cerberus pro answers for infrastructure. cerberus pro ... · product catalog cerberus pro product...
TRANSCRIPT
Answers for infrastructure.www.siemens.com/cerberus
Answers for infrastructure. Megatrends driving the future
The megatrends – demographic change, urbanization, climate change, and glo-bali zation – are shaping the world today. These have an unprecedented impact on our lives and on vital sectors of our economy.
Innovative technologies to answer the associated toughest questions
Throughout a 160-year history of pro-ven research and engineering talent, with more than 50,000 active patents, Siemens has continuously provided its customers with innovations in the ar eas of healthcare, energy, industry, and in frastructure – globally and locally.
Increase productivity and efficiency through complete building life cycle management
Building Technologies offers intelligent integrated solutions for industry, com-mercial and residential buildings, and public infrastructure. Over the entire fa cility’s life cycle, our comprehensive and environmentally conscious port - fo lio of products, systems, solutions , and services for low-voltage power distribution and electrical installation technology, building automation, fire safety and security ensures the:– optimum comfort and highest energy
efficiency in buildings,– safety and security for people,
processes and assets,,– increased business productivity.
The information in this document contains general descriptions of technical options available, which do not always have to be present in individual cases. The required features should therefore be specifi ed in each individual case at the time of closing the contract.
© Siemens Switzerland Ltd, 2010 • Order no. 0-92238-en • 1,51007
Siemens Switzerland LtdIndustry SectorBuilding Technologies DivisionInternational HeadquartersGubelstrasse 226301 ZugSwitzerlandTel +41 41 724 24 24
Cerberus PRO product catalogFire safety products and accessories
Cer
ber
us
PR
O p
rod
uct
cat
alo
g
Table of Contents
1© Siemens Switzerland Ltd 2010
Stand-alone Fire Control Panels........................................................................................... 1-1
FC72x Compact Fire Control Panels .................................................................................. 1-2
FC721 Series ............................................................................................................. 1-3
Expansion FC721....................................................................................................... 1-6
Accessories FC721 ..................................................................................................... 1-9
Fire Control Network Participants........................................................................................ 2-1
FC72x Networkable Fire Control Panels ............................................................................ 2-2
FC722 Series ............................................................................................................. 2-4
FC724 Series ........................................................................................................... 2-11
FC726 Series ........................................................................................................... 2-16
Expansion FC72x ..................................................................................................... 2-18
Network Components Cluster (C-WEB/SAFEDLINK) ................................................... 2-26
Network Components Backbone (C-WEB/LAN).......................................................... 2-27
Accessories FC72x ................................................................................................... 2-28
FT724 Networkable Fire Operating Terminals ................................................................. 2-30
FT724 Operating Terminal to FC72x......................................................................... 2-30
Expansion FT724 ..................................................................................................... 2-32
Accessories FT724 ................................................................................................... 2-35
Conventional Fire Control Panels......................................................................................... 3-1
1-zone Panels .................................................................................................................. 3-2
Genesis Series ........................................................................................................... 3-2
2-zone Panels .................................................................................................................. 3-6
FC10 Series ............................................................................................................... 3-6
Accessories FC1002 ................................................................................................... 3-7
4-zone Panels .................................................................................................................. 3-8
FC10 Series ............................................................................................................... 3-8
Accessories FC1004 ................................................................................................... 3-9
8-zone Panels ................................................................................................................ 3-10
FC10 Series ............................................................................................................. 3-10
Expansion FC1008................................................................................................... 3-12
Accessories FC1008 ................................................................................................. 3-13
12-zone Panels .............................................................................................................. 3-14
FC10 Series ............................................................................................................. 3-14
Expansion FC1012................................................................................................... 3-16
Accessories FC1012 ................................................................................................. 3-17
Conventional Extinguishing Control Panels......................................................................... 4-1
Connectable to Fire Detection Systems............................................................................. 4-2
XC10 Series ............................................................................................................... 4-2
Expansion XC10......................................................................................................... 4-5
Accessories XC10....................................................................................................... 4-6
XT10 Series ............................................................................................................... 4-7
Fire Detection Network (C-NET) Peripherals ........................................................................ 5-1
Addressable Fire Detectors ............................................................................................... 5-3
Point Detectors .......................................................................................................... 5-3
Addressable Manual Call Points ........................................................................................ 5-8
MCP with Direct Operation......................................................................................... 5-8
MCP with Indirect Operation .................................................................................... 5-19
Alarm Equipment........................................................................................................... 5-25
Alarm Sounders‚ Alarm Sounder Beacon................................................................... 5-25
Bases for Alarm Sounders‚ Alarm Sounder Beacon .................................................... 5-29
Sounder Base for Automatic Detectors ..................................................................... 5-32
Table of Contents
2 © Siemens Switzerland Ltd 2010
Addressable Modules ..................................................................................................... 5-35
Line Separator ......................................................................................................... 5-35
Input Modules ......................................................................................................... 5-37
Input/Output Modules.............................................................................................. 5-38
Accessories for Input-‚ Input/Output Modules ........................................................... 5-42
Floor Repeater Panels‚ Mimic Display .............................................................................. 5-43
Floor Repeater Terminals ......................................................................................... 5-43
Floor Repeater Display ............................................................................................. 5-45
Mimic Display Driver ................................................................................................ 5-46
Visual Parallel Alarm Indicators............................................................................................ 6-1
Alarm Indicators............................................................................................................... 6-1
AI Series for C-NET Devices......................................................................................... 6-1
Fire Detection Collective Peripherals ................................................................................... 7-1
Conventional Line SynoLINE300....................................................................................... 7-3
Conventional Detectors Synova 300 Series ................................................................. 7-3
Conventional Manual Call Points ................................................................................ 7-6
Alarm Indicators for SynoLINE300 .............................................................................. 7-9
Collective Line SynoLINE600 .......................................................................................... 7-10
Collective Detectors AlgoRex Series .......................................................................... 7-10
Collective Manual Call Points.................................................................................... 7-15
Alarm Indicators for SynoLINE600 ............................................................................ 7-24
Conventional Alarm Equipment........................................................................................... 8-1
Sounders ......................................................................................................................... 8-1
Optical Signaling Equipment ............................................................................................ 8-3
Special Applications ............................................................................................................. 9-1
Special Detectors ............................................................................................................. 9-2
Infrared Flame Detectors............................................................................................ 9-2
Linear Smoke Detectors ............................................................................................. 9-5
Air Sampling Smoke Detection ................................................................................. 9-10
Aspirating Smoke Detection ..................................................................................... 9-14
Radio Fire Detection Wireless System ....................................................................... 9-16
Explosion-Hazard Area Products ..................................................................................... 9-22
Interface to C-NET.................................................................................................... 9-23
Interface to Collective Line SynoLINE600.................................................................. 9-25
Ex-Barrier................................................................................................................. 9-27
Point Detectors Ex-Series.......................................................................................... 9-28
Infrared Flame Detector Ex-Series............................................................................. 9-31
Manual Call Points ................................................................................................... 9-33
Alarm Indicators Ex-Series ........................................................................................ 9-36
Alarm Device ........................................................................................................... 9-38
Special Equipment.............................................................................................................. 10-1
Test Equipment.............................................................................................................. 10-2
Detector Tester ........................................................................................................ 10-2
Detector Tester for Special Detectors........................................................................ 10-6
Line Tester............................................................................................................... 10-8
Interface ........................................................................................................................ 10-9
Adapter for C-NET Devices........................................................................................ 10-9
Batteries ............................................................................................................................. 11-1
Spare Parts.......................................................................................................................... 12-1
Fire Control Panels FC72x and Operating Terminals FT724‚ Printers................................. 12-1
Conventional Fire Control Panels FC10 ........................................................................... 12-3
Extinguishing Control Panels XC10 ................................................................................. 12-5
Manual Call Points ......................................................................................................... 12-6
Input Modules‚ Input/Output Modules‚ Alarm Indicator ................................................... 12-8
Test Equipment.............................................................................................................. 12-9
Table of Contents
3© Siemens Switzerland Ltd 2010
Repair Parts ........................................................................................................................ 13-1
Fire Control Panels FC72xx and Operating Terminals FT724xx ........................................ 13-1
Operating Units and Add-on..................................................................................... 13-1
Periphery Boards‚ Expansion Modules and Power Supply................................................. 13-2
Floor Repeater Panels..................................................................................................... 13-4
Danger Management System ............................................................................................ 14-1
MM8000 Management Station ...................................................................................... 14-2
System Overview ............................................................................................................... 15-1
Control Panels‚ Networks‚ Accessories............................................................................. 15-2
C-NET Devices................................................................................................................ 15-4
Answers for infrastructure.
Cerberus PRO – enjoy protecting!The new generation of a smart fi re safety system.
Protecting people and assets. Securing business processes and continuity. This is what fi re protection is all about. Cerberus® PRO from Siemens is a smart fi re safety system for fast, reliable fi re detection, alarm signaling and control. Its broad portfolio comprises powerful control panels from stand-alone to networkable units, reliable detectors with patented technology and a comprehensive range of loop-powered peripheral devices. All system components have special safety features installed that increase safety even further – such as degrade mode in control panels or built-in isolators in each detector and periph-eral device. For more information, please visit www.siemens.com/cerberus
Does anyone know a clever fi re safety system starting with a “C”?
090026_AZ_Cerberus_Image_03RZ.indd 1 30.07.09 09:41
,
C-NET
C-NET
Backbone (C-WEB/LAN)
C-NET
Cluster (C-WEB/SAFEDLINK)
Customer network Ethernet
Remote access with Cerberus-Remote
Danger management system from Siemens
Ethernet switch FN2008-A1
Ethernet switch FN2008-A1
Ethernet switch FN2008-A1
Ethernet switch FN2008-A1
Security module (fi rewall) FN2009-A1
Security module (fi rewall)
FN2009-A1
Sounder base DBS720
Alarm sounderFDS221
Floor repeater terminal FT2010
Manual call point
FDM221
Fire control panelFC722
Fire control panel FC722
Fire terminal FT724
Fire control panel
FC724
Fire control panel FC726
Fault transmission
Alarm transmission
Input/output moduleFDCIO222
Optical smoke detector OP720
Floor repeater display FT2011
Alarm sounder beaconFDS229-R
Heat detector HI722
Sinorix extinguishing solution
Extinguishing control unit XC10
Multi-sensor smoke detector OH320C
Fire control panel FC724
Flame detector FDF241-9
Heat detector HI720Multi-sensor
smoke detector OH720
Opticalsmoke detector OP720
Stub line
Input moduleFDCI222
Radio gatewayFDCW221
Radio smoke detectorDOW1171
Safety barrier SB3
Smoke detector DO1101A-Ex
Linear smoke detector
FDL241-9
LaserFOCUSVLF-500
Mimic display driver FT2001-A1
Input/output module “transponder”
FDCIO223
Manual call point
FDM223Manual release
Cerberus PRO – enjoy protectingPowerful control panels, clever fi re detectors, and smart peripheral devices. This is what our comprehensive Cerberus® PRO family offers. The brief overview below demonstrates the most important system components.
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 2 28.05.10 16:56
Compatibility chart
Compatible
( ) Compatible with an interface
Addressable devices
Optical detec-
tor
Multi-sensor detec-
tor
Heat detectors
Manual call points
OP7
20
OH
72
0
HI7
20
st
atic
an
d r
ate
of
rise
HI7
22
st
atic
FDM
22
1
FDM
22
5/F
DM
22
6
FDM
22
4/F
DM
22
4H
FDM
22
3/F
DM
22
3H
Stand-alone addressable fi re control panel
FC721 (1 loop)
Networkable addressable fi re control panels
FC722 (2 loops)
FC724 (4 loops)
FC726 (4 loops)
Conventional fi re control panels
Genesis (1 zone)
FC10 (2 – 12 zones)
Conventional extinguishing control panel
XC10
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 3 28.05.10 16:56
Conventional and collective devices Special applications
Optical detector
Multi-sensor detec-
tor
Heat detectorsManual call
pointsSpecial detectors
OP3
20
C
DO
11
01
Ah
arsh
en
viro
nm
en
t
DO
11
04
Ah
igh
se
nsi
tivi
ty
OH
32
0C
HI3
22
Cra
te o
f ri
se a
nd
max
imu
m
HI3
22
Cm
axim
um
DT1
10
1A
rate
of
rise
, har
sh e
nvi
ron
me
nt
DT1
10
2A
rate
of
rise
an
d m
ax, h
arsh
en
viro
nm
.
DM
11
01
/FD
M1
10
1A
/FD
M1
10
1
DM
11
03
(IP
65
)/D
M1
10
4 (
IP6
5)
FDF2
21
-9In
frar
ed
fl a
me
de
tect
or,
sin
gle
ch
ann
el
FDF2
41
-9
Infr
are
d fl
am
e d
ete
cto
r, t
hre
e c
han
ne
ls
FDL2
41
-9Li
ne
ar s
mo
ke d
ete
cto
r
Lase
rFO
CU
S V
LF-2
50
/VLF
-50
0A
spir
atin
g s
mo
ke d
ete
ctio
n
Ex
de
tect
ors
Rad
io fi
re
de
tect
ors
( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( )
( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( )
( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( )
( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( )
( )
( )
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 4 28.05.10 16:56
Protecting people and assets reliably Protecting people and assets. Securing business processes and continuity. This is what fi re protection is all about. Cerberus® PRO is a powerful fi re protection system for fast, reliable fi re detection, alarm signaling, and control. Its wide portfolio of inno vative products provides clever technology with extensive safety features.
Protecting people and assets reliably with Siemens products
The Cerberus PRO family comprises differ- ent control panels, fi re detectors, periph-eral devices, and accessories. They all have one thing in common: smart, unique safety features. For example, all periph -eral devices, even fi re terminals, have built-in isolators. Thus, even with faults such as an open or a short circuit the sys-tem remains fully operational and faults can be quickly located. Degrade mode functionality is integrated throughout the system, ensuring detection, control, alarming, and fi re brigade communication even in the event of a pro cessor failure.
Cerberus PRO fi re detectors also increase safety thanks to their distributed intelli-gence: decisions are made on the spot in the detector. As a result, unshielded cabling can be used, making Cerberus PRO easy to plan and install. In short: Cerberus PRO is the smart answer to your fi re safety needs.
Creating networks in various sizesCerberus PRO is a straightforward fi re protection system. It offers all from stand-alone to networkable control panels. The uniform hardware concept of the panels facilitates the planning process. Even large, campus-wide networks can be easily
Highlights
Smart, unique safety features – such as built-in isolators and integrated degrade mode
Easy planning – even for campus-wide networks
Extended network possibilities for widely distributed or complex buildings
Safe and easy commissioning – thanks to auto-confi guration
Integration into the danger manage-ment system from Siemens possible
Broad range of fi re detectors – to cover various requirements
Cerberus PRO portfolio – reliable, high-quality products from Siemens
realized with little additional planning. Simply connect up to 14 clusters (C-WEB/SAFEDLINK) to an EN 54-approved fi ber-optic backbone (C-WEB/LAN). The indus-trial LAN technology also enables you to optimally adapt Cerberus PRO to any building or process structure. In addition, Cerberus PRO can be integrated into an existing IT network. Information can then be distributed across a network, further enhancing system usability.
Commissioning of the system is safe and easy thanks to auto-confi guration. It enables instant fi re protection during the construction phase, supporting on-time handover. Moreover, Cerberus PRO can be integrated into the danger manage-ment system from Siemens. Your benefi t: You can connect fi re protection with other security-related subsystems such as access control or intrusion detection.
Relying on experience Siemens is known for innovation power, technology leadership, and high quality. We were the fi rst manufacturer to offer automatic fi re detectors. Our products are backed by decades of experience and know-how. We will continue to further extend our Cerberus PRO portfolio. Compatibility of future add-ons is a matter of course – making Cerberus PRO a safe investment.
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 5 28.05.10 16:56
Stand-alone Fire Control PanelsFire Control Network Participants
Ensuring comprehensive safety with powerful panelsCerberus® PRO fi re control panels combine high security standards with the latest technology. Competitive for simple applications, yet powerful enough for every application – they are the ideal choice whatever the size and complexity of a project. The Cerberus PRO family offers four models, covering small to very large application areas. They can either stand alone or be networked into a larger system. Furthermore, all panels can be accessed either remotely or on site.
A competitive range of control panels – with unique features to put the system into operation quickly and safely
Networking possibilities – to realize redundant and EN 54-approved networks Simple networking of control panels and fi re terminals Extended network possibilities – with industrial LAN technology for widely distributed or complex buildings
Easy and intuitive to operate – to ensure right action in case of an event Remote access – for remote and cost-effi cient servicing Fire terminals for additional, remote system user interfaces – such as in the security monitoring room or the reception area
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 6 28.05.10 16:56
Stand-alone addressable fi re control panel FC721*
2x batteries max. 12 V/7 AhFA2003-A1
Up to 2 relay modules Z3B171
Cable kit (communication) FCA2014-A1
RS485 module FCA2002-A1 or RS232 moduleFCA2001-A1
Key switch (Kaba)FTO2005-C1 or Key switch (Nordic) FTO2006-B1
License key (L1) FCA2012-A1 for Cerberus-Remote
* Control panel shown with 24 indicator groups, each with one red and one yellow LED
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 7 28.05.10 16:56
Stand-alone Fire Control PanelsFC72x Compact Fire Control PanelsFC721 Series
1-3© Siemens Switzerland Ltd 2010
1
Type Order No.
FC721.. Fire control panel (1-loop) in housing (Eco)
The FC721.. is a compact fire control panel with integrated operating unit that can process signals from Cerberus PRO devices of up to 126 addresses.The fire control panel may be used as a stand-alone unit only.In addition‚ an Ethernet connection is available at each station. Via this fast Ethernet interface remote control service is possible. All detector lines are monitored for ground faults.The Cerberus-Engineering-Tool permits the system to be adapted to specific customers' requirements. Up to 2000 events can be stored according to various criteria. Automatic summer/winter change. Detec-tion and automatic read-in (auto-configuration) of all C-NET devices‚ providing immediate simple operation. Stored data can be uploaded via Cerberus-Remote access.The FC721.. is ideally suited for smaller applications‚ e.g. in workshops‚ hotels‚ etc.The expansion and accessories must be ordered separately.
Detector compatibility Cerberus PRO FD720
Number of addresses max. 126
Number of detector lines 1 loop or 2 stub lines
Programmable input/output 4
Relay outputs
Supervised output 1 x RT alarm1 x RT fault1 x Horn
Mains voltage 85… 265 VAC
Operating voltage 21… 28.6 VDC
Operating current max. 2.5 A
Power supply 70 W
Emergency power supply up to 72 h (optional)
Battery capacity 2 x 12 V‚ 7 Ah
Plug-in position 1 -> for serial interface RS232 or RS485
Operating temperature -8… +42 °C
Storage temperature -20… +60 °C
Relative humidity L95 % (no condensation)
Protection category IP30
Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design 050 00 00
Cabinet dimensions (W x H x D) 430 x 398 x 80 mm
Data sheet A6V10203220
FC721..
01.fm Seite 3 Mittwoch, 28. Juli 2010 9:08 09
Stand-alone Fire Control PanelsFC72x Compact Fire Control PanelsFC721 Series
1-4 © Siemens Switzerland Ltd 2010
Type Order No.
FC721-ZZ Fire control panel (1-loop) in housing (Eco)
See FC721.. for technical overview and note the additional / other specifications:
Expansion FCA2012-A1 License key (L1)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FH7201-Z3 Housing (Eco)FH7202-Z3 Housing (Standard)
Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (Communica-tion)DL3750+ Matrix printer (Extern)
S54400-C32-A2
FC721-YZ Fire control panel (1-loop) in housing (Eco) with 1 LED indicator
See FC721.. for technical overview and note the additional / other specifications:
With 24 indicator groups‚ each with one red and one yellow LED.
Expansion FCA2012-A1 License key (L1)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FH7201-Z3 Housing (Eco)FH7202-Z3 Housing (Standard)
Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (Communica-tion)DL3750+ Matrix printer (Extern)
S54400-C32-A3
01.fm Seite 4 Mittwoch, 28. Juli 2010 9:08 09
Stand-alone Fire Control PanelsFC72x Compact Fire Control PanelsFC721 Series
1-5© Siemens Switzerland Ltd 2010
1
Type Order No.
FC721-HZ Fire control panel (1-loop) in housing (Eco) with EVAC operating unit
See FC721.. for technical overview and note the additional / other specifications:
With 10 evacuation operating zones for Netherlands.
Expansion FCA2012-A1 License key (L1)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FH7201-Z3 Housing (Eco)FH7202-Z3 Housing (Standard)
Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (Communica-tion)DL3750+ Matrix printer (Extern)
S54400-C32-A1
01.fm Seite 5 Mittwoch, 28. Juli 2010 9:08 09
Stand-alone Fire Control PanelsFC72x Compact Fire Control PanelsExpansion FC721
1-6 © Siemens Switzerland Ltd 2010
Type Order No.
FCA2012-A1 License key (L1)
iButton with license for:Sinteso™ -> SintesoViewCerberus® PRO -> Cerberus-RemoteOnly one license key is required per station.
A5Q00018856
FCA2001-A1 RS232 module (isolated)
Module for periphery devices with RS232 interface‚ e.g. for event print-er FTO2001-A1. Plugged into the back side of the operating unit.RS232 module incl. 1 EMC screwed cable gland M10 x 1.5.
Cable capacity 0.2… 1.5 mm2
Dimensions (W x H x D) 50 x 15 x 70 mm
A5Q00005327
FCA2002-A1 RS485 module (isolated)
Module for periphery devices with RS485 interface‚ e.g. for FAT (GER). Plugged into the back side of the operating unit.RS485 module incl. 1 EMC screwed cable gland M10 x 1.5.
Cable capacity 0.2… 1.5 mm2
Dimensions (W x H x D) 50 x 15 x 70 mm
A5Q00009923
FH7201-Z3 Housing (Eco)
Empty housing for open use‚ e.g. power supply kit with batteries‚ oper-ating add-on‚ event printer or mimic display.
Cabinet dimensions (W x H x D) 430 x 398 x 80 mm
Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design 050 00 00
Protection category IP30
Integral battery space 2 x FA2003-A1 (7 Ah)
Expansion FTO2001-A1 Event printerFCM7211-Y3 Operating add-on (2xLED-ind.)FCM7212-Y3 Operating add-on (4xLED-ind.)FP2003-A1 Power supply kit (70 W)
S54400-B72-A1
01.fm Seite 6 Mittwoch, 28. Juli 2010 9:08 09
Stand-alone Fire Control PanelsFC72x Compact Fire Control PanelsExpansion FC721
1-7© Siemens Switzerland Ltd 2010
1
Type Order No.
FH7202-Z3 Housing (Standard)
Empty housing for open use‚ e.g. power supply kit with batteries‚ oper-ating add-on or for the event printer.
Cabinet dimensions (W x H x D) 430 x 398 x 160 mm
Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design 050 00 00
Protection category IP30
Integral battery space 2 x FA2003-A1 (7 Ah) or2 x FA2004-A1 (12 Ah) or2 x FA2006-A1 (26 Ah)
Expansion FTO2001-A1 Event printerFCM7211-Y3 Operating add-on (2xLED-ind)FCM7212-Y3 Operating add-on (4xLED-ind)FP2003-A1 Power supply kit (70 W)FP2004-A1 Power supply kit (150 W‚ A)FP2005-A1 Power supply kit (150 W‚ B)
S54400-B70-A1
FTO2001-A1 Event printer
The event printer is a thermal printer that logs alarms‚ faults and gener-al messages. The event printer can be used in all control panels if space is available. The RS232 module is required to operate the printer. Event printer includes cables for interface and power supply and a paper roll.The RS232 module FCA2001-A1 must be ordered separately.
Operating voltage 9… 48 VDC
Quiescent current 50 mA
Operating current 3 A @ 9 VDC0.7 A @ 48 VDC
Interface RS232 serial
Operating temperature 0… +50 °C
Storage temperature -20… +70 °C
Relative humidity L95 % (no condensation)
Dimensions (W x H x D) 85 x 85 x 55 mm
A5Q00010126
FP2003-A1 Power supply kit (70 W)
Auxiliary power supply to all stations (control panels and terminals).Converts mains voltage to system voltage. Monitors mains voltage and batteries.
Supply voltage 85... 265 VAC
Power consumption max. 90 VA
Current 0.5… 1 A
Dimensions (W x H x D) 95 x 170 x 54 mm
A5Q00016005
01.fm Seite 7 Mittwoch, 28. Juli 2010 9:08 09
Stand-alone Fire Control PanelsFC72x Compact Fire Control PanelsExpansion FC721
1-8 © Siemens Switzerland Ltd 2010
Type Order No.
FP2004-A1 Power supply kit (150 W‚ A)
Power supply kit (150 W‚ A) as auxiliary power supply for installation into empty housings.Converts mains voltage to system voltage. Monitors mains voltage and batteries.
Supply voltage 115... 230 VAC
Power consumption max. 300 VA
Current 2.6 / 1.2 A
Dimensions (W x H x D) 130 x 150 x 70 mm
A5Q00020825
01.fm Seite 8 Mittwoch, 28. Juli 2010 9:08 09
Stand-alone Fire Control PanelsFC72x Compact Fire Control PanelsAccessories FC721
1-9© Siemens Switzerland Ltd 2010
1
Type Order No.
FTO2005-C1 Key switch (Kaba)
Kaba key switch with mounting accessories and key (Kaba 8 #100)‚ as an option for operating access (operating unit).
A5Q00010113
FTO2006-B1 Key switch (Nordic)
Nordic key switch with mounting accessories and key (Nordic)‚ as an option for operating access (operating unit).
A5Q00010129
Z3B171 Relay module with 1 contact
The relay module is an additional fire event control module‚ activated by the fire control panel's control output.
Contact rating 250 VAC / 10 A
Delivery unit 10 pieces
BPZ:4843830001
FHA2016-A1 19" mounting kit
To install fire control panels and fire terminals in a 19" third-party hous-ing.
Dimensions (W x H x D) 430 x 100 x 324 mm
A5Q00020179
FCA2014-A1 Cable kit (communication)
For flexible cable connections to the modules on the PMI-& main board.
A5Q00023027
01.fm Seite 9 Mittwoch, 28. Juli 2010 9:08 09
Stand-alone Fire Control PanelsFC72x Compact Fire Control PanelsAccessories FC721
1-10 © Siemens Switzerland Ltd 2010
Type Order No.
DL3750+ Matrix printer external
The Fujitsu DL3750+ is a compact‚ noiseless A4 matrix printer. It is used for documenting relevant information in a system on continuous paper. The printer is constantly supervised by the fire control panel. The type of events to be printed is configurable. It offers a maximum of speed and reliability.The RS232 module FCA2001-A1 is required to operate the printer and must be ordered separately.
Number of copies 5 incl. original
Character set 6
Resolution 360 x 360 dpi
Interface RS232 orEthernet (via Print-Server PS01a)
Operating temperature +5… +38 °C
Storage temperature -15… +60 °C
Relative humidity L95 % (no condensation)
Dimensions (W x H x D) 415 x 120 x 330 mm
A5Q00023962
01.fm Seite 10 Mittwoch, 28. Juli 2010 9:08 09
Answers for infrastructure.
Cerberus PRO – ensuring comprehensive safety with powerful panelsCombining high security standards with the latest technology
Whether small or very large networks – with Cerberus® PRO, you always have the right control panel at hand. They are com petitive for simple applications, yet powerful enough for every application, which makes them the ideal choice what-ever the size and complexity of your project. Moreover, the control panels also offer a great number of safety features such as the degrade mode, which ensures that alarms are still transmitted even if a panel should fail. Cerberus PRO control panels are also easy and intuitive to operate. In the event of an alarm, customized intervention texts facilitate correct actions. An important factor especially in stressful emergency situations when quick and reliable action is essential to save people and assets. You see, Cerberus PRO control panels are always a clever solution. For more information, please visit www.siemens.com/cerberus
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 9 28.05.10 16:56
Networkable addressable fi re control panel FC722 Standard
RS485 module FCA2002-A1 and/or RS232 module FCA2001-A1
Event printer FTO2001-A1
Network module (SAFEDLINK)FN2001-A1
2x batteries max. 12 V/12 AhFA2004-A1
Key switch (Kaba)FTO2005-C1 or Key switch (Nordic) FTO2006-B1
License key (L1) FCA2012-A1 for Cerberus-Remote or License key (L2) FCA2013-A1 for Cerberus-Remote and connection to a danger management system
Up to 3 relay modules Z3B171
Mounting plate FHA2007-A1 for fi re brigade periphery module FCI2001-D1 or sounder module FCA2005-A1
Loop extension FCI2003-A1
Cable kit (communication) FCA2014-A1
FCA2005-A1
or
Sounder module FCA2005-A1
and/or
FCI2001-D1
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 10 28.05.10 16:56
Networkable addressable fi re control panel FC722 Comfort*
Mounting plate FHA2007-A1 for fi re brigade periphery module FCI2001-D1 or sounder module FCA2005-A1
Sounder moduleFCA2005-A1
Event printer FTO2001-A1
2x batteries max. 12 V/24 AhFA2006-A1
Additional power supply kit FP2005-A1
Key switch (Kaba) FTO2005-C1 or Key switch (Nordic) FTO2006-B1
License key (L1) FCA2012-A1 for Cerberus-Remote or License key (L2) FCA2013-A1 for Cerberus-Remote and connection to a danger management system
Up to 6 relay modules Z3B171
Up to 2 loop extensionsFCI2003-A1
Network module (SAFEDLINK)FN2001-A1
RS485 module FCA2002-A1 and/or RS232 module FCA2001-A1
Up to 2 cable kits (communication) FCA2014-A1
* Control panel shown with 48 indicator groups, each with one red and one yellow LED
Sounder moduleFCA2005-A1
and/or
Fire brigade periphery moduleFCI2001-D1
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 11 28.05.10 16:56
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC722 Series
2-4 © Siemens Switzerland Ltd 2010
Type Order No.
FC722.. Fire control panel (2-loop) in housing (Standard)
The FC722.. (2-loop‚ expandable to 4) is a compact fire control panel with an integrated operating unit that can process signals from Cer-berus PRO devices of up to 252 addresses. The fire control panel can be used as a stand-alone version or networked. It can be programmed with a user-friendly Cerberus-Engineering-Tool to create a system with great versatility. Up to 32 fire control panels and fire terminals can be con-nected in a single cluster (C-WEB/SAFEDLINK network)‚ or up to 16 pan-els when the cluster is connected to a danger management system. Using a fiber-optic backbone (C-WEB/LAN) up to 14 of these clusters with up to 16 panels each can be networked. This topology enables the construction of an EN 54-conform network with up to 64 fire control panels and fire terminals. In addition‚ an Ethernet connection is availa-ble at each station. This Ethernet connection enables a maximum of 4 stations including a Global Access Point 'GAP' (via Hub) to be networked together and be connected to a Siemens danger management system (not EN 54-compliant).All detector lines are monitored for ground faults.Adaptation of the user text directly on the terminal or with the Cerberus-Engineering-Tool. Up to 2000 events can be stored according to various criteria. Automatic summer/winter time change.Detection and automatic read-in (auto configuration) of all C-NET devices‚ providing immediate simple operation.Stored data can be uploaded via Cerberus-Remote access.The FC722.. is ideally suited for medium-sized applications‚ e.g. in workshops‚ hotels‚ etc. or when networked as part of much larger appli-cations. The FC722.. with flexible cross-linking possibilities can also be used for extensive systems.The expansion and accessories must be ordered separately.
Detector compatibility Cerberus PRO FD720
Number of addresses max. 252
Number of detector lines 2 (4) loops or 4 (8) stub lines
Programmable input/output 8
Relay outputs 1 x RT alarm1 x RT fault
Supervised output 1 x RT alarm1 x RT fault1 x horn
Emergency power supply up to 72 h (optional)
Plug-in position 2 -> for serial interfaces RS232‚ RS4852 -> for network modules1 -> for loop extension (C-NET)
Operating temperature -8… +42 °C
Storage temperature -20... +60 °C
Relative humidity L95 % (no condensation)
Protection category IP30
Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design 050 00 00
Data sheet A6V10206525
FC722..
02.fm Seite 4 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC722 Series
2-5© Siemens Switzerland Ltd 2010
2Type Order No.
FC722-ZZ Fire control panel (2-loop) in housing (Standard)
See FC722.. for technical overview and note the additional / other specifications:
Mains voltage 85... 265 VAC
Operating voltage 21… 28.6 VDC
Operating current max. 2.5 A
Power supply 70 W
Battery capacity 2 x 12 V‚ 7... 12 Ah
Cabinet dimensions (W x H x D) 430 x 398 x 160 mm
Expansion FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FTO2001-A1 Event printerFHA2007-A1 Mounting plateFCI2001-A1 Fire brigade periphery module kitFCA2005-A1 Sounder moduleFN2001-A1 Network module (SAFEDLINK)FN2002-A1 Repeater (SAFEDLINK)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FCI2003-A1 Loop extension (FDnet/C-NET)FH7202-Z3 Housing (Standard)FH7203-Z3 Housing (Comfort)
Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer (Extern)
S54400-C29-A5
02.fm Seite 5 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC722 Series
2-6 © Siemens Switzerland Ltd 2010
Type Order No.
FC722-YZ Fire control panel (2-loop) in housing (Standard) with 1 LED indica-tor
See FC722.. for technical overview and note the additional / other specifications:
With 24 indicator groups‚ each with one red and one yellow LED.
Mains voltage 85… 265 VAC
Operating voltage 21… 28.6 VDC
Operating current max. 2.5 A
Power supply 70 W
Battery capacity 2 x 12 V‚ 7... 12 Ah
Cabinet dimensions (W x H x D) 430 x 398 x 160 mm
Expansion FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FHA2007-A1 Mounting plateFCI2001-A1 Fire brigade periphery module kitFCA2005-A1 Sounder moduleFN2001-A1 Network module (SAFEDLINK)FN2002-A1 Repeater (SAFEDLINK)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FCI2003-A1 Loop extension (FDnet/C-NET)FH7202-Z3 Housing (Standard)FH7203-Z3 Housing (Comfort)
Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer (Extern)
S54400-C29-A4
02.fm Seite 6 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC722 Series
2-7© Siemens Switzerland Ltd 2010
2Type Order No.
FC722-ZA Fire control panel (2-loop) in housing (Comfort)
See FC722.. for technical overview and note the additional / other specifications:
Mains voltage 230 VAC
Operating voltage 21… 28.4 VDC
Operating current max. 5 A
Power supply 150 W
Battery capacity 2 x 12 V‚ 26 Ah
Cabinet dimensions (W x H x D) 430 x 796 x 160 mm
Expansion FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FTO2001-A1 Event printerFHA2007-A1 Mounting plateFCI2001-A1 Fire brigade periphery module kitFCA2005-A1 Sounder moduleFN2001-A1 Network module (SAFEDLINK)FN2002-A1 Repeater (SAFEDLINK)FP2005-A1 Power supply kit (150 W‚ B)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FCI2003-A1 Loop extension (FDnet/C-NET)FH7202-Z3 Housing (Standard)FH7203-Z3 Housing (Comfort)
Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer (Extern)
S54400-C29-A2
02.fm Seite 7 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC722 Series
2-8 © Siemens Switzerland Ltd 2010
Type Order No.
FC722-ZE Fire control panel (2-loop) in housing (Comfort) with 2 LED indica-tors
See FC722.. for technical overview and note the additional / other specifications:
With 48 indicator groups‚ each with one red and one yellow LED.
Mains voltage 230 VAC
Operating voltage 21… 28.4 VDC
Operating current max. 5 A
Power supply 150 W
Battery capacity 2 x 12 V‚ 26 Ah
Cabinet dimensions (W x H x D) 430 x 796 x 160 mm
Expansion FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FTO2001-A1 Event printerFHA2007-A1 Mounting plateFCI2001-A1 Fire brigade periphery module kitFCA2005-A1 Sounder moduleFN2001-A1 Network module (SAFEDLINK)FN2002-A1 Repeater (SAFEDLINK)FP2005-A1 Power supply kit (150 W‚ B)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FCI2003-A1 Loop extension (FDnet/C-NET)FH7202-Z3 Housing (Standard)FH7203-Z3 Housing (Comfort)
Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer (Extern)
S54400-C29-A1
02.fm Seite 8 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC722 Series
2-9© Siemens Switzerland Ltd 2010
2Type Order No.
FC722-HA Fire control panel (2-loop) in housing (Comfort) with EVAC operat-ing unit
See FC722.. for technical overview and note the additional / other specifications:
With 10 evacuation operating zones for Netherlands.
Mains voltage 230 VAC
Operating voltage 21… 28.4 VDC
Operating current max. 5 A
Power supply 150 W
Battery capacity 2 x 12 V‚ 26 Ah
Cabinet dimensions (W x H x D) 430 x 796 x 160 mm
Expansion FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FTO2001-A1 Event printerFHA2007-A1 Mounting plateFCI2005-N1 RT Interface SetFCA2005-A1 Sounder moduleFN2001-A1 Network module (SAFEDLINK)FN2002-A1 Repeater (SAFEDLINK)FP2005-A1 Power supply kit (150 W‚ B)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FCI2003-A1 Loop extension (FDnet/C-NET)FH7202-Z3 Housing (Standard)FH7203-Z3 Housing (Comfort)
Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer (Extern)
S54400-C29-A3
02.fm Seite 9 Mittwoch, 28. Juli 2010 8:17 08
Fire brigade periphery moduleFCI2001-D1
Networkable addressable fi re control panel FC724 Comfort*
Upt to 2 sounder modulesFCA2005-A1
* Control panel shown with 48 indicator groups, each with one red and one yellow LED
Sounder moduleFCA2005-A1
and/or
Mounting plate FHA2007-A1 for fi re brigade periphery module FCI2001-D1 or sounder module FCA2005-A1
Event printer FTO2001-A1
2x batteries max. 12 V/24 AhFA2006-A1
Additional power supply kit FP2005-A1
Key switch (Kaba) FTO2005-C1 or Key switch (Nordic) FTO2006-B1
License key (L1) FCA2012-A1 for Cerberus-Remote or License key (L2) FCA2013-A1 for Cerberus-Remote and connection to a danger management system
Up to 6 relay modules Z3B171
Up to 2 loop extensionsFCI2003-A1
Network module (SAFEDLINK)FN2001-A1
RS485 module FCA2002-A1 and/or RS232 module FCA2001-A1
Up to 2 cable kits (communication) FCA2014-A1and/or
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 12 28.05.10 16:56
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC724 Series
2-11© Siemens Switzerland Ltd 2010
2Type Order No.
FC724.. Fire control panel (4-loop)
The FC724.. (4-loop‚ expandable to 8) is a compact fire control panel with an integrated operating unit that can process signals from Cer-berus PRO devices of up to 504 addresses. The fire control panel can be used as a stand-alone version or networked. The control panel can be programmed with a user-friendly Cerberus-Engineering-Tool to create a system with great versatility. Up to 32 fire control panels and fire ter-minals can be connected in a single cluster (C-WEB/SAFEDLINK net-work)‚ or up to 16 panels when the cluster is connected to a danger management system. Using a fiber-optic backbone (C-WEB/LAN) up to 14 of these clusters with up to 16 panels each can be networked. This topology enables the construction of an EN 54-conform network with up to 64 fire control panels and fire terminals. In addition‚ an Ethernet connection is available at each station. This Ethernet connection ena-bles a maximum of 4 stations including a Global Access Point 'GAP' (via Hub) to be networked together and be connected to a Siemens danger management system (not EN 54-compliant). All detector lines are mon-itored for ground faults.Adaptation of the user text directly on the terminal or with the Cerberus-Engineering-Tool. Up to 2000 events can be stored according to various criteria. Automatic summer/winter time change.Detection and automatic read-in (auto configuration) of all C-NET devices‚ providing immediate simple operation.Stored data can be uploaded via Cerberus-Remote access.The FC724.. is ideally suited for large-sized applications‚ e.g. in industri-al plants‚ regional banks‚ office complexes‚ etc. The FC724.. with flexi-ble cross linking possibilities can also be used for extensive systems.The expansion and accessories must be ordered separately.
Detector compatibility Cerberus PRO FD720
Number of addresses max. 504
Number of detector lines 4 (8) loops or 8 (16) stub lines
Programmable input/output 12
Relay outputs 1x RT alarm1x RT fault
Supervised output 1x RT alarm1x RT fault2x Horn
Mains voltage 230 VAC
Operating voltage 21… 28.6 VDC
Operating current max. 5 A
Power supply 150 W
Emergency power supply up to 72 h (optional)
Battery capacity 2 x 12 V‚ 26 Ah
Plug-in position 2 -> for serial interfaces RS232‚ RS4852 -> for network modules2 -> for loop extension (C-NET)
Operating temperature -8… +42 °C
Storage temperature -20… +60 °C
Relative humidity L95 % (no condensation)
Protection category IP30
Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design 050 00 00
Cabinet dimensions (W x H x D) 430 x 796 x 160 mm
Data sheet A6V10207176
FC724..
02.fm Seite 11 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC724 Series
2-12 © Siemens Switzerland Ltd 2010
Type Order No.
FC724-ZA Fire control panel (4-loop)
See FC724.. for technical overview and note the additional / other specifications:
Expansion FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FTO2001-A1 Event printerFHA2007-A1 Mounting plateFCI2001-A1 Fire brigade periphery module kitFCA2005-A1 Sounder moduleFN2001-A1 Network module (SAFEDLINK)FN2002-A1 Repeater (SAFEDLINK)FP2005-A1 Power supply kit (150 W‚ B)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FCI2003-A1 Loop extension (FDnet/C-NET)FH7202-Z3 Housing (Standard)FH7203-Z3 Housing (Comfort)
Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer (Extern)
S54400-C30-A2
02.fm Seite 12 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC724 Series
2-13© Siemens Switzerland Ltd 2010
2Type Order No.
FC724-ZE Fire control panel (4-loop) with 2 LED indicators
See FC724.. for technical overview and note the additional / other specifications:
With 48 indicator groups‚ each with one red and one yellow LED.
Expansion FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FTO2001-A1 Event printerFHA2007-A1 Mounting plateFCI2001-A1 Fire brigade periphery module kitFCA2005-A1 Sounder moduleFN2001-A1 Network module (SAFEDLINK)FN2002-A1 Repeater (SAFEDLINK)FP2005-A1 Power supply kit (150 W‚ B)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FCI2003-A1 Loop extension (FDnet/C-NET)FH7202-Z3 Housing (Standard)FH7203-Z3 Housing (Comfort)
Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer (Extern)
S54400-C30-A3
02.fm Seite 13 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC724 Series
2-14 © Siemens Switzerland Ltd 2010
Type Order No.
FC724-HA Fire control panel (4-loop) with EVAC operating unit
See FC724.. for technical overview and note the additional / other specifications:
With 10 evacuation operating zones for Netherlands.
Expansion FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FTO2001-A1 Event printerFHA2007-A1 Mounting plateFCI2005-N1 RT Interface SetFCA2005-A1 Sounder moduleFN2001-A1 Network module (SAFEDLINK)FN2002-A1 Repeater (SAFEDLINK)FP2005-A1 Power supply kit (150 W‚ B)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FCI2003-A1 Loop extension (FDnet/C-NET)FH7202-Z3 Housing (Standard)FH7203-Z3 Housing (Comfort)
Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer (Extern)
S54400-C30-A1
02.fm Seite 14 Mittwoch, 28. Juli 2010 8:17 08
Networkable addressable modular fi re control panel FC726
I/O card (programmable) FCI2008-A1
Sounder moduleFCA2005-A1
Mounting plate FHA2007-A1 for fi re brigade periphery module FCI2001-D1 or sounder module FCA2005-A1
Event printer FTO2001-A1
2x batteries 12 V/24 AhFA2006-A1
Additional power supply kit FP2005-A1
Up to 2 sounder modules FCA2005-A1
and/or Any number of relay modules Z3B171
Key switch (Kaba) FTO2005-C1 or Key switch (Nordic) FTO2006-B1
License key (L1) FCA2012-A1 for Cerberus-Remote or License key (L2) FCA2013-A1 for Cerberus-Remote and connection to a danger management system
Line card (C-NET) FCL2001-A1
Up to 2 loop extensionsFCI2003-A1
Network module (SAFEDLINK)FN2001-A1
RS485 module FCA2002-A1 and/or RS232 module FCA2001-A1
Up to 2 cable kits (communication) FCA2014-A1
Fire brigade periphery moduleFCI2001-D1
Operating add-on (2x LED-ind) FCM7211-Y3 orOperating add-on (4x LED-ind) FCM7212-Y3
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 13 28.05.10 16:57
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC726 Series
2-16 © Siemens Switzerland Ltd 2010
Type Order No.
FC726.. Fire control panel (modular)
The FC726... (4-loop‚ expandable to 28 loops) is a modular fire control panel with an integrated operating unit that can process signals from Cerberus PRO devices of up to 1512 addresses. A card cage in the basic fire control panel equipment is used for installation of additional line cards (C-NET) or I/O cards. A mix of up to 5 cards max. is possible. Line and I/O cards can be exchanged without removing power from control panel. The fire control panel can be used as a stand-alone version or net-worked. The control panel can be programmed with a user-friendly Cerberus-Engineering-Tool to create a system with great versatility. Up to 32 fire control panels and fire terminals can be connected in a sin-gle cluster (C-WEB/SAFEDLINK network)‚ or up to 16 panels when the cluster is connected to a danger management system. Using a fiber-optic backbone (C-WEB/LAN) up to 14 of these clusters with up to 16 panels each can be networked. This topology enables the construction of an EN 54-conform network with up to 64 fire control panels and fire terminals. In addition‚ an Ethernet connection is available at each sta-tion. This Ethernet connection enables a maximum of 4 stations includ-ing a Global Access Point 'GAP' (via Hub) to be networked together and be connected to a Siemens danger management system (not EN 54-compliant). All detector lines are monitored for ground faults.Adaptation of the user text directly on the terminal or with the software engineering tool. Up to 2000 events can be stored according to various criteria. Automatic summer/winter time change. Detection and auto-matic read-in (auto configuration) of all C-NET devices‚ providing imme-diate simple operation. Stored data can be uploaded via remote access.The FC726 is ideally suited for very large and complex buildings‚ e.g. office buildings‚ university campuses‚ etc. The FC726.. with flexible cross linking possibilities can also be used for extensive systems. The expansion and accessories must be ordered separately.
Detector compatibility Cerberus PRO FD 720
Number of addresses max. 1512
Number of detector lines Loop with loop extension -> 4 loops or 8 stub linesC-NET -> max. 20 (4 per line card)
Programmable input/output max. 60 (12 per card)
Relay outputs 1 x RT alarm; 1 x RT fault
Supervised output 1 x RT alarm; 1 x RT fault2 x Horn
Mains voltage 230 VAC
Operating voltage 21... 28.4 VDC
Operating current Max. 5 A
Power supply 150 W
Emergency power supply up to 72 h (optional)
Battery capacity 2 x 12‚ 45 Ah
Plug-in position 2 -> for serial interfaces RS232‚ RS48522 -> for network modules1 -> for loop extension (C-NET)5 -> for line or I/O cards (card cage)
Operating temperature -8… +42 °C
Storage temperature -20… +60 °C
Relative humidity L95 % (no condensation)
Protection category IP30
Standard EN 54-2‚ EN 54-4
Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design050 00 00
Cabinet dimensions (W x H x D) 430 x 796 x 260
Data sheet A6V10263277
FC726..
02.fm Seite 16 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC726 Series
2-17© Siemens Switzerland Ltd 2010
2Type Order No.
