253
Answers for infrastructure. www.siemens.com/cerberus Answers for infrastructure. Q Megatrends driving the future The megatrends – demographic change, urbanization, climate change, and glo- balization – are shaping the world today. These have an unprecedented impact on our lives and on vital sectors of our economy. Q Innovative technologies to answer the associated toughest questions Throughout a 160-year history of pro- ven research and engineering talent, with more than 50,000 active patents, Siemens has continuously provided its customers with innovations in the areas of healthcare, energy, industry, and infrastructure – globally and locally. Q Increase productivity and efficiency through complete building life cycle management Building Technologies offers intelligent integrated solutions for industry, com- mercial and residential buildings, and public infrastructure. Over the entire facility’s life cycle, our comprehensive and environmentally conscious port- folio of products, systems, solutions, and services for low-voltage power distribution and electrical installation technology, building automation, fire safety and security ensures the: optimum comfort and highest energy efficiency in buildings, safety and security for people, processes and assets, , – increased business productivity. The information in this document contains general descriptions of technical options available, which do not always have to be present in individual cases. The required features should therefore be specified in each individual case at the time of closing the contract. © Siemens Switzerland Ltd, 2010 • Order no. 0-92238-en • 1,51007 Siemens Switzerland Ltd Industry Sector Building Technologies Division International Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel +41 41 724 24 24 Cerberus PRO product catalog Fire safety products and accessories Cerberus PRO product catalog

Upload: lethuan

Post on 16-Apr-2018

282 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Answers for infrastructure.www.siemens.com/cerberus

Answers for infrastructure. Megatrends driving the future

The megatrends – demographic change, urbanization, climate change, and glo-bali zation – are shaping the world today. These have an unprecedented impact on our lives and on vital sectors of our economy.

Innovative technologies to answer the associated toughest questions

Throughout a 160-year history of pro-ven research and engineering talent, with more than 50,000 active patents, Siemens has continuously provided its customers with innovations in the ar eas of healthcare, energy, industry, and in frastructure – globally and locally.

Increase productivity and efficiency through complete building life cycle management

Building Technologies offers intelligent integrated solutions for industry, com-mercial and residential buildings, and public infrastructure. Over the entire fa cility’s life cycle, our comprehensive and environmentally conscious port - fo lio of products, systems, solutions , and services for low-voltage power distribution and electrical installation technology, building automation, fire safety and security ensures the:– optimum comfort and highest energy

efficiency in buildings,– safety and security for people,

processes and assets,,– increased business productivity.

The information in this document contains general descriptions of technical options available, which do not always have to be present in individual cases. The required features should therefore be specifi ed in each individual case at the time of closing the contract.

© Siemens Switzerland Ltd, 2010 • Order no. 0-92238-en • 1,51007

Siemens Switzerland LtdIndustry SectorBuilding Technologies DivisionInternational HeadquartersGubelstrasse 226301 ZugSwitzerlandTel +41 41 724 24 24

Cerberus PRO product catalogFire safety products and accessories

Cer

ber

us

PR

O p

rod

uct

cat

alo

g

Page 2: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Table of Contents

1© Siemens Switzerland Ltd 2010

Stand-alone Fire Control Panels........................................................................................... 1-1

FC72x Compact Fire Control Panels .................................................................................. 1-2

FC721 Series ............................................................................................................. 1-3

Expansion FC721....................................................................................................... 1-6

Accessories FC721 ..................................................................................................... 1-9

Fire Control Network Participants........................................................................................ 2-1

FC72x Networkable Fire Control Panels ............................................................................ 2-2

FC722 Series ............................................................................................................. 2-4

FC724 Series ........................................................................................................... 2-11

FC726 Series ........................................................................................................... 2-16

Expansion FC72x ..................................................................................................... 2-18

Network Components Cluster (C-WEB/SAFEDLINK) ................................................... 2-26

Network Components Backbone (C-WEB/LAN).......................................................... 2-27

Accessories FC72x ................................................................................................... 2-28

FT724 Networkable Fire Operating Terminals ................................................................. 2-30

FT724 Operating Terminal to FC72x......................................................................... 2-30

Expansion FT724 ..................................................................................................... 2-32

Accessories FT724 ................................................................................................... 2-35

Conventional Fire Control Panels......................................................................................... 3-1

1-zone Panels .................................................................................................................. 3-2

Genesis Series ........................................................................................................... 3-2

2-zone Panels .................................................................................................................. 3-6

FC10 Series ............................................................................................................... 3-6

Accessories FC1002 ................................................................................................... 3-7

4-zone Panels .................................................................................................................. 3-8

FC10 Series ............................................................................................................... 3-8

Accessories FC1004 ................................................................................................... 3-9

8-zone Panels ................................................................................................................ 3-10

FC10 Series ............................................................................................................. 3-10

Expansion FC1008................................................................................................... 3-12

Accessories FC1008 ................................................................................................. 3-13

12-zone Panels .............................................................................................................. 3-14

FC10 Series ............................................................................................................. 3-14

Expansion FC1012................................................................................................... 3-16

Accessories FC1012 ................................................................................................. 3-17

Conventional Extinguishing Control Panels......................................................................... 4-1

Connectable to Fire Detection Systems............................................................................. 4-2

XC10 Series ............................................................................................................... 4-2

Expansion XC10......................................................................................................... 4-5

Accessories XC10....................................................................................................... 4-6

XT10 Series ............................................................................................................... 4-7

Fire Detection Network (C-NET) Peripherals ........................................................................ 5-1

Addressable Fire Detectors ............................................................................................... 5-3

Point Detectors .......................................................................................................... 5-3

Addressable Manual Call Points ........................................................................................ 5-8

MCP with Direct Operation......................................................................................... 5-8

MCP with Indirect Operation .................................................................................... 5-19

Alarm Equipment........................................................................................................... 5-25

Alarm Sounders‚ Alarm Sounder Beacon................................................................... 5-25

Bases for Alarm Sounders‚ Alarm Sounder Beacon .................................................... 5-29

Sounder Base for Automatic Detectors ..................................................................... 5-32

Page 3: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Table of Contents

2 © Siemens Switzerland Ltd 2010

Addressable Modules ..................................................................................................... 5-35

Line Separator ......................................................................................................... 5-35

Input Modules ......................................................................................................... 5-37

Input/Output Modules.............................................................................................. 5-38

Accessories for Input-‚ Input/Output Modules ........................................................... 5-42

Floor Repeater Panels‚ Mimic Display .............................................................................. 5-43

Floor Repeater Terminals ......................................................................................... 5-43

Floor Repeater Display ............................................................................................. 5-45

Mimic Display Driver ................................................................................................ 5-46

Visual Parallel Alarm Indicators............................................................................................ 6-1

Alarm Indicators............................................................................................................... 6-1

AI Series for C-NET Devices......................................................................................... 6-1

Fire Detection Collective Peripherals ................................................................................... 7-1

Conventional Line SynoLINE300....................................................................................... 7-3

Conventional Detectors Synova 300 Series ................................................................. 7-3

Conventional Manual Call Points ................................................................................ 7-6

Alarm Indicators for SynoLINE300 .............................................................................. 7-9

Collective Line SynoLINE600 .......................................................................................... 7-10

Collective Detectors AlgoRex Series .......................................................................... 7-10

Collective Manual Call Points.................................................................................... 7-15

Alarm Indicators for SynoLINE600 ............................................................................ 7-24

Conventional Alarm Equipment........................................................................................... 8-1

Sounders ......................................................................................................................... 8-1

Optical Signaling Equipment ............................................................................................ 8-3

Special Applications ............................................................................................................. 9-1

Special Detectors ............................................................................................................. 9-2

Infrared Flame Detectors............................................................................................ 9-2

Linear Smoke Detectors ............................................................................................. 9-5

Air Sampling Smoke Detection ................................................................................. 9-10

Aspirating Smoke Detection ..................................................................................... 9-14

Radio Fire Detection Wireless System ....................................................................... 9-16

Explosion-Hazard Area Products ..................................................................................... 9-22

Interface to C-NET.................................................................................................... 9-23

Interface to Collective Line SynoLINE600.................................................................. 9-25

Ex-Barrier................................................................................................................. 9-27

Point Detectors Ex-Series.......................................................................................... 9-28

Infrared Flame Detector Ex-Series............................................................................. 9-31

Manual Call Points ................................................................................................... 9-33

Alarm Indicators Ex-Series ........................................................................................ 9-36

Alarm Device ........................................................................................................... 9-38

Special Equipment.............................................................................................................. 10-1

Test Equipment.............................................................................................................. 10-2

Detector Tester ........................................................................................................ 10-2

Detector Tester for Special Detectors........................................................................ 10-6

Line Tester............................................................................................................... 10-8

Interface ........................................................................................................................ 10-9

Adapter for C-NET Devices........................................................................................ 10-9

Batteries ............................................................................................................................. 11-1

Spare Parts.......................................................................................................................... 12-1

Fire Control Panels FC72x and Operating Terminals FT724‚ Printers................................. 12-1

Conventional Fire Control Panels FC10 ........................................................................... 12-3

Extinguishing Control Panels XC10 ................................................................................. 12-5

Manual Call Points ......................................................................................................... 12-6

Input Modules‚ Input/Output Modules‚ Alarm Indicator ................................................... 12-8

Test Equipment.............................................................................................................. 12-9

Page 4: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Table of Contents

3© Siemens Switzerland Ltd 2010

Repair Parts ........................................................................................................................ 13-1

Fire Control Panels FC72xx and Operating Terminals FT724xx ........................................ 13-1

Operating Units and Add-on..................................................................................... 13-1

Periphery Boards‚ Expansion Modules and Power Supply................................................. 13-2

Floor Repeater Panels..................................................................................................... 13-4

Danger Management System ............................................................................................ 14-1

MM8000 Management Station ...................................................................................... 14-2

System Overview ............................................................................................................... 15-1

Control Panels‚ Networks‚ Accessories............................................................................. 15-2

C-NET Devices................................................................................................................ 15-4

Page 5: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Answers for infrastructure.

Cerberus PRO – enjoy protecting!The new generation of a smart fi re safety system.

Protecting people and assets. Securing business processes and continuity. This is what fi re protection is all about. Cerberus® PRO from Siemens is a smart fi re safety system for fast, reliable fi re detection, alarm signaling and control. Its broad portfolio comprises powerful control panels from stand-alone to networkable units, reliable detectors with patented technology and a comprehensive range of loop-powered peripheral devices. All system components have special safety features installed that increase safety even further – such as degrade mode in control panels or built-in isolators in each detector and periph-eral device. For more information, please visit www.siemens.com/cerberus

Does anyone know a clever fi re safety system starting with a “C”?

090026_AZ_Cerberus_Image_03RZ.indd 1 30.07.09 09:41

,

Page 6: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

C-NET

C-NET

Backbone (C-WEB/LAN)

C-NET

Cluster (C-WEB/SAFEDLINK)

Customer network Ethernet

Remote access with Cerberus-Remote

Danger management system from Siemens

Ethernet switch FN2008-A1

Ethernet switch FN2008-A1

Ethernet switch FN2008-A1

Ethernet switch FN2008-A1

Security module (fi rewall) FN2009-A1

Security module (fi rewall)

FN2009-A1

Sounder base DBS720

Alarm sounderFDS221

Floor repeater terminal FT2010

Manual call point

FDM221

Fire control panelFC722

Fire control panel FC722

Fire terminal FT724

Fire control panel

FC724

Fire control panel FC726

Fault transmission

Alarm transmission

Input/output moduleFDCIO222

Optical smoke detector OP720

Floor repeater display FT2011

Alarm sounder beaconFDS229-R

Heat detector HI722

Sinorix extinguishing solution

Extinguishing control unit XC10

Multi-sensor smoke detector OH320C

Fire control panel FC724

Flame detector FDF241-9

Heat detector HI720Multi-sensor

smoke detector OH720

Opticalsmoke detector OP720

Stub line

Input moduleFDCI222

Radio gatewayFDCW221

Radio smoke detectorDOW1171

Safety barrier SB3

Smoke detector DO1101A-Ex

Linear smoke detector

FDL241-9

LaserFOCUSVLF-500

Mimic display driver FT2001-A1

Input/output module “transponder”

FDCIO223

Manual call point

FDM223Manual release

Cerberus PRO – enjoy protectingPowerful control panels, clever fi re detectors, and smart peripheral devices. This is what our comprehensive Cerberus® PRO family offers. The brief overview below demonstrates the most important system components.

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 2 28.05.10 16:56

Page 7: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Compatibility chart

Compatible

( ) Compatible with an interface

Addressable devices

Optical detec-

tor

Multi-sensor detec-

tor

Heat detectors

Manual call points

OP7

20

OH

72

0

HI7

20

st

atic

an

d r

ate

of

rise

HI7

22

st

atic

FDM

22

1

FDM

22

5/F

DM

22

6

FDM

22

4/F

DM

22

4H

FDM

22

3/F

DM

22

3H

Stand-alone addressable fi re control panel

FC721 (1 loop)

Networkable addressable fi re control panels

FC722 (2 loops)

FC724 (4 loops)

FC726 (4 loops)

Conventional fi re control panels

Genesis (1 zone)

FC10 (2 – 12 zones)

Conventional extinguishing control panel

XC10

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 3 28.05.10 16:56

Page 8: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional and collective devices Special applications

Optical detector

Multi-sensor detec-

tor

Heat detectorsManual call

pointsSpecial detectors

OP3

20

C

DO

11

01

Ah

arsh

en

viro

nm

en

t

DO

11

04

Ah

igh

se

nsi

tivi

ty

OH

32

0C

HI3

22

Cra

te o

f ri

se a

nd

max

imu

m

HI3

22

Cm

axim

um

DT1

10

1A

rate

of

rise

, har

sh e

nvi

ron

me

nt

DT1

10

2A

rate

of

rise

an

d m

ax, h

arsh

en

viro

nm

.

DM

11

01

/FD

M1

10

1A

/FD

M1

10

1

DM

11

03

(IP

65

)/D

M1

10

4 (

IP6

5)

FDF2

21

-9In

frar

ed

fl a

me

de

tect

or,

sin

gle

ch

ann

el

FDF2

41

-9

Infr

are

d fl

am

e d

ete

cto

r, t

hre

e c

han

ne

ls

FDL2

41

-9Li

ne

ar s

mo

ke d

ete

cto

r

Lase

rFO

CU

S V

LF-2

50

/VLF

-50

0A

spir

atin

g s

mo

ke d

ete

ctio

n

Ex

de

tect

ors

Rad

io fi

re

de

tect

ors

( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( )

( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( )

( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( )

( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( )

( )

( )

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 4 28.05.10 16:56

Page 9: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Protecting people and assets reliably Protecting people and assets. Securing business processes and continuity. This is what fi re protection is all about. Cerberus® PRO is a powerful fi re protection system for fast, reliable fi re detection, alarm signaling, and control. Its wide portfolio of inno vative products provides clever technology with extensive safety features.

Protecting people and assets reliably with Siemens products

The Cerberus PRO family comprises differ- ent control panels, fi re detectors, periph-eral devices, and accessories. They all have one thing in common: smart, unique safety features. For example, all periph -eral devices, even fi re terminals, have built-in isolators. Thus, even with faults such as an open or a short circuit the sys-tem remains fully operational and faults can be quickly located. Degrade mode functionality is integrated throughout the system, ensuring detection, control, alarming, and fi re brigade communication even in the event of a pro cessor failure.

Cerberus PRO fi re detectors also increase safety thanks to their distributed intelli-gence: decisions are made on the spot in the detector. As a result, unshielded cabling can be used, making Cerberus PRO easy to plan and install. In short: Cerberus PRO is the smart answer to your fi re safety needs.

Creating networks in various sizesCerberus PRO is a straightforward fi re protection system. It offers all from stand-alone to networkable control panels. The uniform hardware concept of the panels facilitates the planning process. Even large, campus-wide networks can be easily

Highlights

Smart, unique safety features – such as built-in isolators and integrated degrade mode

Easy planning – even for campus-wide networks

Extended network possibilities for widely distributed or complex buildings

Safe and easy commissioning – thanks to auto-confi guration

Integration into the danger manage-ment system from Siemens possible

Broad range of fi re detectors – to cover various requirements

Cerberus PRO portfolio – reliable, high-quality products from Siemens

realized with little additional planning. Simply connect up to 14 clusters (C-WEB/SAFEDLINK) to an EN 54-approved fi ber-optic backbone (C-WEB/LAN). The indus-trial LAN technology also enables you to optimally adapt Cerberus PRO to any building or process structure. In addition, Cerberus PRO can be integrated into an existing IT network. Information can then be distributed across a network, further enhancing system usability.

Commissioning of the system is safe and easy thanks to auto-confi guration. It enables instant fi re protection during the construction phase, supporting on-time handover. Moreover, Cerberus PRO can be integrated into the danger manage-ment system from Siemens. Your benefi t: You can connect fi re protection with other security-related subsystems such as access control or intrusion detection.

Relying on experience Siemens is known for innovation power, technology leadership, and high quality. We were the fi rst manufacturer to offer automatic fi re detectors. Our products are backed by decades of experience and know-how. We will continue to further extend our Cerberus PRO portfolio. Compatibility of future add-ons is a matter of course – making Cerberus PRO a safe investment.

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 5 28.05.10 16:56

Page 10: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Stand-alone Fire Control PanelsFire Control Network Participants

Ensuring comprehensive safety with powerful panelsCerberus® PRO fi re control panels combine high security standards with the latest technology. Competitive for simple applications, yet powerful enough for every application – they are the ideal choice whatever the size and complexity of a project. The Cerberus PRO family offers four models, covering small to very large application areas. They can either stand alone or be networked into a larger system. Furthermore, all panels can be accessed either remotely or on site.

A competitive range of control panels – with unique features to put the system into operation quickly and safely

Networking possibilities – to realize redundant and EN 54-approved networks Simple networking of control panels and fi re terminals Extended network possibilities – with industrial LAN technology for widely distributed or complex buildings

Easy and intuitive to operate – to ensure right action in case of an event Remote access – for remote and cost-effi cient servicing Fire terminals for additional, remote system user interfaces – such as in the security monitoring room or the reception area

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 6 28.05.10 16:56

Page 11: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Stand-alone addressable fi re control panel FC721*

2x batteries max. 12 V/7 AhFA2003-A1

Up to 2 relay modules Z3B171

Cable kit (communication) FCA2014-A1

RS485 module FCA2002-A1 or RS232 moduleFCA2001-A1

Key switch (Kaba)FTO2005-C1 or Key switch (Nordic) FTO2006-B1

License key (L1) FCA2012-A1 for Cerberus-Remote

* Control panel shown with 24 indicator groups, each with one red and one yellow LED

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 7 28.05.10 16:56

Page 12: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Stand-alone Fire Control PanelsFC72x Compact Fire Control PanelsFC721 Series

1-3© Siemens Switzerland Ltd 2010

1

Type Order No.

FC721.. Fire control panel (1-loop) in housing (Eco)

The FC721.. is a compact fire control panel with integrated operating unit that can process signals from Cerberus PRO devices of up to 126 addresses.The fire control panel may be used as a stand-alone unit only.In addition‚ an Ethernet connection is available at each station. Via this fast Ethernet interface remote control service is possible. All detector lines are monitored for ground faults.The Cerberus-Engineering-Tool permits the system to be adapted to specific customers' requirements. Up to 2000 events can be stored according to various criteria. Automatic summer/winter change. Detec-tion and automatic read-in (auto-configuration) of all C-NET devices‚ providing immediate simple operation. Stored data can be uploaded via Cerberus-Remote access.The FC721.. is ideally suited for smaller applications‚ e.g. in workshops‚ hotels‚ etc.The expansion and accessories must be ordered separately.

Detector compatibility Cerberus PRO FD720

Number of addresses max. 126

Number of detector lines 1 loop or 2 stub lines

Programmable input/output 4

Relay outputs

Supervised output 1 x RT alarm1 x RT fault1 x Horn

Mains voltage 85… 265 VAC

Operating voltage 21… 28.6 VDC

Operating current max. 2.5 A

Power supply 70 W

Emergency power supply up to 72 h (optional)

Battery capacity 2 x 12 V‚ 7 Ah

Plug-in position 1 -> for serial interface RS232 or RS485

Operating temperature -8… +42 °C

Storage temperature -20… +60 °C

Relative humidity L95 % (no condensation)

Protection category IP30

Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design 050 00 00

Cabinet dimensions (W x H x D) 430 x 398 x 80 mm

Data sheet A6V10203220

FC721..

01.fm Seite 3 Mittwoch, 28. Juli 2010 9:08 09

Page 13: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Stand-alone Fire Control PanelsFC72x Compact Fire Control PanelsFC721 Series

1-4 © Siemens Switzerland Ltd 2010

Type Order No.

FC721-ZZ Fire control panel (1-loop) in housing (Eco)

See FC721.. for technical overview and note the additional / other specifications:

Expansion FCA2012-A1 License key (L1)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FH7201-Z3 Housing (Eco)FH7202-Z3 Housing (Standard)

Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (Communica-tion)DL3750+ Matrix printer (Extern)

S54400-C32-A2

FC721-YZ Fire control panel (1-loop) in housing (Eco) with 1 LED indicator

See FC721.. for technical overview and note the additional / other specifications:

With 24 indicator groups‚ each with one red and one yellow LED.

Expansion FCA2012-A1 License key (L1)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FH7201-Z3 Housing (Eco)FH7202-Z3 Housing (Standard)

Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (Communica-tion)DL3750+ Matrix printer (Extern)

S54400-C32-A3

01.fm Seite 4 Mittwoch, 28. Juli 2010 9:08 09

Page 14: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Stand-alone Fire Control PanelsFC72x Compact Fire Control PanelsFC721 Series

1-5© Siemens Switzerland Ltd 2010

1

Type Order No.

FC721-HZ Fire control panel (1-loop) in housing (Eco) with EVAC operating unit

See FC721.. for technical overview and note the additional / other specifications:

With 10 evacuation operating zones for Netherlands.

Expansion FCA2012-A1 License key (L1)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FH7201-Z3 Housing (Eco)FH7202-Z3 Housing (Standard)

Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (Communica-tion)DL3750+ Matrix printer (Extern)

S54400-C32-A1

01.fm Seite 5 Mittwoch, 28. Juli 2010 9:08 09

Page 15: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Stand-alone Fire Control PanelsFC72x Compact Fire Control PanelsExpansion FC721

1-6 © Siemens Switzerland Ltd 2010

Type Order No.

FCA2012-A1 License key (L1)

iButton with license for:Sinteso™ -> SintesoViewCerberus® PRO -> Cerberus-RemoteOnly one license key is required per station.

A5Q00018856

FCA2001-A1 RS232 module (isolated)

Module for periphery devices with RS232 interface‚ e.g. for event print-er FTO2001-A1. Plugged into the back side of the operating unit.RS232 module incl. 1 EMC screwed cable gland M10 x 1.5.

Cable capacity 0.2… 1.5 mm2

Dimensions (W x H x D) 50 x 15 x 70 mm

A5Q00005327

FCA2002-A1 RS485 module (isolated)

Module for periphery devices with RS485 interface‚ e.g. for FAT (GER). Plugged into the back side of the operating unit.RS485 module incl. 1 EMC screwed cable gland M10 x 1.5.

Cable capacity 0.2… 1.5 mm2

Dimensions (W x H x D) 50 x 15 x 70 mm

A5Q00009923

FH7201-Z3 Housing (Eco)

Empty housing for open use‚ e.g. power supply kit with batteries‚ oper-ating add-on‚ event printer or mimic display.

Cabinet dimensions (W x H x D) 430 x 398 x 80 mm

Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design 050 00 00

Protection category IP30

Integral battery space 2 x FA2003-A1 (7 Ah)

Expansion FTO2001-A1 Event printerFCM7211-Y3 Operating add-on (2xLED-ind.)FCM7212-Y3 Operating add-on (4xLED-ind.)FP2003-A1 Power supply kit (70 W)

S54400-B72-A1

01.fm Seite 6 Mittwoch, 28. Juli 2010 9:08 09

Page 16: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Stand-alone Fire Control PanelsFC72x Compact Fire Control PanelsExpansion FC721

1-7© Siemens Switzerland Ltd 2010

1

Type Order No.

FH7202-Z3 Housing (Standard)

Empty housing for open use‚ e.g. power supply kit with batteries‚ oper-ating add-on or for the event printer.

Cabinet dimensions (W x H x D) 430 x 398 x 160 mm

Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design 050 00 00

Protection category IP30

Integral battery space 2 x FA2003-A1 (7 Ah) or2 x FA2004-A1 (12 Ah) or2 x FA2006-A1 (26 Ah)

Expansion FTO2001-A1 Event printerFCM7211-Y3 Operating add-on (2xLED-ind)FCM7212-Y3 Operating add-on (4xLED-ind)FP2003-A1 Power supply kit (70 W)FP2004-A1 Power supply kit (150 W‚ A)FP2005-A1 Power supply kit (150 W‚ B)

S54400-B70-A1

FTO2001-A1 Event printer

The event printer is a thermal printer that logs alarms‚ faults and gener-al messages. The event printer can be used in all control panels if space is available. The RS232 module is required to operate the printer. Event printer includes cables for interface and power supply and a paper roll.The RS232 module FCA2001-A1 must be ordered separately.

Operating voltage 9… 48 VDC

Quiescent current 50 mA

Operating current 3 A @ 9 VDC0.7 A @ 48 VDC

Interface RS232 serial

Operating temperature 0… +50 °C

Storage temperature -20… +70 °C

Relative humidity L95 % (no condensation)

Dimensions (W x H x D) 85 x 85 x 55 mm

A5Q00010126

FP2003-A1 Power supply kit (70 W)

Auxiliary power supply to all stations (control panels and terminals).Converts mains voltage to system voltage. Monitors mains voltage and batteries.

Supply voltage 85... 265 VAC

Power consumption max. 90 VA

Current 0.5… 1 A

Dimensions (W x H x D) 95 x 170 x 54 mm

A5Q00016005

01.fm Seite 7 Mittwoch, 28. Juli 2010 9:08 09

Page 17: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Stand-alone Fire Control PanelsFC72x Compact Fire Control PanelsExpansion FC721

1-8 © Siemens Switzerland Ltd 2010

Type Order No.

FP2004-A1 Power supply kit (150 W‚ A)

Power supply kit (150 W‚ A) as auxiliary power supply for installation into empty housings.Converts mains voltage to system voltage. Monitors mains voltage and batteries.

Supply voltage 115... 230 VAC

Power consumption max. 300 VA

Current 2.6 / 1.2 A

Dimensions (W x H x D) 130 x 150 x 70 mm

A5Q00020825

01.fm Seite 8 Mittwoch, 28. Juli 2010 9:08 09

Page 18: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Stand-alone Fire Control PanelsFC72x Compact Fire Control PanelsAccessories FC721

1-9© Siemens Switzerland Ltd 2010

1

Type Order No.

FTO2005-C1 Key switch (Kaba)

Kaba key switch with mounting accessories and key (Kaba 8 #100)‚ as an option for operating access (operating unit).

A5Q00010113

FTO2006-B1 Key switch (Nordic)

Nordic key switch with mounting accessories and key (Nordic)‚ as an option for operating access (operating unit).

A5Q00010129

Z3B171 Relay module with 1 contact

The relay module is an additional fire event control module‚ activated by the fire control panel's control output.

Contact rating 250 VAC / 10 A

Delivery unit 10 pieces

BPZ:4843830001

FHA2016-A1 19" mounting kit

To install fire control panels and fire terminals in a 19" third-party hous-ing.

Dimensions (W x H x D) 430 x 100 x 324 mm

A5Q00020179

FCA2014-A1 Cable kit (communication)

For flexible cable connections to the modules on the PMI-& main board.

A5Q00023027

01.fm Seite 9 Mittwoch, 28. Juli 2010 9:08 09

Page 19: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Stand-alone Fire Control PanelsFC72x Compact Fire Control PanelsAccessories FC721

1-10 © Siemens Switzerland Ltd 2010

Type Order No.

DL3750+ Matrix printer external

The Fujitsu DL3750+ is a compact‚ noiseless A4 matrix printer. It is used for documenting relevant information in a system on continuous paper. The printer is constantly supervised by the fire control panel. The type of events to be printed is configurable. It offers a maximum of speed and reliability.The RS232 module FCA2001-A1 is required to operate the printer and must be ordered separately.

Number of copies 5 incl. original

Character set 6

Resolution 360 x 360 dpi

Interface RS232 orEthernet (via Print-Server PS01a)

Operating temperature +5… +38 °C

Storage temperature -15… +60 °C

Relative humidity L95 % (no condensation)

Dimensions (W x H x D) 415 x 120 x 330 mm

A5Q00023962

01.fm Seite 10 Mittwoch, 28. Juli 2010 9:08 09

Page 20: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Answers for infrastructure.

Cerberus PRO – ensuring comprehensive safety with powerful panelsCombining high security standards with the latest technology

Whether small or very large networks – with Cerberus® PRO, you always have the right control panel at hand. They are com petitive for simple applications, yet powerful enough for every application, which makes them the ideal choice what-ever the size and complexity of your project. Moreover, the control panels also offer a great number of safety features such as the degrade mode, which ensures that alarms are still transmitted even if a panel should fail. Cerberus PRO control panels are also easy and intuitive to operate. In the event of an alarm, customized intervention texts facilitate correct actions. An important factor especially in stressful emergency situations when quick and reliable action is essential to save people and assets. You see, Cerberus PRO control panels are always a clever solution. For more information, please visit www.siemens.com/cerberus

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 9 28.05.10 16:56

Page 21: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Networkable addressable fi re control panel FC722 Standard

RS485 module FCA2002-A1 and/or RS232 module FCA2001-A1

Event printer FTO2001-A1

Network module (SAFEDLINK)FN2001-A1

2x batteries max. 12 V/12 AhFA2004-A1

Key switch (Kaba)FTO2005-C1 or Key switch (Nordic) FTO2006-B1

License key (L1) FCA2012-A1 for Cerberus-Remote or License key (L2) FCA2013-A1 for Cerberus-Remote and connection to a danger management system

Up to 3 relay modules Z3B171

Mounting plate FHA2007-A1 for fi re brigade periphery module FCI2001-D1 or sounder module FCA2005-A1

Loop extension FCI2003-A1

Cable kit (communication) FCA2014-A1

FCA2005-A1

or

Sounder module FCA2005-A1

and/or

FCI2001-D1

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 10 28.05.10 16:56

Page 22: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Networkable addressable fi re control panel FC722 Comfort*

Mounting plate FHA2007-A1 for fi re brigade periphery module FCI2001-D1 or sounder module FCA2005-A1

Sounder moduleFCA2005-A1

Event printer FTO2001-A1

2x batteries max. 12 V/24 AhFA2006-A1

Additional power supply kit FP2005-A1

Key switch (Kaba) FTO2005-C1 or Key switch (Nordic) FTO2006-B1

License key (L1) FCA2012-A1 for Cerberus-Remote or License key (L2) FCA2013-A1 for Cerberus-Remote and connection to a danger management system

Up to 6 relay modules Z3B171

Up to 2 loop extensionsFCI2003-A1

Network module (SAFEDLINK)FN2001-A1

RS485 module FCA2002-A1 and/or RS232 module FCA2001-A1

Up to 2 cable kits (communication) FCA2014-A1

* Control panel shown with 48 indicator groups, each with one red and one yellow LED

Sounder moduleFCA2005-A1

and/or

Fire brigade periphery moduleFCI2001-D1

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 11 28.05.10 16:56

Page 23: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC722 Series

2-4 © Siemens Switzerland Ltd 2010

Type Order No.

FC722.. Fire control panel (2-loop) in housing (Standard)

The FC722.. (2-loop‚ expandable to 4) is a compact fire control panel with an integrated operating unit that can process signals from Cer-berus PRO devices of up to 252 addresses. The fire control panel can be used as a stand-alone version or networked. It can be programmed with a user-friendly Cerberus-Engineering-Tool to create a system with great versatility. Up to 32 fire control panels and fire terminals can be con-nected in a single cluster (C-WEB/SAFEDLINK network)‚ or up to 16 pan-els when the cluster is connected to a danger management system. Using a fiber-optic backbone (C-WEB/LAN) up to 14 of these clusters with up to 16 panels each can be networked. This topology enables the construction of an EN 54-conform network with up to 64 fire control panels and fire terminals. In addition‚ an Ethernet connection is availa-ble at each station. This Ethernet connection enables a maximum of 4 stations including a Global Access Point 'GAP' (via Hub) to be networked together and be connected to a Siemens danger management system (not EN 54-compliant).All detector lines are monitored for ground faults.Adaptation of the user text directly on the terminal or with the Cerberus-Engineering-Tool. Up to 2000 events can be stored according to various criteria. Automatic summer/winter time change.Detection and automatic read-in (auto configuration) of all C-NET devices‚ providing immediate simple operation.Stored data can be uploaded via Cerberus-Remote access.The FC722.. is ideally suited for medium-sized applications‚ e.g. in workshops‚ hotels‚ etc. or when networked as part of much larger appli-cations. The FC722.. with flexible cross-linking possibilities can also be used for extensive systems.The expansion and accessories must be ordered separately.

Detector compatibility Cerberus PRO FD720

Number of addresses max. 252

Number of detector lines 2 (4) loops or 4 (8) stub lines

Programmable input/output 8

Relay outputs 1 x RT alarm1 x RT fault

Supervised output 1 x RT alarm1 x RT fault1 x horn

Emergency power supply up to 72 h (optional)

Plug-in position 2 -> for serial interfaces RS232‚ RS4852 -> for network modules1 -> for loop extension (C-NET)

Operating temperature -8… +42 °C

Storage temperature -20... +60 °C

Relative humidity L95 % (no condensation)

Protection category IP30

Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design 050 00 00

Data sheet A6V10206525

FC722..

02.fm Seite 4 Mittwoch, 28. Juli 2010 8:17 08

Page 24: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC722 Series

2-5© Siemens Switzerland Ltd 2010

2Type Order No.

FC722-ZZ Fire control panel (2-loop) in housing (Standard)

See FC722.. for technical overview and note the additional / other specifications:

Mains voltage 85... 265 VAC

Operating voltage 21… 28.6 VDC

Operating current max. 2.5 A

Power supply 70 W

Battery capacity 2 x 12 V‚ 7... 12 Ah

Cabinet dimensions (W x H x D) 430 x 398 x 160 mm

Expansion FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FTO2001-A1 Event printerFHA2007-A1 Mounting plateFCI2001-A1 Fire brigade periphery module kitFCA2005-A1 Sounder moduleFN2001-A1 Network module (SAFEDLINK)FN2002-A1 Repeater (SAFEDLINK)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FCI2003-A1 Loop extension (FDnet/C-NET)FH7202-Z3 Housing (Standard)FH7203-Z3 Housing (Comfort)

Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer (Extern)

S54400-C29-A5

02.fm Seite 5 Mittwoch, 28. Juli 2010 8:17 08

Page 25: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC722 Series

2-6 © Siemens Switzerland Ltd 2010

Type Order No.

FC722-YZ Fire control panel (2-loop) in housing (Standard) with 1 LED indica-tor

See FC722.. for technical overview and note the additional / other specifications:

With 24 indicator groups‚ each with one red and one yellow LED.

Mains voltage 85… 265 VAC

Operating voltage 21… 28.6 VDC

Operating current max. 2.5 A

Power supply 70 W

Battery capacity 2 x 12 V‚ 7... 12 Ah

Cabinet dimensions (W x H x D) 430 x 398 x 160 mm

Expansion FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FHA2007-A1 Mounting plateFCI2001-A1 Fire brigade periphery module kitFCA2005-A1 Sounder moduleFN2001-A1 Network module (SAFEDLINK)FN2002-A1 Repeater (SAFEDLINK)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FCI2003-A1 Loop extension (FDnet/C-NET)FH7202-Z3 Housing (Standard)FH7203-Z3 Housing (Comfort)

Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer (Extern)

S54400-C29-A4

02.fm Seite 6 Mittwoch, 28. Juli 2010 8:17 08

Page 26: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC722 Series

2-7© Siemens Switzerland Ltd 2010

2Type Order No.

FC722-ZA Fire control panel (2-loop) in housing (Comfort)

See FC722.. for technical overview and note the additional / other specifications:

Mains voltage 230 VAC

Operating voltage 21… 28.4 VDC

Operating current max. 5 A

Power supply 150 W

Battery capacity 2 x 12 V‚ 26 Ah

Cabinet dimensions (W x H x D) 430 x 796 x 160 mm

Expansion FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FTO2001-A1 Event printerFHA2007-A1 Mounting plateFCI2001-A1 Fire brigade periphery module kitFCA2005-A1 Sounder moduleFN2001-A1 Network module (SAFEDLINK)FN2002-A1 Repeater (SAFEDLINK)FP2005-A1 Power supply kit (150 W‚ B)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FCI2003-A1 Loop extension (FDnet/C-NET)FH7202-Z3 Housing (Standard)FH7203-Z3 Housing (Comfort)

Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer (Extern)

S54400-C29-A2

02.fm Seite 7 Mittwoch, 28. Juli 2010 8:17 08

Page 27: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC722 Series

2-8 © Siemens Switzerland Ltd 2010

Type Order No.

FC722-ZE Fire control panel (2-loop) in housing (Comfort) with 2 LED indica-tors

See FC722.. for technical overview and note the additional / other specifications:

With 48 indicator groups‚ each with one red and one yellow LED.

Mains voltage 230 VAC

Operating voltage 21… 28.4 VDC

Operating current max. 5 A

Power supply 150 W

Battery capacity 2 x 12 V‚ 26 Ah

Cabinet dimensions (W x H x D) 430 x 796 x 160 mm

Expansion FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FTO2001-A1 Event printerFHA2007-A1 Mounting plateFCI2001-A1 Fire brigade periphery module kitFCA2005-A1 Sounder moduleFN2001-A1 Network module (SAFEDLINK)FN2002-A1 Repeater (SAFEDLINK)FP2005-A1 Power supply kit (150 W‚ B)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FCI2003-A1 Loop extension (FDnet/C-NET)FH7202-Z3 Housing (Standard)FH7203-Z3 Housing (Comfort)

Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer (Extern)

S54400-C29-A1

02.fm Seite 8 Mittwoch, 28. Juli 2010 8:17 08

Page 28: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC722 Series

2-9© Siemens Switzerland Ltd 2010

2Type Order No.

FC722-HA Fire control panel (2-loop) in housing (Comfort) with EVAC operat-ing unit

See FC722.. for technical overview and note the additional / other specifications:

With 10 evacuation operating zones for Netherlands.

Mains voltage 230 VAC

Operating voltage 21… 28.4 VDC

Operating current max. 5 A

Power supply 150 W

Battery capacity 2 x 12 V‚ 26 Ah

Cabinet dimensions (W x H x D) 430 x 796 x 160 mm

Expansion FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FTO2001-A1 Event printerFHA2007-A1 Mounting plateFCI2005-N1 RT Interface SetFCA2005-A1 Sounder moduleFN2001-A1 Network module (SAFEDLINK)FN2002-A1 Repeater (SAFEDLINK)FP2005-A1 Power supply kit (150 W‚ B)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FCI2003-A1 Loop extension (FDnet/C-NET)FH7202-Z3 Housing (Standard)FH7203-Z3 Housing (Comfort)

Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer (Extern)

S54400-C29-A3

02.fm Seite 9 Mittwoch, 28. Juli 2010 8:17 08

Page 29: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire brigade periphery moduleFCI2001-D1

Networkable addressable fi re control panel FC724 Comfort*

Upt to 2 sounder modulesFCA2005-A1

* Control panel shown with 48 indicator groups, each with one red and one yellow LED

Sounder moduleFCA2005-A1

and/or

Mounting plate FHA2007-A1 for fi re brigade periphery module FCI2001-D1 or sounder module FCA2005-A1

Event printer FTO2001-A1

2x batteries max. 12 V/24 AhFA2006-A1

Additional power supply kit FP2005-A1

Key switch (Kaba) FTO2005-C1 or Key switch (Nordic) FTO2006-B1

License key (L1) FCA2012-A1 for Cerberus-Remote or License key (L2) FCA2013-A1 for Cerberus-Remote and connection to a danger management system

Up to 6 relay modules Z3B171

Up to 2 loop extensionsFCI2003-A1

Network module (SAFEDLINK)FN2001-A1

RS485 module FCA2002-A1 and/or RS232 module FCA2001-A1

Up to 2 cable kits (communication) FCA2014-A1and/or

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 12 28.05.10 16:56

Page 30: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC724 Series

2-11© Siemens Switzerland Ltd 2010

2Type Order No.

FC724.. Fire control panel (4-loop)

The FC724.. (4-loop‚ expandable to 8) is a compact fire control panel with an integrated operating unit that can process signals from Cer-berus PRO devices of up to 504 addresses. The fire control panel can be used as a stand-alone version or networked. The control panel can be programmed with a user-friendly Cerberus-Engineering-Tool to create a system with great versatility. Up to 32 fire control panels and fire ter-minals can be connected in a single cluster (C-WEB/SAFEDLINK net-work)‚ or up to 16 panels when the cluster is connected to a danger management system. Using a fiber-optic backbone (C-WEB/LAN) up to 14 of these clusters with up to 16 panels each can be networked. This topology enables the construction of an EN 54-conform network with up to 64 fire control panels and fire terminals. In addition‚ an Ethernet connection is available at each station. This Ethernet connection ena-bles a maximum of 4 stations including a Global Access Point 'GAP' (via Hub) to be networked together and be connected to a Siemens danger management system (not EN 54-compliant). All detector lines are mon-itored for ground faults.Adaptation of the user text directly on the terminal or with the Cerberus-Engineering-Tool. Up to 2000 events can be stored according to various criteria. Automatic summer/winter time change.Detection and automatic read-in (auto configuration) of all C-NET devices‚ providing immediate simple operation.Stored data can be uploaded via Cerberus-Remote access.The FC724.. is ideally suited for large-sized applications‚ e.g. in industri-al plants‚ regional banks‚ office complexes‚ etc. The FC724.. with flexi-ble cross linking possibilities can also be used for extensive systems.The expansion and accessories must be ordered separately.

Detector compatibility Cerberus PRO FD720

Number of addresses max. 504

Number of detector lines 4 (8) loops or 8 (16) stub lines

Programmable input/output 12

Relay outputs 1x RT alarm1x RT fault

Supervised output 1x RT alarm1x RT fault2x Horn

Mains voltage 230 VAC

Operating voltage 21… 28.6 VDC

Operating current max. 5 A

Power supply 150 W

Emergency power supply up to 72 h (optional)

Battery capacity 2 x 12 V‚ 26 Ah

Plug-in position 2 -> for serial interfaces RS232‚ RS4852 -> for network modules2 -> for loop extension (C-NET)

Operating temperature -8… +42 °C

Storage temperature -20… +60 °C

Relative humidity L95 % (no condensation)

Protection category IP30

Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design 050 00 00

Cabinet dimensions (W x H x D) 430 x 796 x 160 mm

Data sheet A6V10207176

FC724..

02.fm Seite 11 Mittwoch, 28. Juli 2010 8:17 08

Page 31: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC724 Series

2-12 © Siemens Switzerland Ltd 2010

Type Order No.

FC724-ZA Fire control panel (4-loop)

See FC724.. for technical overview and note the additional / other specifications:

Expansion FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FTO2001-A1 Event printerFHA2007-A1 Mounting plateFCI2001-A1 Fire brigade periphery module kitFCA2005-A1 Sounder moduleFN2001-A1 Network module (SAFEDLINK)FN2002-A1 Repeater (SAFEDLINK)FP2005-A1 Power supply kit (150 W‚ B)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FCI2003-A1 Loop extension (FDnet/C-NET)FH7202-Z3 Housing (Standard)FH7203-Z3 Housing (Comfort)

Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer (Extern)

S54400-C30-A2

02.fm Seite 12 Mittwoch, 28. Juli 2010 8:17 08

Page 32: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC724 Series

2-13© Siemens Switzerland Ltd 2010

2Type Order No.

FC724-ZE Fire control panel (4-loop) with 2 LED indicators

See FC724.. for technical overview and note the additional / other specifications:

With 48 indicator groups‚ each with one red and one yellow LED.

Expansion FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FTO2001-A1 Event printerFHA2007-A1 Mounting plateFCI2001-A1 Fire brigade periphery module kitFCA2005-A1 Sounder moduleFN2001-A1 Network module (SAFEDLINK)FN2002-A1 Repeater (SAFEDLINK)FP2005-A1 Power supply kit (150 W‚ B)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FCI2003-A1 Loop extension (FDnet/C-NET)FH7202-Z3 Housing (Standard)FH7203-Z3 Housing (Comfort)

Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer (Extern)

S54400-C30-A3

02.fm Seite 13 Mittwoch, 28. Juli 2010 8:17 08

Page 33: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC724 Series

2-14 © Siemens Switzerland Ltd 2010

Type Order No.

FC724-HA Fire control panel (4-loop) with EVAC operating unit

See FC724.. for technical overview and note the additional / other specifications:

With 10 evacuation operating zones for Netherlands.

