 ∆/Y 230/400 1.0/0.6 0.18 2730 50 55 70 5.8

10 ENG 5-12,5 Ex 620 735 ┴ 230 1.6 0.18 2650 50 55 70 8.5

10 DNG 5-12,5 Ex 620 735 ∆/Y 230/400 1.06/0.61 0.18 2648 50 55 70 8.5

10

DNG 5-12,5 WS

620-655

675-760

715

980-1015

∆ 202-288 Y 350-500 ∆ 202-306 Y 350-530

∆ 1.23-1.64 Y 0.71-0.94 ∆ 1.68-1.45 Y 0.97-0.84

0.25

0.35

2765/2890

3065/3445

50

60

55

55

70

73

10.8

11 ENG 5-16 1000 630 ┴ 230 2.6 0.37 2720 50 55 74 7.3

11 DNG 5-16 1000 630 ∆/Y 230/400 2.0/1.2 0.37 2720 50 55 74 7.3

11 ENG 5-16 Ex 1000 630 ┴ 230 3.2 0.37 2720 50 55 74 16.4

11 DNG 5-16 Ex 1000 630 ∆/Y 230/400 1.51/0.87 0.37 2810 50 55 74 16.4

11 DNG 5-16 Ex 990-1030 1100-2020

640 920-930

∆ 202-306 Y 350-530

2.4/1.4 2.6/1.5

0.48 0.75

2840 3300

50 60

55 55

76 80

9.4 9.4

12 ENG 5-19 1160 695 ┴ 230 2.6 0.37 2720 50 55 72 7.3

12 DNG 5-19 1160 695 ∆/Y 230/400 2.0/1.2 0.37 2720 50 55 72 7.3

12 ENG 5-19 Ex 1160 695 ┴ 230 3.2 0.37 2720 50 55 76 16.2

12 DNG 5-19 Ex 1160 695 ∆/Y 230/400 1.51/0.87 0.37 2810 50 55 76 16.2

12

DNG 5-19 WS

1185-1250

1245-1450

680

990

∆ 202-277 Y 350-480 ∆ 202-306 Y 350-530

2.4/1.4

2.6/1.5

0.48

0.75

2840

3300

50

60

55

55

74

78

9.4

9.4

ATEX-Design II 2 G c T4

ATEX-Design II 2 G c T4

ATEX-Design II 2 G c T4

ATEX-Design II 2 G c T3

Page 10: Centrifugal ENG and DNG Fans

Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

Curve Type Performance of air

Pressure differential

Voltage Current Power out

Speed Frequency Protection mode

Noise level

Weight

m3/h Pa V A kW min-1 Hz IP dB(A) kg

13 ENG 6-22,5 1180 835 ┴ 230 2.6 0.37 2720 50 55 70 7.8

13 DNG 6-22,5 1180 835 ∆/Y 230/400 2.0/1.2 0.37 2720 50 55 70 7.8

13 ENG 6-22,5 Ex 1180 835 ┴ 230 3.2 0.37 2720 50 55 70 17.3

13 DNG 6-22,5 Ex 1180 835 ∆/Y 230/400 1.51/0.87 0.37 2810 50 55 70 17.3

13

DNG 6-22,5 WS

1200-1270

1210-1490