FC726-ZA Fire control panel (modular)
See FC726.. for technical overview and note the additional / other specifications:
Expansion FCI2003-A1 Loop extension (FDnet/C-NET)FCI2008-A1 I/O card (programma-ble)FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FTO2001-A1 Event printerFHA2007-A1 Mounting plateFCI2001-A1 Fire brigade periphery module kitFCA2005-A1 Sounder moduleFCL2001-A1 Line card (FDnet/C-NET)FN2001-A1 Network module (SAFEDLINK)FN2002-A1 Repeater (SAFEDLINK)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FH7204-Z3 Housing (Large Exten-sion)FH7205-Z3 Housing (Large)
Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer
S54400-C87-A1
02.fm Seite 17 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsExpansion FC72x
2-18 © Siemens Switzerland Ltd 2010
Type Order No.
FCI2003-A1 Loop extension (FDnet/C-NET)
With the loop extension‚ the number of connectable loops is doubled from 2 to 4. The number of FDnet/C-NET addresses per station remains unchanged.Plugged onto the periphery board of the control panel. Each integrated line can be equipped with one loop extension (exclude FC721).
Number of detector lines 2 loops or 4 stub lines
Cable capacity 0.2... 1.5 mm2
Dimensions (W x H x D) 48 x 20 x 70 mm
A5Q00010136
FCL2001-A1 Line card (FDnet/C-NET)
The line card is an additional card for integrated FDnet/C-NET lines‚ mounted in card cage (5 slots) of FC2060 or FC726 fire control panel. It is used to expand FC2060/FC726 with additional FDnet/C-NET lines. All FDnet or C-NET devices can be connected to the line card. The line card is designed for 4 loops or 8 stub lines.
Number of detector lines 4 loops or 8 stub lines
Number of addresses max. 252
Input current max. 0.8 A
A5Q00009875
FCI2008-A1 I/O card (programmable)
The I/O card is an additional card with programmable inputs and out-puts for expansion of the integrated inputs and outputs. The card is mounted in the card cage (5 slots) of the fire control panel FC2060/FC726.
Input current max. 2 A
S54400-A6-A1
FCA2012-A1 License key (L1)
iButton with license for:Sinteso -> SintesoViewCerberus PRO -> Cerberus-RemoteOnly one license key is required per station.
A5Q00018856
FCA2013-A1 License key (L2)
iButton with license for:Sinteso -> SintesoView and BACnetCerberus PRO -> Cerberus-Remote and BACnetOnly one license key is required per station.
A5Q00018857
02.fm Seite 18 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsExpansion FC72x
2-19© Siemens Switzerland Ltd 2010
2Type Order No.
FTO2001-A1 Event printer
The event printer is a thermal printer that logs alarms‚ faults and gener-al messages. The event printer can be used in all control panels if space is available. The RS232 module is required to operate the printer. Event printer includes cables for interface and power supply and a paper roll.The RS232 module FCA2001-A1 must be ordered separately.
Operating voltage 9… 48 VDC
Quiescent current 50 mA
Operating current 3 A @ 9 VDC0.7 A @ 48 VDC
Interface RS232 serial
Operating temperature 0… +50 °C
Storage temperature -20… +70 °C
Relative humidity L95 % (no condensation)
Dimensions (W x H x D) 85 x 85 x 55 mm
A5Q00010126
FHA2007-A1 Mounting plate
The mounting plate must be screwed onto the back wall of the housing. The mounting plate can pivot‚ allowing access to the underlying mod-ule‚ i.e. to mount the fire brigade periphery module or the sounder modules.
Dimensions (W x H x D) 221 x 241 x 46 mm
A5Q00010151
FCI2001-D1 Fire brigade periphery module
For VdS-compliant switching to fire department periphery devices (for Germany). The module has connections for FBF‚ FSD‚ ÜE‚ FSE‚ ÖA‚ KL‚ tamper alarm FSD.Mounted in the housing on the mounting plate FHA2007-A1‚ or on the back wall of the housing.
Operating voltage 21… 28.6 VDC
Operating current max. 1.6 A
Cable capacity 0.2... 1.5 mm2 / 0.5... 2.5 mm2
Dimensions (W x H x D) 150 x 190 x 40 mm
A5Q00013100
FCI2005-N1 RT Interface Set
For fire department periphery devices (for Netherlands). Mounted in the housing on the mounting plate FHA2007-A1.
Operating voltage 20… 30 VDC
Operating current max. 20 mA
Cable capacity 0.4... 1.5 mm2 / 0.2... 2.5 mm2
Dimensions (W x H x D) 190 x 150 x 36 mm
A5Q00026302
02.fm Seite 19 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsExpansion FC72x
2-20 © Siemens Switzerland Ltd 2010
Type Order No.
FCA2005-A1 Sounder module
With the sounder module‚ it is possible to split a collective horn line onto 4 individual lines. Each line controls and monitors an individual sounder. 2 sounder modules can also be used‚ but must then be cascad-ed.The sounder module can be mounted onto the mounting plate FHA2007-A1 or onto the U-rail TS35 with the enclosed mounting feet.
Operating voltage 21... 28.6 VDC
Quiescent current 20 mA
Operating current max. 2 A (fused with 2 AT)
Supervised output 4 x 1 A
Cable capacity 0.08... 1.5 mm2
Relative humidity L95 %
Color housing/cover white‚ zRAL 9010/transparent matt
Protection category IP30
Dimensions (W x H x D) 132 x 90 x 24 mm
A5Q00014866
Accessories
TS35_122 U-rail TS35/7.5/122
Universal mounting rail (U-rail) enables mounting of various equip-ment.
Dimensions (W x H) 35 x 122 mm
BPZ:5644780001
TS35_288 U-rail TS35/7.5/288
Universal mounting rail (U-rail) enables mounting of various equip-ment.
Dimensions (W x H) 35 x 288 mm
BPZ:5644230001
FDCH221 Housing for input/output modules
Housing with seal for the mounting of the input/output modules for wet applications.The required screwed cable glands and back nuts M20 must be ordered separately.
Dimensions (W x H x D) 207 x 119 x 48 mm
Color white‚ zRAL 9010 / transparent matt
Protection category IP65
Accessories A5Q00004478 Screwed cable gland M20A5Q00004479 Back nut M20
S54312-F3-A1
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
02.fm Seite 20 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsExpansion FC72x
2-21© Siemens Switzerland Ltd 2010
2Type Order No.
A5Q00004479 Back nut M20
Back nut to screwed cable gland M20 x 1.5.
Delivery unit 10 pieces
A5Q00004479
FCA2001-A1 RS232 module (isolated)
Module for periphery devices with RS232 interface‚ e.g. for event print-er FTO2001-A1. Plugged into the back side of the operating unit.RS232 module incl. 1 EMC screwed cable gland M10 x 1.5.
Cable capacity 0.2… 1.5 mm2
Dimensions (W x H x D) 50 x 15 x 70 mm
A5Q00005327
FCA2002-A1 RS485 module (isolated)
Module for periphery devices with RS485 interface‚ e.g. for FAT (GER). Plugged into the back side of the operating unit.RS485 module incl. 1 EMC screwed cable gland M10 x 1.5.
Cable capacity 0.2… 1.5 mm2
Dimensions (W x H x D) 50 x 15 x 70 mm
A5Q00009923
FH7201-Z3 Housing (Eco)
Empty housing for open use‚ e.g. power supply kit with batteries‚ oper-ating add-on‚ event printer or mimic display.
Cabinet dimensions (W x H x D) 430 x 398 x 80 mm
Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design 050 00 00
Protection category IP30
Integral battery space 2 x FA2003-A1 (7 Ah)
Expansion FTO2001-A1 Event printerFCM7211-Y3 Operating add-on (2xLED-ind.)FCM7212-Y3 Operating add-on (4xLED-ind.)FP2003-A1 Power supply kit (70 W)
S54400-B72-A1
02.fm Seite 21 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsExpansion FC72x
2-22 © Siemens Switzerland Ltd 2010
Type Order No.
FH7202-Z3 Housing (Standard)
Empty housing for open use‚ e.g. power supply kit with batteries‚ oper-ating add-on or for the event printer.
Cabinet dimensions (W x H x D) 430 x 398 x 160 mm
Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design 050 00 00
Protection category IP30
Integral battery space 2 x FA2003-A1 (7 Ah) or2 x FA2004-A1 (12 Ah) or2 x FA2006-A1 (26 Ah)
Expansion FTO2001-A1 Event printerFCM7211-Y3 Operating add-on (2xLED-ind.)FCM7212-Y3 Operating add-on (4xLED-ind.)FP2003-A1 Power supply kit (70 W)FP2004-A1 Power supply kit (150 W‚ A)FP2005-A1 Power supply kit (150 W‚ B)
S54400-B70-A1
FH7203-Z3 Housing (Comfort)
Empty housing for open application‚ e.g. power supply kit with batter-ies‚ for operating add-on or for the event printer.
Cabinet dimensions (W x H x D) 430 x 796 x 160 mm
Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design 050 00 00
Protection category IP30
Integral battery space 2 x FA2003-A1 (7 Ah) or2 x FA2004-A1 (12 Ah) or2 x FA2005-A1 (17 Ah) or2 x FA2006-A1 (26 Ah)
Expansion FTO2001-A1 Event printerFCM7211-Y3 Operating add-on (2xLED ind.)FCM7212-Y3 Operating add-on (4xLED ind.)FP2003-A1 Power supply kit (70 W)FP2004-A1 Power supply kit (150 W‚ A)FP2005-A1 Power supply kit (150 W‚ B)
S54400-B71-A1
02.fm Seite 22 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsExpansion FC72x
2-23© Siemens Switzerland Ltd 2010
2Type Order No.
FH7204-Z3 Housing (Large Extension)
Empty housing for open application‚ e.g. additional batteries‚ for oper-ating add-ons or for the event printer.
Cabinet dimensions (W x H x D) 430 x 398 x 260 mm
Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design050 00 00
Protection category IP30
Integral battery space 2 x FA2007-A1 (45 Ah) or2 x FA2008-A1 (65 Ah) or2 x FA2009-A1 (100 Ah)
Expansion FTO2001-A1 Event printerFCM7211-Y3 Operating add-on (2xLED ind.)FCM7212-Y3 Operating add-on (4xLED ind.)FP2003-A1 Power supply kit (70 W)FP2004-A1 Power supply kit (150 W‚ A)FP2005-A1 Power supply kit (150 W‚ B)
S54400-B89-A1
FH7205-Z3 Housing (Large)
Empty housing for open application‚ e.g. additional batteries‚ for oper-ating add-ons or for the event printer.
Cabinet dimensions (W x H x D) 430 x 796 x 260 mm
Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design050 00 00
Protection category IP30
Integral battery space 4 x FA2006-A1 (26 Ah) or4 x FA2007-A1 (45 Ah) or2 x FA2008-A1 (65 Ah) or2 x FA2009-A1 (100 Ah)
Expansion FTO2001-A1 Event printerFCM7211-Y3 Operating add-on (2xLED ind.)FCM7212-Y3 Operating add-on (4xLED ind.)FP2003-A1 Power supply kit (70 W)FP2004-A1 Power supply kit (150 W‚ A)FP2005-A1 Power supply kit (150 W‚ B)
S54400-B86-A1
FCM7211-Y3 Operating add-on (2xLED ind.)
To update 48 LED display groups‚ with one red and one yellow LED each.Can be inserted in all empty housings.Inclusive cables and screws for installation.
Dimensions (W x H x D) 427 x 200 x 25 mm
S54400-F75-A1
02.fm Seite 23 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsExpansion FC72x
2-24 © Siemens Switzerland Ltd 2010
Type Order No.
FCM7212-Y3 Operating add-on (4xLED ind.)
To update 96 LED display groups‚ with one red and one yellow LED each.Can be inserted in all empty housings.Inclusive cables and screws for installation.
Dimensions (W x H x D) 427 x 200 x 25 mm
S54400-F88-A1
FCM7221-H3 Operating add-on (2xEVAC)
The operating add-on is composed of an operation of 10 zones and an extension of another 10 zones. This application completes the fire con-trol panel with evacuation operating panel used by the fire brigade to activate or deactivate alarming devices in single zones. The operating add-on can be directly mounted into a fire control panel. When the operating add-on is used remote from the control panel in a separate housing the connector board FTI2001-N1 is necessary.Connection to fire control panel via serial RS485 interface.Inclusive cables and screws for installation.The RS485 module and the connector board FTI2002-N1 must be ordered separately.
Dimensions (W x H x D) 427 x 200 x 25 mm
Data sheet A6V10223093
S54400-F78-A1
FTI2002-N1 EVAC-NL connector board
The connector board is necessary if the operating add-on (2xEVAC) is used remote from the control panel in a separate housing. The connec-tion to the control panel occurs via the RS485 interface. The remote access to the operating add-on is possible until 1000 m.The RS485 module must be ordered separately and to be mounted in the control panel.
Supply voltage 20… 32 VDC
Operating current max. 190 mA @ 21 VDC
Cable capacity 0.5… 1.5 mm2
Dimensions (W x H x D) 121 x 130 x 32 mm
Data sheet A6V10223093
S54400-A15-A1
FT2003-N1 Mimic display driver (EVAC)
The mimic display driver is necessary if the evacuation panel has to be built in a customer-specific housing with customized LEDs and keys in a plant layout (mimic display). The mimic display is composed of a con-nector board and a print of the operating add-on.In order to realize a panel for 20 evacuation zones‚ 2 mimic display driv-ers are required (Master and Slave).The 34-pin ribbon cable for connection of LEDs‚ keys and key switch must be provided by the customer.The RS485 module must be ordered separately and mounted in the control panel.
Supply voltage 20… 32 VDC
Operating current max. 190 mA @ 21 VDC
Cable capacity 0.5… 1.5 mm2
Dimensions (W x H x D) 121 x 206 x 47 mm
Data sheet A6V10223093
S54400-A14-A1
02.fm Seite 24 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsExpansion FC72x
2-25© Siemens Switzerland Ltd 2010
2Type Order No.
FP2003-A1 Power supply kit (70 W)
Auxiliary power supply to all stations (control panels and terminals).Converts mains voltage to system voltage. Monitors mains voltage and batteries.
Supply voltage 85... 265 VAC
Power consumption max. 90 VA
Current 0.5… 1 A
Dimensions (W x H x D) 95 x 170 x 54 mm
A5Q00016005
FP2004-A1 Power supply kit (150 W‚ A)
Power supply kit (150 W‚ A) as auxiliary power supply for installation into empty housings.Converts mains voltage to system voltage. Monitors mains voltage and batteries.
Supply voltage 115... 230 VAC
Power consumption max. 300 VA
Current 2.6 / 1.2 A
Dimensions (W x H x D) 130 x 150 x 70 mm
A5Q00020825
FP2005-A1 Power supply kit (150 W‚ B)
Power supply kit (150 W‚ B) as auxiliary power supply for cascading.Converts mains voltage to system voltage. Monitors mains voltage and batteries.
Supply voltage 115... 230 VAC
Power consumption max. 300 VA
Current 2.6 / 1.2 A
Dimensions (W x H x D) 130 x 150 x 70 mm
A5Q00018779
02.fm Seite 25 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsNetwork Components Cluster (C-WEB/SAFEDLINK)
2-26 © Siemens Switzerland Ltd 2010
Type Order No.
FN2001-A1 Network module (SAFEDLINK)
To network multiple stations in the FCnet/C-WEB cluster. Up to 32 pan-els can be networked. Plugged into the back side of the operating unit.
Cable capacity 0.2… 1.5 mm2
Dimensions (W x H x D) 50 x 20 x 70 mm
A5Q00012851
FN2002-A1 Repeater (SAFEDLINK)
The module is a repeater in the FCnet/C-WEB cluster. It is used for the extension of the range of the system bus. 1 repeater max. can be used between 2 stations. The distance between network module and repeat-er may be up to 1000 m.The repeater can be mounted directly on a plane surface‚ onto a U-rail TS35 with the enclosed mounting feet or in the housing FDCH221.The accessories must be ordered separately.
Communication protocol SAFEDLINK (UDP/IP)
Operating voltage 9... 30 VDC
Operating current max. 45 mA
Cable capacity 0.08... 1.5 mm2
Relative humidity L95 %
Color housing/cover white‚ zRAL 9010/transparent matt
Protection category IP30IP65 with aux. housing FDCH221
Dimensions (W x H x D) 132 x 90 x 24 mm
Accessories TS35_122 U-railTS35_288 U-railFDCH221 Housing IP65
S24236-B2502-A1
02.fm Seite 26 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsNetwork Components Backbone (C-WEB/LAN)
2-27© Siemens Switzerland Ltd 2010
2Type Order No.
FN2008-A1 Ethernet switch
The Ethernet switch connects individual clusters via the Ethernet back-bone. A second switch can be added if a cluster has more than 512 detectors. With a mounting kit (FHA2029-A1 or FHA2030-A1)‚ the Ethernet switch can be easily integrated into panels or additional hous-ings.
S54400-F94-A1
FN2009-A1 Security module
Protects devices and networks in automation and industrial communi-cation with a combination of different security measures such as fire-wall and VPN (Virtual Private Network) via IPsec tunnel. The security module can be easily integrated into a panel with a mounting kit (FHA2029-A1 or FHA2030-A1).
S54400-F95-A1
FHA2029-A1 Mounting kit for housing (Comfort) S54400-B79-A1
FHA2030-A1 Mounting kit for housing (Large Extension) S54400-B81-A1
02.fm Seite 27 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsAccessories FC72x
2-28 © Siemens Switzerland Ltd 2010
Type Order No.
FTO2005-C1 Key switch (Kaba)
Kaba key switch with mounting accessories and key (Kaba 8 #100)‚ as an option for operating access (operating unit).
A5Q00010113
FTO2006-B1 Key switch (Nordic)
Nordic key switch with mounting accessories and key (Nordic)‚ as an option for operating access (operating unit).
A5Q00010129
Z3B171 Relay module with 1 contact
The relay module is an additional fire event control module‚ activated by the fire control panel's control output.
Contact rating 250 VAC / 10 A
Delivery unit 10 pieces
BPZ:4843830001
FHA2016-A1 19" mounting kit
To install fire control panels and fire terminals in a 19" third-party hous-ing.
Dimensions (W x H x D) 430 x 100 x 324 mm
A5Q00020179
FCA2014-A1 Cable kit (communication)
For flexible cable connections to the modules on the PMI-& main board.
A5Q00023027
02.fm Seite 28 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsAccessories FC72x
2-29© Siemens Switzerland Ltd 2010
2Type Order No.
DL3750+ Matrix printer external
The Fujitsu DL3750+ is a compact‚ noiseless A4 matrix printer. It is used for documenting relevant information in a system on continuous paper. The printer is constantly supervised by the fire control panel. The type of events to be printed is configurable. It offers a maximum of speed and reliability.The RS232 module FCA2001-A1 is required to operate the printer and must be ordered separately.
Number of copies 5 incl. original
Character set 6
Resolution 360 x 360 dpi
Interface RS232 orEthernet (via Print-Server PS01a)
Operating temperature +5… +38 °C
Storage temperature -15… +60 °C
Relative humidity L95 % (no condensation)
Dimensions (W x H x D) 415 x 120 x 330 mm
A5Q00023962
02.fm Seite 29 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFT724 Networkable Fire Operating TerminalsFT724 Operating Terminal to FC72x
2-30 © Siemens Switzerland Ltd 2010
Type Order No.
FT724.. Fire terminal
The FT724.. fire terminal is an operating panel remote from the central control panel that can be operated with its own power supply as well‚ as an option. The operating unit has installation slots for optional inter-faces such as RS232‚ RS485‚ networking modules (SAFEDLINK) and a key switch. Each station has an Ethernet connection to which other fire terminals or a PC can be connected for remote operation/engineering. This Ethernet connection enables a maximum of 4 stations including a Global Access Point 'GAP' (via Hub) to be networked together and be connected to a Siemens danger management system (not EN 54-com-pliant). Up to 32 fire control panels and fire terminals can be connected in a single cluster (C-WEB/SAFEDLINK network)‚ or up to 16 panels when the cluster is connected to a danger management system. Using a fiber-optic backbone (C-WEB/LAN) up to 14 of these clusters with up to 16 panels each can be networked. This topology enables the construction of an EN 54-conform network with up to 64 fire control panels and fire terminals.The optional power supply i.e. power supply kit (70 W) and batteries 2 x 12 V / 7 Ah must be ordered separately.
Operating voltage 21… 28.6 VDC
Quiescent current 125 mA
Alarm current 130 mA
Power supply 70 W (optional)
Battery capacity max. 2 x 12 V / 7 Ah (optional)
Plug-in position 2 -> for serial interfaces RS232‚ RS4852 -> for network modules
Operating temperature -8… +42 °C
Storage temperature -20… +60 °C
Relative humidity L95 % (no condensation)
Protection category IP30
Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design 050 00 00
Cabinet dimensions (W x H x D) 430 x 398 x 80 mm
Data sheet A6V10207898
FT724..
FT724-ZZ Fire terminal
See FT724.. for technical overview and note the additional / other specifications:
Expansion FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FTO2001-A1 Event printerFN2001-A1 Network module (SAFEDLINK)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FP2003-A1 Power supply kit (70 W)FH7201-Z3 Housing (Eco)
Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)FHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer (Extern)
S54400-C31-A2
02.fm Seite 30 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFT724 Networkable Fire Operating TerminalsFT724 Operating Terminal to FC72x
2-31© Siemens Switzerland Ltd 2010
2Type Order No.
FT724-HZ Fire terminal with EVAC operating unit
See FT724.. for technical overview and note the additional / other specifications:
With 10 evacuation operating zones for Netherlands.
Expansion FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FN2001-A1 Network module (SAFEDLINK)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FP2003-A1 Power supply kit (70 W)FH7201-Z3 Housing (Eco)
Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)FHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer (Extern)
S54400-C31-A1
02.fm Seite 31 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFT724 Networkable Fire Operating TerminalsExpansion FT724
2-32 © Siemens Switzerland Ltd 2010
Type Order No.
FCA2012-A1 License key (L1)
iButton with license for:Sinteso -> SintesoViewCerberus PRO -> Cerberus-RemoteOnly one license key is required per system.
A5Q00018856
FCA2013-A1 License key (L2)
iButton with license for:Sinteso -> SintesoView and BACnetCerberus PRO -> Cerberus-Remote and BACnetOne license key is required per station.
A5Q00018857
FN2001-A1 Network module (SAFEDLINK)
To network multiple stations in the FCnet/C-WEB cluster. Up to 32 pan-els can be networked. Plugged into the back side of the operating unit.
Cable capacity 0.2… 1.5 mm2
Dimensions (W x H x D) 50 x 20 x 70 mm
A5Q00012851
FCA2001-A1 RS232 module (isolated)
Module for periphery devices with RS232 interface‚ e.g. for event print-er FTO2001-A1. Plugged into the back side of the operating unit.RS232 module incl. 1 EMC screwed cable gland M10 x 1.5.
Cable capacity 0.2… 1.5 mm2
Dimensions (W x H x D) 50 x 15 x 70 mm
A5Q00005327
FCA2002-A1 RS485 module (isolated)
Module for periphery devices with RS485 interface‚ e.g. for FAT (GER). Plugged into the back side of the operating unit.RS485 module incl. 1 EMC screwed cable gland M10 x 1.5.
Cable capacity 0.2… 1.5 mm2
Dimensions (W x H x D) 50 x 15 x 70 mm
A5Q00009923
02.fm Seite 32 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFT724 Networkable Fire Operating TerminalsExpansion FT724
2-33© Siemens Switzerland Ltd 2010
2Type Order No.
FP2003-A1 Power supply kit (70 W)
Auxiliary power supply to all stations (control panels and terminals).Converts mains voltage to system voltage. Monitors mains voltage and batteries.
Supply voltage 85... 265 VAC
Power consumption max. 90 VA
Current 0.5… 1 A
Dimensions (W x H x D) 95 x 170 x 54 mm
A5Q00016005
FH7201-Z3 Housing (Eco)
Empty housing for open use‚ e.g. power supply kit with batteries‚ oper-ating add-on‚ event printer or mimic display.
Protection category IP30
Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design 050 00 00
Cabinet dimensions (W x H x D) 430 x 398 x 80 mm
Integral battery space 2 x FA2003-A1 (7 Ah)
Expansion FTO2001-A1 Event printerFCM7211-Y3 Operating add-on (2xLED-ind.)FCM7212-Y3 Operating add-on (4xLED-ind.)FP2003-A1 Power supply kit (70 W)
S54400-B72-A1
FCM7211-Y3 Operating add-on (2xLED ind.)
To update 48 LED display groups‚ with one red and one yellow LED each.Can be inserted in all empty housings.Inclusive cables and screws for installation.
Dimensions (W x H x D) 427 x 200 x 25 mm
S54400-F75-A1
FCM7212-Y3 Operating add-on (4xLED ind.)
To update 96 LED display groups‚ with one red and one yellow LED each.Can be inserted in all empty housings.Inclusive cables and screws for installation.
Dimensions (W x H x D) 427 x 200 x 25 mm
S54400-F88-A1
02.fm Seite 33 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFT724 Networkable Fire Operating TerminalsExpansion FT724
2-34 © Siemens Switzerland Ltd 2010
Type Order No.
FTO2001-A1 Event printer
The event printer is a thermal printer that logs alarms‚ faults and gener-al messages. The event printer can be used in all control panels if space is available. The RS232 module is required to operate the printer. Event printer includes cables for interface and power supply and a paper roll.The RS232 module FCA2001-A1 must be ordered separately.
Operating voltage 9… 48 VDC
Quiescent current 50 mA
Operating current 3 A @ 9 VDC0.7 A @ 48 VDC
Interface RS232 serial
Operating temperature 0… +50 °C
Storage temperature -20… +70 °C
Relative humidity L95 % (no condensation)
Dimensions (W x H x D) 85 x 85 x 55 mm
A5Q00010126
02.fm Seite 34 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFT724 Networkable Fire Operating TerminalsAccessories FT724
2-35© Siemens Switzerland Ltd 2010
2Type Order No.
FTO2005-C1 Key switch (Kaba)
Kaba key switch with mounting accessories and key (Kaba 8 #100)‚ as an option for operating access (operating unit).
A5Q00010113
FTO2006-B1 Key switch (Nordic)
Nordic key switch with mounting accessories and key (Nordic)‚ as an option for operating access (operating unit).
A5Q00010129
FHA2016-A1 19" mounting kit
To install fire control panels and fire terminals in a 19" third-party hous-ing.
Dimensions (W x H x D) 430 x 100 x 324 mm
A5Q00020179
FCA2014-A1 Cable kit (communication)
For flexible cable connections to the modules on the PMI-& main board.
A5Q00023027
02.fm Seite 35 Mittwoch, 28. Juli 2010 8:17 08
Fire Control Network ParticipantsFT724 Networkable Fire Operating TerminalsAccessories FT724
2-36 © Siemens Switzerland Ltd 2010
Type Order No.
DL3750+ Matrix printer external
The Fujitsu DL3750+ is a compact‚ noiseless A4 matrix printer. It is used for documenting relevant information in a system on continuous paper. The printer is constantly supervised by the fire control panel. The type of events to be printed is configurable. It offers a maximum of speed and reliability.The RS232 module FCA2001-A1 is required to operate the printer and must be ordered separately.
Number of copies 5 incl. original
Character set 6
Resolution 360 x 360 dpi
Interface RS232 orEthernet (via Print-Server PS01a)
Operating temperature +5… +38 °C
Storage temperature -15… +60 °C
Relative humidity L95 % (no condensation)
Dimensions (W x H x D) 415 x 120 x 330 mm
A5Q00023962
02.fm Seite 36 Mittwoch, 28. Juli 2010 8:17 08
Genesis Series (1-zone Panels)
Safety for people and assetsOur Genesis Series stands for comprehensive safety. In combination with an intrusion control panel, it is the professional solution for reliable fi re detection. As your existing network infrastructure can be used for instal-lation, you will profi t from low investment costs.
Connected to an intrusion detection control panel, Genesis 2 enables the installation of a single-zone fi re detection system. It also controls and supervises a 2-wire line, equipped with up to 32 conventional detectors. Supplied with 12 VDC from the intrusion control panel, it is able to provide 24 VDC thanks to an internal converter. This is the power needed by detec-tors and/or call points.
One conventional line with a maximum of 32 detectors Compatible with conventional (SynoLINE300) and collective (SynoLINE600) devices Universal usage thanks to easy connectivity to all 12 VDC systems Reliable alarming via existing network Easy installation due to free contacts for fi re and fault alarm
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 15 28.05.10 16:57
Conventional Fire Control Panels1-zone PanelsGenesis Series
3-2 © Siemens Switzerland Ltd 2010
Type Order No.
GEN2.. Fire control panel for connection to 12 VDC supply
The Genesis 2 makes it possible to install a single fire detection zone when connected to intrusion control panel‚ controlling and supervising a 2-wire line‚ equipped with up to 32 conventional/collective detectors at 24 VDC.The Genesis 2 is supplied with 13.8 VDC from the intrusion control pan-el and‚ by means of an internal converter‚ is able to provide the 24 VDC supply required by the detectors and/or call points. This eliminates the need for an external 24 VDC power supply and battery backup‚ as in the case of mains failure or disconnection‚ the intrusion control panel back-up powers the system. Compatible with conventional/SynoLINE300 and collective/SynoLINE600.
Alarm relay output (NO/NC) 30 VDC / 1 A
Fault relay output (NO/NC) 30 VDC / 1 A
Power supply 11... 14 VDC / <200 mA
Output line voltage (stand-by) 17.5... 24 VDC
Stand-by current 35... 45 mA
Dimensions (W x H x D) 134 x 85 x 27 mm
Data sheet 009159
GEN2..
GEN2-en Fire control panel for connection to 12 VDC supply
See GEN2.. for technical overview and note the additional / other specifications:
English language printed on the product.
BPZ:9300110001
GEN2-de Fire control panel for connection to 12 VDC supply
See GEN2.. for technical overview and note the additional / other specifications:
German language printed on the product.
BPZ:9300150001
GEN2-it Fire control panel for connection to 12 VDC supply
See GEN2.. for technical overview and note the additional / other specifications:
Italian language printed on the product.
BPZ:9300120001
GEN2-se Fire control panel for connection to 12 VDC supply
See GEN2.. for technical overview and note the additional / other specifications:
Swedish language printed on the product.
BPZ:9300130001
GEN2-fr Fire control panel for connection to 12 VDC supply
See GEN2.. for technical overview and note the additional / other specifications:
French language printed on the product.
BPZ:9300180001
GEN2-nl Fire control panel for connection to 12 VDC supply
See GEN2.. for technical overview and note the additional / other specifications:
Dutch language printed on the product.
BPZ:9300190001
03.fm Seite 2 Mittwoch, 28. Juli 2010 8:25 08
Conventional Fire Control Panels1-zone PanelsGenesis Series
3-3© Siemens Switzerland Ltd 2010
3Type Order No.
GEN2-es Fire control panel for connection to 12 VDC supply
See GEN2.. for technical overview and note the additional / other specifications:
Spanish language printed on the product.
BPZ:9300100001
MGEN2 Fire control panel PCB for all languages
As GEN2.. for technical specifications but without housing.
BPZ:9300170001
03.fm Seite 3 Mittwoch, 28. Juli 2010 8:25 08
Conventional Fire Control Panels
FC10 fi re control panel – for easy controlFC10 has been designed to ensure the simplest operation possible – with clear LED displays, a key switch, and an ergonomically designed keyboard. System testing and isolation can be performed with confi dence using the comprehensive array of clear, concise controls and indicators. Independent controls and the option of code or key switch access allow users to decide which is best for them. The ability of FC10 to work in two distinct modes reduces the possibility of false alarms and the simple method of selection allows this feature to be used without complication. Furthermore, FC10 can be programmed to delay communication with the fi re brigade for automatic alarms in “manned” mode.
Manned/unmanned operation Differentiation of manual and automatic alarm origin without separate wiring Code or key switch user access Clear, comprehensive indication and controls for easy operation Vast array of programmable functions Optional clock and alarm counter
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 16 28.05.10 16:57
Easy control with the conventional fi re control panel FC10The brief overview below demonstrates the perfect interaction of the panel and the devices
FC1002-A
Manual call pointFDM1101A-Rx
Optical smoke detector OP320C
Manual callpointDM1101
Alarm transmission
Fault transmission
Multi-sensor smoke detector OH320C
Heat detector HI320C (rate of rise and maximum)
Smoke detector DO1101A collective wide spectrum
Heat detector HI322C (maximum)
Alarm indicator AI91C/AI92C
Alarm indicator FDAI91/FDAI92
conventional (SynoLINE300)
conventional (SynoLINE300)
collective (SynoLINE600)
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 17 28.05.10 16:57
Conventional Fire Control Panels2-zone PanelsFC10 Series
3-6 © Siemens Switzerland Ltd 2010
Type Order No.
FC1002.. 2-zone conventional unit
The FC10 series sets the new standard in functionality and design for conventional fire detection panels. FC1002.. is an easy-to-handle‚ cost-effective fire detection panel that is ideal for small installations. Easy on-site configuration. Each line can be individually configured to AlgoRex collective or Synova conventional. This allows connection to Sinteso FDOOT241-9 (collective mode)‚ AlgoRex DS11 (collective) and Synova conventional detectors. Furthermore this includes special detectors as FDF2x1-9 flame detectors‚ FDL241-9 linear smoke detec-tor.
Conventional line 2
Transmission output contact 2 x 30 VDC / 1 A
Supervised output 2 x 24 VDC / 0.5 A
Control output 5 x 24 VDC / 40 mA
Control input 3
Mains voltage 115... 230 VAC / 0.7 A +10 %... -15 %‚ 50/60 Hz
Power consumption 13... 25 VA
Quiescent current 80 mA
Battery capacity 2 x 12 V / 7.2 Ah
Standard EN 54-2‚ EN 54-4
Dimensions (W x H x D) 370 x 286 x 90 mm
Case protection category IP40
Color white‚ zRAL 9003
Data sheet A6V10277145
Accessories Z3B171 Relay moduleFCA1007 Key switch kitFCA1016 Battery holder
FC1002..
FC1002-A 2-zone conventional unit (Standard)
See FC1002.. for technical overview and note the additional / other specifications:
Inscription stripes are enclosed in the following languages: English‚ French‚ German‚ Italian‚ Spanish‚ Dutch‚ Flemish‚ Portuguese‚ Polish‚ Czech‚ Swedish and Danish.
S54380-C2-A1
FC1002-B 2-zone conventional unit (Head removal monitoring)
See FC1002.. for technical overview and note the additional / other specifications:
Special line monitoring for removal of a detector.Inscription stripes in English are enclosed.
S54380-C2-A10
FC1002-C 2-zone conventional unit (Nordic)
See FC1002.. for technical overview and note the additional / other specifications:
Operating access through Nordic key.Inscription stripes are enclosed in the following languages: Swedish‚ Danish‚ Norwegian and Finnish.
S54380-C2-A20
03.fm Seite 6 Mittwoch, 28. Juli 2010 8:25 08
Conventional Fire Control Panels2-zone PanelsAccessories FC1002
3-7© Siemens Switzerland Ltd 2010
3Type Order No.
Z3B171 Relay module with 1 contact
The relay module is an additional fire event control module‚ activated by the fire control panel's control output.
Contact rating 250 VAC / 10 A
Delivery unit 10 pieces
BPZ:4843830001
FCA1007 Key switch kit
To provide operating access via key switch instead of password.
A6E60500026
FCA1016 Battery holder
Battery holder for 7 Ah batteries
S54400-B90-A1
03.fm Seite 7 Mittwoch, 28. Juli 2010 8:25 08
Conventional Fire Control Panels4-zone PanelsFC10 Series
3-8 © Siemens Switzerland Ltd 2010
Type Order No.
FC1004.. 4-zone conventional unit
The FC10 series sets the new standard in functionality and design for conventional fire detection panels. FC1004.. is an easy-to-handle‚ cost-effective fire detection panel that is ideal for small installations. Easy on-site configuration. Each line can be individually configured to AlgoRex collective or Synova conventional. This allows connection to Sinteso FDOOT241-9 (collective mode)‚ AlgoRex DS11 (collective) and Synova conventional detectors. Furthermore this includes special detectors as FDF2x1-9 flame detectors‚ FDL241-9 linear smoke detec-tor.
Conventional line 4
Transmission output contact 2 x 30 VDC / 1 A
Supervised output 2 x 24 VDC / 0.5 A
Control output 7 x 24 VDC / 40 mA
Control input 3
Mains voltage 115... 230 VAC / 0.7 A +10 %... -15 %‚ 50/60 Hz
Power consumption 13... 25 VA
Quiescent current 90 mA
Battery capacity 2 x 12 V / 7.2 Ah
Standard EN 54-2‚ EN 54-4
Dimensions (W x H x D) 370 x 286 x 90 mm
Case protection category IP40
Color white‚ zRAL 9003
Data sheet A6V10277145
Accessories Z3B171 Relay moduleFCA1007 Key switch kitFCA1016 Battery holder
FC1004..
FC1004-A 4-zone conventional unit (Standard)
See FC1004.. for technical overview and note the additional / other specifications:
Inscription stripes are enclosed in the following languages: English‚ French‚ German‚ Italian‚ Spanish‚ Dutch‚ Flemish‚ Portuguese‚ Polish‚ Czech‚ Swedish and Danish.
S54380-C3-A1
FC1004-B 4-zone conventional unit (Head removal monitoring)
See FC1004.. for technical overview and note the additional / other specifications:
Special line monitoring for removal of a detector.Inscription stripes in English are enclosed.
S54380-C3-A10
FC1004-C 4-zone conventional unit (Nordic)
See FC1004.. for technical overview and note the additional / other specifications:
Operating access through Nordic key.Inscription stripes are enclosed in the following languages: Swedish‚ Danish‚ Norwegian and Finnish.
S54380-C3-A20
FC1004-E 4-zone conventional unit (NL)
See FC1004.. for technical overview and note the additional / other specifications:
Additional evacuation functions according to NEN2575.Inscription stripes in Dutch are enclosed.
S54380-C3-A30
03.fm Seite 8 Mittwoch, 28. Juli 2010 8:25 08
Conventional Fire Control Panels4-zone PanelsAccessories FC1004
3-9© Siemens Switzerland Ltd 2010
3Type Order No.
Z3B171 Relay module with 1 contact
The relay module is an additional fire event control module‚ activated by the fire control panel's control output.
Contact rating 250 VAC / 10 A
Delivery unit 10 pieces
BPZ:4843830001
FCA1007 Key switch kit
To provide operating access via key switch instead of password.
A6E60500026
FCA1016 Battery holder
Battery holder for 7 Ah batteries
S54400-B90-A1
03.fm Seite 9 Mittwoch, 28. Juli 2010 8:25 08
Conventional Fire Control Panels8-zone PanelsFC10 Series
3-10 © Siemens Switzerland Ltd 2010
Type Order No.
FC1008.. 8-zone conventional unit
The FC10 series sets the new standard in functionality and design for conventional fire detection panels. FC1008.. is an easy-to-handle‚ cost-effective fire detection panel that is ideal for small installations. Easy on-site configuration. Each line can be individually configured to AlgoRex collective or Synova conventional. This allows connection to Sinteso FDOOT241-9 (collective mode)‚ AlgoRex DS11 (collective) and Synova conventional detectors. Furthermore this includes special detectors as FDF2x1-9 flame detectors‚ FDL241-9 linear smoke detec-tor.
Conventional line 8
Transmission output contact 2 x 30 VDC / 1 A
Supervised output 2 x 24 VDC / 0.5 A
Control output 14 x 24 VDC / 40 mA
Control input 6
Mains voltage 115... 230 VAC / 1.5 A +10 %... -15 %‚ 50/60 Hz
Battery capacity 2 x 12 V / 12 Ah
Standard EN 54-2‚ EN 54-4
Dimensions (W x H x D) 506 x 378 x 125 mm
Case protection category IP40
Color housing/cover grey‚ zRAL 9006/white‚ zRAL 9003
Data sheet A6V10277147
Expansion FCA1002 Display unitFCA1003 Sounder control cardFCA1000-FF Interface card SSTFCA1005-D RT-isolation cardFCA1006-F RS232 adapter
Accessories Z3B171 Relay moduleFCA1007 Key switch kitFCA1014 Battery holder
FC1008..
FC1008-A 8-zone conventional unit (Standard)
See FC1008.. for technical overview and note the additional / other specifications:
Inscription stripes are enclosed in the following languages: English‚ French‚ German‚ Italian‚ Spanish‚ Dutch‚ Flemish‚ Portuguese‚ Polish‚ Czech‚ Swedish and Danish.
Power consumption 25... 45 VA
Quiescent current 125 mA
S54380-C4-A1
FC1008-B 8-zone conventional unit (Head removal monitoring)
See FC1008.. for technical overview and note the additional / other specifications:
Special line monitoring for removal of a detector.Inscription stripes in English are enclosed.
Power consumption 25... 45 VA
Quiescent current 125 mA
S54380-C4-A10
03.fm Seite 10 Mittwoch, 28. Juli 2010 8:25 08
Conventional Fire Control Panels8-zone PanelsFC10 Series
3-11© Siemens Switzerland Ltd 2010
3Type Order No.
FC1008-C 8-zone conventional unit (Nordic)
See FC1008.. for technical overview and note the additional / other specifications:
Operating access through Nordic key.Inscription stripes are enclosed in the following languages: Swedish‚ Danish‚ Norwegian and Finnish.
Power consumption 25... 45 VA
Quiescent current 125 mA
S54380-C4-A20
FC1008-D 8-zone conventional unit (CH)
See FC1008.. for technical overview and note the additional / other specifications:
With special fire brigade operating panel for the Swiss market.Inscription stripes in Swiss German‚ Swiss Italian and Swiss French are enclosed.
Power consumption 25... 45 VA
Quiescent current 125 mA
S54380-C4-A30
FC1008-E 8-zone conventional unit (Evacuation)
See FC1008.. for technical overview and note the additional / other specifications:
Additional evacuation functions according to NEN2575.With 3.5 A power supply FCP1004-E.Inscription stripes in Dutch are enclosed.
Power consumption 20... 110 VA
Quiescent current 170 mA
S54380-C4-A40
03.fm Seite 11 Mittwoch, 28. Juli 2010 8:25 08
Conventional Fire Control Panels8-zone PanelsExpansion FC1008
3-12 © Siemens Switzerland Ltd 2010
Type Order No.
FCA1002 Display unit
To provide alarm counter‚ clock‚ event memory‚ delay countdown. Fac-tory equipped with FC1008-E and FC1008-F‚ FC1012-F. Optional with FC1008-A/-B/-C/-D‚ FC1012-A/-B-C.
A6E60500021
FCA1003 Sounder control card
To provide 4 additional‚ monitored control lines. Not possible with FC1008-F‚ FC1012-F.
A6E60500022
FCA1005-D RT-isolation card
To provide hardware disconnecting facility for the remote transmission channels.
A6E60500024
03.fm Seite 12 Mittwoch, 28. Juli 2010 8:25 08
Conventional Fire Control Panels8-zone PanelsAccessories FC1008
3-13© Siemens Switzerland Ltd 2010
3Type Order No.
Z3B171 Relay module with 1 contact
The relay module is an additional fire event control module‚ activated by the fire control panel's control output.
Contact rating 250 VAC / 10 A
Delivery unit 10 pieces
BPZ:4843830001
FCA1007 Key switch kit
To provide operating access via key switch instead of password.
A6E60500026
FCA1014 Battery holder
Battery holder for 12 Ah or 17 Ah batteries
A6E60500069
03.fm Seite 13 Mittwoch, 28. Juli 2010 8:25 08
Conventional Fire Control Panels12-zone PanelsFC10 Series
3-14 © Siemens Switzerland Ltd 2010
Type Order No.
FC1012.. 12-zone conventional unit
The FC10 series sets the new standard in functionality and design for conventional fire detection panels. FC1012.. is an easy-to-handle‚ cost-effective fire detection panel that is ideal for small installations. Easy on-site configuration. Each line can be individually configured to AlgoRex collective or Synova conventional. This allows connection to Sinteso FDOOT241-9 (collective mode)‚ AlgoRex DS11 (collective) and Synova conventional detectors. Furthermore this includes special detectors as FDF2x1-9 flame detectors‚ FDL241-9 linear smoke detec-tor.
Conventional line 12
Transmission output contact 2 x 30 VDC / 1 A
Supervised output 2 x 24 VDC / 0.5 A
Control output 18 x 24 VDC / 40 mA
Control input 6
Mains voltage 115... 230 VAC / 1.5 A +10 %... -15 %‚ 50/60 Hz
Power consumption 25... 45 VA
Battery capacity 2 x 12 V / 12 Ah
Standard EN 54-2‚ EN 54-4
Dimensions (W x H x D) 506 x 378 x 125 mm
Case protection category IP40
Color housing/cover grey‚ zRAL 9006/white‚ zRAL 9003
Data sheet A6V10277147
Expansion FCA1002 Display unitFCA1003 Sounder control cardFCA1004-F Line extension card SSTFCA1005-D RT-isolation cardFCA1006-F RS232 adapter
Accessories Z3B171 Relay moduleFCA1007 Key switch kit
FC1012..
FC1012-A 12-zone conventional unit (Standard)
See FC1012.. for technical overview and note the additional / other specifications:
Inscription stripes are enclosed in the following languages: English‚ French‚ German‚ Italian‚ Spanish‚ Dutch‚ Flemish‚ Portuguese‚ Polish‚ Czech‚ Swedish and Danish.
Quiescent current 155 mA
S54380-C5-A1
FC1012-B 12-zone conventional unit (Head removal monitoring)
See FC1012.. for technical overview and note the additional / other specifications:
Special line monitoring for removal of a detector.Inscription stripes in English are enclosed.
Quiescent current 155 mA
S54380-C5-A10
03.fm Seite 14 Mittwoch, 28. Juli 2010 8:25 08
Conventional Fire Control Panels12-zone PanelsFC10 Series
3-15© Siemens Switzerland Ltd 2010
3Type Order No.
FC1012-C 12-zone conventional unit (Nordic)
See FC1012.. for technical overview and note the additional / other specifications:
Operating access through Nordic key.Inscription stripes are enclosed in the following languages: Swedish‚ Danish‚ Norwegian and Finnish.
Quiescent current 155 mA
S54380-C5-A20
03.fm Seite 15 Mittwoch, 28. Juli 2010 8:25 08
Conventional Fire Control Panels12-zone PanelsExpansion FC1012
3-16 © Siemens Switzerland Ltd 2010
Type Order No.
FCA1002 Display unit
To provide alarm counter‚ clock‚ event memory‚ delay countdown. Fac-tory equipped with FC1008-E and FC1008-F‚ FC1012-F. Optional with FC1008-A/-B/-C/-D‚ FC1012-A/-B-C.
A6E60500021
FCA1003 Sounder control card
To provide 4 additional‚ monitored control lines. Not possible with FC1008-F‚ FC1012-F.
A6E60500022
FCA1005-D RT-isolation card
To provide hardware disconnecting facility for the remote transmission channels.
A6E60500024
03.fm Seite 16 Mittwoch, 28. Juli 2010 8:25 08
Conventional Fire Control Panels12-zone PanelsAccessories FC1012
3-17© Siemens Switzerland Ltd 2010
3Type Order No.
Z3B171 Relay module with 1 contact
The relay module is an additional fire event control module‚ activated by the fire control panel's control output.
Contact rating 250 VAC / 10 A
Delivery unit 10 pieces
BPZ:4843830001
FCA1007 Key switch kit
To provide operating access via key switch instead of password.