Expansion FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FTO2001-A1 Event printerFHA2007-A1 Mounting plateFCI2005-N1 RT Interface SetFCA2005-A1 Sounder moduleFN2001-A1 Network module (SAFEDLINK)FN2002-A1 Repeater (SAFEDLINK)FP2005-A1 Power supply kit (150 W‚ B)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FCI2003-A1 Loop extension (FDnet/C-NET)FH7202-Z3 Housing (Standard)FH7203-Z3 Housing (Comfort)

Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer (Extern)

S54400-C30-A1

02.fm Seite 14 Mittwoch, 28. Juli 2010 8:17 08

Page 34: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Networkable addressable modular fi re control panel FC726

I/O card (programmable) FCI2008-A1

Sounder moduleFCA2005-A1

Mounting plate FHA2007-A1 for fi re brigade periphery module FCI2001-D1 or sounder module FCA2005-A1

Event printer FTO2001-A1

2x batteries 12 V/24 AhFA2006-A1

Additional power supply kit FP2005-A1

Up to 2 sounder modules FCA2005-A1

and/or Any number of relay modules Z3B171

Key switch (Kaba) FTO2005-C1 or Key switch (Nordic) FTO2006-B1

License key (L1) FCA2012-A1 for Cerberus-Remote or License key (L2) FCA2013-A1 for Cerberus-Remote and connection to a danger management system

Line card (C-NET) FCL2001-A1

Up to 2 loop extensionsFCI2003-A1

Network module (SAFEDLINK)FN2001-A1

RS485 module FCA2002-A1 and/or RS232 module FCA2001-A1

Up to 2 cable kits (communication) FCA2014-A1

Fire brigade periphery moduleFCI2001-D1

Operating add-on (2x LED-ind) FCM7211-Y3 orOperating add-on (4x LED-ind) FCM7212-Y3

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 13 28.05.10 16:57

Page 35: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC726 Series

2-16 © Siemens Switzerland Ltd 2010

Type Order No.

FC726.. Fire control panel (modular)

The FC726... (4-loop‚ expandable to 28 loops) is a modular fire control panel with an integrated operating unit that can process signals from Cerberus PRO devices of up to 1512 addresses. A card cage in the basic fire control panel equipment is used for installation of additional line cards (C-NET) or I/O cards. A mix of up to 5 cards max. is possible. Line and I/O cards can be exchanged without removing power from control panel. The fire control panel can be used as a stand-alone version or net-worked. The control panel can be programmed with a user-friendly Cerberus-Engineering-Tool to create a system with great versatility. Up to 32 fire control panels and fire terminals can be connected in a sin-gle cluster (C-WEB/SAFEDLINK network)‚ or up to 16 panels when the cluster is connected to a danger management system. Using a fiber-optic backbone (C-WEB/LAN) up to 14 of these clusters with up to 16 panels each can be networked. This topology enables the construction of an EN 54-conform network with up to 64 fire control panels and fire terminals. In addition‚ an Ethernet connection is available at each sta-tion. This Ethernet connection enables a maximum of 4 stations includ-ing a Global Access Point 'GAP' (via Hub) to be networked together and be connected to a Siemens danger management system (not EN 54-compliant). All detector lines are monitored for ground faults.Adaptation of the user text directly on the terminal or with the software engineering tool. Up to 2000 events can be stored according to various criteria. Automatic summer/winter time change. Detection and auto-matic read-in (auto configuration) of all C-NET devices‚ providing imme-diate simple operation. Stored data can be uploaded via remote access.The FC726 is ideally suited for very large and complex buildings‚ e.g. office buildings‚ university campuses‚ etc. The FC726.. with flexible cross linking possibilities can also be used for extensive systems. The expansion and accessories must be ordered separately.

Detector compatibility Cerberus PRO FD 720

Number of addresses max. 1512

Number of detector lines Loop with loop extension -> 4 loops or 8 stub linesC-NET -> max. 20 (4 per line card)

Programmable input/output max. 60 (12 per card)

Relay outputs 1 x RT alarm; 1 x RT fault

Supervised output 1 x RT alarm; 1 x RT fault2 x Horn

Mains voltage 230 VAC

Operating voltage 21... 28.4 VDC

Operating current Max. 5 A

Power supply 150 W

Emergency power supply up to 72 h (optional)

Battery capacity 2 x 12‚ 45 Ah

Plug-in position 2 -> for serial interfaces RS232‚ RS48522 -> for network modules1 -> for loop extension (C-NET)5 -> for line or I/O cards (card cage)

Operating temperature -8… +42 °C

Storage temperature -20… +60 °C

Relative humidity L95 % (no condensation)

Protection category IP30

Standard EN 54-2‚ EN 54-4

Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design050 00 00

Cabinet dimensions (W x H x D) 430 x 796 x 260

Data sheet A6V10263277

FC726..

02.fm Seite 16 Mittwoch, 28. Juli 2010 8:17 08

Page 36: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsFC726 Series

2-17© Siemens Switzerland Ltd 2010

2Type Order No.

FC726-ZA Fire control panel (modular)

See FC726.. for technical overview and note the additional / other specifications:

Expansion FCI2003-A1 Loop extension (FDnet/C-NET)FCI2008-A1 I/O card (programma-ble)FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FTO2001-A1 Event printerFHA2007-A1 Mounting plateFCI2001-A1 Fire brigade periphery module kitFCA2005-A1 Sounder moduleFCL2001-A1 Line card (FDnet/C-NET)FN2001-A1 Network module (SAFEDLINK)FN2002-A1 Repeater (SAFEDLINK)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FH7204-Z3 Housing (Large Exten-sion)FH7205-Z3 Housing (Large)

Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)Z3B171 Relay moduleFHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer

S54400-C87-A1

02.fm Seite 17 Mittwoch, 28. Juli 2010 8:17 08

Page 37: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsExpansion FC72x

2-18 © Siemens Switzerland Ltd 2010

Type Order No.

FCI2003-A1 Loop extension (FDnet/C-NET)

With the loop extension‚ the number of connectable loops is doubled from 2 to 4. The number of FDnet/C-NET addresses per station remains unchanged.Plugged onto the periphery board of the control panel. Each integrated line can be equipped with one loop extension (exclude FC721).

Number of detector lines 2 loops or 4 stub lines

Cable capacity 0.2... 1.5 mm2

Dimensions (W x H x D) 48 x 20 x 70 mm

A5Q00010136

FCL2001-A1 Line card (FDnet/C-NET)

The line card is an additional card for integrated FDnet/C-NET lines‚ mounted in card cage (5 slots) of FC2060 or FC726 fire control panel. It is used to expand FC2060/FC726 with additional FDnet/C-NET lines. All FDnet or C-NET devices can be connected to the line card. The line card is designed for 4 loops or 8 stub lines.

Number of detector lines 4 loops or 8 stub lines

Number of addresses max. 252

Input current max. 0.8 A

A5Q00009875

FCI2008-A1 I/O card (programmable)

The I/O card is an additional card with programmable inputs and out-puts for expansion of the integrated inputs and outputs. The card is mounted in the card cage (5 slots) of the fire control panel FC2060/FC726.

Input current max. 2 A

S54400-A6-A1

FCA2012-A1 License key (L1)

iButton with license for:Sinteso -> SintesoViewCerberus PRO -> Cerberus-RemoteOnly one license key is required per station.

A5Q00018856

FCA2013-A1 License key (L2)

iButton with license for:Sinteso -> SintesoView and BACnetCerberus PRO -> Cerberus-Remote and BACnetOnly one license key is required per station.

A5Q00018857

02.fm Seite 18 Mittwoch, 28. Juli 2010 8:17 08

Page 38: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsExpansion FC72x

2-19© Siemens Switzerland Ltd 2010

2Type Order No.

FTO2001-A1 Event printer

The event printer is a thermal printer that logs alarms‚ faults and gener-al messages. The event printer can be used in all control panels if space is available. The RS232 module is required to operate the printer. Event printer includes cables for interface and power supply and a paper roll.The RS232 module FCA2001-A1 must be ordered separately.

Operating voltage 9… 48 VDC

Quiescent current 50 mA

Operating current 3 A @ 9 VDC0.7 A @ 48 VDC

Interface RS232 serial

Operating temperature 0… +50 °C

Storage temperature -20… +70 °C

Relative humidity L95 % (no condensation)

Dimensions (W x H x D) 85 x 85 x 55 mm

A5Q00010126

FHA2007-A1 Mounting plate

The mounting plate must be screwed onto the back wall of the housing. The mounting plate can pivot‚ allowing access to the underlying mod-ule‚ i.e. to mount the fire brigade periphery module or the sounder modules.

Dimensions (W x H x D) 221 x 241 x 46 mm

A5Q00010151

FCI2001-D1 Fire brigade periphery module

For VdS-compliant switching to fire department periphery devices (for Germany). The module has connections for FBF‚ FSD‚ ÜE‚ FSE‚ ÖA‚ KL‚ tamper alarm FSD.Mounted in the housing on the mounting plate FHA2007-A1‚ or on the back wall of the housing.

Operating voltage 21… 28.6 VDC

Operating current max. 1.6 A

Cable capacity 0.2... 1.5 mm2 / 0.5... 2.5 mm2

Dimensions (W x H x D) 150 x 190 x 40 mm

A5Q00013100

FCI2005-N1 RT Interface Set

For fire department periphery devices (for Netherlands). Mounted in the housing on the mounting plate FHA2007-A1.

Operating voltage 20… 30 VDC

Operating current max. 20 mA

Cable capacity 0.4... 1.5 mm2 / 0.2... 2.5 mm2

Dimensions (W x H x D) 190 x 150 x 36 mm

A5Q00026302

02.fm Seite 19 Mittwoch, 28. Juli 2010 8:17 08

Page 39: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsExpansion FC72x

2-20 © Siemens Switzerland Ltd 2010

Type Order No.

FCA2005-A1 Sounder module

With the sounder module‚ it is possible to split a collective horn line onto 4 individual lines. Each line controls and monitors an individual sounder. 2 sounder modules can also be used‚ but must then be cascad-ed.The sounder module can be mounted onto the mounting plate FHA2007-A1 or onto the U-rail TS35 with the enclosed mounting feet.

Operating voltage 21... 28.6 VDC

Quiescent current 20 mA

Operating current max. 2 A (fused with 2 AT)

Supervised output 4 x 1 A

Cable capacity 0.08... 1.5 mm2

Relative humidity L95 %

Color housing/cover white‚ zRAL 9010/transparent matt

Protection category IP30

Dimensions (W x H x D) 132 x 90 x 24 mm

A5Q00014866

Accessories

TS35_122 U-rail TS35/7.5/122

Universal mounting rail (U-rail) enables mounting of various equip-ment.

Dimensions (W x H) 35 x 122 mm

BPZ:5644780001

TS35_288 U-rail TS35/7.5/288

Universal mounting rail (U-rail) enables mounting of various equip-ment.

Dimensions (W x H) 35 x 288 mm

BPZ:5644230001

FDCH221 Housing for input/output modules

Housing with seal for the mounting of the input/output modules for wet applications.The required screwed cable glands and back nuts M20 must be ordered separately.

Dimensions (W x H x D) 207 x 119 x 48 mm

Color white‚ zRAL 9010 / transparent matt

Protection category IP65

Accessories A5Q00004478 Screwed cable gland M20A5Q00004479 Back nut M20

S54312-F3-A1

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

02.fm Seite 20 Mittwoch, 28. Juli 2010 8:17 08

Page 40: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsExpansion FC72x

2-21© Siemens Switzerland Ltd 2010

2Type Order No.

A5Q00004479 Back nut M20

Back nut to screwed cable gland M20 x 1.5.

Delivery unit 10 pieces

A5Q00004479

FCA2001-A1 RS232 module (isolated)

Module for periphery devices with RS232 interface‚ e.g. for event print-er FTO2001-A1. Plugged into the back side of the operating unit.RS232 module incl. 1 EMC screwed cable gland M10 x 1.5.

Cable capacity 0.2… 1.5 mm2

Dimensions (W x H x D) 50 x 15 x 70 mm

A5Q00005327

FCA2002-A1 RS485 module (isolated)

Module for periphery devices with RS485 interface‚ e.g. for FAT (GER). Plugged into the back side of the operating unit.RS485 module incl. 1 EMC screwed cable gland M10 x 1.5.

Cable capacity 0.2… 1.5 mm2

Dimensions (W x H x D) 50 x 15 x 70 mm

A5Q00009923

FH7201-Z3 Housing (Eco)

Empty housing for open use‚ e.g. power supply kit with batteries‚ oper-ating add-on‚ event printer or mimic display.

Cabinet dimensions (W x H x D) 430 x 398 x 80 mm

Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design 050 00 00

Protection category IP30

Integral battery space 2 x FA2003-A1 (7 Ah)

Expansion FTO2001-A1 Event printerFCM7211-Y3 Operating add-on (2xLED-ind.)FCM7212-Y3 Operating add-on (4xLED-ind.)FP2003-A1 Power supply kit (70 W)

S54400-B72-A1

02.fm Seite 21 Mittwoch, 28. Juli 2010 8:17 08

Page 41: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsExpansion FC72x

2-22 © Siemens Switzerland Ltd 2010

Type Order No.

FH7202-Z3 Housing (Standard)

Empty housing for open use‚ e.g. power supply kit with batteries‚ oper-ating add-on or for the event printer.

Cabinet dimensions (W x H x D) 430 x 398 x 160 mm

Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design 050 00 00

Protection category IP30

Integral battery space 2 x FA2003-A1 (7 Ah) or2 x FA2004-A1 (12 Ah) or2 x FA2006-A1 (26 Ah)

Expansion FTO2001-A1 Event printerFCM7211-Y3 Operating add-on (2xLED-ind.)FCM7212-Y3 Operating add-on (4xLED-ind.)FP2003-A1 Power supply kit (70 W)FP2004-A1 Power supply kit (150 W‚ A)FP2005-A1 Power supply kit (150 W‚ B)

S54400-B70-A1

FH7203-Z3 Housing (Comfort)

Empty housing for open application‚ e.g. power supply kit with batter-ies‚ for operating add-on or for the event printer.

Cabinet dimensions (W x H x D) 430 x 796 x 160 mm

Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design 050 00 00

Protection category IP30

Integral battery space 2 x FA2003-A1 (7 Ah) or2 x FA2004-A1 (12 Ah) or2 x FA2005-A1 (17 Ah) or2 x FA2006-A1 (26 Ah)

Expansion FTO2001-A1 Event printerFCM7211-Y3 Operating add-on (2xLED ind.)FCM7212-Y3 Operating add-on (4xLED ind.)FP2003-A1 Power supply kit (70 W)FP2004-A1 Power supply kit (150 W‚ A)FP2005-A1 Power supply kit (150 W‚ B)

S54400-B71-A1

02.fm Seite 22 Mittwoch, 28. Juli 2010 8:17 08

Page 42: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsExpansion FC72x

2-23© Siemens Switzerland Ltd 2010

2Type Order No.

FH7204-Z3 Housing (Large Extension)

Empty housing for open application‚ e.g. additional batteries‚ for oper-ating add-ons or for the event printer.

Cabinet dimensions (W x H x D) 430 x 398 x 260 mm

Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design050 00 00

Protection category IP30

Integral battery space 2 x FA2007-A1 (45 Ah) or2 x FA2008-A1 (65 Ah) or2 x FA2009-A1 (100 Ah)

Expansion FTO2001-A1 Event printerFCM7211-Y3 Operating add-on (2xLED ind.)FCM7212-Y3 Operating add-on (4xLED ind.)FP2003-A1 Power supply kit (70 W)FP2004-A1 Power supply kit (150 W‚ A)FP2005-A1 Power supply kit (150 W‚ B)

S54400-B89-A1

FH7205-Z3 Housing (Large)

Empty housing for open application‚ e.g. additional batteries‚ for oper-ating add-ons or for the event printer.

Cabinet dimensions (W x H x D) 430 x 796 x 260 mm

Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design050 00 00

Protection category IP30

Integral battery space 4 x FA2006-A1 (26 Ah) or4 x FA2007-A1 (45 Ah) or2 x FA2008-A1 (65 Ah) or2 x FA2009-A1 (100 Ah)

Expansion FTO2001-A1 Event printerFCM7211-Y3 Operating add-on (2xLED ind.)FCM7212-Y3 Operating add-on (4xLED ind.)FP2003-A1 Power supply kit (70 W)FP2004-A1 Power supply kit (150 W‚ A)FP2005-A1 Power supply kit (150 W‚ B)

S54400-B86-A1

FCM7211-Y3 Operating add-on (2xLED ind.)

To update 48 LED display groups‚ with one red and one yellow LED each.Can be inserted in all empty housings.Inclusive cables and screws for installation.

Dimensions (W x H x D) 427 x 200 x 25 mm

S54400-F75-A1

02.fm Seite 23 Mittwoch, 28. Juli 2010 8:17 08

Page 43: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsExpansion FC72x

2-24 © Siemens Switzerland Ltd 2010

Type Order No.

FCM7212-Y3 Operating add-on (4xLED ind.)

To update 96 LED display groups‚ with one red and one yellow LED each.Can be inserted in all empty housings.Inclusive cables and screws for installation.

Dimensions (W x H x D) 427 x 200 x 25 mm

S54400-F88-A1

FCM7221-H3 Operating add-on (2xEVAC)

The operating add-on is composed of an operation of 10 zones and an extension of another 10 zones. This application completes the fire con-trol panel with evacuation operating panel used by the fire brigade to activate or deactivate alarming devices in single zones. The operating add-on can be directly mounted into a fire control panel. When the operating add-on is used remote from the control panel in a separate housing the connector board FTI2001-N1 is necessary.Connection to fire control panel via serial RS485 interface.Inclusive cables and screws for installation.The RS485 module and the connector board FTI2002-N1 must be ordered separately.

Dimensions (W x H x D) 427 x 200 x 25 mm

Data sheet A6V10223093

S54400-F78-A1

FTI2002-N1 EVAC-NL connector board

The connector board is necessary if the operating add-on (2xEVAC) is used remote from the control panel in a separate housing. The connec-tion to the control panel occurs via the RS485 interface. The remote access to the operating add-on is possible until 1000 m.The RS485 module must be ordered separately and to be mounted in the control panel.

Supply voltage 20… 32 VDC

Operating current max. 190 mA @ 21 VDC

Cable capacity 0.5… 1.5 mm2

Dimensions (W x H x D) 121 x 130 x 32 mm

Data sheet A6V10223093

S54400-A15-A1

FT2003-N1 Mimic display driver (EVAC)

The mimic display driver is necessary if the evacuation panel has to be built in a customer-specific housing with customized LEDs and keys in a plant layout (mimic display). The mimic display is composed of a con-nector board and a print of the operating add-on.In order to realize a panel for 20 evacuation zones‚ 2 mimic display driv-ers are required (Master and Slave).The 34-pin ribbon cable for connection of LEDs‚ keys and key switch must be provided by the customer.The RS485 module must be ordered separately and mounted in the control panel.

Supply voltage 20… 32 VDC

Operating current max. 190 mA @ 21 VDC

Cable capacity 0.5… 1.5 mm2

Dimensions (W x H x D) 121 x 206 x 47 mm

Data sheet A6V10223093

S54400-A14-A1

02.fm Seite 24 Mittwoch, 28. Juli 2010 8:17 08

Page 44: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsExpansion FC72x

2-25© Siemens Switzerland Ltd 2010

2Type Order No.

FP2003-A1 Power supply kit (70 W)

Auxiliary power supply to all stations (control panels and terminals).Converts mains voltage to system voltage. Monitors mains voltage and batteries.

Supply voltage 85... 265 VAC

Power consumption max. 90 VA

Current 0.5… 1 A

Dimensions (W x H x D) 95 x 170 x 54 mm

A5Q00016005

FP2004-A1 Power supply kit (150 W‚ A)

Power supply kit (150 W‚ A) as auxiliary power supply for installation into empty housings.Converts mains voltage to system voltage. Monitors mains voltage and batteries.

Supply voltage 115... 230 VAC

Power consumption max. 300 VA

Current 2.6 / 1.2 A

Dimensions (W x H x D) 130 x 150 x 70 mm

A5Q00020825

FP2005-A1 Power supply kit (150 W‚ B)

Power supply kit (150 W‚ B) as auxiliary power supply for cascading.Converts mains voltage to system voltage. Monitors mains voltage and batteries.

Supply voltage 115... 230 VAC

Power consumption max. 300 VA

Current 2.6 / 1.2 A

Dimensions (W x H x D) 130 x 150 x 70 mm

A5Q00018779

02.fm Seite 25 Mittwoch, 28. Juli 2010 8:17 08

Page 45: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsNetwork Components Cluster (C-WEB/SAFEDLINK)

2-26 © Siemens Switzerland Ltd 2010

Type Order No.

FN2001-A1 Network module (SAFEDLINK)

To network multiple stations in the FCnet/C-WEB cluster. Up to 32 pan-els can be networked. Plugged into the back side of the operating unit.

Cable capacity 0.2… 1.5 mm2

Dimensions (W x H x D) 50 x 20 x 70 mm

A5Q00012851

FN2002-A1 Repeater (SAFEDLINK)

The module is a repeater in the FCnet/C-WEB cluster. It is used for the extension of the range of the system bus. 1 repeater max. can be used between 2 stations. The distance between network module and repeat-er may be up to 1000 m.The repeater can be mounted directly on a plane surface‚ onto a U-rail TS35 with the enclosed mounting feet or in the housing FDCH221.The accessories must be ordered separately.

Communication protocol SAFEDLINK (UDP/IP)

Operating voltage 9... 30 VDC

Operating current max. 45 mA

Cable capacity 0.08... 1.5 mm2

Relative humidity L95 %

Color housing/cover white‚ zRAL 9010/transparent matt

Protection category IP30IP65 with aux. housing FDCH221

Dimensions (W x H x D) 132 x 90 x 24 mm

Accessories TS35_122 U-railTS35_288 U-railFDCH221 Housing IP65

S24236-B2502-A1

02.fm Seite 26 Mittwoch, 28. Juli 2010 8:17 08

Page 46: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsNetwork Components Backbone (C-WEB/LAN)

2-27© Siemens Switzerland Ltd 2010

2Type Order No.

FN2008-A1 Ethernet switch

The Ethernet switch connects individual clusters via the Ethernet back-bone. A second switch can be added if a cluster has more than 512 detectors. With a mounting kit (FHA2029-A1 or FHA2030-A1)‚ the Ethernet switch can be easily integrated into panels or additional hous-ings.

S54400-F94-A1

FN2009-A1 Security module

Protects devices and networks in automation and industrial communi-cation with a combination of different security measures such as fire-wall and VPN (Virtual Private Network) via IPsec tunnel. The security module can be easily integrated into a panel with a mounting kit (FHA2029-A1 or FHA2030-A1).

S54400-F95-A1

FHA2029-A1 Mounting kit for housing (Comfort) S54400-B79-A1

FHA2030-A1 Mounting kit for housing (Large Extension) S54400-B81-A1

02.fm Seite 27 Mittwoch, 28. Juli 2010 8:17 08

Page 47: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsAccessories FC72x

2-28 © Siemens Switzerland Ltd 2010

Type Order No.

FTO2005-C1 Key switch (Kaba)

Kaba key switch with mounting accessories and key (Kaba 8 #100)‚ as an option for operating access (operating unit).

A5Q00010113

FTO2006-B1 Key switch (Nordic)

Nordic key switch with mounting accessories and key (Nordic)‚ as an option for operating access (operating unit).

A5Q00010129

Z3B171 Relay module with 1 contact

The relay module is an additional fire event control module‚ activated by the fire control panel's control output.

Contact rating 250 VAC / 10 A

Delivery unit 10 pieces

BPZ:4843830001

FHA2016-A1 19" mounting kit

To install fire control panels and fire terminals in a 19" third-party hous-ing.

Dimensions (W x H x D) 430 x 100 x 324 mm

A5Q00020179

FCA2014-A1 Cable kit (communication)

For flexible cable connections to the modules on the PMI-& main board.

A5Q00023027

02.fm Seite 28 Mittwoch, 28. Juli 2010 8:17 08

Page 48: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFC72x Networkable Fire Control PanelsAccessories FC72x

2-29© Siemens Switzerland Ltd 2010

2Type Order No.

DL3750+ Matrix printer external

The Fujitsu DL3750+ is a compact‚ noiseless A4 matrix printer. It is used for documenting relevant information in a system on continuous paper. The printer is constantly supervised by the fire control panel. The type of events to be printed is configurable. It offers a maximum of speed and reliability.The RS232 module FCA2001-A1 is required to operate the printer and must be ordered separately.

Number of copies 5 incl. original

Character set 6

Resolution 360 x 360 dpi

Interface RS232 orEthernet (via Print-Server PS01a)

Operating temperature +5… +38 °C

Storage temperature -15… +60 °C

Relative humidity L95 % (no condensation)

Dimensions (W x H x D) 415 x 120 x 330 mm

A5Q00023962

02.fm Seite 29 Mittwoch, 28. Juli 2010 8:17 08

Page 49: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFT724 Networkable Fire Operating TerminalsFT724 Operating Terminal to FC72x

2-30 © Siemens Switzerland Ltd 2010

Type Order No.

FT724.. Fire terminal

The FT724.. fire terminal is an operating panel remote from the central control panel that can be operated with its own power supply as well‚ as an option. The operating unit has installation slots for optional inter-faces such as RS232‚ RS485‚ networking modules (SAFEDLINK) and a key switch. Each station has an Ethernet connection to which other fire terminals or a PC can be connected for remote operation/engineering. This Ethernet connection enables a maximum of 4 stations including a Global Access Point 'GAP' (via Hub) to be networked together and be connected to a Siemens danger management system (not EN 54-com-pliant). Up to 32 fire control panels and fire terminals can be connected in a single cluster (C-WEB/SAFEDLINK network)‚ or up to 16 panels when the cluster is connected to a danger management system. Using a fiber-optic backbone (C-WEB/LAN) up to 14 of these clusters with up to 16 panels each can be networked. This topology enables the construction of an EN 54-conform network with up to 64 fire control panels and fire terminals.The optional power supply i.e. power supply kit (70 W) and batteries 2 x 12 V / 7 Ah must be ordered separately.

Operating voltage 21… 28.6 VDC

Quiescent current 125 mA

Alarm current 130 mA

Power supply 70 W (optional)

Battery capacity max. 2 x 12 V / 7 Ah (optional)

Plug-in position 2 -> for serial interfaces RS232‚ RS4852 -> for network modules

Operating temperature -8… +42 °C

Storage temperature -20… +60 °C

Relative humidity L95 % (no condensation)

Protection category IP30

Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design 050 00 00

Cabinet dimensions (W x H x D) 430 x 398 x 80 mm

Data sheet A6V10207898

FT724..

FT724-ZZ Fire terminal

See FT724.. for technical overview and note the additional / other specifications:

Expansion FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FTO2001-A1 Event printerFN2001-A1 Network module (SAFEDLINK)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FP2003-A1 Power supply kit (70 W)FH7201-Z3 Housing (Eco)

Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)FHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer (Extern)

S54400-C31-A2

02.fm Seite 30 Mittwoch, 28. Juli 2010 8:17 08

Page 50: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFT724 Networkable Fire Operating TerminalsFT724 Operating Terminal to FC72x

2-31© Siemens Switzerland Ltd 2010

2Type Order No.

FT724-HZ Fire terminal with EVAC operating unit

See FT724.. for technical overview and note the additional / other specifications:

With 10 evacuation operating zones for Netherlands.

Expansion FCA2012-A1 License key (L1)FCA2013-A1 License key (L2)FN2001-A1 Network module (SAFEDLINK)FCA2001-A1 RS232 module (isolat-ed)FCA2002-A1 RS485 module (isolat-ed)FP2003-A1 Power supply kit (70 W)FH7201-Z3 Housing (Eco)

Accessories FTO2005-C1 Key switch (Kaba)FTO2006-B1 Key switch (Nordic)FHA2016-A1 19" mounting kitFCA2014-A1 Cable kit (communica-tion)DL3750+ Matrix printer (Extern)

S54400-C31-A1

02.fm Seite 31 Mittwoch, 28. Juli 2010 8:17 08

Page 51: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFT724 Networkable Fire Operating TerminalsExpansion FT724

2-32 © Siemens Switzerland Ltd 2010

Type Order No.

FCA2012-A1 License key (L1)

iButton with license for:Sinteso -> SintesoViewCerberus PRO -> Cerberus-RemoteOnly one license key is required per system.

A5Q00018856

FCA2013-A1 License key (L2)

iButton with license for:Sinteso -> SintesoView and BACnetCerberus PRO -> Cerberus-Remote and BACnetOne license key is required per station.

A5Q00018857

FN2001-A1 Network module (SAFEDLINK)

To network multiple stations in the FCnet/C-WEB cluster. Up to 32 pan-els can be networked. Plugged into the back side of the operating unit.

Cable capacity 0.2… 1.5 mm2

Dimensions (W x H x D) 50 x 20 x 70 mm

A5Q00012851

FCA2001-A1 RS232 module (isolated)

Module for periphery devices with RS232 interface‚ e.g. for event print-er FTO2001-A1. Plugged into the back side of the operating unit.RS232 module incl. 1 EMC screwed cable gland M10 x 1.5.

Cable capacity 0.2… 1.5 mm2

Dimensions (W x H x D) 50 x 15 x 70 mm

A5Q00005327

FCA2002-A1 RS485 module (isolated)

Module for periphery devices with RS485 interface‚ e.g. for FAT (GER). Plugged into the back side of the operating unit.RS485 module incl. 1 EMC screwed cable gland M10 x 1.5.

Cable capacity 0.2… 1.5 mm2

Dimensions (W x H x D) 50 x 15 x 70 mm

A5Q00009923

02.fm Seite 32 Mittwoch, 28. Juli 2010 8:17 08

Page 52: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFT724 Networkable Fire Operating TerminalsExpansion FT724

2-33© Siemens Switzerland Ltd 2010

2Type Order No.

FP2003-A1 Power supply kit (70 W)

Auxiliary power supply to all stations (control panels and terminals).Converts mains voltage to system voltage. Monitors mains voltage and batteries.

Supply voltage 85... 265 VAC

Power consumption max. 90 VA

Current 0.5… 1 A

Dimensions (W x H x D) 95 x 170 x 54 mm

A5Q00016005

FH7201-Z3 Housing (Eco)

Empty housing for open use‚ e.g. power supply kit with batteries‚ oper-ating add-on‚ event printer or mimic display.

Protection category IP30

Color housing/cover grey‚ zRAL 7035/grey‚ zRAL-Design 050 00 00

Cabinet dimensions (W x H x D) 430 x 398 x 80 mm

Integral battery space 2 x FA2003-A1 (7 Ah)

Expansion FTO2001-A1 Event printerFCM7211-Y3 Operating add-on (2xLED-ind.)FCM7212-Y3 Operating add-on (4xLED-ind.)FP2003-A1 Power supply kit (70 W)

S54400-B72-A1

FCM7211-Y3 Operating add-on (2xLED ind.)

To update 48 LED display groups‚ with one red and one yellow LED each.Can be inserted in all empty housings.Inclusive cables and screws for installation.

Dimensions (W x H x D) 427 x 200 x 25 mm

S54400-F75-A1

FCM7212-Y3 Operating add-on (4xLED ind.)

To update 96 LED display groups‚ with one red and one yellow LED each.Can be inserted in all empty housings.Inclusive cables and screws for installation.

Dimensions (W x H x D) 427 x 200 x 25 mm

S54400-F88-A1

02.fm Seite 33 Mittwoch, 28. Juli 2010 8:17 08

Page 53: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFT724 Networkable Fire Operating TerminalsExpansion FT724

2-34 © Siemens Switzerland Ltd 2010

Type Order No.

FTO2001-A1 Event printer

The event printer is a thermal printer that logs alarms‚ faults and gener-al messages. The event printer can be used in all control panels if space is available. The RS232 module is required to operate the printer. Event printer includes cables for interface and power supply and a paper roll.The RS232 module FCA2001-A1 must be ordered separately.

Operating voltage 9… 48 VDC

Quiescent current 50 mA

Operating current 3 A @ 9 VDC0.7 A @ 48 VDC

Interface RS232 serial

Operating temperature 0… +50 °C

Storage temperature -20… +70 °C

Relative humidity L95 % (no condensation)

Dimensions (W x H x D) 85 x 85 x 55 mm

A5Q00010126

02.fm Seite 34 Mittwoch, 28. Juli 2010 8:17 08

Page 54: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFT724 Networkable Fire Operating TerminalsAccessories FT724

2-35© Siemens Switzerland Ltd 2010

2Type Order No.

FTO2005-C1 Key switch (Kaba)

Kaba key switch with mounting accessories and key (Kaba 8 #100)‚ as an option for operating access (operating unit).

A5Q00010113

FTO2006-B1 Key switch (Nordic)

Nordic key switch with mounting accessories and key (Nordic)‚ as an option for operating access (operating unit).

A5Q00010129

FHA2016-A1 19" mounting kit

To install fire control panels and fire terminals in a 19" third-party hous-ing.

Dimensions (W x H x D) 430 x 100 x 324 mm

A5Q00020179

FCA2014-A1 Cable kit (communication)

For flexible cable connections to the modules on the PMI-& main board.

A5Q00023027

02.fm Seite 35 Mittwoch, 28. Juli 2010 8:17 08

Page 55: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Control Network ParticipantsFT724 Networkable Fire Operating TerminalsAccessories FT724

2-36 © Siemens Switzerland Ltd 2010

Type Order No.

DL3750+ Matrix printer external

The Fujitsu DL3750+ is a compact‚ noiseless A4 matrix printer. It is used for documenting relevant information in a system on continuous paper. The printer is constantly supervised by the fire control panel. The type of events to be printed is configurable. It offers a maximum of speed and reliability.The RS232 module FCA2001-A1 is required to operate the printer and must be ordered separately.

Number of copies 5 incl. original

Character set 6

Resolution 360 x 360 dpi

Interface RS232 orEthernet (via Print-Server PS01a)

Operating temperature +5… +38 °C

Storage temperature -15… +60 °C

Relative humidity L95 % (no condensation)

Dimensions (W x H x D) 415 x 120 x 330 mm

A5Q00023962

02.fm Seite 36 Mittwoch, 28. Juli 2010 8:17 08

Page 56: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Genesis Series (1-zone Panels)

Safety for people and assetsOur Genesis Series stands for comprehensive safety. In combination with an intrusion control panel, it is the professional solution for reliable fi re detection. As your existing network infrastructure can be used for instal-lation, you will profi t from low investment costs.

Connected to an intrusion detection control panel, Genesis 2 enables the installation of a single-zone fi re detection system. It also controls and supervises a 2-wire line, equipped with up to 32 conventional detectors. Supplied with 12 VDC from the intrusion control panel, it is able to provide 24 VDC thanks to an internal converter. This is the power needed by detec-tors and/or call points.

One conventional line with a maximum of 32 detectors Compatible with conventional (SynoLINE300) and collective (SynoLINE600) devices Universal usage thanks to easy connectivity to all 12 VDC systems Reliable alarming via existing network Easy installation due to free contacts for fi re and fault alarm

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 15 28.05.10 16:57

Page 57: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Fire Control Panels1-zone PanelsGenesis Series

3-2 © Siemens Switzerland Ltd 2010

Type Order No.

GEN2.. Fire control panel for connection to 12 VDC supply

The Genesis 2 makes it possible to install a single fire detection zone when connected to intrusion control panel‚ controlling and supervising a 2-wire line‚ equipped with up to 32 conventional/collective detectors at 24 VDC.The Genesis 2 is supplied with 13.8 VDC from the intrusion control pan-el and‚ by means of an internal converter‚ is able to provide the 24 VDC supply required by the detectors and/or call points. This eliminates the need for an external 24 VDC power supply and battery backup‚ as in the case of mains failure or disconnection‚ the intrusion control panel back-up powers the system. Compatible with conventional/SynoLINE300 and collective/SynoLINE600.

Alarm relay output (NO/NC) 30 VDC / 1 A

Fault relay output (NO/NC) 30 VDC / 1 A

Power supply 11... 14 VDC / <200 mA

Output line voltage (stand-by) 17.5... 24 VDC

Stand-by current 35... 45 mA

Dimensions (W x H x D) 134 x 85 x 27 mm

Data sheet 009159

GEN2..

GEN2-en Fire control panel for connection to 12 VDC supply

See GEN2.. for technical overview and note the additional / other specifications:

English language printed on the product.

BPZ:9300110001

GEN2-de Fire control panel for connection to 12 VDC supply

See GEN2.. for technical overview and note the additional / other specifications:

German language printed on the product.

BPZ:9300150001

GEN2-it Fire control panel for connection to 12 VDC supply

See GEN2.. for technical overview and note the additional / other specifications:

Italian language printed on the product.

BPZ:9300120001

GEN2-se Fire control panel for connection to 12 VDC supply

See GEN2.. for technical overview and note the additional / other specifications:

Swedish language printed on the product.

BPZ:9300130001

GEN2-fr Fire control panel for connection to 12 VDC supply

See GEN2.. for technical overview and note the additional / other specifications:

French language printed on the product.

BPZ:9300180001

GEN2-nl Fire control panel for connection to 12 VDC supply

See GEN2.. for technical overview and note the additional / other specifications:

Dutch language printed on the product.

BPZ:9300190001

03.fm Seite 2 Mittwoch, 28. Juli 2010 8:25 08

Page 58: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Fire Control Panels1-zone PanelsGenesis Series

3-3© Siemens Switzerland Ltd 2010

3Type Order No.

GEN2-es Fire control panel for connection to 12 VDC supply

See GEN2.. for technical overview and note the additional / other specifications:

Spanish language printed on the product.

BPZ:9300100001

MGEN2 Fire control panel PCB for all languages

As GEN2.. for technical specifications but without housing.

BPZ:9300170001

03.fm Seite 3 Mittwoch, 28. Juli 2010 8:25 08

Page 59: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Fire Control Panels

FC10 fi re control panel – for easy controlFC10 has been designed to ensure the simplest operation possible – with clear LED displays, a key switch, and an ergonomically designed keyboard. System testing and isolation can be performed with confi dence using the comprehensive array of clear, concise controls and indicators. Independent controls and the option of code or key switch access allow users to decide which is best for them. The ability of FC10 to work in two distinct modes reduces the possibility of false alarms and the simple method of selection allows this feature to be used without complication. Furthermore, FC10 can be programmed to delay communication with the fi re brigade for automatic alarms in “manned” mode.

Manned/unmanned operation Differentiation of manual and automatic alarm origin without separate wiring Code or key switch user access Clear, comprehensive indication and controls for easy operation Vast array of programmable functions Optional clock and alarm counter

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 16 28.05.10 16:57

Page 60: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Easy control with the conventional fi re control panel FC10The brief overview below demonstrates the perfect interaction of the panel and the devices

FC1002-A

Manual call pointFDM1101A-Rx

Optical smoke detector OP320C

Manual callpointDM1101

Alarm transmission

Fault transmission

Multi-sensor smoke detector OH320C

Heat detector HI320C (rate of rise and maximum)

Smoke detector DO1101A collective wide spectrum

Heat detector HI322C (maximum)

Alarm indicator AI91C/AI92C

Alarm indicator FDAI91/FDAI92

conventional (SynoLINE300)

conventional (SynoLINE300)

collective (SynoLINE600)

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 17 28.05.10 16:57

Page 61: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Fire Control Panels2-zone PanelsFC10 Series

3-6 © Siemens Switzerland Ltd 2010

Type Order No.

FC1002.. 2-zone conventional unit

The FC10 series sets the new standard in functionality and design for conventional fire detection panels. FC1002.. is an easy-to-handle‚ cost-effective fire detection panel that is ideal for small installations. Easy on-site configuration. Each line can be individually configured to AlgoRex collective or Synova conventional. This allows connection to Sinteso FDOOT241-9 (collective mode)‚ AlgoRex DS11 (collective) and Synova conventional detectors. Furthermore this includes special detectors as FDF2x1-9 flame detectors‚ FDL241-9 linear smoke detec-tor.

Conventional line 2

Transmission output contact 2 x 30 VDC / 1 A

Supervised output 2 x 24 VDC / 0.5 A

Control output 5 x 24 VDC / 40 mA

Control input 3

Mains voltage 115... 230 VAC / 0.7 A +10 %... -15 %‚ 50/60 Hz

Power consumption 13... 25 VA

Quiescent current 80 mA

Battery capacity 2 x 12 V / 7.2 Ah

Standard EN 54-2‚ EN 54-4

Dimensions (W x H x D) 370 x 286 x 90 mm

Case protection category IP40

Color white‚ zRAL 9003

Data sheet A6V10277145

Accessories Z3B171 Relay moduleFCA1007 Key switch kitFCA1016 Battery holder

FC1002..

FC1002-A 2-zone conventional unit (Standard)

See FC1002.. for technical overview and note the additional / other specifications:

Inscription stripes are enclosed in the following languages: English‚ French‚ German‚ Italian‚ Spanish‚ Dutch‚ Flemish‚ Portuguese‚ Polish‚ Czech‚ Swedish and Danish.

S54380-C2-A1

FC1002-B 2-zone conventional unit (Head removal monitoring)

See FC1002.. for technical overview and note the additional / other specifications:

Special line monitoring for removal of a detector.Inscription stripes in English are enclosed.

S54380-C2-A10

FC1002-C 2-zone conventional unit (Nordic)

See FC1002.. for technical overview and note the additional / other specifications:

Operating access through Nordic key.Inscription stripes are enclosed in the following languages: Swedish‚ Danish‚ Norwegian and Finnish.

S54380-C2-A20

03.fm Seite 6 Mittwoch, 28. Juli 2010 8:25 08

Page 62: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Fire Control Panels2-zone PanelsAccessories FC1002

3-7© Siemens Switzerland Ltd 2010

3Type Order No.

Z3B171 Relay module with 1 contact

The relay module is an additional fire event control module‚ activated by the fire control panel's control output.

Contact rating 250 VAC / 10 A

Delivery unit 10 pieces

BPZ:4843830001

FCA1007 Key switch kit

To provide operating access via key switch instead of password.

A6E60500026

FCA1016 Battery holder

Battery holder for 7 Ah batteries

S54400-B90-A1

03.fm Seite 7 Mittwoch, 28. Juli 2010 8:25 08

Page 63: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Fire Control Panels4-zone PanelsFC10 Series

3-8 © Siemens Switzerland Ltd 2010

Type Order No.

FC1004.. 4-zone conventional unit

The FC10 series sets the new standard in functionality and design for conventional fire detection panels. FC1004.. is an easy-to-handle‚ cost-effective fire detection panel that is ideal for small installations. Easy on-site configuration. Each line can be individually configured to AlgoRex collective or Synova conventional. This allows connection to Sinteso FDOOT241-9 (collective mode)‚ AlgoRex DS11 (collective) and Synova conventional detectors. Furthermore this includes special detectors as FDF2x1-9 flame detectors‚ FDL241-9 linear smoke detec-tor.

Conventional line 4

Transmission output contact 2 x 30 VDC / 1 A

Supervised output 2 x 24 VDC / 0.5 A

Control output 7 x 24 VDC / 40 mA

Control input 3

Mains voltage 115... 230 VAC / 0.7 A +10 %... -15 %‚ 50/60 Hz

Power consumption 13... 25 VA

Quiescent current 90 mA

Battery capacity 2 x 12 V / 7.2 Ah

Standard EN 54-2‚ EN 54-4

Dimensions (W x H x D) 370 x 286 x 90 mm

Case protection category IP40

Color white‚ zRAL 9003

Data sheet A6V10277145

Accessories Z3B171 Relay moduleFCA1007 Key switch kitFCA1016 Battery holder

FC1004..

FC1004-A 4-zone conventional unit (Standard)

See FC1004.. for technical overview and note the additional / other specifications:

Inscription stripes are enclosed in the following languages: English‚ French‚ German‚ Italian‚ Spanish‚ Dutch‚ Flemish‚ Portuguese‚ Polish‚ Czech‚ Swedish and Danish.

S54380-C3-A1

FC1004-B 4-zone conventional unit (Head removal monitoring)

See FC1004.. for technical overview and note the additional / other specifications:

Special line monitoring for removal of a detector.Inscription stripes in English are enclosed.

S54380-C3-A10

FC1004-C 4-zone conventional unit (Nordic)

See FC1004.. for technical overview and note the additional / other specifications:

Operating access through Nordic key.Inscription stripes are enclosed in the following languages: Swedish‚ Danish‚ Norwegian and Finnish.

S54380-C3-A20

FC1004-E 4-zone conventional unit (NL)

See FC1004.. for technical overview and note the additional / other specifications:

Additional evacuation functions according to NEN2575.Inscription stripes in Dutch are enclosed.

S54380-C3-A30

03.fm Seite 8 Mittwoch, 28. Juli 2010 8:25 08

Page 64: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Fire Control Panels4-zone PanelsAccessories FC1004

3-9© Siemens Switzerland Ltd 2010

3Type Order No.