840-845

1205-1225

∆ 202-277 Y 350-480 ∆ 202-306 Y 350-530

2.4/1.4

2.6/1.5

0.48

0.75

2840

3300

50

50

55

55

74

77

9.5

9.5

14 DNG 6-25 1320 950 ∆/Y 230/400 2.4/1.4 0.55 2700 50 55 75 10.5

14 DNG 6-25 Ex 1320 950 ∆/Y 230/400 2.31/1.33 0.55 2810 50 55 75 10.5

14

DNG 6-25 WS

1400

1600

960-970

1380-1410

∆ 202-306 Y 350-530 ∆ 202-306 Y 380-530

3.3/2.2

4.4/2.5

0.65

1.0

2800

3200

50

60

55

55

78

81

15

15

15 ENG 6-28 1460 675 ┴ 230 2.4 0.37 2830 50 55 78 9.2

15 DNG 6-28 1460 675 ∆/Y 230/400 1.64/0.95 0.37 2790 50 55 78 9.2

15 ENG 6-28 Ex 1460 675 ┴ 230 3.2 0.37 2720 50 55 78 18.5

15 DNG 6-28 Ex 1460 675 ∆/Y 230/400 1.51/0.87 0.37 2810 50 55 78 18.5

15

DNG 6-28 Ex

1400-1525

1240-1500

645-655

955-970

∆ 202-277 Y 350-480 ∆ 202-306 Y 350-530

2.4/1.4

2.6/1.5

0.48

0.75

2840

3300

50

60

55

55

78

81

11

11

16 DNG 6-35 1760 780 ∆/Y 230/400 3.3/1.9 0.75 2790 50 55 81 14.6

16DNG 6-35 Ex 1760 780 ∆/Y 230/400 2.99/1.72 0.75 2780 50 55 81 15.6

16

DNG 6-35 WS

1830-1900

1920-2160

820

1190-1200

∆ 202-306 Y 350-530 ∆ 202-306 Y 380-530

3.3/2.2

4.4/2.5

0.65

1.0

2800

3200

50

60

55

55

78

81

15

15

17 DNG 6-40 1740 1050 ∆/Y 230/400 3.3/1.9 0.75 2790 50 55 78 14.6

17 DNG 6-40 Ex 1740 1050 ∆/Y 230/400 2.99/1.72 0.75 2780 50 55 78 16

18 DNG 7-52 2400 950 ∆/Y 230/400 5.9/3.4 1.5 2840 50 55 81 26

18 DNG 7-52 Ex 2400 950 ∆/Y 230/400 5.74/3.3 1.5 2860 50 55 81 26

19 DNG 7-60 2300 1255 ∆/Y 230/400 5.9/3.4 1.5 2740 50 55 81 26.5

19DNG 7-60 Ex 2300 1255 ∆/Y 230/400 5.74/3.3 1.5 2860 50 55 81 26.5

ATEX-Design II 2 G c T3

ATEX-Design II 2 G c T4

ATEX-Design II 2 G c T3

ATEX-Design II 2 G c T4

ATEX-Design II 2 G c T3

ATEX-Design II 2 G c T3

ATEX-Design II 2 G c T3

Page 11: Centrifugal ENG and DNG Fans

Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

Dimension (in mm)