A6E60500026
03.fm Seite 17 Mittwoch, 28. Juli 2010 8:25 08
081031_Product_Catalog_Innen_07lay.indd 17 24.07.09 18:04
Conventional Extinguishing Control Panels
XC10 – compact panels for fi re detection and extinguishing controlXC10 panels are the perfect choice for protecting valuable objects, a single room or multiple sectors with sophisticated requirements.XC10 can be installed as an independent control panel or be integrated into the fi re safety system Cerberus® PRO and be combined with the extinguishing system Sinorix.
Fire detection and extinguishing control in one panel Broad range of installations possible – single and multi sectors, stand-alone or integrated into a larger fi re safety system
Easy integration into Cerberus PRO for increased safety snoitacilppa dna stnega gnihsiug nitxe fo sepyt lla rof elbatiuS Multi-sector applications for the protection of up to 16 fl ooding zones Fast easy installation and commissioning Complies with international standards (EN 54-2/4, EN 12094-1,...)
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen_NEU.indd 19 01.06.10 13:31
Conventional Extinguishing Control PanelsConnectable to Fire Detection SystemsXC10 Series
4-2 © Siemens Switzerland Ltd 2010
Type Order No.
XC1001-A Extinguishing panel Standard
The compact dimensions of the Standard variant of XC1001-A are ide-ally adapted for single-sector applications‚ small to medium installa-tions. It provides a full range of monitored inputs and outputs as well as digital and relays outputs. Self-contained control panel including fire detection and extinguishing control. The configurable relay outputs can be used to transmit informations to an FS20/FC20 fire detection panel via FDnet/C-NET I/O modules.The detection lines can be configured to AlgoRex‚ Cerberus PRO‚ Sinteso and Synova.Easy and fast commissioning using 4 digital displays.
Conventional line 3
Alarm relay output (NO/NC) 30 V / 1 A max.
Control output 24 V / 1 A max.
Control input 4 (non monitored). Activation via contact.
Mains voltage 115... 230 VAC +10 %... -15 %‚ 50/60 Hz
Power consumption max. 150 VA
Battery capacity 2 x 12 V / 4.5... 17 Ah
Standard EN 12094-1‚ EN 54-2/A1‚ EN 54-4/A2
Dimensions (W x H x D) 370 x 286 x 90 mm
Case protection category IP30
Color white‚ zRAL 9003 (cover)‚ white alu-minium‚ zRAL 9006 (user interface)
Data sheet A6V10257471
Expansion XCE1002 Trigger elementXCA1020 Accessory set for FDCIOXCA1030 Multi-zone extension moduleXCA1031 Common multi-zone module
Accessories Z3B171 Relay moduleFCA1007 Key switch kitFCA1014 Battery holderXCH1001-A Cover set
S54390-C1-A1
04.fm Seite 2 Mittwoch, 28. Juli 2010 8:28 08
Conventional Extinguishing Control PanelsConnectable to Fire Detection SystemsXC10 Series
4-3© Siemens Switzerland Ltd 2010
4
Type Order No.
XC1005-A Extinguishing panel Comfort
The XC1005-A Comfort variant offers the same functions and connec-tion possibilities than XC1001-A. Thanks to the robustness of the cabi-net‚ this variant is an ideal choice for medium size single-sector instal-lations.With large and robust cabinet‚ a maximum of 72 h backup time with bat-tery capacity of 17 Ah‚ more space inside the cabinet for optional inter-faces or modules and display countdown timer before extinguishing release.
Conventional line 3
Alarm relay output (NO/NC) 30 V / 1 A max.
Control output 24 V / 1 A max.
Control input 4 (non monitored). Activation via contact.
Mains voltage 115... 230 VAC +10 %... -15 %‚ 50/60 Hz
Battery capacity 2 x 12 V / 4.5... 17 Ah
Dimensions (W x H x D) 505 x 375 x 125 mm
Case protection category IP40
Color white‚ zRAL 9003 (cover)‚ white alu-minium‚ zRAL 9006 (user interface)
Data sheet A6V10257471
Expansion XCE1002 Trigger elementXCA1020 Accessory set for FDCIOXCA1030 Multi-zone extension moduleXCA1031 Common multi-zone module
Accessories Z3B171 Relay moduleFCA1007 Key switch kitFCA1014 Battery holderXCH1005-A Cover set
S54390-C3-A1
04.fm Seite 3 Mittwoch, 28. Juli 2010 8:28 08
Conventional Extinguishing Control PanelsConnectable to Fire Detection SystemsXC10 Series
4-4 © Siemens Switzerland Ltd 2010
Type Order No.
XC1003-A Extinguishing panel Rack
The XC1003-A 19" Rack variant offers the same connection possibilities than XC1001-A. Up to 16 panels can be installed in a 19'' housing and configured to control a complex multi-sector installation.Thanks to the optional multi-sector modules‚ up to 16 panels can be connected together‚ a common control cylinder can be activated‚ selec-tor valves can be controlled and their position can be monitored and inter-blocking functions can be configured.
Conventional line 3
Alarm relay output (NO/NC) 30 V / 1 A max.
Control output 24 V / 1 A max.
Control input 4 (non monitored). Activation via contact.
Mains voltage 115... 230 VAC +10 %... -15 %‚ 50/60 Hz
Power consumption max. 150 VA
Battery capacity 2 x 12 V / 4.5... 17 Ah
Standard EN 12094-1‚ EN 54-2/A1‚ EN 54-4/A2
Dimensions (W x H x D) 482.6 x 177.8 x 187
Case protection category IP30
Color White aluminium‚ zRAL 9006
Data sheet A6V10257471
Expansion XCE1002 Trigger elementXCA1020 Accessory set for FDCIOXCA1030 Multi-zone extension moduleXCA1031 Common multi-zone module
Accessories Z3B171 Relay moduleFCA1007 Key switch kitFCA1014 Battery holderPF12 Cover plate 1UPF13 Cover plate 2UXCH1003-A Cover set
S54390-C2-A1
04.fm Seite 4 Mittwoch, 28. Juli 2010 8:28 08
Conventional Extinguishing Control PanelsConnectable to Fire Detection SystemsExpansion XC10
4-5© Siemens Switzerland Ltd 2010
4
Type Order No.
FCA1014 Battery holder
Battery holder for 12 Ah or 17 Ah batteries
A6E60500069
XCA1030 Multi-zone extension module
This module is connected to the XC1003-A mainboard XCM1002. Each extinguishing panel which is included in a multi-sector application must be equipped with this module.
S54390-A5-A1
XCA1031 Common multi-zone module
The inputs/outputs are monitored by the module itself. The power sup-ply is provided by the first and the last XC1003-A control unit.
S54390-A6-A1
XCA1020 Accessory set for FDCIO
Mounting support for I/O module FDCIO222 for the connection to a fire detection system.
A5Q00025158
XCE1002 Trigger element
Required as an alarm trigger element for manual call points with func-tionality Hold/Abort in case more than one manual call point is connect-ed on monitor control line 3 of the XC10.Manual call point type DM1103-S does not use this element‚ but the functionality of this trigger element XCE1002 is implemented.
A5Q00015659
04.fm Seite 5 Mittwoch, 28. Juli 2010 8:28 08
Conventional Extinguishing Control PanelsConnectable to Fire Detection SystemsAccessories XC10
4-6 © Siemens Switzerland Ltd 2010
Type Order No.
Z3B171 Relay module with 1 contact
The relay module is an additional fire event control module‚ activated by the fire control panel's control output.
Contact rating 250 VAC / 10 A
Delivery unit 10 pieces
BPZ:4843830001
FCA1007 Key switch kit
To provide operating access via key switch instead of password.
A6E60500026
04.fm Seite 6 Mittwoch, 28. Juli 2010 8:28 08
Conventional Extinguishing Control PanelsConnectable to Fire Detection SystemsXT10 Series
4-7© Siemens Switzerland Ltd 2010
4
Type Order No.
XT1001-A1 Repeater display
Small repeater display for use with XC10 extinguishing control panel system.Up to 16 repeaters can be connected to each XC10 extinguishing con-trol panel to provide control and remote status indication like Fire alarms‚ Communication faults‚ Activated‚ Discharged‚ Manual blocked‚ Automatic blocked‚ Fault‚ Disable‚ Loss of agent‚ Emergency hold and Power supply fault possible. Controls are Buzzer silence and Lamp test.One cable for data communication and one cable for power supply required. Power supply via the XC10 power supply output‚ separate 24 V power supply possible.
Storage temperature -10… +60 °C
Operating temperature -5... +40 °C
Quiescent current 18 mA at 24 V
Mains voltage 8... 30 VDC
Dimensions (W x H x D) 200 x 210 x 48
Case protection category IP40
Color grey‚ zRAL 9002
S54390-Z16-A1
XT1002-A1 Repeater display
Small repeater display for use with XC10 extinguishing control panel system.Up to 16 repeaters can be connected to each XC10 extinguishing con-trol panel to provide control and remote status indication like Fire alarms‚ Communication faults‚ Activated‚ Discharged‚ Manual blocked‚ Automatic blocked‚ Fault‚ Disable‚ Loss of agent‚ Emergency hold and Power supply fault possible. Controls are Buzzer silence‚ Lamp test‚ Mode of operation and Sounder silence via access level key operation.One cable for data communication and one cable for power supply required. Power supply via the XC10 power supply output‚ separate 24 V power supply possible.
Storage temperature -10… +60 °C
Operating temperature -5... +40 °C
Quiescent current 18 mA at 24 V
Mains voltage 8... 30 VDC
Dimensions (W x H x D) 200 x 210 x 48
Case protection category IP40
Color grey‚ zRAL 9002
S54390-Z15-A1
04.fm Seite 7 Mittwoch, 28. Juli 2010 8:28 08
Answers for infrastructure.
With XC10, Siemens offers a family of control panels for comprehensive fi re safety: the panel family combines both fi re detection and extinguishing control. XC10 panels are the ideal choice for protecting valuable objects, a single- or a multi-sector application with sophisticated requirements. XC10 can be installed as an independent control panel or be integrated into a larger fi re safety system. In addition, XC10 panels are easy to operate. The user interface provides a clear layout, so users can gain a complete system overview at a glance. And it’s a matter of course that all products comply with the latest international standards. www.siemens.com/XC10
XC10 – effi cient controlpanels for comprehensivefi re safetyFrom fi re detection to extinguishing control –from single-sector to multi-sector applications
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen_NEU.indd 20 01.06.10 13:31
Fire Detection Network (C-NET) Peripherals
Providing fast reliable detection with patented technologyNursing homes, offi ce buildings or production areas – people and assets have to be protected and business continuity secured. The Cerberus® PRO detector range provides the benefi ts of Siemens’ vast experience in detection techniques and applications. This experience ensures utterly reliable detection response. Thanks to special algo-rithms and selectable parameter sets, for example, detectors can be
.snoitidnoc lat nemnorivne detcepxe eht ot detsujda
Siemens has more than 150 years experience in fi re safety – with more than 60 million detectors installed worldwide
Fire detectors process signals with special detection algorithms – high reliability from false alarms Fire detectors offer selectable parameter sets – to adjust them to the surrounding conditions A wide range of special detectors – to cover even special applications All detectors are connected via and powered by C-NET – less wiring and reuse of existing cables
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 21 28.05.10 16:57
Addressable fi re detectors – point detectors
Detector base sealRS720
Connection terminalDBZ1190-AB
* cannot be used together with RS720
Micro terminalDBZ1190-AA
Multi-sensor smoke detector
OH720
Detector base DB721
Designation plateFDBZ291*
Detector locking deviceLP720
or
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 22 28.05.10 16:57
Fire Detection Network (C-NET) PeripheralsAddressable Fire DetectorsPoint Detectors
5-3© Siemens Switzerland Ltd 2010
5
Type Order No.
OH720 Multi-sensor smoke detector
For the detection of flaming fires caused by the combustion of liquid and solid matters‚ as well as smoldering fires. For reliable fire detection in environments with deceptive phenomena.Works according to the scattered-light principle with an optical forward scattering sensor. An additional heat sensor increases the fire detector's immunity to deceptive phenomena. Selectable detection behavior by different parameter sets. Immunity against transient false alarm causes.The base must be ordered separately.Scope of deliveryDetector and dust cap.
Communication protocol C-NET
Operating voltage 12... 33 VDC
Quiescent current z230 NA
Ext. alarm indicator 2
Operating temperature -10... +50 °C
Storage temperature -30... +70 °C
Permissible air speed max. 5 m/s
Relative humidity L95 %
Color white‚ zRAL 9010
Protection category IP40IP42 with detector base seal RS720
System compatibility FS720
Standard CEA4021‚ EN 54-7‚ EN 54-17
Dimensions (Ø x H) 117 x 59 mm (incl. base)
Data sheet A6V10202198
Accessories LP720 Detector locking device
S54310-F2-A1
OP720 Optical smoke detector
For the detection of smoke-generating flaming and smoldering fires. Works according to the scattered-light principle with an optical forward scattering sensor. Selectable detection behavior by different parameter sets. The base must be ordered separately.Scope of deliveryDetector and dust cap.
Communication protocol C-NET
Operating voltage 12... 33 VDC
Quiescent current z220 NA
Ext. alarm indicator 2
Operating temperature -10... +50 °C
Storage temperature -30... +70 °C
Permissible air speed max. 5 m/s
Relative humidity L95 %
Color white‚ zRAL 9010
Protection category IP40IP42 with detector base seal RS720
System compatibility FS720
Standard EN 54-7‚ EN 54-17
Dimensions (Ø x H) 117 x 56 mm (incl. base)
Data sheet A6V10202198
Accessories LP720 Detector locking device
S54310-F1-A1
05.fm Seite 3 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Fire DetectorsPoint Detectors
5-4 © Siemens Switzerland Ltd 2010
Type Order No.
HI720 Heat detector (static+RoR)
For use in areas where smoke detection is impractical due to high level of dust‚ dirt‚ steam and high humidity. Selectable parameter sets for rate of rise and fixed temperature.The base must be ordered separately.Scope of deliveryDetector and dust cap.
Communication protocol C-NET
Operating voltage 12... 33 VDC
Quiescent current z200 NA
Ext. alarm indicator 2
Operating temperature -10... +50 °C
Storage temperature -30... +70 °C
Relative humidity L95 %
Color white‚ zRAL 9010
Protection category IP40IP42 with detector base seal RS720
System compatibility FS720
Standard EN 54-5‚ EN 54-17
Dimensions (Ø x H) 117 x 59 mm (incl. base)
Data sheet A6V10202198
Accessories LP720 Detector locking device
S54310-F4-A1
HI722 Heat detector (static)
Suitable in areas‚ in which temporary high variations in temperature arise. Measures the ambient temperature‚ when the maximum temper-ature is exceeded the detector sends a danger signal to the fire control panel.The base must be ordered separatelyScope of deliveryDetector and dust cap.
Communication protocol C-NET
Operating voltage 12... 33 VDC
Quiescent current z200 NA
Ext. alarm indicator 2
Operating temperature -10... +50 °C
Storage temperature -30... +70 °C
Relative humidity L95 %
Color white‚ zRAL 9010
Protection category IP40IP42 with detector base seal RS720
System compatibility FS720
Standard EN 54-5‚ EN 54-17
Dimensions (Ø x H) 117 x 59 mm (incl. base)
Data sheet A6V10202198
Accessories LP720 Detector locking device
S54310-F3-A1
05.fm Seite 4 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Fire DetectorsPoint Detectors
5-5© Siemens Switzerland Ltd 2010
5
Type Order No.
Accessories
LP720 Detector locking device
Threaded pin M3 x 12 to protect detector against theft.Scope of delivery2 hexagonal wrenches100 threaded pins
S54319-F9-A1
DB721 Detector base with loop contact
Universal base with extra large mounting slots facilitate use with a wide variety of back boxes and other electrical accessories. Connecting ter-minals for cable diameter at 1.6 mm2. Place for auxiliary terminals 2x DBZ1190-AA and 2x DBZ1190-AB. For all point detectors of the series Cerberus PRO FD720. Back entry for recess supply wiring. 2 breakouts on the side for surface wiring of cables up to 8 mm in diameter. By using the detector base with loop contact (DB721) the detector line is not interrupted even if no point detector is mounted
Cable capacity 0.2... 1.6 mm2
Dimensions (Ø x H) 117 x 23 mm
Color white‚ zRAL 9010
Accessories FDBZ291 Designation plateRS720 Detector base sealDBZ1190-AA Micro terminal 0.5 mm2
DBZ1190-AB Connection terminal 2.5 mm2
S54319-F11-A1
05.fm Seite 5 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Fire DetectorsPoint Detectors
5-6 © Siemens Switzerland Ltd 2010
Type Order No.
DBS720 Sounder base
Compatible with all point detectors of the series Cerberus PRO.The sounder base DBS720 and the detector compose a single unit‚ which already has a base and is mounted on ceilings‚ e.g. in hotel rooms‚ hospitals or nursing homes.The sounder base serves for acoustic alarming in the addressed FS720 fire detection system. The sounder base can be allocated freely from the fire control panel to activate as required. It is not dependent upon an alarm signal from its associated detector.Synchronized with all other alarm sounder and sounder beacon devices in the same detector line (C-NET).No auxiliary power supply required; power is supplied via C-NET.For recess supply wiring. For surface supply wiring‚ remove the corre-sponding breakouts for cable diameter up to max. Ø8 mm.
Communication protocol C-NET
Operating voltage 12... 33 VDC
Quiescent current 150 μA
Alarm current 1.2 mA
Cable capacity 0.2... 1.6 mm2
Number of sounds 11
Sound intensity 80... 88 dBA
Ext. alarm indicator 2
Operating temperature -25... +70 °C
Storage temperature -30... +70 °C
Relative humidity L95 %
Color white‚ zRAL 9010
Protection category IP41IP42 with detector base seal RS720
System compatibility C-NET -> FS720
Standard EN 54-3
Dimensions (W x H x D) 175 x 117 x 29 mm
Data sheet A6V10203095
Accessories FDBZ291 Designation plateRS720 Detector base sealDBZ1190-AA Micro terminal 0.5 mm2
DBZ1190-AB Connection terminal 2.5 mm2
S54319-F5-A1
Accessories
FDBZ291 Designation plate
To identify the location address for detector bases.
Dimensions (W x H) 62 x 35 mm
Color transparent
Delivery unit 10 pieces
A5Q00002621
RS720 Detector base seal
Seal for higher protection category.Compatible with base DB721 and sounder base DBS720.Not usable together with the designation plate FDBZ291.
Dimensions (Ø x H) 119 x 6.5 mm
Color transparent
Delivery unit 10 pieces
S54319-F8-A1
05.fm Seite 6 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Fire DetectorsPoint Detectors
5-7© Siemens Switzerland Ltd 2010
5
Type Order No.
DBZ1190-AA Micro terminal 0.5 mm2‚ 4-pole
As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.
Cable capacity 0.28... 0.5 mm2
Dimensions (W x H x D) 10 x 7 x 10 mm
Delivery unit 50 pieces
BPZ:4677080001
DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole
As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.
Cable capacity 1... 2.5 mm2
Dimensions (W x H x D) 13.5 x 9.5 x 19.5 mm
Delivery unit 50 pieces
BPZ:4942340001
05.fm Seite 7 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation
5-8 © Siemens Switzerland Ltd 2010
Type Order No.
FDM221__ Manual call point
For immediate manual actuation of an alarm. For indoor and outdoor application. For surface- and recess-mounted feed lines in easily acces-sible places. Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is set back and the device is ready for operation again.The housing FDMH291-x and the switching unit FDME221 must be ordered separately.
Communication protocol FDnet/C-NET
Operating temperature -25... +70 °C
Storage temperature -30... +75 °C
Relative humidity L95 % (no condensation)
Protection category IP44
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard EN 54-11‚ EN 54-17
Dimensions (W x H x D) 87 x 87 x 46.6 mm
Data sheet 007001
Accessories FDMC291 Protective coverA5Q00004478 Screwed cable gland M20A5Q00004479 Back nut M20
Products to select from
FDMH291-R See Page 5-8
FDMH291-B See Page 5-9
FDMH291-G See Page 5-9
FDMH291-Y See Page 5-8
FDME221 See Page 5-9
FDM221__
FDMH291-R Housing red with key
Housing with key for electronic unit.
Color red‚ zRAL 3000
A5Q00002217
FDMH291-Y Housing yellow with key
Housing with key for electronic unit.
Color yellow‚ zRAL 1023
A5Q00004979
05.fm Seite 8 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation
5-9© Siemens Switzerland Ltd 2010
5
Type Order No.
FDMH291-G Housing green with key
Housing with key for electronic unit.
Color green‚ zRAL 6024
A5Q00004981
FDMH291-B Housing blue with key
Housing with key for electronic unit.
Color blue‚ zRAL 5005
A5Q00004980
FDME221 Switching unit with direct alarm actuation
Switching unit with integrated line separator and built-in alarm indica-tor (LED). Two-colored LED for alarm and test.The switching unit can be placed immediately after connecting the feed line‚ which is an advantage if the line is tested with a line testing device.
Operating voltage 12... 33 VDC
Quiescent current 200 NA
Terminal block 0.28... 1.5 mm2
A5Q00002451
Accessories
FDMC291 Protective cover
The protective cover protects the manual call point from unintentional glass break. For manual call point housings FDMH291-x.
Delivery unit 5 pieces
A5Q00001644
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
05.fm Seite 9 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation
5-10 © Siemens Switzerland Ltd 2010
Type Order No.
A5Q00004479 Back nut M20
Back nut to screwed cable gland M20 x 1.5.
Delivery unit 10 pieces
A5Q00004479
FDM225-RG Manual call point with glass plate
For immediate manual actuation of a fire alarm. For indoor and outdoor application. Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is reset and the device is ready for operation again. For surface- and recess-mounted feed lines in eas-ily accessible places.For surface mounting the housing base FDMH295-x must be ordered separately.
Communication protocol FDnet/C-NET
Operating voltage 13... 33 VDC
Quiescent current 180 NA
Terminal block 0.28… 1.5 mm2
Operating temperature -25... +70 °C
Storage temperature -30... +75 °C
Relative humidity L95 % (no condensation)
Protection category IP44
Color red‚ zRAL 3000
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard EN 54-11‚ EN 54-17
Dimensions (W x H x D) 87 x 87 x 20 mm
Data sheet 009023
Accessories FDMH295-R housing baseFDMH295-S housing base with 2 holes + grommets for cable Ø5 mmFDMC295 Protective cover
A5Q00013434
05.fm Seite 10 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation
5-11© Siemens Switzerland Ltd 2010
5
Type Order No.
FDM225-RP Manual call point with resettable plastic element
For immediate manual actuation of a fire alarm. For indoor and outdoor application. Direct alarm actuation by pushing on the plastic element. The switch is reset with the key and the device is ready for operation again. For surface- and recess-mounted feed lines in easily accessible places.For surface mounting the housing base FDMH295-x must be ordered separately.
Communication protocol FDnet/C-NET
Operating voltage 13... 33 VDC
Quiescent current 180 NA
Terminal block 0.28… 1.5 mm2
Operating temperature -25... +70 °C
Storage temperature -30... +75 °C
Relative humidity L95 % (no condensation)
Protection category IP44
Color red‚ zRAL 3000
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard EN 54-11‚ EN 54-17
Dimensions (W x H x D) 87 x 87 x 20 mm
Data sheet 009023
Accessories FDMH295-R housing baseFDMH295-S housing base with 2 holes + grommets for cable Ø5 mmFDMC295 Protective cover
A5Q00012020
Accessories
FDMH295-R Back box
Housing base for manual call points FDM225‚ FDM1101 and FDM1101A for surface mounting.
Color red‚ zRAL 3000
Dimensions (W x H x D) 87 x 87 x 33
Accessories A5Q00004478 Screwed cable gland M20A5Q00004479 Back nut M20DBZ1190-AB Connection terminal 2.5 mm2
A5Q00013437
FDMH295-S Back box with 2 entries
Housing base for manual call points FDM225‚ FDM1101 and FDM1101A with 2 holes on top fitted with grommet for cable Ø5 mm for surface mounting.
Color red‚ zRAL 3000
Dimensions (W x H x D) 87 x 87 x 33
Accessories DBZ1190-AB Connection terminal 2.5 mm2
A5Q00013438
05.fm Seite 11 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation
5-12 © Siemens Switzerland Ltd 2010
Type Order No.
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
A5Q00004479 Back nut M20
Back nut to screwed cable gland M20 x 1.5.
Delivery unit 10 pieces
A5Q00004479
DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole
As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.
Cable capacity 1... 2.5 mm2
Delivery unit 50 pieces
BPZ:4942340001
FDMC295 Protective cover
The protective cover protects the manual call points FDM225‚ FDM226‚ FDM1101 and FDM1101A from unintentional glass break.
Color transparent
Delivery unit 10 pieces
A5Q00013440
FDM226-RG Manual call point with glass plate incl. housing base
For immediate manual actuation of a fire alarm. For indoor and outdoor application. Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is reset and the device is ready for operation again. For surface- and recess-mounted feed lines in eas-ily accessible places.
Communication protocol FDnet/C-NET
Operating voltage 13... 33 VDC
Quiescent current 180 NA
Terminal block 0.28… 1.5 mm2
Operating temperature -25... +70 °C
Storage temperature -30... +75 °C
Relative humidity L95 % (no condensation)
Protection category IP66
Color red‚ zRAL 3000
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard EN 54-11‚ EN 54-17
Dimensions (W x H x D) 87 x 87 (113) x 57 mm
Data sheet 009023
Accessories FDMC295 Protective cover
A5Q00013435
05.fm Seite 12 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation
5-13© Siemens Switzerland Ltd 2010
5
Type Order No.
FDM226-RP Manual call point with resettable plastic element incl. housing base
For immediate manual actuation of a fire alarm. For indoor and outdoor application. Direct alarm actuation by pushing on the plastic element. The switch is reset with the key and the device is ready for operation again. For surface- and recess-mounted feed lines in easily accessible places.
Communication protocol FDnet/C-NET
Operating voltage 13... 33 VDC
Quiescent current 180 NA
Terminal block 0.28… 1.5 mm2
Operating temperature -25... +70 °C
Storage temperature -30... +75 °C
Relative humidity L95 % (no condensation)
Protection category IP66
Color red‚ zRAL 3000
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard EN 54-11‚ EN 54-17
Dimensions (W x H x D) 87 x 87 (113) x 57 mm
Data sheet 009023
Accessories FDMC295 Protective cover
A5Q00013436
Accessories
FDMC295 Protective cover
The protective cover protects the manual call points FDM225‚ FDM226‚ FDM1101 and FDM1101A from unintentional glass break.
Color transparent
Delivery unit 10 pieces
A5Q00013440
05.fm Seite 13 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation
5-14 © Siemens Switzerland Ltd 2010
Type Order No.
FDM224__ Manual call point
For immediate manual actuation of an alarm. For indoor and outdoor application. For surface- and recess-mounted feed lines in easily acces-sible places. Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is reset and the device is ready for operation again.The housing FDMH293-x and the switching unit FDME224 must be ordered separately.
Communication protocol FDnet/C-NET
Ext. alarm indicator 2
Operating temperature -25... +70 °C
Storage temperature -30... +75 °C
Relative humidity L95 % (no condensation)
Protection category IP44 (IP64 with protection seal)
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard EN 54-11‚ EN 54-17
Dimensions (W x H x D) 134 x 134 x 43 mm
Data sheet 007001
Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20A5Q00006735 Locking plug M20(1 hole)A5Q00010055 Locking plug M20(2 holes)
Products to select from
FDMH293-R See Page 5-14
FDMH293-B See Page 5-15
FDMH293-O See Page 5-15
FDMH293-G See Page 5-15
FDMH293-Y See Page 5-15
FDME224 See Page 5-16
FDM224__
FDMH293-R Housing red‚ with glass and key
Manual call point housing for the switching unit FDME223‚ FDME224.
Color red‚ zRAL 3000
A5Q00004023
05.fm Seite 14 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation
5-15© Siemens Switzerland Ltd 2010
5
Type Order No.
FDMH293-Y Housing yellow‚ with glass and key
Manual call point housing for the switching unit FDME223‚ FDME224.
Color yellow‚ zRAL 1023
A5Q00004908
FDMH293-G Housing green‚ with glass and key
Manual call point housing for the switching unit FDME223‚ FDME224.
Color green‚ zRAL 6024
A5Q00004911
FDMH293-B Housing blue‚ with glass and key
Manual call point housing for the switching unit FDME223‚ FDME224.
Color blue‚ zRAL 5005
A5Q00004909
FDMH293-O Housing orange‚ with glass and key
Manual call point housing for the switching unit FDME223‚ FDME224.
Color orange‚ zRAL 2010
S54311-F2-A1
05.fm Seite 15 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation
5-16 © Siemens Switzerland Ltd 2010
Type Order No.
FDME224 Switching unit with direct alarm actuation
Switching unit with integrated line separator and built-in alarm indica-tor (LED). Two-colored LED for alarm and test.The switching unit can be placed immediately after connecting the feed line‚ which is an advantage if the line is tested with a line testing device.
Operating voltage 12... 33 VDC
Quiescent current 200 NA
Terminal block 0.28... 1.5 mm2
A5Q00009392
Accessories
DMZ1197-AD Protection seal
Protects the manual call point in wet applications.The seal improves the manual call point housing's protection category.
Delivery unit 5 pieces
BPZ:5470680001
DMZ1197-AC Protective cover
Protects the manual call point from unintentional glass break. Protec-tive cover can be easily fitted directly in the housing cover.
Delivery unit 5 pieces
BPZ:5223550001
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
A5Q00006735 Locking plug M20 x 1.5 (1 hole)
For manual call point housings and surface-mounted feed lines in the manual call point housing.For applications in dry rooms.
Color red‚ zRAL 3000
Delivery unit 10 pieces
A5Q00006735
05.fm Seite 16 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation
5-17© Siemens Switzerland Ltd 2010
5
Type Order No.
A5Q00010055 Locking plug M20 x 1.5 (2 holes)
For manual call point housings and surface-mounted feed lines in the manual call point housing.For applications in dry rooms.
Color red‚ zRAL 3000
Delivery unit 10 pieces
A5Q00010055
FDM224H__ Manual call point 'Heavy Duty'
For immediate manual actuation of a fire alarm. Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push but-ton is reset and the device is ready for operation again.For indoor and outdoor application‚ equally suited for wet‚ humid and dusty areas. Only for surface-mounted feed lines in easily accessible places‚ e.g. Tunnels‚ Industry.The housing is equipped with one opening at the top and two openings at the bottom for locking plugs and for metal screwed cable glands M20.For IP64 applications the unused openings must be locked with the V-plug.The housing FDMH292-R and the switching unit FDME224 must be ordered separately.
Communication protocol FDnet/C-NET
Ext. alarm indicator 2
Operating temperature -25... +70 °C
Storage temperature -30... +75 °C
Relative humidity L95 % (no condensation)
Protection category IP44 (IP64 with protection seal and V-plug)
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard EN 54-11‚ EN 54-17
Dimensions (W x H x D) 134 x 134 x 43 mm
Data sheet 008345
Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20A5Q00010055 V-plug PA M20
Products to select from
FDME224 See Page 5-18
FDMH292-R See Page 5-17
FDM224H__
FDMH292-R Housing red 'Heavy Duty'
Housing with glass‚ 3 pieces locking plugs M20 (2 holes)‚ hexagonal wrench 2.5 mm and label 'Feuerwehr/Brandmelder'.
Color red‚ zRAL 3000
A5Q00005525
05.fm Seite 17 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation
5-18 © Siemens Switzerland Ltd 2010
Type Order No.
FDME224 Switching unit with direct alarm actuation
Switching unit with integrated line separator and built-in alarm indica-tor (LED). Two-colored LED for alarm and test.The switching unit can be placed immediately after connecting the feed line‚ which is an advantage if the line is tested with a line testing device.
Operating voltage 12... 33 VDC
Quiescent current 200 NA
Terminal block 0.28... 1.5 mm2
A5Q00009392
Accessories
DMZ1197-AD Protection seal
Protects the manual call point in wet applications.The seal improves the manual call point housing's protection category.
Delivery unit 5 pieces
BPZ:5470680001
DMZ1197-AC Protective cover
Protects the manual call point from unintentional glass break. Protec-tive cover can be easily fitted directly in the housing cover.
Delivery unit 5 pieces
BPZ:5223550001
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
A5Q00008131 V-plug PA M20 x 1.5
For outdoor applications for locking the unused openings in the hous-ing FDMH292-R to improve the higher protection category.
Color black
A5Q00008131
05.fm Seite 18 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Indirect Operation
5-19© Siemens Switzerland Ltd 2010
5
Type Order No.
FDM223 Manual call point complete
For immediate manual actuation of a fire alarm. For indoor and outdoor application‚ equally suited for wet‚ humid and dusty areas. For surface- and recess-mounted feed lines in easily accessible places.Indirect alarm actuation by smashing in the glass plate and pressing the push button. To replace the glass plate‚ open the housing door with the key. The push button must be reset before closing the door again.The manual call point consists of a housing red with glass‚ key‚ switch-ing unit‚ 2 labels (standard with house and Feuerwehr/Brandmelder) and 2 locking plugs (2 holes).
Communication protocol FDnet/C-NET
Operating voltage 12... 33 VDC
Quiescent current 200 NA
Ext. alarm indicator 2
Operating temperature -25... +70 °C
Storage temperature -30... +75 °C
Relative humidity L95 % (no condensation)
Protection category IP44 (IP64 with protection seal)
Color red‚ zRAL 3000
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard EN 54-11‚ EN 54-17
Dimensions (W x H x D) 134 x 134 x 43 mm
Data sheet 007001
Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20
A5Q00008098
05.fm Seite 19 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Indirect Operation
5-20 © Siemens Switzerland Ltd 2010
Type Order No.
FDM223__ Manual call point
For immediate manual actuation of an alarm. For indoor and outdoor application‚ equally suited for wet‚ humid and dusty areas. For surface- and recess-mounted feed lines in easily accessible places.Indirect alarm actuation by pushing in the glass plate and pressing the push button. To replace the glass plate‚ open the housing door with the key. The push button must be reset before closing the door again.The housing FDMH293-x and the switching unit FDME223 must be ordered separately.
Communication protocol FDnet/C-NET
Ext. alarm indicator 2
Operating temperature -25... +70 °C
Storage temperature -30... +75 °C
Relative humidity L95 % (no condensation)
Protection category IP44 (IP64 with protection seal)
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard EN 54-11‚ EN 54-17
Dimensions (W x H x D) 134 x 134 x 43 mm
Data sheet 007001
Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20A5Q00006735 Locking plug M20(1 hole)A5Q00010055 Locking plug M20(2 holes)
Products to select from
FDMH293-B See Page 5-21
FDMH293-G See Page 5-21
FDMH293-R See Page 5-20
FDMH293-Y See Page 5-21
FDMH293-O See Page 5-21
FDME223 See Page 5-22
FDM223__
FDMH293-R Housing red‚ with glass and key
Manual call point housing for the switching unit FDME223‚ FDME224.
Color red‚ zRAL 3000
A5Q00004023
05.fm Seite 20 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Indirect Operation
5-21© Siemens Switzerland Ltd 2010
5
Type Order No.
FDMH293-Y Housing yellow‚ with glass and key
Manual call point housing for the switching unit FDME223‚ FDME224.
Color yellow‚ zRAL 1023
A5Q00004908
FDMH293-G Housing green‚ with glass and key
Manual call point housing for the switching unit FDME223‚ FDME224.
Color green‚ zRAL 6024
A5Q00004911
FDMH293-B Housing blue‚ with glass and key
Manual call point housing for the switching unit FDME223‚ FDME224.
Color blue‚ zRAL 5005
A5Q00004909
FDMH293-O Housing orange‚ with glass and key
Manual call point housing for the switching unit FDME223‚ FDME224.
Color orange‚ zRAL 2010
S54311-F2-A1
05.fm Seite 21 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Indirect Operation
5-22 © Siemens Switzerland Ltd 2010
Type Order No.
FDME223 Switching unit with indirect alarm actuation
Switching unit with integrated line separator and built-in alarm indica-tor (LED). Two-colored LED for alarm and test.The switching unit can be placed immediately after connecting the feed line‚ which is an advantage if the line is tested with a line testing device.
Operating voltage 12... 33 VDC
Quiescent current 200 NA
Terminal block 0.28... 1.5 mm2
A5Q00003087
Accessories
DMZ1197-AD Protection seal
Protects the manual call point in wet applications.The seal improves the manual call point housing's protection category.
Delivery unit 5 pieces
BPZ:5470680001
DMZ1197-AC Protective cover
Protects the manual call point from unintentional glass break. Protec-tive cover can be easily fitted directly in the housing cover.
Delivery unit 5 pieces
BPZ:5223550001
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
A5Q00006735 Locking plug M20 x 1.5 (1 hole)
For manual call point housings and surface-mounted feed lines in the manual call point housing.For applications in dry rooms.
Color red‚ zRAL 3000
Delivery unit 10 pieces
A5Q00006735
05.fm Seite 22 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Indirect Operation
5-23© Siemens Switzerland Ltd 2010
5
Type Order No.
A5Q00010055 Locking plug M20 x 1.5 (2 holes)
For manual call point housings and surface-mounted feed lines in the manual call point housing.For applications in dry rooms.
Color red‚ zRAL 3000
Delivery unit 10 pieces
A5Q00010055
FDM223H__ Manual call point 'Heavy Duty'
For immediate manual actuation of a fire alarm. Indirect alarm actua-tion by pushing in the glass plate and pressing the push button. To replace the glass plate‚ open the housing door with the key. The push button must be reset before closing the door again.For indoor and outdoor application‚ equally suited for wet‚ humid and dusty areas. Only for surface-mounted feed lines in easily accessible places‚ e.g. tunnels‚ industry.The housing is equipped with one opening at the top and two openings at the bottom for locking plugs and for metal screwed cable glands M20.For IP64 applications the unused openings must be locked with the V-plug.The housing FDMH292-R and the switching unit FDME223 must be ordered separately.
Communication protocol FDnet/C-NET
Operating temperature -25... +70 °C
Ext. alarm indicator 2
Storage temperature -30... +75 °C
Relative humidity L95 % (no condensation)
Protection category IP44 (IP64 with protection seal)
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard EN 54-11‚ EN 54-17
Dimensions (W x H x D) 134 x 134 x 43 mm
Data sheet 008345
Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20A5Q00010055 V-plug PA M20
Products to select from
FDMH292-R See Page 5-23
FDME223 See Page 5-24
FDM223H__
FDMH292-R Housing red 'Heavy Duty'
Housing with glass‚ 3 pieces locking plugs M20 (2 holes)‚ hexagonal wrench 2.5 mm and label 'Feuerwehr/Brandmelder'.
Color red‚ zRAL 3000
A5Q00005525
05.fm Seite 23 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Indirect Operation
5-24 © Siemens Switzerland Ltd 2010
Type Order No.
FDME223 Switching unit with indirect alarm actuation
Switching unit with integrated line separator and built-in alarm indica-tor (LED). Two-colored LED for alarm and test.The switching unit can be placed immediately after connecting the feed line‚ which is an advantage if the line is tested with a line testing device.
Operating voltage 12... 33 VDC
Quiescent current 200 NA
Terminal block 0.28... 1.5 mm2
A5Q00003087
Accessories
DMZ1197-AD Protection seal
Protects the manual call point in wet applications.The seal improves the manual call point housing's protection category.
Delivery unit 5 pieces
BPZ:5470680001
DMZ1197-AC Protective cover
Protects the manual call point from unintentional glass break. Protec-tive cover can be easily fitted directly in the housing cover.
Delivery unit 5 pieces
BPZ:5223550001
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
A5Q00008131 V-plug PA M20 x 1.5
For outdoor applications for locking the unused openings in the hous-ing FDMH292-R to improve the higher protection category.
Color black
A5Q00008131
05.fm Seite 24 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAlarm EquipmentAlarm Sounders‚ Alarm Sounder Beacon
5-25© Siemens Switzerland Ltd 2010
5
Type Order No.
FDS221-R Alarm sounder red
Loud alarming in case of fire alarm‚ clearly recognizable as danger sig-nal. To be mounted on the wall or on the ceiling along escape routes‚ corridors‚ staircases. Only applicable with addressable detector base. Power is supplied via FDnet/C-NET‚ no auxiliary power supply required. Monitoring of device status.For recess supply line. For surface supply line up to cable 6 mm in diam-eter with base FDB221‚ otherwise use the base attachment or the base attachment wet.The base must be ordered separately.
Communication protocol FDnet/C-NET
Operating voltage 12... 33 VDC
Operating current 3.5 mA (sound activated)
Quiescent current 250 NA
Terminals according to detector base
Number of sounds 11
Sound intensity 80... 99 dBA
Ext. alarm indicator 2
Operating temperature -25... +70 °C
Storage temperature -30... +75 °C
Relative humidity L95 %
Color red‚ zRAL 3000
Protection category With base FDB221 and base attach-ment FDB291 mounting on the wall with cable feed from bottom -> IP43‚ otherwise IP40. With base FDB221 and sealing ele-ment FDBZ295 -> IP44.With base attachment humid FDB293 -> IP54.
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard EN 54-3‚ EN 54-17
Dimensions (Ø x D) 100 x 43 mm
Data sheet Sinteso -> 007026Cerberus PRO -> A6V10203095
Accessories FDBZ293 Detector locking device
A5Q00004117
05.fm Seite 25 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAlarm EquipmentAlarm Sounders‚ Alarm Sounder Beacon
5-26 © Siemens Switzerland Ltd 2010
Type Order No.
FDS221-W Alarm sounder white
Loud alarming in case of fire alarm‚ clearly recognizable as danger sig-nal. To be mounted on the wall or on the ceiling along escape routes‚ corridors‚ staircases. Only applicable with addressable detector base. Power is supplied via FDnet/C-NET‚ no auxiliary power supply required. Monitoring of device status.For recess supply line. For surface supply line up to cable 6 mm in diam-eter with base FDB221‚ otherwise use the base attachment or the base attachment wet.The base must be ordered separately.
Communication protocol FDnet/C-NET
Operating voltage 12... 33 VDC
Operating current 3.5 mA (sound activated)
Quiescent current 250 NA
Terminals according to detector base
Number of sounds 11
Sound intensity 80... 99 dBA
Ext. alarm indicator 2
Operating temperature -25... +70 °C
Storage temperature -30... +75 °C
Relative humidity L95 %
Color white‚ zRAL 9010
Protection category With base FDB221 and base attach-ment FDB291 mounting on the wall with cable feed from bottom -> IP43‚ otherwise IP40. With base FDB221 and sealing ele-ment FDBZ295 -> IP44.With base attachment humid FDB293 -> IP54.
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard EN 54-3‚ EN 54-17
Dimensions (Ø x D) 100 x 43 mm
Data sheet Sinteso -> 007026Cerberus PRO -> A6V10203095
Accessories FDBZ293 Detector locking device
A5Q00006711
05.fm Seite 26 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAlarm EquipmentAlarm Sounders‚ Alarm Sounder Beacon
5-27© Siemens Switzerland Ltd 2010
5
Type Order No.
FDS229-R Alarm sounder beacon‚ red
Acoustic and optical alarming in case of fire alarm‚ clearly recognizable as danger signal. To be mounted on the wall or on the ceiling along escape routes‚ corridors‚ staircases. Only applicable with addressable detector base. Power is supplied via FDnet/C-NET‚ no auxiliary power supply required. Monitoring of device status.For recess supply line. For surface supply line up to cable 6 mm in diam-eter with base FDB221‚ otherwise use the base attachment or the base attachment wet.The base must be ordered separately.
Communication protocol FDnet/C-NET
Operating voltage 12... 33 VDC
Quiescent current 250 NA
Operating current 3.5 mA (sound activated)3.5 mA (beacon activated)7.0 mA (sound and beacon activat-ed)
Terminals according to detector base
Number of sounds 11
Number of flashing pattern 1 (intermittent)
Sound intensity 80... 99 dBA
Light intensity 1.27... 3.2 cd
Ext. alarm indicator 2
Operating temperature -25... +55 °C
Storage temperature -30... +75 °C
Relative humidity L95 %
Color transparent red
Protection category With base FDB221 and base attach-ment FDB291 mounting on the wall with cable feed from bottom -> IP43‚ otherwise IP42. With base FDB221 and sealing ele-ment FDBZ295 -> IP44.With base attachment humid FDB293 -> IP54.
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard EN 54-3‚ EN 54-17
Dimensions (Ø x D) 100 x 43 mm
Data sheet Sinteso -> A6V10067776Cerberus PRO -> A6V10229545
Accessories FDBZ293 Detector locking device
A5Q00023093
05.fm Seite 27 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAlarm EquipmentAlarm Sounders‚ Alarm Sounder Beacon
5-28 © Siemens Switzerland Ltd 2010
Type Order No.
FDS229-A Alarm sounder beacon‚ orange
Acoustic and optical alarming in case of fire alarm‚ clearly recognizable as danger signal. To be mounted on the wall or on the ceiling along escape routes‚ corridors‚ staircases. Only applicable with addressable detector base. Power is supplied via FDnet/C-NET‚ no auxiliary power supply required. Monitoring of device status.For recess supply line. For surface supply line up to cable 6 mm in diam-eter with base FDB221‚ otherwise use the base attachment or the base attachment wet.The base must be ordered separately.
Communication protocol FDnet/C-NET
Operating voltage 12... 33 VDC
Quiescent current 250 NA
Operating current 3.5 mA (sound activated)3.5 mA (beacon activated)7.0 mA (sound and beacon activat-ed)
Terminals according to detector base
Number of sounds 11
Number of flashing pattern 1 (intermittent)
Sound intensity 80... 99 dBA
Light intensity 1.1… 2.8 cd
Ext. alarm indicator 2
Operating temperature -25... +65 °C
Storage temperature -30... +75 °C
Relative humidity L95 %
Color transparent orange
Protection category With base FDB221 and base attach-ment FDB291 mounting on the wall with cable feed from bottom -> IP43‚ otherwise IP42. With base FDB221 and sealing ele-ment FDBZ295 -> IP44.With base attachment humid FDB293 -> IP54.
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard EN 54-3‚ EN 54-17
Dimensions (Ø x D) 100 x 43 mm
Data sheet Sinteso -> A6V10067776Cerberus PRO -> A6V10229545
Accessories FDBZ293 Detector locking device
A5Q00023092
Accessories
FDBZ293 Detector locking device
Threaded pin M3 x 6 to protect detector against theft.Scope of delivery2 hexagonal wrenches100 threaded pins
A5Q00005035
05.fm Seite 28 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAlarm EquipmentBases for Alarm Sounders‚ Alarm Sounder Beacon
5-29© Siemens Switzerland Ltd 2010
5
Type Order No.
FDB221 Detector base addressable
Base made from impact-proof and scratch-resistant synthetic material. Large opening in the detector base permits the reuse of existing bore-holes from older systems. Screwless connection terminals 'orange'. Space for auxiliary terminals as micro terminals 0.5 mm2 or connection terminals 2.5 mm2.For equipment with addressable signal processing.For recess supply wiring. For surface supply wiring‚ cable diameter up to 6 mm.
Cable capacity 0.2... 1.5 mm2
Dimensions (Ø x H) 100 x 22 mm
Color white‚ zRAL 9010
Data sheet Sinteso -> 007775Cerberus PRO -> A6V10203095‚ A6V10229545
Accessories FDBZ291 Designation plateDBZ1190-AA Micro terminal 0.5 mm2
DBZ1190-AB Connection terminal 2.5 mm2
FDB291 Base attachmentFDB293 Base attachment wet
A5Q00001664
FDB222 Detector base flat‚ addressable
Base made from impact-proof and scratch-resistant synthetic material. Large opening in the detector base permits the reuse of existing bore-holes from older systems. Screwless connection terminals 'orange'. Space for auxiliary terminals as micro terminals 0.5 mm2 or connection terminals 2.5 mm2.For equipment with addressable signal processing.For recess supply wiring.