Z3B171 Relay module with 1 contact

The relay module is an additional fire event control module‚ activated by the fire control panel's control output.

Contact rating 250 VAC / 10 A

Delivery unit 10 pieces

BPZ:4843830001

FCA1007 Key switch kit

To provide operating access via key switch instead of password.

A6E60500026

FCA1016 Battery holder

Battery holder for 7 Ah batteries

S54400-B90-A1

03.fm Seite 9 Mittwoch, 28. Juli 2010 8:25 08

Page 65: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Fire Control Panels8-zone PanelsFC10 Series

3-10 © Siemens Switzerland Ltd 2010

Type Order No.

FC1008.. 8-zone conventional unit

The FC10 series sets the new standard in functionality and design for conventional fire detection panels. FC1008.. is an easy-to-handle‚ cost-effective fire detection panel that is ideal for small installations. Easy on-site configuration. Each line can be individually configured to AlgoRex collective or Synova conventional. This allows connection to Sinteso FDOOT241-9 (collective mode)‚ AlgoRex DS11 (collective) and Synova conventional detectors. Furthermore this includes special detectors as FDF2x1-9 flame detectors‚ FDL241-9 linear smoke detec-tor.

Conventional line 8

Transmission output contact 2 x 30 VDC / 1 A

Supervised output 2 x 24 VDC / 0.5 A

Control output 14 x 24 VDC / 40 mA

Control input 6

Mains voltage 115... 230 VAC / 1.5 A +10 %... -15 %‚ 50/60 Hz

Battery capacity 2 x 12 V / 12 Ah

Standard EN 54-2‚ EN 54-4

Dimensions (W x H x D) 506 x 378 x 125 mm

Case protection category IP40

Color housing/cover grey‚ zRAL 9006/white‚ zRAL 9003

Data sheet A6V10277147

Expansion FCA1002 Display unitFCA1003 Sounder control cardFCA1000-FF Interface card SSTFCA1005-D RT-isolation cardFCA1006-F RS232 adapter

Accessories Z3B171 Relay moduleFCA1007 Key switch kitFCA1014 Battery holder

FC1008..

FC1008-A 8-zone conventional unit (Standard)

See FC1008.. for technical overview and note the additional / other specifications:

Inscription stripes are enclosed in the following languages: English‚ French‚ German‚ Italian‚ Spanish‚ Dutch‚ Flemish‚ Portuguese‚ Polish‚ Czech‚ Swedish and Danish.

Power consumption 25... 45 VA

Quiescent current 125 mA

S54380-C4-A1

FC1008-B 8-zone conventional unit (Head removal monitoring)

See FC1008.. for technical overview and note the additional / other specifications:

Special line monitoring for removal of a detector.Inscription stripes in English are enclosed.

Power consumption 25... 45 VA

Quiescent current 125 mA

S54380-C4-A10

03.fm Seite 10 Mittwoch, 28. Juli 2010 8:25 08

Page 66: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Fire Control Panels8-zone PanelsFC10 Series

3-11© Siemens Switzerland Ltd 2010

3Type Order No.

FC1008-C 8-zone conventional unit (Nordic)

See FC1008.. for technical overview and note the additional / other specifications:

Operating access through Nordic key.Inscription stripes are enclosed in the following languages: Swedish‚ Danish‚ Norwegian and Finnish.

Power consumption 25... 45 VA

Quiescent current 125 mA

S54380-C4-A20

FC1008-D 8-zone conventional unit (CH)

See FC1008.. for technical overview and note the additional / other specifications:

With special fire brigade operating panel for the Swiss market.Inscription stripes in Swiss German‚ Swiss Italian and Swiss French are enclosed.

Power consumption 25... 45 VA

Quiescent current 125 mA

S54380-C4-A30

FC1008-E 8-zone conventional unit (Evacuation)

See FC1008.. for technical overview and note the additional / other specifications:

Additional evacuation functions according to NEN2575.With 3.5 A power supply FCP1004-E.Inscription stripes in Dutch are enclosed.

Power consumption 20... 110 VA

Quiescent current 170 mA

S54380-C4-A40

03.fm Seite 11 Mittwoch, 28. Juli 2010 8:25 08

Page 67: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Fire Control Panels8-zone PanelsExpansion FC1008

3-12 © Siemens Switzerland Ltd 2010

Type Order No.

FCA1002 Display unit

To provide alarm counter‚ clock‚ event memory‚ delay countdown. Fac-tory equipped with FC1008-E and FC1008-F‚ FC1012-F. Optional with FC1008-A/-B/-C/-D‚ FC1012-A/-B-C.

A6E60500021

FCA1003 Sounder control card

To provide 4 additional‚ monitored control lines. Not possible with FC1008-F‚ FC1012-F.

A6E60500022

FCA1005-D RT-isolation card

To provide hardware disconnecting facility for the remote transmission channels.

A6E60500024

03.fm Seite 12 Mittwoch, 28. Juli 2010 8:25 08

Page 68: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Fire Control Panels8-zone PanelsAccessories FC1008

3-13© Siemens Switzerland Ltd 2010

3Type Order No.

Z3B171 Relay module with 1 contact

The relay module is an additional fire event control module‚ activated by the fire control panel's control output.

Contact rating 250 VAC / 10 A

Delivery unit 10 pieces

BPZ:4843830001

FCA1007 Key switch kit

To provide operating access via key switch instead of password.

A6E60500026

FCA1014 Battery holder

Battery holder for 12 Ah or 17 Ah batteries

A6E60500069

03.fm Seite 13 Mittwoch, 28. Juli 2010 8:25 08

Page 69: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Fire Control Panels12-zone PanelsFC10 Series

3-14 © Siemens Switzerland Ltd 2010

Type Order No.

FC1012.. 12-zone conventional unit

The FC10 series sets the new standard in functionality and design for conventional fire detection panels. FC1012.. is an easy-to-handle‚ cost-effective fire detection panel that is ideal for small installations. Easy on-site configuration. Each line can be individually configured to AlgoRex collective or Synova conventional. This allows connection to Sinteso FDOOT241-9 (collective mode)‚ AlgoRex DS11 (collective) and Synova conventional detectors. Furthermore this includes special detectors as FDF2x1-9 flame detectors‚ FDL241-9 linear smoke detec-tor.

Conventional line 12

Transmission output contact 2 x 30 VDC / 1 A

Supervised output 2 x 24 VDC / 0.5 A

Control output 18 x 24 VDC / 40 mA

Control input 6

Mains voltage 115... 230 VAC / 1.5 A +10 %... -15 %‚ 50/60 Hz

Power consumption 25... 45 VA

Battery capacity 2 x 12 V / 12 Ah

Standard EN 54-2‚ EN 54-4

Dimensions (W x H x D) 506 x 378 x 125 mm

Case protection category IP40

Color housing/cover grey‚ zRAL 9006/white‚ zRAL 9003

Data sheet A6V10277147

Expansion FCA1002 Display unitFCA1003 Sounder control cardFCA1004-F Line extension card SSTFCA1005-D RT-isolation cardFCA1006-F RS232 adapter

Accessories Z3B171 Relay moduleFCA1007 Key switch kit

FC1012..

FC1012-A 12-zone conventional unit (Standard)

See FC1012.. for technical overview and note the additional / other specifications:

Inscription stripes are enclosed in the following languages: English‚ French‚ German‚ Italian‚ Spanish‚ Dutch‚ Flemish‚ Portuguese‚ Polish‚ Czech‚ Swedish and Danish.

Quiescent current 155 mA

S54380-C5-A1

FC1012-B 12-zone conventional unit (Head removal monitoring)

See FC1012.. for technical overview and note the additional / other specifications:

Special line monitoring for removal of a detector.Inscription stripes in English are enclosed.

Quiescent current 155 mA

S54380-C5-A10

03.fm Seite 14 Mittwoch, 28. Juli 2010 8:25 08

Page 70: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Fire Control Panels12-zone PanelsFC10 Series

3-15© Siemens Switzerland Ltd 2010

3Type Order No.

FC1012-C 12-zone conventional unit (Nordic)

See FC1012.. for technical overview and note the additional / other specifications:

Operating access through Nordic key.Inscription stripes are enclosed in the following languages: Swedish‚ Danish‚ Norwegian and Finnish.

Quiescent current 155 mA

S54380-C5-A20

03.fm Seite 15 Mittwoch, 28. Juli 2010 8:25 08

Page 71: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Fire Control Panels12-zone PanelsExpansion FC1012

3-16 © Siemens Switzerland Ltd 2010

Type Order No.

FCA1002 Display unit

To provide alarm counter‚ clock‚ event memory‚ delay countdown. Fac-tory equipped with FC1008-E and FC1008-F‚ FC1012-F. Optional with FC1008-A/-B/-C/-D‚ FC1012-A/-B-C.

A6E60500021

FCA1003 Sounder control card

To provide 4 additional‚ monitored control lines. Not possible with FC1008-F‚ FC1012-F.

A6E60500022

FCA1005-D RT-isolation card

To provide hardware disconnecting facility for the remote transmission channels.

A6E60500024

03.fm Seite 16 Mittwoch, 28. Juli 2010 8:25 08

Page 72: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Fire Control Panels12-zone PanelsAccessories FC1012

3-17© Siemens Switzerland Ltd 2010

3Type Order No.

Z3B171 Relay module with 1 contact

The relay module is an additional fire event control module‚ activated by the fire control panel's control output.

Contact rating 250 VAC / 10 A

Delivery unit 10 pieces

BPZ:4843830001

FCA1007 Key switch kit

To provide operating access via key switch instead of password.

A6E60500026

03.fm Seite 17 Mittwoch, 28. Juli 2010 8:25 08

Page 73: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

081031_Product_Catalog_Innen_07lay.indd 17 24.07.09 18:04

Page 74: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Extinguishing Control Panels

XC10 – compact panels for fi re detection and extinguishing controlXC10 panels are the perfect choice for protecting valuable objects, a single room or multiple sectors with sophisticated requirements.XC10 can be installed as an independent control panel or be integrated into the fi re safety system Cerberus® PRO and be combined with the extinguishing system Sinorix.

Fire detection and extinguishing control in one panel Broad range of installations possible – single and multi sectors, stand-alone or integrated into a larger fi re safety system

Easy integration into Cerberus PRO for increased safety snoitacilppa dna stnega gnihsiug nitxe fo sepyt lla rof elbatiuS Multi-sector applications for the protection of up to 16 fl ooding zones Fast easy installation and commissioning Complies with international standards (EN 54-2/4, EN 12094-1,...)

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen_NEU.indd 19 01.06.10 13:31

Page 75: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Extinguishing Control PanelsConnectable to Fire Detection SystemsXC10 Series

4-2 © Siemens Switzerland Ltd 2010

Type Order No.

XC1001-A Extinguishing panel Standard

The compact dimensions of the Standard variant of XC1001-A are ide-ally adapted for single-sector applications‚ small to medium installa-tions. It provides a full range of monitored inputs and outputs as well as digital and relays outputs. Self-contained control panel including fire detection and extinguishing control. The configurable relay outputs can be used to transmit informations to an FS20/FC20 fire detection panel via FDnet/C-NET I/O modules.The detection lines can be configured to AlgoRex‚ Cerberus PRO‚ Sinteso and Synova.Easy and fast commissioning using 4 digital displays.

Conventional line 3

Alarm relay output (NO/NC) 30 V / 1 A max.

Control output 24 V / 1 A max.

Control input 4 (non monitored). Activation via contact.

Mains voltage 115... 230 VAC +10 %... -15 %‚ 50/60 Hz

Power consumption max. 150 VA

Battery capacity 2 x 12 V / 4.5... 17 Ah

Standard EN 12094-1‚ EN 54-2/A1‚ EN 54-4/A2

Dimensions (W x H x D) 370 x 286 x 90 mm

Case protection category IP30

Color white‚ zRAL 9003 (cover)‚ white alu-minium‚ zRAL 9006 (user interface)

Data sheet A6V10257471

Expansion XCE1002 Trigger elementXCA1020 Accessory set for FDCIOXCA1030 Multi-zone extension moduleXCA1031 Common multi-zone module

Accessories Z3B171 Relay moduleFCA1007 Key switch kitFCA1014 Battery holderXCH1001-A Cover set

S54390-C1-A1

04.fm Seite 2 Mittwoch, 28. Juli 2010 8:28 08

Page 76: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Extinguishing Control PanelsConnectable to Fire Detection SystemsXC10 Series

4-3© Siemens Switzerland Ltd 2010

4

Type Order No.

XC1005-A Extinguishing panel Comfort

The XC1005-A Comfort variant offers the same functions and connec-tion possibilities than XC1001-A. Thanks to the robustness of the cabi-net‚ this variant is an ideal choice for medium size single-sector instal-lations.With large and robust cabinet‚ a maximum of 72 h backup time with bat-tery capacity of 17 Ah‚ more space inside the cabinet for optional inter-faces or modules and display countdown timer before extinguishing release.

Conventional line 3

Alarm relay output (NO/NC) 30 V / 1 A max.

Control output 24 V / 1 A max.

Control input 4 (non monitored). Activation via contact.

Mains voltage 115... 230 VAC +10 %... -15 %‚ 50/60 Hz

Battery capacity 2 x 12 V / 4.5... 17 Ah

Dimensions (W x H x D) 505 x 375 x 125 mm

Case protection category IP40

Color white‚ zRAL 9003 (cover)‚ white alu-minium‚ zRAL 9006 (user interface)

Data sheet A6V10257471

Expansion XCE1002 Trigger elementXCA1020 Accessory set for FDCIOXCA1030 Multi-zone extension moduleXCA1031 Common multi-zone module

Accessories Z3B171 Relay moduleFCA1007 Key switch kitFCA1014 Battery holderXCH1005-A Cover set

S54390-C3-A1

04.fm Seite 3 Mittwoch, 28. Juli 2010 8:28 08

Page 77: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Extinguishing Control PanelsConnectable to Fire Detection SystemsXC10 Series

4-4 © Siemens Switzerland Ltd 2010

Type Order No.

XC1003-A Extinguishing panel Rack

The XC1003-A 19" Rack variant offers the same connection possibilities than XC1001-A. Up to 16 panels can be installed in a 19'' housing and configured to control a complex multi-sector installation.Thanks to the optional multi-sector modules‚ up to 16 panels can be connected together‚ a common control cylinder can be activated‚ selec-tor valves can be controlled and their position can be monitored and inter-blocking functions can be configured.

Conventional line 3

Alarm relay output (NO/NC) 30 V / 1 A max.

Control output 24 V / 1 A max.

Control input 4 (non monitored). Activation via contact.

Mains voltage 115... 230 VAC +10 %... -15 %‚ 50/60 Hz

Power consumption max. 150 VA

Battery capacity 2 x 12 V / 4.5... 17 Ah

Standard EN 12094-1‚ EN 54-2/A1‚ EN 54-4/A2

Dimensions (W x H x D) 482.6 x 177.8 x 187

Case protection category IP30

Color White aluminium‚ zRAL 9006

Data sheet A6V10257471

Expansion XCE1002 Trigger elementXCA1020 Accessory set for FDCIOXCA1030 Multi-zone extension moduleXCA1031 Common multi-zone module

Accessories Z3B171 Relay moduleFCA1007 Key switch kitFCA1014 Battery holderPF12 Cover plate 1UPF13 Cover plate 2UXCH1003-A Cover set

S54390-C2-A1

04.fm Seite 4 Mittwoch, 28. Juli 2010 8:28 08

Page 78: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Extinguishing Control PanelsConnectable to Fire Detection SystemsExpansion XC10

4-5© Siemens Switzerland Ltd 2010

4

Type Order No.

FCA1014 Battery holder

Battery holder for 12 Ah or 17 Ah batteries

A6E60500069

XCA1030 Multi-zone extension module

This module is connected to the XC1003-A mainboard XCM1002. Each extinguishing panel which is included in a multi-sector application must be equipped with this module.

S54390-A5-A1

XCA1031 Common multi-zone module

The inputs/outputs are monitored by the module itself. The power sup-ply is provided by the first and the last XC1003-A control unit.

S54390-A6-A1

XCA1020 Accessory set for FDCIO

Mounting support for I/O module FDCIO222 for the connection to a fire detection system.

A5Q00025158

XCE1002 Trigger element

Required as an alarm trigger element for manual call points with func-tionality Hold/Abort in case more than one manual call point is connect-ed on monitor control line 3 of the XC10.Manual call point type DM1103-S does not use this element‚ but the functionality of this trigger element XCE1002 is implemented.

A5Q00015659

04.fm Seite 5 Mittwoch, 28. Juli 2010 8:28 08

Page 79: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Extinguishing Control PanelsConnectable to Fire Detection SystemsAccessories XC10

4-6 © Siemens Switzerland Ltd 2010

Type Order No.

Z3B171 Relay module with 1 contact

The relay module is an additional fire event control module‚ activated by the fire control panel's control output.

Contact rating 250 VAC / 10 A

Delivery unit 10 pieces

BPZ:4843830001

FCA1007 Key switch kit

To provide operating access via key switch instead of password.

A6E60500026

04.fm Seite 6 Mittwoch, 28. Juli 2010 8:28 08

Page 80: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Extinguishing Control PanelsConnectable to Fire Detection SystemsXT10 Series

4-7© Siemens Switzerland Ltd 2010

4

Type Order No.

XT1001-A1 Repeater display

Small repeater display for use with XC10 extinguishing control panel system.Up to 16 repeaters can be connected to each XC10 extinguishing con-trol panel to provide control and remote status indication like Fire alarms‚ Communication faults‚ Activated‚ Discharged‚ Manual blocked‚ Automatic blocked‚ Fault‚ Disable‚ Loss of agent‚ Emergency hold and Power supply fault possible. Controls are Buzzer silence and Lamp test.One cable for data communication and one cable for power supply required. Power supply via the XC10 power supply output‚ separate 24 V power supply possible.

Storage temperature -10… +60 °C

Operating temperature -5... +40 °C

Quiescent current 18 mA at 24 V

Mains voltage 8... 30 VDC

Dimensions (W x H x D) 200 x 210 x 48

Case protection category IP40

Color grey‚ zRAL 9002

S54390-Z16-A1

XT1002-A1 Repeater display

Small repeater display for use with XC10 extinguishing control panel system.Up to 16 repeaters can be connected to each XC10 extinguishing con-trol panel to provide control and remote status indication like Fire alarms‚ Communication faults‚ Activated‚ Discharged‚ Manual blocked‚ Automatic blocked‚ Fault‚ Disable‚ Loss of agent‚ Emergency hold and Power supply fault possible. Controls are Buzzer silence‚ Lamp test‚ Mode of operation and Sounder silence via access level key operation.One cable for data communication and one cable for power supply required. Power supply via the XC10 power supply output‚ separate 24 V power supply possible.

Storage temperature -10… +60 °C

Operating temperature -5... +40 °C

Quiescent current 18 mA at 24 V

Mains voltage 8... 30 VDC

Dimensions (W x H x D) 200 x 210 x 48

Case protection category IP40

Color grey‚ zRAL 9002

S54390-Z15-A1

04.fm Seite 7 Mittwoch, 28. Juli 2010 8:28 08

Page 81: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Answers for infrastructure.

With XC10, Siemens offers a family of control panels for comprehensive fi re safety: the panel family combines both fi re detection and extinguishing control. XC10 panels are the ideal choice for protecting valuable objects, a single- or a multi-sector application with sophisticated requirements. XC10 can be installed as an independent control panel or be integrated into a larger fi re safety system. In addition, XC10 panels are easy to operate. The user interface provides a clear layout, so users can gain a complete system overview at a glance. And it’s a matter of course that all products comply with the latest international standards. www.siemens.com/XC10

XC10 – effi cient controlpanels for comprehensivefi re safetyFrom fi re detection to extinguishing control –from single-sector to multi-sector applications

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen_NEU.indd 20 01.06.10 13:31

Page 82: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) Peripherals

Providing fast reliable detection with patented technologyNursing homes, offi ce buildings or production areas – people and assets have to be protected and business continuity secured. The Cerberus® PRO detector range provides the benefi ts of Siemens’ vast experience in detection techniques and applications. This experience ensures utterly reliable detection response. Thanks to special algo-rithms and selectable parameter sets, for example, detectors can be

.snoitidnoc lat nemnorivne detcepxe eht ot detsujda

Siemens has more than 150 years experience in fi re safety – with more than 60 million detectors installed worldwide

Fire detectors process signals with special detection algorithms – high reliability from false alarms Fire detectors offer selectable parameter sets – to adjust them to the surrounding conditions A wide range of special detectors – to cover even special applications All detectors are connected via and powered by C-NET – less wiring and reuse of existing cables

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 21 28.05.10 16:57

Page 83: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Addressable fi re detectors – point detectors

Detector base sealRS720

Connection terminalDBZ1190-AB

* cannot be used together with RS720

Micro terminalDBZ1190-AA

Multi-sensor smoke detector

OH720

Detector base DB721

Designation plateFDBZ291*

Detector locking deviceLP720

or

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 22 28.05.10 16:57

Page 84: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Fire DetectorsPoint Detectors

5-3© Siemens Switzerland Ltd 2010

5

Type Order No.

OH720 Multi-sensor smoke detector

For the detection of flaming fires caused by the combustion of liquid and solid matters‚ as well as smoldering fires. For reliable fire detection in environments with deceptive phenomena.Works according to the scattered-light principle with an optical forward scattering sensor. An additional heat sensor increases the fire detector's immunity to deceptive phenomena. Selectable detection behavior by different parameter sets. Immunity against transient false alarm causes.The base must be ordered separately.Scope of deliveryDetector and dust cap.

Communication protocol C-NET

Operating voltage 12... 33 VDC

Quiescent current z230 NA

Ext. alarm indicator 2

Operating temperature -10... +50 °C

Storage temperature -30... +70 °C

Permissible air speed max. 5 m/s

Relative humidity L95 %

Color white‚ zRAL 9010

Protection category IP40IP42 with detector base seal RS720

System compatibility FS720

Standard CEA4021‚ EN 54-7‚ EN 54-17

Dimensions (Ø x H) 117 x 59 mm (incl. base)

Data sheet A6V10202198

Accessories LP720 Detector locking device

S54310-F2-A1

OP720 Optical smoke detector

For the detection of smoke-generating flaming and smoldering fires. Works according to the scattered-light principle with an optical forward scattering sensor. Selectable detection behavior by different parameter sets. The base must be ordered separately.Scope of deliveryDetector and dust cap.

Communication protocol C-NET

Operating voltage 12... 33 VDC

Quiescent current z220 NA

Ext. alarm indicator 2

Operating temperature -10... +50 °C

Storage temperature -30... +70 °C

Permissible air speed max. 5 m/s

Relative humidity L95 %

Color white‚ zRAL 9010

Protection category IP40IP42 with detector base seal RS720

System compatibility FS720

Standard EN 54-7‚ EN 54-17

Dimensions (Ø x H) 117 x 56 mm (incl. base)

Data sheet A6V10202198

Accessories LP720 Detector locking device

S54310-F1-A1

05.fm Seite 3 Mittwoch, 28. Juli 2010 8:33 08

Page 85: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Fire DetectorsPoint Detectors

5-4 © Siemens Switzerland Ltd 2010

Type Order No.

HI720 Heat detector (static+RoR)

For use in areas where smoke detection is impractical due to high level of dust‚ dirt‚ steam and high humidity. Selectable parameter sets for rate of rise and fixed temperature.The base must be ordered separately.Scope of deliveryDetector and dust cap.

Communication protocol C-NET

Operating voltage 12... 33 VDC

Quiescent current z200 NA

Ext. alarm indicator 2

Operating temperature -10... +50 °C

Storage temperature -30... +70 °C

Relative humidity L95 %

Color white‚ zRAL 9010

Protection category IP40IP42 with detector base seal RS720

System compatibility FS720

Standard EN 54-5‚ EN 54-17

Dimensions (Ø x H) 117 x 59 mm (incl. base)

Data sheet A6V10202198

Accessories LP720 Detector locking device

S54310-F4-A1

HI722 Heat detector (static)

Suitable in areas‚ in which temporary high variations in temperature arise. Measures the ambient temperature‚ when the maximum temper-ature is exceeded the detector sends a danger signal to the fire control panel.The base must be ordered separatelyScope of deliveryDetector and dust cap.

Communication protocol C-NET

Operating voltage 12... 33 VDC

Quiescent current z200 NA

Ext. alarm indicator 2

Operating temperature -10... +50 °C

Storage temperature -30... +70 °C

Relative humidity L95 %

Color white‚ zRAL 9010

Protection category IP40IP42 with detector base seal RS720

System compatibility FS720

Standard EN 54-5‚ EN 54-17

Dimensions (Ø x H) 117 x 59 mm (incl. base)

Data sheet A6V10202198

Accessories LP720 Detector locking device

S54310-F3-A1

05.fm Seite 4 Mittwoch, 28. Juli 2010 8:33 08

Page 86: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Fire DetectorsPoint Detectors

5-5© Siemens Switzerland Ltd 2010

5

Type Order No.

Accessories

LP720 Detector locking device

Threaded pin M3 x 12 to protect detector against theft.Scope of delivery2 hexagonal wrenches100 threaded pins

S54319-F9-A1

DB721 Detector base with loop contact

Universal base with extra large mounting slots facilitate use with a wide variety of back boxes and other electrical accessories. Connecting ter-minals for cable diameter at 1.6 mm2. Place for auxiliary terminals 2x DBZ1190-AA and 2x DBZ1190-AB. For all point detectors of the series Cerberus PRO FD720. Back entry for recess supply wiring. 2 breakouts on the side for surface wiring of cables up to 8 mm in diameter. By using the detector base with loop contact (DB721) the detector line is not interrupted even if no point detector is mounted

Cable capacity 0.2... 1.6 mm2

Dimensions (Ø x H) 117 x 23 mm

Color white‚ zRAL 9010

Accessories FDBZ291 Designation plateRS720 Detector base sealDBZ1190-AA Micro terminal 0.5 mm2

DBZ1190-AB Connection terminal 2.5 mm2

S54319-F11-A1

05.fm Seite 5 Mittwoch, 28. Juli 2010 8:33 08

Page 87: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Fire DetectorsPoint Detectors

5-6 © Siemens Switzerland Ltd 2010

Type Order No.

DBS720 Sounder base

Compatible with all point detectors of the series Cerberus PRO.The sounder base DBS720 and the detector compose a single unit‚ which already has a base and is mounted on ceilings‚ e.g. in hotel rooms‚ hospitals or nursing homes.The sounder base serves for acoustic alarming in the addressed FS720 fire detection system. The sounder base can be allocated freely from the fire control panel to activate as required. It is not dependent upon an alarm signal from its associated detector.Synchronized with all other alarm sounder and sounder beacon devices in the same detector line (C-NET).No auxiliary power supply required; power is supplied via C-NET.For recess supply wiring. For surface supply wiring‚ remove the corre-sponding breakouts for cable diameter up to max. Ø8 mm.

Communication protocol C-NET

Operating voltage 12... 33 VDC

Quiescent current 150 μA

Alarm current 1.2 mA

Cable capacity 0.2... 1.6 mm2

Number of sounds 11

Sound intensity 80... 88 dBA

Ext. alarm indicator 2

Operating temperature -25... +70 °C

Storage temperature -30... +70 °C

Relative humidity L95 %

Color white‚ zRAL 9010

Protection category IP41IP42 with detector base seal RS720

System compatibility C-NET -> FS720

Standard EN 54-3

Dimensions (W x H x D) 175 x 117 x 29 mm

Data sheet A6V10203095

Accessories FDBZ291 Designation plateRS720 Detector base sealDBZ1190-AA Micro terminal 0.5 mm2

DBZ1190-AB Connection terminal 2.5 mm2

S54319-F5-A1

Accessories

FDBZ291 Designation plate

To identify the location address for detector bases.

Dimensions (W x H) 62 x 35 mm

Color transparent

Delivery unit 10 pieces

A5Q00002621

RS720 Detector base seal

Seal for higher protection category.Compatible with base DB721 and sounder base DBS720.Not usable together with the designation plate FDBZ291.

Dimensions (Ø x H) 119 x 6.5 mm

Color transparent

Delivery unit 10 pieces

S54319-F8-A1

05.fm Seite 6 Mittwoch, 28. Juli 2010 8:33 08

Page 88: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Fire DetectorsPoint Detectors

5-7© Siemens Switzerland Ltd 2010

5

Type Order No.

DBZ1190-AA Micro terminal 0.5 mm2‚ 4-pole

As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.

Cable capacity 0.28... 0.5 mm2

Dimensions (W x H x D) 10 x 7 x 10 mm

Delivery unit 50 pieces

BPZ:4677080001

DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole

As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.

Cable capacity 1... 2.5 mm2

Dimensions (W x H x D) 13.5 x 9.5 x 19.5 mm

Delivery unit 50 pieces

BPZ:4942340001

05.fm Seite 7 Mittwoch, 28. Juli 2010 8:33 08

Page 89: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation

5-8 © Siemens Switzerland Ltd 2010

Type Order No.

FDM221__ Manual call point

For immediate manual actuation of an alarm. For indoor and outdoor application. For surface- and recess-mounted feed lines in easily acces-sible places. Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is set back and the device is ready for operation again.The housing FDMH291-x and the switching unit FDME221 must be ordered separately.

Communication protocol FDnet/C-NET

Operating temperature -25... +70 °C

Storage temperature -30... +75 °C

Relative humidity L95 % (no condensation)

Protection category IP44

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard EN 54-11‚ EN 54-17

Dimensions (W x H x D) 87 x 87 x 46.6 mm

Data sheet 007001

Accessories FDMC291 Protective coverA5Q00004478 Screwed cable gland M20A5Q00004479 Back nut M20

Products to select from

FDMH291-R See Page 5-8

FDMH291-B See Page 5-9

FDMH291-G See Page 5-9

FDMH291-Y See Page 5-8

FDME221 See Page 5-9

FDM221__

FDMH291-R Housing red with key

Housing with key for electronic unit.

Color red‚ zRAL 3000

A5Q00002217

FDMH291-Y Housing yellow with key

Housing with key for electronic unit.

Color yellow‚ zRAL 1023

A5Q00004979

05.fm Seite 8 Mittwoch, 28. Juli 2010 8:33 08

Page 90: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation

5-9© Siemens Switzerland Ltd 2010

5

Type Order No.

FDMH291-G Housing green with key

Housing with key for electronic unit.

Color green‚ zRAL 6024

A5Q00004981

FDMH291-B Housing blue with key

Housing with key for electronic unit.

Color blue‚ zRAL 5005

A5Q00004980

FDME221 Switching unit with direct alarm actuation

Switching unit with integrated line separator and built-in alarm indica-tor (LED). Two-colored LED for alarm and test.The switching unit can be placed immediately after connecting the feed line‚ which is an advantage if the line is tested with a line testing device.

Operating voltage 12... 33 VDC

Quiescent current 200 NA

Terminal block 0.28... 1.5 mm2

A5Q00002451

Accessories

FDMC291 Protective cover

The protective cover protects the manual call point from unintentional glass break. For manual call point housings FDMH291-x.

Delivery unit 5 pieces

A5Q00001644

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

05.fm Seite 9 Mittwoch, 28. Juli 2010 8:33 08

Page 91: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation

5-10 © Siemens Switzerland Ltd 2010

Type Order No.

A5Q00004479 Back nut M20

Back nut to screwed cable gland M20 x 1.5.

Delivery unit 10 pieces

A5Q00004479

FDM225-RG Manual call point with glass plate

For immediate manual actuation of a fire alarm. For indoor and outdoor application. Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is reset and the device is ready for operation again. For surface- and recess-mounted feed lines in eas-ily accessible places.For surface mounting the housing base FDMH295-x must be ordered separately.

Communication protocol FDnet/C-NET

Operating voltage 13... 33 VDC

Quiescent current 180 NA

Terminal block 0.28… 1.5 mm2

Operating temperature -25... +70 °C

Storage temperature -30... +75 °C

Relative humidity L95 % (no condensation)

Protection category IP44

Color red‚ zRAL 3000

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard EN 54-11‚ EN 54-17

Dimensions (W x H x D) 87 x 87 x 20 mm

Data sheet 009023

Accessories FDMH295-R housing baseFDMH295-S housing base with 2 holes + grommets for cable Ø5 mmFDMC295 Protective cover

A5Q00013434

05.fm Seite 10 Mittwoch, 28. Juli 2010 8:33 08

Page 92: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation

5-11© Siemens Switzerland Ltd 2010

5

Type Order No.

FDM225-RP Manual call point with resettable plastic element

For immediate manual actuation of a fire alarm. For indoor and outdoor application. Direct alarm actuation by pushing on the plastic element. The switch is reset with the key and the device is ready for operation again. For surface- and recess-mounted feed lines in easily accessible places.For surface mounting the housing base FDMH295-x must be ordered separately.

Communication protocol FDnet/C-NET

Operating voltage 13... 33 VDC

Quiescent current 180 NA

Terminal block 0.28… 1.5 mm2

Operating temperature -25... +70 °C

Storage temperature -30... +75 °C

Relative humidity L95 % (no condensation)

Protection category IP44

Color red‚ zRAL 3000

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard EN 54-11‚ EN 54-17

Dimensions (W x H x D) 87 x 87 x 20 mm

Data sheet 009023

Accessories FDMH295-R housing baseFDMH295-S housing base with 2 holes + grommets for cable Ø5 mmFDMC295 Protective cover

A5Q00012020

Accessories

FDMH295-R Back box

Housing base for manual call points FDM225‚ FDM1101 and FDM1101A for surface mounting.

Color red‚ zRAL 3000

Dimensions (W x H x D) 87 x 87 x 33

Accessories A5Q00004478 Screwed cable gland M20A5Q00004479 Back nut M20DBZ1190-AB Connection terminal 2.5 mm2

A5Q00013437

FDMH295-S Back box with 2 entries

Housing base for manual call points FDM225‚ FDM1101 and FDM1101A with 2 holes on top fitted with grommet for cable Ø5 mm for surface mounting.

Color red‚ zRAL 3000

Dimensions (W x H x D) 87 x 87 x 33

Accessories DBZ1190-AB Connection terminal 2.5 mm2

A5Q00013438

05.fm Seite 11 Mittwoch, 28. Juli 2010 8:33 08

Page 93: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation

5-12 © Siemens Switzerland Ltd 2010

Type Order No.

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

A5Q00004479 Back nut M20

Back nut to screwed cable gland M20 x 1.5.

Delivery unit 10 pieces

A5Q00004479

DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole

As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.

Cable capacity 1... 2.5 mm2

Delivery unit 50 pieces

BPZ:4942340001

FDMC295 Protective cover

The protective cover protects the manual call points FDM225‚ FDM226‚ FDM1101 and FDM1101A from unintentional glass break.

Color transparent

Delivery unit 10 pieces

A5Q00013440

FDM226-RG Manual call point with glass plate incl. housing base

For immediate manual actuation of a fire alarm. For indoor and outdoor application. Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is reset and the device is ready for operation again. For surface- and recess-mounted feed lines in eas-ily accessible places.

Communication protocol FDnet/C-NET

Operating voltage 13... 33 VDC

Quiescent current 180 NA

Terminal block 0.28… 1.5 mm2

Operating temperature -25... +70 °C

Storage temperature -30... +75 °C

Relative humidity L95 % (no condensation)

Protection category IP66

Color red‚ zRAL 3000

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard EN 54-11‚ EN 54-17

Dimensions (W x H x D) 87 x 87 (113) x 57 mm

Data sheet 009023

Accessories FDMC295 Protective cover

A5Q00013435

05.fm Seite 12 Mittwoch, 28. Juli 2010 8:33 08

Page 94: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation

5-13© Siemens Switzerland Ltd 2010

5

Type Order No.

FDM226-RP Manual call point with resettable plastic element incl. housing base

For immediate manual actuation of a fire alarm. For indoor and outdoor application. Direct alarm actuation by pushing on the plastic element. The switch is reset with the key and the device is ready for operation again. For surface- and recess-mounted feed lines in easily accessible places.

Communication protocol FDnet/C-NET

Operating voltage 13... 33 VDC

Quiescent current 180 NA

Terminal block 0.28… 1.5 mm2

Operating temperature -25... +70 °C

Storage temperature -30... +75 °C

Relative humidity L95 % (no condensation)

Protection category IP66

Color red‚ zRAL 3000

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard EN 54-11‚ EN 54-17

Dimensions (W x H x D) 87 x 87 (113) x 57 mm

Data sheet 009023

Accessories FDMC295 Protective cover

A5Q00013436

Accessories

FDMC295 Protective cover

The protective cover protects the manual call points FDM225‚ FDM226‚ FDM1101 and FDM1101A from unintentional glass break.

Color transparent

Delivery unit 10 pieces

A5Q00013440

05.fm Seite 13 Mittwoch, 28. Juli 2010 8:33 08

Page 95: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation

5-14 © Siemens Switzerland Ltd 2010

Type Order No.

FDM224__ Manual call point

For immediate manual actuation of an alarm. For indoor and outdoor application. For surface- and recess-mounted feed lines in easily acces-sible places. Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is reset and the device is ready for operation again.The housing FDMH293-x and the switching unit FDME224 must be ordered separately.

Communication protocol FDnet/C-NET

Ext. alarm indicator 2

Operating temperature -25... +70 °C

Storage temperature -30... +75 °C

Relative humidity L95 % (no condensation)

Protection category IP44 (IP64 with protection seal)

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard EN 54-11‚ EN 54-17

Dimensions (W x H x D) 134 x 134 x 43 mm

Data sheet 007001

Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20A5Q00006735 Locking plug M20(1 hole)A5Q00010055 Locking plug M20(2 holes)

Products to select from

FDMH293-R See Page 5-14

FDMH293-B See Page 5-15

FDMH293-O See Page 5-15

FDMH293-G See Page 5-15

FDMH293-Y See Page 5-15

FDME224 See Page 5-16

FDM224__

FDMH293-R Housing red‚ with glass and key

Manual call point housing for the switching unit FDME223‚ FDME224.

Color red‚ zRAL 3000

A5Q00004023

05.fm Seite 14 Mittwoch, 28. Juli 2010 8:33 08

Page 96: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation

5-15© Siemens Switzerland Ltd 2010

5

Type Order No.

FDMH293-Y Housing yellow‚ with glass and key

Manual call point housing for the switching unit FDME223‚ FDME224.

Color yellow‚ zRAL 1023

A5Q00004908

FDMH293-G Housing green‚ with glass and key

Manual call point housing for the switching unit FDME223‚ FDME224.

Color green‚ zRAL 6024

A5Q00004911

FDMH293-B Housing blue‚ with glass and key

Manual call point housing for the switching unit FDME223‚ FDME224.

Color blue‚ zRAL 5005

A5Q00004909

FDMH293-O Housing orange‚ with glass and key

Manual call point housing for the switching unit FDME223‚ FDME224.

Color orange‚ zRAL 2010

S54311-F2-A1

05.fm Seite 15 Mittwoch, 28. Juli 2010 8:33 08

Page 97: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation

5-16 © Siemens Switzerland Ltd 2010

Type Order No.

FDME224 Switching unit with direct alarm actuation

Switching unit with integrated line separator and built-in alarm indica-tor (LED). Two-colored LED for alarm and test.The switching unit can be placed immediately after connecting the feed line‚ which is an advantage if the line is tested with a line testing device.

Operating voltage 12... 33 VDC

Quiescent current 200 NA

Terminal block 0.28... 1.5 mm2

A5Q00009392

Accessories

DMZ1197-AD Protection seal

Protects the manual call point in wet applications.The seal improves the manual call point housing's protection category.

Delivery unit 5 pieces

BPZ:5470680001

DMZ1197-AC Protective cover

Protects the manual call point from unintentional glass break. Protec-tive cover can be easily fitted directly in the housing cover.

Delivery unit 5 pieces

BPZ:5223550001

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

A5Q00006735 Locking plug M20 x 1.5 (1 hole)

For manual call point housings and surface-mounted feed lines in the manual call point housing.For applications in dry rooms.

Color red‚ zRAL 3000

Delivery unit 10 pieces

A5Q00006735

05.fm Seite 16 Mittwoch, 28. Juli 2010 8:33 08

Page 98: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation

5-17© Siemens Switzerland Ltd 2010

5

Type Order No.

A5Q00010055 Locking plug M20 x 1.5 (2 holes)

For manual call point housings and surface-mounted feed lines in the manual call point housing.For applications in dry rooms.

Color red‚ zRAL 3000

Delivery unit 10 pieces

A5Q00010055

FDM224H__ Manual call point 'Heavy Duty'

For immediate manual actuation of a fire alarm. Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push but-ton is reset and the device is ready for operation again.For indoor and outdoor application‚ equally suited for wet‚ humid and dusty areas. Only for surface-mounted feed lines in easily accessible places‚ e.g. Tunnels‚ Industry.The housing is equipped with one opening at the top and two openings at the bottom for locking plugs and for metal screwed cable glands M20.For IP64 applications the unused openings must be locked with the V-plug.The housing FDMH292-R and the switching unit FDME224 must be ordered separately.

Communication protocol FDnet/C-NET

Ext. alarm indicator 2

Operating temperature -25... +70 °C

Storage temperature -30... +75 °C

Relative humidity L95 % (no condensation)

Protection category IP44 (IP64 with protection seal and V-plug)

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard EN 54-11‚ EN 54-17

Dimensions (W x H x D) 134 x 134 x 43 mm

Data sheet 008345

Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20A5Q00010055 V-plug PA M20

Products to select from

FDME224 See Page 5-18

FDMH292-R See Page 5-17

FDM224H__

FDMH292-R Housing red 'Heavy Duty'

Housing with glass‚ 3 pieces locking plugs M20 (2 holes)‚ hexagonal wrench 2.5 mm and label 'Feuerwehr/Brandmelder'.

Color red‚ zRAL 3000

A5Q00005525

05.fm Seite 17 Mittwoch, 28. Juli 2010 8:33 08

Page 99: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Direct Operation

5-18 © Siemens Switzerland Ltd 2010

Type Order No.

FDME224 Switching unit with direct alarm actuation

Switching unit with integrated line separator and built-in alarm indica-tor (LED). Two-colored LED for alarm and test.The switching unit can be placed immediately after connecting the feed line‚ which is an advantage if the line is tested with a line testing device.

Operating voltage 12... 33 VDC

Quiescent current 200 NA

Terminal block 0.28... 1.5 mm2

A5Q00009392

Accessories

DMZ1197-AD Protection seal

Protects the manual call point in wet applications.The seal improves the manual call point housing's protection category.

Delivery unit 5 pieces

BPZ:5470680001

DMZ1197-AC Protective cover

Protects the manual call point from unintentional glass break. Protec-tive cover can be easily fitted directly in the housing cover.

Delivery unit 5 pieces

BPZ:5223550001

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

A5Q00008131 V-plug PA M20 x 1.5

For outdoor applications for locking the unused openings in the hous-ing FDMH292-R to improve the higher protection category.

Color black

A5Q00008131

05.fm Seite 18 Mittwoch, 28. Juli 2010 8:33 08

Page 100: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Indirect Operation

5-19© Siemens Switzerland Ltd 2010

5

Type Order No.

FDM223 Manual call point complete

For immediate manual actuation of a fire alarm. For indoor and outdoor application‚ equally suited for wet‚ humid and dusty areas. For surface- and recess-mounted feed lines in easily accessible places.Indirect alarm actuation by smashing in the glass plate and pressing the push button. To replace the glass plate‚ open the housing door with the key. The push button must be reset before closing the door again.The manual call point consists of a housing red with glass‚ key‚ switch-ing unit‚ 2 labels (standard with house and Feuerwehr/Brandmelder) and 2 locking plugs (2 holes).

Communication protocol FDnet/C-NET

Operating voltage 12... 33 VDC

Quiescent current 200 NA

Ext. alarm indicator 2

Operating temperature -25... +70 °C

Storage temperature -30... +75 °C

Relative humidity L95 % (no condensation)

Protection category IP44 (IP64 with protection seal)

Color red‚ zRAL 3000

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard EN 54-11‚ EN 54-17

Dimensions (W x H x D) 134 x 134 x 43 mm

Data sheet 007001

Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20

A5Q00008098

05.fm Seite 19 Mittwoch, 28. Juli 2010 8:33 08

Page 101: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Indirect Operation

5-20 © Siemens Switzerland Ltd 2010

Type Order No.

FDM223__ Manual call point

For immediate manual actuation of an alarm. For indoor and outdoor application‚ equally suited for wet‚ humid and dusty areas. For surface- and recess-mounted feed lines in easily accessible places.Indirect alarm actuation by pushing in the glass plate and pressing the push button. To replace the glass plate‚ open the housing door with the key. The push button must be reset before closing the door again.The housing FDMH293-x and the switching unit FDME223 must be ordered separately.