Type A B C D TkE F G H I

ENG 4-14 228

102

100

162

144

84

111

93

90DNG 4-14

ENG 4-14 Ex 228

102

100

181

144

84

123

93

90DNG 4-14 Ex

DNG 4-14 WS 228 102 100 181 144 84 123 93 90

ENG 5-12,5 267

114

87

167

175

123.5

112

79

65DNG 5-12,5

ENG 5-12,5 Ex 267

114

87

194

175

123

123

79

65DNG 5-12,5 Ex

DNG 5-12,5 WS 267 114 87 194 175 123 123 79 65

ENG 5-16 259

101

94

187

157

98

123

90

100DNG 5-16

ENG 5-16 Ex 259

101

94

212

157

98

138

90

100DNG 5-16 Ex

DNG 5-16 WS 259 101 94 212 157 98 138 90 100

ENG 5-19 265

110

118

186

157

101.5

123

109

99DNG 5-19

ENG 5-19 Ex 265

110

118

212

157

101.5

138

109

99DNG 5-19 Ex

DNG 5-19 WS 265 110 118 212 157 101.5 138 109 99

ENG 6-22,5 290

115

102

187

175

118

123

97

94DNG 6-22,5

ENG 6-22,5 Ex 290

115

102

218

175

118

141

97

94ENG 6-22,5 Ex

DNG 6-22,5 WS 286 119 102 212 175 118 138 97 94

DNG 6-25 301 132 100 212 196 118 138 95 105

DNG 6-25 Ex 301 132 100 218 196 118 138 95 105

DNG 6-25 WS 301 132 100 233 196 118 156 95 105

ENG 6-28 298

119

129

218

175

114

138

124

112DNG 6-28

ENG 6-28 Ex 298

119

129

218

175

114

141

124

112DNG 6-28 Ex

DNG 6-28 WS 298 119 129 212 175 114 138 124 112

DNG 6-35 298 119 129 233 175 114 156 124 112

DNG 6-35 Ex 298 119 129 236 175 114 159 124 112

DNG 6-35 WS 298 119 129 233 175 114 156 124 112

DNG 6-40 301 132 129 233 196 114.5 156 124 112

DNG 6-40 Ex 301 132 129 236 196 114.5 159 124 112

DNG 7-52 333

140

130

254

196

121.5

178

125

130DNG 7-52 Ex

DNG 7-60 333

140

130

254

212

121.5

178

125

130DNG 7-60 Ex

Page 12: Centrifugal ENG and DNG Fans

Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

Page 13: Centrifugal ENG and DNG Fans

Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

Curve Type Performance of air

Pressure differential

Voltage Current Power out

Speed Frequency Protection mode

Noise level

Weight

m3/h Pa V A kW min-1 Hz IP dB(A) kg

20 ENG 8-7,5 435 885 ┴ 230 1.4 0.18 2730 50 55 70 8.7

20 DNG 8-7,5 435 885 ∆/Y 230/400 1.0/0.6 0.18 2730 50 55 70 8.4