Cable capacity 0.2... 1.5 mm2
Dimensions (Ø x H) 100 x 22 mm
Color white‚ zRAL 9010
Data sheet Sinteso -> 007775Cerberus PRO -> A6V10203095‚ A6V10229545
Accessories FDBZ291 Designation plateDBZ1190-AA Micro terminal 0.5 mm2
DBZ1190-AB Connection terminal 2.5 mm2
S54319-F1-A1
Accessories
FDBZ295 Sealing element
Use only with base FDB221‚ FDB221-AA for higher protection category. Not usable together with the designation plate FDBZ291.
Dimensions (Ø x H) 107 x 30 mm
Color white‚ zRAL 9010
S54319-F10-A1
05.fm Seite 29 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAlarm EquipmentBases for Alarm Sounders‚ Alarm Sounder Beacon
5-30 © Siemens Switzerland Ltd 2010
Type Order No.
FDBZ291 Designation plate
To identify the location address for detector bases.
Dimensions (W x H) 62 x 35 mm
Color transparent
Delivery unit 10 pieces
A5Q00002621
DBZ1190-AA Micro terminal 0.5 mm2‚ 4-pole
As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.
Cable capacity 0.28... 0.5 mm2
Dimensions (W x H x D) 10 x 7 x 10 mm
Delivery unit 50 pieces
BPZ:4677080001
DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole
As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.
Cable capacity 1... 2.5 mm2
Dimensions (W x H x D) 13.5 x 9.5 x 19.5 mm
Delivery unit 50 pieces
BPZ:4942340001
FDB291 Base attachment
For the supply of surface-mounted lines MI6 mm. The detector base FDB2xx is fixed with a spring-loaded catch.Mounting slots 46... 90 mm.
Dimensions (Ø x H) 120 x 25 mm
Color white‚ zRAL 9010
Accessories FDBZ291 Designation plate
A5Q00001603
FDB293 Base attachment humid with seal
For mounting in humid or wet environments‚ and when the detector-heating unit is used. 6 breakout plugs for screwed cable gland M20.For IP54 applications.
Dimensions (W x H x D) 135 x 135 x 49 mm
Color white‚ zRAL 9010
Accessories DBZ1194 Protective cageFDBZ294 EMC protective cage (only for Sinteso point detectors)A5Q00004478 Screwed cable gland M20DBZ1193A Detector designation plate
A5Q00003945
05.fm Seite 30 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAlarm EquipmentBases for Alarm Sounders‚ Alarm Sounder Beacon
5-31© Siemens Switzerland Ltd 2010
5
Type Order No.
DBZ1194 Protective cage
To protect the detector from damage. Can only be used together with the base attachment humid.
Dimensions (Ø x H) 160 x 126 mm
BPZ:4677110001
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
DBZ1193A Detector designation plate
To indicate a location address. To number detectors according to instal-lation drawings. The font may be up to 10 mm in an area of 60 x 20 mm. The detector designation plate is connected directly to the base or base attachment.
Dimensions (W x H) 62 x 52 mm
Color transparent
Delivery unit 10 pieces
BPZ:4864330001
05.fm Seite 31 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAlarm EquipmentSounder Base for Automatic Detectors
5-32 © Siemens Switzerland Ltd 2010
Type Order No.
DBS720 Sounder base
Compatible with all point detectors of the series Cerberus PRO.The sounder base DBS720 and the detector compose a single unit‚ which already has a base and is mounted on ceilings‚ e.g. in hotel rooms‚ hospitals or nursing homes.The sounder base serves for acoustic alarming in the addressed FS720 fire detection system. The sounder base can be allocated freely from the fire control panel to activate as required. It is not dependent upon an alarm signal from its associated detector.Synchronized with all other alarm sounder and sounder beacon devices in the same detector line (C-NET).No auxiliary power supply required; power is supplied via C-NET.For recess supply wiring. For surface supply wiring‚ remove the corre-sponding breakouts for cable diameter up to max. Ø8 mm.
Communication protocol C-NET
Operating voltage 12... 33 VDC
Quiescent current 150 μA
Alarm current 1.2 mA
Cable capacity 0.2... 1.6 mm2
Number of sounds 11
Sound intensity 80... 88 dBA
Ext. alarm indicator 2
Operating temperature -25... +70 °C
Storage temperature -30... +70 °C
Relative humidity L95 %
Color white‚ zRAL 9010
Protection category IP41IP42 with detector base seal RS720
System compatibility C-NET -> FS720
Standard EN 54-3
Dimensions (W x H x D) 175 x 117 x 29 mm
Data sheet A6V10203095
Accessories FDBZ291 Designation plateRS720 Detector base sealDBZ1190-AA Micro terminal 0.5 mm2
DBZ1190-AB Connection terminal 2.5 mm2
S54319-F5-A1
Accessories
FDBZ291 Designation plate
To identify the location address for detector bases.
Dimensions (W x H) 62 x 35 mm
Color transparent
Delivery unit 10 pieces
A5Q00002621
RS720 Detector base seal
Seal for higher protection category.Compatible with base DB721 and sounder base DBS720.Not usable together with the designation plate FDBZ291.
Dimensions (Ø x H) 119 x 6.5 mm
Color transparent
Delivery unit 10 pieces
S54319-F8-A1
05.fm Seite 32 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAlarm EquipmentSounder Base for Automatic Detectors
5-33© Siemens Switzerland Ltd 2010
5
Type Order No.
DBZ1190-AA Micro terminal 0.5 mm2‚ 4-pole
As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.
Cable capacity 0.28... 0.5 mm2
Dimensions (W x H x D) 10 x 7 x 10 mm
Delivery unit 50 pieces
BPZ:4677080001
DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole
As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.
Cable capacity 1... 2.5 mm2
Dimensions (W x H x D) 13.5 x 9.5 x 19.5 mm
Delivery unit 50 pieces
BPZ:4942340001
05.fm Seite 33 Mittwoch, 28. Juli 2010 8:33 08
No. Tonality
Frequency pattern Sweep
from – to
Pulse pattern
Adjustable FDS221 and FDS229 soundintensity level (typ. values in [dBA/1m]*)
Norm
at 12 V at 32 V
1 Continuous 970 Hz 988881
1019282
“evacuate”BS 5839 Part 1 1988
2 Intermittent 950 Hz 968779
1009181
“alert”BS 5839 Part 1 1988
3 Sweep-down 1200 Hz – 500 Hz 968779
1009180
DIN-ToneDIN33404 Part 3
4 Slow-whoopSweep-up, linear
500 Hz – 1200 Hz 978881
1019282
NEN2575(Netherlands)
5 Pulse tone 500 Hz 948575
978875
Swedish StandardSS 03 17 11, No. 1“Imminent Danger”
6 Intermittent 500 Hz 938475
968775
Swedish StandardSS 03 17 11, No. 6
“Local Warning”
7 Continuous 500 Hz 948576
978876
Swedish StandardSS 03 17 11, No. 4
“All clear”
8 Alternating 560 Hz440 Hz
948575
988976
“French fi re sound” NF S 32-001-1975
9 Intermittent 420 Hz 948576
988977
Australia “Alert”AS 2220 -1978
10 Slow-whoopSweep-up, linear
500 Hz – 1200 Hz 968981
1009382
Australia “Action”AS 2220 -1978
11 Intermittent 970 Hz 998982
1029283
ISO 8201US Temporal Tone LF
* Sound intensity ±2 dBASound intensity depending on the angle, see 'Operating instruction 008109'
Alarm sounder tones
1s
1s
0.6 s
0.5 s
1s
0.65 s
0.5 s 1.5 s
0.15 s
0.15 s
0.1s
0.1s
0.4 s
0.6 s
3.5 s
0.5 s
3.75 s
0.25 s
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 23 28.05.10 16:57
Fire Detection Network (C-NET) PeripheralsAddressable ModulesLine Separator
5-35© Siemens Switzerland Ltd 2010
5
Type Order No.
FDCL221 Line separator
To avoid the breakdown of several stub lines in case of a short circuit‚ line separators may be inserted. The line separator is used where sever-al stub lines are connected to the FDnet/C-NET at one point ‚ if no other device is given between the T-tap. For retrofitting of existing‚ collective systems to addressable Sinteso/Cerberus PRO fire detection systems.The separator is an electronic switch‚ integrated into the FDnet/C-NET. It separates the negative conductor in case of a short circuit‚ so that the short circuit-free side can continue to operate. The separator has 2x2 connectors for the detector line. Yellow LED for the status indication signals the short circuit separation.
Communication protocol FDnet/C-NET
Operating voltage 12... 33 VDC
Quiescent current 250 NA
Operating temperature -25... +70 °C
Storage temperature -30... +80 °C
Relative humidity L95 %
Color transparent
Protection category IP44
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard EN54-17
Dimensions (W x H x D) 44 x 47.5 x 10 mm
Data sheet 007065
Accessories TS35_122 U-railTS35_288 U-rail
A5Q00004011
05.fm Seite 35 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable ModulesLine Separator
5-36 © Siemens Switzerland Ltd 2010
Type Order No.
FDCL221-M Multi-line separator module
To avoid the breakdown of several stub lines in case of a short circuit‚ line separators may be inserted. The line separator is used where sever-al stub lines are connected to the FDnet/C-NET at one point. The mod-ule can also be connected to 2 separate loops. For retrofitting of exist-ing‚ collective systems to addressable Sinteso/Cerberus PRO fire detec-tion systems.The module has total 9 separators. Each separator is an electronic switch‚ integrated into the FDnet/C-NET. It separates the negative con-ductor in case of a short circuit‚ so that the short circuit-free side can continue to operate. The separator has connections for the detector lines‚ connections for the stub lines (T-taps)‚ jumpers for programming of operation mode (1-loop or 2-loop mode)‚ yellow LED for the status indication signals the short circuit separation.
Communication protocol FDnet/C-NET
Operating voltage 12... 33 VDC
Quiescent current 2.25 mA (9 x 250 NA) or2 x 1 mA (4 x 250 NA)
Operating temperature -25... +70 °C
Storage temperature -30... +75 °C
Relative humidity L95 % rel.
Color housing white zRAL9010cover transparent‚ mattaux. housing FDCH221 white zRAL9010
Protection category IP30with ext. housing FDCH221 -> IP65
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard EN 54-17
Dimensions (W x H x D)
Data sheet A6V10230308
Accessories TS35_122 U-railTS35_288 U-rail
S54312-F6-A1
Accessories
TS35_122 U-rail TS35/7.5/122
Universal mounting rail (U-rail) enables mounting of various equip-ment.
Dimensions (W x H) 35 x 122 mm
BPZ:5644780001
TS35_288 U-rail TS35/7.5/288
Universal mounting rail (U-rail) enables mounting of various equip-ment.
Dimensions (W x H) 35 x 288 mm
BPZ:5644230001
05.fm Seite 36 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable ModulesInput Modules
5-37© Siemens Switzerland Ltd 2010
5
Type Order No.
FDCI221 Input module
For the connection of 1 circuit of potential-free make-or-break contact for the indication of technical states (e.g. door or ventilation control) or for alarm actuation (e.g. sprinkler alarm).1 input for potential-free contact. Input line is monitored for open line and short circuit (termination resistors). The input can be configured via the fire control panel for status or alarm messages.Status indication by LED. Power supply via FDnet/C-NET.Input module incl. 2 resistors and 2 mounting feet for TS35 U-rail.
Communication protocol FDnet/C-NET
Operating voltage 12... 33 VDC
Quiescent current max. 0.3 mA
Cable capacity 0.2... 1.5 mm2 (2.5 mm2)
Operating temperature -25... +70 °C
Storage temperature -30... +75 °C
Relative humidity L95 %
Color white‚ zRAL 9010/transparent matt
Protection category IP30IP65 with aux. housing FDCH221
System compatibility FDnet -> FS20C-NET -> FS720
Standard EN 54-17‚ EN 54-18
Dimensions (W x H x D) 95 x 71 x 23 mm
Data sheet A6V10202196
Accessories TS35_122 U-railTS35_288 U-railFDCH221 Housing IP65
S54312-F1-A1
FDCI222 Input module
For the connection of 4 independent circuits of potential-free‚ make-or-break contacts for the indication of technical states (e.g. door or venti-lation control) or for alarm actuation (e.g. sprinkler alarm).4 inputs for potential-free contacts. Input lines are monitored for open line and short circuit (termination resistors). Inputs can be independ-ently configured via the fire control panel for status or alarm messages.Status indication by LED. Power supply via FDnet/C-NET.Input module incl. 8 resistors and 2 mounting feet for TS35 U-rail.
Communication protocol FDnet/C-NET
Operating voltage 12... 33 VDC
Quiescent current 0.25... 0.35 mA
Cable capacity 0.2... 1.5 mm2 (2.5 mm2)
Operating temperature -25... +60 °C
Storage temperature -30... +65 °C
Relative humidity L95 %
Color white‚ zRAL 9010/transparent matt
Protection category IP30IP65 with aux. housing FDCH221
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard CEA GEI 1-84‚ EN 54-17‚ EN 54-18
Dimensions (W x H x D) 130 x 90 x 20 mm
Data sheet 007024
Accessories TS35_122 U-railTS35_288 U-railFDCH221 Housing IP65
A5Q00001984
05.fm Seite 37 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable ModulesInput/Output Modules
5-38 © Siemens Switzerland Ltd 2010
Type Order No.
FDCIO221 Input/output module
For the connection of 1 circuit of potential-free, make-or-break contact for the indication of technical states (e.g. door or ventilation control) or for alarm actuation (e.g. sprinkler alarm). For the decentralized control of fire doors‚ ventilation and air conditioning.1 input for potential-free contact. The input line is monitored for open line and short circuit (termination resistors). The input can be config-ured via the fire control panel for status or alarm message. 1 output configurable as a potential-free relay contact (30 VAC/VDC‚ 2 A) or as a monitored circuit (30 VDC‚ 2 A).Status indication by LED. Power supply via FDnet/C-NET in potential-free mode. Monitored mode requires additional 24 VDC power supply.Input/output module incl. 3 resistors and 2 mounting feet for TS35 U-rail.
Communication protocol FDnet/C-NET
Operating voltage 12... 33 VDC
Quiescent current max. 0.4 mA
Relay output (volt-free) 30 VAC‚ 2 A‚ max 60 VA30 VDC‚ 2 A‚ max 60 W
Cable capacity 0.2... 2.5 mm2
Operating temperature -25... +70 °C
Storage temperature -30... +75 °C
Relative humidity L95 %
Color white‚ zRAL 9010/transparent matt
Protection category IP30IP65 with aux. housing FDCH221
System compatibility FDnet -> FS20C-NET -> FS720
Standard EN 54-17‚ EN 54-18
Dimensions (W x H x D) 95 x 71 x 23 mm
Data sheet A6V10202196
Accessories TS35_122 U-railTS35_288 U-railFDCH221 Housing IP65
S54312-F2-A1
05.fm Seite 38 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable ModulesInput/Output Modules
5-39© Siemens Switzerland Ltd 2010
5
Type Order No.
FDCIO222 Input/output module
For the connection of 4 independent‚ potential-free‚ make-or-break contacts for the indication of technical states (e.g. door or ventilation control) or for alarm actuation (e.g. sprinkler alarm).4 inputs for potential-free contacts. Input lines are monitored for open line and short circuit (termination resistors). Inputs can be independ-ently configured via the fire control panel for status or alarm messages. 4 outputs with 4 potential-free relay contacts (230 VAC / 4 A) for fire control installations.Status indication by LED. Power supply via FDnet/C-NET.Input/output module incl. 8 resistors and 2 mounting feet for TS35 U-rail.
Communication protocol FDnet/C-NET
Operating voltage 12... 33 VDC
Quiescent current 0.6... 0.75 mA
Relay output (volt-free) 250 VAC‚ 4 A‚ max. 1000 VA30 VDC‚ 4 A‚ max. 120 W
Cable capacity 0.2... 1.5 mm2 (2.5 mm2)
Operating temperature -25... +60 °C
Storage temperature -30... +65 °C
Relative humidity L95 %
Color white‚ zRAL 9010/transparent matt
Protection category IP30IP65 with aux. housing FDCH221
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard CEA GEI 1-84‚ EN 54-17‚ EN 54-18
Dimensions (W x H x D) 130 x 90 x 20 mm
Data sheet 007024
Accessories TS35_122 U-railTS35_288 U-railFDCH221 Housing IP65
A5Q00002369
05.fm Seite 39 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable ModulesInput/Output Modules
5-40 © Siemens Switzerland Ltd 2010
Type Order No.
FDCIO224 Input/output module
For the VdS interface for extinguishing activating devices. 4 inputs for potential-free contacts. Input lines are monitored for open line and short circuit (termination resistors). Inputs can be independently con-figured via the fire control panel for status or alarm messages.4 outputs with 4 potential-free relay contacts (230 VAC / 4 A) for the VdS interface for extinguishing controls. Status indication by LED. Pow-er supply via FDnet/C-NET.Input/output module incl. 8 resistors and 2 mounting feet for TS35 U-rail.
Communication protocol FDnet/C-NET
Operating voltage 12... 33 VDC
Quiescent current 0.6... 0.75 mA
Relay output (volt-free) 250 VAC‚ 4 A‚ max. 1000 VA30 VDC‚ 4 A‚ max. 120 W
Cable capacity 0.2... 1.5 mm2 (2.5 mm2)
Operating temperature -25... +60 °C
Storage temperature -30... +65 °C
Relative humidity L95 %
Color white‚ zRAL 9010/transparent matt
Protection category IP30IP65 with aux. housing FDCH221
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard CEA GEI I-084‚ EN 54-17‚ EN 54-18
Dimensions (W x H x D) 130 x 90 x 20 mm
Data sheet 007024
Accessories TS35_122 U-railTS35_288 U-railFDCH221 Housing IP65
A5Q00018689
05.fm Seite 40 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable ModulesInput/Output Modules
5-41© Siemens Switzerland Ltd 2010
5
Type Order No.
FDCIO223 Input/output module 'Transponder'
For connection of collective fire detectors (GMT/conventional line‚ GMT/conventional line with shunt Zener diode barrier (SB3) for explo-sion-hazard areas). For monitored controls of e.g. smoke dampers‚ alarm devices‚ door magnets and extinguishing activation devices (adhere to country-specific instructions). Monitored signal input for status and alarm messages or for acknowledging technical status.The 2 input/outputs can be parameterized autonomously in each case as detector line collective‚ contact input‚ control output‚ control output and input as acknowledgement with selectable monitoring time frame. Status indication by LED.Transponder incl. 2 Transzorb diode 20 V‚ 8 resistors and 2 mounting feet for TS35 U-rail.
Power supply External input voltage 18... 32 VDC
Communication protocol FDnet/C-NET
Operating voltage FDnet/C-NET 12... 33 VDC
Detector line collective GMT Siemens/Cerberus‚ Synova conventional/SynoLINE300‚ collective/SynoLINE600 or similar
Control output 24 VDC ± 5 % / 2 A
EOL resistor 3.3 kT/680 T‚ 2.7 kT/560 T‚ 3.3 kT
Cable capacity 0.2... 1.5 mm2 (2.5 mm2)
Operating temperature -25... +60 °C
Storage temperature -30... +65 °C
Relative humidity L95 %
Color white‚ zRAL 9010/transparent matt
Protection category IP30IP65 with aux. housing FDCH221
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard CEA GEI I-084‚ EN 54-17‚ EN 54-18
Dimensions (W x H x D) 132 x 90 x 24 mm
Data sheet 009168
Accessories TS35_122 U-railTS35_288 U-railFDCH221 Housing IP65
S24218-B102-A1
05.fm Seite 41 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsAddressable ModulesAccessories for Input-‚ Input/Output Modules
5-42 © Siemens Switzerland Ltd 2010
Type Order No.
TS35_122 U-rail TS35/7.5/122
Universal mounting rail (U-rail) enables mounting of various equip-ment.
Dimensions (W x H) 35 x 122 mm
BPZ:5644780001
TS35_288 U-rail TS35/7.5/288
Universal mounting rail (U-rail) enables mounting of various equip-ment.
Dimensions (W x H) 35 x 288 mm
BPZ:5644230001
FDCH221 Housing for input/output modules
Housing with seal for the mounting of the input/output modules for wet applications.The required screwed cable glands and back nuts M20 must be ordered separately.
Dimensions (W x H x D) 207 x 119 x 48 mm
Color white‚ zRAL 9010 / transparent matt
Protection category IP65
Accessories A5Q00004478 Screwed cable gland M20A5Q00004479 Back nut M20
S54312-F3-A1
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
A5Q00004479 Back nut M20
Back nut to screwed cable gland M20 x 1.5.
Delivery unit 10 pieces
A5Q00004479
DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole
As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.
Cable capacity 1... 2.5 mm2
Delivery unit 50 pieces
BPZ:4942340001
05.fm Seite 42 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsFloor Repeater Panels‚ Mimic DisplayFloor Repeater Terminals
5-43© Siemens Switzerland Ltd 2010
5
Type Order No.
FT2010-A1 Floor repeater terminal
Small floor repeater operation and display panel with large backlit dis-play and plain text readout (6 lines of 40 characters each) for use with the addressed Sinteso FS20 and Cerberus PRO FS720 fire detection sys-tem.The personnel responsible at the customer's premises have access to a clearly structured user interface for customer-specific plain texts to enable exact localization of events. Sections and zones operated and visualized using the floor repeater terminal can be configured. Display of alarms‚ pre-alarms‚ technical messages‚ faults‚ isolations possible. With the navigation keys an indicated list in the display can be scrolled through. Acknowledgement and resetting of events. Event text identi-cal with the fire control panel or fire terminal. Nordic key switch for operating access may be replaced by key switch (Kaba).Power supply via FDnet/C-NET‚ separate 24 V power supply possible.The floor repeater terminal can be operated in loops or stub lines.
Operating voltage 12... 32 VDC
Supply voltage 20... 30 VDC15… 18 VAC (external supply input)
Current consumption 5 mA @ 24 V (quiescent current‚ LCD illumination inactive)45 mA @ 24 V (max. current‚ LCD illumination active)
Communication protocol FDnet/C-NET
Cable capacity 0.8... 1.5 mm2
Color grey‚ zRAL 7035
Dimensions (W x H x D) 282 x 207 x 79 mm
Operating temperature -8... +42 °C
Storage temperature -20... +60 °C
Protection category IP30
Relative humidity L95 % (no condensation)
Standard EN 54-17‚ EN 54-18
System compatibility FDnet -> FS20C-NET -> FS720
Data sheet 009393
Accessories FHA2013-A1 Rear (FT201x flat)FTO2005-C1 Key switch (Kaba)
A5Q00014104
05.fm Seite 43 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsFloor Repeater Panels‚ Mimic DisplayFloor Repeater Terminals
5-44 © Siemens Switzerland Ltd 2010
Type Order No.
FT2010-C1 Floor repeater terminal
Small floor repeater operation and display panel with large backlit dis-play and plain text readout (6 lines of 40 characters each) for use with the addressed Sinteso FS20 and Cerberus PRO FS720 fire detection sys-tem.The personnel responsible at the customer's premises have access to a clearly structured user interface for customer-specific plain texts to enable exact localization of events. Sections and zones operated and visualized using the floor repeater terminal can be configured. Display of alarms‚ pre-alarms‚ technical messages‚ faults‚ isolations possible. With the navigation keys an indicated list in the display can be scrolled through. Acknowledgement and resetting of events. Event text identi-cal with the fire control panel or fire terminal. Kaba key switch for oper-ating access and sheet metal flat rear. Power supply via FDnet/C-NET‚ separate 24 V power supply possible.The floor repeater terminal can be operated in loops or stub lines.
Operating voltage 12... 32 VDC
Supply voltage 20... 30 VDC15… 18 VAC (external supply input)
Current consumption 5 mA @ 24 V (quiescent current‚ LCD illumination inactive)45 mA @ 24 V (max. current‚ LCD illumination active)
Communication protocol FDnet/C-NET
Cable capacity 0.8... 1.5 mm2
Color grey‚ zRAL 7035
Dimensions (W x H x D) 282 x 207 x 46 mm
Operating temperature -8... +42 °C
Storage temperature -20... +60 °C
Protection category IP30
Relative humidity L95 % (no condensation)
Standard EN 54-17‚ EN 54-18
System compatibility FDnet -> FS20C-NET -> FS720
Data sheet 009393
S54400-F34-A1
05.fm Seite 44 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsFloor Repeater Panels‚ Mimic DisplayFloor Repeater Display
5-45© Siemens Switzerland Ltd 2010
5
Type Order No.
FT2011-A1 Floor repeater display
Small floor repeater display panel with large backlit display and plain text readout (6 lines of 40 characters each) for use with the addressed Sinteso FS20 and Cerberus PRO FS720 fire detection system.The personnel responsible at the customer's premises have access to a clearly structured user interface for customer-specific plain texts to enable events to be localized unambiguously. Sections and zones visu-alized using the floor repeater display can be configured. Display of alarms‚ pre-alarms‚ technical messages‚ faults‚ isolations possible. With the navigation keys an indicated list in the display can be scrolled through. The internal buzzer can be switched off in case of alarm mes-sages. Event text identical with the fire control panel or fire terminal.Power supply via FDnet/C-NET‚ separate 24 V power supply possible.The floor repeater display can be operated in loops or stub lines.
Operating voltage 12... 32 VDC
Supply voltage 20... 30 VDC15… 18 VAC (external supply input)
Current consumption 5 mA @ 24 V (Quiescent current‚ LCD illumination inactive)45 mA @ 24 V (max. current‚ LCD illumination active)
Communication protocol FDnet/C-NET
Cable capacity 0.8... 1.5 mm2
Color grey‚ zRAL 7035
Dimensions (W x H x D) 282 x 207 x 79 mm
Operating temperature -8... +42 °C
Storage temperature -20... +60 °C
Protection category IP30
Relative humidity L95 % (no condensation)
Standard EN 54-17‚ EN 54-18
System compatibility FDnet -> FS20C-NET -> FS720
Data sheet 009393
Accessories FHA2013-A1 Rear (FT201x flat)
A5Q00017706
Accessories
FHA2013-A1 Rear (FT201x flat)
Flat rear when really flat installation is required and the cable is flush-mounted. In place of the rear supplied with the floor repeater terminal or floor repeater display.
Dimensions (W x H x D) 271 x 191 x 27.5 mm
Material Zinc-plated sheet metal
A5Q00016552
FTO2005-C1 Key switch (Kaba)
Kaba key switch with mounting accessories and key (Kaba 8 #100)‚ as an option for operating access (operating unit).
A5Q00010113
05.fm Seite 45 Mittwoch, 28. Juli 2010 8:33 08
Fire Detection Network (C-NET) PeripheralsFloor Repeater Panels‚ Mimic DisplayMimic Display Driver
5-46 © Siemens Switzerland Ltd 2010
Type Order No.
FT2001-A1 Mimic display driver
The FT2001-A1 has 2x24 outputs for LED activation for mimic display panels. Connection to LED via flat cable F50F410 (50-wire‚ 24 red LEDs‚ cable length 1 m‚ must be ordered separately). 2 control outputs for 'Local buzzer' and 'LED operation'. 2 inputs for 'Switch-off buzzer' and 'Lamp test'. Integrated line separator.Power supply via FDnet/C-NET‚ separate 24 V power supply possible.The mimic display driver can be operated in loops or stub lines.MC-Link plug-in point for firmware update.
Operating voltage 12... 32 VDC
Operating current max. 45 mA
Quiescent current max. 5 mA
Operating LED output max. 2.5 mA @ 2.5 VDC
Buzzer output max. 5 mA @ 12 VDC
Key input (buzzer off‚ lamp test) 2
External supply input 14… 32 VDC‚ galvanically isolated11… 22 VAC‚ galvanically isolated
Communication protocol FDnet/C-NET
Cable capacity 0.08... 1.5 mm2
Dimensions (W x H x D) 106 x 200 x 45 mm
Operating temperature 0... +40 °C
Storage temperature -20... +60 °C
Protection category IP30 (3rd party housing)
Relative humidity L95 %
Standard EN 54-17‚ EN 54-18
System compatibility FDnet -> FS20C-NET -> FS720
Data sheet A6V10082691
Accessories F50F410 LED flat cable 50-wire
A5Q00014417
Accessories
F50F410 LED flat cable 50-wire‚ with 24 red LEDs
Two F50F410 LED cables can be connected directly to the mimic display driver to offer a total of 48 (2x24) red LEDs. The LEDs can be easily con-figured via the configuration tools.
Cable length 1 m
BPZ:5291410001
05.fm Seite 46 Mittwoch, 28. Juli 2010 8:33 08
Visual Parallel Alarm IndicatorsAlarm IndicatorsAI Series for C-NET Devices
6-1© Siemens Switzerland Ltd 2010
6
Type Order No.
FDAI91 Alarm indicator - Door frame
The alarm indicator is connected in parallel to automatic fire detectors in order to indicate quickly the source of an alarm signal from detectors that are not easily accessible or visible. The alarm indicator contains an indicator lamp unit with one or two LEDs. They light up as soon as a connected fire detector gives an alarm.Screwless connection terminals.The alarm indicator is suitable for door frames.
Operating voltage 5... 8 VDC
Operating current max. 35 mA
Cable capacity max. 1.5 mm2
Operating temperature -25… +80 °C
Relative humidity L95 %
Color white‚ zRAL 9010
Protection category IP40
Dimensions (W x H x D) 62 x 37 x 24 mm
Data sheet A6V10276520
S54370-F9-A1
FDAI92 Alarm indicator - Surface
The alarm indicator is connected in parallel to automatic fire detectors in order to indicate quickly the source of an alarm signal from detectors that are not easily accessible or visible. The alarm indicator contains an indicator lamp unit with one or two LEDs. They light up as soon as a connected fire detector gives an alarm.Screwless connection terminals.The alarm indicator is suitable for wall mounting.
Operating voltage 5... 8 VDC
Operating current max. 35 mA
Cable capacity max. 1.5 mm2
Operating temperature -25… +80 °C
Relative humidity L95 %
Color white‚ zRAL 9010
Protection category IP40
Dimensions (W x H x D) 85 x 85 x 28 mm
Data sheet A6V10276520
Accessories AI330 Adapter frame
S54370-F3-A1
FDAI93 Alarm indicator - Flush
Indicator lamp to connect in parallel to automatic fire detectors. Made of transparent plastic‚ the alarm indicator is suitable for installation in door frames‚ switching panels‚ ceiling voids or special housings.The 22.5 mm Ø mounting hole is drilled by the system owner.The holder must be fitted with an insulating cap for safety.
Operating voltage 6... 8 VDC
Operating current max. 35 mA
Cable capacity max. 1.5 mm2
Operating temperature -25… +80 °C
Relative humidity L95 %
Color transparent
Protection category IP56 with DCA1191IP65 with DJZ1193
Data sheet A6V10276520
Accessories DCA1191 Housing (IP56)
S54370-F5-A1
06.fm Seite 1 Mittwoch, 28. Juli 2010 8:37 08
Visual Parallel Alarm IndicatorsAlarm IndicatorsAI Series for C-NET Devices
6-2 © Siemens Switzerland Ltd 2010
Type Order No.
FDCAI221 Addressable alarm indicator
The addressable alarm indicator is connected to automatic fire detec-tors in order to indicate quickly the source of an alarm signal from detectors that are not easily accessible or visible. The addressable alarm indicator contains an indicator lamp unit with two integral LEDs. They light up as soon as a connected fire detector gives an alarm.Screwless connection terminals.The alarm indicator is suitable for wall mounting.
Operating voltage 12... 33 VDC
Quiescent current 240... 400 NA
Operating temperature -10… +55 °C
Relative humidity L95 %
Color white‚ zRAL 9010
Protection category IP40
Dimensions (W x H x D) 85 x 85 x 32 mm
Data sheet A6V10244934
Accessories AI330 Adapter frame
S54370-F10-A1
AI330 Adapter frame for alarm indicator
By means of the additional frame‚ the alarm indicator can also be used for surface laid conduits or ducts‚ to increase the loop space and as an adapter for different makes of the box.
Dimensions (W x H x D) 85 x 85 x 16 mm
BPZ:3169430001
06.fm Seite 2 Mittwoch, 28. Juli 2010 8:37 08
Fire Detection Collective Peripherals
Fire protection with SynoLINE – no problems before switching onSynoLINE has been designed from scratch to combine excellent performance with the simplest possible installation, start-up, maintenance, and daily use. As a result, the installer can work more effi ciently. And the user can start managing his affairs after a shorter period.
Attractive, environmentally aware design Blends unobtrusively into any room Superior resistance to contamination and electromagnetic interference Screwless connection technology High stability against lightning Short-circuit-proof output for the connection of external alarm indicators Wide variation of accessories for countless applications
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 27 28.05.10 16:58
Conventional fi re detectors – point detectors
SOA322Base attachment for
surface mounting
Connection terminal
DBZ1190-AB
Optical smoke detectorOP320C
SO320Base for Synova 300 series detectors
Detector locking device
TP320
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 28 28.05.10 16:58
Fire Detection Collective PeripheralsConventional Line SynoLINE300Conventional Detectors Synova 300 Series
7-3© Siemens Switzerland Ltd 2010
7
Type Order No.
OP320C Optical smoke detector
The OP320C has an excellent all-round performance within the Synova 300 range. It has a completely new optical chamber and the latest elec-tronics which open up new dimensions in safety and functionality.The base SO320 must be ordered separately.
Operating voltage 16... 28 VDC
Operating current no smoke max. 100 NA with smoke max. 170 NA
Operating temperature -10... +55 °C
Protection category IP44
Standard EN 54-7
Color white‚ zRAL 9010 (can be sprayed a different color)
Dimensions (Ø x H) 100 x 44 mm (incl. base)
Delivery unit 2 pieces
Data sheet 006801
BPZ:5081460001
OH320C Smoke detector‚ conventional multi-sensor
The OH320C is the most sensitive detector in the Synova 300 range. It has a completely new and patented optical system and the latest elec-tronics. This opens up new dimensions with regard to safety and func-tionality.The base SO320 must be ordered separately.
Operating voltage 16... 28 VDC
Operating current no smoke max. 100 NA with smoke max. 170 NA
Operating temperature -10... +55 °C
Protection category IP44
Standard EN 54-7
Color white‚ zRAL 9010 (can be sprayed a different color)
Dimensions (Ø x H) 100 x 52 mm (incl. base)
Delivery unit 2 pieces
Data sheet 006886
BPZ:5364190001
HI320C Heat detector (rate of rise and maximum)
The HI320C is an extremely reliable rate of rise and maximum temper-ature detector for demanding applications. It is characterized by relia-ble response behavior‚ not only in the event of temperature rises which are slow‚ but also where the temperature rises are fast.The base SO320 must be ordered separately.
Operating voltage 16... 28 VDC
Quiescent current max. 100 NA
Operating temperature -10... +50 °C
Protection category IP44
Standard EN 54-5: A1R
Color white‚ zRAL 9010 (can be sprayed a different color)
Dimensions (Ø x H) 100 x 36 mm (incl. base)
Delivery unit 2 pieces
Data sheet 006885
BPZ:5081590001
07.fm Seite 3 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsConventional Line SynoLINE300Conventional Detectors Synova 300 Series
7-4 © Siemens Switzerland Ltd 2010
Type Order No.
HI322C Heat detector (maximum)
The HI322C is a reliable heat detector for locations in which there are large fluctuations in temperature. It continuously measures the ambi-ent temperature and reacts if there is a sustained overshoot of defined maximum values.The base SO320 must be ordered separately.
Operating voltage 16... 28 VDC
Quiescent current max. 100 NA
Operating temperature -10... +50 °C
Protection category IP44
Standard EN54-5: A2
Color white‚ zRAL 9010 (can be sprayed a different color)
Dimensions (Ø x H) 100 x 36 mm (incl. base)
Delivery unit 2 pieces
Data sheet 006802
BPZ:5316470001
SO320 Base for Synova 300 series detectors
Base made of impact‚ scratch-proof plastic and environmentally safe materials. The base is completely covered by the detector. It fits all Syn-ova 300 series detectors‚ conventional and addressable. Standard click concept‚ with screwless terminals for easy installation. Click-in connec-tion for alarm indicators is standard on the base. Fits all standard flush mounting boxes from 55 to 80 mm.
Cable capacity 0.2... 1.5 mm2
Color white‚ zRAL 9010
Delivery unit 6 pieces
Accessories SOA322 Base attachment for sur-face mountingTP320 Detector locking device
BPZ:5085990001
Accessories
SOA322 Base attachment for surface mounting
Base attachment for feeding in surface wiring and to provide more wire space. It may also be used as a junction box where up to 30 wires can be connected. Up to 10 connection terminals DBZ1190-AB can be clicked into the base attachment SOA322. The base SO320 is mounted using a spring-loaded catch.
Dimensions (Ø x H) 100 x 20 mm
Cable capacity 0.2... 2.5 mm2
Color white‚ zRAL 9010
Delivery unit 6 pieces
Accessories DBZ1190-AB Connection terminal 2.5 mm2
BPZ:5358340001
DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole
As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.
Cable capacity 1... 2.5 mm2
Delivery unit 50 pieces
BPZ:4942340001
07.fm Seite 4 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsConventional Line SynoLINE300Conventional Detectors Synova 300 Series
7-5© Siemens Switzerland Ltd 2010
7
Type Order No.
TP320 Detector locking device
To protect the detector from theft.Mounts on the detector base SO320.
Delivery unit 50 pieces
BPZ:5093100001
07.fm Seite 5 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsConventional Line SynoLINE300Conventional Manual Call Points
7-6 © Siemens Switzerland Ltd 2010
Type Order No.
FDM1101A-RG Manual call point with glass plate
For immediate manual actuation of a fire alarm. For indoor and outdoor application. Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is reset and the device is ready for operation again. For surface- and recess-mounted feed lines in eas-ily accessible places.For surface mounting the housing base FDMH295-x must be ordered separately.
Communication protocol conventional/SynoLINE300
Operating voltage max. 28 VAC or VDC
Operating current 100 mA… max. 1 A
Terminal block 0.28… 1.5 mm2
Operating temperature -25... +70 °C
Storage temperature -30... +75 °C
Relative humidity L95 % (no condensation)
Protection category IP44
Color red‚ zRAL 3000
Standard EN 54-11
Dimensions (W x H x D) 87 x 87 x 20 mm
Data sheet A6V10206486
Accessories FDMH295-R housing baseFDMH295-S housing base with 2 holes + grommets for cable Ø5 mmFDMC295 Protective cover
S54371-F6-A3
FDM1101A-RP Manual call point with resettable plastic element
For immediate manual actuation of a fire alarm. For indoor and outdoor application. Direct alarm actuation by pushing on the plastic element. The switch is reset with the key and the device is ready for operation again. For surface- and recess-mounted feed lines in easily accessible places.For surface mounting the housing base FDMH295-x must be ordered separately.
Communication protocol conventional/SynoLINE300
Operating voltage max. 28 VAC or VDC
Operating current 100 mA… max. 1 A
Terminal block 0.28… 1.5 mm2
Operating temperature -25... +70 °C
Storage temperature -30... +75 °C
Relative humidity L95 % (no condensation)
Protection category IP44
Color red‚ zRAL 3000
Standard EN 54-11
Dimensions (W x H x D) 87 x 87 x 20 mm
Data sheet A6V10206486
Accessories FDMH295-R housing baseFDMH295-S housing base with 2 holes + grommets for cable Ø5 mmFDMC295 Protective cover
S54371-F6-A4
07.fm Seite 6 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsConventional Line SynoLINE300Conventional Manual Call Points
7-7© Siemens Switzerland Ltd 2010
7
Type Order No.
Accessories
FDMH295-R Back box
Housing base for manual call points FDM225‚ FDM1101 and FDM1101A for surface mounting.
Color red‚ zRAL 3000
Dimensions (W x H x D) 87 x 87 x 33
Accessories A5Q00004478 Screwed cable gland M20A5Q00004479 Back nut M20DBZ1190-AB Connection terminal 2.5 mm2
A5Q00013437
FDMH295-S Back box with 2 entries
Housing base for manual call points FDM225‚ FDM1101 and FDM1101A with 2 holes on top fitted with grommet for cable Ø5 mm for surface mounting.
Color red‚ zRAL 3000
Dimensions (W x H x D) 87 x 87 x 33
Accessories DBZ1190-AB Connection terminal 2.5 mm2
A5Q00013438
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
A5Q00004479 Back nut M20
Back nut to screwed cable gland M20 x 1.5.
Delivery unit 10 pieces
A5Q00004479
DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole
As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.
Cable capacity 1... 2.5 mm2
Delivery unit 50 pieces
BPZ:4942340001
07.fm Seite 7 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsConventional Line SynoLINE300Conventional Manual Call Points
7-8 © Siemens Switzerland Ltd 2010
Type Order No.
FDMC295 Protective cover
The protective cover protects the manual call points FDM225‚ FDM226‚ FDM1101 and FDM1101A from unintentional glass break.
Color transparent
Delivery unit 10 pieces
A5Q00013440
07.fm Seite 8 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsConventional Line SynoLINE300Alarm Indicators for SynoLINE300
7-9© Siemens Switzerland Ltd 2010
7
Type Order No.
AI91C Alarm indicator - Door frame
The AI91C alarm indicator is the visual parallel indication for fire detec-tors used on the SynoLINE300 detector line. It is provided with a dark red luminous element‚ fitted with LEDs. The alarm indicator is ideally used where the fire detector is difficult to see (e.g. hotel rooms‚ switch-ing cabinets). The AI91C is suitable for door frames.
Operating voltage 6... 28 VDC
Operating current max. 35 mA
Cable capacity max. 1.5 mm2
Operating temperature -25... +80 °C
Relative humidity L95 %
Protection category IP40
Dimensions (W x H x D) 62 x 37 x 24
Color white‚ zRAL 9010
Data sheet A6V10276522
S54370-F7-A1
AI92C Alarm indicator - Surface
The AI92C alarm indicator is the visual parallel indication for fire detec-tors used on the SynoLINE300 detector line. It is provided with a dark red luminous element‚ fitted with LEDs. The alarm indicator is ideally used where the fire detector is difficult to see (e.g. hotel rooms‚ switch-ing cabinets). The AI92C is suitable for surface wall mounting.
Operating voltage 6... 28 VDC
Operating current max. 35 mA
Cable capacity max. 1.5 mm2
Operating temperature -25... +80 °C
Relative humidity L95 %
Protection category IP40
Dimensions (W x H x D) 85 x 85 x 28 mm
Color white‚ zRAL 9010
Data sheet A6V10276522
Accessories AI330 Adapter frame
S54370-F8-A1
AI330 Adapter frame for alarm indicator
By means of the additional frame‚ the alarm indicator can also be used for surface laid conduits or ducts‚ to increase the loop space and as an adapter for different makes of the box.
Dimensions (W x H x D) 85 x 85 x 16 mm
BPZ:3169430001
07.fm Seite 9 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Detectors AlgoRex Series
7-10 © Siemens Switzerland Ltd 2010
Type Order No.
DO1101A Smoke detector‚ collective wide spectrum
The DO1101A has a high performance opto-electronic sensor system. It has uniform response behavior for different types of fire. It has a high resistance to soiling and temperature fluctuation.The base DB1101A must be ordered separately.
Operating voltage 16... 24 VDC
Quiescent current max. 100 NA
Operating temperature -25... +60 °C
Protection category IP44
Standard EN 54-7
Dimensions (Ø x H) 115 x 51 mm (incl. base)
Color white‚ zRAL 9010
Data sheet 001578
BPZ:4930020001
DT1101A Heat detector
The DT1101A has precise maximum temperature alarm activation with a quality thermo sensor. It has response behavior immune to deceptive phenomena with rapid and slow increases in temperature. Heat detec-tor with wide application range up to +50 °C. For the monitoring of rooms and installations where in the event of fire‚ a rapid increase in temperature can be expected‚ or other types of detector cannot be used due to operational reasons.The base DB1101A must be ordered separately.
Operating voltage 16... 24 VDC
Quiescent current max. 100 NA
Operating temperature -25... +50 °C
Protection category IP44
Standard EN 54-5: A1R
Dimensions (Ø x H) 115 x 54.5 mm (incl. base)
Color white‚ zRAL 9010
Data sheet 001578
BPZ:4931700001
DT1102A Heat detector
The DT1102A has precise maximum temperature alarm activation with a quality thermo sensor. It has response behavior immune to deceptive phenomena with rapid and slow increases in temperature. Heat detec-tor for high ambient temperatures up to +70 °C. For the monitoring of rooms and installations in which high ambient temperatures can be expected up to +70 °C.The base DB1101A must be ordered separately.
Operating voltage 16... 24 VDC
Quiescent current max. 100 NA
Operating temperature -25... +70 °C
Protection category IP44
Standard EN 54-5: B
Dimensions (Ø x H) 115 x 54.5 mm (incl. base)
Color white‚ zRAL 9010
Data sheet 001578
BPZ:4931830001
07.fm Seite 10 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Detectors AlgoRex Series
7-11© Siemens Switzerland Ltd 2010
7
Type Order No.
DB1101A Base for collective detector series
Base made of impact and scratch-proof plastic and environmentally safe materials. Integral rubber gasket to protect against draught‚ dirt and dripping water from above. Screwless terminals for easy installa-tion. Space for auxiliary terminals as micro terminals (0.5 mm2) and connection terminals (2.5 mm2). Fits all standard flush-mounted boxes from 55 to 80 mm.
Cable capacity 0.2... 2.5 mm2
Dimensions (Ø x H) 115 x 21 mm
Color white‚ zRAL 9010
Data sheet 001035
Accessories DBZ1191 Base attachment for sur-face mountingDBZ1191A-AA Base attachment flat for surface mountingDBZ1192 Base attachment humidDBZ1192-AA Base attachment wetDBZ1195A Acoustic baseDBC1191A-AA Relay baseDBZ1190 Locking deviceDBZ1190A-AC Detector heatingDBZ1193A Detector designation plateDBZ1190-AB Connection terminal 2.5 mm2
DBZ1190-AA Micro terminal 0.5 mm2
BPZ:4863650001
DBZ1191 Base attachment for surface mounting
For surface wiring feed and provision of more wire loop space. Bases are mounted using a spring-loaded catch.
Dimensions (Ø x H) 116 x 22 mm
Color white‚ zRAL 9010
Delivery unit 5 pieces
BPZ:4540830001
DBZ1191A-AA Base attachment flat for surface mounting
For surface-mounted applications with cables up to Ø6 mm‚ and to use existing mounting holes of MS7/MS9 bases. Bases DB1101A are mount-ed using a spring-loaded catch.
Dimensions (Ø x H) 116 x 11 mm
Color white‚ zRAL 9010
Delivery unit 10 pieces
BPZ:5011270001
07.fm Seite 11 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Detectors AlgoRex Series
7-12 © Siemens Switzerland Ltd 2010
Type Order No.
DBZ1192 Base attachment for humid environment
For installation in damp and corrosive environments. M20 x 1.5 cable entries are located on the side of the base attachments for easy access.
Dimensions (W x H x D) 135 x 135 x 45 mm
Color white‚ zRAL 9010
Protection category IP44
Accessories DBZ1194 Protective cageA5Q00004478 Screwed cable gland M20
BPZ:4588140001
DBZ1194 Protective cage
To protect the detector from damage. Can only be used together with the base attachment humid.