Communication protocol FDnet/C-NET

Ext. alarm indicator 2

Operating temperature -25... +70 °C

Storage temperature -30... +75 °C

Relative humidity L95 % (no condensation)

Protection category IP44 (IP64 with protection seal)

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard EN 54-11‚ EN 54-17

Dimensions (W x H x D) 134 x 134 x 43 mm

Data sheet 007001

Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20A5Q00006735 Locking plug M20(1 hole)A5Q00010055 Locking plug M20(2 holes)

Products to select from

FDMH293-B See Page 5-21

FDMH293-G See Page 5-21

FDMH293-R See Page 5-20

FDMH293-Y See Page 5-21

FDMH293-O See Page 5-21

FDME223 See Page 5-22

FDM223__

FDMH293-R Housing red‚ with glass and key

Manual call point housing for the switching unit FDME223‚ FDME224.

Color red‚ zRAL 3000

A5Q00004023

05.fm Seite 20 Mittwoch, 28. Juli 2010 8:33 08

Page 102: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Indirect Operation

5-21© Siemens Switzerland Ltd 2010

5

Type Order No.

FDMH293-Y Housing yellow‚ with glass and key

Manual call point housing for the switching unit FDME223‚ FDME224.

Color yellow‚ zRAL 1023

A5Q00004908

FDMH293-G Housing green‚ with glass and key

Manual call point housing for the switching unit FDME223‚ FDME224.

Color green‚ zRAL 6024

A5Q00004911

FDMH293-B Housing blue‚ with glass and key

Manual call point housing for the switching unit FDME223‚ FDME224.

Color blue‚ zRAL 5005

A5Q00004909

FDMH293-O Housing orange‚ with glass and key

Manual call point housing for the switching unit FDME223‚ FDME224.

Color orange‚ zRAL 2010

S54311-F2-A1

05.fm Seite 21 Mittwoch, 28. Juli 2010 8:33 08

Page 103: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Indirect Operation

5-22 © Siemens Switzerland Ltd 2010

Type Order No.

FDME223 Switching unit with indirect alarm actuation

Switching unit with integrated line separator and built-in alarm indica-tor (LED). Two-colored LED for alarm and test.The switching unit can be placed immediately after connecting the feed line‚ which is an advantage if the line is tested with a line testing device.

Operating voltage 12... 33 VDC

Quiescent current 200 NA

Terminal block 0.28... 1.5 mm2

A5Q00003087

Accessories

DMZ1197-AD Protection seal

Protects the manual call point in wet applications.The seal improves the manual call point housing's protection category.

Delivery unit 5 pieces

BPZ:5470680001

DMZ1197-AC Protective cover

Protects the manual call point from unintentional glass break. Protec-tive cover can be easily fitted directly in the housing cover.

Delivery unit 5 pieces

BPZ:5223550001

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

A5Q00006735 Locking plug M20 x 1.5 (1 hole)

For manual call point housings and surface-mounted feed lines in the manual call point housing.For applications in dry rooms.

Color red‚ zRAL 3000

Delivery unit 10 pieces

A5Q00006735

05.fm Seite 22 Mittwoch, 28. Juli 2010 8:33 08

Page 104: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Indirect Operation

5-23© Siemens Switzerland Ltd 2010

5

Type Order No.

A5Q00010055 Locking plug M20 x 1.5 (2 holes)

For manual call point housings and surface-mounted feed lines in the manual call point housing.For applications in dry rooms.

Color red‚ zRAL 3000

Delivery unit 10 pieces

A5Q00010055

FDM223H__ Manual call point 'Heavy Duty'

For immediate manual actuation of a fire alarm. Indirect alarm actua-tion by pushing in the glass plate and pressing the push button. To replace the glass plate‚ open the housing door with the key. The push button must be reset before closing the door again.For indoor and outdoor application‚ equally suited for wet‚ humid and dusty areas. Only for surface-mounted feed lines in easily accessible places‚ e.g. tunnels‚ industry.The housing is equipped with one opening at the top and two openings at the bottom for locking plugs and for metal screwed cable glands M20.For IP64 applications the unused openings must be locked with the V-plug.The housing FDMH292-R and the switching unit FDME223 must be ordered separately.

Communication protocol FDnet/C-NET

Operating temperature -25... +70 °C

Ext. alarm indicator 2

Storage temperature -30... +75 °C

Relative humidity L95 % (no condensation)

Protection category IP44 (IP64 with protection seal)

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard EN 54-11‚ EN 54-17

Dimensions (W x H x D) 134 x 134 x 43 mm

Data sheet 008345

Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20A5Q00010055 V-plug PA M20

Products to select from

FDMH292-R See Page 5-23

FDME223 See Page 5-24

FDM223H__

FDMH292-R Housing red 'Heavy Duty'

Housing with glass‚ 3 pieces locking plugs M20 (2 holes)‚ hexagonal wrench 2.5 mm and label 'Feuerwehr/Brandmelder'.

Color red‚ zRAL 3000

A5Q00005525

05.fm Seite 23 Mittwoch, 28. Juli 2010 8:33 08

Page 105: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable Manual Call PointsMCP with Indirect Operation

5-24 © Siemens Switzerland Ltd 2010

Type Order No.

FDME223 Switching unit with indirect alarm actuation

Switching unit with integrated line separator and built-in alarm indica-tor (LED). Two-colored LED for alarm and test.The switching unit can be placed immediately after connecting the feed line‚ which is an advantage if the line is tested with a line testing device.

Operating voltage 12... 33 VDC

Quiescent current 200 NA

Terminal block 0.28... 1.5 mm2

A5Q00003087

Accessories

DMZ1197-AD Protection seal

Protects the manual call point in wet applications.The seal improves the manual call point housing's protection category.

Delivery unit 5 pieces

BPZ:5470680001

DMZ1197-AC Protective cover

Protects the manual call point from unintentional glass break. Protec-tive cover can be easily fitted directly in the housing cover.

Delivery unit 5 pieces

BPZ:5223550001

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

A5Q00008131 V-plug PA M20 x 1.5

For outdoor applications for locking the unused openings in the hous-ing FDMH292-R to improve the higher protection category.

Color black

A5Q00008131

05.fm Seite 24 Mittwoch, 28. Juli 2010 8:33 08

Page 106: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAlarm EquipmentAlarm Sounders‚ Alarm Sounder Beacon

5-25© Siemens Switzerland Ltd 2010

5

Type Order No.

FDS221-R Alarm sounder red

Loud alarming in case of fire alarm‚ clearly recognizable as danger sig-nal. To be mounted on the wall or on the ceiling along escape routes‚ corridors‚ staircases. Only applicable with addressable detector base. Power is supplied via FDnet/C-NET‚ no auxiliary power supply required. Monitoring of device status.For recess supply line. For surface supply line up to cable 6 mm in diam-eter with base FDB221‚ otherwise use the base attachment or the base attachment wet.The base must be ordered separately.

Communication protocol FDnet/C-NET

Operating voltage 12... 33 VDC

Operating current 3.5 mA (sound activated)

Quiescent current 250 NA

Terminals according to detector base

Number of sounds 11

Sound intensity 80... 99 dBA

Ext. alarm indicator 2

Operating temperature -25... +70 °C

Storage temperature -30... +75 °C

Relative humidity L95 %

Color red‚ zRAL 3000

Protection category With base FDB221 and base attach-ment FDB291 mounting on the wall with cable feed from bottom -> IP43‚ otherwise IP40. With base FDB221 and sealing ele-ment FDBZ295 -> IP44.With base attachment humid FDB293 -> IP54.

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard EN 54-3‚ EN 54-17

Dimensions (Ø x D) 100 x 43 mm

Data sheet Sinteso -> 007026Cerberus PRO -> A6V10203095

Accessories FDBZ293 Detector locking device

A5Q00004117

05.fm Seite 25 Mittwoch, 28. Juli 2010 8:33 08

Page 107: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAlarm EquipmentAlarm Sounders‚ Alarm Sounder Beacon

5-26 © Siemens Switzerland Ltd 2010

Type Order No.

FDS221-W Alarm sounder white

Loud alarming in case of fire alarm‚ clearly recognizable as danger sig-nal. To be mounted on the wall or on the ceiling along escape routes‚ corridors‚ staircases. Only applicable with addressable detector base. Power is supplied via FDnet/C-NET‚ no auxiliary power supply required. Monitoring of device status.For recess supply line. For surface supply line up to cable 6 mm in diam-eter with base FDB221‚ otherwise use the base attachment or the base attachment wet.The base must be ordered separately.

Communication protocol FDnet/C-NET

Operating voltage 12... 33 VDC

Operating current 3.5 mA (sound activated)

Quiescent current 250 NA

Terminals according to detector base

Number of sounds 11

Sound intensity 80... 99 dBA

Ext. alarm indicator 2

Operating temperature -25... +70 °C

Storage temperature -30... +75 °C

Relative humidity L95 %

Color white‚ zRAL 9010

Protection category With base FDB221 and base attach-ment FDB291 mounting on the wall with cable feed from bottom -> IP43‚ otherwise IP40. With base FDB221 and sealing ele-ment FDBZ295 -> IP44.With base attachment humid FDB293 -> IP54.

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard EN 54-3‚ EN 54-17

Dimensions (Ø x D) 100 x 43 mm

Data sheet Sinteso -> 007026Cerberus PRO -> A6V10203095

Accessories FDBZ293 Detector locking device

A5Q00006711

05.fm Seite 26 Mittwoch, 28. Juli 2010 8:33 08

Page 108: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAlarm EquipmentAlarm Sounders‚ Alarm Sounder Beacon

5-27© Siemens Switzerland Ltd 2010

5

Type Order No.

FDS229-R Alarm sounder beacon‚ red

Acoustic and optical alarming in case of fire alarm‚ clearly recognizable as danger signal. To be mounted on the wall or on the ceiling along escape routes‚ corridors‚ staircases. Only applicable with addressable detector base. Power is supplied via FDnet/C-NET‚ no auxiliary power supply required. Monitoring of device status.For recess supply line. For surface supply line up to cable 6 mm in diam-eter with base FDB221‚ otherwise use the base attachment or the base attachment wet.The base must be ordered separately.

Communication protocol FDnet/C-NET

Operating voltage 12... 33 VDC

Quiescent current 250 NA

Operating current 3.5 mA (sound activated)3.5 mA (beacon activated)7.0 mA (sound and beacon activat-ed)

Terminals according to detector base

Number of sounds 11

Number of flashing pattern 1 (intermittent)

Sound intensity 80... 99 dBA

Light intensity 1.27... 3.2 cd

Ext. alarm indicator 2

Operating temperature -25... +55 °C

Storage temperature -30... +75 °C

Relative humidity L95 %

Color transparent red

Protection category With base FDB221 and base attach-ment FDB291 mounting on the wall with cable feed from bottom -> IP43‚ otherwise IP42. With base FDB221 and sealing ele-ment FDBZ295 -> IP44.With base attachment humid FDB293 -> IP54.

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard EN 54-3‚ EN 54-17

Dimensions (Ø x D) 100 x 43 mm

Data sheet Sinteso -> A6V10067776Cerberus PRO -> A6V10229545

Accessories FDBZ293 Detector locking device

A5Q00023093

05.fm Seite 27 Mittwoch, 28. Juli 2010 8:33 08

Page 109: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAlarm EquipmentAlarm Sounders‚ Alarm Sounder Beacon

5-28 © Siemens Switzerland Ltd 2010

Type Order No.

FDS229-A Alarm sounder beacon‚ orange

Acoustic and optical alarming in case of fire alarm‚ clearly recognizable as danger signal. To be mounted on the wall or on the ceiling along escape routes‚ corridors‚ staircases. Only applicable with addressable detector base. Power is supplied via FDnet/C-NET‚ no auxiliary power supply required. Monitoring of device status.For recess supply line. For surface supply line up to cable 6 mm in diam-eter with base FDB221‚ otherwise use the base attachment or the base attachment wet.The base must be ordered separately.

Communication protocol FDnet/C-NET

Operating voltage 12... 33 VDC

Quiescent current 250 NA

Operating current 3.5 mA (sound activated)3.5 mA (beacon activated)7.0 mA (sound and beacon activat-ed)

Terminals according to detector base

Number of sounds 11

Number of flashing pattern 1 (intermittent)

Sound intensity 80... 99 dBA

Light intensity 1.1… 2.8 cd

Ext. alarm indicator 2

Operating temperature -25... +65 °C

Storage temperature -30... +75 °C

Relative humidity L95 %

Color transparent orange

Protection category With base FDB221 and base attach-ment FDB291 mounting on the wall with cable feed from bottom -> IP43‚ otherwise IP42. With base FDB221 and sealing ele-ment FDBZ295 -> IP44.With base attachment humid FDB293 -> IP54.

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard EN 54-3‚ EN 54-17

Dimensions (Ø x D) 100 x 43 mm

Data sheet Sinteso -> A6V10067776Cerberus PRO -> A6V10229545

Accessories FDBZ293 Detector locking device

A5Q00023092

Accessories

FDBZ293 Detector locking device

Threaded pin M3 x 6 to protect detector against theft.Scope of delivery2 hexagonal wrenches100 threaded pins

A5Q00005035

05.fm Seite 28 Mittwoch, 28. Juli 2010 8:33 08

Page 110: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAlarm EquipmentBases for Alarm Sounders‚ Alarm Sounder Beacon

5-29© Siemens Switzerland Ltd 2010

5

Type Order No.

FDB221 Detector base addressable

Base made from impact-proof and scratch-resistant synthetic material. Large opening in the detector base permits the reuse of existing bore-holes from older systems. Screwless connection terminals 'orange'. Space for auxiliary terminals as micro terminals 0.5 mm2 or connection terminals 2.5 mm2.For equipment with addressable signal processing.For recess supply wiring. For surface supply wiring‚ cable diameter up to 6 mm.

Cable capacity 0.2... 1.5 mm2

Dimensions (Ø x H) 100 x 22 mm

Color white‚ zRAL 9010

Data sheet Sinteso -> 007775Cerberus PRO -> A6V10203095‚ A6V10229545

Accessories FDBZ291 Designation plateDBZ1190-AA Micro terminal 0.5 mm2

DBZ1190-AB Connection terminal 2.5 mm2

FDB291 Base attachmentFDB293 Base attachment wet

A5Q00001664

FDB222 Detector base flat‚ addressable

Base made from impact-proof and scratch-resistant synthetic material. Large opening in the detector base permits the reuse of existing bore-holes from older systems. Screwless connection terminals 'orange'. Space for auxiliary terminals as micro terminals 0.5 mm2 or connection terminals 2.5 mm2.For equipment with addressable signal processing.For recess supply wiring.

Cable capacity 0.2... 1.5 mm2

Dimensions (Ø x H) 100 x 22 mm

Color white‚ zRAL 9010

Data sheet Sinteso -> 007775Cerberus PRO -> A6V10203095‚ A6V10229545

Accessories FDBZ291 Designation plateDBZ1190-AA Micro terminal 0.5 mm2

DBZ1190-AB Connection terminal 2.5 mm2

S54319-F1-A1

Accessories

FDBZ295 Sealing element

Use only with base FDB221‚ FDB221-AA for higher protection category. Not usable together with the designation plate FDBZ291.

Dimensions (Ø x H) 107 x 30 mm

Color white‚ zRAL 9010

S54319-F10-A1

05.fm Seite 29 Mittwoch, 28. Juli 2010 8:33 08

Page 111: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAlarm EquipmentBases for Alarm Sounders‚ Alarm Sounder Beacon

5-30 © Siemens Switzerland Ltd 2010

Type Order No.

FDBZ291 Designation plate

To identify the location address for detector bases.

Dimensions (W x H) 62 x 35 mm

Color transparent

Delivery unit 10 pieces

A5Q00002621

DBZ1190-AA Micro terminal 0.5 mm2‚ 4-pole

As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.

Cable capacity 0.28... 0.5 mm2

Dimensions (W x H x D) 10 x 7 x 10 mm

Delivery unit 50 pieces

BPZ:4677080001

DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole

As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.

Cable capacity 1... 2.5 mm2

Dimensions (W x H x D) 13.5 x 9.5 x 19.5 mm

Delivery unit 50 pieces

BPZ:4942340001

FDB291 Base attachment

For the supply of surface-mounted lines MI6 mm. The detector base FDB2xx is fixed with a spring-loaded catch.Mounting slots 46... 90 mm.

Dimensions (Ø x H) 120 x 25 mm

Color white‚ zRAL 9010

Accessories FDBZ291 Designation plate

A5Q00001603

FDB293 Base attachment humid with seal

For mounting in humid or wet environments‚ and when the detector-heating unit is used. 6 breakout plugs for screwed cable gland M20.For IP54 applications.

Dimensions (W x H x D) 135 x 135 x 49 mm

Color white‚ zRAL 9010

Accessories DBZ1194 Protective cageFDBZ294 EMC protective cage (only for Sinteso point detectors)A5Q00004478 Screwed cable gland M20DBZ1193A Detector designation plate

A5Q00003945

05.fm Seite 30 Mittwoch, 28. Juli 2010 8:33 08

Page 112: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAlarm EquipmentBases for Alarm Sounders‚ Alarm Sounder Beacon

5-31© Siemens Switzerland Ltd 2010

5

Type Order No.

DBZ1194 Protective cage

To protect the detector from damage. Can only be used together with the base attachment humid.

Dimensions (Ø x H) 160 x 126 mm

BPZ:4677110001

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

DBZ1193A Detector designation plate

To indicate a location address. To number detectors according to instal-lation drawings. The font may be up to 10 mm in an area of 60 x 20 mm. The detector designation plate is connected directly to the base or base attachment.

Dimensions (W x H) 62 x 52 mm

Color transparent

Delivery unit 10 pieces

BPZ:4864330001

05.fm Seite 31 Mittwoch, 28. Juli 2010 8:33 08

Page 113: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAlarm EquipmentSounder Base for Automatic Detectors

5-32 © Siemens Switzerland Ltd 2010

Type Order No.

DBS720 Sounder base

Compatible with all point detectors of the series Cerberus PRO.The sounder base DBS720 and the detector compose a single unit‚ which already has a base and is mounted on ceilings‚ e.g. in hotel rooms‚ hospitals or nursing homes.The sounder base serves for acoustic alarming in the addressed FS720 fire detection system. The sounder base can be allocated freely from the fire control panel to activate as required. It is not dependent upon an alarm signal from its associated detector.Synchronized with all other alarm sounder and sounder beacon devices in the same detector line (C-NET).No auxiliary power supply required; power is supplied via C-NET.For recess supply wiring. For surface supply wiring‚ remove the corre-sponding breakouts for cable diameter up to max. Ø8 mm.

Communication protocol C-NET

Operating voltage 12... 33 VDC

Quiescent current 150 μA

Alarm current 1.2 mA

Cable capacity 0.2... 1.6 mm2

Number of sounds 11

Sound intensity 80... 88 dBA

Ext. alarm indicator 2

Operating temperature -25... +70 °C

Storage temperature -30... +70 °C

Relative humidity L95 %

Color white‚ zRAL 9010

Protection category IP41IP42 with detector base seal RS720

System compatibility C-NET -> FS720

Standard EN 54-3

Dimensions (W x H x D) 175 x 117 x 29 mm

Data sheet A6V10203095

Accessories FDBZ291 Designation plateRS720 Detector base sealDBZ1190-AA Micro terminal 0.5 mm2

DBZ1190-AB Connection terminal 2.5 mm2

S54319-F5-A1

Accessories

FDBZ291 Designation plate

To identify the location address for detector bases.

Dimensions (W x H) 62 x 35 mm

Color transparent

Delivery unit 10 pieces

A5Q00002621

RS720 Detector base seal

Seal for higher protection category.Compatible with base DB721 and sounder base DBS720.Not usable together with the designation plate FDBZ291.

Dimensions (Ø x H) 119 x 6.5 mm

Color transparent

Delivery unit 10 pieces

S54319-F8-A1

05.fm Seite 32 Mittwoch, 28. Juli 2010 8:33 08

Page 114: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAlarm EquipmentSounder Base for Automatic Detectors

5-33© Siemens Switzerland Ltd 2010

5

Type Order No.

DBZ1190-AA Micro terminal 0.5 mm2‚ 4-pole

As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.

Cable capacity 0.28... 0.5 mm2

Dimensions (W x H x D) 10 x 7 x 10 mm

Delivery unit 50 pieces

BPZ:4677080001

DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole

As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.

Cable capacity 1... 2.5 mm2

Dimensions (W x H x D) 13.5 x 9.5 x 19.5 mm

Delivery unit 50 pieces

BPZ:4942340001

05.fm Seite 33 Mittwoch, 28. Juli 2010 8:33 08

Page 115: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

No. Tonality

Frequency pattern Sweep

from – to

Pulse pattern

Adjustable FDS221 and FDS229 soundintensity level (typ. values in [dBA/1m]*)

Norm

at 12 V at 32 V

1 Continuous 970 Hz 988881

1019282

“evacuate”BS 5839 Part 1 1988

2 Intermittent 950 Hz 968779

1009181

“alert”BS 5839 Part 1 1988

3 Sweep-down 1200 Hz – 500 Hz 968779

1009180

DIN-ToneDIN33404 Part 3

4 Slow-whoopSweep-up, linear

500 Hz – 1200 Hz 978881

1019282

NEN2575(Netherlands)

5 Pulse tone 500 Hz 948575

978875

Swedish StandardSS 03 17 11, No. 1“Imminent Danger”

6 Intermittent 500 Hz 938475

968775

Swedish StandardSS 03 17 11, No. 6

“Local Warning”

7 Continuous 500 Hz 948576

978876

Swedish StandardSS 03 17 11, No. 4

“All clear”

8 Alternating 560 Hz440 Hz

948575

988976

“French fi re sound” NF S 32-001-1975

9 Intermittent 420 Hz 948576

988977

Australia “Alert”AS 2220 -1978

10 Slow-whoopSweep-up, linear

500 Hz – 1200 Hz 968981

1009382

Australia “Action”AS 2220 -1978

11 Intermittent 970 Hz 998982

1029283

ISO 8201US Temporal Tone LF

* Sound intensity ±2 dBASound intensity depending on the angle, see 'Operating instruction 008109'

Alarm sounder tones

1s

1s

0.6 s

0.5 s

1s

0.65 s

0.5 s 1.5 s

0.15 s

0.15 s

0.1s

0.1s

0.4 s

0.6 s

3.5 s

0.5 s

3.75 s

0.25 s

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 23 28.05.10 16:57

Page 116: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable ModulesLine Separator

5-35© Siemens Switzerland Ltd 2010

5

Type Order No.

FDCL221 Line separator

To avoid the breakdown of several stub lines in case of a short circuit‚ line separators may be inserted. The line separator is used where sever-al stub lines are connected to the FDnet/C-NET at one point ‚ if no other device is given between the T-tap. For retrofitting of existing‚ collective systems to addressable Sinteso/Cerberus PRO fire detection systems.The separator is an electronic switch‚ integrated into the FDnet/C-NET. It separates the negative conductor in case of a short circuit‚ so that the short circuit-free side can continue to operate. The separator has 2x2 connectors for the detector line. Yellow LED for the status indication signals the short circuit separation.

Communication protocol FDnet/C-NET

Operating voltage 12... 33 VDC

Quiescent current 250 NA

Operating temperature -25... +70 °C

Storage temperature -30... +80 °C

Relative humidity L95 %

Color transparent

Protection category IP44

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard EN54-17

Dimensions (W x H x D) 44 x 47.5 x 10 mm

Data sheet 007065

Accessories TS35_122 U-railTS35_288 U-rail

A5Q00004011

05.fm Seite 35 Mittwoch, 28. Juli 2010 8:33 08

Page 117: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable ModulesLine Separator

5-36 © Siemens Switzerland Ltd 2010

Type Order No.

FDCL221-M Multi-line separator module

To avoid the breakdown of several stub lines in case of a short circuit‚ line separators may be inserted. The line separator is used where sever-al stub lines are connected to the FDnet/C-NET at one point. The mod-ule can also be connected to 2 separate loops. For retrofitting of exist-ing‚ collective systems to addressable Sinteso/Cerberus PRO fire detec-tion systems.The module has total 9 separators. Each separator is an electronic switch‚ integrated into the FDnet/C-NET. It separates the negative con-ductor in case of a short circuit‚ so that the short circuit-free side can continue to operate. The separator has connections for the detector lines‚ connections for the stub lines (T-taps)‚ jumpers for programming of operation mode (1-loop or 2-loop mode)‚ yellow LED for the status indication signals the short circuit separation.

Communication protocol FDnet/C-NET

Operating voltage 12... 33 VDC

Quiescent current 2.25 mA (9 x 250 NA) or2 x 1 mA (4 x 250 NA)

Operating temperature -25... +70 °C

Storage temperature -30... +75 °C

Relative humidity L95 % rel.

Color housing white zRAL9010cover transparent‚ mattaux. housing FDCH221 white zRAL9010

Protection category IP30with ext. housing FDCH221 -> IP65

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard EN 54-17

Dimensions (W x H x D)

Data sheet A6V10230308

Accessories TS35_122 U-railTS35_288 U-rail

S54312-F6-A1

Accessories

TS35_122 U-rail TS35/7.5/122

Universal mounting rail (U-rail) enables mounting of various equip-ment.

Dimensions (W x H) 35 x 122 mm

BPZ:5644780001

TS35_288 U-rail TS35/7.5/288

Universal mounting rail (U-rail) enables mounting of various equip-ment.

Dimensions (W x H) 35 x 288 mm

BPZ:5644230001

05.fm Seite 36 Mittwoch, 28. Juli 2010 8:33 08

Page 118: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable ModulesInput Modules

5-37© Siemens Switzerland Ltd 2010

5

Type Order No.

FDCI221 Input module

For the connection of 1 circuit of potential-free make-or-break contact for the indication of technical states (e.g. door or ventilation control) or for alarm actuation (e.g. sprinkler alarm).1 input for potential-free contact. Input line is monitored for open line and short circuit (termination resistors). The input can be configured via the fire control panel for status or alarm messages.Status indication by LED. Power supply via FDnet/C-NET.Input module incl. 2 resistors and 2 mounting feet for TS35 U-rail.

Communication protocol FDnet/C-NET

Operating voltage 12... 33 VDC

Quiescent current max. 0.3 mA

Cable capacity 0.2... 1.5 mm2 (2.5 mm2)

Operating temperature -25... +70 °C

Storage temperature -30... +75 °C

Relative humidity L95 %

Color white‚ zRAL 9010/transparent matt

Protection category IP30IP65 with aux. housing FDCH221

System compatibility FDnet -> FS20C-NET -> FS720

Standard EN 54-17‚ EN 54-18

Dimensions (W x H x D) 95 x 71 x 23 mm

Data sheet A6V10202196

Accessories TS35_122 U-railTS35_288 U-railFDCH221 Housing IP65

S54312-F1-A1

FDCI222 Input module

For the connection of 4 independent circuits of potential-free‚ make-or-break contacts for the indication of technical states (e.g. door or venti-lation control) or for alarm actuation (e.g. sprinkler alarm).4 inputs for potential-free contacts. Input lines are monitored for open line and short circuit (termination resistors). Inputs can be independ-ently configured via the fire control panel for status or alarm messages.Status indication by LED. Power supply via FDnet/C-NET.Input module incl. 8 resistors and 2 mounting feet for TS35 U-rail.

Communication protocol FDnet/C-NET

Operating voltage 12... 33 VDC

Quiescent current 0.25... 0.35 mA

Cable capacity 0.2... 1.5 mm2 (2.5 mm2)

Operating temperature -25... +60 °C

Storage temperature -30... +65 °C

Relative humidity L95 %

Color white‚ zRAL 9010/transparent matt

Protection category IP30IP65 with aux. housing FDCH221

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard CEA GEI 1-84‚ EN 54-17‚ EN 54-18

Dimensions (W x H x D) 130 x 90 x 20 mm

Data sheet 007024

Accessories TS35_122 U-railTS35_288 U-railFDCH221 Housing IP65

A5Q00001984

05.fm Seite 37 Mittwoch, 28. Juli 2010 8:33 08

Page 119: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable ModulesInput/Output Modules

5-38 © Siemens Switzerland Ltd 2010

Type Order No.

FDCIO221 Input/output module

For the connection of 1 circuit of potential-free, make-or-break contact for the indication of technical states (e.g. door or ventilation control) or for alarm actuation (e.g. sprinkler alarm). For the decentralized control of fire doors‚ ventilation and air conditioning.1 input for potential-free contact. The input line is monitored for open line and short circuit (termination resistors). The input can be config-ured via the fire control panel for status or alarm message. 1 output configurable as a potential-free relay contact (30 VAC/VDC‚ 2 A) or as a monitored circuit (30 VDC‚ 2 A).Status indication by LED. Power supply via FDnet/C-NET in potential-free mode. Monitored mode requires additional 24 VDC power supply.Input/output module incl. 3 resistors and 2 mounting feet for TS35 U-rail.

Communication protocol FDnet/C-NET

Operating voltage 12... 33 VDC

Quiescent current max. 0.4 mA

Relay output (volt-free) 30 VAC‚ 2 A‚ max 60 VA30 VDC‚ 2 A‚ max 60 W

Cable capacity 0.2... 2.5 mm2

Operating temperature -25... +70 °C

Storage temperature -30... +75 °C

Relative humidity L95 %

Color white‚ zRAL 9010/transparent matt

Protection category IP30IP65 with aux. housing FDCH221

System compatibility FDnet -> FS20C-NET -> FS720

Standard EN 54-17‚ EN 54-18

Dimensions (W x H x D) 95 x 71 x 23 mm

Data sheet A6V10202196

Accessories TS35_122 U-railTS35_288 U-railFDCH221 Housing IP65

S54312-F2-A1

05.fm Seite 38 Mittwoch, 28. Juli 2010 8:33 08

Page 120: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable ModulesInput/Output Modules

5-39© Siemens Switzerland Ltd 2010

5

Type Order No.

FDCIO222 Input/output module

For the connection of 4 independent‚ potential-free‚ make-or-break contacts for the indication of technical states (e.g. door or ventilation control) or for alarm actuation (e.g. sprinkler alarm).4 inputs for potential-free contacts. Input lines are monitored for open line and short circuit (termination resistors). Inputs can be independ-ently configured via the fire control panel for status or alarm messages. 4 outputs with 4 potential-free relay contacts (230 VAC / 4 A) for fire control installations.Status indication by LED. Power supply via FDnet/C-NET.Input/output module incl. 8 resistors and 2 mounting feet for TS35 U-rail.

Communication protocol FDnet/C-NET

Operating voltage 12... 33 VDC

Quiescent current 0.6... 0.75 mA

Relay output (volt-free) 250 VAC‚ 4 A‚ max. 1000 VA30 VDC‚ 4 A‚ max. 120 W

Cable capacity 0.2... 1.5 mm2 (2.5 mm2)

Operating temperature -25... +60 °C

Storage temperature -30... +65 °C

Relative humidity L95 %

Color white‚ zRAL 9010/transparent matt

Protection category IP30IP65 with aux. housing FDCH221

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard CEA GEI 1-84‚ EN 54-17‚ EN 54-18

Dimensions (W x H x D) 130 x 90 x 20 mm

Data sheet 007024

Accessories TS35_122 U-railTS35_288 U-railFDCH221 Housing IP65

A5Q00002369

05.fm Seite 39 Mittwoch, 28. Juli 2010 8:33 08

Page 121: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable ModulesInput/Output Modules

5-40 © Siemens Switzerland Ltd 2010

Type Order No.

FDCIO224 Input/output module

For the VdS interface for extinguishing activating devices. 4 inputs for potential-free contacts. Input lines are monitored for open line and short circuit (termination resistors). Inputs can be independently con-figured via the fire control panel for status or alarm messages.4 outputs with 4 potential-free relay contacts (230 VAC / 4 A) for the VdS interface for extinguishing controls. Status indication by LED. Pow-er supply via FDnet/C-NET.Input/output module incl. 8 resistors and 2 mounting feet for TS35 U-rail.

Communication protocol FDnet/C-NET

Operating voltage 12... 33 VDC

Quiescent current 0.6... 0.75 mA

Relay output (volt-free) 250 VAC‚ 4 A‚ max. 1000 VA30 VDC‚ 4 A‚ max. 120 W

Cable capacity 0.2... 1.5 mm2 (2.5 mm2)

Operating temperature -25... +60 °C

Storage temperature -30... +65 °C

Relative humidity L95 %

Color white‚ zRAL 9010/transparent matt

Protection category IP30IP65 with aux. housing FDCH221

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard CEA GEI I-084‚ EN 54-17‚ EN 54-18

Dimensions (W x H x D) 130 x 90 x 20 mm

Data sheet 007024

Accessories TS35_122 U-railTS35_288 U-railFDCH221 Housing IP65

A5Q00018689

05.fm Seite 40 Mittwoch, 28. Juli 2010 8:33 08

Page 122: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable ModulesInput/Output Modules

5-41© Siemens Switzerland Ltd 2010

5

Type Order No.

FDCIO223 Input/output module 'Transponder'

For connection of collective fire detectors (GMT/conventional line‚ GMT/conventional line with shunt Zener diode barrier (SB3) for explo-sion-hazard areas). For monitored controls of e.g. smoke dampers‚ alarm devices‚ door magnets and extinguishing activation devices (adhere to country-specific instructions). Monitored signal input for status and alarm messages or for acknowledging technical status.The 2 input/outputs can be parameterized autonomously in each case as detector line collective‚ contact input‚ control output‚ control output and input as acknowledgement with selectable monitoring time frame. Status indication by LED.Transponder incl. 2 Transzorb diode 20 V‚ 8 resistors and 2 mounting feet for TS35 U-rail.

Power supply External input voltage 18... 32 VDC

Communication protocol FDnet/C-NET

Operating voltage FDnet/C-NET 12... 33 VDC

Detector line collective GMT Siemens/Cerberus‚ Synova conventional/SynoLINE300‚ collective/SynoLINE600 or similar

Control output 24 VDC ± 5 % / 2 A

EOL resistor 3.3 kT/680 T‚ 2.7 kT/560 T‚ 3.3 kT

Cable capacity 0.2... 1.5 mm2 (2.5 mm2)

Operating temperature -25... +60 °C

Storage temperature -30... +65 °C

Relative humidity L95 %

Color white‚ zRAL 9010/transparent matt

Protection category IP30IP65 with aux. housing FDCH221

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard CEA GEI I-084‚ EN 54-17‚ EN 54-18

Dimensions (W x H x D) 132 x 90 x 24 mm

Data sheet 009168

Accessories TS35_122 U-railTS35_288 U-railFDCH221 Housing IP65

S24218-B102-A1

05.fm Seite 41 Mittwoch, 28. Juli 2010 8:33 08

Page 123: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsAddressable ModulesAccessories for Input-‚ Input/Output Modules

5-42 © Siemens Switzerland Ltd 2010

Type Order No.

TS35_122 U-rail TS35/7.5/122

Universal mounting rail (U-rail) enables mounting of various equip-ment.

Dimensions (W x H) 35 x 122 mm

BPZ:5644780001

TS35_288 U-rail TS35/7.5/288

Universal mounting rail (U-rail) enables mounting of various equip-ment.

Dimensions (W x H) 35 x 288 mm

BPZ:5644230001

FDCH221 Housing for input/output modules

Housing with seal for the mounting of the input/output modules for wet applications.The required screwed cable glands and back nuts M20 must be ordered separately.

Dimensions (W x H x D) 207 x 119 x 48 mm

Color white‚ zRAL 9010 / transparent matt

Protection category IP65

Accessories A5Q00004478 Screwed cable gland M20A5Q00004479 Back nut M20

S54312-F3-A1

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

A5Q00004479 Back nut M20

Back nut to screwed cable gland M20 x 1.5.

Delivery unit 10 pieces

A5Q00004479

DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole

As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.

Cable capacity 1... 2.5 mm2

Delivery unit 50 pieces

BPZ:4942340001

05.fm Seite 42 Mittwoch, 28. Juli 2010 8:33 08

Page 124: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsFloor Repeater Panels‚ Mimic DisplayFloor Repeater Terminals

5-43© Siemens Switzerland Ltd 2010

5

Type Order No.

FT2010-A1 Floor repeater terminal

Small floor repeater operation and display panel with large backlit dis-play and plain text readout (6 lines of 40 characters each) for use with the addressed Sinteso FS20 and Cerberus PRO FS720 fire detection sys-tem.The personnel responsible at the customer's premises have access to a clearly structured user interface for customer-specific plain texts to enable exact localization of events. Sections and zones operated and visualized using the floor repeater terminal can be configured. Display of alarms‚ pre-alarms‚ technical messages‚ faults‚ isolations possible. With the navigation keys an indicated list in the display can be scrolled through. Acknowledgement and resetting of events. Event text identi-cal with the fire control panel or fire terminal. Nordic key switch for operating access may be replaced by key switch (Kaba).Power supply via FDnet/C-NET‚ separate 24 V power supply possible.The floor repeater terminal can be operated in loops or stub lines.

Operating voltage 12... 32 VDC

Supply voltage 20... 30 VDC15… 18 VAC (external supply input)

Current consumption 5 mA @ 24 V (quiescent current‚ LCD illumination inactive)45 mA @ 24 V (max. current‚ LCD illumination active)

Communication protocol FDnet/C-NET

Cable capacity 0.8... 1.5 mm2

Color grey‚ zRAL 7035

Dimensions (W x H x D) 282 x 207 x 79 mm

Operating temperature -8... +42 °C

Storage temperature -20... +60 °C

Protection category IP30

Relative humidity L95 % (no condensation)

Standard EN 54-17‚ EN 54-18

System compatibility FDnet -> FS20C-NET -> FS720

Data sheet 009393

Accessories FHA2013-A1 Rear (FT201x flat)FTO2005-C1 Key switch (Kaba)

A5Q00014104

05.fm Seite 43 Mittwoch, 28. Juli 2010 8:33 08

Page 125: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsFloor Repeater Panels‚ Mimic DisplayFloor Repeater Terminals

5-44 © Siemens Switzerland Ltd 2010

Type Order No.

FT2010-C1 Floor repeater terminal

Small floor repeater operation and display panel with large backlit dis-play and plain text readout (6 lines of 40 characters each) for use with the addressed Sinteso FS20 and Cerberus PRO FS720 fire detection sys-tem.The personnel responsible at the customer's premises have access to a clearly structured user interface for customer-specific plain texts to enable exact localization of events. Sections and zones operated and visualized using the floor repeater terminal can be configured. Display of alarms‚ pre-alarms‚ technical messages‚ faults‚ isolations possible. With the navigation keys an indicated list in the display can be scrolled through. Acknowledgement and resetting of events. Event text identi-cal with the fire control panel or fire terminal. Kaba key switch for oper-ating access and sheet metal flat rear. Power supply via FDnet/C-NET‚ separate 24 V power supply possible.The floor repeater terminal can be operated in loops or stub lines.

Operating voltage 12... 32 VDC

Supply voltage 20... 30 VDC15… 18 VAC (external supply input)

Current consumption 5 mA @ 24 V (quiescent current‚ LCD illumination inactive)45 mA @ 24 V (max. current‚ LCD illumination active)

Communication protocol FDnet/C-NET

Cable capacity 0.8... 1.5 mm2

Color grey‚ zRAL 7035

Dimensions (W x H x D) 282 x 207 x 46 mm

Operating temperature -8... +42 °C

Storage temperature -20... +60 °C

Protection category IP30

Relative humidity L95 % (no condensation)

Standard EN 54-17‚ EN 54-18

System compatibility FDnet -> FS20C-NET -> FS720

Data sheet 009393

S54400-F34-A1

05.fm Seite 44 Mittwoch, 28. Juli 2010 8:33 08

Page 126: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsFloor Repeater Panels‚ Mimic DisplayFloor Repeater Display

5-45© Siemens Switzerland Ltd 2010

5

Type Order No.

FT2011-A1 Floor repeater display

Small floor repeater display panel with large backlit display and plain text readout (6 lines of 40 characters each) for use with the addressed Sinteso FS20 and Cerberus PRO FS720 fire detection system.The personnel responsible at the customer's premises have access to a clearly structured user interface for customer-specific plain texts to enable events to be localized unambiguously. Sections and zones visu-alized using the floor repeater display can be configured. Display of alarms‚ pre-alarms‚ technical messages‚ faults‚ isolations possible. With the navigation keys an indicated list in the display can be scrolled through. The internal buzzer can be switched off in case of alarm mes-sages. Event text identical with the fire control panel or fire terminal.Power supply via FDnet/C-NET‚ separate 24 V power supply possible.The floor repeater display can be operated in loops or stub lines.

Operating voltage 12... 32 VDC

Supply voltage 20... 30 VDC15… 18 VAC (external supply input)

Current consumption 5 mA @ 24 V (Quiescent current‚ LCD illumination inactive)45 mA @ 24 V (max. current‚ LCD illumination active)

Communication protocol FDnet/C-NET

Cable capacity 0.8... 1.5 mm2

Color grey‚ zRAL 7035

Dimensions (W x H x D) 282 x 207 x 79 mm

Operating temperature -8... +42 °C

Storage temperature -20... +60 °C

Protection category IP30

Relative humidity L95 % (no condensation)

Standard EN 54-17‚ EN 54-18

System compatibility FDnet -> FS20C-NET -> FS720

Data sheet 009393

Accessories FHA2013-A1 Rear (FT201x flat)

A5Q00017706

Accessories

FHA2013-A1 Rear (FT201x flat)

Flat rear when really flat installation is required and the cable is flush-mounted. In place of the rear supplied with the floor repeater terminal or floor repeater display.

Dimensions (W x H x D) 271 x 191 x 27.5 mm

Material Zinc-plated sheet metal

A5Q00016552

FTO2005-C1 Key switch (Kaba)

Kaba key switch with mounting accessories and key (Kaba 8 #100)‚ as an option for operating access (operating unit).

A5Q00010113

05.fm Seite 45 Mittwoch, 28. Juli 2010 8:33 08

Page 127: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Network (C-NET) PeripheralsFloor Repeater Panels‚ Mimic DisplayMimic Display Driver

5-46 © Siemens Switzerland Ltd 2010

Type Order No.

FT2001-A1 Mimic display driver

The FT2001-A1 has 2x24 outputs for LED activation for mimic display panels. Connection to LED via flat cable F50F410 (50-wire‚ 24 red LEDs‚ cable length 1 m‚ must be ordered separately). 2 control outputs for 'Local buzzer' and 'LED operation'. 2 inputs for 'Switch-off buzzer' and 'Lamp test'. Integrated line separator.Power supply via FDnet/C-NET‚ separate 24 V power supply possible.The mimic display driver can be operated in loops or stub lines.MC-Link plug-in point for firmware update.

Operating voltage 12... 32 VDC

Operating current max. 45 mA

Quiescent current max. 5 mA

Operating LED output max. 2.5 mA @ 2.5 VDC

Buzzer output max. 5 mA @ 12 VDC

Key input (buzzer off‚ lamp test) 2

External supply input 14… 32 VDC‚ galvanically isolated11… 22 VAC‚ galvanically isolated

Communication protocol FDnet/C-NET

Cable capacity 0.08... 1.5 mm2

Dimensions (W x H x D) 106 x 200 x 45 mm

Operating temperature 0... +40 °C

Storage temperature -20... +60 °C

Protection category IP30 (3rd party housing)

Relative humidity L95 %

Standard EN 54-17‚ EN 54-18

System compatibility FDnet -> FS20C-NET -> FS720

Data sheet A6V10082691

Accessories F50F410 LED flat cable 50-wire

A5Q00014417

Accessories

F50F410 LED flat cable 50-wire‚ with 24 red LEDs

Two F50F410 LED cables can be connected directly to the mimic display driver to offer a total of 48 (2x24) red LEDs. The LEDs can be easily con-figured via the configuration tools.

Cable length 1 m

BPZ:5291410001

05.fm Seite 46 Mittwoch, 28. Juli 2010 8:33 08

Page 128: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Visual Parallel Alarm IndicatorsAlarm IndicatorsAI Series for C-NET Devices

6-1© Siemens Switzerland Ltd 2010

6

Type Order No.

FDAI91 Alarm indicator - Door frame

The alarm indicator is connected in parallel to automatic fire detectors in order to indicate quickly the source of an alarm signal from detectors that are not easily accessible or visible. The alarm indicator contains an indicator lamp unit with one or two LEDs. They light up as soon as a connected fire detector gives an alarm.Screwless connection terminals.The alarm indicator is suitable for door frames.

Operating voltage 5... 8 VDC

Operating current max. 35 mA

Cable capacity max. 1.5 mm2

Operating temperature -25… +80 °C

Relative humidity L95 %

Color white‚ zRAL 9010

Protection category IP40

Dimensions (W x H x D) 62 x 37 x 24 mm

Data sheet A6V10276520

S54370-F9-A1

FDAI92 Alarm indicator - Surface

The alarm indicator is connected in parallel to automatic fire detectors in order to indicate quickly the source of an alarm signal from detectors that are not easily accessible or visible. The alarm indicator contains an indicator lamp unit with one or two LEDs. They light up as soon as a connected fire detector gives an alarm.Screwless connection terminals.The alarm indicator is suitable for wall mounting.