20 DNG 8-7,5 Ex 435 885 ∆/Y 230/400 1.06/0.61 0.18 2648 50 55 70 8.5

20

DNG 8-7,5 WS

435-460

475-540

850-860

1190-1250

∆ 202-288 Y 350-500 ∆ 202-306 Y 380-530

∆ 1.23-1.64 Y 0.71-0.94 ∆ 202-306 Y 380-530

0.25

0.35

2765-2890

3065-3445

50

60

55

55

70

75

11.2

11.2

21 ENG 8-12 190 890 ┴ 230 2.6 0.37 2800 50 55 74 7.8

21 DNG 8-12 190 890 ∆/Y 230/400 2.0/1.2 0.37 2720 50 55 74 7.8

21 ENG 8-12 Ex 190 890 ┴ 230 3.2 0.37 2720 50 55 74 17

21 DNG 8-12 Ex 190 890 ∆/Y 230/400 1.51/0.87 0.37 2810 50 55 74 17

21

DNG 8-12 WS 905

875-985

805-845

1295-1310

∆ 202-277 Y 350-480 ∆ 202-306 Y 350-530

2.4/1.4

2.6/1.5

0.48

0.75

2840

3300

50

60

55

55

74

79

10.6

10.6

22 DNG 8-70 3450 1305 ∆/Y 230/400 8.0/4.6 2.2 2870 50 55 84 27.5

22 DNG 8-70 Ex 3450 1305 ∆/Y 230/400 9.0/5.2 2.5 2880 50 55 84 35

23 DNG 8-80/2,2 3000 1590 ∆/Y 230/400 8.0/4.6 2.2 2870 50 55 85 30.2

23 DNG 8-80/3 3800 1590 ∆/Y 230/400 11.6/6.7 3.3 2850 50 55 85 35.4

23 DNG 8-8-/2,5 Ex 3000 1590 ∆/Y 230/400 9.0/5.2 2.5 2850 50 55 85 35

23 DNG 8-80/3,3 Ex 3800 1590 ∆/Y 230/400 11.48/6.6 3.3 2895 50 55 85 38

24 DNG 9-80 4670 1670 ∆ 400 11 5.5 2900 50 55 92 46

24 DNG 9-80 Ex 4670 1670 ∆ 400 10.9 5.5 2925 50 55 92 46

25 DNG 9-90 4600 1960 ∆ 400 11 5.5 2900 50 55 93 51

25 DNG 9-90 Ex 4600 1960 ∆ 400 10.9 5.5 2925 50 55 93 51

26 DNG 9-97/7,5 5600 2225 ∆ 400 14.6 7.5 2925 50 55 93 79

26 DNG 9-97/11 7000 2225 ∆ 400 21 11 2915 50 55 96 84

27 DNG 10-125/7,5 5000 3300 ∆ 400 14.6 7.5 2880 50 55 96 89

27 DNG 10-125/11 7000 3300 ∆ 400 21 11 2915 50 55 99 97

ATEX-Design II 2 G c T3

ATEX-Design II 2 G c T4

ATEX-Design II 2 G c T3

ATEX-Design II 2 G c T3

ATEX-Design II 2 G c T3

ATEX-Design II 2 G c T3

Page 14: Centrifugal ENG and DNG Fans

Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

Type

ENG 8-7,5

DNG 8-7,5

DNG 8-7,5 Ex

DNG 8-7,5 WS

ENG 8-12

DNG 8-12

ENG 8-12 Ex

DNG 8-12 Ex

DNG 8-12 WS

DNG 8-70

DNG 8-70 Ex

DNG 8-80 / 2,2

DNG 8-80 / 3

DNG 8-80 / 2,5 Ex

DNG 8-80 / 3,3 Ex

DNG 9-80

DNG 9-80 Ex

DNG 9-90

DNG 9-90 Ex

DNG 9-97 / 7,5

DNG 9-97 / 11

DNG 10-125/7,5

DNG 10-125/11

Dimension (in mm)