Dimensions (Ø x H) 160 x 126 mm
BPZ:4677110001
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
DBZ1192-AA Base attachment for wet environment
As DBZ1192 but for IP55 protection for heat detectors DT110xA only.
Dimensions (W x H x D) 135 x 135 x 45 mm
Color white‚ zRAL 9010
Protection category IP55
Accessories A5Q00004478 Screwed cable gland M20
BPZ:5355590001
07.fm Seite 12 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Detectors AlgoRex Series
7-13© Siemens Switzerland Ltd 2010
7
Type Order No.
DBZ1195A Acoustic base
The base DBZ1195A has an integrated base sounder. It is mainly used for hotel rooms or wherever it is sensible to have an acoustic warning when a detector is activated. The sounder is operated when the detec-tor LED is lit. The base DB1101A is mounted in the acoustic base using a spring-loaded catch.The acoustic base is connected to the external output of the detector alarm indicator direct.
Sound level M75 dB / 1 m
Operating temperature -10... +60 °C
Dimensions (Ø x H) 128.5 x 32 mm (without detector)
Color white‚ zRAL 9010
Protection category IP44
Relative humidity L95 % (no condensation)
Standard EN54-3
Data sheet 001444
Accessories DBZ1190-AA Micro terminal 0.5 mm2
DBZ1190-AB Connection terminal 2.5 mm2
BPZ:4940140001
DBC1191A-AA Relay base
The base DBC1191A-AA has an integrated relay. It enables the connec-tion of a simple fire control output facility. The contact is activated when the detector LED is lit. The base DB1101A is mounted using a spring-loaded catch.
Operating voltage external supply 10... 48 VDC
Operating current 12... 24 mA
Quiescent current 3.5... 7 mA
Relay outputs 30 VDC / 1 A
Operating temperature -10... +60 °C
Dimensions (Ø x H) 128.5 x 32 mm (without detector)
Color white‚ zRAL 9010
Protection category IP44
Relative humidity L95 % (no condensation)
Data sheet 001566
Accessories DBZ1190-AA Micro terminal 0.5 mm2
DBZ1190-AB Connection terminal 2.5 mm2
BPZ:5017870001
DBZ1190-AA Micro terminal 0.5 mm2‚ 4-pole
As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.
Cable capacity 0.28... 0.5 mm2
Delivery unit 50 pieces
BPZ:4677080001
07.fm Seite 13 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Detectors AlgoRex Series
7-14 © Siemens Switzerland Ltd 2010
Type Order No.
DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole
As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.
Cable capacity 1... 2.5 mm2
Delivery unit 50 pieces
BPZ:4942340001
DBZ1190 Locking device
To protect the detector from theft.
Delivery unit 50 pieces
BPZ:4585260001
DBZ1190A-AC Detector heating
Allows the AlgoRex series smoke detectors to operate under critical environmental conditions‚ for example where there is a danger of icing‚ moisture or condensation‚ in refrigeration plants‚ cold storage rooms‚ attics‚ loading ramps etc. Fits in DB1101A.
Operating voltage 20... 30 VDC
Operating current 35... 55 mA
Operating temperature -30... +40 °C
BPZ:5167850001
DBZ1193A Detector designation plate
To indicate a location address. To number detectors according to instal-lation drawings. The font may be up to 10 mm in an area of 60 x 20 mm. The detector designation plate is connected directly to the base or base attachment.
Color transparent
Delivery unit 10 pieces
BPZ:4864330001
07.fm Seite 14 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Manual Call Points
7-15© Siemens Switzerland Ltd 2010
7
Type Order No.
FDM1101-RG Manual call point with glass plate
For immediate manual actuation of a fire alarm. For indoor and outdoor application. Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is reset and the device is ready for operation again. For surface- and recess-mounted feed lines in eas-ily accessible places.For surface mounting the housing base FDMH295-x must be ordered separately.
Communication protocol collective/SynoLINE600
Operating voltage 16… 28 VDC
Operating current 60… 100 mA
Terminal block 0.28… 1.5 mm2
Operating temperature -25... +70 °C
Storage temperature -30... +75 °C
Relative humidity L95 % (no condensation)
Protection category IP44
Color red‚ zRAL 3000
Standard EN 54-11
Dimensions (W x H x D) 87 x 87 x 20 mm
Data sheet A6V10206486
Accessories FDMH295-R housing baseFDMH295-S housing base with 2 holes + grommets for cable Ø5 mmFDMC295 Protective cover
S54371-F6-A1
FDM1101-RP Manual call point with resettable plastic element
For immediate manual actuation of a fire alarm. For indoor and outdoor application. Direct alarm actuation by pushing on the plastic element. The switch is reset with the key and the device is ready for operation again. For surface- and recess-mounted feed lines in easily accessible places.For surface mounting the housing base FDMH295-x must be ordered separately.
Communication protocol collective/SynoLINE600
Operating voltage 16… 28 VDC
Operating current 60… 100 mA
Terminal block 0.28… 1.5 mm2
Operating temperature -25... +70 °C
Storage temperature -30... +75 °C
Relative humidity L95 % (no condensation)
Protection category IP44
Color red‚ zRAL 3000
Standard EN 54-11
Dimensions (W x H x D) 87 x 87 x 20 mm
Data sheet A6V10206486
Accessories FDMH295-R housing baseFDMH295-S housing base with 2 holes + grommets for cable Ø5 mmFDMC295 Protective cover
S54371-F6-A2
07.fm Seite 15 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Manual Call Points
7-16 © Siemens Switzerland Ltd 2010
Type Order No.
Accessories
FDMH295-R Back box
Housing base for manual call points FDM225‚ FDM1101 and FDM1101A for surface mounting.
Color red‚ zRAL 3000
Dimensions (W x H x D) 87 x 87 x 33
Accessories A5Q00004478 Screwed cable gland M20A5Q00004479 Back nut M20DBZ1190-AB Connection terminal 2.5 mm2
A5Q00013437
FDMH295-S Back box with 2 entries
Housing base for manual call points FDM225‚ FDM1101 and FDM1101A with 2 holes on top fitted with grommet for cable Ø5 mm for surface mounting.
Color red‚ zRAL 3000
Dimensions (W x H x D) 87 x 87 x 33
Accessories DBZ1190-AB Connection terminal 2.5 mm2
A5Q00013438
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
A5Q00004479 Back nut M20
Back nut to screwed cable gland M20 x 1.5.
Delivery unit 10 pieces
A5Q00004479
DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole
As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.
Cable capacity 1... 2.5 mm2
Delivery unit 50 pieces
BPZ:4942340001
07.fm Seite 16 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Manual Call Points
7-17© Siemens Switzerland Ltd 2010
7
Type Order No.
FDMC295 Protective cover
The protective cover protects the manual call points FDM225‚ FDM226‚ FDM1101 and FDM1101A from unintentional glass break.
Color transparent
Delivery unit 10 pieces
A5Q00013440
DM1101__ Collective manual call point
Collective manual call point for the immediate manual actuation of a fire alarm by pushing in the glass plate.The housing FDMH291-x and the switching unit DMA1101 must be ordered separately.
Operating temperature -25... +70 ºC
Protection category IP44
Standard EN54-11
Dimensions (W x H x D) 87 x 87 x 46.6 mm
Data sheet 007980
Accessories FDMC291 Protective coverA5Q00004478 Screwed cable gland M20A5Q00004479 Back nut M20
Products to select from
FDMH291-R See Page 7-17
FDMH291-B See Page 7-18
FDMH291-G See Page 7-18
FDMH291-Y See Page 7-18
DMA1101 See Page 7-18
DM1101__
FDMH291-R Housing red with key
Housing with key for electronic unit.
Color red‚ zRAL 3000
A5Q00002217
07.fm Seite 17 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Manual Call Points
7-18 © Siemens Switzerland Ltd 2010
Type Order No.
FDMH291-Y Housing yellow with key
Housing with key for electronic unit.
Color yellow‚ zRAL 1023
A5Q00004979
FDMH291-G Housing green with key
Housing with key for electronic unit.
Color green‚ zRAL 6024
A5Q00004981
FDMH291-B Housing blue with key
Housing with key for electronic unit.
Color blue‚ zRAL 5005
A5Q00004980
DMA1101 Switching unit collective (single action)
Direct operation switch module for use within the FDMH291-x hous-ings. For connection to collective/SynoLINE600 detection lines. An inte-gral LED provides visual indication of alarm. Provided complete with glass.
Operating voltage 16... 26 VDC
Operating current 60... 100 mA
Terminal block min. 0.28... 1.5 mm2
A5Q00005578
07.fm Seite 18 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Manual Call Points
7-19© Siemens Switzerland Ltd 2010
7
Type Order No.
Accessories
FDMC291 Protective cover
The protective cover protects the manual call point from unintentional glass break. For manual call point housings FDMH291-x.
Delivery unit 5 pieces
A5Q00001644
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
A5Q00004479 Back nut M20
Back nut to screwed cable gland M20 x 1.5.
Delivery unit 10 pieces
A5Q00004479
DM1104__ Collective manual call point
Collective manual call point for the immediate manual actuation of a fire alarm by pushing in the glass plate.The housing DMA1192-xx and the switching unit DMA1104D must be ordered separately.
Operating temperature -25... +70 °C
Protection category IP54 (IP65 with protection seal and screwed cable gland)
Standard EN 54-11
Dimensions (W x H x D) 134 x 134 x 43 mm
Data sheet 007980
Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20A5Q00006735 Locking plug M20(1 hole)A5Q00010055 Locking plug M20(2 holes)
Products to select from
DMA1192-AA See Page 7-21
DMA1192-AB See Page 7-21
DMA1192-AC See Page 7-21
DMA1192-AD See Page 7-21
DMA1104D See Page 7-20
DM1104__
07.fm Seite 19 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Manual Call Points
7-20 © Siemens Switzerland Ltd 2010
Type Order No.
DMA1104D Switching unit collective (single action)
The electronic unit is a single action device by smashing in the glass plate to activate an alarm. For connection to collective/SynoLINE600 detection lines. An LED always indicates the status of the manual call point. The electronic unit is plugged into the housing during commis-sioning.Attach the enclosed sticker 'avoid electrostatic charging' when the switching unit is used in explosion hazard areas only.
Operating voltage 16... 26 VDC
Operating current 60... 100 mA
Terminal block min. 0.28... 1.5 mm2
A5Q00005925
DM1103__ Collective manual call point
Collective manual call point for the immediate manual actuation of a fire alarm by pushing in the glass plate and pressing the push button.The housing DMA1192-xx and the switching unit DMA1103D must be ordered separately.
Operating temperature -25... +70 °C
Protection category IP54 (IP65 with protection seal and screwed cable gland)
Standard EN 54-11
Dimensions (W x H x D) 134 x 134 x 43 mm
Data sheet 007980
Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20A5Q00006735 Locking plug M20(1 hole)A5Q00010055 Locking plug M20(2 holes)
Products to select from
DMA1103D See Page 7-20
DMA1192-AA See Page 7-21
DMA1192-AB See Page 7-21
DMA1192-AC See Page 7-21
DMA1192-AD See Page 7-21
DM1103__
DMA1103D Switching unit collective (double action)
The electronic unit is a double action device; just break the glass and press the button to activate an alarm. For connection to collec-tive/SynoLINE600 detection lines. An LED always indicates the status of the manual call point. The electronic unit is plugged into the housing during commissioning.Attach the enclosed sticker 'avoid electrostatic charging' when the switching unit is used in explosion hazard areas only.
Operating voltage 16... 26 VDC
Operating current 60... 100 mA
Terminal block min. 0.28... 1.5 mm2
A5Q00004470
07.fm Seite 20 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Manual Call Points
7-21© Siemens Switzerland Ltd 2010
7
Type Order No.
DMA1192-AA Housing red‚ with glass and key
Manual call point housing for the switching units DMA110xD.
Color red‚ zRAL 3000
BPZ:5222870001
DMA1192-AB Housing blue‚ with glass and key
Manual call point housing for the switching units DMA110xD.
Color blue‚ zRAL 5005
BPZ:5464250001
DMA1192-AC Housing yellow‚ with glass and key
Manual call point housing for the switching units DMA110xD.
Color yellow‚ zRAL 1023
BPZ:5464120001
DMA1192-AD Housing green‚ with glass and key
Manual call point housing for the switching units DMA110xD.
Color green‚ zRAL 6024
BPZ:5090190001
07.fm Seite 21 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Manual Call Points
7-22 © Siemens Switzerland Ltd 2010
Type Order No.
DM1103-L Manual release button complete
Manual release button DM1103-L for the immediate manual actuation of a gas extinguishing system.For indoor and outdoor application‚ equally suited for wet‚ humid and dusty areas.For surface-mounted feed lines to the DM1103-L the housing is equipped with opening at the top and bottom‚ with sealing studs for M20 cable glands or locking plug (2 locking plugs‚ 2 holes enclosed).For indirect extinguishing release by smashing in the glass plate and pressing the push button. To replace the glass plate‚ open the housing door with the key. The push button must be set back before closing the door again.
Terminal block 0.28... 1.5 mm2
Standard EN12094-3
Protection category IP54 (IP65 with seal DMZ1197-AD)
Operating temperature -25... +70 °C
Dimensions (W x H x D) 134 x 134 x 43 mm
Data sheet 007980
Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20
A5Q00017630
DM1103-S Emergency stop button complete
Emergency stop button DM1103-S for the stop function of a gas extin-guishing system.For indoor and outdoor application‚ equally suited for wet‚ humid and dusty areas.For surface-mounted feed lines to the DM1103-S‚ the housing is equipped with openings at the top and bottom‚ with sealing studs for M20 cable glands or locking plug (2 locking plugs‚ 2 holes enclosed).Indirect stop function by smashing in the glass plate and pressing the push button. As soon as the button is not pressed any longer (self reset)‚ the stopped extinguishing release will continue. To replace the glass plate‚ open the housing door with the key.
Terminal block 0.28... 1.5 mm2
Standard EN12094-3
Protection category IP54 (IP65 with seal DMZ1197-AD)
Operating temperature -25... +70 °C
Dimensions (W x H x D) 134 x 134 x 43 mm
Data sheet 007980
Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20
A5Q00014486
07.fm Seite 22 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Manual Call Points
7-23© Siemens Switzerland Ltd 2010
7
Type Order No.
Accessories
DMZ1197-AD Protection seal
Protects the manual call point in wet applications.The seal improves the manual call point housing's protection category.
Delivery unit 5 pieces
BPZ:5470680001
DMZ1197-AC Protective cover
Protects the manual call point from unintentional glass break. Protec-tive cover can be easily fitted directly in the housing cover.
Delivery unit 5 pieces
BPZ:5223550001
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
A5Q00006735 Locking plug M20 x 1.5 (1 hole)
For manual call point housings and surface-mounted feed lines in the manual call point housing.For applications in dry rooms.
Color red‚ zRAL 3000
Delivery unit 10 pieces
A5Q00006735
A5Q00010055 Locking plug M20 x 1.5 (2 holes)
For manual call point housings and surface-mounted feed lines in the manual call point housing.For applications in dry rooms.
Color red‚ zRAL 3000
Delivery unit 10 pieces
A5Q00010055
07.fm Seite 23 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsCollective Line SynoLINE600Alarm Indicators for SynoLINE600
7-24 © Siemens Switzerland Ltd 2010
Type Order No.
FDAI91 Alarm indicator - Door frame
The alarm indicator is connected in parallel to automatic fire detectors in order to indicate quickly the source of an alarm signal from detectors that are not easily accessible or visible. The alarm indicator contains an indicator lamp unit with one or two LEDs. They light up as soon as a connected fire detector gives an alarm.Screwless connection terminals.The alarm indicator is suitable for door frames.
Operating voltage 5... 8 VDC
Operating current max. 35 mA
Cable capacity max. 1.5 mm2
Operating temperature -25… +80 °C
Relative humidity L95 %
Color white‚ zRAL 9010
Protection category IP40
Dimensions (W x H x D) 62 x 37 x 24 mm
Data sheet A6V10276520
S54370-F9-A1
FDAI92 Alarm indicator - Surface
The alarm indicator is connected in parallel to automatic fire detectors in order to indicate quickly the source of an alarm signal from detectors that are not easily accessible or visible. The alarm indicator contains an indicator lamp unit with one or two LEDs. They light up as soon as a connected fire detector gives an alarm.Screwless connection terminals.The alarm indicator is suitable for wall mounting.
Operating voltage 5... 8 VDC
Operating current max. 35 mA
Cable capacity max. 1.5 mm2
Operating temperature -25… +80 °C
Relative humidity L95 %
Color white‚ zRAL 9010
Protection category IP40
Dimensions (W x H x D) 85 x 85 x 28 mm
Data sheet A6V10276520
Accessories AI330 Adapter frame
S54370-F3-A1
AI330 Adapter frame for alarm indicator
By means of the additional frame‚ the alarm indicator can also be used for surface laid conduits or ducts‚ to increase the loop space and as an adapter for different makes of the box.
Dimensions (W x H x D) 85 x 85 x 16 mm
BPZ:3169430001
07.fm Seite 24 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsCollective Line SynoLINE600Alarm Indicators for SynoLINE600
7-25© Siemens Switzerland Ltd 2010
7
Type Order No.
FDAI93 Alarm indicator - Flush
Indicator lamp to connect in parallel to automatic fire detectors. Made of transparent plastic‚ the alarm indicator is suitable for installation in door frames‚ switching panels‚ ceiling voids or special housings.The 22.5 mm Ø mounting hole is drilled by the system owner.The holder must be fitted with an insulating cap for safety.
Operating voltage 6... 8 VDC
Operating current max. 35 mA
Cable capacity max. 1.5 mm2
Operating temperature -25… +80 °C
Relative humidity L95 %
Color transparent
Protection category IP56 with DCA1191IP65 with DJZ1193
Data sheet A6V10276520
Accessories DCA1191 Housing (IP56)
S54370-F5-A1
DCA1191 Housing (empty)
Housing with cover for several applications. The housing offers six M20 cable feed-throughs for screwed cable glands and offers a higher pro-tection category.The screwed cable gland must be ordered separately.
Dimensions (W x H x D) 135 x 135 x 65 mm
Color white‚ zRAL 9010
Protection category IP56
Accessories A5Q00004478 Screwed cable gland M20
BPZ:4588560001
BPZ:2473130001 Washer
Washer for alarm indicator model recess mounting. The washer can be used for applications in humid rooms.
Dimensions (Ø x D) 23 x 1 mm
BPZ:2473130001
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
DJZ1193 Alarm indicator housing incl. washer
For surface mounting in wet areas.1 alarm indicator can be built into the housing.
Dimensions (W x H x D) 87 x 87 x 64 mm
Color white‚ zRAL 9010
Protection category IP65
BPZ:5302950001
07.fm Seite 25 Mittwoch, 28. Juli 2010 8:45 08
Fire Detection Collective PeripheralsCollective Line SynoLINE600Alarm Indicators for SynoLINE600
7-26 © Siemens Switzerland Ltd 2010
Type Order No.
MVH1 Mounting bracket
For mounting of the alarm indicator housing DJZ1193 and detectors in hollow floors.
Length 0.29... 0.42 m (pipe clamp 1/2")
BPZ:3496190001
07.fm Seite 26 Mittwoch, 28. Juli 2010 8:45 08
Conventional Alarm EquipmentSounders
8-1© Siemens Switzerland Ltd 2010
8
Type Order No.
AGN24.6 Alarm device
The alarm sounder is the most popular fire sounder for inside and out-door applications‚ although under roof or canopy. The volume is adjust-able with a potentiometer. The alarm sounder allows differentiation between various alarms. Choice of 28 preset tones with volume con-trol. Line monitoring possible by changing the polarity. The base is included.The adapter base ZS/AGN24.5 for IP65 must be ordered separately.
Operating voltage 9... 30 VDC
Alarm current 18 mA
Operating temperature -25... +80 °C
Number of sounds 28
Frequency range 500... 4000 Hz
Volume at 24 V and 1 m 92.. 111 dB
Cable capacity 0.28... 1.5 mm2
Protection category IP54
Dimensions (Ø x D) 93 x 63 mm
Color white‚ zRAL 9003
Data sheet 001790
Accessories ZS/AGN24.5 Adapter base for IP65
BPZ:5371170001
ZS/AGN24.5 Adapter base
The ZS/AGN24.5 adapter base is used to upgrade the alarm device AGN24.6 and ALB24.. to IP65.
Dimensions (Ø x D) 93 x 30 mm
Color white‚ zRAL 9003
Protection category IP65
Data sheet 001790
BPZ:4242620001
AGT24.1 Alarm device
Ultra slim profile sounder for ceiling mounting for small to medium size rooms with a low background noise level. Detectors can be fitted to the unit providing a neat‚ unobtrusive installation. Choice of 4 different tones with two sound intensities‚ remote-controlled change of tone for two-stage alarm.
Operating voltage 9... 30 VDC
Alarm current 3... 15 mA
Operating temperature -25... +85 °C
Number of sounds 4
Frequency range 510... 970 Hz
Volume at 24 V and 1 m 86... 97 dB
Cable capacity 0.28... 1.5 mm2
Protection category IP42
Dimensions (Ø x D) 110 x 35 mm
Color white‚ zRAL 9003
Data sheet 001790
BPZ:5371040001
08.fm Seite 1 Mittwoch, 28. Juli 2010 8:49 08
Conventional Alarm EquipmentSounders
8-2 © Siemens Switzerland Ltd 2010
Type Order No.
AGS24.5 Mallory buzzer
Buzzer for small‚ dry rooms with a low background noise level. Buzzer with continuous tone. For incorporation in equipment‚ panels etc. (for front panels with a max. thickness of 5 mm‚ a drill hole of 29.5 mm is adequate).
Operating voltage 18... 36 VDC
Alarm current 12 mA
Operating temperature -20... +40 °C
Number of sounds 1
Frequency range 2900 Hz
Volume at 24 V and 1 m 80 dB
Cable capacity 0.28... 1.5 mm2
Protection category IP20
Dimensions (Ø x D) 56 x 52 mm
Color black
Data sheet 001790
BPZ:2785020001
08.fm Seite 2 Mittwoch, 28. Juli 2010 8:49 08
Conventional Alarm EquipmentOptical Signaling Equipment
8-3© Siemens Switzerland Ltd 2010
8
Type Order No.
ALB24.1OR Flashing signal lamp 'orange'
Powerful light intensity generated by electronic flash tube‚ ribbed dome with strong diffusion. Ideal for noisy environments. To identify build-ings‚ entrances and exits: help can be brought quickly in an emergency. For inside and outside application.The adapter base ZS/AGN24.5 for IP65 must be ordered separately.
Operating voltage 20... 30 VDC
Alarm current 155 mA (3.7 W)
Operating temperature -20... +55 °C
Frequency range ca. 1 Hz (60/min.)
Flash energy 2 Joule
Cable capacity 1.5 mm2
Protection category IP54
Dimensions (Ø x D) 93 x 75 mm
Data sheet 001570
Accessories ZS/AGN24.5 Adapter base for IP65
BPZ:5154140001
ALB24.1R Flashing signal lamp 'red'
Powerful light intensity generated by electronic flash tube‚ ribbed dome with strong diffusion. Ideal for noisy environments. To identify build-ings‚ entrances and exits: help can be brought quickly in an emergency. For inside and outside application.The adapter base ZS/AGN24.5 for IP65 must be ordered separately.
Operating voltage 20... 30 VDC
Alarm current 155 mA (3.7 W)
Operating temperature -20... +55 °C
Frequency range ca. 1 Hz (60/min.)
Flash energy 2 Joule
Cable capacity 1.5 mm2
Protection category IP54
Dimensions (Ø x D) 93 x 75 mm
Data sheet 001570
Accessories ZS/AGN24.5 Adapter base for IP65
BPZ:5154270001
ZS/AGN24.5 Adapter base
The ZS/AGN24.5 adapter base is used to upgrade the alarm device AGN24.6 and ALB24.. to IP65.
Dimensions (Ø x D) 93 x 30 mm
Color white‚ zRAL 9003
Protection category IP65
Data sheet 001790
BPZ:4242620001
08.fm Seite 3 Mittwoch, 28. Juli 2010 8:49 08
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 29 28.05.10 16:58
Special Applications
Offering a wide range of special detectorsThe detector range of Cerberus® PRO includes a broad range of special detectors, meeting various needs. In areas with limited access such as high bay warehouses, linear smoke detectors are the ideal choice. Flame detectors cover areas containing highly fl ammable materials best. Furthermore, Cerberus PRO offers a complete range for areas subject to explosion hazards and for areas that require very high sensitivity.
Flame detection – for areas with highly fl ammable materials Linear smoke detector – for high ceiling areas with limited accessibility Aspirating smoke detection – for areas requiring high sensitivity Ex detectors – for areas subject to explosion hazards Radio fi re detectors – for historical buildings and other special applications
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 31 28.05.10 16:58
Special ApplicationsSpecial DetectorsInfrared Flame Detectors
9-2 © Siemens Switzerland Ltd 2010
Type Order No.
FDF__ Infrared flame detector
Infrared flame detector for special applications. The infrared flame detector detects smokeless liquid and gas fires as well as smoke-gener-ating open fires resulting from the combustion of carbonaceous mate-rials such as wood‚ synthetics‚ gases‚ oil products‚ etc. The LE3 test lamp is used to make a performance check on the infrared flame detector at a distance of up to 10 m.Can be used as an addressable‚ collective or conventional device.The detector unit FDF2x1-9 and the base FDFB291 must be ordered separately.
Communication protocol FDnet/C-NET‚ collective‚ conven-tional
Ext. alarm indicator 2
Relative humidity L95 %
Color white‚ zRAL 9010
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720collective‚ conventional -> CZ10‚ BC10‚ FC10‚ XC10‚ CS11‚ FC700A‚ FC330A‚ SIGMASYS‚ BMS‚ SM80/88/D100
Standard EN54-10‚ EN54-17
Dimensions (W x H x D) 135 x 135 x 77 mm
Data sheet 007012
Accessories DFZ1190 Rain hoodMV1 Mounting bracketMWV1 Ball and socket joint
Products to select from
FDF221-9 See Page 9-2
FDF241-9 See Page 9-3
FDFB291 See Page 9-3
FDF__
FDF221-9 DA Infrared flame detector unit (1 sensor)
The infrared flame detector is used for simple applications‚ additional to smoke detectors. Only used without source of interference such as sun‚ halogen light‚ and black body radiation.1 infrared sensor with detection algorithms.The base FDFB291 must be ordered separately.
Operating voltage FDnet/C-NET-> 12... 33 VDCcollective/conv. -> 16... 28 VDC
Quiescent current FDnet/C-NET -> 0.7 mA collective/conv. -> 0.5 mA
Operating temperature -25... +70 °C
Storage temperature -40... +75 °C
Dimensions (W x H x D) 135 x 135 x 32 mm
Protection category IP44
A5Q00003902
09.fm Seite 2 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsSpecial DetectorsInfrared Flame Detectors
9-3© Siemens Switzerland Ltd 2010
9
Type Order No.
FDF241-9 ASA Infrared flame detector unit (3 sensors)
The infrared flame detector is specially suited to environments where deceptive phenomena such as e.g. sun‚ radiation or hot engines have to be expected. For large industrial warehouses‚ hangars for military and civil aircraft‚ underground tunnels etc.3 infrared sensors with ASAtechnology™.The base FDFB291 must be ordered separately.
Operating voltage FDnet/C-NET -> 12... 33 VDCcollective/conv. -> 14... 28 VDC
Quiescent current FDnet/C-NET -> 0.7 mAcollective/conv. -> 0.5 mA
Operating temperature -35... +70 °C
Storage temperature -40... +75 °C
Dimensions (W x H x D) 135 x 135 x 32 mm
Protection category IP67
A5Q00003006
FDFB291 Base for infrared flame detectors FDF2x1-9
The base comprises a robust‚ glass fiber-reinforced‚ plastic housing which provides the required isolated installation of the detector. The base contains screwless terminals‚ isolated auxiliary terminals and six M20 cable entry possibilities for cable glands.
Cable capacity 0.2... 1.5 mm2 (AWG24... 15)
Dimensions (W x H x D) 135 x 135 x 45 mm
Accessories A5Q00004478 Screwed cable gland M20
A5Q00003310
DFZ1190 Rain hood
Rain hood for the infrared flame detector for outdoor applications.
Dimensions (W x H x D) 150 x 165 x 130 mm
BPZ:5302660001
MV1 Mounting bracket
The mounting bracket for volumetric surveillance‚ fixes the infrared flame detector at the right angle.
Dimensions (W x H x D) 136 x 120 x 120 mm
BPZ:3950450001
09.fm Seite 3 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsSpecial DetectorsInfrared Flame Detectors
9-4 © Siemens Switzerland Ltd 2010
Type Order No.
MWV1 Ball and socket joint
Ball and socket joint for the infrared flame detector for the orientation to a defined object.
Dimensions (H x W x D) 120 x 164 x 118 mm
BPZ:3674840001
LE3 Test lamp for flame detectors
The test lamp is used for testing the operation of all flame detectors (non explosion-hazard areas). It is supplied with all the necessary acces-sories in a suitable carrying case (incl. charger‚ without battery). The carrying case also provides a means of storing the test lamp free of dust.The battery FA2003-A1 must be ordered separately.
Operating temperature -20... +45 °C
Storage temperature -20... +45 °C
Battery capacity 1 x 12 V / 7 Ah
Data sheet AlgoRex‚ Synova‚ Sinteso -> 000252Cerberus PRO -> A6V10203222
BPZ:3669510001
09.fm Seite 4 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsSpecial DetectorsLinear Smoke Detectors
9-5© Siemens Switzerland Ltd 2010
9
Type Order No.
FDL__ ASA Linear smoke detector
The linear smoke detector is ideal to monitor extensive areas (detec-tion distance 5... 100 m). Wiring is simple‚ and needed only on one side. The linear smoke detector consists of a detector‚ a base‚ and a simple reflector or a sophisticated prism on the opposite side. It is the ideal solution for monitoring of large store-rooms and production work-shops‚ areas with complex roof structures or historically valuable ceil-ings‚ covered courtyards‚ atrium type buildings and reception halls.Can be used as an addressable‚ collective or conventional device.The detector FDL241-9 and the base FDLB291 must be ordered sepa-rately.
Communication protocol FDnet/C-NET‚ collective‚ conven-tional
Ext. alarm indicator 2
Operating temperature -25... +60 °C
Storage temperature -30... +75 °C
Relative humidity L95 %
Color white‚ zRAL 9010
Protection category IP65
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720collective‚ conventional -> CZ10‚ BC10‚ FC10‚ XC10‚ CS11‚ FC700A‚ FC330A‚ SIGMASYS‚ BMS‚ SM80/88/D100
Standard EN54-12‚ EN54-17
Dimensions (W x H x D) 135 x 135 x 115 mm
Data sheet 007017
Products to select from
FDL241-9 See Page 9-6
FDLB291 See Page 9-6
FDL__
09.fm Seite 5 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsSpecial DetectorsLinear Smoke Detectors
9-6 © Siemens Switzerland Ltd 2010
Type Order No.
FDL241-9 ASA Linear smoke detector unit
The detector consists of a light emitter and a light receiver. The light emitter emits a bundled infrared ray‚ which is scattered back by the prism shaped reflector to the light emitter. The receiver converts the received infrared signal to an electric signal‚ which is evaluated by the microprocessor-controlled electronics. Smoke penetrating the measur-ing section attenuates the infrared signal. When the signal reaches pre-defined measuring values‚ the detector transmits the corresponding danger level to the control unit. Distance measurement for the recog-nition of foreign matter. The built-in alarm indicator signals the alarm status locally. For various distances‚ different reflectors are available.The optics can be efficiently adjusted to the reflector by single-handed alignment via the adjustment device FDLU291.The base FDLB291 must be ordered separately.
Operating voltage FDnet/C-NET -> 12... 33 VDCcollective/conv. -> 14... 28 VDC
Quiescent current 0.8 mA / 0.7 mA
Dimensions (W x H x D) 135 x 135 x 70 mm
Accessories DLR1191 Reflector for long distanceDLR1192 Reflector for middle dis-tanceDLR1193 Reflector for short dis-tanceDLF1191-AA Short distance filter for 7... 10 mDLF1191-AB Short distance filter for 5... 8 mDLF1191-AC Extraneous light filterDLH1191A Detector heatingFDLU291 Adjustment device
A5Q00002298
FDLB291 Base for linear smoke detector FDL241-9
The base comprises a robust‚ glass fiber-reinforced‚ plastic housing which provides the required isolated installation of the detector. The base contains screwless terminals and six M20 cable entry possibilities for cable glands.
Cable capacity 0.2... 1.5 mm2 (AWG24... 15)
Dimensions (W x H x D) 135 x 135 x 45 mm
Accessories A5Q00004478 Screwed cable gland M20
A5Q00003941
09.fm Seite 6 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsSpecial DetectorsLinear Smoke Detectors
9-7© Siemens Switzerland Ltd 2010
9
Type Order No.
Accessories
DLR1191 Reflector for long distance (prism)
Retro-reflectors are characterized by the fact that an impinging light ray is reflected in parallel. The reflector does not need to be mounted at a right angle to the light ray. Vibrations and distortions in the wall where the reflector is mounted do not cause any disturbances either. Another advantage lies in the fact that possibly interfering light is also reflected in on itself and can thus not reach the receiver.The retro-reflecting prism has the shape of an even pyramid‚ the lateral surfaces of which are made up from isosceles‚ right-angled triangles. Light rays coming in through the base surface are completely reflected by the lateral surfaces and are then scattered back through the base.For distances of 20... 100 m.
Detector heating equipped‚ external power supply 24 VDC is required
Dimensions (W x H x D) 135 x 135 x 65 mm
Color white‚ zRAL 9010
Accessories A5Q00004478 Screwed cable gland M20
BPZ:4787710001
DLR1192 Reflector for middle distance (foil)
The foil consists of micro-prismatic elements‚ which are formed in a transparent‚ synthetic resin‚ sealed and mounted on a plastic base. The reflector foil has the same principal effect (function) as the prism.For distances of 30... 65 m.
Dimensions (W x H x D) 200 x 200 x 2.5 mm
BPZ:4788490001
DLR1193 Reflector for short distance (foil)
The foil consists of micro-prismatic elements‚ which are formed in a transparent‚ synthetic resin‚ sealed and mounted on a plastic base. The reflector foil has the same principal effect (function) as the prism.For distances of 10... 30 m.
Dimensions (W x H x D) 100 x 100 x 2.5 mm
BPZ:4787840001
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
DLF1191-AA Filter for short distances (7... 10 m)
For short distances between 7 and 10 meters‚ an additional short dis-tance filter is required. The filter attenuates the detector signal over short distances. The filter can be inserted directly into the detector unit.
BPZ:4933030001
09.fm Seite 7 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsSpecial DetectorsLinear Smoke Detectors
9-8 © Siemens Switzerland Ltd 2010
Type Order No.
DLF1191-AB Filter for short distances (5... 8 m)
For short distances between 5 and 8 meters‚ an additional short dis-tance filter is required. The filter attenuates the detector signal over short distances. The filter can be inserted directly into the detector unit.
BPZ:4933160001
DLF1191-AC Filter against external light influences
Interferences of the detector by extraneous light are rather rare. How-ever‚ if such a disturbance should occur in case of a strong impact of extraneous light‚ the extraneous light filter is available. The filter absorbs disturbing IR rays. The filter can be inserted into the detector (not possible if short distance filter is inserted).
BPZ:5221480001
DLH1191A Detector heating
Enables operation of a linear smoke detector where there is a risk of condensation.24 VDC external power supply is necessary.
Operating voltage 20… 30 VDC
Operating current 30... 50 mA
BPZ:4787970001
FDLU291 Adjustment device set for linear smoke detector
The optics of the linear smoke detector can be efficiently adjusted to the reflector by single-handed alignment via the adjustment device.Box with adjustment device‚ alarm test filter‚ visor‚ magnet‚ spiral cable‚ MC-Link cable‚ and battery 9 V‚ 0.5 Ah.
A5Q00004905
RE10 Detector tester for linear smoke detectors
For performance check of linear smoke detector. In compliance with the type of detector to be tested‚ the alarm test filter is inserted in the detector tester.The detector tester is then held in front of the optical parts of the detec-tor (i.e. into the infrared ray). The detector reacts after a few seconds.Alarm test filter contained in FDLU291 or TF04 must be ordered sepa-rately.
Data sheet Synova‚ AlgoRex -> 001164Sinteso -> 007228Cerberus PRO -> A6V10203222
Accessories TF04 Alarm test filterFDUM291 Telescope rodFDUM292 Telescope rod
BPZ:3685190001
09.fm Seite 8 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsSpecial DetectorsLinear Smoke Detectors
9-9© Siemens Switzerland Ltd 2010
9
Type Order No.
TF04 Alarm test filter (Absorption 77 %)
Alarm test filter for detector tester RE10.
BPZ:4931090001
09.fm Seite 9 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsSpecial DetectorsAir Sampling Smoke Detection
9-10 © Siemens Switzerland Ltd 2010
Type Order No.
FDBZ292 Air sampling smoke detection kit
The air sampling smoke detection kit is a passive monitoring system without its own fan. It makes use of the existing pressure difference in the ventilation system in order to supply a continuous flow of air through a bypass from the ventilation duct to the air sampling smoke detection kit.The air sampling smoke detection kit only works if the ventilation sys-tem is in operation and the air is circulating. The monitored air must be clean‚ i.e. free from dust and aerosols.When a smoke concentration set in the smoke detector is reached‚ the corresponding danger level is signaled to the fire alarm control unit which initiates the corresponding alarm.Can be used as an addressable or collective device.The smoke detectors and bases must be ordered separately.
Smoke detector Sinteso -> FDO241‚ FDOOT241-8‚ FDOOT241-9AlgoRex‚ Synova -> DO1133A‚ DO1103A‚ DO1104ACerberus PRO -> DO1104A
Detector base Sinteso -> FDB201/221‚ FDB201/221-AAAlgoRex -> DB1151A‚ DB1131A‚ DB1101ASynova -> DB1101A‚ SO620ACerberus PRO -> DB1101A
System compatibility Sinteso -> FDnetAlgoRex -> interactive‚ AnalogPLUS‚ collectiveSynova -> SynoLINE600‚ SynoLOOPCerberus PRO -> collective‚ in C-NET via FDCIO223
Min. duct diameter 100 mm
Permissible air speed 1... 20 m/s
Airflow indicator M1 m/s
Ambient temperature‚ operation -20… +50 °C
Protection category IP54
Relative humidity L95 %
Dimensions (W x H x D) 146 x 235 x 183 mm
Color grey‚ zRAL 7001
Data sheet 009728
Accessories FDBZ292-AA Air flow tube‚ L = 0.6 mFDBZ292-AB Air flow tube‚ L = 1.5 mFDBZ292-AC Air flow tube‚ L = 2.8 mFDBZ292-AD Sealing kitFDBZ292-AF Mounting bracketDBZ1190-AB Connection terminal 1... 2.5 mm2
A5Q00021362
09.fm Seite 10 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsSpecial DetectorsAir Sampling Smoke Detection
9-11© Siemens Switzerland Ltd 2010
9
Type Order No.
DO1104A Smoke detector‚ collective wide spectrum
Automatic fire detector with higher response sensitivity for the early warning of smoke-forming‚ flaming fires and smoldering fires. For applications in hospital rooms‚ archives‚ museums etc.The base DB1101A must be ordered separately.
Operating voltage 16... 24 VDC
Quiescent current max. 100 NA
Operating temperature -25... +60 °C
Storage temperature -30… +75 °C
Sensitivity Typ. 1.8 %/m
Protection category IP44
Color white‚ zRAL 9010
Dimensions (Ø x H) 115 x 51mm (incl. base)
Standard EN 54-7
Data sheet 001578
BPZ:5090640001
DB1101A Base for collective detector series
Base made of impact and scratch-proof plastic and environmentally safe materials. Integral rubber gasket to protect against draught‚ dirt and dripping water from above. Screwless terminals for easy installa-tion. Space for auxiliary terminals as micro terminals (0.5 mm2) and connection terminals (2.5 mm2). Fits all standard flush-mounted boxes from 55 to 80 mm.
Cable capacity 0.2... 2.5 mm2
Dimensions (Ø x H) 115 x 21 mm
Color white‚ zRAL 9010
Data sheet 001035
BPZ:4863650001
Accessories
FDBZ292-AA Air flow tube 0.6 m
The air flow tube is introduced through a hole drilled into the duct and shortened according to the diameter of the duct.
Length 0.6 m
A5Q00021363
09.fm Seite 11 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsSpecial DetectorsAir Sampling Smoke Detection
9-12 © Siemens Switzerland Ltd 2010
Type Order No.
FDBZ292-AB Air flow tube 1.5 m
As FDBZ292-AA but different length.
Length 1.5 m
A5Q00021364
FDBZ292-AC Air flow tube 2.8 m
As FDBZ292-AA but different length.
Length 2.8 m
A5Q00021366
FDBZ292-AD Sealing kit for air flow tubes
One sealing kit is necessary for-> applications using the mounting bracket-> applications using air flow tubes longer than 1 mTwo sealing kits are necessary for-> applications using the mounting bracket and air flow tubes longer than 1 m
A5Q00021367
FDBZ292-AF Mounting bracket
The mounting bracket is used for uneven‚ round and insulated ducts.
A5Q00021369
09.fm Seite 12 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsSpecial DetectorsAir Sampling Smoke Detection
9-13© Siemens Switzerland Ltd 2010
9
Type Order No.
DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole
As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.
Cable capacity 1... 2.5 mm2
Delivery unit 50 pieces
BPZ:4942340001
09.fm Seite 13 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsSpecial DetectorsAspirating Smoke Detection
9-14 © Siemens Switzerland Ltd 2010
Type Order No.
LaserFOCUS VLF-250 Aspirating smoke detector with display
The LaserFOCUS detector is a very early warning smoke detector (Aspi-rating Smoke Detector ASD) designed to protect small‚ business-critical environments of less than 250 sqm. The detector works by continually drawing air into sampling holes in a pipe network. The air is filtered and passed into a detection chamber where light-scattering technology detects the presence of very small amounts of smoke. Detector status information is communicated on the detector display.The FDnet/C-NET interface card is integrated.
Communication protocol FDnet/C-NET
Operating voltage 18… 30 VDC
Quiescent current 220 mA
Alarm current 295 mA
Display 4 Alarm state indicatorsFault and disabled indicatorsSmoke level indicator
Area coverage up to 250 m2
Alarm threshold 0.025 - 2.00 %/m / Info alarm‚ Pre-alarm0.025 - 20.00 %/m / Fire 1‚ Fire 2
Air inlet pipe Accepts both metric and American standard pipe sizesExternal diameter 25 mmInternal diameter 21 mm
Pipe length max. 1 x 25 m (max. 12 holes)max. 2 x 15 m per branch (max. 6 holes per branch)
Relay outputs 3x 2 A / 30 VPre-alarm‚ Alarm‚ Fault
Terminals 0.2… 2.5 mm2 (30… 12 AWG)
Dimensions (W x H x D) 255 x 185 x 90 mm
Operating temperature 0... +40 °C
Relative humidity L95 % (no condensation)
Protection category IP30
Data sheet A6V10221433
VLF-250-SIE
09.fm Seite 14 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsSpecial DetectorsAspirating Smoke Detection
9-15© Siemens Switzerland Ltd 2010
9
Type Order No.
LaserFOCUS VLF-500 Aspirating smoke detector with display
The LaserFOCUS detector is a very early warning smoke detector (Aspi-rating Smoke Detector ASD) designed to protect small‚ business-critical environments of less than 500 sqm. The detector works by continually drawing air into sampling holes in a pipe network. The air is filtered and passed into a detection chamber where light-scattering technology detects the presence of very small amounts of smoke. Detector status information is communicated on the detector display.The FDnet/C-NET interface card is integrated.
Communication protocol FDnet/C-NET
Operating voltage 18… 30 VDC
Quiescent current 410 mA
Alarm current 490 mA
Display 4 Alarm state indicatorsFault and disabled indicatorsSmoke level indicator
Area coverage up to 500 m2
Alarm threshold 0.025 - 2.00 %/m / Info alarm‚ Pre-alarm0.025 - 20.00 %/m / Fire 1‚ Fire 2
Air inlet pipe Accepts both metric and American standard pipe sizesExternal diameter 25 mmInternal diameter 21 mm
Pipe length max. 1 x 50 m (max. 24 holes)max. 2 x 30 m per branch (max. 12 holes per branch)
Relay outputs 3x 2 A / 30 VPre-alarm‚ Alarm‚ Fault
Terminals 0.2… 2.5 mm2 (30… 12 AWG)
Dimensions (W x H x D) 255 x 185 x 90 mm
Operating temperature 0... +40 °C
Relative humidity L95 % (no condensation)
Protection category IP30
Data sheet A6V10221433
VLF-500-SIE
09.fm Seite 15 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsSpecial DetectorsRadio Fire Detection Wireless System
9-16 © Siemens Switzerland Ltd 2010
Type Order No.
FDCW221 Radio gateway
Wireless fire detection is used in situations where the user wants to avoid wires and their installation. In addition it means less interruption of operation and high flexibility for extensions and changes. High trans-mission reliability by radio transmission in SRD band (Short Range Device)‚ a reserved frequency band with defined user rules. 80 chan-nels are available.The radio gateway FDCW221 is connected to the detector bus FDnet/C-NET and communicates with up to 30 radio detectors (smoke detectors and manual call points). Each detector has its own location address.The additional 9 V battery (must be ordered separately A5Q00004142) safeguards operation during commissioning or when the detector bus is without voltage. MC-Link connector for commissioning and mainte-nance with detector exchanger and tester.
Supply voltage via FDnet/C-NET‚ additionally 1x 9 V lithium battery‚ monitored
Communication protocol FDnet/C-NET
Transmitter/receiver antenna 2 (antenna diversity)
Transmitting power L5 mW ERP
Transmission distance max. 40 m in buildingmax. 200 m in open air
Channel width 25 kHz
Radio frequency 868 ... 870 MHz (SRD band)
Ext. alarm indicator 2
Operating temperature -10... + 55 °C
Dimensions (W x H x D) 58 x 213.5 x 33.4 mm
Color grey-white‚ zRAL 9002
Protection category IP40
Relative humidity L95 %
Standard EN 54-17‚ EN 54-18
Approval
Data sheet 010087
A5Q00020241
09.fm Seite 16 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsSpecial DetectorsRadio Fire Detection Wireless System
9-17© Siemens Switzerland Ltd 2010
9
Type Order No.
DOW1171/DBW1171 Radio smoke detector complete
Uniform response to various types of fires. Dynamic analysis of the sen-sor signal in the detector itself. Built-in diagnostic algorithms with auto-matic self-test. High immunity to false alarms and ambient influences. High-quality opto-electronic sensor system. Automatic compensation of soiling. Each radio smoke detector has its own address and can trans-mit 4 danger levels.The radio smoke detector is supplied by two 9 V lithium batteries and can be mounted at any position within radio range. In normal operating condition they have a service life of more than 5 years.The radio smoke detector can be inserted and removed and actuated using the DZ1191‚ DZ1193 detector exchanger.The radio smoke detector complete consists of the radio smoke detec-tor DOW1171‚ the base DBW1171 and 2 batteries (A5Q00004142).
Supply voltage 2x 9 V lithium batteries‚ separately monitored
Transmitter/receiver antenna 2 (antenna diversity)
Transmitting power L5 mW ERP
Transmission distance max. 40 m in buildingmax. 200 m in open air
Channel width 25 kHz
Radio frequency 868... 870 MHz (SRD band)
Operating temperature -10... + 55 °C
Dimensions (Ø x H) 119 x 73 mm
Color white‚ zRAL 9010
Protection category IP44
Relative humidity L95 %
Standard EN 54-7
Approval
Data sheet 010087
S24218-F62-A5
09.fm Seite 17 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsSpecial DetectorsRadio Fire Detection Wireless System
9-18 © Siemens Switzerland Ltd 2010
Type Order No.