Operating voltage 5... 8 VDC

Operating current max. 35 mA

Cable capacity max. 1.5 mm2

Operating temperature -25… +80 °C

Relative humidity L95 %

Color white‚ zRAL 9010

Protection category IP40

Dimensions (W x H x D) 85 x 85 x 28 mm

Data sheet A6V10276520

Accessories AI330 Adapter frame

S54370-F3-A1

FDAI93 Alarm indicator - Flush

Indicator lamp to connect in parallel to automatic fire detectors. Made of transparent plastic‚ the alarm indicator is suitable for installation in door frames‚ switching panels‚ ceiling voids or special housings.The 22.5 mm Ø mounting hole is drilled by the system owner.The holder must be fitted with an insulating cap for safety.

Operating voltage 6... 8 VDC

Operating current max. 35 mA

Cable capacity max. 1.5 mm2

Operating temperature -25… +80 °C

Relative humidity L95 %

Color transparent

Protection category IP56 with DCA1191IP65 with DJZ1193

Data sheet A6V10276520

Accessories DCA1191 Housing (IP56)

S54370-F5-A1

06.fm Seite 1 Mittwoch, 28. Juli 2010 8:37 08

Page 129: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Visual Parallel Alarm IndicatorsAlarm IndicatorsAI Series for C-NET Devices

6-2 © Siemens Switzerland Ltd 2010

Type Order No.

FDCAI221 Addressable alarm indicator

The addressable alarm indicator is connected to automatic fire detec-tors in order to indicate quickly the source of an alarm signal from detectors that are not easily accessible or visible. The addressable alarm indicator contains an indicator lamp unit with two integral LEDs. They light up as soon as a connected fire detector gives an alarm.Screwless connection terminals.The alarm indicator is suitable for wall mounting.

Operating voltage 12... 33 VDC

Quiescent current 240... 400 NA

Operating temperature -10… +55 °C

Relative humidity L95 %

Color white‚ zRAL 9010

Protection category IP40

Dimensions (W x H x D) 85 x 85 x 32 mm

Data sheet A6V10244934

Accessories AI330 Adapter frame

S54370-F10-A1

AI330 Adapter frame for alarm indicator

By means of the additional frame‚ the alarm indicator can also be used for surface laid conduits or ducts‚ to increase the loop space and as an adapter for different makes of the box.

Dimensions (W x H x D) 85 x 85 x 16 mm

BPZ:3169430001

06.fm Seite 2 Mittwoch, 28. Juli 2010 8:37 08

Page 130: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective Peripherals

Fire protection with SynoLINE – no problems before switching onSynoLINE has been designed from scratch to combine excellent performance with the simplest possible installation, start-up, maintenance, and daily use. As a result, the installer can work more effi ciently. And the user can start managing his affairs after a shorter period.

Attractive, environmentally aware design Blends unobtrusively into any room Superior resistance to contamination and electromagnetic interference Screwless connection technology High stability against lightning Short-circuit-proof output for the connection of external alarm indicators Wide variation of accessories for countless applications

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 27 28.05.10 16:58

Page 131: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional fi re detectors – point detectors

SOA322Base attachment for

surface mounting

Connection terminal

DBZ1190-AB

Optical smoke detectorOP320C

SO320Base for Synova 300 series detectors

Detector locking device

TP320

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 28 28.05.10 16:58

Page 132: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsConventional Line SynoLINE300Conventional Detectors Synova 300 Series

7-3© Siemens Switzerland Ltd 2010

7

Type Order No.

OP320C Optical smoke detector

The OP320C has an excellent all-round performance within the Synova 300 range. It has a completely new optical chamber and the latest elec-tronics which open up new dimensions in safety and functionality.The base SO320 must be ordered separately.

Operating voltage 16... 28 VDC

Operating current no smoke max. 100 NA with smoke max. 170 NA

Operating temperature -10... +55 °C

Protection category IP44

Standard EN 54-7

Color white‚ zRAL 9010 (can be sprayed a different color)

Dimensions (Ø x H) 100 x 44 mm (incl. base)

Delivery unit 2 pieces

Data sheet 006801

BPZ:5081460001

OH320C Smoke detector‚ conventional multi-sensor

The OH320C is the most sensitive detector in the Synova 300 range. It has a completely new and patented optical system and the latest elec-tronics. This opens up new dimensions with regard to safety and func-tionality.The base SO320 must be ordered separately.

Operating voltage 16... 28 VDC

Operating current no smoke max. 100 NA with smoke max. 170 NA

Operating temperature -10... +55 °C

Protection category IP44

Standard EN 54-7

Color white‚ zRAL 9010 (can be sprayed a different color)

Dimensions (Ø x H) 100 x 52 mm (incl. base)

Delivery unit 2 pieces

Data sheet 006886

BPZ:5364190001

HI320C Heat detector (rate of rise and maximum)

The HI320C is an extremely reliable rate of rise and maximum temper-ature detector for demanding applications. It is characterized by relia-ble response behavior‚ not only in the event of temperature rises which are slow‚ but also where the temperature rises are fast.The base SO320 must be ordered separately.

Operating voltage 16... 28 VDC

Quiescent current max. 100 NA

Operating temperature -10... +50 °C

Protection category IP44

Standard EN 54-5: A1R

Color white‚ zRAL 9010 (can be sprayed a different color)

Dimensions (Ø x H) 100 x 36 mm (incl. base)

Delivery unit 2 pieces

Data sheet 006885

BPZ:5081590001

07.fm Seite 3 Mittwoch, 28. Juli 2010 8:45 08

Page 133: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsConventional Line SynoLINE300Conventional Detectors Synova 300 Series

7-4 © Siemens Switzerland Ltd 2010

Type Order No.

HI322C Heat detector (maximum)

The HI322C is a reliable heat detector for locations in which there are large fluctuations in temperature. It continuously measures the ambi-ent temperature and reacts if there is a sustained overshoot of defined maximum values.The base SO320 must be ordered separately.

Operating voltage 16... 28 VDC

Quiescent current max. 100 NA

Operating temperature -10... +50 °C

Protection category IP44

Standard EN54-5: A2

Color white‚ zRAL 9010 (can be sprayed a different color)

Dimensions (Ø x H) 100 x 36 mm (incl. base)

Delivery unit 2 pieces

Data sheet 006802

BPZ:5316470001

SO320 Base for Synova 300 series detectors

Base made of impact‚ scratch-proof plastic and environmentally safe materials. The base is completely covered by the detector. It fits all Syn-ova 300 series detectors‚ conventional and addressable. Standard click concept‚ with screwless terminals for easy installation. Click-in connec-tion for alarm indicators is standard on the base. Fits all standard flush mounting boxes from 55 to 80 mm.

Cable capacity 0.2... 1.5 mm2

Color white‚ zRAL 9010

Delivery unit 6 pieces

Accessories SOA322 Base attachment for sur-face mountingTP320 Detector locking device

BPZ:5085990001

Accessories

SOA322 Base attachment for surface mounting

Base attachment for feeding in surface wiring and to provide more wire space. It may also be used as a junction box where up to 30 wires can be connected. Up to 10 connection terminals DBZ1190-AB can be clicked into the base attachment SOA322. The base SO320 is mounted using a spring-loaded catch.

Dimensions (Ø x H) 100 x 20 mm

Cable capacity 0.2... 2.5 mm2

Color white‚ zRAL 9010

Delivery unit 6 pieces

Accessories DBZ1190-AB Connection terminal 2.5 mm2

BPZ:5358340001

DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole

As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.

Cable capacity 1... 2.5 mm2

Delivery unit 50 pieces

BPZ:4942340001

07.fm Seite 4 Mittwoch, 28. Juli 2010 8:45 08

Page 134: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsConventional Line SynoLINE300Conventional Detectors Synova 300 Series

7-5© Siemens Switzerland Ltd 2010

7

Type Order No.

TP320 Detector locking device

To protect the detector from theft.Mounts on the detector base SO320.

Delivery unit 50 pieces

BPZ:5093100001

07.fm Seite 5 Mittwoch, 28. Juli 2010 8:45 08

Page 135: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsConventional Line SynoLINE300Conventional Manual Call Points

7-6 © Siemens Switzerland Ltd 2010

Type Order No.

FDM1101A-RG Manual call point with glass plate

For immediate manual actuation of a fire alarm. For indoor and outdoor application. Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is reset and the device is ready for operation again. For surface- and recess-mounted feed lines in eas-ily accessible places.For surface mounting the housing base FDMH295-x must be ordered separately.

Communication protocol conventional/SynoLINE300

Operating voltage max. 28 VAC or VDC

Operating current 100 mA… max. 1 A

Terminal block 0.28… 1.5 mm2

Operating temperature -25... +70 °C

Storage temperature -30... +75 °C

Relative humidity L95 % (no condensation)

Protection category IP44

Color red‚ zRAL 3000

Standard EN 54-11

Dimensions (W x H x D) 87 x 87 x 20 mm

Data sheet A6V10206486

Accessories FDMH295-R housing baseFDMH295-S housing base with 2 holes + grommets for cable Ø5 mmFDMC295 Protective cover

S54371-F6-A3

FDM1101A-RP Manual call point with resettable plastic element

For immediate manual actuation of a fire alarm. For indoor and outdoor application. Direct alarm actuation by pushing on the plastic element. The switch is reset with the key and the device is ready for operation again. For surface- and recess-mounted feed lines in easily accessible places.For surface mounting the housing base FDMH295-x must be ordered separately.

Communication protocol conventional/SynoLINE300

Operating voltage max. 28 VAC or VDC

Operating current 100 mA… max. 1 A

Terminal block 0.28… 1.5 mm2

Operating temperature -25... +70 °C

Storage temperature -30... +75 °C

Relative humidity L95 % (no condensation)

Protection category IP44

Color red‚ zRAL 3000

Standard EN 54-11

Dimensions (W x H x D) 87 x 87 x 20 mm

Data sheet A6V10206486

Accessories FDMH295-R housing baseFDMH295-S housing base with 2 holes + grommets for cable Ø5 mmFDMC295 Protective cover

S54371-F6-A4

07.fm Seite 6 Mittwoch, 28. Juli 2010 8:45 08

Page 136: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsConventional Line SynoLINE300Conventional Manual Call Points

7-7© Siemens Switzerland Ltd 2010

7

Type Order No.

Accessories

FDMH295-R Back box

Housing base for manual call points FDM225‚ FDM1101 and FDM1101A for surface mounting.

Color red‚ zRAL 3000

Dimensions (W x H x D) 87 x 87 x 33

Accessories A5Q00004478 Screwed cable gland M20A5Q00004479 Back nut M20DBZ1190-AB Connection terminal 2.5 mm2

A5Q00013437

FDMH295-S Back box with 2 entries

Housing base for manual call points FDM225‚ FDM1101 and FDM1101A with 2 holes on top fitted with grommet for cable Ø5 mm for surface mounting.

Color red‚ zRAL 3000

Dimensions (W x H x D) 87 x 87 x 33

Accessories DBZ1190-AB Connection terminal 2.5 mm2

A5Q00013438

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

A5Q00004479 Back nut M20

Back nut to screwed cable gland M20 x 1.5.

Delivery unit 10 pieces

A5Q00004479

DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole

As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.

Cable capacity 1... 2.5 mm2

Delivery unit 50 pieces

BPZ:4942340001

07.fm Seite 7 Mittwoch, 28. Juli 2010 8:45 08

Page 137: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsConventional Line SynoLINE300Conventional Manual Call Points

7-8 © Siemens Switzerland Ltd 2010

Type Order No.

FDMC295 Protective cover

The protective cover protects the manual call points FDM225‚ FDM226‚ FDM1101 and FDM1101A from unintentional glass break.

Color transparent

Delivery unit 10 pieces

A5Q00013440

07.fm Seite 8 Mittwoch, 28. Juli 2010 8:45 08

Page 138: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsConventional Line SynoLINE300Alarm Indicators for SynoLINE300

7-9© Siemens Switzerland Ltd 2010

7

Type Order No.

AI91C Alarm indicator - Door frame

The AI91C alarm indicator is the visual parallel indication for fire detec-tors used on the SynoLINE300 detector line. It is provided with a dark red luminous element‚ fitted with LEDs. The alarm indicator is ideally used where the fire detector is difficult to see (e.g. hotel rooms‚ switch-ing cabinets). The AI91C is suitable for door frames.

Operating voltage 6... 28 VDC

Operating current max. 35 mA

Cable capacity max. 1.5 mm2

Operating temperature -25... +80 °C

Relative humidity L95 %

Protection category IP40

Dimensions (W x H x D) 62 x 37 x 24

Color white‚ zRAL 9010

Data sheet A6V10276522

S54370-F7-A1

AI92C Alarm indicator - Surface

The AI92C alarm indicator is the visual parallel indication for fire detec-tors used on the SynoLINE300 detector line. It is provided with a dark red luminous element‚ fitted with LEDs. The alarm indicator is ideally used where the fire detector is difficult to see (e.g. hotel rooms‚ switch-ing cabinets). The AI92C is suitable for surface wall mounting.

Operating voltage 6... 28 VDC

Operating current max. 35 mA

Cable capacity max. 1.5 mm2

Operating temperature -25... +80 °C

Relative humidity L95 %

Protection category IP40

Dimensions (W x H x D) 85 x 85 x 28 mm

Color white‚ zRAL 9010

Data sheet A6V10276522

Accessories AI330 Adapter frame

S54370-F8-A1

AI330 Adapter frame for alarm indicator

By means of the additional frame‚ the alarm indicator can also be used for surface laid conduits or ducts‚ to increase the loop space and as an adapter for different makes of the box.

Dimensions (W x H x D) 85 x 85 x 16 mm

BPZ:3169430001

07.fm Seite 9 Mittwoch, 28. Juli 2010 8:45 08

Page 139: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Detectors AlgoRex Series

7-10 © Siemens Switzerland Ltd 2010

Type Order No.

DO1101A Smoke detector‚ collective wide spectrum

The DO1101A has a high performance opto-electronic sensor system. It has uniform response behavior for different types of fire. It has a high resistance to soiling and temperature fluctuation.The base DB1101A must be ordered separately.

Operating voltage 16... 24 VDC

Quiescent current max. 100 NA

Operating temperature -25... +60 °C

Protection category IP44

Standard EN 54-7

Dimensions (Ø x H) 115 x 51 mm (incl. base)

Color white‚ zRAL 9010

Data sheet 001578

BPZ:4930020001

DT1101A Heat detector

The DT1101A has precise maximum temperature alarm activation with a quality thermo sensor. It has response behavior immune to deceptive phenomena with rapid and slow increases in temperature. Heat detec-tor with wide application range up to +50 °C. For the monitoring of rooms and installations where in the event of fire‚ a rapid increase in temperature can be expected‚ or other types of detector cannot be used due to operational reasons.The base DB1101A must be ordered separately.

Operating voltage 16... 24 VDC

Quiescent current max. 100 NA

Operating temperature -25... +50 °C

Protection category IP44

Standard EN 54-5: A1R

Dimensions (Ø x H) 115 x 54.5 mm (incl. base)

Color white‚ zRAL 9010

Data sheet 001578

BPZ:4931700001

DT1102A Heat detector

The DT1102A has precise maximum temperature alarm activation with a quality thermo sensor. It has response behavior immune to deceptive phenomena with rapid and slow increases in temperature. Heat detec-tor for high ambient temperatures up to +70 °C. For the monitoring of rooms and installations in which high ambient temperatures can be expected up to +70 °C.The base DB1101A must be ordered separately.

Operating voltage 16... 24 VDC

Quiescent current max. 100 NA

Operating temperature -25... +70 °C

Protection category IP44

Standard EN 54-5: B

Dimensions (Ø x H) 115 x 54.5 mm (incl. base)

Color white‚ zRAL 9010

Data sheet 001578

BPZ:4931830001

07.fm Seite 10 Mittwoch, 28. Juli 2010 8:45 08

Page 140: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Detectors AlgoRex Series

7-11© Siemens Switzerland Ltd 2010

7

Type Order No.

DB1101A Base for collective detector series

Base made of impact and scratch-proof plastic and environmentally safe materials. Integral rubber gasket to protect against draught‚ dirt and dripping water from above. Screwless terminals for easy installa-tion. Space for auxiliary terminals as micro terminals (0.5 mm2) and connection terminals (2.5 mm2). Fits all standard flush-mounted boxes from 55 to 80 mm.

Cable capacity 0.2... 2.5 mm2

Dimensions (Ø x H) 115 x 21 mm

Color white‚ zRAL 9010

Data sheet 001035

Accessories DBZ1191 Base attachment for sur-face mountingDBZ1191A-AA Base attachment flat for surface mountingDBZ1192 Base attachment humidDBZ1192-AA Base attachment wetDBZ1195A Acoustic baseDBC1191A-AA Relay baseDBZ1190 Locking deviceDBZ1190A-AC Detector heatingDBZ1193A Detector designation plateDBZ1190-AB Connection terminal 2.5 mm2

DBZ1190-AA Micro terminal 0.5 mm2

BPZ:4863650001

DBZ1191 Base attachment for surface mounting

For surface wiring feed and provision of more wire loop space. Bases are mounted using a spring-loaded catch.

Dimensions (Ø x H) 116 x 22 mm

Color white‚ zRAL 9010

Delivery unit 5 pieces

BPZ:4540830001

DBZ1191A-AA Base attachment flat for surface mounting

For surface-mounted applications with cables up to Ø6 mm‚ and to use existing mounting holes of MS7/MS9 bases. Bases DB1101A are mount-ed using a spring-loaded catch.

Dimensions (Ø x H) 116 x 11 mm

Color white‚ zRAL 9010

Delivery unit 10 pieces

BPZ:5011270001

07.fm Seite 11 Mittwoch, 28. Juli 2010 8:45 08

Page 141: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Detectors AlgoRex Series

7-12 © Siemens Switzerland Ltd 2010

Type Order No.

DBZ1192 Base attachment for humid environment

For installation in damp and corrosive environments. M20 x 1.5 cable entries are located on the side of the base attachments for easy access.

Dimensions (W x H x D) 135 x 135 x 45 mm

Color white‚ zRAL 9010

Protection category IP44

Accessories DBZ1194 Protective cageA5Q00004478 Screwed cable gland M20

BPZ:4588140001

DBZ1194 Protective cage

To protect the detector from damage. Can only be used together with the base attachment humid.

Dimensions (Ø x H) 160 x 126 mm

BPZ:4677110001

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

DBZ1192-AA Base attachment for wet environment

As DBZ1192 but for IP55 protection for heat detectors DT110xA only.

Dimensions (W x H x D) 135 x 135 x 45 mm

Color white‚ zRAL 9010

Protection category IP55

Accessories A5Q00004478 Screwed cable gland M20

BPZ:5355590001

07.fm Seite 12 Mittwoch, 28. Juli 2010 8:45 08

Page 142: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Detectors AlgoRex Series

7-13© Siemens Switzerland Ltd 2010

7

Type Order No.

DBZ1195A Acoustic base

The base DBZ1195A has an integrated base sounder. It is mainly used for hotel rooms or wherever it is sensible to have an acoustic warning when a detector is activated. The sounder is operated when the detec-tor LED is lit. The base DB1101A is mounted in the acoustic base using a spring-loaded catch.The acoustic base is connected to the external output of the detector alarm indicator direct.

Sound level M75 dB / 1 m

Operating temperature -10... +60 °C

Dimensions (Ø x H) 128.5 x 32 mm (without detector)

Color white‚ zRAL 9010

Protection category IP44

Relative humidity L95 % (no condensation)

Standard EN54-3

Data sheet 001444

Accessories DBZ1190-AA Micro terminal 0.5 mm2

DBZ1190-AB Connection terminal 2.5 mm2

BPZ:4940140001

DBC1191A-AA Relay base

The base DBC1191A-AA has an integrated relay. It enables the connec-tion of a simple fire control output facility. The contact is activated when the detector LED is lit. The base DB1101A is mounted using a spring-loaded catch.

Operating voltage external supply 10... 48 VDC

Operating current 12... 24 mA

Quiescent current 3.5... 7 mA

Relay outputs 30 VDC / 1 A

Operating temperature -10... +60 °C

Dimensions (Ø x H) 128.5 x 32 mm (without detector)

Color white‚ zRAL 9010

Protection category IP44

Relative humidity L95 % (no condensation)

Data sheet 001566

Accessories DBZ1190-AA Micro terminal 0.5 mm2

DBZ1190-AB Connection terminal 2.5 mm2

BPZ:5017870001

DBZ1190-AA Micro terminal 0.5 mm2‚ 4-pole

As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.

Cable capacity 0.28... 0.5 mm2

Delivery unit 50 pieces

BPZ:4677080001

07.fm Seite 13 Mittwoch, 28. Juli 2010 8:45 08

Page 143: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Detectors AlgoRex Series

7-14 © Siemens Switzerland Ltd 2010

Type Order No.

DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole

As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.

Cable capacity 1... 2.5 mm2

Delivery unit 50 pieces

BPZ:4942340001

DBZ1190 Locking device

To protect the detector from theft.

Delivery unit 50 pieces

BPZ:4585260001

DBZ1190A-AC Detector heating

Allows the AlgoRex series smoke detectors to operate under critical environmental conditions‚ for example where there is a danger of icing‚ moisture or condensation‚ in refrigeration plants‚ cold storage rooms‚ attics‚ loading ramps etc. Fits in DB1101A.

Operating voltage 20... 30 VDC

Operating current 35... 55 mA

Operating temperature -30... +40 °C

BPZ:5167850001

DBZ1193A Detector designation plate

To indicate a location address. To number detectors according to instal-lation drawings. The font may be up to 10 mm in an area of 60 x 20 mm. The detector designation plate is connected directly to the base or base attachment.

Color transparent

Delivery unit 10 pieces

BPZ:4864330001

07.fm Seite 14 Mittwoch, 28. Juli 2010 8:45 08

Page 144: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Manual Call Points

7-15© Siemens Switzerland Ltd 2010

7

Type Order No.

FDM1101-RG Manual call point with glass plate

For immediate manual actuation of a fire alarm. For indoor and outdoor application. Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is reset and the device is ready for operation again. For surface- and recess-mounted feed lines in eas-ily accessible places.For surface mounting the housing base FDMH295-x must be ordered separately.

Communication protocol collective/SynoLINE600

Operating voltage 16… 28 VDC

Operating current 60… 100 mA

Terminal block 0.28… 1.5 mm2

Operating temperature -25... +70 °C

Storage temperature -30... +75 °C

Relative humidity L95 % (no condensation)

Protection category IP44

Color red‚ zRAL 3000

Standard EN 54-11

Dimensions (W x H x D) 87 x 87 x 20 mm

Data sheet A6V10206486

Accessories FDMH295-R housing baseFDMH295-S housing base with 2 holes + grommets for cable Ø5 mmFDMC295 Protective cover

S54371-F6-A1

FDM1101-RP Manual call point with resettable plastic element

For immediate manual actuation of a fire alarm. For indoor and outdoor application. Direct alarm actuation by pushing on the plastic element. The switch is reset with the key and the device is ready for operation again. For surface- and recess-mounted feed lines in easily accessible places.For surface mounting the housing base FDMH295-x must be ordered separately.

Communication protocol collective/SynoLINE600

Operating voltage 16… 28 VDC

Operating current 60… 100 mA

Terminal block 0.28… 1.5 mm2

Operating temperature -25... +70 °C

Storage temperature -30... +75 °C

Relative humidity L95 % (no condensation)

Protection category IP44

Color red‚ zRAL 3000

Standard EN 54-11

Dimensions (W x H x D) 87 x 87 x 20 mm

Data sheet A6V10206486

Accessories FDMH295-R housing baseFDMH295-S housing base with 2 holes + grommets for cable Ø5 mmFDMC295 Protective cover

S54371-F6-A2

07.fm Seite 15 Mittwoch, 28. Juli 2010 8:45 08

Page 145: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Manual Call Points

7-16 © Siemens Switzerland Ltd 2010

Type Order No.

Accessories

FDMH295-R Back box

Housing base for manual call points FDM225‚ FDM1101 and FDM1101A for surface mounting.

Color red‚ zRAL 3000

Dimensions (W x H x D) 87 x 87 x 33

Accessories A5Q00004478 Screwed cable gland M20A5Q00004479 Back nut M20DBZ1190-AB Connection terminal 2.5 mm2

A5Q00013437

FDMH295-S Back box with 2 entries

Housing base for manual call points FDM225‚ FDM1101 and FDM1101A with 2 holes on top fitted with grommet for cable Ø5 mm for surface mounting.

Color red‚ zRAL 3000

Dimensions (W x H x D) 87 x 87 x 33

Accessories DBZ1190-AB Connection terminal 2.5 mm2

A5Q00013438

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

A5Q00004479 Back nut M20

Back nut to screwed cable gland M20 x 1.5.

Delivery unit 10 pieces

A5Q00004479

DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole

As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.

Cable capacity 1... 2.5 mm2

Delivery unit 50 pieces

BPZ:4942340001

07.fm Seite 16 Mittwoch, 28. Juli 2010 8:45 08

Page 146: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Manual Call Points

7-17© Siemens Switzerland Ltd 2010

7

Type Order No.

FDMC295 Protective cover

The protective cover protects the manual call points FDM225‚ FDM226‚ FDM1101 and FDM1101A from unintentional glass break.

Color transparent

Delivery unit 10 pieces

A5Q00013440

DM1101__ Collective manual call point

Collective manual call point for the immediate manual actuation of a fire alarm by pushing in the glass plate.The housing FDMH291-x and the switching unit DMA1101 must be ordered separately.

Operating temperature -25... +70 ºC

Protection category IP44

Standard EN54-11

Dimensions (W x H x D) 87 x 87 x 46.6 mm

Data sheet 007980

Accessories FDMC291 Protective coverA5Q00004478 Screwed cable gland M20A5Q00004479 Back nut M20

Products to select from

FDMH291-R See Page 7-17

FDMH291-B See Page 7-18

FDMH291-G See Page 7-18

FDMH291-Y See Page 7-18

DMA1101 See Page 7-18

DM1101__

FDMH291-R Housing red with key

Housing with key for electronic unit.

Color red‚ zRAL 3000

A5Q00002217

07.fm Seite 17 Mittwoch, 28. Juli 2010 8:45 08

Page 147: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Manual Call Points

7-18 © Siemens Switzerland Ltd 2010

Type Order No.

FDMH291-Y Housing yellow with key

Housing with key for electronic unit.

Color yellow‚ zRAL 1023

A5Q00004979

FDMH291-G Housing green with key

Housing with key for electronic unit.

Color green‚ zRAL 6024

A5Q00004981

FDMH291-B Housing blue with key

Housing with key for electronic unit.

Color blue‚ zRAL 5005

A5Q00004980

DMA1101 Switching unit collective (single action)

Direct operation switch module for use within the FDMH291-x hous-ings. For connection to collective/SynoLINE600 detection lines. An inte-gral LED provides visual indication of alarm. Provided complete with glass.

Operating voltage 16... 26 VDC

Operating current 60... 100 mA

Terminal block min. 0.28... 1.5 mm2

A5Q00005578

07.fm Seite 18 Mittwoch, 28. Juli 2010 8:45 08

Page 148: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Manual Call Points

7-19© Siemens Switzerland Ltd 2010

7

Type Order No.

Accessories

FDMC291 Protective cover

The protective cover protects the manual call point from unintentional glass break. For manual call point housings FDMH291-x.

Delivery unit 5 pieces

A5Q00001644

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

A5Q00004479 Back nut M20

Back nut to screwed cable gland M20 x 1.5.

Delivery unit 10 pieces

A5Q00004479

DM1104__ Collective manual call point

Collective manual call point for the immediate manual actuation of a fire alarm by pushing in the glass plate.The housing DMA1192-xx and the switching unit DMA1104D must be ordered separately.

Operating temperature -25... +70 °C

Protection category IP54 (IP65 with protection seal and screwed cable gland)

Standard EN 54-11

Dimensions (W x H x D) 134 x 134 x 43 mm

Data sheet 007980

Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20A5Q00006735 Locking plug M20(1 hole)A5Q00010055 Locking plug M20(2 holes)

Products to select from

DMA1192-AA See Page 7-21

DMA1192-AB See Page 7-21

DMA1192-AC See Page 7-21

DMA1192-AD See Page 7-21

DMA1104D See Page 7-20

DM1104__

07.fm Seite 19 Mittwoch, 28. Juli 2010 8:45 08

Page 149: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Manual Call Points

7-20 © Siemens Switzerland Ltd 2010

Type Order No.

DMA1104D Switching unit collective (single action)

The electronic unit is a single action device by smashing in the glass plate to activate an alarm. For connection to collective/SynoLINE600 detection lines. An LED always indicates the status of the manual call point. The electronic unit is plugged into the housing during commis-sioning.Attach the enclosed sticker 'avoid electrostatic charging' when the switching unit is used in explosion hazard areas only.

Operating voltage 16... 26 VDC

Operating current 60... 100 mA

Terminal block min. 0.28... 1.5 mm2

A5Q00005925

DM1103__ Collective manual call point

Collective manual call point for the immediate manual actuation of a fire alarm by pushing in the glass plate and pressing the push button.The housing DMA1192-xx and the switching unit DMA1103D must be ordered separately.

Operating temperature -25... +70 °C

Protection category IP54 (IP65 with protection seal and screwed cable gland)

Standard EN 54-11

Dimensions (W x H x D) 134 x 134 x 43 mm

Data sheet 007980

Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20A5Q00006735 Locking plug M20(1 hole)A5Q00010055 Locking plug M20(2 holes)

Products to select from

DMA1103D See Page 7-20

DMA1192-AA See Page 7-21

DMA1192-AB See Page 7-21

DMA1192-AC See Page 7-21

DMA1192-AD See Page 7-21

DM1103__

DMA1103D Switching unit collective (double action)

The electronic unit is a double action device; just break the glass and press the button to activate an alarm. For connection to collec-tive/SynoLINE600 detection lines. An LED always indicates the status of the manual call point. The electronic unit is plugged into the housing during commissioning.Attach the enclosed sticker 'avoid electrostatic charging' when the switching unit is used in explosion hazard areas only.

Operating voltage 16... 26 VDC

Operating current 60... 100 mA

Terminal block min. 0.28... 1.5 mm2

A5Q00004470

07.fm Seite 20 Mittwoch, 28. Juli 2010 8:45 08

Page 150: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Manual Call Points

7-21© Siemens Switzerland Ltd 2010

7

Type Order No.

DMA1192-AA Housing red‚ with glass and key

Manual call point housing for the switching units DMA110xD.

Color red‚ zRAL 3000

BPZ:5222870001

DMA1192-AB Housing blue‚ with glass and key

Manual call point housing for the switching units DMA110xD.

Color blue‚ zRAL 5005

BPZ:5464250001

DMA1192-AC Housing yellow‚ with glass and key

Manual call point housing for the switching units DMA110xD.

Color yellow‚ zRAL 1023

BPZ:5464120001

DMA1192-AD Housing green‚ with glass and key

Manual call point housing for the switching units DMA110xD.

Color green‚ zRAL 6024

BPZ:5090190001

07.fm Seite 21 Mittwoch, 28. Juli 2010 8:45 08

Page 151: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Manual Call Points

7-22 © Siemens Switzerland Ltd 2010

Type Order No.

DM1103-L Manual release button complete

Manual release button DM1103-L for the immediate manual actuation of a gas extinguishing system.For indoor and outdoor application‚ equally suited for wet‚ humid and dusty areas.For surface-mounted feed lines to the DM1103-L the housing is equipped with opening at the top and bottom‚ with sealing studs for M20 cable glands or locking plug (2 locking plugs‚ 2 holes enclosed).For indirect extinguishing release by smashing in the glass plate and pressing the push button. To replace the glass plate‚ open the housing door with the key. The push button must be set back before closing the door again.

Terminal block 0.28... 1.5 mm2

Standard EN12094-3

Protection category IP54 (IP65 with seal DMZ1197-AD)

Operating temperature -25... +70 °C

Dimensions (W x H x D) 134 x 134 x 43 mm

Data sheet 007980

Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20

A5Q00017630

DM1103-S Emergency stop button complete

Emergency stop button DM1103-S for the stop function of a gas extin-guishing system.For indoor and outdoor application‚ equally suited for wet‚ humid and dusty areas.For surface-mounted feed lines to the DM1103-S‚ the housing is equipped with openings at the top and bottom‚ with sealing studs for M20 cable glands or locking plug (2 locking plugs‚ 2 holes enclosed).Indirect stop function by smashing in the glass plate and pressing the push button. As soon as the button is not pressed any longer (self reset)‚ the stopped extinguishing release will continue. To replace the glass plate‚ open the housing door with the key.

Terminal block 0.28... 1.5 mm2

Standard EN12094-3

Protection category IP54 (IP65 with seal DMZ1197-AD)

Operating temperature -25... +70 °C

Dimensions (W x H x D) 134 x 134 x 43 mm

Data sheet 007980

Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20

A5Q00014486

07.fm Seite 22 Mittwoch, 28. Juli 2010 8:45 08

Page 152: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsCollective Line SynoLINE600Collective Manual Call Points

7-23© Siemens Switzerland Ltd 2010

7

Type Order No.

Accessories

DMZ1197-AD Protection seal

Protects the manual call point in wet applications.The seal improves the manual call point housing's protection category.

Delivery unit 5 pieces

BPZ:5470680001

DMZ1197-AC Protective cover

Protects the manual call point from unintentional glass break. Protec-tive cover can be easily fitted directly in the housing cover.

Delivery unit 5 pieces

BPZ:5223550001

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

A5Q00006735 Locking plug M20 x 1.5 (1 hole)

For manual call point housings and surface-mounted feed lines in the manual call point housing.For applications in dry rooms.

Color red‚ zRAL 3000

Delivery unit 10 pieces

A5Q00006735

A5Q00010055 Locking plug M20 x 1.5 (2 holes)

For manual call point housings and surface-mounted feed lines in the manual call point housing.For applications in dry rooms.

Color red‚ zRAL 3000

Delivery unit 10 pieces

A5Q00010055

07.fm Seite 23 Mittwoch, 28. Juli 2010 8:45 08

Page 153: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsCollective Line SynoLINE600Alarm Indicators for SynoLINE600

7-24 © Siemens Switzerland Ltd 2010

Type Order No.

FDAI91 Alarm indicator - Door frame

The alarm indicator is connected in parallel to automatic fire detectors in order to indicate quickly the source of an alarm signal from detectors that are not easily accessible or visible. The alarm indicator contains an indicator lamp unit with one or two LEDs. They light up as soon as a connected fire detector gives an alarm.Screwless connection terminals.The alarm indicator is suitable for door frames.

Operating voltage 5... 8 VDC

Operating current max. 35 mA

Cable capacity max. 1.5 mm2

Operating temperature -25… +80 °C

Relative humidity L95 %

Color white‚ zRAL 9010

Protection category IP40

Dimensions (W x H x D) 62 x 37 x 24 mm

Data sheet A6V10276520

S54370-F9-A1

FDAI92 Alarm indicator - Surface

The alarm indicator is connected in parallel to automatic fire detectors in order to indicate quickly the source of an alarm signal from detectors that are not easily accessible or visible. The alarm indicator contains an indicator lamp unit with one or two LEDs. They light up as soon as a connected fire detector gives an alarm.Screwless connection terminals.The alarm indicator is suitable for wall mounting.

Operating voltage 5... 8 VDC

Operating current max. 35 mA

Cable capacity max. 1.5 mm2

Operating temperature -25… +80 °C

Relative humidity L95 %

Color white‚ zRAL 9010

Protection category IP40

Dimensions (W x H x D) 85 x 85 x 28 mm

Data sheet A6V10276520

Accessories AI330 Adapter frame

S54370-F3-A1

AI330 Adapter frame for alarm indicator

By means of the additional frame‚ the alarm indicator can also be used for surface laid conduits or ducts‚ to increase the loop space and as an adapter for different makes of the box.

Dimensions (W x H x D) 85 x 85 x 16 mm

BPZ:3169430001

07.fm Seite 24 Mittwoch, 28. Juli 2010 8:45 08

Page 154: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsCollective Line SynoLINE600Alarm Indicators for SynoLINE600

7-25© Siemens Switzerland Ltd 2010

7

Type Order No.

FDAI93 Alarm indicator - Flush

Indicator lamp to connect in parallel to automatic fire detectors. Made of transparent plastic‚ the alarm indicator is suitable for installation in door frames‚ switching panels‚ ceiling voids or special housings.The 22.5 mm Ø mounting hole is drilled by the system owner.The holder must be fitted with an insulating cap for safety.

Operating voltage 6... 8 VDC

Operating current max. 35 mA

Cable capacity max. 1.5 mm2

Operating temperature -25… +80 °C

Relative humidity L95 %

Color transparent

Protection category IP56 with DCA1191IP65 with DJZ1193

Data sheet A6V10276520

Accessories DCA1191 Housing (IP56)

S54370-F5-A1

DCA1191 Housing (empty)

Housing with cover for several applications. The housing offers six M20 cable feed-throughs for screwed cable glands and offers a higher pro-tection category.The screwed cable gland must be ordered separately.

Dimensions (W x H x D) 135 x 135 x 65 mm

Color white‚ zRAL 9010

Protection category IP56

Accessories A5Q00004478 Screwed cable gland M20

BPZ:4588560001

BPZ:2473130001 Washer

Washer for alarm indicator model recess mounting. The washer can be used for applications in humid rooms.

Dimensions (Ø x D) 23 x 1 mm

BPZ:2473130001

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

DJZ1193 Alarm indicator housing incl. washer

For surface mounting in wet areas.1 alarm indicator can be built into the housing.

Dimensions (W x H x D) 87 x 87 x 64 mm

Color white‚ zRAL 9010

Protection category IP65

BPZ:5302950001

07.fm Seite 25 Mittwoch, 28. Juli 2010 8:45 08

Page 155: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire Detection Collective PeripheralsCollective Line SynoLINE600Alarm Indicators for SynoLINE600

7-26 © Siemens Switzerland Ltd 2010

Type Order No.

MVH1 Mounting bracket

For mounting of the alarm indicator housing DJZ1193 and detectors in hollow floors.

Length 0.29... 0.42 m (pipe clamp 1/2")

BPZ:3496190001

07.fm Seite 26 Mittwoch, 28. Juli 2010 8:45 08

Page 156: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Alarm EquipmentSounders

8-1© Siemens Switzerland Ltd 2010

8

Type Order No.

AGN24.6 Alarm device

The alarm sounder is the most popular fire sounder for inside and out-door applications‚ although under roof or canopy. The volume is adjust-able with a potentiometer. The alarm sounder allows differentiation between various alarms. Choice of 28 preset tones with volume con-trol. Line monitoring possible by changing the polarity. The base is included.The adapter base ZS/AGN24.5 for IP65 must be ordered separately.

Operating voltage 9... 30 VDC

Alarm current 18 mA

Operating temperature -25... +80 °C

Number of sounds 28

Frequency range 500... 4000 Hz

Volume at 24 V and 1 m 92.. 111 dB

Cable capacity 0.28... 1.5 mm2

Protection category IP54

Dimensions (Ø x D) 93 x 63 mm

Color white‚ zRAL 9003

Data sheet 001790

Accessories ZS/AGN24.5 Adapter base for IP65

BPZ:5371170001

ZS/AGN24.5 Adapter base

The ZS/AGN24.5 adapter base is used to upgrade the alarm device AGN24.6 and ALB24.. to IP65.

Dimensions (Ø x D) 93 x 30 mm

Color white‚ zRAL 9003

Protection category IP65

Data sheet 001790

BPZ:4242620001

AGT24.1 Alarm device

Ultra slim profile sounder for ceiling mounting for small to medium size rooms with a low background noise level. Detectors can be fitted to the unit providing a neat‚ unobtrusive installation. Choice of 4 different tones with two sound intensities‚ remote-controlled change of tone for two-stage alarm.

Operating voltage 9... 30 VDC

Alarm current 3... 15 mA

Operating temperature -25... +85 °C

Number of sounds 4

Frequency range 510... 970 Hz

Volume at 24 V and 1 m 86... 97 dB

Cable capacity 0.28... 1.5 mm2

Protection category IP42

Dimensions (Ø x D) 110 x 35 mm

Color white‚ zRAL 9003

Data sheet 001790

BPZ:5371040001

08.fm Seite 1 Mittwoch, 28. Juli 2010 8:49 08

Page 157: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Alarm EquipmentSounders

8-2 © Siemens Switzerland Ltd 2010

Type Order No.

AGS24.5 Mallory buzzer

Buzzer for small‚ dry rooms with a low background noise level. Buzzer with continuous tone. For incorporation in equipment‚ panels etc. (for front panels with a max. thickness of 5 mm‚ a drill hole of 29.5 mm is adequate).

Operating voltage 18... 36 VDC

Alarm current 12 mA

Operating temperature -20... +40 °C

Number of sounds 1

Frequency range 2900 Hz

Volume at 24 V and 1 m 80 dB

Cable capacity 0.28... 1.5 mm2

Protection category IP20

Dimensions (Ø x D) 56 x 52 mm

Color black

Data sheet 001790

BPZ:2785020001

08.fm Seite 2 Mittwoch, 28. Juli 2010 8:49 08

Page 158: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Conventional Alarm EquipmentOptical Signaling Equipment

8-3© Siemens Switzerland Ltd 2010

8

Type Order No.

ALB24.1OR Flashing signal lamp 'orange'

Powerful light intensity generated by electronic flash tube‚ ribbed dome with strong diffusion. Ideal for noisy environments. To identify build-ings‚ entrances and exits: help can be brought quickly in an emergency. For inside and outside application.The adapter base ZS/AGN24.5 for IP65 must be ordered separately.

Operating voltage 20... 30 VDC

Alarm current 155 mA (3.7 W)

Operating temperature -20... +55 °C

Frequency range ca. 1 Hz (60/min.)

Flash energy 2 Joule

Cable capacity 1.5 mm2

Protection category IP54

Dimensions (Ø x D) 93 x 75 mm

Data sheet 001570

Accessories ZS/AGN24.5 Adapter base for IP65

BPZ:5154140001

ALB24.1R Flashing signal lamp 'red'

Powerful light intensity generated by electronic flash tube‚ ribbed dome with strong diffusion. Ideal for noisy environments. To identify build-ings‚ entrances and exits: help can be brought quickly in an emergency. For inside and outside application.The adapter base ZS/AGN24.5 for IP65 must be ordered separately.

Operating voltage 20... 30 VDC

Alarm current 155 mA (3.7 W)

Operating temperature -20... +55 °C

Frequency range ca. 1 Hz (60/min.)

Flash energy 2 Joule

Cable capacity 1.5 mm2

Protection category IP54

Dimensions (Ø x D) 93 x 75 mm

Data sheet 001570

Accessories ZS/AGN24.5 Adapter base for IP65

BPZ:5154270001

ZS/AGN24.5 Adapter base

The ZS/AGN24.5 adapter base is used to upgrade the alarm device AGN24.6 and ALB24.. to IP65.

Dimensions (Ø x D) 93 x 30 mm

Color white‚ zRAL 9003

Protection category IP65

Data sheet 001790

BPZ:4242620001

08.fm Seite 3 Mittwoch, 28. Juli 2010 8:49 08

Page 159: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 29 28.05.10 16:58

Page 160: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special Applications

Offering a wide range of special detectorsThe detector range of Cerberus® PRO includes a broad range of special detectors, meeting various needs. In areas with limited access such as high bay warehouses, linear smoke detectors are the ideal choice. Flame detectors cover areas containing highly fl ammable materials best. Furthermore, Cerberus PRO offers a complete range for areas subject to explosion hazards and for areas that require very high sensitivity.

Flame detection – for areas with highly fl ammable materials Linear smoke detector – for high ceiling areas with limited accessibility Aspirating smoke detection – for areas requiring high sensitivity Ex detectors – for areas subject to explosion hazards Radio fi re detectors – for historical buildings and other special applications

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 31 28.05.10 16:58

Page 161: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsSpecial DetectorsInfrared Flame Detectors

9-2 © Siemens Switzerland Ltd 2010

Type Order No.

FDF__ Infrared flame detector

Infrared flame detector for special applications. The infrared flame detector detects smokeless liquid and gas fires as well as smoke-gener-ating open fires resulting from the combustion of carbonaceous mate-rials such as wood‚ synthetics‚ gases‚ oil products‚ etc. The LE3 test lamp is used to make a performance check on the infrared flame detector at a distance of up to 10 m.Can be used as an addressable‚ collective or conventional device.The detector unit FDF2x1-9 and the base FDFB291 must be ordered separately.

Communication protocol FDnet/C-NET‚ collective‚ conven-tional

Ext. alarm indicator 2

Relative humidity L95 %

Color white‚ zRAL 9010

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720collective‚ conventional -> CZ10‚ BC10‚ FC10‚ XC10‚ CS11‚ FC700A‚ FC330A‚ SIGMASYS‚ BMS‚ SM80/88/D100

Standard EN54-10‚ EN54-17

Dimensions (W x H x D) 135 x 135 x 77 mm

Data sheet 007012

Accessories DFZ1190 Rain hoodMV1 Mounting bracketMWV1 Ball and socket joint

Products to select from

FDF221-9 See Page 9-2

FDF241-9 See Page 9-3

FDFB291 See Page 9-3

FDF__

FDF221-9 DA Infrared flame detector unit (1 sensor)

The infrared flame detector is used for simple applications‚ additional to smoke detectors. Only used without source of interference such as sun‚ halogen light‚ and black body radiation.1 infrared sensor with detection algorithms.The base FDFB291 must be ordered separately.