A B C D TkE F G H I

293 133

62.5 169 212 124 112 56.5 58.5

293 133 62.5 189 212 124 123 56.5 58.5

296 132 82 212 187 125.5 123 77 68

296 132 82 212 212 125.5 138 77 68

296 132 82 212 212 125.5 138 77 68

371 148 147 279 212 141.5 173 141 143

371 148 147 316 212 141.5 199 141 143

371 148 147 279 232 141.5 176 141 143

371 148 147

316

232 141.5

199

141 143333 222

438 192 145 333 276 161 220 140 183

438 192 145 972 276 161 270 140 183

438 192 145 333 276 161 220 140 183

438 192 145 372 276 161 270 140 183

463 206 161 372 276 169 260 156 200

463 206 161 410 276 169 260 156 200

560 253 176 372 350 214 260 170 205

560 253 176 410 350 214 260 170 205

Page 15: Centrifugal ENG and DNG Fans

Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

Page 16: Centrifugal ENG and DNG Fans

Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

Curve Type Performance of air

Pressure differential

Voltage Current Power out

Speed Frequency Protection mode

Noise level

Weight

m3/h Pa V A kW min-1 Hz IP dB(A) kg

28ENG 3-10D

880 340┴ 230 1.45 0.18 2750

50 55 69 6.7DNG 3-10D ∆/Y 230/400 1.0 / 0.6 0.18 2790

28 DNG 3-10D WS865 - 910

330 - 335∆ 202/306 Y 350/530

1.47 / 0.85 0.25 2700 50 55 69 6.7960 - 1060

29ENG 3-12D

1060 415

┴ 230 1.8 0.25 2850 50 55 707.6

DNG 3-12D∆ 202/306 Y 350-530 1.47/0.85 0.25 2700 50 55 70

29 DNG 3-12D WS

990-1050 415 ∆ 202-306 Y 350-530 ∆ 202-306 Y 350-530

1.47/0.85 0.25 2700 50 55 708

990-1050 580-590 1.44/0.83 0.35 3100 60 55 73

30ENG 4-28

1330 535┴ 230 1.8 0.25 2850

50 55 74 8.4DNG 4-28D

∆ 202/306Y 350-530 1.47/0.85 0.25 2700

30 DNG 3-28D WS1230-1350 520-525

∆ 202/306Y 350-530 1.47/0.85 0.25 2700 50

5572

8.4930-1130 745-770

∆ 202/306Y 350-530

0.35 3100 60 731.44/0.83

31 DNG 5-38D 1850 680 ∆/Y 230/400 2.15/1.24 0.55 2810 50 55 76 14.4

32 DNG 5-45D 1700 840 ∆/Y 230/400 2.1/1.2 0.55 2900 50 55 77 24

33 DNG 6-50D 2640 950 ∆/Y 230/400 3.11/1.8 0.9 2915 50 55 79 25

34ENG 3-3

225 80┴ 230 0.31 0.02 1350

50 54 46 3.8DNG 3-3 ∆/Y 230/400 0.24/0.14 0.025 1320

34 DNG 3-3 Ex 225 80 ∆/Y 230/400 0.73/0.42 0.09 1360 50 55 483.8

35ENG 3-4,9

250 105┴ 230 0.31 0.02 1350

50 55 48 3.8DNG 3-4,9 ∆/Y 230/400 0.24/0.14 0.025 1350

35 DNG 3-4,9 Ex 250 105 ∆/Y 230/400 0.73/0.42 0.09 1360 50 55 505.5

36ENG 4-7

380 135┴ 230 0.31 0.02 1350

50 54 52 4.5DNG 4-7 ∆/Y 230/400 0.24/0.14 0.025 1320

36 DNG 4-7 Ex 380 135 ∆/Y 230/400 0.73/0.42 0.09 1360 50 55 525.8

37ENG 5-9,2

590 175┴ 230 0.31 0.09 1320

50 55 57 5DNG 5-9,2 ∆/Y 230/400 0.24/0.14 0.09 1380

37 DNG 5-9,2 Ex 590 175 ∆/Y 230/400 0.73/0.42 0.09 1360 50 55 626.8

38ENG 6-13,5

750 165┴ 230 0.91 0.09 1320

50 55 60 7.4DNG 6-13,5 ∆/Y 230/400 0.78/0.45 0.09 1380

38 DNG 6-13,5 Ex 750 165 ∆/Y 230/400 0.73/0.42 0.09 1360 50 55 6211.5

39ENG 6-18

920 205┴ 230 1.15 0.1 1395

50 55 62 9.4DNG 6-18 ∆/Y 230/400 0.86/0.50 0.12 1340

39 DNG 6-18 Ex 920 205 ∆/Y 230/400 0.87/0.50 0.12 1340 50 55 6212

40ENG 7-26

1160 230┴ 230 2 0.18 1390

50 55 64 11DNG 7-26 ∆/Y 230/400 1.0/0.6 0.18 1350

40 DNG 7-26 Ex 1160 230 ∆/Y 230/400 1.10/0.63 0.18 1330 50 55 6415

ATEX-Design II 2 G c T4

ATEX-Design II 2 G c T4

ATEX-Design II 2 G c T4

ATEX-Design II 2 G c T4

ATEX-Design II 2 G c T4

ATEX-Design II 2 G c T3

ATEX-Design II 2 G c T3

Page 17: Centrifugal ENG and DNG Fans

Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

Type

ENG 3-10D

DNG 3-10D

DNG 3-10D WS

ENG 3-12D

DNG 3-12D

DNG 3-12D WS

ENG 4-28

DNG 4-28D

DNG 4-28D WS

DNG 5-38D

DNG 5-45D

DNG 6-50D

ENG 3-3

DNG 3-3

DNG 3-3 Ex

ENG 3-4,9

DNG 3-4,9

DNG 3-4,9 Ex

ENG 4-7

DNG 4-7

DNG 4-7 Ex

ENG 5-9,2

DNG 5-9,2

DNG 5-9,2 Ex

EMG 6-13,5

DNG 6-13,5

DNG 6-13,5 Ex

ENG 6-18

DNG 6-18

DNG 6-18 Ex

ENG 7-26

DNG 7-26

DNG 7-26 Ex

Dimension (in mm)