DOW1171 Radio smoke detector
Uniform response to various types of fires. Dynamic analysis of the sen-sor signal in the detector itself. Built-in diagnostic algorithms with auto-matic self-test. High immunity to false alarms and ambient influences. High-quality opto-electronic sensor system. Automatic compensation of soiling. Each radio smoke detector has its own address and can trans-mit 4 danger levels.The radio smoke detector is supplied by two 9 V lithium batteries (must be ordered separately) and can be mounted at any position within radio range. In normal operating condition they have a service life of more than 5 years.The radio smoke detector can be inserted and removed and actuated using the DZ1191‚ DZ1193 detector exchanger.The base DBW1171 and the batteries (A5Q00004142) must be ordered separately.
Supply voltage 2x 9 V lithium batteries‚ separately monitored
Transmitter/receiver antenna 2 (antenna diversity)
Transmitting power L5 mW ERP
Transmission distance max. 40 m in buildingmax. 200 m in open air
Channel width 25 kHz
Radio frequency 868... 870 MHz (SRD band)
Operating temperature -10... + 55 °C
Dimensions (Ø x H) 119 x 73 mm
Color white‚ zRAL 9010
Protection category IP44
Relative humidity L95 %
Standard EN 54-7
Approval
Data sheet 010087
S24218-F62-A6
DBW1171 Base for radio smoke detector
Base made of impact and scratch-proof plastic and environmentally safe materials. The base is required for installation of radio smoke detector DOW1171.
Dimensions (Ø x H) 118 x 38.7 mm
Color white‚ zRAL 9010
Accessories DBZ1190 Detector locking deviceDBZ1193A Detector designation plateDBZ1192 Base attachment‚ wet application
S24218-F316-A1
Accessories
DBZ1190 Locking device
To protect the detector from theft.
Delivery unit 50 pieces
BPZ:4585260001
09.fm Seite 18 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsSpecial DetectorsRadio Fire Detection Wireless System
9-19© Siemens Switzerland Ltd 2010
9
Type Order No.
DBZ1193A Detector designation plate
To indicate a location address. To number detectors according to instal-lation drawings. The font may be up to 10 mm in an area of 60 x 20 mm. The detector designation plate is connected directly to the base or base attachment.
Dimensions (W x H) 62 x 52 mm
Color transparent
Delivery unit 10 pieces
BPZ:4864330001
DBZ1192 Base attachment for humid environment
For installation in damp and corrosive environments. M20 x 1.5 cable entries are located on the side of the base attachments for easy access.
Dimensions (W x H x D) 135 x 135 x 45 mm
Color white‚ zRAL 9010
Protection category IP44
Accessories DBZ1194 Protective cageA5Q00004478 Screwed cable gland M20
BPZ:4588140001
DBZ1194 Protective cage
To protect the detector from damage. Can only be used together with the base attachment humid.
Dimensions (Ø x H) 160 x 126 mm
BPZ:4677110001
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
09.fm Seite 19 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsSpecial DetectorsRadio Fire Detection Wireless System
9-20 © Siemens Switzerland Ltd 2010
Type Order No.
SMF__ Manual call point
Radio manual call point for the radio fire detection system. Manual call point with indirect alarm actuation by breaking the glass and pressing the push button. The radio module is integrated in the base.The base SMF6120 and the manual call point SMF121 must be ordered separately.
Standard EN 54-11
Protection category IP43
Operating temperature -10... + 55 °C
Dimensions (W x H x D) 125 x 125 x 57 mm
Relative humidity L95 % (no condensation)
Color red‚ zRAL 3000
Approval
Data sheet 010087
Products to select from
SMF6120 See Page 9-20
V24069-Z112-A1 See Page 9-20
SMF121 See Page 9-21
SMF121 See Page 9-21
SMF__
SMF6120 Radio base
The radio base is battery-operated and can be mounted at every loca-tion within radio range. The radio base consists of a housing including radio electronics and antennas. The two 3.6 V batteries used are insert-ed here. The batteries must only be inserted in the base during commis-sioning (address allocation).The batteries V24069-Z112-A1 and the manual call point SMF121 must be ordered separately.
Supply voltage 2 x 3.6 V lithium batteries‚ separate-ly monitored
Transmitter/receiver antenna 2 (antenna diversity)
Transmitting power L5 mW ERP
Transmission distance max. 40 m in buildingmax. 200 m in open air
Channel width 25 kHz
Radio frequency 868... 870 MHz (SRD band)
S24218-F72-A1
V24069-Z112-A1 Lithium battery 3.6 V / 2.1 Ah
For the supply of the radio base SMF6120.
Dimensions (Ø x H) 14.5 x 50 mm
V24069-Z112-A1
09.fm Seite 20 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsSpecial DetectorsRadio Fire Detection Wireless System
9-21© Siemens Switzerland Ltd 2010
9
Type Order No.
SMF121 Manual call point
Manual call point with indirect alarm actuation labeled with Siemens‚ compatible with radio base SMF6120.The radio base SMF6120 must be ordered separately.
V24217-C1218-W200
SMF121 Manual call point
Manual call point with indirect alarm actuation without Siemens label‚ compatible with radio base SMF6120.The radio base SMF6120 must be ordered separately.
V24217-C1218-W100
S24217-G34-A1 Key
The key is used for manual call point SMF121.
Delivery unit 10 pieces
S24217-G34-A1
DZW1171 Radio test set
Field strength measurements can be carried out in the building to ensure reliable planning. Such measurements can be made using the mobile radio test set DZW1171.Position module A at the location of the radio gateway. It is now possi-ble to check the radio contact at the radio smoke detector position by means of module B. As long as the LED on module B lights up‚ the trans-mission of radio signals is ensured.Two 9 V lithium batteries (A5Q00004142) are needed and must be ordered separately.
BPZ:5762200001
A5Q00004142 Lithium brownstone battery 9 V / 1 Ah
For the supply of the detector testers‚ line tester‚ radio smoke detector etc.
Dimensions (W x H x D) 25 x 48 x 16 mm
Delivery unit 10 pieces
A5Q00004142
09.fm Seite 21 Mittwoch, 28. Juli 2010 8:51 08
+DC 24 V
Explosion-hazard area productsEx product overview
FDCIO223 input/output module “transponder” for the connection of the Ex components to C-NET
SB3 Shunt Zener diode barrier mounted together with installation set Z3I410 in housing DCA1191
Smoke detectorDO1101A-Exwide spectrum
Heat detectorsDT1101A-Ex/DT1102A-Ex
Manual call pointsDM1103/04(Ex)with label “avoid electrostatic charging”
Infrared fl ame detector DF1101-Ex
DB3 Alarm device
Alarm indicator FDAI92-Ex
Non explosion-hazard area
Explosion-hazard area
C-NET
To the sounder output of the fi re control panel
Line termination EOL22(Ex)in last detector
DC1192 input/output module as galvanic isolator between SynoLINE600 and Ex components
SynoLINE600or
+DC 24 V
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 32 28.05.10 16:58
Special ApplicationsExplosion-Hazard Area ProductsInterface to C-NET
9-23© Siemens Switzerland Ltd 2010
9
Type Order No.
FDCIO223 Input/output module 'Transponder'
For connection of collective fire detectors (GMT/conventional line‚ GMT/conventional line with shunt Zener diode barrier (SB3) for explo-sion-hazard areas). For monitored controls of e.g. smoke dampers‚ alarm devices‚ door magnets and extinguishing activation devices (adhere to country-specific instructions). Monitored signal input for status and alarm messages or for acknowledging technical status.The 2 input/outputs can be parameterized autonomously in each case as detector line collective‚ contact input‚ control output‚ control output and input as acknowledgement with selectable monitoring time frame. Status indication by LED.Transponder incl. 2 Transzorb diode 20 V‚ 8 resistors and 2 mounting feet for TS35 U-rail.
Power supply External input voltage 18... 32 VDC
Communication protocol FDnet/C-NET
Operating voltage FDnet/C-NET 12... 33 VDC
Detector line collective GMT Siemens/Cerberus‚ Synova conventional/SynoLINE300‚ collective/SynoLINE600 or similar
Control output 24 VDC ± 5 % / 2 A
EOL resistor 3.3 kT/680 T‚ 2.7 kT/560 T‚ 3.3 kT
Cable capacity 0.2... 1.5 mm2 (2.5 mm2)
Operating temperature -25... +60 °C
Storage temperature -30... +65 °C
Relative humidity L95 %
Color white‚ zRAL 9010/transparent matt
Protection category IP30IP65 with aux. housing FDCH221
System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720
Standard CEA GEI I-084‚ EN 54-17‚ EN 54-18
Dimensions (W x H x D) 132 x 90 x 24 mm
Data sheet 009168
Accessories TS35_122 U-railTS35_288 U-railFDCH221 Housing IP65
S24218-B102-A1
Accessories
FDCH221 Housing for input/output modules
Housing with seal for the mounting of the input/output modules for wet applications.The required screwed cable glands and back nuts M20 must be ordered separately.
Dimensions (W x H x D) 207 x 119 x 48 mm
Color white‚ zRAL 9010 / transparent matt
Protection category IP65
Accessories A5Q00004478 Screwed cable gland M20A5Q00004479 Back nut M20
S54312-F3-A1
09.fm Seite 23 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsExplosion-Hazard Area ProductsInterface to C-NET
9-24 © Siemens Switzerland Ltd 2010
Type Order No.
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
A5Q00004479 Back nut M20
Back nut to screwed cable gland M20 x 1.5.
Delivery unit 10 pieces
A5Q00004479
DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole
As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.
Cable capacity 1... 2.5 mm2
Delivery unit 50 pieces
BPZ:4942340001
EOL22(Ex) Line termination
End-of-line unit for collective detection lines or as end-of-line unit with-in explosion-hazard areas of zones 1 and 2.
BPZ:5162220001
09.fm Seite 24 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsExplosion-Hazard Area ProductsInterface to Collective Line SynoLINE600
9-25© Siemens Switzerland Ltd 2010
9
Type Order No.
DC1192-I__ Input/output module for galvanic isolation
The input/output module DC1192 for galvanic isolation (detection line coupler) between control unit of collective line SynoLINE600 and e.g. shunt Zener diode barrier with fire detectors for explosion-hazard areas (via SB3).The housing DCA1191‚ the terminal base DCB1192A and the electronic unit DCA1192A must be ordered separately.
Operating temperature -25... +70 °C
Protection category IP56
Data sheet 001571
Products to select from
DCA1191 See Page 9-25
DCB1192A See Page 9-25
DCA1192A See Page 9-25
DC1192-I__
DCA1191 Housing (empty)
Housing with cover for several applications. The housing offers six M20 cable feed-throughs for screwed cable glands and offers a higher pro-tection category.The screwed cable gland must be ordered separately.
Dimensions (W x H x D) 135 x 135 x 65 mm
Color white‚ zRAL 9010
Protection category IP56
Accessories A5Q00004478 Screwed cable gland M20
BPZ:4588560001
DCB1192A Terminal base for DC1192
The terminal base for the auto-addressable input/output module DC1192. The terminal base can be pre-installed together with the hous-ing DCA1191 to save time and money during installation.
Cable capacity 0.2... 2.5 mm2 / AWG 24... 14
Accessories DBZ1190-AA Micro terminal 0.5 mm2
BPZ:5084500001
DCA1192A Electronic unit for DC1192
Electronic unit for DC1192 input/output module is used in the Syno-LOOP fire detection system for the connection of fire detectors with collective/SynoLINE600 address (special detectorsor via shunt Zener diode barriers‚ detectors for explosion-hazard areas) or for the activation of alarm devices. The built-in isolator enables the fire control panel to localize short circuits and open lines. With the auto-addressable feature‚ no dip switch or punch card settings have to be made. The electronic unit is plugged into the housing just before com-missioning.The line termination elements are also included in the packaging.
Detection line current max. 5 mA
Detection line voltage 18... 22 VDC
Operating current control line max. 2 A‚ 60 W
Operating voltage external 18... 32 VDC
Quiescent current L45 mA
BPZ:5081200001
09.fm Seite 25 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsExplosion-Hazard Area ProductsInterface to Collective Line SynoLINE600
9-26 © Siemens Switzerland Ltd 2010
Type Order No.
EOL22(Ex) Line termination
End-of-line unit for collective detection lines or as end-of-line unit with-in explosion-hazard areas of zones 1 and 2.
BPZ:5162220001
Accessories
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
DBZ1190-AA Micro terminal 0.5 mm2‚ 4-pole
As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.
Cable capacity 0.28... 0.5 mm2
Delivery unit 50 pieces
BPZ:4677080001
09.fm Seite 26 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsExplosion-Hazard Area ProductsEx-Barrier
9-27© Siemens Switzerland Ltd 2010
9
Type Order No.
SB3 Shunt Zener diode barrier
This barrier is needed for an intrinsically safe installation in explosion-hazard areas connected to the in-/output module. This barrier restricts the electrical energy between non-intrinsically safe and intrinsically safe circuits. The installation has to be done according to the national safety regulations. The SB3 has to be mounted into the housing DCA1191 together with the Z3I410 installation set.Always install shunt Zener diode barriers outside explosion-hazard areas.
Operating voltage max. 28 VDC
Operating current max. 100 mA
Type Stahl 9001/00-280-100-101
Standard EN 50014 (IEC60079-0)/EN 50020 (IEC60079-11)
Data sheet 001222
BPZ:4837400001
DCA1191 Housing (empty)
Housing with cover for several applications. The housing offers six M20 cable feed-throughs for screwed cable glands and offers a higher pro-tection category.The screwed cable gland must be ordered separately.
Dimensions (W x H x D) 135 x 135 x 65 mm
Color white‚ zRAL 9010
Protection category IP56
Accessories A5Q00004478 Screwed cable gland M20
BPZ:4588560001
Z3I410 Installation set
One SB3 shunt Zener diode barrier may be mounted together with sup-port plate Z3I410 in housing DCA1191 with protection category IP56.
BPZ:4837660001
DBZ1190-AA Micro terminal 0.5 mm2‚ 4-pole
As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.
Cable capacity 0.28... 0.5 mm2
Delivery unit 50 pieces
BPZ:4677080001
Accessories
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
09.fm Seite 27 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsExplosion-Hazard Area ProductsPoint Detectors Ex-Series
9-28 © Siemens Switzerland Ltd 2010
Type Order No.
DO1101A-Ex Smoke detector‚ wide spectrum collective 'Ex'
For the early warning of smoke-forming‚ flaming fires and smoldering fires in explosion-hazard areas of zones 1 and 2.The base DB1101A must be ordered separately.
Operating voltage 17... 24 VDC
Quiescent current max. 100 μA
Operating temperature -25... +60 °C
Storage temperature -30... +75 °C
Relative humidity L95 %
Ex-classification II 2 G Ex ib IIC T4(-25 °C LTa L60 °C)
Dimensions (Ø x H) 115 x 51 mm (incl. base)
Color white‚ zRAL 9010
Standard for fire detectors EN54-7for explosion-hazard areasEN 50014 (IEC60079-0)/EN 50020 (IEC60079-11)
Protection category IP44
Data sheet 001469
BPZ:5008010001
DT1101A-Ex Heat detector collective 'Ex'
For the monitoring of explosion-hazard areas of zones 1 and 2 with a maximum ambient temperature of 50 °C. It is characterized by reliable response behavior‚ not only in the event of slow temperature rises‚ but also where the temperature rises are fast.The base DB1101A must be ordered separately.
Operating voltage 16... 24 VDC
Quiescent current max. 100 NA
Operating temperature -25... +50 °C
Storage temperature -30... +75 °C
Relative humidity L95 %
Ex-classification II 2 G Ex ib IIC T4(-25 °C LTa L50 °C)
Dimensions (Ø x H) 115 x 54.5 mm (incl. base)
Color white‚ zRAL 9010
Standard for fire detectors EN 54-5: A1Rfor explosion-hazard areasEN 50014 (IEC60079-0)/EN 50020 (IEC60079-11)
Protection category IP44
Data sheet 001469
BPZ:4852140001
09.fm Seite 28 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsExplosion-Hazard Area ProductsPoint Detectors Ex-Series
9-29© Siemens Switzerland Ltd 2010
9
Type Order No.
DT1102A-Ex Heat detector collective 'Ex'
For the monitoring of explosion-hazard areas of zones 1 and 2 with a maximum ambient temperature of 70 °C. It is the right heat detector for locations where large temperature fluctuations and high temperatures occur. It continuously measures the ambient temperature and reacts if defined maximum values are exceeded.The base DB1101A must be ordered separately.
Operating voltage 16... 24 VDC
Quiescent current max. 100 NA
Operating temperature -25... +70 °C
Storage temperature -30... +75 °C
Relative humidity L95 %
Ex-classification II 2 G Ex ib IIC T4(-25 °C LTa L70 °C)
Dimensions (Ø x H) 115 x 54.5 mm (incl. base)
Color white‚ zRAL 9010
Standard for fire detectors EN54-5: Bfor explosion-hazard areasEN 50014 (IEC60079-0)/EN 50020 (IEC60079-11)
Protection category IP44
Data sheet 001469
BPZ:4852270001
DB1101A Base for collective detector series
Base made of impact and scratch-proof plastic and environmentally safe materials. Integral rubber gasket to protect against draught‚ dirt and dripping water from above. Screwless terminals for easy installa-tion. Space for auxiliary terminals as micro terminals (0.5 mm2) and connection terminals (2.5 mm2). Fits all standard flush-mounted boxes from 55 to 80 mm.
Cable capacity 0.2... 2.5 mm2
Dimensions (Ø x H) 115 x 21 mm
Color white‚ zRAL 9010
Data sheet 001035
Further accessories DBZ1191 Base attachment for sur-face mountingDBZ1190-AA Micro terminal 0.5 mm2
DBZ1190-AB Connection terminal 2.5 mm2
BPZ:4863650001
Accessories
DBZ1191 Base attachment for surface mounting
For surface wiring feed and provision of more wire loop space. Bases are mounted using a spring-loaded catch.
Dimensions (Ø x H) 116 x 22 mm
Color white‚ zRAL 9010
Delivery unit 5 pieces
BPZ:4540830001
09.fm Seite 29 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsExplosion-Hazard Area ProductsPoint Detectors Ex-Series
9-30 © Siemens Switzerland Ltd 2010
Type Order No.
DBZ1190-AA Micro terminal 0.5 mm2‚ 4-pole
As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.
Cable capacity 0.28... 0.5 mm2
Delivery unit 50 pieces
BPZ:4677080001
DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole
As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.
Cable capacity 1... 2.5 mm2
Delivery unit 50 pieces
BPZ:4942340001
09.fm Seite 30 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsExplosion-Hazard Area ProductsInfrared Flame Detector Ex-Series
9-31© Siemens Switzerland Ltd 2010
9
Type Order No.
DF11Ex__ Infrared flame detector collective 'Ex'
Connectable to collective systems. Connection to the detection line via the input/output module for galvanic isolation. Infrared flame detector for explosion-hazard areas of zones 1 and 2‚ for inside and outside applications.The Stabex HF test lamp is used to make a performance check of the infrared flame detector. It must be held in front of the detector.The detector unit DF1101-Ex and the base DFB1190 must be ordered separately.
Dimensions (W x H x D) 135 x 135 x 77 mm
Operating temperature -35... +70 °C
Storage temperature -40... +75 °C
Relative humidity L95 %
Ex-classification II 2 G Ex ib IIC T4(-35 °C LTa L70 °C)
Color white‚ zRAL 9010
Standard EN 54-10 for flame detectorEN 50014 (IEC60079-0)/EN 50020 (IEC60079-11)for explosion-hazard areas
Protection category IP67
Data sheet 001744
Products to select from
DF1101-Ex See Page 9-31
DFB1190 See Page 9-32
DF11Ex__
DF1101-Ex Infrared flame detector unit collective 'Ex'
Flame detector DF1101-Ex intrinsically safe for Ex-protected areas. The infrared flame detector DF1101-Ex is designed to the explosion protec-tion category 'Intrinsic safety' Ex i.One sensor measures the hot carbon dioxide in a specific flame wave-length; the two other sensors simultaneously measure the interference radiation in other wavelengths. With intelligent signal processing through fuzzy algorithms and wavelet analysis‚ the DF1101-Ex achieves excellent detection reliability while maintaining the highest immunity to interference radiation and sunlight. In order to safeguard against a possible decision emergency‚ the detector contains an additional emer-gency activation channel.It is suitable for chemical production plants‚ oil refineries‚ propane and butane filling installations‚ for all explosion-hazard areas in which flam-ing fires involving carbonaceous materials could be expected.The base DFB1190 must be ordered separately.
Dimensions (W x H x D) 135 x 135 x 32 mm
Operating voltage 16... 28 VDC
Quiescent current 0.5 mA
BPZ:5166750001
09.fm Seite 31 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsExplosion-Hazard Area ProductsInfrared Flame Detector Ex-Series
9-32 © Siemens Switzerland Ltd 2010
Type Order No.
DFB1190 Base for infrared flame detectors DF119x
The base comprises a robust‚ glass fiber-reinforced‚ plastic housing which provides the required isolated installation of the detector. The base contains screwless terminals‚ chokes to protect against EMI‚ a plug attachment for the detector‚ six M20 cable entry possibilities.
Cable capacity 0.2... 1.5 mm2 (AWG24... 15)
Dimensions (W x H x D) 135 x 135 x 45 mm
Color white‚ zRAL 9010
Accessories A5Q00004478 Screwed cable gland M20
BPZ:5165360001
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
StabexHF Test lamp for flame detectors 'Ex'
The test lamp is used to carry out a performance check of intrinsically safe flame detectors in explosion-hazard areas of zones 1 and 2.
Operating temperature -20... +40 °C
Storage temperature -20... +40 °C
Battery capacity 2 x Alkali battery 1.5 V‚ single-cell UM1
Ex-classification II 2 G Ex ib e IIC T4
Protection category IP65
Data sheet AlgoRex‚ Synova‚ Sinteso -> 000252Cerberus PRO -> A6V10203222
BPZ:4620910001
09.fm Seite 32 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsExplosion-Hazard Area ProductsManual Call Points
9-33© Siemens Switzerland Ltd 2010
9
Type Order No.
DM1103(Ex)__ Collective manual call point (double action) for explosion-hazard areas
For immediate manual actuation of an alarm. For indoor and outdoor application‚ equally suited for wet‚ humid and dusty areas. For surface- and recess-mounted feed lines in easily accessible places.Indirect alarm actuation by pushing in the glass plate and pressing the push button. To replace the glass plate‚ open the housing door with the key. The push button must be reset before closing the door again.The housing DMA1192-AA and the switching unit DMA1103D must be ordered separately.
Standard EN54-11
Protection category IP54 (IP65 with protection seal and screwed cable gland)
Operating temperature -25... +70 °C
Dimensions (W x H x D) 134 x 134 x 43 mm
Data sheet A6V10236643
Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20A5Q00006735 Locking plug M20(1 hole)A5Q00010055 Locking plug M20(2 holes)
Products to select from
DMA1192-AA See Page 9-33
DMA1103D See Page 9-33
DM1103(Ex)__
DMA1192-AA Housing red‚ with glass and key
Manual call point housing for the switching units DMA110xD.
Color red‚ zRAL 3000
BPZ:5222870001
DMA1103D Switching unit collective (double action)
The electronic unit is a double action device; just break the glass and press the button to activate an alarm. For connection to collec-tive/SynoLINE600 detection lines. An LED always indicates the status of the manual call point. The electronic unit is plugged into the housing during commissioning.Attach the enclosed sticker 'avoid electrostatic charging' when the switching unit is used in explosion-hazard areas only.
Operating voltage 16... 26 VDC
Operating current 60... 100 mA
Terminal block min. 0.28... 1.5 mm2
A5Q00004470
09.fm Seite 33 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsExplosion-Hazard Area ProductsManual Call Points
9-34 © Siemens Switzerland Ltd 2010
Type Order No.
DM1104(Ex)__ Collective manual call point (single action) for explosion-hazard areas
For immediate manual actuation of an alarm. For indoor and outdoor application‚ equally suited for wet‚ humid and dusty areas. For surface- and recess-mounted feed lines in easily accessible places.Direct alarm actuation by pushing in the glass plate. To replace the glass plate‚ open the housing door with the key‚ upon closing the door the button is reset.The housing DMA1192-AA and the switching unit DMA1104D must be ordered separately.
Standard EN 54-11
Protection category IP54 (IP65 with protection seal and screwed cable gland)
Operating temperature -25... +70 °C
Dimensions (W x H x D) 134 x 134 x 43 mm
Data sheet A6V10236643
Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20A5Q00006735 Locking plug M20(1 hole)A5Q00010055 Locking plug M20(2 holes)
Products to select from
DMA1192-AA See Page 9-34
DMA1104D See Page 9-34
DM1104(Ex)__
DMA1192-AA Housing red‚ with glass and key
Manual call point housing for the switching units DMA110xD.
Color red‚ zRAL 3000
BPZ:5222870001
DMA1104D Switching unit collective (single action)
The electronic unit is a single action device by smashing in the glass plate to activate an alarm. For connection to collective/SynoLINE600 detection lines. An LED always indicates the status of the manual call point. The electronic unit is plugged into the housing during commis-sioning.Attach the enclosed sticker 'avoid electrostatic charging' when the switching unit is used in explosion-hazard areas only.
Operating voltage 16... 26 VDC
Operating current 60... 100 mA
Terminal block min. 0.28... 1.5 mm2
A5Q00005925
09.fm Seite 34 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsExplosion-Hazard Area ProductsManual Call Points
9-35© Siemens Switzerland Ltd 2010
9
Type Order No.
Accessories
DMZ1197-AD Protection seal
Protects the manual call point in wet applications.The seal improves the manual call point housing's protection category.
Delivery unit 5 pieces
BPZ:5470680001
DMZ1197-AC Protective cover
Protects the manual call point from unintentional glass break. Protec-tive cover can be easily fitted directly in the housing cover.
Delivery unit 5 pieces
BPZ:5223550001
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
A5Q00006735 Locking plug M20 x 1.5 (1 hole)
For manual call point housings and surface-mounted feed lines in the manual call point housing.For applications in dry rooms.
Color red‚ zRAL 3000
Delivery unit 10 pieces
A5Q00006735
A5Q00010055 Locking plug M20 x 1.5 (2 holes)
For manual call point housings and surface-mounted feed lines in the manual call point housing.For applications in dry rooms.
Color red‚ zRAL 3000
Delivery unit 10 pieces
A5Q00010055
09.fm Seite 35 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsExplosion-Hazard Area ProductsAlarm Indicators Ex-Series
9-36 © Siemens Switzerland Ltd 2010
Type Order No.
FDAI92-Ex Alarm indicator - Surface for explosion-hazard areas
The alarm indicator is connected in parallel to automatic fire detectors in order to indicate quickly the source of an alarm signal from detectors that are not easily accessible or visible. The alarm indicator contains an indicator lamp unit with one or two LEDs. They light up as soon as a connected fire detector gives an alarm.Screwless connection terminals.The alarm indicator is suitable for wall mounting.
Operating voltage 1.5 VDC
Operating current max. 35 mA (continuous)
Operating temperature -25... +80 °C
Relative humidity L95 %
Terminals max. 1.5 mm2
Ex-classification 'simple apparatus'acc. to EN 50020 § 5.4Ex ib IIC T4 (Ta L70 °C)
Dimensions (W x H x D) 85 x 85 x 28 mm
Color white‚ zRAL 9010
Protection category IP40
Data sheet A6V10276518
Accessories AI330 Adapter frame
S54370-F4-A1
AI330 Adapter frame for alarm indicator
By means of the additional frame‚ the alarm indicator can also be used for surface laid conduits or ducts‚ to increase the loop space and as an adapter for different makes of the box.
Dimensions (W x H x D) 85 x 85 x 16 mm
BPZ:3169430001
FDAI93-Ex Alarm indicator - Flush
Made of transparent plastic‚ the FDAI93-Ex alarm indicator is suitable for installation in door frames‚ switching panels‚ ceiling voids or special housings. The 22.5 mm Ø mounting hole is drilled by the system own-er. The holder must be fitted with the insulating cap for safety. For installation in humid rooms the DCA1191‚ DJZ1193 housings as well as a washer are available (must be ordered separately). Up to 4 alarm indi-cators can be built into the housing DCA1191.
Operating voltage 1.5 VDC
Operating current max. 20… 30 mA (continuous)
Operating temperature -25... +80 °C
Ex-classification 'simple apparatus'acc. to EN 50020 § 5.4Ex ib IIC T4 (Ta L70 °C)
Color transparent plastic
Dimensions (Ø x D) 26 x 51 mm
Protection category IP56 with DCA1191IP65 with DJZ1193
Data sheet A6V10276518
Accessories DCA1191 Housing (IP56)BPZ:2473130001 Washer
Further accessories DJZ1193 Housing (IP65)
S54370-F6-A1
09.fm Seite 36 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsExplosion-Hazard Area ProductsAlarm Indicators Ex-Series
9-37© Siemens Switzerland Ltd 2010
9
Type Order No.
DCA1191 Housing (empty)
Housing with cover for several applications. The housing offers six M20 cable feed-throughs for screwed cable glands and offers a higher pro-tection category.The screwed cable gland must be ordered separately.
Dimensions (W x H x D) 135 x 135 x 65 mm
Color white‚ zRAL 9010
Protection category IP56
Accessories A5Q00004478 Screwed cable gland M20
BPZ:4588560001
BPZ:2473130001 Washer
Washer for alarm indicator model recess mounting. The washer can be used for applications in humid rooms.
Dimensions (Ø x D) 23 x 1 mm
BPZ:2473130001
A5Q00004478 Screwed cable gland M20 x 1.5
The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.
Delivery unit 10 pieces
A5Q00004478
DJZ1193 Alarm indicator housing incl. washer
For surface mounting in wet areas.1 alarm indicator can be built into the housing.
Dimensions (W x H x D) 87 x 87 x 64 mm
Color white‚ zRAL 9010
Protection category IP65
BPZ:5302950001
MVH1 Mounting bracket
For mounting of the alarm indicator housing DJZ1193 and detectors in hollow floors.
Length 0.29... 0.42 m (pipe clamp 1/2")
BPZ:3496190001
09.fm Seite 37 Mittwoch, 28. Juli 2010 8:51 08
Special ApplicationsExplosion-Hazard Area ProductsAlarm Device
9-38 © Siemens Switzerland Ltd 2010
Type Order No.
DB3 Alarm device for explosion-hazard areas of zones 1 and 2
The flameproof audible alarm device is intended for the use in poten-tially explosive atmospheres. It has been designed with high ingress protection to cope with harsh environmental conditions.
Operating voltage 12... 48 VDC
Alarm current max. 380 mA
Volume at 24 V and 1 m 101... 115 dB
Number of sounds 27
Operating temperature -20... +55 °C
Ex-classification II 2 G Ex d IIC T5(-20 °C LTa L55 °C)
Terminals 6 x 2.5 mm2
Dimensions (Ø x D) 137 x 184 mm
Color red‚ anti-static‚ UV stable‚ glass rein-forced polyester
Standard CENELEC‚ EN 50014‚ 18
Protection category IP66/67
Data sheet 009001
BPZ:5757970001
09.fm Seite 38 Mittwoch, 28. Juli 2010 8:51 08
Special Equipment
Cutting-edge technology – for all security and safety needsFire and security products from Siemens are the obvious choice because they are continually setting new standards in terms of quality, design, reli-ability, value for money and availability. For more than 150 years now we have been developing solutions for all types of problems, applications and needs, from fi re detection through to alert and evacuation systems, consist-ing of everything from simple conventional systems to complex addressable networks. Over the years, our products and components have passed every test to which they have been subjected with fl ying colors.
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 34 28.05.10 16:58
Special EquipmentTest EquipmentDetector Tester
10-2 © Siemens Switzerland Ltd 2010
Type Order No.
DX791 Detector exchanger
Insertion and removal of all Cerberus PRO point detectors. Equipped with a vacuum cup for insertion and removal of dust cap.Compatible with the telescope rods FDUM291/292.
Data sheet A6V10203222
Accessories FDUM291 Telescope rodFDUM292 Telescope rod
S54319-F6-A1
RE6 Detector tester for smoke detectors
The detector tester (delivered with bellow DZZ1190) is placed over the detector and given a brief push to release the test gas and so simulate the presence of fire aerosols. The detector responds quickly and actu-ates an alarm. The test gas is free of halogenated chlorofluorocarbons (CFCs). It is not combustible.The extension rod FDUM291/292 and the test gas can REF8‚ REF8-S must be ordered separately.
Data sheet AlgoRex‚ Synova -> 001164Sinteso -> 007228Cerberus PRO -> A6V10203222
Accessories FDUM291 Telescope rodFDUM292 Telescope rod
Further accessories RG320 Bellow
BPZ:3680300001
REF8 Test gas can for smoke detectors
REF8 has been developed as an environment-friendly test gas for the testing of smoke detectors. It fulfills severe environmental regulations. REF8 can be used in the temperature range of 0... +40 °C in dry or in humid environments.Use only together with detector tester RE6.
Delivery unit 6 pieces
A5Q00011687
REF8-S Test gas can for smoke detectors
REF8-S has been developed as environment-friendly test gas for the testing of smoke detectors. It fulfills severe environmental regulations. REF8-S can be used in the temperature range of -20... +40 °C in dry or in humid environments. REF8-S remains measurable longer than REF8‚ and is used for detectors having a longer signal evaluation time.Use only together with detector tester RE6.
Delivery unit 6 pieces
A5Q00011688
10.fm Seite 2 Mittwoch, 28. Juli 2010 8:54 08
Special EquipmentTest EquipmentDetector Tester
10-3© Siemens Switzerland Ltd 2010
10
Type Order No.
RG320 Bellow for RE6
The bellow is fitted to the RE6 to fit all SynoLINE300 point detectors in an ideal way.
BPZ:5166880001
RE6T Detector tester for heat detectors
This detector tester contains a hot air generator. For the performance check‚ the tester is pushed over the detector. The hot air released‚ heats the detector and so actuates an alarm.Forbidden in electrical switching stations or areas where there is a danger of explosion!The extension rod FDUM291/292 must be ordered separately.
Mains voltage 220 VAC/50… 60 Hz‚ z300 W
Operating temperature 0… +40 °C
Data sheet AlgoRex‚ Synova -> 001164Sinteso -> 007228Cerberus PRO -> A6V10203222
Accessories FDUM291 Telescope rodFDUM292 Telescope rod
BPZ:3680270001
RE7T Solo461 Heat detector tester kit
The detector tester contains a hot air generator and is battery-powered. The detector tester will automatically start testing when infrared beam in cup is broken.Forbidden in electrical switching stations or areas where there is a danger of explosion!The adapter RE7T-A and the extension rod FDUM291/292 must be ordered separately.
Relative humidity L95 %
Operating temperature 5... +45 °C
Storage temperature -10… +50 °C
Data sheet A6V10252901
Accessories RE7T-A Solo719 Adapter for FDUM29xFDUM291 Telescope rodFDUM292 Telescope rod
S54370-S3-A1
10.fm Seite 3 Mittwoch, 28. Juli 2010 8:54 08
Special EquipmentTest EquipmentDetector Tester
10-4 © Siemens Switzerland Ltd 2010
Type Order No.
Accessories
RE7T-A Solo719 Adapter for FDUM29x
Adapter from heat detector tester RE7T to the telescope rods FDUM29x.
Data sheet A6V10252901
S54370-N4-A1
Accessories
FDUM291 Telescope rod
The three-part telescope with tri-oval tubes serves as an extension for the detector exchanger‚ detector testers and other applications up to 5 m.
Length 1.6 m extendable to 4.2 m
Color yellow‚ black
A5Q00004996
10.fm Seite 4 Mittwoch, 28. Juli 2010 8:54 08
Special EquipmentTest EquipmentDetector Tester
10-5© Siemens Switzerland Ltd 2010
10
Type Order No.
FDUM292 Telescope rod
The stable‚ four-part telescope with round tubes serves as an extension for the detector exchanger‚ detector testers and other applications up to 8 m.
Length 2.1 m extendable to 7.3 m
Color yellow‚ black
A5Q00004997
DZB1191 Detector base tester
The DB1191 base tester is handy and simple means of testing the detection line and detector base connections. The base tester is insert-ed in the detector base like a detector. All AlgoRex DS11 bases can be tested during installation either individually or consecutively after installation is completed.The DBZ1191 can test for open lines‚ short circuit‚ earth leakages‚ polar-ity and alarm indicator connection.
Data sheet 001049
BPZ:4680660001
10.fm Seite 5 Mittwoch, 28. Juli 2010 8:54 08
Special EquipmentTest EquipmentDetector Tester for Special Detectors
10-6 © Siemens Switzerland Ltd 2010
Type Order No.
LE3 Test lamp for flame detectors
The test lamp is used for testing the operation of all flame detectors (non explosion-hazard areas). It is supplied with all the necessary acces-sories in a suitable carrying case (incl. charger‚ without battery). The carrying case also provides a means of storing the test lamp free of dust.The battery FA2003-A1 must be ordered separately.
Operating temperature -20... +45 °C
Storage temperature -20... +45 °C
Battery capacity 1 x 12 V / 7 Ah
Data sheet AlgoRex‚ Synova‚ Sinteso -> 000252Cerberus PRO -> A6V10203222
BPZ:3669510001
StabexHF Test lamp for flame detectors 'Ex'
The test lamp is used to carry out a performance check of intrinsically safe flame detectors in explosion-hazard areas of zones 1 and 2.
Operating temperature -20... +40 °C
Storage temperature -20... +40 °C
Battery capacity 2 x Alkali battery 1.5 V‚ single-cell UM1
Ex-classification II 2 G Ex ib e IIC T4
Protection category IP65
Data sheet AlgoRex‚ Synova‚ Sinteso -> 000252Cerberus PRO -> A6V10203222
BPZ:4620910001
FDLU291 Adjustment device set for linear smoke detector
The optics of the linear smoke detector can be efficiently adjusted to the reflector by single-handed alignment via the adjustment device.Box with adjustment device‚ alarm test filter‚ visor‚ magnet‚ spiral cable‚ MC-Link cable‚ and battery 9 V‚ 0.5 Ah.
A5Q00004905
RE10 Detector tester for linear smoke detectors
For performance check of linear smoke detector. In compliance with the type of detector to be tested‚ the alarm test filter is inserted in the detector tester.The detector tester is then held in front of the optical parts of the detec-tor (i.e. into the infrared ray). The detector reacts after a few seconds.Alarm test filter contained in FDLU291 or TF04 must be ordered sepa-rately.
Data sheet Synova‚ AlgoRex -> 001164Sinteso -> 007228Cerberus PRO -> A6V10203222
Accessories TF04 Alarm test filterFDUM291 Telescope rodFDUM292 Telescope rod
BPZ:3685190001
10.fm Seite 6 Mittwoch, 28. Juli 2010 8:54 08
Special EquipmentTest EquipmentDetector Tester for Special Detectors
10-7© Siemens Switzerland Ltd 2010
10
Type Order No.
TF04 Alarm test filter (Absorption 77 %)
Alarm test filter for detector tester RE10.
BPZ:4931090001
10.fm Seite 7 Mittwoch, 28. Juli 2010 8:54 08
Special EquipmentTest EquipmentLine Tester
10-8 © Siemens Switzerland Ltd 2010
Type Order No.
FDUL221 Line tester
The line tester is a universal device for the testing of installed FDnet/C-NET fire detection lines‚ when no control unit has been connected yet. For troubleshooting for electricians‚ installers or service technicians.Different functions can be polled‚ e.g. number of devices found‚ number and place of line errors found‚ short circuit‚ open line‚ ground fault with conductor(s)‚ scrolling from detector to detector‚ with indica-tion of type and serial number etc. Update of the device software (Firmware) via PC possible.Power supply via battery or mains adapter.Line tester incl. line connection set FDUL221-A and power supply set FDUL221-B.
Operating voltage min. 10‚ max. 30 VDCBattery 2 x 9 VMains adapter 240 VAC / 24 VDC‚ 624 mA
Detection line voltage 32 VDC -> FDnet (FS20‚ AlgoRex)28 VDC -> FDnet (SIGMASYS)32 VDC -> C-NET (FS720)
Current consumption depending on number of devices and display illumination
Operating temperature -25... +40 °C
Storage temperature -30... +75 °C(-25... +60 °C with battery)
Relative humidity L95 % (no condensation)
Data sheet Sinteso -> 007228Cerberus PRO -> A6V10203222
A5Q00004397
A5Q00004142 Lithium brownstone battery 9 V / 1 Ah
For the supply of the detector testers‚ line tester‚ radio smoke detector etc.
Dimensions (W x H x D) 25 x 48 x 16 mm
Delivery unit 10 pieces
A5Q00004142
10.fm Seite 8 Mittwoch, 28. Juli 2010 8:54 08
Special EquipmentInterfaceAdapter for C-NET Devices
10-9© Siemens Switzerland Ltd 2010
10
Type Order No.
FDUZ221 MCL USB adapter
The MCL USB adapter is an interface converter for USB to MC-Link. It can be used to connect FDnet/C-NET devices to a PC using a serial protocol (MCL). The adapter is used for the firmware update or for operation. The adapter is used e.g. for floor repeater display FT2010-A1‚ floor repeater terminal FT2010-A1‚ line tester FDUL221 etc. (in the future other FDnet/C-NET devices possible).The MC-Link cable‚ the USB cable (1.8 m) and a CD with USB driver soft-ware are included.
Power supply via USB
Interface USB 2.0/1.1MC-Link
Operating temperature -10… +55 °C
Storage temperature -20… +60 °C
Relative humidity L95 %
Dimensions (W x H x D) 100 x 30 x 54 mm
Protection category IP30
Data sheet Sinteso -> A6V10084591Cerberus PRO -> A6V10203222
A5Q00020131
10.fm Seite 9 Mittwoch, 28. Juli 2010 8:54 08
081031_Product_Catalog_Innen_07lay.indd 34 24.07.09 18:11
Batteries
11-1© Siemens Switzerland Ltd 2010
11
Type Order No.
FA2003-A1 Battery (12 V‚ 7 Ah‚ VDS)
Rechargeable‚ sealed lead-acid battery for emergency power supply.2 batteries must be ordered (system voltage 24 V).
Dimensions (W x H x D) 151 x 94 x 65 mm
A5Q00019353
FA2004-A1 Battery (12 V‚ 12 Ah‚ VDS)
Rechargeable‚ sealed lead-acid battery for emergency power supply.2 batteries must be ordered (system voltage 24 V).
Dimensions (W x H x D) 151 x 95 x 98 mm
A5Q00019354
FA2005-A1 Battery (12 V‚ 17 Ah‚ VDS)
Rechargeable‚ sealed lead-acid battery for emergency power supply.2 batteries must be ordered (system voltage 24 V).
Dimensions (W x H x D) 181 x 167 x 77 mm
A5Q00019677
FA2006-A1 Battery (12 V‚ 26 Ah‚ VDS)
Rechargeable‚ sealed lead-acid battery for emergency power supply.2 batteries must be ordered (system voltage 24 V).
Dimensions (W x H x D) 166 x 125 x 177 mm
A5Q00019356
FA2007-A1 Battery (12 V‚ 45 Ah‚ VDS)
Rechargeable‚ sealed lead-acid battery for emergency power supply.2 batteries must be ordered (system voltage 24 V).
Dimensions (W x H x D) 197 x 170 x 165 mm
A5Q00022897
11.fm Seite 1 Mittwoch, 28. Juli 2010 8:58 08
Batteries
11-2 © Siemens Switzerland Ltd 2010
Type Order No.
FA2008-A1 Battery (12 V‚ 65 Ah‚ VDS)
Rechargeable‚ sealed lead-acid battery for emergency power supply.2 batteries must be ordered (system voltage 24 V).
Dimensions (W x H x D) 348 x 178 x 167 mm
A5Q00019357
FA2009-A1 Battery (12 V‚ 100 Ah‚ VDS)
Rechargeable sealed lead-acid battery for emergency power supply.2 batteries must be ordered (system voltage 24 V).
Dimensions (W x H x D) 305 x 212 x 168 mm
A5Q00023101
11.fm Seite 2 Mittwoch, 28. Juli 2010 8:58 08
Spare PartsFire Control Panels FC72x and Operating Terminals FT724‚ Printers
12-1© Siemens Switzerland Ltd 2010
12
Type Order No.
SV 24V-150W Power supply (150 W)
Power supply (150 W) without accessories.Use as spare part.
V24230-Z6-A4
FHA7201-A3 Cover cap (Cerberus)
Cover with Cerberus label.Use as spare part only.
S54400-B77-A1
FHA7202-A3 Cover cap (without print)
Cover without print.Use as spare part only.
S54400-B74-A1
FCM7210-Z3 Operating add-on
Operating add-on (complete base) without accessories.Use as spare part only.
S54400-F76-A1
FCM7211-Y3 Operating add-on (2xLED ind.)
To update 48 LED display groups‚ with one red and one yellow LED each.Can be inserted in all empty housings.Inclusive cables and screws for installation.
Dimensions (W x H x D) 427 x 200 x 25 mm
S54400-F75-A1
12.fm Seite 1 Mittwoch, 28. Juli 2010 8:59 08
Spare PartsFire Control Panels FC72x and Operating Terminals FT724‚ Printers
12-2 © Siemens Switzerland Ltd 2010
Type Order No.
FCM7212-Y3 Operating add-on (4xLED ind.)
To update 96 LED display groups‚ with one red and one yellow LED each.Can be inserted in all empty housings.Inclusive cables and screws for installation.
Dimensions (W x H x D) 427 x 200 x 25 mm
S54400-F88-A1
A5Q00017619 Thermo printer rolls for Custom Plus-S-0004
Replacement printer rolls (10 rolls) for event printer FTO2001-A1.Use as spare part.
Delivery unit 10 pieces
A5Q00017619
A5Q00023963 Typewriter ribbon
Genuine Fujitsu CA02374-C104 black fabric impact printer ribbon designed for the Fujitsu DL3750+ matrix printer.
Color black
A5Q00023963
12.fm Seite 2 Mittwoch, 28. Juli 2010 8:59 08
Spare PartsConventional Fire Control Panels FC10
12-3© Siemens Switzerland Ltd 2010
12
Type Order No.
FCA1001 Line extension card 4-zones A6E60500020
FCA1007-B Add-on line card
To provide line continuity with diode bases according to British Stand-ard BS5839 Pt1. One unit per 2 lines.Use as spare part.
A6E60500027
FCA1009-E EVAC module
Evacuation control module. Mounts on FC1008-E.
S54380-B11-A1
FCA1013 Universal accessory bag
Consists of:2 EOL (FCE1002) for sounder control lines12 EOL resistors 3.9 kT3 cable binder1 LED diffuser base (16 pins)1 LED diffuser base (1 pin)1 Allen key 3 mm for M4 screws5 eco-fix screws M3x54 Allen screws M4x124 stainless Allen screws M4x124 O-ring 2.90 x 1.783 fuses (315 mA‚ 630 mA‚160 mA)6 mini jumpers 2.54 mm
Accessories FCE1003-B EOL elementFCE1004-F EOL element
A6E60500068
FCE1001 EOL resistor 3.9 kT (set of 10 pcs.) A6E60500031
FCE1003-B EOL element for head removal monitoring A6E60500033
FCE1002 Termination element‚ control line
End-of-line for sounder control lines‚ as spare part.