Operating voltage FDnet/C-NET-> 12... 33 VDCcollective/conv. -> 16... 28 VDC

Quiescent current FDnet/C-NET -> 0.7 mA collective/conv. -> 0.5 mA

Operating temperature -25... +70 °C

Storage temperature -40... +75 °C

Dimensions (W x H x D) 135 x 135 x 32 mm

Protection category IP44

A5Q00003902

09.fm Seite 2 Mittwoch, 28. Juli 2010 8:51 08

Page 162: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsSpecial DetectorsInfrared Flame Detectors

9-3© Siemens Switzerland Ltd 2010

9

Type Order No.

FDF241-9 ASA Infrared flame detector unit (3 sensors)

The infrared flame detector is specially suited to environments where deceptive phenomena such as e.g. sun‚ radiation or hot engines have to be expected. For large industrial warehouses‚ hangars for military and civil aircraft‚ underground tunnels etc.3 infrared sensors with ASAtechnology™.The base FDFB291 must be ordered separately.

Operating voltage FDnet/C-NET -> 12... 33 VDCcollective/conv. -> 14... 28 VDC

Quiescent current FDnet/C-NET -> 0.7 mAcollective/conv. -> 0.5 mA

Operating temperature -35... +70 °C

Storage temperature -40... +75 °C

Dimensions (W x H x D) 135 x 135 x 32 mm

Protection category IP67

A5Q00003006

FDFB291 Base for infrared flame detectors FDF2x1-9

The base comprises a robust‚ glass fiber-reinforced‚ plastic housing which provides the required isolated installation of the detector. The base contains screwless terminals‚ isolated auxiliary terminals and six M20 cable entry possibilities for cable glands.

Cable capacity 0.2... 1.5 mm2 (AWG24... 15)

Dimensions (W x H x D) 135 x 135 x 45 mm

Accessories A5Q00004478 Screwed cable gland M20

A5Q00003310

DFZ1190 Rain hood

Rain hood for the infrared flame detector for outdoor applications.

Dimensions (W x H x D) 150 x 165 x 130 mm

BPZ:5302660001

MV1 Mounting bracket

The mounting bracket for volumetric surveillance‚ fixes the infrared flame detector at the right angle.

Dimensions (W x H x D) 136 x 120 x 120 mm

BPZ:3950450001

09.fm Seite 3 Mittwoch, 28. Juli 2010 8:51 08

Page 163: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsSpecial DetectorsInfrared Flame Detectors

9-4 © Siemens Switzerland Ltd 2010

Type Order No.

MWV1 Ball and socket joint

Ball and socket joint for the infrared flame detector for the orientation to a defined object.

Dimensions (H x W x D) 120 x 164 x 118 mm

BPZ:3674840001

LE3 Test lamp for flame detectors

The test lamp is used for testing the operation of all flame detectors (non explosion-hazard areas). It is supplied with all the necessary acces-sories in a suitable carrying case (incl. charger‚ without battery). The carrying case also provides a means of storing the test lamp free of dust.The battery FA2003-A1 must be ordered separately.

Operating temperature -20... +45 °C

Storage temperature -20... +45 °C

Battery capacity 1 x 12 V / 7 Ah

Data sheet AlgoRex‚ Synova‚ Sinteso -> 000252Cerberus PRO -> A6V10203222

BPZ:3669510001

09.fm Seite 4 Mittwoch, 28. Juli 2010 8:51 08

Page 164: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsSpecial DetectorsLinear Smoke Detectors

9-5© Siemens Switzerland Ltd 2010

9

Type Order No.

FDL__ ASA Linear smoke detector

The linear smoke detector is ideal to monitor extensive areas (detec-tion distance 5... 100 m). Wiring is simple‚ and needed only on one side. The linear smoke detector consists of a detector‚ a base‚ and a simple reflector or a sophisticated prism on the opposite side. It is the ideal solution for monitoring of large store-rooms and production work-shops‚ areas with complex roof structures or historically valuable ceil-ings‚ covered courtyards‚ atrium type buildings and reception halls.Can be used as an addressable‚ collective or conventional device.The detector FDL241-9 and the base FDLB291 must be ordered sepa-rately.

Communication protocol FDnet/C-NET‚ collective‚ conven-tional

Ext. alarm indicator 2

Operating temperature -25... +60 °C

Storage temperature -30... +75 °C

Relative humidity L95 %

Color white‚ zRAL 9010

Protection category IP65

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720collective‚ conventional -> CZ10‚ BC10‚ FC10‚ XC10‚ CS11‚ FC700A‚ FC330A‚ SIGMASYS‚ BMS‚ SM80/88/D100

Standard EN54-12‚ EN54-17

Dimensions (W x H x D) 135 x 135 x 115 mm

Data sheet 007017

Products to select from

FDL241-9 See Page 9-6

FDLB291 See Page 9-6

FDL__

09.fm Seite 5 Mittwoch, 28. Juli 2010 8:51 08

Page 165: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsSpecial DetectorsLinear Smoke Detectors

9-6 © Siemens Switzerland Ltd 2010

Type Order No.

FDL241-9 ASA Linear smoke detector unit

The detector consists of a light emitter and a light receiver. The light emitter emits a bundled infrared ray‚ which is scattered back by the prism shaped reflector to the light emitter. The receiver converts the received infrared signal to an electric signal‚ which is evaluated by the microprocessor-controlled electronics. Smoke penetrating the measur-ing section attenuates the infrared signal. When the signal reaches pre-defined measuring values‚ the detector transmits the corresponding danger level to the control unit. Distance measurement for the recog-nition of foreign matter. The built-in alarm indicator signals the alarm status locally. For various distances‚ different reflectors are available.The optics can be efficiently adjusted to the reflector by single-handed alignment via the adjustment device FDLU291.The base FDLB291 must be ordered separately.

Operating voltage FDnet/C-NET -> 12... 33 VDCcollective/conv. -> 14... 28 VDC

Quiescent current 0.8 mA / 0.7 mA

Dimensions (W x H x D) 135 x 135 x 70 mm

Accessories DLR1191 Reflector for long distanceDLR1192 Reflector for middle dis-tanceDLR1193 Reflector for short dis-tanceDLF1191-AA Short distance filter for 7... 10 mDLF1191-AB Short distance filter for 5... 8 mDLF1191-AC Extraneous light filterDLH1191A Detector heatingFDLU291 Adjustment device

A5Q00002298

FDLB291 Base for linear smoke detector FDL241-9

The base comprises a robust‚ glass fiber-reinforced‚ plastic housing which provides the required isolated installation of the detector. The base contains screwless terminals and six M20 cable entry possibilities for cable glands.

Cable capacity 0.2... 1.5 mm2 (AWG24... 15)

Dimensions (W x H x D) 135 x 135 x 45 mm

Accessories A5Q00004478 Screwed cable gland M20

A5Q00003941

09.fm Seite 6 Mittwoch, 28. Juli 2010 8:51 08

Page 166: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsSpecial DetectorsLinear Smoke Detectors

9-7© Siemens Switzerland Ltd 2010

9

Type Order No.

Accessories

DLR1191 Reflector for long distance (prism)

Retro-reflectors are characterized by the fact that an impinging light ray is reflected in parallel. The reflector does not need to be mounted at a right angle to the light ray. Vibrations and distortions in the wall where the reflector is mounted do not cause any disturbances either. Another advantage lies in the fact that possibly interfering light is also reflected in on itself and can thus not reach the receiver.The retro-reflecting prism has the shape of an even pyramid‚ the lateral surfaces of which are made up from isosceles‚ right-angled triangles. Light rays coming in through the base surface are completely reflected by the lateral surfaces and are then scattered back through the base.For distances of 20... 100 m.

Detector heating equipped‚ external power supply 24 VDC is required

Dimensions (W x H x D) 135 x 135 x 65 mm

Color white‚ zRAL 9010

Accessories A5Q00004478 Screwed cable gland M20

BPZ:4787710001

DLR1192 Reflector for middle distance (foil)

The foil consists of micro-prismatic elements‚ which are formed in a transparent‚ synthetic resin‚ sealed and mounted on a plastic base. The reflector foil has the same principal effect (function) as the prism.For distances of 30... 65 m.

Dimensions (W x H x D) 200 x 200 x 2.5 mm

BPZ:4788490001

DLR1193 Reflector for short distance (foil)

The foil consists of micro-prismatic elements‚ which are formed in a transparent‚ synthetic resin‚ sealed and mounted on a plastic base. The reflector foil has the same principal effect (function) as the prism.For distances of 10... 30 m.

Dimensions (W x H x D) 100 x 100 x 2.5 mm

BPZ:4787840001

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

DLF1191-AA Filter for short distances (7... 10 m)

For short distances between 7 and 10 meters‚ an additional short dis-tance filter is required. The filter attenuates the detector signal over short distances. The filter can be inserted directly into the detector unit.

BPZ:4933030001

09.fm Seite 7 Mittwoch, 28. Juli 2010 8:51 08

Page 167: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsSpecial DetectorsLinear Smoke Detectors

9-8 © Siemens Switzerland Ltd 2010

Type Order No.

DLF1191-AB Filter for short distances (5... 8 m)

For short distances between 5 and 8 meters‚ an additional short dis-tance filter is required. The filter attenuates the detector signal over short distances. The filter can be inserted directly into the detector unit.

BPZ:4933160001

DLF1191-AC Filter against external light influences

Interferences of the detector by extraneous light are rather rare. How-ever‚ if such a disturbance should occur in case of a strong impact of extraneous light‚ the extraneous light filter is available. The filter absorbs disturbing IR rays. The filter can be inserted into the detector (not possible if short distance filter is inserted).

BPZ:5221480001

DLH1191A Detector heating

Enables operation of a linear smoke detector where there is a risk of condensation.24 VDC external power supply is necessary.

Operating voltage 20… 30 VDC

Operating current 30... 50 mA

BPZ:4787970001

FDLU291 Adjustment device set for linear smoke detector

The optics of the linear smoke detector can be efficiently adjusted to the reflector by single-handed alignment via the adjustment device.Box with adjustment device‚ alarm test filter‚ visor‚ magnet‚ spiral cable‚ MC-Link cable‚ and battery 9 V‚ 0.5 Ah.

A5Q00004905

RE10 Detector tester for linear smoke detectors

For performance check of linear smoke detector. In compliance with the type of detector to be tested‚ the alarm test filter is inserted in the detector tester.The detector tester is then held in front of the optical parts of the detec-tor (i.e. into the infrared ray). The detector reacts after a few seconds.Alarm test filter contained in FDLU291 or TF04 must be ordered sepa-rately.

Data sheet Synova‚ AlgoRex -> 001164Sinteso -> 007228Cerberus PRO -> A6V10203222

Accessories TF04 Alarm test filterFDUM291 Telescope rodFDUM292 Telescope rod

BPZ:3685190001

09.fm Seite 8 Mittwoch, 28. Juli 2010 8:51 08

Page 168: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsSpecial DetectorsLinear Smoke Detectors

9-9© Siemens Switzerland Ltd 2010

9

Type Order No.

TF04 Alarm test filter (Absorption 77 %)

Alarm test filter for detector tester RE10.

BPZ:4931090001

09.fm Seite 9 Mittwoch, 28. Juli 2010 8:51 08

Page 169: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsSpecial DetectorsAir Sampling Smoke Detection

9-10 © Siemens Switzerland Ltd 2010

Type Order No.

FDBZ292 Air sampling smoke detection kit

The air sampling smoke detection kit is a passive monitoring system without its own fan. It makes use of the existing pressure difference in the ventilation system in order to supply a continuous flow of air through a bypass from the ventilation duct to the air sampling smoke detection kit.The air sampling smoke detection kit only works if the ventilation sys-tem is in operation and the air is circulating. The monitored air must be clean‚ i.e. free from dust and aerosols.When a smoke concentration set in the smoke detector is reached‚ the corresponding danger level is signaled to the fire alarm control unit which initiates the corresponding alarm.Can be used as an addressable or collective device.The smoke detectors and bases must be ordered separately.

Smoke detector Sinteso -> FDO241‚ FDOOT241-8‚ FDOOT241-9AlgoRex‚ Synova -> DO1133A‚ DO1103A‚ DO1104ACerberus PRO -> DO1104A

Detector base Sinteso -> FDB201/221‚ FDB201/221-AAAlgoRex -> DB1151A‚ DB1131A‚ DB1101ASynova -> DB1101A‚ SO620ACerberus PRO -> DB1101A

System compatibility Sinteso -> FDnetAlgoRex -> interactive‚ AnalogPLUS‚ collectiveSynova -> SynoLINE600‚ SynoLOOPCerberus PRO -> collective‚ in C-NET via FDCIO223

Min. duct diameter 100 mm

Permissible air speed 1... 20 m/s

Airflow indicator M1 m/s

Ambient temperature‚ operation -20… +50 °C

Protection category IP54

Relative humidity L95 %

Dimensions (W x H x D) 146 x 235 x 183 mm

Color grey‚ zRAL 7001

Data sheet 009728

Accessories FDBZ292-AA Air flow tube‚ L = 0.6 mFDBZ292-AB Air flow tube‚ L = 1.5 mFDBZ292-AC Air flow tube‚ L = 2.8 mFDBZ292-AD Sealing kitFDBZ292-AF Mounting bracketDBZ1190-AB Connection terminal 1... 2.5 mm2

A5Q00021362

09.fm Seite 10 Mittwoch, 28. Juli 2010 8:51 08

Page 170: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsSpecial DetectorsAir Sampling Smoke Detection

9-11© Siemens Switzerland Ltd 2010

9

Type Order No.

DO1104A Smoke detector‚ collective wide spectrum

Automatic fire detector with higher response sensitivity for the early warning of smoke-forming‚ flaming fires and smoldering fires. For applications in hospital rooms‚ archives‚ museums etc.The base DB1101A must be ordered separately.

Operating voltage 16... 24 VDC

Quiescent current max. 100 NA

Operating temperature -25... +60 °C

Storage temperature -30… +75 °C

Sensitivity Typ. 1.8 %/m

Protection category IP44

Color white‚ zRAL 9010

Dimensions (Ø x H) 115 x 51mm (incl. base)

Standard EN 54-7

Data sheet 001578

BPZ:5090640001

DB1101A Base for collective detector series

Base made of impact and scratch-proof plastic and environmentally safe materials. Integral rubber gasket to protect against draught‚ dirt and dripping water from above. Screwless terminals for easy installa-tion. Space for auxiliary terminals as micro terminals (0.5 mm2) and connection terminals (2.5 mm2). Fits all standard flush-mounted boxes from 55 to 80 mm.

Cable capacity 0.2... 2.5 mm2

Dimensions (Ø x H) 115 x 21 mm

Color white‚ zRAL 9010

Data sheet 001035

BPZ:4863650001

Accessories

FDBZ292-AA Air flow tube 0.6 m

The air flow tube is introduced through a hole drilled into the duct and shortened according to the diameter of the duct.

Length 0.6 m

A5Q00021363

09.fm Seite 11 Mittwoch, 28. Juli 2010 8:51 08

Page 171: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsSpecial DetectorsAir Sampling Smoke Detection

9-12 © Siemens Switzerland Ltd 2010

Type Order No.

FDBZ292-AB Air flow tube 1.5 m

As FDBZ292-AA but different length.

Length 1.5 m

A5Q00021364

FDBZ292-AC Air flow tube 2.8 m

As FDBZ292-AA but different length.

Length 2.8 m

A5Q00021366

FDBZ292-AD Sealing kit for air flow tubes

One sealing kit is necessary for-> applications using the mounting bracket-> applications using air flow tubes longer than 1 mTwo sealing kits are necessary for-> applications using the mounting bracket and air flow tubes longer than 1 m

A5Q00021367

FDBZ292-AF Mounting bracket

The mounting bracket is used for uneven‚ round and insulated ducts.

A5Q00021369

09.fm Seite 12 Mittwoch, 28. Juli 2010 8:51 08

Page 172: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsSpecial DetectorsAir Sampling Smoke Detection

9-13© Siemens Switzerland Ltd 2010

9

Type Order No.

DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole

As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.

Cable capacity 1... 2.5 mm2

Delivery unit 50 pieces

BPZ:4942340001

09.fm Seite 13 Mittwoch, 28. Juli 2010 8:51 08

Page 173: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsSpecial DetectorsAspirating Smoke Detection

9-14 © Siemens Switzerland Ltd 2010

Type Order No.

LaserFOCUS VLF-250 Aspirating smoke detector with display

The LaserFOCUS detector is a very early warning smoke detector (Aspi-rating Smoke Detector ASD) designed to protect small‚ business-critical environments of less than 250 sqm. The detector works by continually drawing air into sampling holes in a pipe network. The air is filtered and passed into a detection chamber where light-scattering technology detects the presence of very small amounts of smoke. Detector status information is communicated on the detector display.The FDnet/C-NET interface card is integrated.

Communication protocol FDnet/C-NET

Operating voltage 18… 30 VDC

Quiescent current 220 mA

Alarm current 295 mA

Display 4 Alarm state indicatorsFault and disabled indicatorsSmoke level indicator

Area coverage up to 250 m2

Alarm threshold 0.025 - 2.00 %/m / Info alarm‚ Pre-alarm0.025 - 20.00 %/m / Fire 1‚ Fire 2

Air inlet pipe Accepts both metric and American standard pipe sizesExternal diameter 25 mmInternal diameter 21 mm

Pipe length max. 1 x 25 m (max. 12 holes)max. 2 x 15 m per branch (max. 6 holes per branch)

Relay outputs 3x 2 A / 30 VPre-alarm‚ Alarm‚ Fault

Terminals 0.2… 2.5 mm2 (30… 12 AWG)

Dimensions (W x H x D) 255 x 185 x 90 mm

Operating temperature 0... +40 °C

Relative humidity L95 % (no condensation)

Protection category IP30

Data sheet A6V10221433

VLF-250-SIE

09.fm Seite 14 Mittwoch, 28. Juli 2010 8:51 08

Page 174: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsSpecial DetectorsAspirating Smoke Detection

9-15© Siemens Switzerland Ltd 2010

9

Type Order No.

LaserFOCUS VLF-500 Aspirating smoke detector with display

The LaserFOCUS detector is a very early warning smoke detector (Aspi-rating Smoke Detector ASD) designed to protect small‚ business-critical environments of less than 500 sqm. The detector works by continually drawing air into sampling holes in a pipe network. The air is filtered and passed into a detection chamber where light-scattering technology detects the presence of very small amounts of smoke. Detector status information is communicated on the detector display.The FDnet/C-NET interface card is integrated.

Communication protocol FDnet/C-NET

Operating voltage 18… 30 VDC

Quiescent current 410 mA

Alarm current 490 mA

Display 4 Alarm state indicatorsFault and disabled indicatorsSmoke level indicator

Area coverage up to 500 m2

Alarm threshold 0.025 - 2.00 %/m / Info alarm‚ Pre-alarm0.025 - 20.00 %/m / Fire 1‚ Fire 2

Air inlet pipe Accepts both metric and American standard pipe sizesExternal diameter 25 mmInternal diameter 21 mm

Pipe length max. 1 x 50 m (max. 24 holes)max. 2 x 30 m per branch (max. 12 holes per branch)

Relay outputs 3x 2 A / 30 VPre-alarm‚ Alarm‚ Fault

Terminals 0.2… 2.5 mm2 (30… 12 AWG)

Dimensions (W x H x D) 255 x 185 x 90 mm

Operating temperature 0... +40 °C

Relative humidity L95 % (no condensation)

Protection category IP30

Data sheet A6V10221433

VLF-500-SIE

09.fm Seite 15 Mittwoch, 28. Juli 2010 8:51 08

Page 175: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsSpecial DetectorsRadio Fire Detection Wireless System

9-16 © Siemens Switzerland Ltd 2010

Type Order No.

FDCW221 Radio gateway

Wireless fire detection is used in situations where the user wants to avoid wires and their installation. In addition it means less interruption of operation and high flexibility for extensions and changes. High trans-mission reliability by radio transmission in SRD band (Short Range Device)‚ a reserved frequency band with defined user rules. 80 chan-nels are available.The radio gateway FDCW221 is connected to the detector bus FDnet/C-NET and communicates with up to 30 radio detectors (smoke detectors and manual call points). Each detector has its own location address.The additional 9 V battery (must be ordered separately A5Q00004142) safeguards operation during commissioning or when the detector bus is without voltage. MC-Link connector for commissioning and mainte-nance with detector exchanger and tester.

Supply voltage via FDnet/C-NET‚ additionally 1x 9 V lithium battery‚ monitored

Communication protocol FDnet/C-NET

Transmitter/receiver antenna 2 (antenna diversity)

Transmitting power L5 mW ERP

Transmission distance max. 40 m in buildingmax. 200 m in open air

Channel width 25 kHz

Radio frequency 868 ... 870 MHz (SRD band)

Ext. alarm indicator 2

Operating temperature -10... + 55 °C

Dimensions (W x H x D) 58 x 213.5 x 33.4 mm

Color grey-white‚ zRAL 9002

Protection category IP40

Relative humidity L95 %

Standard EN 54-17‚ EN 54-18

Approval

Data sheet 010087

A5Q00020241

09.fm Seite 16 Mittwoch, 28. Juli 2010 8:51 08

Page 176: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsSpecial DetectorsRadio Fire Detection Wireless System

9-17© Siemens Switzerland Ltd 2010

9

Type Order No.

DOW1171/DBW1171 Radio smoke detector complete

Uniform response to various types of fires. Dynamic analysis of the sen-sor signal in the detector itself. Built-in diagnostic algorithms with auto-matic self-test. High immunity to false alarms and ambient influences. High-quality opto-electronic sensor system. Automatic compensation of soiling. Each radio smoke detector has its own address and can trans-mit 4 danger levels.The radio smoke detector is supplied by two 9 V lithium batteries and can be mounted at any position within radio range. In normal operating condition they have a service life of more than 5 years.The radio smoke detector can be inserted and removed and actuated using the DZ1191‚ DZ1193 detector exchanger.The radio smoke detector complete consists of the radio smoke detec-tor DOW1171‚ the base DBW1171 and 2 batteries (A5Q00004142).

Supply voltage 2x 9 V lithium batteries‚ separately monitored

Transmitter/receiver antenna 2 (antenna diversity)

Transmitting power L5 mW ERP

Transmission distance max. 40 m in buildingmax. 200 m in open air

Channel width 25 kHz

Radio frequency 868... 870 MHz (SRD band)

Operating temperature -10... + 55 °C

Dimensions (Ø x H) 119 x 73 mm

Color white‚ zRAL 9010

Protection category IP44

Relative humidity L95 %

Standard EN 54-7

Approval

Data sheet 010087

S24218-F62-A5

09.fm Seite 17 Mittwoch, 28. Juli 2010 8:51 08

Page 177: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsSpecial DetectorsRadio Fire Detection Wireless System

9-18 © Siemens Switzerland Ltd 2010

Type Order No.

DOW1171 Radio smoke detector

Uniform response to various types of fires. Dynamic analysis of the sen-sor signal in the detector itself. Built-in diagnostic algorithms with auto-matic self-test. High immunity to false alarms and ambient influences. High-quality opto-electronic sensor system. Automatic compensation of soiling. Each radio smoke detector has its own address and can trans-mit 4 danger levels.The radio smoke detector is supplied by two 9 V lithium batteries (must be ordered separately) and can be mounted at any position within radio range. In normal operating condition they have a service life of more than 5 years.The radio smoke detector can be inserted and removed and actuated using the DZ1191‚ DZ1193 detector exchanger.The base DBW1171 and the batteries (A5Q00004142) must be ordered separately.

Supply voltage 2x 9 V lithium batteries‚ separately monitored

Transmitter/receiver antenna 2 (antenna diversity)

Transmitting power L5 mW ERP

Transmission distance max. 40 m in buildingmax. 200 m in open air

Channel width 25 kHz

Radio frequency 868... 870 MHz (SRD band)

Operating temperature -10... + 55 °C

Dimensions (Ø x H) 119 x 73 mm

Color white‚ zRAL 9010

Protection category IP44

Relative humidity L95 %

Standard EN 54-7

Approval

Data sheet 010087

S24218-F62-A6

DBW1171 Base for radio smoke detector

Base made of impact and scratch-proof plastic and environmentally safe materials. The base is required for installation of radio smoke detector DOW1171.

Dimensions (Ø x H) 118 x 38.7 mm

Color white‚ zRAL 9010

Accessories DBZ1190 Detector locking deviceDBZ1193A Detector designation plateDBZ1192 Base attachment‚ wet application

S24218-F316-A1

Accessories

DBZ1190 Locking device

To protect the detector from theft.

Delivery unit 50 pieces

BPZ:4585260001

09.fm Seite 18 Mittwoch, 28. Juli 2010 8:51 08

Page 178: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsSpecial DetectorsRadio Fire Detection Wireless System

9-19© Siemens Switzerland Ltd 2010

9

Type Order No.

DBZ1193A Detector designation plate

To indicate a location address. To number detectors according to instal-lation drawings. The font may be up to 10 mm in an area of 60 x 20 mm. The detector designation plate is connected directly to the base or base attachment.

Dimensions (W x H) 62 x 52 mm

Color transparent

Delivery unit 10 pieces

BPZ:4864330001

DBZ1192 Base attachment for humid environment

For installation in damp and corrosive environments. M20 x 1.5 cable entries are located on the side of the base attachments for easy access.

Dimensions (W x H x D) 135 x 135 x 45 mm

Color white‚ zRAL 9010

Protection category IP44

Accessories DBZ1194 Protective cageA5Q00004478 Screwed cable gland M20

BPZ:4588140001

DBZ1194 Protective cage

To protect the detector from damage. Can only be used together with the base attachment humid.

Dimensions (Ø x H) 160 x 126 mm

BPZ:4677110001

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

09.fm Seite 19 Mittwoch, 28. Juli 2010 8:51 08

Page 179: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsSpecial DetectorsRadio Fire Detection Wireless System

9-20 © Siemens Switzerland Ltd 2010

Type Order No.

SMF__ Manual call point

Radio manual call point for the radio fire detection system. Manual call point with indirect alarm actuation by breaking the glass and pressing the push button. The radio module is integrated in the base.The base SMF6120 and the manual call point SMF121 must be ordered separately.

Standard EN 54-11

Protection category IP43

Operating temperature -10... + 55 °C

Dimensions (W x H x D) 125 x 125 x 57 mm

Relative humidity L95 % (no condensation)

Color red‚ zRAL 3000

Approval

Data sheet 010087

Products to select from

SMF6120 See Page 9-20

V24069-Z112-A1 See Page 9-20

SMF121 See Page 9-21

SMF121 See Page 9-21

SMF__

SMF6120 Radio base

The radio base is battery-operated and can be mounted at every loca-tion within radio range. The radio base consists of a housing including radio electronics and antennas. The two 3.6 V batteries used are insert-ed here. The batteries must only be inserted in the base during commis-sioning (address allocation).The batteries V24069-Z112-A1 and the manual call point SMF121 must be ordered separately.

Supply voltage 2 x 3.6 V lithium batteries‚ separate-ly monitored

Transmitter/receiver antenna 2 (antenna diversity)

Transmitting power L5 mW ERP

Transmission distance max. 40 m in buildingmax. 200 m in open air

Channel width 25 kHz

Radio frequency 868... 870 MHz (SRD band)

S24218-F72-A1

V24069-Z112-A1 Lithium battery 3.6 V / 2.1 Ah

For the supply of the radio base SMF6120.

Dimensions (Ø x H) 14.5 x 50 mm

V24069-Z112-A1

09.fm Seite 20 Mittwoch, 28. Juli 2010 8:51 08

Page 180: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsSpecial DetectorsRadio Fire Detection Wireless System

9-21© Siemens Switzerland Ltd 2010

9

Type Order No.

SMF121 Manual call point

Manual call point with indirect alarm actuation labeled with Siemens‚ compatible with radio base SMF6120.The radio base SMF6120 must be ordered separately.

V24217-C1218-W200

SMF121 Manual call point

Manual call point with indirect alarm actuation without Siemens label‚ compatible with radio base SMF6120.The radio base SMF6120 must be ordered separately.

V24217-C1218-W100

S24217-G34-A1 Key

The key is used for manual call point SMF121.

Delivery unit 10 pieces

S24217-G34-A1

DZW1171 Radio test set

Field strength measurements can be carried out in the building to ensure reliable planning. Such measurements can be made using the mobile radio test set DZW1171.Position module A at the location of the radio gateway. It is now possi-ble to check the radio contact at the radio smoke detector position by means of module B. As long as the LED on module B lights up‚ the trans-mission of radio signals is ensured.Two 9 V lithium batteries (A5Q00004142) are needed and must be ordered separately.

BPZ:5762200001

A5Q00004142 Lithium brownstone battery 9 V / 1 Ah

For the supply of the detector testers‚ line tester‚ radio smoke detector etc.

Dimensions (W x H x D) 25 x 48 x 16 mm

Delivery unit 10 pieces

A5Q00004142

09.fm Seite 21 Mittwoch, 28. Juli 2010 8:51 08

Page 181: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

+DC 24 V

Explosion-hazard area productsEx product overview

FDCIO223 input/output module “transponder” for the connection of the Ex components to C-NET

SB3 Shunt Zener diode barrier mounted together with installation set Z3I410 in housing DCA1191

Smoke detectorDO1101A-Exwide spectrum

Heat detectorsDT1101A-Ex/DT1102A-Ex

Manual call pointsDM1103/04(Ex)with label “avoid electrostatic charging”

Infrared fl ame detector DF1101-Ex

DB3 Alarm device

Alarm indicator FDAI92-Ex

Non explosion-hazard area

Explosion-hazard area

C-NET

To the sounder output of the fi re control panel

Line termination EOL22(Ex)in last detector

DC1192 input/output module as galvanic isolator between SynoLINE600 and Ex components

SynoLINE600or

+DC 24 V

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 32 28.05.10 16:58

Page 182: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsExplosion-Hazard Area ProductsInterface to C-NET

9-23© Siemens Switzerland Ltd 2010

9

Type Order No.

FDCIO223 Input/output module 'Transponder'

For connection of collective fire detectors (GMT/conventional line‚ GMT/conventional line with shunt Zener diode barrier (SB3) for explo-sion-hazard areas). For monitored controls of e.g. smoke dampers‚ alarm devices‚ door magnets and extinguishing activation devices (adhere to country-specific instructions). Monitored signal input for status and alarm messages or for acknowledging technical status.The 2 input/outputs can be parameterized autonomously in each case as detector line collective‚ contact input‚ control output‚ control output and input as acknowledgement with selectable monitoring time frame. Status indication by LED.Transponder incl. 2 Transzorb diode 20 V‚ 8 resistors and 2 mounting feet for TS35 U-rail.

Power supply External input voltage 18... 32 VDC

Communication protocol FDnet/C-NET

Operating voltage FDnet/C-NET 12... 33 VDC

Detector line collective GMT Siemens/Cerberus‚ Synova conventional/SynoLINE300‚ collective/SynoLINE600 or similar

Control output 24 VDC ± 5 % / 2 A

EOL resistor 3.3 kT/680 T‚ 2.7 kT/560 T‚ 3.3 kT

Cable capacity 0.2... 1.5 mm2 (2.5 mm2)

Operating temperature -25... +60 °C

Storage temperature -30... +65 °C

Relative humidity L95 %

Color white‚ zRAL 9010/transparent matt

Protection category IP30IP65 with aux. housing FDCH221

System compatibility FDnet -> FS20‚ AlgoRex‚ SIGMASYSC-NET -> FS720

Standard CEA GEI I-084‚ EN 54-17‚ EN 54-18

Dimensions (W x H x D) 132 x 90 x 24 mm

Data sheet 009168

Accessories TS35_122 U-railTS35_288 U-railFDCH221 Housing IP65

S24218-B102-A1

Accessories

FDCH221 Housing for input/output modules

Housing with seal for the mounting of the input/output modules for wet applications.The required screwed cable glands and back nuts M20 must be ordered separately.

Dimensions (W x H x D) 207 x 119 x 48 mm

Color white‚ zRAL 9010 / transparent matt

Protection category IP65

Accessories A5Q00004478 Screwed cable gland M20A5Q00004479 Back nut M20

S54312-F3-A1

09.fm Seite 23 Mittwoch, 28. Juli 2010 8:51 08

Page 183: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsExplosion-Hazard Area ProductsInterface to C-NET

9-24 © Siemens Switzerland Ltd 2010

Type Order No.

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

A5Q00004479 Back nut M20

Back nut to screwed cable gland M20 x 1.5.

Delivery unit 10 pieces

A5Q00004479

DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole

As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.

Cable capacity 1... 2.5 mm2

Delivery unit 50 pieces

BPZ:4942340001

EOL22(Ex) Line termination

End-of-line unit for collective detection lines or as end-of-line unit with-in explosion-hazard areas of zones 1 and 2.

BPZ:5162220001

09.fm Seite 24 Mittwoch, 28. Juli 2010 8:51 08

Page 184: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsExplosion-Hazard Area ProductsInterface to Collective Line SynoLINE600

9-25© Siemens Switzerland Ltd 2010

9

Type Order No.

DC1192-I__ Input/output module for galvanic isolation

The input/output module DC1192 for galvanic isolation (detection line coupler) between control unit of collective line SynoLINE600 and e.g. shunt Zener diode barrier with fire detectors for explosion-hazard areas (via SB3).The housing DCA1191‚ the terminal base DCB1192A and the electronic unit DCA1192A must be ordered separately.

Operating temperature -25... +70 °C

Protection category IP56

Data sheet 001571

Products to select from

DCA1191 See Page 9-25

DCB1192A See Page 9-25

DCA1192A See Page 9-25

DC1192-I__

DCA1191 Housing (empty)

Housing with cover for several applications. The housing offers six M20 cable feed-throughs for screwed cable glands and offers a higher pro-tection category.The screwed cable gland must be ordered separately.

Dimensions (W x H x D) 135 x 135 x 65 mm

Color white‚ zRAL 9010

Protection category IP56

Accessories A5Q00004478 Screwed cable gland M20

BPZ:4588560001

DCB1192A Terminal base for DC1192

The terminal base for the auto-addressable input/output module DC1192. The terminal base can be pre-installed together with the hous-ing DCA1191 to save time and money during installation.

Cable capacity 0.2... 2.5 mm2 / AWG 24... 14

Accessories DBZ1190-AA Micro terminal 0.5 mm2

BPZ:5084500001

DCA1192A Electronic unit for DC1192

Electronic unit for DC1192 input/output module is used in the Syno-LOOP fire detection system for the connection of fire detectors with collective/SynoLINE600 address (special detectorsor via shunt Zener diode barriers‚ detectors for explosion-hazard areas) or for the activation of alarm devices. The built-in isolator enables the fire control panel to localize short circuits and open lines. With the auto-addressable feature‚ no dip switch or punch card settings have to be made. The electronic unit is plugged into the housing just before com-missioning.The line termination elements are also included in the packaging.

Detection line current max. 5 mA

Detection line voltage 18... 22 VDC

Operating current control line max. 2 A‚ 60 W

Operating voltage external 18... 32 VDC

Quiescent current L45 mA

BPZ:5081200001

09.fm Seite 25 Mittwoch, 28. Juli 2010 8:51 08

Page 185: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsExplosion-Hazard Area ProductsInterface to Collective Line SynoLINE600

9-26 © Siemens Switzerland Ltd 2010

Type Order No.

EOL22(Ex) Line termination

End-of-line unit for collective detection lines or as end-of-line unit with-in explosion-hazard areas of zones 1 and 2.

BPZ:5162220001

Accessories

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

DBZ1190-AA Micro terminal 0.5 mm2‚ 4-pole

As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.

Cable capacity 0.28... 0.5 mm2

Delivery unit 50 pieces

BPZ:4677080001

09.fm Seite 26 Mittwoch, 28. Juli 2010 8:51 08

Page 186: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsExplosion-Hazard Area ProductsEx-Barrier

9-27© Siemens Switzerland Ltd 2010

9

Type Order No.

SB3 Shunt Zener diode barrier

This barrier is needed for an intrinsically safe installation in explosion-hazard areas connected to the in-/output module. This barrier restricts the electrical energy between non-intrinsically safe and intrinsically safe circuits. The installation has to be done according to the national safety regulations. The SB3 has to be mounted into the housing DCA1191 together with the Z3I410 installation set.Always install shunt Zener diode barriers outside explosion-hazard areas.

Operating voltage max. 28 VDC

Operating current max. 100 mA

Type Stahl 9001/00-280-100-101

Standard EN 50014 (IEC60079-0)/EN 50020 (IEC60079-11)

Data sheet 001222

BPZ:4837400001

DCA1191 Housing (empty)

Housing with cover for several applications. The housing offers six M20 cable feed-throughs for screwed cable glands and offers a higher pro-tection category.The screwed cable gland must be ordered separately.

Dimensions (W x H x D) 135 x 135 x 65 mm

Color white‚ zRAL 9010

Protection category IP56

Accessories A5Q00004478 Screwed cable gland M20

BPZ:4588560001

Z3I410 Installation set

One SB3 shunt Zener diode barrier may be mounted together with sup-port plate Z3I410 in housing DCA1191 with protection category IP56.

BPZ:4837660001

DBZ1190-AA Micro terminal 0.5 mm2‚ 4-pole

As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.

Cable capacity 0.28... 0.5 mm2

Delivery unit 50 pieces

BPZ:4677080001

Accessories

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

09.fm Seite 27 Mittwoch, 28. Juli 2010 8:51 08

Page 187: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsExplosion-Hazard Area ProductsPoint Detectors Ex-Series

9-28 © Siemens Switzerland Ltd 2010

Type Order No.

DO1101A-Ex Smoke detector‚ wide spectrum collective 'Ex'

For the early warning of smoke-forming‚ flaming fires and smoldering fires in explosion-hazard areas of zones 1 and 2.The base DB1101A must be ordered separately.

Operating voltage 17... 24 VDC

Quiescent current max. 100 μA

Operating temperature -25... +60 °C

Storage temperature -30... +75 °C

Relative humidity L95 %

Ex-classification II 2 G Ex ib IIC T4(-25 °C LTa L60 °C)

Dimensions (Ø x H) 115 x 51 mm (incl. base)

Color white‚ zRAL 9010

Standard for fire detectors EN54-7for explosion-hazard areasEN 50014 (IEC60079-0)/EN 50020 (IEC60079-11)

Protection category IP44

Data sheet 001469

BPZ:5008010001

DT1101A-Ex Heat detector collective 'Ex'

For the monitoring of explosion-hazard areas of zones 1 and 2 with a maximum ambient temperature of 50 °C. It is characterized by reliable response behavior‚ not only in the event of slow temperature rises‚ but also where the temperature rises are fast.The base DB1101A must be ordered separately.

Operating voltage 16... 24 VDC

Quiescent current max. 100 NA

Operating temperature -25... +50 °C

Storage temperature -30... +75 °C

Relative humidity L95 %

Ex-classification II 2 G Ex ib IIC T4(-25 °C LTa L50 °C)

Dimensions (Ø x H) 115 x 54.5 mm (incl. base)

Color white‚ zRAL 9010

Standard for fire detectors EN 54-5: A1Rfor explosion-hazard areasEN 50014 (IEC60079-0)/EN 50020 (IEC60079-11)

Protection category IP44

Data sheet 001469

BPZ:4852140001

09.fm Seite 28 Mittwoch, 28. Juli 2010 8:51 08

Page 188: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsExplosion-Hazard Area ProductsPoint Detectors Ex-Series

9-29© Siemens Switzerland Ltd 2010

9

Type Order No.

DT1102A-Ex Heat detector collective 'Ex'

For the monitoring of explosion-hazard areas of zones 1 and 2 with a maximum ambient temperature of 70 °C. It is the right heat detector for locations where large temperature fluctuations and high temperatures occur. It continuously measures the ambient temperature and reacts if defined maximum values are exceeded.The base DB1101A must be ordered separately.

Operating voltage 16... 24 VDC

Quiescent current max. 100 NA

Operating temperature -25... +70 °C

Storage temperature -30... +75 °C

Relative humidity L95 %

Ex-classification II 2 G Ex ib IIC T4(-25 °C LTa L70 °C)

Dimensions (Ø x H) 115 x 54.5 mm (incl. base)

Color white‚ zRAL 9010

Standard for fire detectors EN54-5: Bfor explosion-hazard areasEN 50014 (IEC60079-0)/EN 50020 (IEC60079-11)

Protection category IP44

Data sheet 001469

BPZ:4852270001

DB1101A Base for collective detector series

Base made of impact and scratch-proof plastic and environmentally safe materials. Integral rubber gasket to protect against draught‚ dirt and dripping water from above. Screwless terminals for easy installa-tion. Space for auxiliary terminals as micro terminals (0.5 mm2) and connection terminals (2.5 mm2). Fits all standard flush-mounted boxes from 55 to 80 mm.

Cable capacity 0.2... 2.5 mm2

Dimensions (Ø x H) 115 x 21 mm

Color white‚ zRAL 9010

Data sheet 001035

Further accessories DBZ1191 Base attachment for sur-face mountingDBZ1190-AA Micro terminal 0.5 mm2

DBZ1190-AB Connection terminal 2.5 mm2

BPZ:4863650001

Accessories

DBZ1191 Base attachment for surface mounting

For surface wiring feed and provision of more wire loop space. Bases are mounted using a spring-loaded catch.

Dimensions (Ø x H) 116 x 22 mm

Color white‚ zRAL 9010

Delivery unit 5 pieces

BPZ:4540830001

09.fm Seite 29 Mittwoch, 28. Juli 2010 8:51 08

Page 189: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsExplosion-Hazard Area ProductsPoint Detectors Ex-Series

9-30 © Siemens Switzerland Ltd 2010

Type Order No.

DBZ1190-AA Micro terminal 0.5 mm2‚ 4-pole

As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.

Cable capacity 0.28... 0.5 mm2

Delivery unit 50 pieces

BPZ:4677080001

DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole

As cross-connection in bases for external alarm indicators (AI)‚ cable shielding‚ for the connection of a power supply unit or other compo-nents.Can easily be inserted.

Cable capacity 1... 2.5 mm2

Delivery unit 50 pieces

BPZ:4942340001

09.fm Seite 30 Mittwoch, 28. Juli 2010 8:51 08

Page 190: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsExplosion-Hazard Area ProductsInfrared Flame Detector Ex-Series

9-31© Siemens Switzerland Ltd 2010

9

Type Order No.

DF11Ex__ Infrared flame detector collective 'Ex'

Connectable to collective systems. Connection to the detection line via the input/output module for galvanic isolation. Infrared flame detector for explosion-hazard areas of zones 1 and 2‚ for inside and outside applications.The Stabex HF test lamp is used to make a performance check of the infrared flame detector. It must be held in front of the detector.The detector unit DF1101-Ex and the base DFB1190 must be ordered separately.

Dimensions (W x H x D) 135 x 135 x 77 mm

Operating temperature -35... +70 °C

Storage temperature -40... +75 °C

Relative humidity L95 %

Ex-classification II 2 G Ex ib IIC T4(-35 °C LTa L70 °C)

Color white‚ zRAL 9010

Standard EN 54-10 for flame detectorEN 50014 (IEC60079-0)/EN 50020 (IEC60079-11)for explosion-hazard areas

Protection category IP67

Data sheet 001744

Products to select from

DF1101-Ex See Page 9-31

DFB1190 See Page 9-32

DF11Ex__

DF1101-Ex Infrared flame detector unit collective 'Ex'

Flame detector DF1101-Ex intrinsically safe for Ex-protected areas. The infrared flame detector DF1101-Ex is designed to the explosion protec-tion category 'Intrinsic safety' Ex i.One sensor measures the hot carbon dioxide in a specific flame wave-length; the two other sensors simultaneously measure the interference radiation in other wavelengths. With intelligent signal processing through fuzzy algorithms and wavelet analysis‚ the DF1101-Ex achieves excellent detection reliability while maintaining the highest immunity to interference radiation and sunlight. In order to safeguard against a possible decision emergency‚ the detector contains an additional emer-gency activation channel.It is suitable for chemical production plants‚ oil refineries‚ propane and butane filling installations‚ for all explosion-hazard areas in which flam-ing fires involving carbonaceous materials could be expected.The base DFB1190 must be ordered separately.

Dimensions (W x H x D) 135 x 135 x 32 mm

Operating voltage 16... 28 VDC

Quiescent current 0.5 mA

BPZ:5166750001

09.fm Seite 31 Mittwoch, 28. Juli 2010 8:51 08

Page 191: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsExplosion-Hazard Area ProductsInfrared Flame Detector Ex-Series

9-32 © Siemens Switzerland Ltd 2010

Type Order No.