A B C D TkE F G H I

199 94 84 147.5 231.5 144 79 80 66

199 94 84 147.5 213.5 144 78 80 66

199 94 84 177.5 261.5 144 78 80 66

199 94 84 177.5 261.5 144 78 80 66

228 102 100 147.5 247.5 144 84 93 90

228 102 100 147.5 247.5 144 84 93 90

265 110 118 198 316 157 101.5 109 99

290 115 102 237 339 175 118 97 94

301 132 100 237 337 196 118 97 94

301 132 100 237 337 196 118 95 105

199 94 84 114 144 78 109 80 66

199 94 84 161 144 78 111 80 66

199 94 84 122 144 78 109 80 66

199 94 84 122 144 78 109 80 66

199 94 84 164 144 78 111 80 66

228 102 100 114.5 144 84 109 93 90

228 102 100 164 144 84 111 93 90

265 110 118 167 157 101.5 111 109 99

298 119 129 167 175 114 111 124 112

298 119 129 187 175 114 123 124 112

298 11 9129 193 175 114 125 124 112

298 119 129 193 175 114 125 124 112

333 140 130 187 196 121.5 123 125 130

333 140 130 193 196 121.5 125 125 130

Page 18: Centrifugal ENG and DNG Fans

Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

Curve Type Performance of air

Pressure differential

Voltage Current Power out

Speed Frequency Protection mode

Noise level

Weight

m3/h Pa V A kW min-1 Hz IP dB(A) kg

1ENG 9-30

1750 558┴ 230 1.5 0.18 2800

50 55 72 19DNG 9-30 ∆/Y 230/400 1.06/0.62 0.18 2750

1 DNG 9-30 Ex 1750 558 ∆/Y 230/400 0.94/0.54 0.18 2825 50 55 7219

2ENG 9-43

2450 940

┴ 230 3.4 0.55 277050 55 81 20,7

DNG 9-43 ∆/Y 230/400 2.3/1.3 0.55 2830

2 DNG 9-43 Ex 2450 940 ∆/Y 230/400 2.3/1.3 0.55 2810 50 55 81 20.7

3

DNG 10-45

2750 1300

∆/Y 230/400 3.2/1.3 0.55 281050 55 80

31

DNG 10-45 Ex ∆/Y 230/400 2.31/1.33 0.55 282031

4

DNG 10-65

3800 1140

∆/Y 230/400 4.3/2.5 1.1 2780

50 55 8435

DNG 10-65 Ex ∆/Y 230/400 1.5 28404.3/2.535

5DNG 11-80

4740 1700∆/Y 230/400 6.3/2.5 1.5 2820

50 5583 38

DNG 11-80 Ex ∆/Y 230/400 5.74/3.3 1.5 2860 8438

6DNG 11-120

7350 1660∆/Y 230/400 11.5/6.7 3 2850

50 5592 45

DNG 11-120 Ex ∆/Y 230/400 11.48/6.6 3.3 2895 88 53

7DNG 12-92

5500 1900∆/Y 230/400 7.9/4.6 2.2 2850

50 55 8847

DNG 12-92 Ex ∆/Y 230/400 8.59/4.95 2.5 288052

8DNG 13-120

7150 2200∆/Y 230/400 11.5/6.7 3 2850

50 55 8865

DNG 13-120 Ex ∆/Y 230/400 11.48/6.6 3.3 289573

9DNG 13-150

9300 2615∆/Y 230/400 14.3/8.3 4 2880

50 55 9275

DNG 13-150 Ex ∆/Y 230/400 16.5/9.5 4.6 291099

ATEX-Design II 2 G c T4

ATEX-Design II 2 G c T3

ATEX-Design II 2 G c T3

ATEX-Design II 2 G c T3

ATEX-Design II 2 G c T3

ATEX-Design II 2 G c T3

ATEX-Design II 2 G c T3

ATEX-Design II 2 G c T3

ATEX-Design II 2 G c T3

Page 19: Centrifugal ENG and DNG Fans

Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

Type

ENG 9-30

DNG 9-30

DNG 9-30 Ex

ENG 9-43

DNG 9-43

DNG 9-43 Ex

DNG 10-45

DNG 10-45 Ex

DNG 10-65

DNG 10-65 Ex

DNG 11-80

DNG 11-80 Ex

DNG 11-120

DNG 11-120 Ex

DNG 12-92

DNG 12-92 Ex

DNG 13-120

DNG 13-120 Ex

DNG 13-150

DNG 13-150 Ex

Dimension (in mm)