A6E60500032
FCH1002 Cover for the FC1002-A‚ -B‚ -C
A6E60500035
FCH1004 Cover for the FC1004-A‚ -B‚ -C
A6E60500036
12.fm Seite 3 Mittwoch, 28. Juli 2010 8:59 08
Spare PartsConventional Fire Control Panels FC10
12-4 © Siemens Switzerland Ltd 2010
Type Order No.
FCH1004-E Cover for the FC1004-E
A6E60500037
FCH1008 Cover for the FC1008-A‚ -B‚ -C
A6E60500038
FCH1008-D Cover for the FC1008-D A6E60500039
FCH1008-E Cover for the FC1008-E S54380-F10-A1
FCH1012 Cover for the FC1012-A‚ -B‚ -C
A6E60500043
FCM1002 Main board 2-zones S54380-C8-A1
FCM1004 Main board 4-zones S54380-C9-A1
FCM1004-E FCM1004-E Main board 4 zone NL S54380-C9-A10
FCM1008 Main board for 8-zone units S54380-C1-A10
FCM1008-E FCM1008-E Main board 8 zone NL S54380-C1-A30
FCM1008-D FCM1008-D Main board 8 zone CH S54380-C1-A20
FCP1002 Transformer for 2/4-zone units
The transformer is delivered with mains connecting terminal.
S54390-N12-A1
12.fm Seite 4 Mittwoch, 28. Juli 2010 8:59 08
Spare PartsExtinguishing Control Panels XC10
12-5© Siemens Switzerland Ltd 2010
12
Type Order No.
XCM1002 Main board
Main board for XC10‚ as spare part
S54390-A4-A1
FCP1004-E Power supply 3.5 A
Power supply 3.5 A. Spare part for XC10.
A6E60500054
XCH1001-A Cover set
Cover set for XC1001-A‚ as spare part
S54390-B9-A1
XCH1003-A Cover set
Cover set for XC1003-A‚ as spare part
S54390-B10-A1
XCH1005-A Cover set
Cover set for XC1005-A‚ as spare part
S54390-B11-A1
XCA1002-1 Display adapter
Display adapter‚ as spare part
S54390-B7-A1
XCA1002-2 Display adapter
Display adapter‚ as spare part
S54390-B8-A1
12.fm Seite 5 Mittwoch, 28. Juli 2010 8:59 08
Spare PartsManual Call Points
12-6 © Siemens Switzerland Ltd 2010
Type Order No.
FDMG291 Replacement glass
Replacement glass for manual call point housings FDMH291-x.
Delivery unit 10 pieces
A5Q00002122
FDMK291 Cover with key
Spare key with call point front for manual call point housings FDMH291-x.
A5Q00001643
DMZ1196-AC Spare glass neutral
Easy to replace spare glass for the manual call point housings DMA1192-x‚ FDMH29x-x. The spare glass is neutral and has no marks.
Delivery unit 10 pieces
BPZ:4942050001
DMZ1195 Spare key
The spare key is used for all manual call point housings DMA1192-xx‚ FDMH293-x.
Delivery unit 10 pieces
BPZ:4851910001
FDMG295 Glass plate neutral
Glass plate for manual call points FDM225-RG‚ FDM226-RG‚ FDM1101-RG and FDM1101A-RG.Use as spare part.
Delivery unit 5 pieces
A5Q00013442
FDMP295 Plastic element neutral
Plastic element for manual call points FDM225-RP‚ FM226-RP‚ FDM1101-RP and FDM1101A-RP.Use as spare part.
Delivery unit 5 pieces
A5Q00013445
12.fm Seite 6 Mittwoch, 28. Juli 2010 8:59 08
Spare PartsManual Call Points
12-7© Siemens Switzerland Ltd 2010
12
Type Order No.
FDMK295 Spare key
Key for manual call points FDM225‚ FDM226‚ FDM1101 and FDM1101A.Use as spare part.
Delivery unit 10 pieces
A5Q00013448
12.fm Seite 7 Mittwoch, 28. Juli 2010 8:59 08
Spare PartsInput Modules‚ Input/Output Modules‚ Alarm Indicator
12-8 © Siemens Switzerland Ltd 2010
Type Order No.
FDCM291 Mounting feet for in-/output modules
Installation in range of the in-/output modules with mounting feet onto top U-rail TS35.Use as spare part.
Delivery unit 25 pieces
A5Q00003855
BPZ:3048160001 Insulating cap for alarm indicators
Use as spare part.
Delivery unit 20 pieces
BPZ:3048160001
12.fm Seite 8 Mittwoch, 28. Juli 2010 8:59 08
Spare PartsTest Equipment
12-9© Siemens Switzerland Ltd 2010
12
Type Order No.
FDLU291 Adjustment device for FDLU291
Adjustment device use only as spare part.
A5Q00006540
FDUD292-A Adapter cable
MC-Link cable from detector exchanger and tester to the in-/output modules‚ to the linear smoke detector and other devices (audio stereo cable 1.5 m with direct and bent stereo jack 3.5 mm).Use as spare part for FDUD292‚ FDUD293‚ FDUZ221.
A5Q00004990
A5Q00009786 Adapter with lever‚ screw and nut incl. attachment and bushing screw
Use as spare part to the telescope rods FDUM291 and FDUM292.
A5Q00009786
A5Q00009787 Lever with screw and nut
Use as spare part to the telescope rods FDUM291 and FDUM292.
A5Q00009787
A5Q00009788 Small flap with screw and nut
Use as spare part to the telescope rod FDUM291.
A5Q00009788
A5Q00009789 Large flap with screw and nut
Use as spare part to the telescope rod FDUM291.
A5Q00009789
12.fm Seite 9 Mittwoch, 28. Juli 2010 8:59 08
Spare PartsTest Equipment
12-10 © Siemens Switzerland Ltd 2010
Type Order No.
FDUL221-A Line connection set
Use as spare part for line tester FDUL221.
A5Q00008436
FDUL221-B Mains adapter set
Use as spare part for line tester FDUL221.
A5Q00008437
FDUL221-C PC cable (RS232)
Use as spare part for line tester FDUL221.
A5Q00008438
BPZ:3679630001 Halogen lamp 12 V / 50 W
Use as spare part for LE3.
BPZ:3679630001
12.fm Seite 10 Mittwoch, 28. Juli 2010 8:59 08
Spare PartsTest Equipment
12-11© Siemens Switzerland Ltd 2010
12
Type Order No.
RE7T-B Solo760 Battery for RE7T
Use as spare part for RE7T heat detector tester.
Data sheet A6V10252901
S54370-N5-A1
RE7T-C Solo725 Charger for RE7T
Use as spare part for charging of battery baton to the RE7T heat detec-tor tester.
Data sheet A6V10252901
S54370-N6-A1
RG320 Bellow for RE6
The bellow is fitted to the RE6 to fit all SynoLINE300 point detectors in an ideal way.
BPZ:5166880001
DZZ1190 Bellow for RE6
The bellow is fitted to the RE6 to fit all SynoLINE600 and AlgoRex point detectors in an ideal way.
BPZ:4478380001
12.fm Seite 11 Mittwoch, 28. Juli 2010 8:59 08
081031_Product_Catalog_Innen_07lay.indd 35 24.07.09 18:12
Repair PartsFire Control Panels FC72xx and Operating Terminals FT724xxOperating Units and Add-on
13-1© Siemens Switzerland Ltd 2010
13
Type Order No.
FCM7201-Z3 Operating unit
Complete operating unit (support base‚ keypad‚ PMI main board‚ CPU module) without accessories.Use as repair part only.
A5Q00018923-R
FCM7202-Y3 Operating unit (+LED ind.)
Complete operating unit (support base‚ keypad‚ PMI main board‚ CPU module) without accessories.Use as repair part only.
A5Q00018925-R
FCM7203-H3 Operating unit (+EVAC term.)
Complete operating unit (support base‚ keypad‚ PMI main board‚ CPU module) without accessories.Use as repair part only.
A5Q00018933-R
13.fm Seite 1 Mittwoch, 28. Juli 2010 9:00 09
Repair PartsPeriphery Boards‚ Expansion Modules and Power Supply
13-2 © Siemens Switzerland Ltd 2010
Type Order No.
FCI2010-A1 Periphery board (1-loop)
Periphery board (1-loop) without accessories.Use as repair part only.
A5Q00031729-R
FCI2002-A1 Periphery board (2-loop)
Periphery board (2-loop) without accessories.Use as repair part only.
A5Q00005545-R
FCI2004-A1 Periphery board (4-loop)
Periphery board (4-loop) without accessories.Use as repair part only.
A5Q00009953-R
FTI2001-A1 Fire terminal board
Fire terminal board without accessories.Use as repair part only.
A5Q00013279-R
13.fm Seite 2 Mittwoch, 28. Juli 2010 9:00 09
Repair PartsPeriphery Boards‚ Expansion Modules and Power Supply
13-3© Siemens Switzerland Ltd 2010
13
Type Order No.
FN2001-A1 Network module (SAFEDLINK)
Network module (SAFEDLINK) without accessories.Use as repair part only.
A5Q00012851-R
13.fm Seite 3 Mittwoch, 28. Juli 2010 9:00 09
Repair PartsFloor Repeater Panels
13-4 © Siemens Switzerland Ltd 2010
Type Order No.
FT2010-A1 Floor repeater terminal
Front part of the floor repeater terminal (cover cap‚ stick-on labels‚ key-pad) without accessories.Use as repair part only.
A5Q00014104-R
FT2011-A1 Floor repeater display
Front part of the floor repeater display (cover cap‚ stick-on label‚ key-pad) without accessories.Use as repair part only.
A5Q00017706-R
13.fm Seite 4 Mittwoch, 28. Juli 2010 9:00 09
Danger Management System
MM8000 – the danger management station for Cerberus PROMM8000 enables centralized alarm management and supervision of a broad range of fi re safety, electronic security, and control systems. All are displayed in a uniform and clearly structured manner. Alarms and messages are listed according to security-relevant priorities, so operators have all relevant infor-mation at a glance. And in case of an event, MM8000 guides the user step by step through predefi ned procedures. Thanks to a user-friendly engineering tool, MM8000 can be confi gured quickly and easily. Moreover, MM8000 is a highly fl exible and scalable danger management station that can be adapted to changing requirements any time.
MM8000 can integrate the following subsystems:– Fire safety– Intrusion detection– Access control– Video surveillance– Building automation installations– and other subsystems
fieneb ynam sreffo 0008MM ot ORP s®urebreC gnitcennoC ts, among them are:– Central control and operation– Interaction with other safety subsystems– Easy navigation and quick alarm localization– Guided event treatment– History database
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 38 28.05.10 16:59
Danger Management SystemMM8000 Management Station
14-2 © Siemens Switzerland Ltd 2010
Type Order No.
MM8000xxx MM8000 danger management station
The MM8000 danger management station provides a powerful solu-tion for the centralized alarm management and supervision of a wide range of fire safety‚ security and control systems. It supports specifically fire‚ gas and intrusion detection‚ access control‚ video surveillance and building automation installations.
The MM8000 architecture allows the integration of Siemens fire safety‚ security and control systems as well as 3rd party solutions via standard interfaces.
FunctionalityComplete overview of the actual state of technical installations in a building at any time.Homogeneous and intuitive operation of the different subsystems.Comprehensive guidance and support of the operator in case of an alarm.Logging of all activities and powerful reporting possibilities.
AdvantagesSafety: User guidance in case of an emergency guarantees that the right measures are taken.Reliability: Based on the concept of autonomous subsystems and dis-tributed control; possibility of redundant configurations.Flexibility: Can be built and configured to fit the requirements of the customer.Openness: OPC‚ BACnet and Modbus (via NK) interfaces for subsystem integration.Scalability: MM8000 will easily grow to support more subsystems‚ dis-ciplines and stations.
FeaturesComfortable navigation through the system via graphical maps or object trees.Advanced graphics including AutoCAD.Automatic and/or manual alarm dispatching via e-mail‚ SMS and pag-ers.Scheduler application for time-based actions.Configurable interactions between different subsystems.Macro editor for complex commands.System security based on Microsoft Windows (combined login).Flexible configuration of user access rights.Support of dual monitor configurations.
System requirements The MM8000 SW runs on a Micro-soft Windows PC.
Ordering information Contact your local BT sales support representative for further informa-tion.
Data sheet A6V10074451
MM8000xxx
14.fm Seite 2 Mittwoch, 28. Juli 2010 9:01 09
System Overview
Cerberus PRO – an overview of a smart systemThe Cerberus® PRO portfolio provides everything needed for smart fi re protection: powerful control panels, clever fi re detectors, smart peripheral devices – and elaborate safety features. What’s more, every component comes from the same source.
Unique safety features – such as degrade mode in control panels and built-in isolators in each peripheral device
Powerful panels – from stand-alone to networkable control units Reliable detectors – developed and proven under countless job-site conditions Broad range of additional devices and accessories – from alarm sounders to sounder bases and combined sounder beacons and many more
Cost effi ciency – thanks to smart products and remote access Integration into the danger management system from Siemens – interoperability with other subsystems such as access control, intrusion detection, video surveillance, and others
Control panels and fi re terminals can serve as a standby operating unit for increased safety Extended network possibilities for widely distributed or complex buildings
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 40 28.05.10 16:59
Cerberus PRO Planning Tool – panels, network, and accessories
Customer network
Cluster (C-WEB/SAFEDLINK)
In the basic version each FC724 control panel contains:
Alarm transmissionFault transmissionFire controlsMonitoring of 2 conven-tional sounder lines
Each FC726 control panel contains:
Alarm transmissionFault transmissionFire controlsMonitoring of 2 conven-tional sounder lines
To enable remote operation with Cerberus-Remote, the PC has to be connected to an Ethernet switch of the backbone. Access to a certain panel in a cluster will be granted by installing an L1 license key into this panel.
Security module
(firewall) FN2009-A1
Danger management
system
The danger management system from Siemens is either directly connected to the backbone (via Ethernet switch) or via the customer network by using ad-ditional security modules. Each station that is to be addressed by the danger management system must be released by means of the license key (L2).
System-wide view with the fire terminal FT2040-EZ
Ethernet switch FN2008-A1
Security module (firewall) FN2009-A1
Fire control panel FC724-ZE
Art. no.: S54400-C30-A3
Remote access with Cerberus-Remote
Ethernet switch FN2008-A1
Ethernet
Fire control panel FC724-ZA
Art. no.: S54400-C30-A2
Backbone (C-WEB/LAN)Clusters can be networked via an Ethernet back-bone, using industrial LAN technology. Siemens is the first manufacturer who offers this as EN 54-approved solution. With this architecture that is standard in IT, building structures and or-ganizational processes can be ideally depicted.
Characteristics of networking via backbone– Ethernet switch to connect a cluster to the
backbone– Redundant transmission thanks to circular
wiring– Redundant connection possible due to two
Ethernet switches– Increased EMC protection thanks to fiber-
optic cabling– Easily programmable, EN 54-conform system-
wide control– Configurable view of single panels– All panels can be used as router panel (for
further information on FC726, please have a look into the separate documentation).
Key data– Max. number of panels in EN 54 system: 64– Max. number of panels in a cluster: 16– Max. number of networkable clusters: 14– Number of panels placed directly
on backbone: 4*– Number of panels with
system-wide view: 5*– Max. distance between clusters
(fiber optic: multi mode): 3,000 m
* and more with respective system topology
The following guidelines must be observed– To fulfill the EN 54 norm, you need only
1 Ethernet switch to connect control panels with less than 512 fire detectors to the backbone.
Cluster (C-WEB/SAFEDLINK)Via the powerful cluster, up to 32 panels can be networked (fire control panels and fire terminals).
Characteristics of networking via the system bus– Wiring with two wires– Redundant transmission thanks to circular
wiring– Increased safety due to degrade mode using a
second network module– No additional cabling necessary for degrade
mode; even for systems with more than 512 fire detectors
– Configurable view of individual panels
Key data– Max. number of networkable panels: 32– Max. number of networkable panels
if connected to a danger management system: 16
– Max. distance between panels with copper cable• without repeater: 1,000 m • with repeater: 2,000 m
– Max. distance between panels with fiber-optic cable • multi mode: 2,500 m • single mode: 15,000 m
– Max. number of panels with system-wide view: 5
C-NETThe C-NET is a modern, multi-purpose bus system. It allows rapid, fail-safe communication between the Cerberus® PRO bus elements and the fire control panel.
Characteristics of networking via the detector bus– Use of all cable types (shielded or unshielded)– Integration of star-shaped cable networks
without modifications to cable network– Shielding not necessary
C-NET(For further details see also the Cerberus PRO Planning Tool – C-NET devices)
Fire terminal FT724-ZZ
Art. no.: S54400-C31-A2
Fire terminal FT724 The FT724 has the following features:– Integrated control unit– Separate DC 24 V supply input possible– Redundant DC 24 V supply input– Networkability via C-WEB/SAFEDLINK or Ethernet
Fire control panel FC724 (4-loop) The FC724 is a compact 4-loop fi re control panel. It has the following features:– 4 C-NET loops– Integrated inputs/outputs for peripherals– Integrated control unit– Integrated power supply– Automatic confi guration– Networkability via backbone (C-WEB/LAN),
cluster (C-WEB/SAFEDLINK) or Ethernet
Fire control panel FC726 (modular)FC726 is a modular fi re control panel.It has the following features:– 4 C-NET loops– 5 slots for additional module bus cards– Integrated inputs/outputs for peripherals– Integrated control unit– Integrated power supply– Automatic confi guration– Networkability via backbone (C-WEB/LAN),
cluster (C-WEB/SAFEDLINK) or Ethernet
Fire control panel FC726-ZA
Art. no.: S54400-C87-A1
Backbone (C-WEB/LAN)
– 2-wire loop– Power supply to all bus elements via the C-NET
(except transponder FDCIO223, LaserFOCUS, extinguishing control unit XC10)
Key data– Up to 40 T-taps– Up to 126 bus elements on one loop– Cable lengths up to 3.3 km with up to 126 bus
elements
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 41 28.05.10 16:59
© Siemens 2010
In the basic version each FC722 control panel contains:
Alarm transmissionFault transmissionFire controlsMonitoring of conven-tional sounder line
Fire control panel FC721 (1-loop)The FC721 is a compact fi re control panel. It has the following features:– 1 C-NET loop– Integrated inputs/outputs for
peripherals– Integrated control unit– Integrated power supply– Automatic confi guration
Fire control panel FC721-ZZ
Art. no.: S54400-C32-A2
Fire control panel FC721-YZ
Art. no.: S54400-C32-A3
Manual call point, red FDM221
Fire control panel FC722 (2-loop)The FC722 is a compact 2-loop fi re con-trol panel. It has the following features:– 2 C-NET loops– Integrated inputs/outputs for
peripherals– Integrated control unit– Integrated power supply– Automatic confi guration– Networkability via backbone (C-WEB/
LAN), cluster (C-WEB/SAFEDLINK) or Ethernet
Fire control panel FC722-ZA
Art. no.: S54400-C29-A2
Fire control panel FC722-ZE
Art. no.: S54400-C29-A1Floor repeater terminal FT2010-A1
Art. no.: A5Q00014104
Optical smoke detector OP720
Alarm sounderFDS221-R
Serial interfaces One optional RS232 and/or one RS485 interface (also freely combinable) per panel or fire terminal
Backbone (C-WEB/LAN) Network to connect clusters Cluster (C-WEB/SAFEDLINK) Network to connect panelsC-NET Network to connect Cerberus PRO devices
Legend for the interfaces and networks:
Repeater (SAFEDLINK) FN2002-A1
Art. no.: S24236-B2502-A1
Fire control panel FC722-YZ
Art. no.: S54400-C29-A4
Fire control panel FC722-ZZ
Art. no.: S54400-C29-A5
BackboneSecurity module (firewall) FN2009-A1
Art. no.: S54400-F95-A1
Ethernet switch FN2008-A1
Art. no.: S54400-F94-A1
Cluster Network module (SAFEDLINK) FN2001-A1
Art. no.: A5Q00012851
Housing (Eco) FH7201-Z3
Art. no.: S54400-B72-A1
Housing (Standard) FH7202-Z3
Art. no.: S54400-B70-A1
Housing (Comfort) FH7203-Z3
Art. no.: S54400-B71-A1
Housing (Large) FH7205-Z3
Art. no.: S54400-B86-A1
Housing (Large Extension) FH7204-Z3
Art. no.: S54400-B89-A1
19“ mounting kit FHA2016-A1
Art. no.: A5Q00020179
Loop extension (C-NET) FCI2003-A1
Art. no.: A5Q00010136
RS232 module (isolated) FCA2001-A1
Art. no.: A5Q00005327
RS485 module (isolated) FCA2002-A1
Art. no.: A5Q00009923
Sounder module FCA2005-A1
Art. no.: A5Q00014866
License key L1 FCA2012-A1
Art. no.: A5Q00018856
License key L2 FCA2013-A1
Art. no.: A5Q00018857
Line card (C-NET) FCL2001-A1
Art. no.: A5Q00009875
Module bus cards for FC726
I/O card (programmable) FCI2008-A1
Art. no.: S54400-A6-A1
Power supply kit (70 W) FP2003-A1
Art. no.: A5Q00016005
Power supply kit (150 W) FP2004-A1
Art. no.: A5Q00020825
Additional power supply (150 W) FP2005-A1
Art. no.: A5Q00018779
Power supply
Operating add-ons
Operating add-on (2xLED-ind.) FCM7211-Y3
Art. no.: S54400-F75-A1
Operating add-on (4xLED-ind.) FCM7212-Y3
Art. no.: S54400-F88-A1
Key switch Kaba FTO2005-C1
Art. no.: A5Q00010113
Key switch NordicFTO2006-B1
Art. no.: A5Q00010129
Event printer FTO2001-A1
Art. no.: A5Q00010126
Event printer DL3750+
Art. no.: A5Q00023962
Network components Housings Expansion options
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 42 28.05.10 16:59
Fire control panel FC722
Fire control panel FC724
Fire control panel FC726
Multi-line separator module FDCL221-M
Art. no.: S54312-F6-A1
C-NETThe C-NET is a modern, multi-purpose bus system. It allows rapid, fail-safe communication between the Cerberus® PRO bus elements and the fire control panel.
Cerberus PRO fi re detectors
Extinguishing panel standard XC1001-A
Art. no.: S54390-C1-A1
Input/output module FDCIO222
Art. no.: A5Q00002369
Cerberus PRO control panels
Floor repeater terminal FT2010-A1
Art. no.: A5Q00014104
Floor repeater display FT2011-A1
Art. no.: A5Q00017706
Mimic display driver FT2001-A1
Art. no.: A5Q00014417
Line separator FDCL221
Art. no.: A5Q00004011
Cluster (C-WEB/SAFEDLINK)
Legend for the designation of fire detectors:Cluster (C-WEB/SAFEDLINK) Network for connecting up to 32 panels or up to
16 panels if connected to a danger management systemC-NET Network for connecting Cerberus PRO devices...xxx-9 Connection to collective and conventional technology possible
Cerberus PRO Planning Tool – C-NET devices
Alarm indicator (addressable)FDCAI221
Art. no.: S54370-F10-A1
Alarm equipment(audible/visible)
Sounder base DBS720
Art. no.: S54319-F5-A1
Alarm sounderFDS221-W
Art. no.: A5Q00006711
Alarm sounderFDS221-R
Art. no.: A5Q00004117
Alarm sounder beacon FDS229-R
Art. no.: A5Q00023093
Alarm sounder beacon FDS229-A
Art. no.: A5Q00023092
Sounder base FDB221
Art. no.: A5Q00001664
Sounder base flat FDB222
Art. no.: S54319-F1-A1
or
Sealing element FDBZ295
Art. no.: S54319-F10-A1
Designation plate FDBZ291
Art. no.: A5Q00002621
Base attachment FDB291
Art. no.: A5Q00001603
Base attachment wet FDB293
Art. no.: A5Q00003945
Designation plate DBZ1193A
Art. no.: BPZ:4864330001
Detector locking device FDBZ293
Art. no.: A5Q00005035
Optical smoke detector OP720
Art. no.: S54310-F1-A1
Heat detector HI720
Art. no.: S54310-F4-A1
Heat detector HI722
Art. no.: S54310-F3-A1
Alarm indicator FDAI93
Art. no.: S54370-F5-A1
Alarm indicator FDAI91
Art. no.: S54370-F9-A1
Alarm indicator FDAI92
Art. no.: S54370-F3-A1
Additional frame AI330
Art. no.: BPZ:3169430001
Detector base seal RS720
Art. no.: S54319-F8-A1
Designation plate FDBZ291
Art. no.: A5Q00002621
Detector locking device LP720
Art. no.: S54319-F9-A1
Line tester FDUL221
Art. no.: A5Q00004397
Detector exchanger DX791
Art. no.: S54319-F6-A1
Detector tester RE6 for smoke detectors
Art. no.: BPZ:3680300001
Detector tester RE7T for heat detectors
Art. no.: S54370-S3-A1
Detector tester RE10 for linear smoke detectors
Art. no.: BPZ:3685190001
Test lamp StapexHF for flame detectors ‘Ex’
Art. no.: BPZ:4620910001
Test lamp LE3 for flame detectors
Art. no.: BPZ:3669510001
Detector base accessories
Detector base DB721
Art. no.: S54319-F11-A1
Sounder base DBS720
Art. no.: S54319-F5-A1
or
Fire control panel FC722
LED flat cable 24 LEDs
Art. no.: BPZ:5291410001
Flat rear FHA2013-A1
Art. no.: A5Q00016552
Sounder accessories
Test equipment
Multi-sensor smoke detector OH720
Art. no.: S54310-F2-A1
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 43 28.05.10 17:00
+DC 24 V
up to 100 m +DC 24 V
Fire control
Fire control
Fire control
4 isolatedcontrol inputs
Collective interface
Housing red with key FDMH291-RArt. no.: A5Q00002217Housing yel-low with key FDMH291-YArt. no.: A5Q00004979Housing green with key FDMH291-GArt. no.: A5Q00004981Housing blue with key FDMH291-BArt. no.: A5Q00004980Accessories*
Manual call point with glass plate FDM225-RGArt. no.: A5Q00013434Accessories*
Manual call point with glass plate incl. back box FDM226-RGArt. no.: A5Q00013435Accessories*
Housing with glass and key:FDMH293-RArt. no.: A5Q00004023Housing yellow FDMH293-YArt. no.: A5Q00004908Housing green FDMH293-GArt. no.: A5Q00004911Housing blue FDMH293-BArt. no.: A5Q00004909Housing orange FDMH293-OArt. no.: S54311-F2-A1Accessories*
Housing red FDMH292-RArt. no.: A5Q00005525Accessories*
Housing with glass and key:FDMH293-RArt. no.: A5Q00004023Housing yellow FDMH293-YArt. no.: A5Q00004908Housing green FDMH293-GArt. no.: A5Q00004911Housing blue FDMH293-BArt. no.: A5Q00004909Housing orange FDMH293-OArt. no.: S54311-F2-A1Accessories*
Housing red FDMH292-RArt. no.: A5Q00005525Accessories*
Manual call point FDM221 Electronic switching unit FDME221Art. no.: A5Q00002451
Manual call point FDM225 Manual call point with re-settable plas-tic element FDM225-RPArt. no.: A5Q00012020
Manual call point FDM226 Manual call point with resettable plastic element incl. back box FDM226-RPArt. no.: A5Q00013436
Manual call point FDM224 Electronic switching unit FDME224Art. no.: A5Q00009392
Manual call point FDM224H Electronic switching unit FDME224Art. no.: A5Q00009392
Manual call point FDM223 Electronic switching unit FDME223Art. no.: A5Q00003087
Manual call point FDM223H Electronic switching unit FDME223Art. no.: A5Q00003087
* See respective catalog page
Base and smoke detector DOW1171
Art. no.: S24218-F62-A5
Lithium battery 3.6 V
Art. no.: V24069-Z112-A1
Key
Art. no.: S24217-G34-A1
Manual call point SMF121
Art. no.: V24217-C1218-W200
MCP base SMF6120
Art. no.: S24218-F72-A1
Radio gateway FDCW221
Art. no.: A5Q00020241
Radio network in SRD band
Radio fi re detection
Input/output module“transponder” FDCIO223
Art. no.: S24218-B102-A1
Input module FDCI221
Art. no.: S54312-F1-A1
Input/output module FDCIO221
Art. no.: S54312-F2-A1
Input module FDCI222
Art. no.: A5Q00001984
Input/output module FDCIO222
Art. no.: A5Q00002369
4 isolatedcontrol inputs
4 isolatedcontrol outputs
Aspirating smoke detection
LaserFOCUS VLF-250
Art. no.: VLF-250-SIE
LaserFOCUS VLF-500
Art. no.: VLF-500-SIE
Housing FDCH221IP65Art. no.: S54312-F3-A1
Air sampling smoke detection kit FDBZ292 (without air flow pipe)
Art. no.: A5Q00021362
Air flow pipe FDBZ292-AAlength 0.6 m
Art. no.: A5Q00021363
Air flow pipe FDBZ292-ABlength 1.5 m
Art. no.: A5Q00021364
Air flow pipe FDBZ292-AClength 2.8 m
Art. no.: A5Q00021366
Optical smoke detector DO1104A
Art. no.: BPZ:5090640001
Detector base DB1101A
Art. no.: BPZ:4863650001
Long-distance reflector DLR1191 (Prism)
Art. no.: BPZ:4787710001
Mid-distance reflector DLR1192
Art. no.: BPZ:4788490001
Short-distance reflector DLR1193
Art. no.: BPZ:4787840001
Short-distance filter 7 – 10 m DLF1191-AA
Art. no.: BPZ:4933030001
Short-distance filter 5 – 8 m DLF1191-AB
Art. no.: BPZ:4933160001
Detector heating DLH1191A
Art. no.: BPZ:4787970001
Input/output module “transponder” FDCIO223
Art. no.: S24218-B102-A1
Rain hood DFZ1190
Art. no.: BPZ:5302660001
Mounting bracket MV1
Art. no.: BPZ:3950450001
Ball and socket joint MWV1
Art. no.: BPZ:3674840001
Conventional detectors
Conventional line
Heat detector DT1102A-ExArt. no.: BPZ:4852270001
Heat detector DT1101A-ExArt. no.: BPZ:4852140001
Smoke detector DO1101A-ExArt. no.: BPZ:5008010001
Alarm indicator FDAI93-ExArt. no.: S54370-F6-A1
Alarm indicator FDAI92-ExArt. no.: S54370-F4-A1
Flame detector DF1101-Ex Art. no.: BPZ:5166750001Base DFB1190Art. no.: BPZ:5165360001
Detector base DB1101AArt. no.: BPZ:4863650001
Line termination EOL22 (Ex)Art. no.: BPZ:516222001
Housing DCA1191Art. no.: BPZ:4588560001Installation set Z3I410Art. no.: BPZ:4837660001Shunt Zener diode barrier SB3Art. no.: BPZ:4837400001
Manual call point DM1103 (Ex) Electronic DMA1103DArt. no.: A5Q00004470Housing red with key DMA1192-AAArt. no.: BPZ:5222870001
Manual call pointDM1104 (Ex)Electronic DMA1104DArt. no.: A5Q00005925Housing red with key DMA1192-AAArt. no.: BPZ:5222870001
Ex zoneFlame detector base FDFB291
Art. no.: A5Q00003310
DA fl ame detector FDF221-9
Art. no.: A5Q00003902
Flame detector FDF241-9
Art. no.: A5Q00003006
Linear smoke detector FDL241-9
Art. no.: A5Q00002298
Linear smoke detector base FDLB291
Art. no.: A5Q00003941
Manual call points and accessories
© Siemens 2010
002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 44 28.05.10 17:00
081031_Product_Catalog_Innen_07lay.indd 25 24.07.09 18:07
Type Index
1© Siemens Switzerland Ltd 2010
Type Description Order No. Page
A5Q00004142 Lithium brownstone battery 9 V / 1 Ah A5Q00004142 9-21,10-8
A5Q00004478 Screwed cable gland M20 x 1.5 A5Q00004478 2-20, 5-9, 5-12,5-16, 5-
18, 5-22, 5-24, 5-31, 5-
42, 7-7,7-12, 7-
16, 7-19, 7-23, 7-
25, 9-7,9-19, 9-
24, 9-26–27,
9-32, 9-35, 9-37
A5Q00004479 Back nut M20 A5Q00004479 2-21, 5-10, 5-12, 5-
42, 7-7,7-16, 7-
19, 9-24
A5Q00006735 Locking plug M20 x 1.5 (1 hole) A5Q00006735 5-16, 5-22, 7-
23, 9-35
A5Q00008131 V-plug PA M20 x 1.5 A5Q00008131 5-18, 5-24
A5Q00009786 Adapter with lever‚ screw and nut incl. attachment and bushing screw
A5Q00009786 12-9
A5Q00009787 Lever with screw and nut A5Q00009787 12-9
A5Q00009788 Small flap with screw and nut A5Q00009788 12-9
A5Q00009789 Large flap with screw and nut A5Q00009789 12-9
A5Q00010055 Locking plug M20 x 1.5 (2 holes) A5Q00010055 5-17, 5-23, 7-
23, 9-35
A5Q00017619 Thermo printer rolls for Custom Plus-S-0004 A5Q00017619 12-2
A5Q00023963 Typewriter ribbon A5Q00023963 12-2
AGN24.6 Alarm device BPZ:5371170001 8-1, 8-3
AGS24.5 Mallory buzzer BPZ:2785020001 8-2
AGT24.1 Alarm device BPZ:5371040001 8-1
AI330 Adapter frame for alarm indicator BPZ:3169430001 6-2, 7-9,7-24, 9-
36
AI91C Alarm indicator - Door frame S54370-F7-A1 7-9
AI92C Alarm indicator - Surface S54370-F8-A1 7-9
ALB24.1OR Flashing signal lamp 'orange' BPZ:5154140001 8-3
ALB24.1R Flashing signal lamp 'red' BPZ:5154270001 8-3
BPZ:2473130001 Washer BPZ:2473130001 7-25, 9-37
BPZ:3048160001 Insulating cap for alarm indicators BPZ:3048160001 7-25, 9-37, 12-8
BPZ:3679630001 Halogen lamp 12 V / 50 W BPZ:3679630001 12-10
Type Index
2 © Siemens Switzerland Ltd 2010
Type Description Order No. Page
DB1101A Base for collective detector series BPZ:4863650001 7-11, 9-11, 9-29
DB3 Alarm device for explosion-hazard areas of zones 1 and 2 BPZ:5757970001 9-38
DB721 Detector base with loop contact S54319-F11-A1 5-5
DBC1191A-AA Relay base BPZ:5017870001 7-13
DBS720 Sounder base S54319-F5-A1 5-6, 5-32
DBW1171 Base for radio smoke detector S24218-F316-A1 9-18
DBZ1190 Locking device BPZ:4585260001 7-14, 9-18
DBZ1190-AA Micro terminal 0.5 mm2‚ 4-pole BPZ:4677080001 5-7, 5-30, 5-33, 7-13, 9-
26–27,9-30
DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole BPZ:4942340001 5-7, 5-12, 5-30, 5-33, 5-
42, 7-4,7-7, 7-14, 7-16, 9-13, 9-
24, 9-30
DBZ1190A-AC Detector heating BPZ:5167850001 7-14
DBZ1191 Base attachment for surface mounting BPZ:4540830001 7-11, 9-29
DBZ1191A-AA Base attachment flat for surface mounting BPZ:5011270001 7-11
DBZ1192 Base attachment for humid environment BPZ:4588140001 7-12, 9-19
DBZ1192-AA Base attachment for wet environment BPZ:5355590001 7-12
DBZ1193A Detector designation plate BPZ:4864330001 5-31, 7-14, 9-19
DBZ1194 Protective cage BPZ:4677110001 5-31, 7-12, 9-19
DBZ1195A Acoustic base BPZ:4940140001 7-13
DBZ1197-AA Air flow tube for ASD-Duct BPZ:4926630001 9-11
DBZ1197-AC Air flow tube for ASD-Duct BPZ:4995140001 9-12
DC1192-I__ Input/output module for galvanic isolation DC1192-I__ 9-25
DCA1191 Housing (empty) BPZ:4588560001 7-25, 9-25, 9-
27, 9-37
DCA1192A Electronic unit for DC1192 BPZ:5081200001 9-25
DCB1192A Terminal base for DC1192 BPZ:5084500001 9-25
DF1101-Ex Infrared flame detector unit collective 'Ex' BPZ:5166750001 9-31
DF11Ex__ Infrared flame detector collective 'Ex' DF11Ex__ 9-31
DFB1190 Base for infrared flame detectors DF119x BPZ:5165360001 9-31–32
DFZ1190 Rain hood BPZ:5302660001 9-3
DJZ1193 Alarm indicator housing incl. washer BPZ:5302950001 7-25, 9-37
DL3750+ Matrix printer external A5Q00023962 1-10, 2-29, 2-36
DLF1191-AA Filter for short distances (7... 10 m) BPZ:4933030001 9-7
DLF1191-AB Filter for short distances (5... 8 m) BPZ:4933160001 9-8
Type Index
3© Siemens Switzerland Ltd 2010
Type Description Order No. Page
DLF1191-AC Filter against external light influences BPZ:5221480001 9-8
DLH1191A Detector heating BPZ:4787970001 9-8
DLR1191 Reflector for long distance (prism) BPZ:4787710001 9-7
DLR1192 Reflector for middle distance (foil) BPZ:4788490001 9-7
DLR1193 Reflector for short distance (foil) BPZ:4787840001 9-7
DM1101__ Collective manual call point DM1101__ 7-17
DM1103-L Manual release button complete A5Q00017630 7-22
DM1103-S Emergency stop button complete A5Q00014486 7-22
DM1103(Ex)__ Collective manual call point (double action) for explosion-hazard areas
DM1103(Ex)__ 9-33
DM1103__ Collective manual call point DM1103__ 7-20
DM1104(Ex)__ Collective manual call point (single action) for explosion-hazard areas
DM1104(Ex)__ 9-34
DM1104__ Collective manual call point DM1104__ 7-19
DMA1101 Switching unit collective (single action) A5Q00005578 7-17–18
DMA1103D Switching unit collective (double action) A5Q00004470 7-20, 9-33
DMA1104D Switching unit collective (single action) A5Q00005925 7-19–20,
9-34
DMA1192-AA Housing red‚ with glass and key BPZ:5222870001 7-19–21,
9-33–34
DMA1192-AB Housing blue‚ with glass and key BPZ:5464250001 7-19–21
DMA1192-AC Housing yellow‚ with glass and key BPZ:5464120001 7-19–21
DMA1192-AD Housing green‚ with glass and key BPZ:5090190001 7-19–21
DMZ1195 Spare key BPZ:4851910001 12-6
DMZ1196-AC Spare glass neutral BPZ:4942050001 12-6
DMZ1197-AC Protective cover BPZ:5223550001 5-16, 5-18, 5-22, 5-24, 7-
23, 9-35
DMZ1197-AD Protection seal BPZ:5470680001 5-16, 5-18, 5-22, 5-24, 7-
23, 9-35
DO1101A Smoke detector‚ collective wide spectrum BPZ:4930020001 7-10
DO1101A-Ex Smoke detector‚ wide spectrum collective 'Ex' BPZ:5008010001 9-28
DO1104A Smoke detector‚ collective wide spectrum BPZ:5090640001 9-11
DOW1171 Radio smoke detector S24218-F62-A6 9-18
DOW1171/DBW1171 Radio smoke detector complete S24218-F62-A5 9-17
DT1101A Heat detector BPZ:4931700001 7-10
DT1101A-Ex Heat detector collective 'Ex' BPZ:4852140001 9-28
DT1102A Heat detector BPZ:4931830001 7-10
DT1102A-Ex Heat detector collective 'Ex' BPZ:4852270001 9-29
DX791 Detector exchanger S54319-F6-A1 10-2
DZB1191 Detector base tester BPZ:4680660001 10-5
DZW1171 Radio test set BPZ:5762200001 9-21
DZZ1190 Bellow for RE6 BPZ:4478380001 12-11
EOL22(Ex) Line termination BPZ:5162220001 9-24, 9-26
Type Index
4 © Siemens Switzerland Ltd 2010
Type Description Order No. Page
F50F410 LED flat cable 50-wire‚ with 24 red LEDs BPZ:5291410001 5-46
FA2003-A1 Battery (12 V‚ 7 Ah‚ VDS) A5Q00019353 11-1
FA2004-A1 Battery (12 V‚ 12 Ah‚ VDS) A5Q00019354 11-1
FA2005-A1 Battery (12 V‚ 17 Ah‚ VDS) A5Q00019677 11-1
FA2006-A1 Battery (12 V‚ 26 Ah‚ VDS) A5Q00019356 11-1
FA2007-A1 Battery (12 V‚ 45 Ah‚ VDS) A5Q00022897 11-1
FA2008-A1 Battery (12 V‚ 65 Ah‚ VDS) A5Q00019357 11-2
FA2009-A1 Battery (12 V‚ 100 Ah‚ VDS) A5Q00023101 11-2
FC1002-A 2-zone conventional unit (Standard) S54380-C2-A1 3-6
FC1002-B 2-zone conventional unit (Head removal monitoring) S54380-C2-A10 3-6
FC1002-C 2-zone conventional unit (Nordic) S54380-C2-A20 3-6
FC1002.. 2-zone conventional unit FC1002.. 3-6
FC1004-A 4-zone conventional unit (Standard) S54380-C3-A1 3-8
FC1004-B 4-zone conventional unit (Head removal monitoring) S54380-C3-A10 3-8
FC1004-C 4-zone conventional unit (Nordic) S54380-C3-A20 3-8
FC1004-E 4-zone conventional unit (NL) S54380-C3-A30 3-8
FC1004.. 4-zone conventional unit FC1004.. 3-8
FC1008-A 8-zone conventional unit (Standard) S54380-C4-A1 3-10
FC1008-B 8-zone conventional unit (Head removal monitoring) S54380-C4-A10 3-10
FC1008-C 8-zone conventional unit (Nordic) S54380-C4-A20 3-11
FC1008-D 8-zone conventional unit (CH) S54380-C4-A30 3-11
FC1008-E 8-zone conventional unit (Evacuation) S54380-C4-A40 3-11
FC1008.. 8-zone conventional unit FC1008.. 3-10
FC1012-A 12-zone conventional unit (Standard) S54380-C5-A1 3-14
FC1012-B 12-zone conventional unit (Head removal monitoring) S54380-C5-A10 3-14
FC1012-B 12-zone conventional unit (Head removal monitoring) A6E60500015 3-14
FC1012-C 12-zone conventional unit (Nordic) S54380-C5-A20 3-15
FC1012.. 12-zone conventional unit FC1012.. 3-14
FC721-HZ Fire control panel (1-loop) in housing (Eco) with EVAC operating unit
S54400-C32-A1 1-5
FC721-YZ Fire control panel (1-loop) in housing (Eco) with 1 LED indicator S54400-C32-A3 1-4
FC721-ZZ Fire control panel (1-loop) in housing (Eco) S54400-C32-A2 1-4
FC721.. Fire control panel (1-loop) in housing (Eco) FC721.. 1-3
FC722-HA Fire control panel (2-loop) in housing (Comfort) with EVAC oper-ating unit
S54400-C29-A3 2-9
FC722-YZ Fire control panel (2-loop) in housing (Standard) with 1 LED indi-cator
S54400-C29-A4 2-6
FC722-ZA Fire control panel (2-loop) in housing (Comfort) S54400-C29-A2 2-7
FC722-ZE Fire control panel (2-loop) in housing (Comfort) with 2 LED indi-cators
S54400-C29-A1 2-8