DFB1190 Base for infrared flame detectors DF119x

The base comprises a robust‚ glass fiber-reinforced‚ plastic housing which provides the required isolated installation of the detector. The base contains screwless terminals‚ chokes to protect against EMI‚ a plug attachment for the detector‚ six M20 cable entry possibilities.

Cable capacity 0.2... 1.5 mm2 (AWG24... 15)

Dimensions (W x H x D) 135 x 135 x 45 mm

Color white‚ zRAL 9010

Accessories A5Q00004478 Screwed cable gland M20

BPZ:5165360001

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

StabexHF Test lamp for flame detectors 'Ex'

The test lamp is used to carry out a performance check of intrinsically safe flame detectors in explosion-hazard areas of zones 1 and 2.

Operating temperature -20... +40 °C

Storage temperature -20... +40 °C

Battery capacity 2 x Alkali battery 1.5 V‚ single-cell UM1

Ex-classification II 2 G Ex ib e IIC T4

Protection category IP65

Data sheet AlgoRex‚ Synova‚ Sinteso -> 000252Cerberus PRO -> A6V10203222

BPZ:4620910001

09.fm Seite 32 Mittwoch, 28. Juli 2010 8:51 08

Page 192: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsExplosion-Hazard Area ProductsManual Call Points

9-33© Siemens Switzerland Ltd 2010

9

Type Order No.

DM1103(Ex)__ Collective manual call point (double action) for explosion-hazard areas

For immediate manual actuation of an alarm. For indoor and outdoor application‚ equally suited for wet‚ humid and dusty areas. For surface- and recess-mounted feed lines in easily accessible places.Indirect alarm actuation by pushing in the glass plate and pressing the push button. To replace the glass plate‚ open the housing door with the key. The push button must be reset before closing the door again.The housing DMA1192-AA and the switching unit DMA1103D must be ordered separately.

Standard EN54-11

Protection category IP54 (IP65 with protection seal and screwed cable gland)

Operating temperature -25... +70 °C

Dimensions (W x H x D) 134 x 134 x 43 mm

Data sheet A6V10236643

Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20A5Q00006735 Locking plug M20(1 hole)A5Q00010055 Locking plug M20(2 holes)

Products to select from

DMA1192-AA See Page 9-33

DMA1103D See Page 9-33

DM1103(Ex)__

DMA1192-AA Housing red‚ with glass and key

Manual call point housing for the switching units DMA110xD.

Color red‚ zRAL 3000

BPZ:5222870001

DMA1103D Switching unit collective (double action)

The electronic unit is a double action device; just break the glass and press the button to activate an alarm. For connection to collec-tive/SynoLINE600 detection lines. An LED always indicates the status of the manual call point. The electronic unit is plugged into the housing during commissioning.Attach the enclosed sticker 'avoid electrostatic charging' when the switching unit is used in explosion-hazard areas only.

Operating voltage 16... 26 VDC

Operating current 60... 100 mA

Terminal block min. 0.28... 1.5 mm2

A5Q00004470

09.fm Seite 33 Mittwoch, 28. Juli 2010 8:51 08

Page 193: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsExplosion-Hazard Area ProductsManual Call Points

9-34 © Siemens Switzerland Ltd 2010

Type Order No.

DM1104(Ex)__ Collective manual call point (single action) for explosion-hazard areas

For immediate manual actuation of an alarm. For indoor and outdoor application‚ equally suited for wet‚ humid and dusty areas. For surface- and recess-mounted feed lines in easily accessible places.Direct alarm actuation by pushing in the glass plate. To replace the glass plate‚ open the housing door with the key‚ upon closing the door the button is reset.The housing DMA1192-AA and the switching unit DMA1104D must be ordered separately.

Standard EN 54-11

Protection category IP54 (IP65 with protection seal and screwed cable gland)

Operating temperature -25... +70 °C

Dimensions (W x H x D) 134 x 134 x 43 mm

Data sheet A6V10236643

Accessories DMZ1197-AD Protection sealDMZ1197-AC Protective coverA5Q00004478 Screwed cable gland M20A5Q00006735 Locking plug M20(1 hole)A5Q00010055 Locking plug M20(2 holes)

Products to select from

DMA1192-AA See Page 9-34

DMA1104D See Page 9-34

DM1104(Ex)__

DMA1192-AA Housing red‚ with glass and key

Manual call point housing for the switching units DMA110xD.

Color red‚ zRAL 3000

BPZ:5222870001

DMA1104D Switching unit collective (single action)

The electronic unit is a single action device by smashing in the glass plate to activate an alarm. For connection to collective/SynoLINE600 detection lines. An LED always indicates the status of the manual call point. The electronic unit is plugged into the housing during commis-sioning.Attach the enclosed sticker 'avoid electrostatic charging' when the switching unit is used in explosion-hazard areas only.

Operating voltage 16... 26 VDC

Operating current 60... 100 mA

Terminal block min. 0.28... 1.5 mm2

A5Q00005925

09.fm Seite 34 Mittwoch, 28. Juli 2010 8:51 08

Page 194: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsExplosion-Hazard Area ProductsManual Call Points

9-35© Siemens Switzerland Ltd 2010

9

Type Order No.

Accessories

DMZ1197-AD Protection seal

Protects the manual call point in wet applications.The seal improves the manual call point housing's protection category.

Delivery unit 5 pieces

BPZ:5470680001

DMZ1197-AC Protective cover

Protects the manual call point from unintentional glass break. Protec-tive cover can be easily fitted directly in the housing cover.

Delivery unit 5 pieces

BPZ:5223550001

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

A5Q00006735 Locking plug M20 x 1.5 (1 hole)

For manual call point housings and surface-mounted feed lines in the manual call point housing.For applications in dry rooms.

Color red‚ zRAL 3000

Delivery unit 10 pieces

A5Q00006735

A5Q00010055 Locking plug M20 x 1.5 (2 holes)

For manual call point housings and surface-mounted feed lines in the manual call point housing.For applications in dry rooms.

Color red‚ zRAL 3000

Delivery unit 10 pieces

A5Q00010055

09.fm Seite 35 Mittwoch, 28. Juli 2010 8:51 08

Page 195: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsExplosion-Hazard Area ProductsAlarm Indicators Ex-Series

9-36 © Siemens Switzerland Ltd 2010

Type Order No.

FDAI92-Ex Alarm indicator - Surface for explosion-hazard areas

The alarm indicator is connected in parallel to automatic fire detectors in order to indicate quickly the source of an alarm signal from detectors that are not easily accessible or visible. The alarm indicator contains an indicator lamp unit with one or two LEDs. They light up as soon as a connected fire detector gives an alarm.Screwless connection terminals.The alarm indicator is suitable for wall mounting.

Operating voltage 1.5 VDC

Operating current max. 35 mA (continuous)

Operating temperature -25... +80 °C

Relative humidity L95 %

Terminals max. 1.5 mm2

Ex-classification 'simple apparatus'acc. to EN 50020 § 5.4Ex ib IIC T4 (Ta L70 °C)

Dimensions (W x H x D) 85 x 85 x 28 mm

Color white‚ zRAL 9010

Protection category IP40

Data sheet A6V10276518

Accessories AI330 Adapter frame

S54370-F4-A1

AI330 Adapter frame for alarm indicator

By means of the additional frame‚ the alarm indicator can also be used for surface laid conduits or ducts‚ to increase the loop space and as an adapter for different makes of the box.

Dimensions (W x H x D) 85 x 85 x 16 mm

BPZ:3169430001

FDAI93-Ex Alarm indicator - Flush

Made of transparent plastic‚ the FDAI93-Ex alarm indicator is suitable for installation in door frames‚ switching panels‚ ceiling voids or special housings. The 22.5 mm Ø mounting hole is drilled by the system own-er. The holder must be fitted with the insulating cap for safety. For installation in humid rooms the DCA1191‚ DJZ1193 housings as well as a washer are available (must be ordered separately). Up to 4 alarm indi-cators can be built into the housing DCA1191.

Operating voltage 1.5 VDC

Operating current max. 20… 30 mA (continuous)

Operating temperature -25... +80 °C

Ex-classification 'simple apparatus'acc. to EN 50020 § 5.4Ex ib IIC T4 (Ta L70 °C)

Color transparent plastic

Dimensions (Ø x D) 26 x 51 mm

Protection category IP56 with DCA1191IP65 with DJZ1193

Data sheet A6V10276518

Accessories DCA1191 Housing (IP56)BPZ:2473130001 Washer

Further accessories DJZ1193 Housing (IP65)

S54370-F6-A1

09.fm Seite 36 Mittwoch, 28. Juli 2010 8:51 08

Page 196: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsExplosion-Hazard Area ProductsAlarm Indicators Ex-Series

9-37© Siemens Switzerland Ltd 2010

9

Type Order No.

DCA1191 Housing (empty)

Housing with cover for several applications. The housing offers six M20 cable feed-throughs for screwed cable glands and offers a higher pro-tection category.The screwed cable gland must be ordered separately.

Dimensions (W x H x D) 135 x 135 x 65 mm

Color white‚ zRAL 9010

Protection category IP56

Accessories A5Q00004478 Screwed cable gland M20

BPZ:4588560001

BPZ:2473130001 Washer

Washer for alarm indicator model recess mounting. The washer can be used for applications in humid rooms.

Dimensions (Ø x D) 23 x 1 mm

BPZ:2473130001

A5Q00004478 Screwed cable gland M20 x 1.5

The screwed cable gland is for M20 cable feed-through. It enables high-er protection category.

Delivery unit 10 pieces

A5Q00004478

DJZ1193 Alarm indicator housing incl. washer

For surface mounting in wet areas.1 alarm indicator can be built into the housing.

Dimensions (W x H x D) 87 x 87 x 64 mm

Color white‚ zRAL 9010

Protection category IP65

BPZ:5302950001

MVH1 Mounting bracket

For mounting of the alarm indicator housing DJZ1193 and detectors in hollow floors.

Length 0.29... 0.42 m (pipe clamp 1/2")

BPZ:3496190001

09.fm Seite 37 Mittwoch, 28. Juli 2010 8:51 08

Page 197: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special ApplicationsExplosion-Hazard Area ProductsAlarm Device

9-38 © Siemens Switzerland Ltd 2010

Type Order No.

DB3 Alarm device for explosion-hazard areas of zones 1 and 2

The flameproof audible alarm device is intended for the use in poten-tially explosive atmospheres. It has been designed with high ingress protection to cope with harsh environmental conditions.

Operating voltage 12... 48 VDC

Alarm current max. 380 mA

Volume at 24 V and 1 m 101... 115 dB

Number of sounds 27

Operating temperature -20... +55 °C

Ex-classification II 2 G Ex d IIC T5(-20 °C LTa L55 °C)

Terminals 6 x 2.5 mm2

Dimensions (Ø x D) 137 x 184 mm

Color red‚ anti-static‚ UV stable‚ glass rein-forced polyester

Standard CENELEC‚ EN 50014‚ 18

Protection category IP66/67

Data sheet 009001

BPZ:5757970001

09.fm Seite 38 Mittwoch, 28. Juli 2010 8:51 08

Page 198: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special Equipment

Cutting-edge technology – for all security and safety needsFire and security products from Siemens are the obvious choice because they are continually setting new standards in terms of quality, design, reli-ability, value for money and availability. For more than 150 years now we have been developing solutions for all types of problems, applications and needs, from fi re detection through to alert and evacuation systems, consist-ing of everything from simple conventional systems to complex addressable networks. Over the years, our products and components have passed every test to which they have been subjected with fl ying colors.

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 34 28.05.10 16:58

Page 199: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special EquipmentTest EquipmentDetector Tester

10-2 © Siemens Switzerland Ltd 2010

Type Order No.

DX791 Detector exchanger

Insertion and removal of all Cerberus PRO point detectors. Equipped with a vacuum cup for insertion and removal of dust cap.Compatible with the telescope rods FDUM291/292.

Data sheet A6V10203222

Accessories FDUM291 Telescope rodFDUM292 Telescope rod

S54319-F6-A1

RE6 Detector tester for smoke detectors

The detector tester (delivered with bellow DZZ1190) is placed over the detector and given a brief push to release the test gas and so simulate the presence of fire aerosols. The detector responds quickly and actu-ates an alarm. The test gas is free of halogenated chlorofluorocarbons (CFCs). It is not combustible.The extension rod FDUM291/292 and the test gas can REF8‚ REF8-S must be ordered separately.

Data sheet AlgoRex‚ Synova -> 001164Sinteso -> 007228Cerberus PRO -> A6V10203222

Accessories FDUM291 Telescope rodFDUM292 Telescope rod

Further accessories RG320 Bellow

BPZ:3680300001

REF8 Test gas can for smoke detectors

REF8 has been developed as an environment-friendly test gas for the testing of smoke detectors. It fulfills severe environmental regulations. REF8 can be used in the temperature range of 0... +40 °C in dry or in humid environments.Use only together with detector tester RE6.

Delivery unit 6 pieces

A5Q00011687

REF8-S Test gas can for smoke detectors

REF8-S has been developed as environment-friendly test gas for the testing of smoke detectors. It fulfills severe environmental regulations. REF8-S can be used in the temperature range of -20... +40 °C in dry or in humid environments. REF8-S remains measurable longer than REF8‚ and is used for detectors having a longer signal evaluation time.Use only together with detector tester RE6.

Delivery unit 6 pieces

A5Q00011688

10.fm Seite 2 Mittwoch, 28. Juli 2010 8:54 08

Page 200: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special EquipmentTest EquipmentDetector Tester

10-3© Siemens Switzerland Ltd 2010

10

Type Order No.

RG320 Bellow for RE6

The bellow is fitted to the RE6 to fit all SynoLINE300 point detectors in an ideal way.

BPZ:5166880001

RE6T Detector tester for heat detectors

This detector tester contains a hot air generator. For the performance check‚ the tester is pushed over the detector. The hot air released‚ heats the detector and so actuates an alarm.Forbidden in electrical switching stations or areas where there is a danger of explosion!The extension rod FDUM291/292 must be ordered separately.

Mains voltage 220 VAC/50… 60 Hz‚ z300 W

Operating temperature 0… +40 °C

Data sheet AlgoRex‚ Synova -> 001164Sinteso -> 007228Cerberus PRO -> A6V10203222

Accessories FDUM291 Telescope rodFDUM292 Telescope rod

BPZ:3680270001

RE7T Solo461 Heat detector tester kit

The detector tester contains a hot air generator and is battery-powered. The detector tester will automatically start testing when infrared beam in cup is broken.Forbidden in electrical switching stations or areas where there is a danger of explosion!The adapter RE7T-A and the extension rod FDUM291/292 must be ordered separately.

Relative humidity L95 %

Operating temperature 5... +45 °C

Storage temperature -10… +50 °C

Data sheet A6V10252901

Accessories RE7T-A Solo719 Adapter for FDUM29xFDUM291 Telescope rodFDUM292 Telescope rod

S54370-S3-A1

10.fm Seite 3 Mittwoch, 28. Juli 2010 8:54 08

Page 201: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special EquipmentTest EquipmentDetector Tester

10-4 © Siemens Switzerland Ltd 2010

Type Order No.

Accessories

RE7T-A Solo719 Adapter for FDUM29x

Adapter from heat detector tester RE7T to the telescope rods FDUM29x.

Data sheet A6V10252901

S54370-N4-A1

Accessories

FDUM291 Telescope rod

The three-part telescope with tri-oval tubes serves as an extension for the detector exchanger‚ detector testers and other applications up to 5 m.

Length 1.6 m extendable to 4.2 m

Color yellow‚ black

A5Q00004996

10.fm Seite 4 Mittwoch, 28. Juli 2010 8:54 08

Page 202: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special EquipmentTest EquipmentDetector Tester

10-5© Siemens Switzerland Ltd 2010

10

Type Order No.

FDUM292 Telescope rod

The stable‚ four-part telescope with round tubes serves as an extension for the detector exchanger‚ detector testers and other applications up to 8 m.

Length 2.1 m extendable to 7.3 m

Color yellow‚ black

A5Q00004997

DZB1191 Detector base tester

The DB1191 base tester is handy and simple means of testing the detection line and detector base connections. The base tester is insert-ed in the detector base like a detector. All AlgoRex DS11 bases can be tested during installation either individually or consecutively after installation is completed.The DBZ1191 can test for open lines‚ short circuit‚ earth leakages‚ polar-ity and alarm indicator connection.

Data sheet 001049

BPZ:4680660001

10.fm Seite 5 Mittwoch, 28. Juli 2010 8:54 08

Page 203: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special EquipmentTest EquipmentDetector Tester for Special Detectors

10-6 © Siemens Switzerland Ltd 2010

Type Order No.

LE3 Test lamp for flame detectors

The test lamp is used for testing the operation of all flame detectors (non explosion-hazard areas). It is supplied with all the necessary acces-sories in a suitable carrying case (incl. charger‚ without battery). The carrying case also provides a means of storing the test lamp free of dust.The battery FA2003-A1 must be ordered separately.

Operating temperature -20... +45 °C

Storage temperature -20... +45 °C

Battery capacity 1 x 12 V / 7 Ah

Data sheet AlgoRex‚ Synova‚ Sinteso -> 000252Cerberus PRO -> A6V10203222

BPZ:3669510001

StabexHF Test lamp for flame detectors 'Ex'

The test lamp is used to carry out a performance check of intrinsically safe flame detectors in explosion-hazard areas of zones 1 and 2.

Operating temperature -20... +40 °C

Storage temperature -20... +40 °C

Battery capacity 2 x Alkali battery 1.5 V‚ single-cell UM1

Ex-classification II 2 G Ex ib e IIC T4

Protection category IP65

Data sheet AlgoRex‚ Synova‚ Sinteso -> 000252Cerberus PRO -> A6V10203222

BPZ:4620910001

FDLU291 Adjustment device set for linear smoke detector

The optics of the linear smoke detector can be efficiently adjusted to the reflector by single-handed alignment via the adjustment device.Box with adjustment device‚ alarm test filter‚ visor‚ magnet‚ spiral cable‚ MC-Link cable‚ and battery 9 V‚ 0.5 Ah.

A5Q00004905

RE10 Detector tester for linear smoke detectors

For performance check of linear smoke detector. In compliance with the type of detector to be tested‚ the alarm test filter is inserted in the detector tester.The detector tester is then held in front of the optical parts of the detec-tor (i.e. into the infrared ray). The detector reacts after a few seconds.Alarm test filter contained in FDLU291 or TF04 must be ordered sepa-rately.

Data sheet Synova‚ AlgoRex -> 001164Sinteso -> 007228Cerberus PRO -> A6V10203222

Accessories TF04 Alarm test filterFDUM291 Telescope rodFDUM292 Telescope rod

BPZ:3685190001

10.fm Seite 6 Mittwoch, 28. Juli 2010 8:54 08

Page 204: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special EquipmentTest EquipmentDetector Tester for Special Detectors

10-7© Siemens Switzerland Ltd 2010

10

Type Order No.

TF04 Alarm test filter (Absorption 77 %)

Alarm test filter for detector tester RE10.

BPZ:4931090001

10.fm Seite 7 Mittwoch, 28. Juli 2010 8:54 08

Page 205: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special EquipmentTest EquipmentLine Tester

10-8 © Siemens Switzerland Ltd 2010

Type Order No.

FDUL221 Line tester

The line tester is a universal device for the testing of installed FDnet/C-NET fire detection lines‚ when no control unit has been connected yet. For troubleshooting for electricians‚ installers or service technicians.Different functions can be polled‚ e.g. number of devices found‚ number and place of line errors found‚ short circuit‚ open line‚ ground fault with conductor(s)‚ scrolling from detector to detector‚ with indica-tion of type and serial number etc. Update of the device software (Firmware) via PC possible.Power supply via battery or mains adapter.Line tester incl. line connection set FDUL221-A and power supply set FDUL221-B.

Operating voltage min. 10‚ max. 30 VDCBattery 2 x 9 VMains adapter 240 VAC / 24 VDC‚ 624 mA

Detection line voltage 32 VDC -> FDnet (FS20‚ AlgoRex)28 VDC -> FDnet (SIGMASYS)32 VDC -> C-NET (FS720)

Current consumption depending on number of devices and display illumination

Operating temperature -25... +40 °C

Storage temperature -30... +75 °C(-25... +60 °C with battery)

Relative humidity L95 % (no condensation)

Data sheet Sinteso -> 007228Cerberus PRO -> A6V10203222

A5Q00004397

A5Q00004142 Lithium brownstone battery 9 V / 1 Ah

For the supply of the detector testers‚ line tester‚ radio smoke detector etc.

Dimensions (W x H x D) 25 x 48 x 16 mm

Delivery unit 10 pieces

A5Q00004142

10.fm Seite 8 Mittwoch, 28. Juli 2010 8:54 08

Page 206: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Special EquipmentInterfaceAdapter for C-NET Devices

10-9© Siemens Switzerland Ltd 2010

10

Type Order No.

FDUZ221 MCL USB adapter

The MCL USB adapter is an interface converter for USB to MC-Link. It can be used to connect FDnet/C-NET devices to a PC using a serial protocol (MCL). The adapter is used for the firmware update or for operation. The adapter is used e.g. for floor repeater display FT2010-A1‚ floor repeater terminal FT2010-A1‚ line tester FDUL221 etc. (in the future other FDnet/C-NET devices possible).The MC-Link cable‚ the USB cable (1.8 m) and a CD with USB driver soft-ware are included.

Power supply via USB

Interface USB 2.0/1.1MC-Link

Operating temperature -10… +55 °C

Storage temperature -20… +60 °C

Relative humidity L95 %

Dimensions (W x H x D) 100 x 30 x 54 mm

Protection category IP30

Data sheet Sinteso -> A6V10084591Cerberus PRO -> A6V10203222

A5Q00020131

10.fm Seite 9 Mittwoch, 28. Juli 2010 8:54 08

Page 207: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

081031_Product_Catalog_Innen_07lay.indd 34 24.07.09 18:11

Page 208: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Batteries

11-1© Siemens Switzerland Ltd 2010

11

Type Order No.

FA2003-A1 Battery (12 V‚ 7 Ah‚ VDS)

Rechargeable‚ sealed lead-acid battery for emergency power supply.2 batteries must be ordered (system voltage 24 V).

Dimensions (W x H x D) 151 x 94 x 65 mm

A5Q00019353

FA2004-A1 Battery (12 V‚ 12 Ah‚ VDS)

Rechargeable‚ sealed lead-acid battery for emergency power supply.2 batteries must be ordered (system voltage 24 V).

Dimensions (W x H x D) 151 x 95 x 98 mm

A5Q00019354

FA2005-A1 Battery (12 V‚ 17 Ah‚ VDS)

Rechargeable‚ sealed lead-acid battery for emergency power supply.2 batteries must be ordered (system voltage 24 V).

Dimensions (W x H x D) 181 x 167 x 77 mm

A5Q00019677

FA2006-A1 Battery (12 V‚ 26 Ah‚ VDS)

Rechargeable‚ sealed lead-acid battery for emergency power supply.2 batteries must be ordered (system voltage 24 V).

Dimensions (W x H x D) 166 x 125 x 177 mm

A5Q00019356

FA2007-A1 Battery (12 V‚ 45 Ah‚ VDS)

Rechargeable‚ sealed lead-acid battery for emergency power supply.2 batteries must be ordered (system voltage 24 V).

Dimensions (W x H x D) 197 x 170 x 165 mm

A5Q00022897

11.fm Seite 1 Mittwoch, 28. Juli 2010 8:58 08

Page 209: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Batteries

11-2 © Siemens Switzerland Ltd 2010

Type Order No.

FA2008-A1 Battery (12 V‚ 65 Ah‚ VDS)

Rechargeable‚ sealed lead-acid battery for emergency power supply.2 batteries must be ordered (system voltage 24 V).

Dimensions (W x H x D) 348 x 178 x 167 mm

A5Q00019357

FA2009-A1 Battery (12 V‚ 100 Ah‚ VDS)

Rechargeable sealed lead-acid battery for emergency power supply.2 batteries must be ordered (system voltage 24 V).

Dimensions (W x H x D) 305 x 212 x 168 mm

A5Q00023101

11.fm Seite 2 Mittwoch, 28. Juli 2010 8:58 08

Page 210: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Spare PartsFire Control Panels FC72x and Operating Terminals FT724‚ Printers

12-1© Siemens Switzerland Ltd 2010

12

Type Order No.

SV 24V-150W Power supply (150 W)

Power supply (150 W) without accessories.Use as spare part.

V24230-Z6-A4

FHA7201-A3 Cover cap (Cerberus)

Cover with Cerberus label.Use as spare part only.

S54400-B77-A1

FHA7202-A3 Cover cap (without print)

Cover without print.Use as spare part only.

S54400-B74-A1

FCM7210-Z3 Operating add-on

Operating add-on (complete base) without accessories.Use as spare part only.

S54400-F76-A1

FCM7211-Y3 Operating add-on (2xLED ind.)

To update 48 LED display groups‚ with one red and one yellow LED each.Can be inserted in all empty housings.Inclusive cables and screws for installation.

Dimensions (W x H x D) 427 x 200 x 25 mm

S54400-F75-A1

12.fm Seite 1 Mittwoch, 28. Juli 2010 8:59 08

Page 211: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Spare PartsFire Control Panels FC72x and Operating Terminals FT724‚ Printers

12-2 © Siemens Switzerland Ltd 2010

Type Order No.

FCM7212-Y3 Operating add-on (4xLED ind.)

To update 96 LED display groups‚ with one red and one yellow LED each.Can be inserted in all empty housings.Inclusive cables and screws for installation.

Dimensions (W x H x D) 427 x 200 x 25 mm

S54400-F88-A1

A5Q00017619 Thermo printer rolls for Custom Plus-S-0004

Replacement printer rolls (10 rolls) for event printer FTO2001-A1.Use as spare part.

Delivery unit 10 pieces

A5Q00017619

A5Q00023963 Typewriter ribbon

Genuine Fujitsu CA02374-C104 black fabric impact printer ribbon designed for the Fujitsu DL3750+ matrix printer.

Color black

A5Q00023963

12.fm Seite 2 Mittwoch, 28. Juli 2010 8:59 08

Page 212: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Spare PartsConventional Fire Control Panels FC10

12-3© Siemens Switzerland Ltd 2010

12

Type Order No.

FCA1001 Line extension card 4-zones A6E60500020

FCA1007-B Add-on line card

To provide line continuity with diode bases according to British Stand-ard BS5839 Pt1. One unit per 2 lines.Use as spare part.

A6E60500027

FCA1009-E EVAC module

Evacuation control module. Mounts on FC1008-E.

S54380-B11-A1

FCA1013 Universal accessory bag

Consists of:2 EOL (FCE1002) for sounder control lines12 EOL resistors 3.9 kT3 cable binder1 LED diffuser base (16 pins)1 LED diffuser base (1 pin)1 Allen key 3 mm for M4 screws5 eco-fix screws M3x54 Allen screws M4x124 stainless Allen screws M4x124 O-ring 2.90 x 1.783 fuses (315 mA‚ 630 mA‚160 mA)6 mini jumpers 2.54 mm

Accessories FCE1003-B EOL elementFCE1004-F EOL element

A6E60500068

FCE1001 EOL resistor 3.9 kT (set of 10 pcs.) A6E60500031

FCE1003-B EOL element for head removal monitoring A6E60500033

FCE1002 Termination element‚ control line

End-of-line for sounder control lines‚ as spare part.

A6E60500032

FCH1002 Cover for the FC1002-A‚ -B‚ -C

A6E60500035

FCH1004 Cover for the FC1004-A‚ -B‚ -C

A6E60500036

12.fm Seite 3 Mittwoch, 28. Juli 2010 8:59 08

Page 213: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Spare PartsConventional Fire Control Panels FC10

12-4 © Siemens Switzerland Ltd 2010

Type Order No.

FCH1004-E Cover for the FC1004-E

A6E60500037

FCH1008 Cover for the FC1008-A‚ -B‚ -C

A6E60500038

FCH1008-D Cover for the FC1008-D A6E60500039

FCH1008-E Cover for the FC1008-E S54380-F10-A1

FCH1012 Cover for the FC1012-A‚ -B‚ -C

A6E60500043

FCM1002 Main board 2-zones S54380-C8-A1

FCM1004 Main board 4-zones S54380-C9-A1

FCM1004-E FCM1004-E Main board 4 zone NL S54380-C9-A10

FCM1008 Main board for 8-zone units S54380-C1-A10

FCM1008-E FCM1008-E Main board 8 zone NL S54380-C1-A30

FCM1008-D FCM1008-D Main board 8 zone CH S54380-C1-A20

FCP1002 Transformer for 2/4-zone units

The transformer is delivered with mains connecting terminal.

S54390-N12-A1

12.fm Seite 4 Mittwoch, 28. Juli 2010 8:59 08

Page 214: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Spare PartsExtinguishing Control Panels XC10

12-5© Siemens Switzerland Ltd 2010

12

Type Order No.

XCM1002 Main board

Main board for XC10‚ as spare part

S54390-A4-A1

FCP1004-E Power supply 3.5 A

Power supply 3.5 A. Spare part for XC10.

A6E60500054

XCH1001-A Cover set

Cover set for XC1001-A‚ as spare part

S54390-B9-A1

XCH1003-A Cover set

Cover set for XC1003-A‚ as spare part

S54390-B10-A1

XCH1005-A Cover set

Cover set for XC1005-A‚ as spare part

S54390-B11-A1

XCA1002-1 Display adapter

Display adapter‚ as spare part

S54390-B7-A1

XCA1002-2 Display adapter

Display adapter‚ as spare part

S54390-B8-A1

12.fm Seite 5 Mittwoch, 28. Juli 2010 8:59 08

Page 215: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Spare PartsManual Call Points

12-6 © Siemens Switzerland Ltd 2010

Type Order No.

FDMG291 Replacement glass

Replacement glass for manual call point housings FDMH291-x.

Delivery unit 10 pieces

A5Q00002122

FDMK291 Cover with key

Spare key with call point front for manual call point housings FDMH291-x.

A5Q00001643

DMZ1196-AC Spare glass neutral

Easy to replace spare glass for the manual call point housings DMA1192-x‚ FDMH29x-x. The spare glass is neutral and has no marks.

Delivery unit 10 pieces

BPZ:4942050001

DMZ1195 Spare key

The spare key is used for all manual call point housings DMA1192-xx‚ FDMH293-x.

Delivery unit 10 pieces

BPZ:4851910001

FDMG295 Glass plate neutral

Glass plate for manual call points FDM225-RG‚ FDM226-RG‚ FDM1101-RG and FDM1101A-RG.Use as spare part.

Delivery unit 5 pieces

A5Q00013442

FDMP295 Plastic element neutral

Plastic element for manual call points FDM225-RP‚ FM226-RP‚ FDM1101-RP and FDM1101A-RP.Use as spare part.

Delivery unit 5 pieces

A5Q00013445

12.fm Seite 6 Mittwoch, 28. Juli 2010 8:59 08

Page 216: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Spare PartsManual Call Points

12-7© Siemens Switzerland Ltd 2010

12

Type Order No.

FDMK295 Spare key

Key for manual call points FDM225‚ FDM226‚ FDM1101 and FDM1101A.Use as spare part.

Delivery unit 10 pieces

A5Q00013448

12.fm Seite 7 Mittwoch, 28. Juli 2010 8:59 08

Page 217: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Spare PartsInput Modules‚ Input/Output Modules‚ Alarm Indicator

12-8 © Siemens Switzerland Ltd 2010

Type Order No.

FDCM291 Mounting feet for in-/output modules

Installation in range of the in-/output modules with mounting feet onto top U-rail TS35.Use as spare part.

Delivery unit 25 pieces

A5Q00003855

BPZ:3048160001 Insulating cap for alarm indicators

Use as spare part.

Delivery unit 20 pieces

BPZ:3048160001

12.fm Seite 8 Mittwoch, 28. Juli 2010 8:59 08

Page 218: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Spare PartsTest Equipment

12-9© Siemens Switzerland Ltd 2010

12

Type Order No.

FDLU291 Adjustment device for FDLU291

Adjustment device use only as spare part.

A5Q00006540

FDUD292-A Adapter cable

MC-Link cable from detector exchanger and tester to the in-/output modules‚ to the linear smoke detector and other devices (audio stereo cable 1.5 m with direct and bent stereo jack 3.5 mm).Use as spare part for FDUD292‚ FDUD293‚ FDUZ221.

A5Q00004990

A5Q00009786 Adapter with lever‚ screw and nut incl. attachment and bushing screw

Use as spare part to the telescope rods FDUM291 and FDUM292.

A5Q00009786

A5Q00009787 Lever with screw and nut

Use as spare part to the telescope rods FDUM291 and FDUM292.

A5Q00009787

A5Q00009788 Small flap with screw and nut

Use as spare part to the telescope rod FDUM291.

A5Q00009788

A5Q00009789 Large flap with screw and nut

Use as spare part to the telescope rod FDUM291.

A5Q00009789

12.fm Seite 9 Mittwoch, 28. Juli 2010 8:59 08

Page 219: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Spare PartsTest Equipment

12-10 © Siemens Switzerland Ltd 2010

Type Order No.

FDUL221-A Line connection set

Use as spare part for line tester FDUL221.

A5Q00008436

FDUL221-B Mains adapter set

Use as spare part for line tester FDUL221.

A5Q00008437

FDUL221-C PC cable (RS232)

Use as spare part for line tester FDUL221.

A5Q00008438

BPZ:3679630001 Halogen lamp 12 V / 50 W

Use as spare part for LE3.

BPZ:3679630001

12.fm Seite 10 Mittwoch, 28. Juli 2010 8:59 08

Page 220: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Spare PartsTest Equipment

12-11© Siemens Switzerland Ltd 2010

12

Type Order No.

RE7T-B Solo760 Battery for RE7T

Use as spare part for RE7T heat detector tester.

Data sheet A6V10252901

S54370-N5-A1

RE7T-C Solo725 Charger for RE7T

Use as spare part for charging of battery baton to the RE7T heat detec-tor tester.

Data sheet A6V10252901

S54370-N6-A1

RG320 Bellow for RE6

The bellow is fitted to the RE6 to fit all SynoLINE300 point detectors in an ideal way.

BPZ:5166880001

DZZ1190 Bellow for RE6

The bellow is fitted to the RE6 to fit all SynoLINE600 and AlgoRex point detectors in an ideal way.

BPZ:4478380001

12.fm Seite 11 Mittwoch, 28. Juli 2010 8:59 08

Page 221: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

081031_Product_Catalog_Innen_07lay.indd 35 24.07.09 18:12

Page 222: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Repair PartsFire Control Panels FC72xx and Operating Terminals FT724xxOperating Units and Add-on

13-1© Siemens Switzerland Ltd 2010

13

Type Order No.

FCM7201-Z3 Operating unit

Complete operating unit (support base‚ keypad‚ PMI main board‚ CPU module) without accessories.Use as repair part only.

A5Q00018923-R

FCM7202-Y3 Operating unit (+LED ind.)

Complete operating unit (support base‚ keypad‚ PMI main board‚ CPU module) without accessories.Use as repair part only.

A5Q00018925-R

FCM7203-H3 Operating unit (+EVAC term.)

Complete operating unit (support base‚ keypad‚ PMI main board‚ CPU module) without accessories.Use as repair part only.

A5Q00018933-R

13.fm Seite 1 Mittwoch, 28. Juli 2010 9:00 09

Page 223: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Repair PartsPeriphery Boards‚ Expansion Modules and Power Supply

13-2 © Siemens Switzerland Ltd 2010

Type Order No.

FCI2010-A1 Periphery board (1-loop)

Periphery board (1-loop) without accessories.Use as repair part only.

A5Q00031729-R

FCI2002-A1 Periphery board (2-loop)

Periphery board (2-loop) without accessories.Use as repair part only.

A5Q00005545-R

FCI2004-A1 Periphery board (4-loop)

Periphery board (4-loop) without accessories.Use as repair part only.

A5Q00009953-R

FTI2001-A1 Fire terminal board

Fire terminal board without accessories.Use as repair part only.

A5Q00013279-R

13.fm Seite 2 Mittwoch, 28. Juli 2010 9:00 09

Page 224: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Repair PartsPeriphery Boards‚ Expansion Modules and Power Supply

13-3© Siemens Switzerland Ltd 2010

13

Type Order No.

FN2001-A1 Network module (SAFEDLINK)

Network module (SAFEDLINK) without accessories.Use as repair part only.

A5Q00012851-R

13.fm Seite 3 Mittwoch, 28. Juli 2010 9:00 09

Page 225: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Repair PartsFloor Repeater Panels

13-4 © Siemens Switzerland Ltd 2010

Type Order No.

FT2010-A1 Floor repeater terminal

Front part of the floor repeater terminal (cover cap‚ stick-on labels‚ key-pad) without accessories.Use as repair part only.

A5Q00014104-R

FT2011-A1 Floor repeater display

Front part of the floor repeater display (cover cap‚ stick-on label‚ key-pad) without accessories.Use as repair part only.

A5Q00017706-R

13.fm Seite 4 Mittwoch, 28. Juli 2010 9:00 09

Page 226: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Danger Management System

MM8000 – the danger management station for Cerberus PROMM8000 enables centralized alarm management and supervision of a broad range of fi re safety, electronic security, and control systems. All are displayed in a uniform and clearly structured manner. Alarms and messages are listed according to security-relevant priorities, so operators have all relevant infor-mation at a glance. And in case of an event, MM8000 guides the user step by step through predefi ned procedures. Thanks to a user-friendly engineering tool, MM8000 can be confi gured quickly and easily. Moreover, MM8000 is a highly fl exible and scalable danger management station that can be adapted to changing requirements any time.

MM8000 can integrate the following subsystems:– Fire safety– Intrusion detection– Access control– Video surveillance– Building automation installations– and other subsystems

fieneb ynam sreffo 0008MM ot ORP s®urebreC gnitcennoC ts, among them are:– Central control and operation– Interaction with other safety subsystems– Easy navigation and quick alarm localization– Guided event treatment– History database

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 38 28.05.10 16:59

Page 227: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Danger Management SystemMM8000 Management Station

14-2 © Siemens Switzerland Ltd 2010

Type Order No.

MM8000xxx MM8000 danger management station

The MM8000 danger management station provides a powerful solu-tion for the centralized alarm management and supervision of a wide range of fire safety‚ security and control systems. It supports specifically fire‚ gas and intrusion detection‚ access control‚ video surveillance and building automation installations.

The MM8000 architecture allows the integration of Siemens fire safety‚ security and control systems as well as 3rd party solutions via standard interfaces.

FunctionalityComplete overview of the actual state of technical installations in a building at any time.Homogeneous and intuitive operation of the different subsystems.Comprehensive guidance and support of the operator in case of an alarm.Logging of all activities and powerful reporting possibilities.

AdvantagesSafety: User guidance in case of an emergency guarantees that the right measures are taken.Reliability: Based on the concept of autonomous subsystems and dis-tributed control; possibility of redundant configurations.Flexibility: Can be built and configured to fit the requirements of the customer.Openness: OPC‚ BACnet and Modbus (via NK) interfaces for subsystem integration.Scalability: MM8000 will easily grow to support more subsystems‚ dis-ciplines and stations.

FeaturesComfortable navigation through the system via graphical maps or object trees.Advanced graphics including AutoCAD.Automatic and/or manual alarm dispatching via e-mail‚ SMS and pag-ers.Scheduler application for time-based actions.Configurable interactions between different subsystems.Macro editor for complex commands.System security based on Microsoft Windows (combined login).Flexible configuration of user access rights.Support of dual monitor configurations.

System requirements The MM8000 SW runs on a Micro-soft Windows PC.

Ordering information Contact your local BT sales support representative for further informa-tion.

Data sheet A6V10074451

MM8000xxx

14.fm Seite 2 Mittwoch, 28. Juli 2010 9:01 09

Page 228: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

System Overview

Cerberus PRO – an overview of a smart systemThe Cerberus® PRO portfolio provides everything needed for smart fi re protection: powerful control panels, clever fi re detectors, smart peripheral devices – and elaborate safety features. What’s more, every component comes from the same source.

Unique safety features – such as degrade mode in control panels and built-in isolators in each peripheral device

Powerful panels – from stand-alone to networkable control units Reliable detectors – developed and proven under countless job-site conditions Broad range of additional devices and accessories – from alarm sounders to sounder bases and combined sounder beacons and many more

Cost effi ciency – thanks to smart products and remote access Integration into the danger management system from Siemens – interoperability with other subsystems such as access control, intrusion detection, video surveillance, and others

Control panels and fi re terminals can serve as a standby operating unit for increased safety Extended network possibilities for widely distributed or complex buildings

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 40 28.05.10 16:59

Page 229: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Cerberus PRO Planning Tool – panels, network, and accessories

Customer network

Cluster (C-WEB/SAFEDLINK)

In the basic version each FC724 control panel contains:

Alarm transmissionFault transmissionFire controlsMonitoring of 2 conven-tional sounder lines

Each FC726 control panel contains:

Alarm transmissionFault transmissionFire controlsMonitoring of 2 conven-tional sounder lines

To enable remote operation with Cerberus-Remote, the PC has to be connected to an Ethernet switch of the backbone. Access to a certain panel in a cluster will be granted by installing an L1 license key into this panel.

Security module

(firewall) FN2009-A1

Danger management

system

The danger management system from Siemens is either directly connected to the backbone (via Ethernet switch) or via the customer network by using ad-ditional security modules. Each station that is to be addressed by the danger management system must be released by means of the license key (L2).

System-wide view with the fire terminal FT2040-EZ

Ethernet switch FN2008-A1

Security module (firewall) FN2009-A1

Fire control panel FC724-ZE

Art. no.: S54400-C30-A3

Remote access with Cerberus-Remote

Ethernet switch FN2008-A1

Ethernet

Fire control panel FC724-ZA

Art. no.: S54400-C30-A2

Backbone (C-WEB/LAN)Clusters can be networked via an Ethernet back-bone, using industrial LAN technology. Siemens is the first manufacturer who offers this as EN 54-approved solution. With this architecture that is standard in IT, building structures and or-ganizational processes can be ideally depicted.

Characteristics of networking via backbone– Ethernet switch to connect a cluster to the

backbone– Redundant transmission thanks to circular

wiring– Redundant connection possible due to two

Ethernet switches– Increased EMC protection thanks to fiber-

optic cabling– Easily programmable, EN 54-conform system-

wide control– Configurable view of single panels– All panels can be used as router panel (for

further information on FC726, please have a look into the separate documentation).

Key data– Max. number of panels in EN 54 system: 64– Max. number of panels in a cluster: 16– Max. number of networkable clusters: 14– Number of panels placed directly

on backbone: 4*– Number of panels with

system-wide view: 5*– Max. distance between clusters

(fiber optic: multi mode): 3,000 m

* and more with respective system topology

The following guidelines must be observed– To fulfill the EN 54 norm, you need only

1 Ethernet switch to connect control panels with less than 512 fire detectors to the backbone.

Cluster (C-WEB/SAFEDLINK)Via the powerful cluster, up to 32 panels can be networked (fire control panels and fire terminals).

Characteristics of networking via the system bus– Wiring with two wires– Redundant transmission thanks to circular

wiring– Increased safety due to degrade mode using a

second network module– No additional cabling necessary for degrade

mode; even for systems with more than 512 fire detectors

– Configurable view of individual panels

Key data– Max. number of networkable panels: 32– Max. number of networkable panels

if connected to a danger management system: 16

– Max. distance between panels with copper cable• without repeater: 1,000 m • with repeater: 2,000 m

– Max. distance between panels with fiber-optic cable • multi mode: 2,500 m • single mode: 15,000 m

– Max. number of panels with system-wide view: 5

C-NETThe C-NET is a modern, multi-purpose bus system. It allows rapid, fail-safe communication between the Cerberus® PRO bus elements and the fire control panel.