A B C D TkE F G H I

199 94 84 147.5 231.5 144 79 80 66

199 94 84 147.5 213.5 144 78 80 66

199 94 84 177.5 261.5 144 78 80 66

199 94 84 177.5 261.5 144 78 80 66

228 102 100 147.5 247.5 144 84 93 90

228 102 100 147.5 247.5 144 84 93 90

265 110 118 198 316 157 101.5 109 99

290 115 102 237 339 175 118 97 94

301 132 100 237 337 196 118 97 94

301 132 100 237 337 196 118 95 105

199 94 84 114 144 78 109 80 66

199 94 84 161 144 78 111 80 66

199 94 84 122 144 78 109 80 66

199 94 84 122 144 78 109 80 66

199 94 84 164 144 78 111 80 66

228 102 100 114.5 144 84 109 93 90

228 102 100 164 144 84 111 93 90

Page 20: Centrifugal ENG and DNG Fans

Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

Curve Type Performance of air

Pressure differential

Voltage Cur-rent

Power out

Speed Frequency Protection mode

Noise level

Weight

m3/h Pa V A kW min-1 Hz IP dB(A) kg

10DNG 14-200

11500 3300∆ 400 15/8.7 7.5 2880

50 55 98115

DNG 14-200 Ex ∆ 400 24.8/14.3 7.5 2950182

11

DNG 14-215

12500 3220

∆ 400 15/8.7 7.5 288050 55 98

120

DNG 14-215 Ex ∆ 400 24.8/14.3 7.5 2950187

12

DNG 15-250

15000 3800

∆ 400 21 11 289050 55 101

145

DNG 15-250 Ex ∆ 400 22.8 12.8 2930227

13 DNG 14-300 18000 4600 ∆ 400 15 26.5 2925 50 55 102 227

14

ENG 10-32,5

1900 285

┴ 230 2.8 0.35 1380

50 55 64 31DNG 10-32,5 ∆/Y 230 1.8/1.0 0.37 1390

DNG 10-32,5 Ex ∆/Y 230/400 1.9/0.1 0.37 1390

15

ENG 11-60

3600 380

┴ 230 2.8 0.35 1380

50 55 72 34DNG 11-60 ∆/Y 230/400 1.8/1.0 0.37 1390

DNG 11-60 Ex ∆/Y 230/400 1.9/0.1 0.37 1390

16

ENG 13-75

4500 650

┴ 230 3.8 0..48 1390

50 55 71 55DNG 13-75 ∆/Y 230/400 2.45/1.4 0.55 1380

DNG 13-75 Ex ∆/Y 230/400 2.48/1.43 0.55 1380

17DNG 14-110

7050 760∆/Y 230/400 4.75/2.8 1.1 1400

50 55 7366

DNG 14-110 Ex ∆/Y 230/400 4.78/2.8 1.1 140069

18DNG 15-160

9550 1030∆/Y 230/400 9.0/5.3 2.2 2200

50 55 77113

DNG 15-160 Ex ∆/Y 230/400 8.2/4.75 2.1 1430118

19 DNG 16-260 16000 1300 ∆/Y 230/400 14.4/8.3 4 1420 50 55 96 130

20 DNG 17-310 19200 1750 ∆/Y 400/690V 11.4 5.5 1440 50 55 95 180

ATEX-Design II 2 G c T3

ATEX-Design II 2 G c T3

ATEX-Design II 2 G c T3

ATEX-Design II 2 G c T4

ATEX-Design II 2 G c T4

ATEX-Design II 2 G c T4

ATEX-Design II 2 G c T3

ATEX-Design II 2 G c T3

Page 21: Centrifugal ENG and DNG Fans

Alternatives available on request.Due to continued product development, Heinen & Hopman reserves the right to introduce alternations without prior notice.