FC722-ZZ Fire control panel (2-loop) in housing (Standard) S54400-C29-A5 2-5
FC722.. Fire control panel (2-loop) in housing (Standard) FC722.. 2-4
FC724-HA Fire control panel (4-loop) with EVAC operating unit S54400-C30-A1 2-14
FC724-ZA Fire control panel (4-loop) S54400-C30-A2 2-12
FC724-ZE Fire control panel (4-loop) with 2 LED indicators S54400-C30-A3 2-13
FC724.. Fire control panel (4-loop) FC724.. 2-11
FC726-ZA Fire control panel (modular) S54400-C87-A1 2-17
FC726.. Fire control panel (modular) FC726.. 2-16
FCA1001 Line extension card 4-zones A6E60500020 12-3
FCA1002 Display unit A6E60500021 3-12, 3-16
FCA1003 Sounder control card A6E60500022 3-12, 3-16
Type Index
5© Siemens Switzerland Ltd 2010
Type Description Order No. Page
FCA1005-D RT-isolation card A6E60500024 3-12, 3-16
FCA1007 Key switch kit A6E60500026 3-7, 3-9,3-13, 3-17, 4-6
FCA1007-B Add-on line card A6E60500027 12-3
FCA1009-E EVAC module S54380-B11-A1 12-3
FCA1013 Universal accessory bag A6E60500068 12-3
FCA1014 Battery holder A6E60500069 3-13, 4-5
FCA1016 Battery holder S54400-B90-A1 3-7, 3-9
FCA2001-A1 RS232 module (isolated) A5Q00005327 1-6, 2-21, 2-32
FCA2002-A1 RS485 module (isolated) A5Q00009923 1-6, 2-21, 2-32
FCA2005-A1 Sounder module A5Q00014866 2-20
FCA2012-A1 License key (L1) A5Q00018856 1-6, 2-18, 2-32
FCA2013-A1 License key (L2) A5Q00018857 2-18, 2-32
FCA2014-A1 Cable kit (communication) A5Q00023027 1-9, 2-28, 2-35
FCE1001 EOL resistor 3.9 kT (set of 10 pcs.) A6E60500031 12-3
FCE1002 Termination element‚ control line A6E60500032 12-3
FCE1003-B EOL element for head removal monitoring A6E60500033 12-3
FCH1002 Cover for the FC1002-A‚ -B‚ -C A6E60500035 12-3
FCH1004 Cover for the FC1004-A‚ -B‚ -C A6E60500036 12-3
FCH1004-E Cover for the FC1004-E A6E60500037 12-4
FCH1008 Cover for the FC1008-A‚ -B‚ -C A6E60500038 12-4
FCH1008-D Cover for the FC1008-D A6E60500039 12-4
FCH1008-E Cover for the FC1008-E S54380-F10-A1 12-4
FCH1012 Cover for the FC1012-A‚ -B‚ -C A6E60500043 12-4
FCI2001-D1 Fire brigade periphery module A5Q00013100 2-19
FCI2002-A1 Periphery board (2-loop) A5Q00005545-R 13-2
FCI2003-A1 Loop extension (FDnet/C-NET) A5Q00010136 2-18
FCI2004-A1 Periphery board (4-loop) A5Q00009953-R 13-2
FCI2005-N1 RT Interface Set A5Q00026302 2-19
FCI2008-A1 I/O card (programmable) S54400-A6-A1 2-18
FCI2010-A1 Periphery board (1-loop) A5Q00031729-R 13-2
FCL2001-A1 Line card (FDnet/C-NET) A5Q00009875 2-18
FCM1002 Main board 2-zones S54380-C8-A1 12-4
FCM1004 Main board 4-zones S54380-C9-A1 12-4
FCM1004-E FCM1004-E Main board 4 zone NL S54380-C9-A10 12-4
FCM1008 Main board for 8-zone units S54380-C1-A10 12-4
FCM1008-D FCM1008-D Main board 8 zone CH S54380-C1-A20 12-4
FCM1008-E FCM1008-E Main board 8 zone NL S54380-C1-A30 12-4
FCM7201-Z3 Operating unit A5Q00018923-R 13-1
FCM7202-Y3 Operating unit (+LED ind.) A5Q00018925-R 13-1
FCM7203-H3 Operating unit (+EVAC term.) A5Q00018933-R 13-1
FCM7210-Z3 Operating add-on S54400-F76-A1 12-1
FCM7211-Y3 Operating add-on (2xLED ind.) S54400-F75-A1 2-23–24,
2-33,12-1
FCM7212-Y3 Operating add-on (4xLED ind.) S54400-F88-A1 2-24, 2-33, 12-2
Type Index
6 © Siemens Switzerland Ltd 2010
Type Description Order No. Page
FCM7221-H3 Operating add-on (2xEVAC) S54400-F78-A1 2-24
FCP1002 Transformer for 2/4-zone units S54390-N12-A1 12-4
FCP1004-E Power supply 3.5 A A6E60500054 12-5
FDAI91 Alarm indicator - Door frame S54370-F9-A1 6-1, 7-24
FDAI92 Alarm indicator - Surface S54370-F3-A1 6-1, 7-24
FDAI92-Ex Alarm indicator - Surface for explosion-hazard areas S54370-F4-A1 9-36
FDAI93 Alarm indicator - Flush S54370-F5-A1 6-1, 7-25
FDAI93-Ex Alarm indicator - Flush S54370-F6-A1 9-36
FDB221 Detector base addressable A5Q00001664 5-29
FDB222 Detector base flat‚ addressable S54319-F1-A1 5-29
FDB291 Base attachment A5Q00001603 5-30
FDB293 Base attachment humid with seal A5Q00003945 5-30
FDBZ291 Designation plate A5Q00002621 5-6, 5-29–30,
5-32
FDBZ292 Air sampling smoke detection kit A5Q00021362 9-10
FDBZ292-AA Air flow tube 0.6 m A5Q00021363 9-11
FDBZ292-AB Air flow tube 1.5 m A5Q00021364 9-12
FDBZ292-AC Air flow tube 2.8 m A5Q00021366 9-12
FDBZ292-AD Sealing kit for air flow tubes A5Q00021367 9-12
FDBZ292-AF Mounting bracket A5Q00021369 9-12
FDBZ293 Detector locking device A5Q00005035 5-28
FDBZ295 Sealing element S54319-F10-A1 5-29
FDCAI221 Addressable alarm indicator S54370-F10-A1 6-2
FDCH221 Housing for input/output modules S54312-F3-A1 2-20, 5-42, 9-23
FDCI221 Input module S54312-F1-A1 5-37
FDCI222 Input module A5Q00001984 5-37
FDCIO221 Input/output module S54312-F2-A1 5-38
FDCIO222 Input/output module A5Q00002369 5-39
FDCIO223 Input/output module 'Transponder' S24218-B102-A1 5-41, 9-23
FDCIO224 Input/output module A5Q00018689 5-40
FDCL221 Line separator A5Q00004011 5-35
FDCL221-M Multi-line separator module S54312-F6-A1 5-36
FDCM291 Mounting feet for in-/output modules A5Q00003855 12-8
FDCW221 Radio gateway A5Q00020241 9-16
FDF221-9 DA Infrared flame detector unit (1 sensor) A5Q00003902 9-2
FDF241-9 ASA Infrared flame detector unit (3 sensors) A5Q00003006 9-2–3
FDF__ Infrared flame detector FDF__ 9-2
FDFB291 Base for infrared flame detectors FDF2x1-9 A5Q00003310 9-2–3
FDL241-9 ASA Linear smoke detector unit A5Q00002298 9-5–6
FDL__ ASA Linear smoke detector FDL__ 9-5
FDLB291 Base for linear smoke detector FDL241-9 A5Q00003941 9-5–6
FDLU291 Adjustment device set for linear smoke detector A5Q00004905 9-8, 10-6
FDLU291 Adjustment device for FDLU291 A5Q00006540 12-9
FDM1101-RG Manual call point with glass plate S54371-F6-A1 7-15
FDM1101-RP Manual call point with resettable plastic element S54371-F6-A2 7-15
FDM1101A-RG Manual call point with glass plate S54371-F6-A3 7-6
FDM1101A-RP Manual call point with resettable plastic element S54371-F6-A4 7-6
Type Index
7© Siemens Switzerland Ltd 2010
Type Description Order No. Page
FDM221__ Manual call point FDM221__ 5-8
FDM223 Manual call point complete A5Q00008098 5-19
FDM223__ Manual call point FDM223__ 5-20
FDM223H__ Manual call point 'Heavy Duty' FDM223H__ 5-23
FDM224__ Manual call point FDM224__ 5-14
FDM224H__ Manual call point 'Heavy Duty' FDM224H__ 5-17
FDM225-RG Manual call point with glass plate A5Q00013434 5-10
FDM225-RP Manual call point with resettable plastic element A5Q00012020 5-11
FDM226-RG Manual call point with glass plate incl. housing base A5Q00013435 5-12
FDM226-RP Manual call point with resettable plastic element incl. housing base
A5Q00013436 5-13
FDMC291 Protective cover A5Q00001644 5-9, 7-19
FDMC295 Protective cover A5Q00013440 5-12–13,7-8, 7-
17
FDME221 Switching unit with direct alarm actuation A5Q00002451 5-8–9
FDME223 Switching unit with indirect alarm actuation A5Q00003087 5-20, 5-22–24
FDME224 Switching unit with direct alarm actuation A5Q00009392 5-14, 5-16–18
FDMG291 Replacement glass A5Q00002122 12-6
FDMG295 Glass plate neutral A5Q00013442 12-6
FDMH291-B Housing blue with key A5Q00004980 5-8–9,7-
17–18
FDMH291-G Housing green with key A5Q00004981 5-8–9,7-
17–18
FDMH291-R Housing red with key A5Q00002217 5-8, 7-17
FDMH291-Y Housing yellow with key A5Q00004979 5-8, 7-17–18
FDMH292-R Housing red 'Heavy Duty' A5Q00005525 5-17, 5-23
FDMH293-B Housing blue‚ with glass and key A5Q00004909 5-14–15,
5-20–21
FDMH293-G Housing green‚ with glass and key A5Q00004911 5-14–15,
5-20–21
FDMH293-O Housing orange‚ with glass and key S54311-F2-A1 5-14–15,
5-20–21
FDMH293-R Housing red‚ with glass and key A5Q00004023 5-14, 5-20
FDMH293-Y Housing yellow‚ with glass and key A5Q00004908 5-14–15,
5-20–21
FDMH295-R Back box A5Q00013437 5-11, 7-7, 7-16
FDMH295-S Back box with 2 entries A5Q00013438 5-11, 7-7, 7-16
Type Index
8 © Siemens Switzerland Ltd 2010
Type Description Order No. Page
FDS221-W Alarm sounder white A5Q00006711 5-26
FDS229-A Alarm sounder beacon‚ orange A5Q00023092 5-28
FDS229-R Alarm sounder beacon‚ red A5Q00023093 5-27
FDUD292-A Adapter cable A5Q00004990 12-9
FDUL221 Line tester A5Q00004397 10-8
FDUL221-A Line connection set A5Q00008436 12-10
FDUL221-B Mains adapter set A5Q00008437 12-10
FDUL221-C PC cable (RS232) A5Q00008438 12-10
FDUM291 Telescope rod A5Q00004996 10-4
FDUM292 Telescope rod A5Q00004997 10-5
FDUZ221 MCL USB adapter A5Q00020131 10-9
FH7201-Z3 Housing (Eco) S54400-B72-A1 1-6, 2-21, 2-33
FH7202-Z3 Housing (Standard) S54400-B70-A1 1-7, 2-22
FH7203-Z3 Housing (Comfort) S54400-B71-A1 2-22–23
FH7204-Z3 Housing (Large Extension) S54400-B89-A1 2-23
FH7205-Z3 Housing (Large) S54400-B86-A1 2-23
FHA2007-A1 Mounting plate A5Q00010151 2-19
FHA2013-A1 Rear (FT201x flat) A5Q00016552 5-45
FHA2016-A1 19" mounting kit A5Q00020179 1-9, 2-28, 2-35
FHA2029-A1 Mounting kit for housing (Comfort) S54400-B79-A1 2-27
FHA2030-A1 Mounting kit for housing (Large Extension) S54400-B81-A1 2-27
FHA7201-A3 Cover cap (Cerberus) S54400-B77-A1 12-1
FHA7202-A3 Cover cap (without print) S54400-B74-A1 12-1
FN2001-A1 Network module (SAFEDLINK) A5Q00012851-R 13-3
FN2001-A1 Network module (SAFEDLINK) A5Q00012851 2-26, 2-32
FN2002-A1 Repeater (SAFEDLINK) S24236-B2502-A1 2-26
FN2008-A1 Ethernet switch S54400-F94-A1 2-27
FN2009-A1 Security module S54400-F95-A1 2-27
FP2003-A1 Power supply kit (70 W) A5Q00016005 1-7, 2-25, 2-33
FP2004-A1 Power supply kit (150 W‚ A) A5Q00020825 1-8, 2-25
FP2005-A1 Power supply kit (150 W‚ B) A5Q00018779 2-25
FT2001-A1 Mimic display driver A5Q00014417 5-46
FT2003-N1 Mimic display driver (EVAC) S54400-A14-A1 2-24
FT2010-A1 Floor repeater terminal A5Q00014104-R 13-4
FT2010-A1 Floor repeater terminal A5Q00014104 5-43
FT2010-C1 Floor repeater terminal S54400-F34-A1 5-44
FT2011-A1 Floor repeater display A5Q00017706 5-45
FT2011-A1 Floor repeater display A5Q00017706-R 13-4
FT724-HZ Fire terminal with EVAC operating unit S54400-C31-A1 2-31
FT724-ZZ Fire terminal S54400-C31-A2 2-30
FT724.. Fire terminal FT724.. 2-30
FTI2001-A1 Fire terminal board A5Q00013279-R 13-2
FTI2002-N1 EVAC-NL connector board S54400-A15-A1 2-24
FTO2001-A1 Event printer A5Q00010126 1-7, 2-19, 2-34
Type Index
9© Siemens Switzerland Ltd 2010
Type Description Order No. Page
FTO2005-C1 Key switch (Kaba) A5Q00010113 1-9, 2-28, 2-
35, 5-45
FTO2006-B1 Key switch (Nordic) A5Q00010129 1-9, 2-28, 2-35
GEN2-de Fire control panel for connection to 12 VDC supply BPZ:9300150001 3-2
GEN2-en Fire control panel for connection to 12 VDC supply BPZ:9300110001 3-2
GEN2-es Fire control panel for connection to 12 VDC supply BPZ:9300100001 3-3
GEN2-fr Fire control panel for connection to 12 VDC supply BPZ:9300180001 3-2
GEN2-it Fire control panel for connection to 12 VDC supply BPZ:9300120001 3-2
GEN2-nl Fire control panel for connection to 12 VDC supply BPZ:9300190001 3-2
GEN2-se Fire control panel for connection to 12 VDC supply BPZ:9300130001 3-2
GEN2.. Fire control panel for connection to 12 VDC supply GEN2.. 3-2
HI320C Heat detector (rate of rise and maximum) BPZ:5081590001 7-3
HI322C Heat detector (maximum) BPZ:5316470001 7-4
HI720 Heat detector (static+RoR) S54310-F4-A1 5-4
HI722 Heat detector (static) S54310-F3-A1 5-4
LaserFOCUS VLF-250 Aspirating smoke detector with display VLF-250-SIE 9-14
LaserFOCUS VLF-500 Aspirating smoke detector with display VLF-500-SIE 9-15
LE3 Test lamp for flame detectors BPZ:3669510001 9-4, 10-6
LP720 Detector locking device S54319-F9-A1 5-5
MGEN2 Fire control panel PCB for all languages BPZ:9300170001 3-3
MM8000xxx MM8000 danger management station MM8000xxx 14-2
MV1 Mounting bracket BPZ:3950450001 9-3
MVH1 Mounting bracket BPZ:3496190001 7-26, 9-37
MWV1 Ball and socket joint BPZ:3674840001 9-4
OH320C Smoke detector‚ conventional multi-sensor BPZ:5364190001 7-3
OH720 Multi-sensor smoke detector S54310-F2-A1 5-3
OP320C Optical smoke detector BPZ:5081460001 7-3
OP720 Optical smoke detector S54310-F1-A1 5-3
RE10 Detector tester for linear smoke detectors BPZ:3685190001 9-8, 10-6
RE6 Detector tester for smoke detectors BPZ:3680300001 10-2
RE6T Detector tester for heat detectors BPZ:3680270001 10-3
RE7T Solo461 Heat detector tester kit S54370-S3-A1 10-3
RE7T-A Solo719 Adapter for FDUM29x S54370-N4-A1 10-4
RE7T-B Solo760 Battery for RE7T S54370-N5-A1 12-11
RE7T-C Solo725 Charger for RE7T S54370-N6-A1 12-11
REF8 Test gas can for smoke detectors A5Q00011687 10-2
REF8-S Test gas can for smoke detectors A5Q00011688 10-2
RG320 Bellow for RE6 BPZ:5166880001 10-3,12-11
RS720 Detector base seal S54319-F8-A1 5-6, 5-32
S24217-G34-A1 Key S24217-G34-A1 9-21
SB3 Shunt Zener diode barrier BPZ:4837400001 9-27
SMF121 Manual call point V24217-C1218-W100 9-20–21
SMF121 Manual call point V24217-C1218-W200 9-20–21
SMF6120 Radio base S24218-F72-A1 9-20
SMF__ Manual call point SMF__ 9-20
Type Index
10 © Siemens Switzerland Ltd 2010
Type Description Order No. Page
SO320 Base for Synova 300 series detectors BPZ:5085990001 7-4
SOA322 Base attachment for surface mounting BPZ:5358340001 7-4
StabexHF Test lamp for flame detectors 'Ex' BPZ:4620910001 9-32,10-6
SV 24V-150W Power supply (150 W) V24230-Z6-A4 12-1
TF04 Alarm test filter (Absorption 77 %) BPZ:4931090001 9-9, 10-7
TP320 Detector locking device BPZ:5093100001 7-5
TS35_122 U-rail TS35/7.5/122 BPZ:5644780001 2-20, 5-36, 5-42
TS35_288 U-rail TS35/7.5/288 BPZ:5644230001 2-20, 5-36, 5-42
V24069-Z112-A1 Lithium battery 3.6 V / 2.1 Ah V24069-Z112-A1 9-20
XC1001-A Extinguishing panel Standard S54390-C1-A1 4-2
XC1003-A Extinguishing panel Rack S54390-C2-A1 4-4
XC1005-A Extinguishing panel Comfort S54390-C3-A1 4-3
XCA1002-1 Display adapter S54390-B7-A1 12-5
XCA1002-2 Display adapter S54390-B8-A1 12-5
XCA1020 Accessory set for FDCIO A5Q00025158 4-5
XCA1030 Multi-zone extension module S54390-A5-A1 4-5
XCA1031 Common multi-zone module S54390-A6-A1 4-5
XCE1002 Trigger element A5Q00015659 4-5
XCH1001-A Cover set S54390-B9-A1 12-5
XCH1003-A Cover set S54390-B10-A1 12-5
XCH1005-A Cover set S54390-B11-A1 12-5
XCM1002 Main board S54390-A4-A1 12-5
XT1001-A1 Repeater display S54390-Z16-A1 4-7
XT1002-A1 Repeater display S54390-Z15-A1 4-7
Z3B171 Relay module with 1 contact BPZ:4843830001 1-9, 2-28, 3-7,
3-9, 3-13, 3-
17, 4-6,8-1, 8-3
Z3I410 Installation set BPZ:4837660001 9-27
ZS/AGN24.5 Adapter base BPZ:4242620001 8-1, 8-3
Order No. Index
1© Siemens Switzerland Ltd 2010
Order No. Description Type Page
A5Q00001603 Base attachment FDB291 5-30
A5Q00001643 Cover with key FDMK291 12-6
A5Q00001644 Protective cover FDMC291 5-9, 7-19
A5Q00001664 Detector base addressable FDB221 5-29
A5Q00001984 Input module FDCI222 5-37
A5Q00002122 Replacement glass FDMG291 12-6
A5Q00002217 Housing red with key FDMH291-R 5-8, 7-17
A5Q00002298 ASA Linear smoke detector unit FDL241-9 9-5–6
A5Q00002369 Input/output module FDCIO222 5-39
A5Q00002451 Switching unit with direct alarm actuation FDME221 5-8–9
A5Q00002621 Designation plate FDBZ291 5-6, 5-29–30,
5-32
A5Q00003006 ASA Infrared flame detector unit (3 sensors) FDF241-9 9-2–3
A5Q00003087 Switching unit with indirect alarm actuation FDME223 5-20, 5-22–24
A5Q00003310 Base for infrared flame detectors FDF2x1-9 FDFB291 9-2–3
A5Q00003855 Mounting feet for in-/output modules FDCM291 12-8
A5Q00003902 DA Infrared flame detector unit (1 sensor) FDF221-9 9-2
A5Q00003941 Base for linear smoke detector FDL241-9 FDLB291 9-5–6
A5Q00003945 Base attachment humid with seal FDB293 5-30
A5Q00004011 Line separator FDCL221 5-35
A5Q00004023 Housing red‚ with glass and key FDMH293-R 5-14, 5-20
A5Q00004117 Alarm sounder red FDS221-R 5-25
A5Q00004142 Lithium brownstone battery 9 V / 1 Ah A5Q00004142 9-21,10-8
A5Q00004397 Line tester FDUL221 10-8
A5Q00004470 Switching unit collective (double action) DMA1103D 7-20, 9-33
A5Q00004478 Screwed cable gland M20 x 1.5 A5Q00004478 2-20, 5-9, 5-12,5-16, 5-
18, 5-22, 5-24, 5-31, 5-
42, 7-7,7-12, 7-
16, 7-19, 7-23, 7-
25, 9-7,9-19, 9-
24, 9-26–27,
9-32, 9-35, 9-37
A5Q00004479 Back nut M20 A5Q00004479 2-21, 5-10, 5-12, 5-
42, 7-7,7-16, 7-
19, 9-24
A5Q00004905 Adjustment device set for linear smoke detector FDLU291 9-8, 10-6
Order No. Index
2 © Siemens Switzerland Ltd 2010
Order No. Description Type Page
A5Q00004908 Housing yellow‚ with glass and key FDMH293-Y 5-14–15,
5-20–21
A5Q00004909 Housing blue‚ with glass and key FDMH293-B 5-14–15,
5-20–21
A5Q00004911 Housing green‚ with glass and key FDMH293-G 5-14–15,
5-20–21
A5Q00004979 Housing yellow with key FDMH291-Y 5-8, 7-17–18
A5Q00004980 Housing blue with key FDMH291-B 5-8–9,7-
17–18
A5Q00004981 Housing green with key FDMH291-G 5-8–9,7-
17–18
A5Q00004990 Adapter cable FDUD292-A 12-9
A5Q00004996 Telescope rod FDUM291 10-4
A5Q00004997 Telescope rod FDUM292 10-5
A5Q00005035 Detector locking device FDBZ293 5-28
A5Q00005327 RS232 module (isolated) FCA2001-A1 1-6, 2-21, 2-32
A5Q00005525 Housing red 'Heavy Duty' FDMH292-R 5-17, 5-23
A5Q00005545-R Periphery board (2-loop) FCI2002-A1 13-2
A5Q00005578 Switching unit collective (single action) DMA1101 7-17–18
A5Q00005925 Switching unit collective (single action) DMA1104D 7-19–20,
9-34
A5Q00006540 Adjustment device for FDLU291 FDLU291 12-9
A5Q00006711 Alarm sounder white FDS221-W 5-26
A5Q00006735 Locking plug M20 x 1.5 (1 hole) A5Q00006735 5-16, 5-22, 7-
23, 9-35
A5Q00008098 Manual call point complete FDM223 5-19
A5Q00008131 V-plug PA M20 x 1.5 A5Q00008131 5-18, 5-24
A5Q00008436 Line connection set FDUL221-A 12-10
A5Q00008437 Mains adapter set FDUL221-B 12-10
A5Q00008438 PC cable (RS232) FDUL221-C 12-10
A5Q00009392 Switching unit with direct alarm actuation FDME224 5-14, 5-16–18
A5Q00009786 Adapter with lever‚ screw and nut incl. attachment and bushing screw
A5Q00009786 12-9
A5Q00009787 Lever with screw and nut A5Q00009787 12-9
A5Q00009788 Small flap with screw and nut A5Q00009788 12-9
A5Q00009789 Large flap with screw and nut A5Q00009789 12-9
A5Q00009875 Line card (FDnet/C-NET) FCL2001-A1 2-18
A5Q00009923 RS485 module (isolated) FCA2002-A1 1-6, 2-21, 2-32
A5Q00009953-R Periphery board (4-loop) FCI2004-A1 13-2
A5Q00010055 Locking plug M20 x 1.5 (2 holes) A5Q00010055 5-17, 5-23, 7-
23, 9-35
Order No. Index
3© Siemens Switzerland Ltd 2010
Order No. Description Type Page
A5Q00010113 Key switch (Kaba) FTO2005-C1 1-9, 2-28, 2-
35, 5-45
A5Q00010126 Event printer FTO2001-A1 1-7, 2-19, 2-34
A5Q00010129 Key switch (Nordic) FTO2006-B1 1-9, 2-28, 2-35
A5Q00010136 Loop extension (FDnet/C-NET) FCI2003-A1 2-18
A5Q00010151 Mounting plate FHA2007-A1 2-19
A5Q00011687 Test gas can for smoke detectors REF8 10-2
A5Q00011688 Test gas can for smoke detectors REF8-S 10-2
A5Q00012020 Manual call point with resettable plastic element FDM225-RP 5-11
A5Q00012851 Network module (SAFEDLINK) FN2001-A1 2-26, 2-32
A5Q00012851-R Network module (SAFEDLINK) FN2001-A1 13-3
A5Q00013100 Fire brigade periphery module FCI2001-D1 2-19
A5Q00013279-R Fire terminal board FTI2001-A1 13-2
A5Q00013434 Manual call point with glass plate FDM225-RG 5-10
A5Q00013435 Manual call point with glass plate incl. housing base FDM226-RG 5-12
A5Q00013436 Manual call point with resettable plastic element incl. housing base
FDM226-RP 5-13
A5Q00013437 Back box FDMH295-R 5-11, 7-7, 7-16
A5Q00013438 Back box with 2 entries FDMH295-S 5-11, 7-7, 7-16
A5Q00013440 Protective cover FDMC295 5-12–13,7-8, 7-
17
A5Q00013442 Glass plate neutral FDMG295 12-6
A5Q00013445 Plastic element neutral FDMP295 12-6
A5Q00013448 Spare key FDMK295 12-7
A5Q00014104 Floor repeater terminal FT2010-A1 5-43
A5Q00014104-R Floor repeater terminal FT2010-A1 13-4
A5Q00014417 Mimic display driver FT2001-A1 5-46
A5Q00014486 Emergency stop button complete DM1103-S 7-22
A5Q00014866 Sounder module FCA2005-A1 2-20
A5Q00015659 Trigger element XCE1002 4-5
A5Q00016005 Power supply kit (70 W) FP2003-A1 1-7, 2-25, 2-33
A5Q00016552 Rear (FT201x flat) FHA2013-A1 5-45
A5Q00017619 Thermo printer rolls for Custom Plus-S-0004 A5Q00017619 12-2
A5Q00017630 Manual release button complete DM1103-L 7-22
A5Q00017706 Floor repeater display FT2011-A1 5-45
A5Q00017706-R Floor repeater display FT2011-A1 13-4
A5Q00018689 Input/output module FDCIO224 5-40
A5Q00018779 Power supply kit (150 W‚ B) FP2005-A1 2-25
A5Q00018856 License key (L1) FCA2012-A1 1-6, 2-18, 2-32
A5Q00018857 License key (L2) FCA2013-A1 2-18, 2-32
A5Q00018923-R Operating unit FCM7201-Z3 13-1
A5Q00018925-R Operating unit (+LED ind.) FCM7202-Y3 13-1
A5Q00018933-R Operating unit (+EVAC term.) FCM7203-H3 13-1
A5Q00019353 Battery (12 V‚ 7 Ah‚ VDS) FA2003-A1 11-1
A5Q00019354 Battery (12 V‚ 12 Ah‚ VDS) FA2004-A1 11-1
Order No. Index
4 © Siemens Switzerland Ltd 2010
Order No. Description Type Page
A5Q00019356 Battery (12 V‚ 26 Ah‚ VDS) FA2006-A1 11-1
A5Q00019357 Battery (12 V‚ 65 Ah‚ VDS) FA2008-A1 11-2
A5Q00019677 Battery (12 V‚ 17 Ah‚ VDS) FA2005-A1 11-1
A5Q00020131 MCL USB adapter FDUZ221 10-9
A5Q00020179 19" mounting kit FHA2016-A1 1-9, 2-28, 2-35
A5Q00020241 Radio gateway FDCW221 9-16
A5Q00020825 Power supply kit (150 W‚ A) FP2004-A1 1-8, 2-25
A5Q00021362 Air sampling smoke detection kit FDBZ292 9-10
A5Q00021363 Air flow tube 0.6 m FDBZ292-AA 9-11
A5Q00021364 Air flow tube 1.5 m FDBZ292-AB 9-12
A5Q00021366 Air flow tube 2.8 m FDBZ292-AC 9-12
A5Q00021367 Sealing kit for air flow tubes FDBZ292-AD 9-12
A5Q00021369 Mounting bracket FDBZ292-AF 9-12
A5Q00022897 Battery (12 V‚ 45 Ah‚ VDS) FA2007-A1 11-1
A5Q00023027 Cable kit (communication) FCA2014-A1 1-9, 2-28, 2-35
A5Q00023092 Alarm sounder beacon‚ orange FDS229-A 5-28
A5Q00023093 Alarm sounder beacon‚ red FDS229-R 5-27
A5Q00023101 Battery (12 V‚ 100 Ah‚ VDS) FA2009-A1 11-2
A5Q00023962 Matrix printer external DL3750+ 1-10, 2-29, 2-36
A5Q00023963 Typewriter ribbon A5Q00023963 12-2
A5Q00025158 Accessory set for FDCIO XCA1020 4-5
A5Q00026302 RT Interface Set FCI2005-N1 2-19
A5Q00031729-R Periphery board (1-loop) FCI2010-A1 13-2
A6E60500015 12-zone conventional unit (Head removal monitoring) FC1012-B 3-14
A6E60500020 Line extension card 4-zones FCA1001 12-3
A6E60500021 Display unit FCA1002 3-12, 3-16
A6E60500022 Sounder control card FCA1003 3-12, 3-16
A6E60500024 RT-isolation card FCA1005-D 3-12, 3-16
A6E60500026 Key switch kit FCA1007 3-7, 3-9,3-13, 3-17, 4-6
A6E60500027 Add-on line card FCA1007-B 12-3
A6E60500031 EOL resistor 3.9 kT (set of 10 pcs.) FCE1001 12-3
A6E60500032 Termination element‚ control line FCE1002 12-3
A6E60500033 EOL element for head removal monitoring FCE1003-B 12-3
A6E60500035 Cover for the FC1002-A‚ -B‚ -C FCH1002 12-3
A6E60500036 Cover for the FC1004-A‚ -B‚ -C FCH1004 12-3
A6E60500037 Cover for the FC1004-E FCH1004-E 12-4
A6E60500038 Cover for the FC1008-A‚ -B‚ -C FCH1008 12-4
A6E60500039 Cover for the FC1008-D FCH1008-D 12-4
A6E60500043 Cover for the FC1012-A‚ -B‚ -C FCH1012 12-4
A6E60500054 Power supply 3.5 A FCP1004-E 12-5
Order No. Index
5© Siemens Switzerland Ltd 2010
Order No. Description Type Page
A6E60500068 Universal accessory bag FCA1013 12-3
A6E60500069 Battery holder FCA1014 3-13, 4-5
BPZ:2473130001 Washer BPZ:2473130001 7-25, 9-37
BPZ:2785020001 Mallory buzzer AGS24.5 8-2
BPZ:3048160001 Insulating cap for alarm indicators BPZ:3048160001 7-25, 9-37, 12-8
BPZ:3169430001 Adapter frame for alarm indicator AI330 6-2, 7-9,7-24, 9-
36
BPZ:3496190001 Mounting bracket MVH1 7-26, 9-37
BPZ:3669510001 Test lamp for flame detectors LE3 9-4, 10-6
BPZ:3674840001 Ball and socket joint MWV1 9-4
BPZ:3679630001 Halogen lamp 12 V / 50 W BPZ:3679630001 12-10
BPZ:3680270001 Detector tester for heat detectors RE6T 10-3
BPZ:3680300001 Detector tester for smoke detectors RE6 10-2
BPZ:3685190001 Detector tester for linear smoke detectors RE10 9-8, 10-6
BPZ:3950450001 Mounting bracket MV1 9-3
BPZ:4242620001 Adapter base ZS/AGN24.5 8-1, 8-3
BPZ:4478380001 Bellow for RE6 DZZ1190 12-11
BPZ:4540830001 Base attachment for surface mounting DBZ1191 7-11, 9-29
BPZ:4585260001 Locking device DBZ1190 7-14, 9-18
BPZ:4588140001 Base attachment for humid environment DBZ1192 7-12, 9-19
BPZ:4588560001 Housing (empty) DCA1191 7-25, 9-25, 9-
27, 9-37
BPZ:4620910001 Test lamp for flame detectors 'Ex' StabexHF 9-32,10-6
BPZ:4677080001 Micro terminal 0.5 mm2‚ 4-pole DBZ1190-AA 5-7, 5-30, 5-33, 7-13, 9-
26–27,9-30
BPZ:4677110001 Protective cage DBZ1194 5-31, 7-12, 9-19
BPZ:4680660001 Detector base tester DZB1191 10-5
BPZ:4787710001 Reflector for long distance (prism) DLR1191 9-7
BPZ:4787840001 Reflector for short distance (foil) DLR1193 9-7
BPZ:4787970001 Detector heating DLH1191A 9-8
BPZ:4788490001 Reflector for middle distance (foil) DLR1192 9-7
BPZ:4837400001 Shunt Zener diode barrier SB3 9-27
BPZ:4837660001 Installation set Z3I410 9-27
BPZ:4843830001 Relay module with 1 contact Z3B171 1-9, 2-28, 3-7,
3-9, 3-13, 3-
17, 4-6,8-1, 8-3
BPZ:4851910001 Spare key DMZ1195 12-6
Order No. Index
6 © Siemens Switzerland Ltd 2010
Order No. Description Type Page
BPZ:4852140001 Heat detector collective 'Ex' DT1101A-Ex 9-28
BPZ:4852270001 Heat detector collective 'Ex' DT1102A-Ex 9-29
BPZ:4863650001 Base for collective detector series DB1101A 7-11, 9-11, 9-29
BPZ:4864330001 Detector designation plate DBZ1193A 5-31, 7-14, 9-19
BPZ:4926630001 Air flow tube for ASD-Duct DBZ1197-AA 9-11
BPZ:4930020001 Smoke detector‚ collective wide spectrum DO1101A 7-10
BPZ:4931090001 Alarm test filter (Absorption 77 %) TF04 9-9, 10-7
BPZ:4931700001 Heat detector DT1101A 7-10
BPZ:4931830001 Heat detector DT1102A 7-10
BPZ:4933030001 Filter for short distances (7... 10 m) DLF1191-AA 9-7
BPZ:4933160001 Filter for short distances (5... 8 m) DLF1191-AB 9-8
BPZ:4940140001 Acoustic base DBZ1195A 7-13
BPZ:4942050001 Spare glass neutral DMZ1196-AC 12-6
BPZ:4942340001 Connection terminal 2.5 mm2‚ 3-pole DBZ1190-AB 5-7, 5-12, 5-30, 5-33, 5-
42, 7-4,7-7, 7-14, 7-16, 9-13, 9-
24, 9-30
BPZ:4995140001 Air flow tube for ASD-Duct DBZ1197-AC 9-12
BPZ:5008010001 Smoke detector‚ wide spectrum collective 'Ex' DO1101A-Ex 9-28
BPZ:5011270001 Base attachment flat for surface mounting DBZ1191A-AA 7-11
BPZ:5017870001 Relay base DBC1191A-AA 7-13
BPZ:5081200001 Electronic unit for DC1192 DCA1192A 9-25
BPZ:5081460001 Optical smoke detector OP320C 7-3
BPZ:5081590001 Heat detector (rate of rise and maximum) HI320C 7-3
BPZ:5084500001 Terminal base for DC1192 DCB1192A 9-25
BPZ:5085990001 Base for Synova 300 series detectors SO320 7-4
BPZ:5090190001 Housing green‚ with glass and key DMA1192-AD 7-19–21
BPZ:5090640001 Smoke detector‚ collective wide spectrum DO1104A 9-11
BPZ:5093100001 Detector locking device TP320 7-5
BPZ:5154140001 Flashing signal lamp 'orange' ALB24.1OR 8-3
BPZ:5154270001 Flashing signal lamp 'red' ALB24.1R 8-3
BPZ:5162220001 Line termination EOL22(Ex) 9-24, 9-26
BPZ:5165360001 Base for infrared flame detectors DF119x DFB1190 9-31–32
BPZ:5166750001 Infrared flame detector unit collective 'Ex' DF1101-Ex 9-31
BPZ:5166880001 Bellow for RE6 RG320 10-3,12-11
BPZ:5167850001 Detector heating DBZ1190A-AC 7-14
BPZ:5221480001 Filter against external light influences DLF1191-AC 9-8
BPZ:5222870001 Housing red‚ with glass and key DMA1192-AA 7-19–21,
9-33–34
Order No. Index
7© Siemens Switzerland Ltd 2010
Order No. Description Type Page
BPZ:5223550001 Protective cover DMZ1197-AC 5-16, 5-18, 5-22, 5-24, 7-
23, 9-35
BPZ:5291410001 LED flat cable 50-wire‚ with 24 red LEDs F50F410 5-46
BPZ:5302660001 Rain hood DFZ1190 9-3
BPZ:5302950001 Alarm indicator housing incl. washer DJZ1193 7-25, 9-37
BPZ:5316470001 Heat detector (maximum) HI322C 7-4
BPZ:5355590001 Base attachment for wet environment DBZ1192-AA 7-12
BPZ:5358340001 Base attachment for surface mounting SOA322 7-4
BPZ:5364190001 Smoke detector‚ conventional multi-sensor OH320C 7-3
BPZ:5371040001 Alarm device AGT24.1 8-1
BPZ:5371170001 Alarm device AGN24.6 8-1, 8-3
BPZ:5464120001 Housing yellow‚ with glass and key DMA1192-AC 7-19–21
BPZ:5464250001 Housing blue‚ with glass and key DMA1192-AB 7-19–21
BPZ:5470680001 Protection seal DMZ1197-AD 5-16, 5-18, 5-22, 5-24, 7-
23, 9-35
BPZ:5644230001 U-rail TS35/7.5/288 TS35_288 2-20, 5-36, 5-42
BPZ:5644780001 U-rail TS35/7.5/122 TS35_122 2-20, 5-36, 5-42
BPZ:5757970001 Alarm device for explosion-hazard areas of zones 1 and 2 DB3 9-38
BPZ:5762200001 Radio test set DZW1171 9-21
BPZ:9300100001 Fire control panel for connection to 12 VDC supply GEN2-es 3-3
BPZ:9300110001 Fire control panel for connection to 12 VDC supply GEN2-en 3-2
BPZ:9300120001 Fire control panel for connection to 12 VDC supply GEN2-it 3-2
BPZ:9300130001 Fire control panel for connection to 12 VDC supply GEN2-se 3-2
BPZ:9300150001 Fire control panel for connection to 12 VDC supply GEN2-de 3-2
BPZ:9300170001 Fire control panel PCB for all languages MGEN2 3-3
BPZ:9300180001 Fire control panel for connection to 12 VDC supply GEN2-fr 3-2
BPZ:9300190001 Fire control panel for connection to 12 VDC supply GEN2-nl 3-2
DC1192-I__ Input/output module for galvanic isolation DC1192-I__ 9-25
DF11Ex__ Infrared flame detector collective 'Ex' DF11Ex__ 9-31
DM1101__ Collective manual call point DM1101__ 7-17
DM1103(Ex)__ Collective manual call point (double action) for explosion-hazard areas
DM1103(Ex)__ 9-33
DM1103__ Collective manual call point DM1103__ 7-20
DM1104(Ex)__ Collective manual call point (single action) for explosion-hazard areas
DM1104(Ex)__ 9-34
DM1104__ Collective manual call point DM1104__ 7-19
FC1002.. 2-zone conventional unit FC1002.. 3-6
FC1004.. 4-zone conventional unit FC1004.. 3-8
FC1008.. 8-zone conventional unit FC1008.. 3-10
FC1012.. 12-zone conventional unit FC1012.. 3-14
FC721.. Fire control panel (1-loop) in housing (Eco) FC721.. 1-3
FC722.. Fire control panel (2-loop) in housing (Standard) FC722.. 2-4
FC724.. Fire control panel (4-loop) FC724.. 2-11
FC726.. Fire control panel (modular) FC726.. 2-16
Order No. Index
8 © Siemens Switzerland Ltd 2010
Order No. Description Type Page
FDF__ Infrared flame detector FDF__ 9-2
FDL__ ASA Linear smoke detector FDL__ 9-5
FDM221__ Manual call point FDM221__ 5-8
FDM223__ Manual call point FDM223__ 5-20
FDM223H__ Manual call point 'Heavy Duty' FDM223H__ 5-23
FDM224__ Manual call point FDM224__ 5-14
FDM224H__ Manual call point 'Heavy Duty' FDM224H__ 5-17
FT724.. Fire terminal FT724.. 2-30
GEN2.. Fire control panel for connection to 12 VDC supply GEN2.. 3-2
MM8000xxx MM8000 danger management station MM8000xxx 14-2
S24217-G34-A1 Key S24217-G34-A1 9-21
S24218-B102-A1 Input/output module 'Transponder' FDCIO223 5-41, 9-23
S24218-F316-A1 Base for radio smoke detector DBW1171 9-18
S24218-F62-A5 Radio smoke detector complete DOW1171/DBW1171 9-17
S24218-F62-A6 Radio smoke detector DOW1171 9-18
S24218-F72-A1 Radio base SMF6120 9-20
S24236-B2502-A1 Repeater (SAFEDLINK) FN2002-A1 2-26
S54310-F1-A1 Optical smoke detector OP720 5-3
S54310-F2-A1 Multi-sensor smoke detector OH720 5-3
S54310-F3-A1 Heat detector (static) HI722 5-4
S54310-F4-A1 Heat detector (static+RoR) HI720 5-4
S54311-F2-A1 Housing orange‚ with glass and key FDMH293-O 5-14–15,
5-20–21
S54312-F1-A1 Input module FDCI221 5-37
S54312-F2-A1 Input/output module FDCIO221 5-38
S54312-F3-A1 Housing for input/output modules FDCH221 2-20, 5-42, 9-23
S54312-F6-A1 Multi-line separator module FDCL221-M 5-36
S54319-F1-A1 Detector base flat‚ addressable FDB222 5-29
S54319-F10-A1 Sealing element FDBZ295 5-29
S54319-F11-A1 Detector base with loop contact DB721 5-5
S54319-F5-A1 Sounder base DBS720 5-6, 5-32
S54319-F6-A1 Detector exchanger DX791 10-2
S54319-F8-A1 Detector base seal RS720 5-6, 5-32
S54319-F9-A1 Detector locking device LP720 5-5
S54370-F10-A1 Addressable alarm indicator FDCAI221 6-2
S54370-F3-A1 Alarm indicator - Surface FDAI92 6-1, 7-24
S54370-F4-A1 Alarm indicator - Surface for explosion-hazard areas FDAI92-Ex 9-36
S54370-F5-A1 Alarm indicator - Flush FDAI93 6-1, 7-25
S54370-F6-A1 Alarm indicator - Flush FDAI93-Ex 9-36
S54370-F7-A1 Alarm indicator - Door frame AI91C 7-9
S54370-F8-A1 Alarm indicator - Surface AI92C 7-9
S54370-F9-A1 Alarm indicator - Door frame FDAI91 6-1, 7-24
S54370-N4-A1 Solo719 Adapter for FDUM29x RE7T-A 10-4
S54370-N5-A1 Solo760 Battery for RE7T RE7T-B 12-11
S54370-N6-A1 Solo725 Charger for RE7T RE7T-C 12-11
S54370-S3-A1 Solo461 Heat detector tester kit RE7T 10-3
Order No. Index
9© Siemens Switzerland Ltd 2010
Order No. Description Type Page
S54371-F6-A1 Manual call point with glass plate FDM1101-RG 7-15
S54371-F6-A2 Manual call point with resettable plastic element FDM1101-RP 7-15
S54371-F6-A3 Manual call point with glass plate FDM1101A-RG 7-6
S54371-F6-A4 Manual call point with resettable plastic element FDM1101A-RP 7-6
S54380-B11-A1 EVAC module FCA1009-E 12-3
S54380-C1-A10 Main board for 8-zone units FCM1008 12-4
S54380-C1-A20 FCM1008-D Main board 8 zone CH FCM1008-D 12-4
S54380-C1-A30 FCM1008-E Main board 8 zone NL FCM1008-E 12-4
S54380-C2-A1 2-zone conventional unit (Standard) FC1002-A 3-6
S54380-C2-A10 2-zone conventional unit (Head removal monitoring) FC1002-B 3-6
S54380-C2-A20 2-zone conventional unit (Nordic) FC1002-C 3-6
S54380-C3-A1 4-zone conventional unit (Standard) FC1004-A 3-8
S54380-C3-A10 4-zone conventional unit (Head removal monitoring) FC1004-B 3-8
S54380-C3-A20 4-zone conventional unit (Nordic) FC1004-C 3-8
S54380-C3-A30 4-zone conventional unit (NL) FC1004-E 3-8
S54380-C4-A1 8-zone conventional unit (Standard) FC1008-A 3-10
S54380-C4-A10 8-zone conventional unit (Head removal monitoring) FC1008-B 3-10
S54380-C4-A20 8-zone conventional unit (Nordic) FC1008-C 3-11
S54380-C4-A30 8-zone conventional unit (CH) FC1008-D 3-11
S54380-C4-A40 8-zone conventional unit (Evacuation) FC1008-E 3-11
S54380-C5-A1 12-zone conventional unit (Standard) FC1012-A 3-14
S54380-C5-A10 12-zone conventional unit (Head removal monitoring) FC1012-B 3-14
S54380-C5-A20 12-zone conventional unit (Nordic) FC1012-C 3-15
S54380-C8-A1 Main board 2-zones FCM1002 12-4
S54380-C9-A1 Main board 4-zones FCM1004 12-4
S54380-C9-A10 FCM1004-E Main board 4 zone NL FCM1004-E 12-4
S54380-F10-A1 Cover for the FC1008-E FCH1008-E 12-4
S54390-A4-A1 Main board XCM1002 12-5
S54390-A5-A1 Multi-zone extension module XCA1030 4-5
S54390-A6-A1 Common multi-zone module XCA1031 4-5
S54390-B10-A1 Cover set XCH1003-A 12-5
S54390-B11-A1 Cover set XCH1005-A 12-5
S54390-B7-A1 Display adapter XCA1002-1 12-5
S54390-B8-A1 Display adapter XCA1002-2 12-5
S54390-B9-A1 Cover set XCH1001-A 12-5
S54390-C1-A1 Extinguishing panel Standard XC1001-A 4-2
S54390-C2-A1 Extinguishing panel Rack XC1003-A 4-4
S54390-C3-A1 Extinguishing panel Comfort XC1005-A 4-3
S54390-N12-A1 Transformer for 2/4-zone units FCP1002 12-4
S54390-Z15-A1 Repeater display XT1002-A1 4-7
S54390-Z16-A1 Repeater display XT1001-A1 4-7
S54400-A14-A1 Mimic display driver (EVAC) FT2003-N1 2-24
S54400-A15-A1 EVAC-NL connector board FTI2002-N1 2-24
S54400-A6-A1 I/O card (programmable) FCI2008-A1 2-18
S54400-B70-A1 Housing (Standard) FH7202-Z3 1-7, 2-22
S54400-B71-A1 Housing (Comfort) FH7203-Z3 2-22–23
S54400-B72-A1 Housing (Eco) FH7201-Z3 1-6, 2-21, 2-33
S54400-B74-A1 Cover cap (without print) FHA7202-A3 12-1
S54400-B77-A1 Cover cap (Cerberus) FHA7201-A3 12-1
S54400-B79-A1 Mounting kit for housing (Comfort) FHA2029-A1 2-27
Order No. Index
10 © Siemens Switzerland Ltd 2010
Order No. Description Type Page
S54400-B81-A1 Mounting kit for housing (Large Extension) FHA2030-A1 2-27
S54400-B86-A1 Housing (Large) FH7205-Z3 2-23
S54400-B89-A1 Housing (Large Extension) FH7204-Z3 2-23
S54400-B90-A1 Battery holder FCA1016 3-7, 3-9
S54400-C29-A1 Fire control panel (2-loop) in housing (Comfort) with 2 LED indi-cators
FC722-ZE 2-8
S54400-C29-A2 Fire control panel (2-loop) in housing (Comfort) FC722-ZA 2-7
S54400-C29-A3 Fire control panel (2-loop) in housing (Comfort) with EVAC oper-ating unit
FC722-HA 2-9
S54400-C29-A4 Fire control panel (2-loop) in housing (Standard) with 1 LED indi-cator
FC722-YZ 2-6
S54400-C29-A5 Fire control panel (2-loop) in housing (Standard) FC722-ZZ 2-5
S54400-C30-A1 Fire control panel (4-loop) with EVAC operating unit FC724-HA 2-14
S54400-C30-A2 Fire control panel (4-loop) FC724-ZA 2-12
S54400-C30-A3 Fire control panel (4-loop) with 2 LED indicators FC724-ZE 2-13
S54400-C31-A1 Fire terminal with EVAC operating unit FT724-HZ 2-31
S54400-C31-A2 Fire terminal FT724-ZZ 2-30
S54400-C32-A1 Fire control panel (1-loop) in housing (Eco) with EVAC operating unit
FC721-HZ 1-5
S54400-C32-A2 Fire control panel (1-loop) in housing (Eco) FC721-ZZ 1-4
S54400-C32-A3 Fire control panel (1-loop) in housing (Eco) with 1 LED indicator FC721-YZ 1-4
S54400-C87-A1 Fire control panel (modular) FC726-ZA 2-17
S54400-F34-A1 Floor repeater terminal FT2010-C1 5-44
S54400-F75-A1 Operating add-on (2xLED ind.) FCM7211-Y3 2-23–24,
2-33,12-1
S54400-F76-A1 Operating add-on FCM7210-Z3 12-1
S54400-F78-A1 Operating add-on (2xEVAC) FCM7221-H3 2-24
S54400-F88-A1 Operating add-on (4xLED ind.) FCM7212-Y3 2-24, 2-33, 12-2
S54400-F94-A1 Ethernet switch FN2008-A1 2-27
S54400-F95-A1 Security module FN2009-A1 2-27
SMF__ Manual call point SMF__ 9-20
V24069-Z112-A1 Lithium battery 3.6 V / 2.1 Ah V24069-Z112-A1 9-20
V24217-C1218-W100 Manual call point SMF121 9-20–21
V24217-C1218-W200 Manual call point SMF121 9-20–21
V24230-Z6-A4 Power supply (150 W) SV 24V-150W 12-1
VLF-250-SIE Aspirating smoke detector with display LaserFOCUS VLF-250 9-14
VLF-500-SIE Aspirating smoke detector with display LaserFOCUS VLF-500 9-15