Type

DNG 14-200

DNG 14-200 Ex

DNG 14-215

DNG 14-215 Ex

DNG 15-250

DNG 15-250 Ex

DNG 14-300

ENG 10-32,5

DNG 10-32,5

DNG 10-32,5 Ex

ENG 11-60

DNG 11-60

DNG 11-60 Ex

ENG 13-75

DNG 13-75

DNG 13-75 Ex

DNG 14-110

DNG 14-110 Ex

DNG 15-160

DNG 15-160 Ex

DNG 16-260

DNG 17-310

Dimension (in mm)

A B C D TkE F G H I

872 327 280 409 540 337 260 274 335

872 327 280 504 540 337 315 274 335

872 327 300 409 540 337 260 294 335

872 327 300 504 540 337 315 294 335

981 372.5 312 409 600 348.5 260 307 450

981 372.5 312 548 600 348.5 315 307 450

981 372.5 353 505 600 348.5 315 347 450

559 252.5 168 215 350 213.5 138 162 205

622 242 230 215 390 217.5 138 224 284

754.5 302 277 233 490 281.5 156 271 300

872 327 271 253 540 337 176 265 335

981 372.5 353 278 600 348.5 176 347 450

981 372.5 353 306 600 348.5 198 347 450

1140 435 435 330 670 448 225 429 425

1256 475 430 375 750 491 265 424 475

Page 22: Centrifugal ENG and DNG Fans

www.heinenhopman.com

Heinen & Hopman encourages a more

sustainable world. By providing eco-friendly solutions and serviceswe offer our clients

the option of reducing energy consumption

and thus co2 emissions. Visit

greenmanifest.info for more information.

BrazilT: +5521 3587 4241/4244E: [email protected]

france - La CiotatT: +334 4204 8685E: [email protected]

france - grasseT: +336 3090 7786 E: [email protected]

germanyT:+49 4073 1680E: [email protected]

IndiaT: +9133 6499 1293E: [email protected]

ItalyT: +3901 8745 7970E: [email protected]

The netherlands (HQ)T: +313 3299 2500E: [email protected]

The netherlands (Rotterdam)T: +317 8890 8050E: [email protected]

norwayT: +47 6919 0900E: [email protected]

Peoples Republic of ChinaT: +8621 3253 2896E: [email protected]

Peoples Republic of ChinaT: +86 510 8528 1763E: [email protected]

PolandT: +489 1433 1800E: [email protected]

RomaniaT: +402 3644 8222E: [email protected]

RussiaT: +7 (4012) 308 801E: [email protected]

singaporeT: +65 6897 7879E: [email protected]

south KoreaT: +8270 4901 0000E: [email protected]

spainT: +349 3225 9668E: [email protected]

swedenT: +46 3121 7500E: [email protected]

TurkeyT: +9021 6493 8118E: [email protected]

UaE (abu dhabi) T:+971 2550 4147E: [email protected]

UaE (dubai)T: +971 4263 5453E: [email protected]

Usa - fort Lauderdale, floridaT: +195 4463 0110E: [email protected]

Usa - Houma, Louisiana T: +198 5876 7989E: [email protected]