Characteristics of networking via the detector bus– Use of all cable types (shielded or unshielded)– Integration of star-shaped cable networks

without modifications to cable network– Shielding not necessary

C-NET(For further details see also the Cerberus PRO Planning Tool – C-NET devices)

Fire terminal FT724-ZZ

Art. no.: S54400-C31-A2

Fire terminal FT724 The FT724 has the following features:– Integrated control unit– Separate DC 24 V supply input possible– Redundant DC 24 V supply input– Networkability via C-WEB/SAFEDLINK or Ethernet

Fire control panel FC724 (4-loop) The FC724 is a compact 4-loop fi re control panel. It has the following features:– 4 C-NET loops– Integrated inputs/outputs for peripherals– Integrated control unit– Integrated power supply– Automatic confi guration– Networkability via backbone (C-WEB/LAN),

cluster (C-WEB/SAFEDLINK) or Ethernet

Fire control panel FC726 (modular)FC726 is a modular fi re control panel.It has the following features:– 4 C-NET loops– 5 slots for additional module bus cards– Integrated inputs/outputs for peripherals– Integrated control unit– Integrated power supply– Automatic confi guration– Networkability via backbone (C-WEB/LAN),

cluster (C-WEB/SAFEDLINK) or Ethernet

Fire control panel FC726-ZA

Art. no.: S54400-C87-A1

Backbone (C-WEB/LAN)

– 2-wire loop– Power supply to all bus elements via the C-NET

(except transponder FDCIO223, LaserFOCUS, extinguishing control unit XC10)

Key data– Up to 40 T-taps– Up to 126 bus elements on one loop– Cable lengths up to 3.3 km with up to 126 bus

elements

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 41 28.05.10 16:59

Page 230: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

© Siemens 2010

In the basic version each FC722 control panel contains:

Alarm transmissionFault transmissionFire controlsMonitoring of conven-tional sounder line

Fire control panel FC721 (1-loop)The FC721 is a compact fi re control panel. It has the following features:– 1 C-NET loop– Integrated inputs/outputs for

peripherals– Integrated control unit– Integrated power supply– Automatic confi guration

Fire control panel FC721-ZZ

Art. no.: S54400-C32-A2

Fire control panel FC721-YZ

Art. no.: S54400-C32-A3

Manual call point, red FDM221

Fire control panel FC722 (2-loop)The FC722 is a compact 2-loop fi re con-trol panel. It has the following features:– 2 C-NET loops– Integrated inputs/outputs for

peripherals– Integrated control unit– Integrated power supply– Automatic confi guration– Networkability via backbone (C-WEB/

LAN), cluster (C-WEB/SAFEDLINK) or Ethernet

Fire control panel FC722-ZA

Art. no.: S54400-C29-A2

Fire control panel FC722-ZE

Art. no.: S54400-C29-A1Floor repeater terminal FT2010-A1

Art. no.: A5Q00014104

Optical smoke detector OP720

Alarm sounderFDS221-R

Serial interfaces One optional RS232 and/or one RS485 interface (also freely combinable) per panel or fire terminal

Backbone (C-WEB/LAN) Network to connect clusters Cluster (C-WEB/SAFEDLINK) Network to connect panelsC-NET Network to connect Cerberus PRO devices

Legend for the interfaces and networks:

Repeater (SAFEDLINK) FN2002-A1

Art. no.: S24236-B2502-A1

Fire control panel FC722-YZ

Art. no.: S54400-C29-A4

Fire control panel FC722-ZZ

Art. no.: S54400-C29-A5

BackboneSecurity module (firewall) FN2009-A1

Art. no.: S54400-F95-A1

Ethernet switch FN2008-A1

Art. no.: S54400-F94-A1

Cluster Network module (SAFEDLINK) FN2001-A1

Art. no.: A5Q00012851

Housing (Eco) FH7201-Z3

Art. no.: S54400-B72-A1

Housing (Standard) FH7202-Z3

Art. no.: S54400-B70-A1

Housing (Comfort) FH7203-Z3

Art. no.: S54400-B71-A1

Housing (Large) FH7205-Z3

Art. no.: S54400-B86-A1

Housing (Large Extension) FH7204-Z3

Art. no.: S54400-B89-A1

19“ mounting kit FHA2016-A1

Art. no.: A5Q00020179

Loop extension (C-NET) FCI2003-A1

Art. no.: A5Q00010136

RS232 module (isolated) FCA2001-A1

Art. no.: A5Q00005327

RS485 module (isolated) FCA2002-A1

Art. no.: A5Q00009923

Sounder module FCA2005-A1

Art. no.: A5Q00014866

License key L1 FCA2012-A1

Art. no.: A5Q00018856

License key L2 FCA2013-A1

Art. no.: A5Q00018857

Line card (C-NET) FCL2001-A1

Art. no.: A5Q00009875

Module bus cards for FC726

I/O card (programmable) FCI2008-A1

Art. no.: S54400-A6-A1

Power supply kit (70 W) FP2003-A1

Art. no.: A5Q00016005

Power supply kit (150 W) FP2004-A1

Art. no.: A5Q00020825

Additional power supply (150 W) FP2005-A1

Art. no.: A5Q00018779

Power supply

Operating add-ons

Operating add-on (2xLED-ind.) FCM7211-Y3

Art. no.: S54400-F75-A1

Operating add-on (4xLED-ind.) FCM7212-Y3

Art. no.: S54400-F88-A1

Key switch Kaba FTO2005-C1

Art. no.: A5Q00010113

Key switch NordicFTO2006-B1

Art. no.: A5Q00010129

Event printer FTO2001-A1

Art. no.: A5Q00010126

Event printer DL3750+

Art. no.: A5Q00023962

Network components Housings Expansion options

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 42 28.05.10 16:59

Page 231: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Fire control panel FC722

Fire control panel FC724

Fire control panel FC726

Multi-line separator module FDCL221-M

Art. no.: S54312-F6-A1

C-NETThe C-NET is a modern, multi-purpose bus system. It allows rapid, fail-safe communication between the Cerberus® PRO bus elements and the fire control panel.

Cerberus PRO fi re detectors

Extinguishing panel standard XC1001-A

Art. no.: S54390-C1-A1

Input/output module FDCIO222

Art. no.: A5Q00002369

Cerberus PRO control panels

Floor repeater terminal FT2010-A1

Art. no.: A5Q00014104

Floor repeater display FT2011-A1

Art. no.: A5Q00017706

Mimic display driver FT2001-A1

Art. no.: A5Q00014417

Line separator FDCL221

Art. no.: A5Q00004011

Cluster (C-WEB/SAFEDLINK)

Legend for the designation of fire detectors:Cluster (C-WEB/SAFEDLINK) Network for connecting up to 32 panels or up to

16 panels if connected to a danger management systemC-NET Network for connecting Cerberus PRO devices...xxx-9 Connection to collective and conventional technology possible

Cerberus PRO Planning Tool – C-NET devices

Alarm indicator (addressable)FDCAI221

Art. no.: S54370-F10-A1

Alarm equipment(audible/visible)

Sounder base DBS720

Art. no.: S54319-F5-A1

Alarm sounderFDS221-W

Art. no.: A5Q00006711

Alarm sounderFDS221-R

Art. no.: A5Q00004117

Alarm sounder beacon FDS229-R

Art. no.: A5Q00023093

Alarm sounder beacon FDS229-A

Art. no.: A5Q00023092

Sounder base FDB221

Art. no.: A5Q00001664

Sounder base flat FDB222

Art. no.: S54319-F1-A1

or

Sealing element FDBZ295

Art. no.: S54319-F10-A1

Designation plate FDBZ291

Art. no.: A5Q00002621

Base attachment FDB291

Art. no.: A5Q00001603

Base attachment wet FDB293

Art. no.: A5Q00003945

Designation plate DBZ1193A

Art. no.: BPZ:4864330001

Detector locking device FDBZ293

Art. no.: A5Q00005035

Optical smoke detector OP720

Art. no.: S54310-F1-A1

Heat detector HI720

Art. no.: S54310-F4-A1

Heat detector HI722

Art. no.: S54310-F3-A1

Alarm indicator FDAI93

Art. no.: S54370-F5-A1

Alarm indicator FDAI91

Art. no.: S54370-F9-A1

Alarm indicator FDAI92

Art. no.: S54370-F3-A1

Additional frame AI330

Art. no.: BPZ:3169430001

Detector base seal RS720

Art. no.: S54319-F8-A1

Designation plate FDBZ291

Art. no.: A5Q00002621

Detector locking device LP720

Art. no.: S54319-F9-A1

Line tester FDUL221

Art. no.: A5Q00004397

Detector exchanger DX791

Art. no.: S54319-F6-A1

Detector tester RE6 for smoke detectors

Art. no.: BPZ:3680300001

Detector tester RE7T for heat detectors

Art. no.: S54370-S3-A1

Detector tester RE10 for linear smoke detectors

Art. no.: BPZ:3685190001

Test lamp StapexHF for flame detectors ‘Ex’

Art. no.: BPZ:4620910001

Test lamp LE3 for flame detectors

Art. no.: BPZ:3669510001

Detector base accessories

Detector base DB721

Art. no.: S54319-F11-A1

Sounder base DBS720

Art. no.: S54319-F5-A1

or

Fire control panel FC722

LED flat cable 24 LEDs

Art. no.: BPZ:5291410001

Flat rear FHA2013-A1

Art. no.: A5Q00016552

Sounder accessories

Test equipment

Multi-sensor smoke detector OH720

Art. no.: S54310-F2-A1

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 43 28.05.10 17:00

Page 232: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

+DC 24 V

up to 100 m +DC 24 V

Fire control

Fire control

Fire control

4 isolatedcontrol inputs

Collective interface

Housing red with key FDMH291-RArt. no.: A5Q00002217Housing yel-low with key FDMH291-YArt. no.: A5Q00004979Housing green with key FDMH291-GArt. no.: A5Q00004981Housing blue with key FDMH291-BArt. no.: A5Q00004980Accessories*

Manual call point with glass plate FDM225-RGArt. no.: A5Q00013434Accessories*

Manual call point with glass plate incl. back box FDM226-RGArt. no.: A5Q00013435Accessories*

Housing with glass and key:FDMH293-RArt. no.: A5Q00004023Housing yellow FDMH293-YArt. no.: A5Q00004908Housing green FDMH293-GArt. no.: A5Q00004911Housing blue FDMH293-BArt. no.: A5Q00004909Housing orange FDMH293-OArt. no.: S54311-F2-A1Accessories*

Housing red FDMH292-RArt. no.: A5Q00005525Accessories*

Housing with glass and key:FDMH293-RArt. no.: A5Q00004023Housing yellow FDMH293-YArt. no.: A5Q00004908Housing green FDMH293-GArt. no.: A5Q00004911Housing blue FDMH293-BArt. no.: A5Q00004909Housing orange FDMH293-OArt. no.: S54311-F2-A1Accessories*

Housing red FDMH292-RArt. no.: A5Q00005525Accessories*

Manual call point FDM221 Electronic switching unit FDME221Art. no.: A5Q00002451

Manual call point FDM225 Manual call point with re-settable plas-tic element FDM225-RPArt. no.: A5Q00012020

Manual call point FDM226 Manual call point with resettable plastic element incl. back box FDM226-RPArt. no.: A5Q00013436

Manual call point FDM224 Electronic switching unit FDME224Art. no.: A5Q00009392

Manual call point FDM224H Electronic switching unit FDME224Art. no.: A5Q00009392

Manual call point FDM223 Electronic switching unit FDME223Art. no.: A5Q00003087

Manual call point FDM223H Electronic switching unit FDME223Art. no.: A5Q00003087

* See respective catalog page

Base and smoke detector DOW1171

Art. no.: S24218-F62-A5

Lithium battery 3.6 V

Art. no.: V24069-Z112-A1

Key

Art. no.: S24217-G34-A1

Manual call point SMF121

Art. no.: V24217-C1218-W200

MCP base SMF6120

Art. no.: S24218-F72-A1

Radio gateway FDCW221

Art. no.: A5Q00020241

Radio network in SRD band

Radio fi re detection

Input/output module“transponder” FDCIO223

Art. no.: S24218-B102-A1

Input module FDCI221

Art. no.: S54312-F1-A1

Input/output module FDCIO221

Art. no.: S54312-F2-A1

Input module FDCI222

Art. no.: A5Q00001984

Input/output module FDCIO222

Art. no.: A5Q00002369

4 isolatedcontrol inputs

4 isolatedcontrol outputs

Aspirating smoke detection

LaserFOCUS VLF-250

Art. no.: VLF-250-SIE

LaserFOCUS VLF-500

Art. no.: VLF-500-SIE

Housing FDCH221IP65Art. no.: S54312-F3-A1

Air sampling smoke detection kit FDBZ292 (without air flow pipe)

Art. no.: A5Q00021362

Air flow pipe FDBZ292-AAlength 0.6 m

Art. no.: A5Q00021363

Air flow pipe FDBZ292-ABlength 1.5 m

Art. no.: A5Q00021364

Air flow pipe FDBZ292-AClength 2.8 m

Art. no.: A5Q00021366

Optical smoke detector DO1104A

Art. no.: BPZ:5090640001

Detector base DB1101A

Art. no.: BPZ:4863650001

Long-distance reflector DLR1191 (Prism)

Art. no.: BPZ:4787710001

Mid-distance reflector DLR1192

Art. no.: BPZ:4788490001

Short-distance reflector DLR1193

Art. no.: BPZ:4787840001

Short-distance filter 7 – 10 m DLF1191-AA

Art. no.: BPZ:4933030001

Short-distance filter 5 – 8 m DLF1191-AB

Art. no.: BPZ:4933160001

Detector heating DLH1191A

Art. no.: BPZ:4787970001

Input/output module “transponder” FDCIO223

Art. no.: S24218-B102-A1

Rain hood DFZ1190

Art. no.: BPZ:5302660001

Mounting bracket MV1

Art. no.: BPZ:3950450001

Ball and socket joint MWV1

Art. no.: BPZ:3674840001

Conventional detectors

Conventional line

Heat detector DT1102A-ExArt. no.: BPZ:4852270001

Heat detector DT1101A-ExArt. no.: BPZ:4852140001

Smoke detector DO1101A-ExArt. no.: BPZ:5008010001

Alarm indicator FDAI93-ExArt. no.: S54370-F6-A1

Alarm indicator FDAI92-ExArt. no.: S54370-F4-A1

Flame detector DF1101-Ex Art. no.: BPZ:5166750001Base DFB1190Art. no.: BPZ:5165360001

Detector base DB1101AArt. no.: BPZ:4863650001

Line termination EOL22 (Ex)Art. no.: BPZ:516222001

Housing DCA1191Art. no.: BPZ:4588560001Installation set Z3I410Art. no.: BPZ:4837660001Shunt Zener diode barrier SB3Art. no.: BPZ:4837400001

Manual call point DM1103 (Ex) Electronic DMA1103DArt. no.: A5Q00004470Housing red with key DMA1192-AAArt. no.: BPZ:5222870001

Manual call pointDM1104 (Ex)Electronic DMA1104DArt. no.: A5Q00005925Housing red with key DMA1192-AAArt. no.: BPZ:5222870001

Ex zoneFlame detector base FDFB291

Art. no.: A5Q00003310

DA fl ame detector FDF221-9

Art. no.: A5Q00003902

Flame detector FDF241-9

Art. no.: A5Q00003006

Linear smoke detector FDL241-9

Art. no.: A5Q00002298

Linear smoke detector base FDLB291

Art. no.: A5Q00003941

Manual call points and accessories

© Siemens 2010

002_Cerberus_0-92202_enDEC2009_Update_IP2_innen02.indd 44 28.05.10 17:00

Page 233: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

081031_Product_Catalog_Innen_07lay.indd 25 24.07.09 18:07

Page 234: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Type Index

1© Siemens Switzerland Ltd 2010

Type Description Order No. Page

A5Q00004142 Lithium brownstone battery 9 V / 1 Ah A5Q00004142 9-21,10-8

A5Q00004478 Screwed cable gland M20 x 1.5 A5Q00004478 2-20, 5-9, 5-12,5-16, 5-

18, 5-22, 5-24, 5-31, 5-

42, 7-7,7-12, 7-

16, 7-19, 7-23, 7-

25, 9-7,9-19, 9-

24, 9-26–27,

9-32, 9-35, 9-37

A5Q00004479 Back nut M20 A5Q00004479 2-21, 5-10, 5-12, 5-

42, 7-7,7-16, 7-

19, 9-24

A5Q00006735 Locking plug M20 x 1.5 (1 hole) A5Q00006735 5-16, 5-22, 7-

23, 9-35

A5Q00008131 V-plug PA M20 x 1.5 A5Q00008131 5-18, 5-24

A5Q00009786 Adapter with lever‚ screw and nut incl. attachment and bushing screw

A5Q00009786 12-9

A5Q00009787 Lever with screw and nut A5Q00009787 12-9

A5Q00009788 Small flap with screw and nut A5Q00009788 12-9

A5Q00009789 Large flap with screw and nut A5Q00009789 12-9

A5Q00010055 Locking plug M20 x 1.5 (2 holes) A5Q00010055 5-17, 5-23, 7-

23, 9-35

A5Q00017619 Thermo printer rolls for Custom Plus-S-0004 A5Q00017619 12-2

A5Q00023963 Typewriter ribbon A5Q00023963 12-2

AGN24.6 Alarm device BPZ:5371170001 8-1, 8-3

AGS24.5 Mallory buzzer BPZ:2785020001 8-2

AGT24.1 Alarm device BPZ:5371040001 8-1

AI330 Adapter frame for alarm indicator BPZ:3169430001 6-2, 7-9,7-24, 9-

36

AI91C Alarm indicator - Door frame S54370-F7-A1 7-9

AI92C Alarm indicator - Surface S54370-F8-A1 7-9

ALB24.1OR Flashing signal lamp 'orange' BPZ:5154140001 8-3

ALB24.1R Flashing signal lamp 'red' BPZ:5154270001 8-3

BPZ:2473130001 Washer BPZ:2473130001 7-25, 9-37

BPZ:3048160001 Insulating cap for alarm indicators BPZ:3048160001 7-25, 9-37, 12-8

BPZ:3679630001 Halogen lamp 12 V / 50 W BPZ:3679630001 12-10

Page 235: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Type Index

2 © Siemens Switzerland Ltd 2010

Type Description Order No. Page

DB1101A Base for collective detector series BPZ:4863650001 7-11, 9-11, 9-29

DB3 Alarm device for explosion-hazard areas of zones 1 and 2 BPZ:5757970001 9-38

DB721 Detector base with loop contact S54319-F11-A1 5-5

DBC1191A-AA Relay base BPZ:5017870001 7-13

DBS720 Sounder base S54319-F5-A1 5-6, 5-32

DBW1171 Base for radio smoke detector S24218-F316-A1 9-18

DBZ1190 Locking device BPZ:4585260001 7-14, 9-18

DBZ1190-AA Micro terminal 0.5 mm2‚ 4-pole BPZ:4677080001 5-7, 5-30, 5-33, 7-13, 9-

26–27,9-30

DBZ1190-AB Connection terminal 2.5 mm2‚ 3-pole BPZ:4942340001 5-7, 5-12, 5-30, 5-33, 5-

42, 7-4,7-7, 7-14, 7-16, 9-13, 9-

24, 9-30

DBZ1190A-AC Detector heating BPZ:5167850001 7-14

DBZ1191 Base attachment for surface mounting BPZ:4540830001 7-11, 9-29

DBZ1191A-AA Base attachment flat for surface mounting BPZ:5011270001 7-11

DBZ1192 Base attachment for humid environment BPZ:4588140001 7-12, 9-19

DBZ1192-AA Base attachment for wet environment BPZ:5355590001 7-12

DBZ1193A Detector designation plate BPZ:4864330001 5-31, 7-14, 9-19

DBZ1194 Protective cage BPZ:4677110001 5-31, 7-12, 9-19

DBZ1195A Acoustic base BPZ:4940140001 7-13

DBZ1197-AA Air flow tube for ASD-Duct BPZ:4926630001 9-11

DBZ1197-AC Air flow tube for ASD-Duct BPZ:4995140001 9-12

DC1192-I__ Input/output module for galvanic isolation DC1192-I__ 9-25

DCA1191 Housing (empty) BPZ:4588560001 7-25, 9-25, 9-

27, 9-37

DCA1192A Electronic unit for DC1192 BPZ:5081200001 9-25

DCB1192A Terminal base for DC1192 BPZ:5084500001 9-25

DF1101-Ex Infrared flame detector unit collective 'Ex' BPZ:5166750001 9-31

DF11Ex__ Infrared flame detector collective 'Ex' DF11Ex__ 9-31

DFB1190 Base for infrared flame detectors DF119x BPZ:5165360001 9-31–32

DFZ1190 Rain hood BPZ:5302660001 9-3

DJZ1193 Alarm indicator housing incl. washer BPZ:5302950001 7-25, 9-37

DL3750+ Matrix printer external A5Q00023962 1-10, 2-29, 2-36

DLF1191-AA Filter for short distances (7... 10 m) BPZ:4933030001 9-7

DLF1191-AB Filter for short distances (5... 8 m) BPZ:4933160001 9-8

Page 236: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Type Index

3© Siemens Switzerland Ltd 2010

Type Description Order No. Page

DLF1191-AC Filter against external light influences BPZ:5221480001 9-8

DLH1191A Detector heating BPZ:4787970001 9-8

DLR1191 Reflector for long distance (prism) BPZ:4787710001 9-7

DLR1192 Reflector for middle distance (foil) BPZ:4788490001 9-7

DLR1193 Reflector for short distance (foil) BPZ:4787840001 9-7

DM1101__ Collective manual call point DM1101__ 7-17

DM1103-L Manual release button complete A5Q00017630 7-22

DM1103-S Emergency stop button complete A5Q00014486 7-22

DM1103(Ex)__ Collective manual call point (double action) for explosion-hazard areas

DM1103(Ex)__ 9-33

DM1103__ Collective manual call point DM1103__ 7-20

DM1104(Ex)__ Collective manual call point (single action) for explosion-hazard areas

DM1104(Ex)__ 9-34

DM1104__ Collective manual call point DM1104__ 7-19

DMA1101 Switching unit collective (single action) A5Q00005578 7-17–18

DMA1103D Switching unit collective (double action) A5Q00004470 7-20, 9-33

DMA1104D Switching unit collective (single action) A5Q00005925 7-19–20,

9-34

DMA1192-AA Housing red‚ with glass and key BPZ:5222870001 7-19–21,

9-33–34

DMA1192-AB Housing blue‚ with glass and key BPZ:5464250001 7-19–21

DMA1192-AC Housing yellow‚ with glass and key BPZ:5464120001 7-19–21

DMA1192-AD Housing green‚ with glass and key BPZ:5090190001 7-19–21

DMZ1195 Spare key BPZ:4851910001 12-6

DMZ1196-AC Spare glass neutral BPZ:4942050001 12-6

DMZ1197-AC Protective cover BPZ:5223550001 5-16, 5-18, 5-22, 5-24, 7-

23, 9-35

DMZ1197-AD Protection seal BPZ:5470680001 5-16, 5-18, 5-22, 5-24, 7-

23, 9-35

DO1101A Smoke detector‚ collective wide spectrum BPZ:4930020001 7-10

DO1101A-Ex Smoke detector‚ wide spectrum collective 'Ex' BPZ:5008010001 9-28

DO1104A Smoke detector‚ collective wide spectrum BPZ:5090640001 9-11

DOW1171 Radio smoke detector S24218-F62-A6 9-18

DOW1171/DBW1171 Radio smoke detector complete S24218-F62-A5 9-17

DT1101A Heat detector BPZ:4931700001 7-10

DT1101A-Ex Heat detector collective 'Ex' BPZ:4852140001 9-28

DT1102A Heat detector BPZ:4931830001 7-10

DT1102A-Ex Heat detector collective 'Ex' BPZ:4852270001 9-29

DX791 Detector exchanger S54319-F6-A1 10-2

DZB1191 Detector base tester BPZ:4680660001 10-5

DZW1171 Radio test set BPZ:5762200001 9-21

DZZ1190 Bellow for RE6 BPZ:4478380001 12-11

EOL22(Ex) Line termination BPZ:5162220001 9-24, 9-26

Page 237: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Type Index

4 © Siemens Switzerland Ltd 2010

Type Description Order No. Page

F50F410 LED flat cable 50-wire‚ with 24 red LEDs BPZ:5291410001 5-46

FA2003-A1 Battery (12 V‚ 7 Ah‚ VDS) A5Q00019353 11-1

FA2004-A1 Battery (12 V‚ 12 Ah‚ VDS) A5Q00019354 11-1

FA2005-A1 Battery (12 V‚ 17 Ah‚ VDS) A5Q00019677 11-1

FA2006-A1 Battery (12 V‚ 26 Ah‚ VDS) A5Q00019356 11-1

FA2007-A1 Battery (12 V‚ 45 Ah‚ VDS) A5Q00022897 11-1

FA2008-A1 Battery (12 V‚ 65 Ah‚ VDS) A5Q00019357 11-2

FA2009-A1 Battery (12 V‚ 100 Ah‚ VDS) A5Q00023101 11-2

FC1002-A 2-zone conventional unit (Standard) S54380-C2-A1 3-6

FC1002-B 2-zone conventional unit (Head removal monitoring) S54380-C2-A10 3-6

FC1002-C 2-zone conventional unit (Nordic) S54380-C2-A20 3-6

FC1002.. 2-zone conventional unit FC1002.. 3-6

FC1004-A 4-zone conventional unit (Standard) S54380-C3-A1 3-8

FC1004-B 4-zone conventional unit (Head removal monitoring) S54380-C3-A10 3-8

FC1004-C 4-zone conventional unit (Nordic) S54380-C3-A20 3-8

FC1004-E 4-zone conventional unit (NL) S54380-C3-A30 3-8

FC1004.. 4-zone conventional unit FC1004.. 3-8

FC1008-A 8-zone conventional unit (Standard) S54380-C4-A1 3-10

FC1008-B 8-zone conventional unit (Head removal monitoring) S54380-C4-A10 3-10

FC1008-C 8-zone conventional unit (Nordic) S54380-C4-A20 3-11

FC1008-D 8-zone conventional unit (CH) S54380-C4-A30 3-11

FC1008-E 8-zone conventional unit (Evacuation) S54380-C4-A40 3-11

FC1008.. 8-zone conventional unit FC1008.. 3-10

FC1012-A 12-zone conventional unit (Standard) S54380-C5-A1 3-14

FC1012-B 12-zone conventional unit (Head removal monitoring) S54380-C5-A10 3-14

FC1012-B 12-zone conventional unit (Head removal monitoring) A6E60500015 3-14

FC1012-C 12-zone conventional unit (Nordic) S54380-C5-A20 3-15

FC1012.. 12-zone conventional unit FC1012.. 3-14

FC721-HZ Fire control panel (1-loop) in housing (Eco) with EVAC operating unit

S54400-C32-A1 1-5

FC721-YZ Fire control panel (1-loop) in housing (Eco) with 1 LED indicator S54400-C32-A3 1-4

FC721-ZZ Fire control panel (1-loop) in housing (Eco) S54400-C32-A2 1-4

FC721.. Fire control panel (1-loop) in housing (Eco) FC721.. 1-3

FC722-HA Fire control panel (2-loop) in housing (Comfort) with EVAC oper-ating unit

S54400-C29-A3 2-9

FC722-YZ Fire control panel (2-loop) in housing (Standard) with 1 LED indi-cator

S54400-C29-A4 2-6

FC722-ZA Fire control panel (2-loop) in housing (Comfort) S54400-C29-A2 2-7

FC722-ZE Fire control panel (2-loop) in housing (Comfort) with 2 LED indi-cators

S54400-C29-A1 2-8

FC722-ZZ Fire control panel (2-loop) in housing (Standard) S54400-C29-A5 2-5

FC722.. Fire control panel (2-loop) in housing (Standard) FC722.. 2-4

FC724-HA Fire control panel (4-loop) with EVAC operating unit S54400-C30-A1 2-14

FC724-ZA Fire control panel (4-loop) S54400-C30-A2 2-12

FC724-ZE Fire control panel (4-loop) with 2 LED indicators S54400-C30-A3 2-13

FC724.. Fire control panel (4-loop) FC724.. 2-11

FC726-ZA Fire control panel (modular) S54400-C87-A1 2-17

FC726.. Fire control panel (modular) FC726.. 2-16

FCA1001 Line extension card 4-zones A6E60500020 12-3

FCA1002 Display unit A6E60500021 3-12, 3-16

FCA1003 Sounder control card A6E60500022 3-12, 3-16

Page 238: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Type Index

5© Siemens Switzerland Ltd 2010

Type Description Order No. Page

FCA1005-D RT-isolation card A6E60500024 3-12, 3-16

FCA1007 Key switch kit A6E60500026 3-7, 3-9,3-13, 3-17, 4-6

FCA1007-B Add-on line card A6E60500027 12-3

FCA1009-E EVAC module S54380-B11-A1 12-3

FCA1013 Universal accessory bag A6E60500068 12-3

FCA1014 Battery holder A6E60500069 3-13, 4-5

FCA1016 Battery holder S54400-B90-A1 3-7, 3-9

FCA2001-A1 RS232 module (isolated) A5Q00005327 1-6, 2-21, 2-32

FCA2002-A1 RS485 module (isolated) A5Q00009923 1-6, 2-21, 2-32

FCA2005-A1 Sounder module A5Q00014866 2-20

FCA2012-A1 License key (L1) A5Q00018856 1-6, 2-18, 2-32

FCA2013-A1 License key (L2) A5Q00018857 2-18, 2-32

FCA2014-A1 Cable kit (communication) A5Q00023027 1-9, 2-28, 2-35

FCE1001 EOL resistor 3.9 kT (set of 10 pcs.) A6E60500031 12-3

FCE1002 Termination element‚ control line A6E60500032 12-3

FCE1003-B EOL element for head removal monitoring A6E60500033 12-3

FCH1002 Cover for the FC1002-A‚ -B‚ -C A6E60500035 12-3

FCH1004 Cover for the FC1004-A‚ -B‚ -C A6E60500036 12-3

FCH1004-E Cover for the FC1004-E A6E60500037 12-4

FCH1008 Cover for the FC1008-A‚ -B‚ -C A6E60500038 12-4

FCH1008-D Cover for the FC1008-D A6E60500039 12-4

FCH1008-E Cover for the FC1008-E S54380-F10-A1 12-4

FCH1012 Cover for the FC1012-A‚ -B‚ -C A6E60500043 12-4

FCI2001-D1 Fire brigade periphery module A5Q00013100 2-19

FCI2002-A1 Periphery board (2-loop) A5Q00005545-R 13-2

FCI2003-A1 Loop extension (FDnet/C-NET) A5Q00010136 2-18

FCI2004-A1 Periphery board (4-loop) A5Q00009953-R 13-2

FCI2005-N1 RT Interface Set A5Q00026302 2-19

FCI2008-A1 I/O card (programmable) S54400-A6-A1 2-18

FCI2010-A1 Periphery board (1-loop) A5Q00031729-R 13-2

FCL2001-A1 Line card (FDnet/C-NET) A5Q00009875 2-18

FCM1002 Main board 2-zones S54380-C8-A1 12-4

FCM1004 Main board 4-zones S54380-C9-A1 12-4

FCM1004-E FCM1004-E Main board 4 zone NL S54380-C9-A10 12-4

FCM1008 Main board for 8-zone units S54380-C1-A10 12-4

FCM1008-D FCM1008-D Main board 8 zone CH S54380-C1-A20 12-4

FCM1008-E FCM1008-E Main board 8 zone NL S54380-C1-A30 12-4

FCM7201-Z3 Operating unit A5Q00018923-R 13-1

FCM7202-Y3 Operating unit (+LED ind.) A5Q00018925-R 13-1

FCM7203-H3 Operating unit (+EVAC term.) A5Q00018933-R 13-1

FCM7210-Z3 Operating add-on S54400-F76-A1 12-1

FCM7211-Y3 Operating add-on (2xLED ind.) S54400-F75-A1 2-23–24,

2-33,12-1

FCM7212-Y3 Operating add-on (4xLED ind.) S54400-F88-A1 2-24, 2-33, 12-2

Page 239: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Type Index

6 © Siemens Switzerland Ltd 2010

Type Description Order No. Page

FCM7221-H3 Operating add-on (2xEVAC) S54400-F78-A1 2-24

FCP1002 Transformer for 2/4-zone units S54390-N12-A1 12-4

FCP1004-E Power supply 3.5 A A6E60500054 12-5

FDAI91 Alarm indicator - Door frame S54370-F9-A1 6-1, 7-24

FDAI92 Alarm indicator - Surface S54370-F3-A1 6-1, 7-24

FDAI92-Ex Alarm indicator - Surface for explosion-hazard areas S54370-F4-A1 9-36

FDAI93 Alarm indicator - Flush S54370-F5-A1 6-1, 7-25

FDAI93-Ex Alarm indicator - Flush S54370-F6-A1 9-36

FDB221 Detector base addressable A5Q00001664 5-29

FDB222 Detector base flat‚ addressable S54319-F1-A1 5-29

FDB291 Base attachment A5Q00001603 5-30

FDB293 Base attachment humid with seal A5Q00003945 5-30

FDBZ291 Designation plate A5Q00002621 5-6, 5-29–30,

5-32

FDBZ292 Air sampling smoke detection kit A5Q00021362 9-10

FDBZ292-AA Air flow tube 0.6 m A5Q00021363 9-11

FDBZ292-AB Air flow tube 1.5 m A5Q00021364 9-12

FDBZ292-AC Air flow tube 2.8 m A5Q00021366 9-12

FDBZ292-AD Sealing kit for air flow tubes A5Q00021367 9-12

FDBZ292-AF Mounting bracket A5Q00021369 9-12

FDBZ293 Detector locking device A5Q00005035 5-28

FDBZ295 Sealing element S54319-F10-A1 5-29

FDCAI221 Addressable alarm indicator S54370-F10-A1 6-2

FDCH221 Housing for input/output modules S54312-F3-A1 2-20, 5-42, 9-23

FDCI221 Input module S54312-F1-A1 5-37

FDCI222 Input module A5Q00001984 5-37

FDCIO221 Input/output module S54312-F2-A1 5-38

FDCIO222 Input/output module A5Q00002369 5-39

FDCIO223 Input/output module 'Transponder' S24218-B102-A1 5-41, 9-23

FDCIO224 Input/output module A5Q00018689 5-40

FDCL221 Line separator A5Q00004011 5-35

FDCL221-M Multi-line separator module S54312-F6-A1 5-36

FDCM291 Mounting feet for in-/output modules A5Q00003855 12-8

FDCW221 Radio gateway A5Q00020241 9-16

FDF221-9 DA Infrared flame detector unit (1 sensor) A5Q00003902 9-2

FDF241-9 ASA Infrared flame detector unit (3 sensors) A5Q00003006 9-2–3

FDF__ Infrared flame detector FDF__ 9-2

FDFB291 Base for infrared flame detectors FDF2x1-9 A5Q00003310 9-2–3

FDL241-9 ASA Linear smoke detector unit A5Q00002298 9-5–6

FDL__ ASA Linear smoke detector FDL__ 9-5

FDLB291 Base for linear smoke detector FDL241-9 A5Q00003941 9-5–6

FDLU291 Adjustment device set for linear smoke detector A5Q00004905 9-8, 10-6

FDLU291 Adjustment device for FDLU291 A5Q00006540 12-9

FDM1101-RG Manual call point with glass plate S54371-F6-A1 7-15

FDM1101-RP Manual call point with resettable plastic element S54371-F6-A2 7-15

FDM1101A-RG Manual call point with glass plate S54371-F6-A3 7-6

FDM1101A-RP Manual call point with resettable plastic element S54371-F6-A4 7-6

Page 240: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Type Index

7© Siemens Switzerland Ltd 2010

Type Description Order No. Page

FDM221__ Manual call point FDM221__ 5-8

FDM223 Manual call point complete A5Q00008098 5-19

FDM223__ Manual call point FDM223__ 5-20

FDM223H__ Manual call point 'Heavy Duty' FDM223H__ 5-23

FDM224__ Manual call point FDM224__ 5-14

FDM224H__ Manual call point 'Heavy Duty' FDM224H__ 5-17

FDM225-RG Manual call point with glass plate A5Q00013434 5-10

FDM225-RP Manual call point with resettable plastic element A5Q00012020 5-11

FDM226-RG Manual call point with glass plate incl. housing base A5Q00013435 5-12

FDM226-RP Manual call point with resettable plastic element incl. housing base

A5Q00013436 5-13

FDMC291 Protective cover A5Q00001644 5-9, 7-19

FDMC295 Protective cover A5Q00013440 5-12–13,7-8, 7-

17

FDME221 Switching unit with direct alarm actuation A5Q00002451 5-8–9

FDME223 Switching unit with indirect alarm actuation A5Q00003087 5-20, 5-22–24

FDME224 Switching unit with direct alarm actuation A5Q00009392 5-14, 5-16–18

FDMG291 Replacement glass A5Q00002122 12-6

FDMG295 Glass plate neutral A5Q00013442 12-6

FDMH291-B Housing blue with key A5Q00004980 5-8–9,7-

17–18

FDMH291-G Housing green with key A5Q00004981 5-8–9,7-

17–18

FDMH291-R Housing red with key A5Q00002217 5-8, 7-17

FDMH291-Y Housing yellow with key A5Q00004979 5-8, 7-17–18

FDMH292-R Housing red 'Heavy Duty' A5Q00005525 5-17, 5-23

FDMH293-B Housing blue‚ with glass and key A5Q00004909 5-14–15,

5-20–21

FDMH293-G Housing green‚ with glass and key A5Q00004911 5-14–15,

5-20–21

FDMH293-O Housing orange‚ with glass and key S54311-F2-A1 5-14–15,

5-20–21

FDMH293-R Housing red‚ with glass and key A5Q00004023 5-14, 5-20

FDMH293-Y Housing yellow‚ with glass and key A5Q00004908 5-14–15,

5-20–21

FDMH295-R Back box A5Q00013437 5-11, 7-7, 7-16

FDMH295-S Back box with 2 entries A5Q00013438 5-11, 7-7, 7-16

Page 241: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Type Index

8 © Siemens Switzerland Ltd 2010

Type Description Order No. Page

FDS221-W Alarm sounder white A5Q00006711 5-26

FDS229-A Alarm sounder beacon‚ orange A5Q00023092 5-28

FDS229-R Alarm sounder beacon‚ red A5Q00023093 5-27

FDUD292-A Adapter cable A5Q00004990 12-9

FDUL221 Line tester A5Q00004397 10-8

FDUL221-A Line connection set A5Q00008436 12-10

FDUL221-B Mains adapter set A5Q00008437 12-10

FDUL221-C PC cable (RS232) A5Q00008438 12-10

FDUM291 Telescope rod A5Q00004996 10-4

FDUM292 Telescope rod A5Q00004997 10-5

FDUZ221 MCL USB adapter A5Q00020131 10-9

FH7201-Z3 Housing (Eco) S54400-B72-A1 1-6, 2-21, 2-33

FH7202-Z3 Housing (Standard) S54400-B70-A1 1-7, 2-22

FH7203-Z3 Housing (Comfort) S54400-B71-A1 2-22–23

FH7204-Z3 Housing (Large Extension) S54400-B89-A1 2-23

FH7205-Z3 Housing (Large) S54400-B86-A1 2-23

FHA2007-A1 Mounting plate A5Q00010151 2-19

FHA2013-A1 Rear (FT201x flat) A5Q00016552 5-45

FHA2016-A1 19" mounting kit A5Q00020179 1-9, 2-28, 2-35

FHA2029-A1 Mounting kit for housing (Comfort) S54400-B79-A1 2-27

FHA2030-A1 Mounting kit for housing (Large Extension) S54400-B81-A1 2-27

FHA7201-A3 Cover cap (Cerberus) S54400-B77-A1 12-1

FHA7202-A3 Cover cap (without print) S54400-B74-A1 12-1

FN2001-A1 Network module (SAFEDLINK) A5Q00012851-R 13-3

FN2001-A1 Network module (SAFEDLINK) A5Q00012851 2-26, 2-32

FN2002-A1 Repeater (SAFEDLINK) S24236-B2502-A1 2-26

FN2008-A1 Ethernet switch S54400-F94-A1 2-27

FN2009-A1 Security module S54400-F95-A1 2-27

FP2003-A1 Power supply kit (70 W) A5Q00016005 1-7, 2-25, 2-33

FP2004-A1 Power supply kit (150 W‚ A) A5Q00020825 1-8, 2-25

FP2005-A1 Power supply kit (150 W‚ B) A5Q00018779 2-25

FT2001-A1 Mimic display driver A5Q00014417 5-46

FT2003-N1 Mimic display driver (EVAC) S54400-A14-A1 2-24

FT2010-A1 Floor repeater terminal A5Q00014104-R 13-4

FT2010-A1 Floor repeater terminal A5Q00014104 5-43

FT2010-C1 Floor repeater terminal S54400-F34-A1 5-44

FT2011-A1 Floor repeater display A5Q00017706 5-45

FT2011-A1 Floor repeater display A5Q00017706-R 13-4

FT724-HZ Fire terminal with EVAC operating unit S54400-C31-A1 2-31

FT724-ZZ Fire terminal S54400-C31-A2 2-30

FT724.. Fire terminal FT724.. 2-30

FTI2001-A1 Fire terminal board A5Q00013279-R 13-2

FTI2002-N1 EVAC-NL connector board S54400-A15-A1 2-24

FTO2001-A1 Event printer A5Q00010126 1-7, 2-19, 2-34

Page 242: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Type Index

9© Siemens Switzerland Ltd 2010

Type Description Order No. Page

FTO2005-C1 Key switch (Kaba) A5Q00010113 1-9, 2-28, 2-

35, 5-45

FTO2006-B1 Key switch (Nordic) A5Q00010129 1-9, 2-28, 2-35

GEN2-de Fire control panel for connection to 12 VDC supply BPZ:9300150001 3-2

GEN2-en Fire control panel for connection to 12 VDC supply BPZ:9300110001 3-2

GEN2-es Fire control panel for connection to 12 VDC supply BPZ:9300100001 3-3

GEN2-fr Fire control panel for connection to 12 VDC supply BPZ:9300180001 3-2

GEN2-it Fire control panel for connection to 12 VDC supply BPZ:9300120001 3-2

GEN2-nl Fire control panel for connection to 12 VDC supply BPZ:9300190001 3-2

GEN2-se Fire control panel for connection to 12 VDC supply BPZ:9300130001 3-2

GEN2.. Fire control panel for connection to 12 VDC supply GEN2.. 3-2

HI320C Heat detector (rate of rise and maximum) BPZ:5081590001 7-3

HI322C Heat detector (maximum) BPZ:5316470001 7-4

HI720 Heat detector (static+RoR) S54310-F4-A1 5-4

HI722 Heat detector (static) S54310-F3-A1 5-4

LaserFOCUS VLF-250 Aspirating smoke detector with display VLF-250-SIE 9-14

LaserFOCUS VLF-500 Aspirating smoke detector with display VLF-500-SIE 9-15

LE3 Test lamp for flame detectors BPZ:3669510001 9-4, 10-6

LP720 Detector locking device S54319-F9-A1 5-5

MGEN2 Fire control panel PCB for all languages BPZ:9300170001 3-3

MM8000xxx MM8000 danger management station MM8000xxx 14-2

MV1 Mounting bracket BPZ:3950450001 9-3

MVH1 Mounting bracket BPZ:3496190001 7-26, 9-37

MWV1 Ball and socket joint BPZ:3674840001 9-4

OH320C Smoke detector‚ conventional multi-sensor BPZ:5364190001 7-3

OH720 Multi-sensor smoke detector S54310-F2-A1 5-3

OP320C Optical smoke detector BPZ:5081460001 7-3

OP720 Optical smoke detector S54310-F1-A1 5-3

RE10 Detector tester for linear smoke detectors BPZ:3685190001 9-8, 10-6

RE6 Detector tester for smoke detectors BPZ:3680300001 10-2

RE6T Detector tester for heat detectors BPZ:3680270001 10-3

RE7T Solo461 Heat detector tester kit S54370-S3-A1 10-3

RE7T-A Solo719 Adapter for FDUM29x S54370-N4-A1 10-4

RE7T-B Solo760 Battery for RE7T S54370-N5-A1 12-11

RE7T-C Solo725 Charger for RE7T S54370-N6-A1 12-11

REF8 Test gas can for smoke detectors A5Q00011687 10-2

REF8-S Test gas can for smoke detectors A5Q00011688 10-2

RG320 Bellow for RE6 BPZ:5166880001 10-3,12-11

RS720 Detector base seal S54319-F8-A1 5-6, 5-32

S24217-G34-A1 Key S24217-G34-A1 9-21

SB3 Shunt Zener diode barrier BPZ:4837400001 9-27

SMF121 Manual call point V24217-C1218-W100 9-20–21

SMF121 Manual call point V24217-C1218-W200 9-20–21

SMF6120 Radio base S24218-F72-A1 9-20

SMF__ Manual call point SMF__ 9-20

Page 243: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Type Index

10 © Siemens Switzerland Ltd 2010

Type Description Order No. Page

SO320 Base for Synova 300 series detectors BPZ:5085990001 7-4

SOA322 Base attachment for surface mounting BPZ:5358340001 7-4

StabexHF Test lamp for flame detectors 'Ex' BPZ:4620910001 9-32,10-6

SV 24V-150W Power supply (150 W) V24230-Z6-A4 12-1

TF04 Alarm test filter (Absorption 77 %) BPZ:4931090001 9-9, 10-7

TP320 Detector locking device BPZ:5093100001 7-5

TS35_122 U-rail TS35/7.5/122 BPZ:5644780001 2-20, 5-36, 5-42

TS35_288 U-rail TS35/7.5/288 BPZ:5644230001 2-20, 5-36, 5-42

V24069-Z112-A1 Lithium battery 3.6 V / 2.1 Ah V24069-Z112-A1 9-20

XC1001-A Extinguishing panel Standard S54390-C1-A1 4-2

XC1003-A Extinguishing panel Rack S54390-C2-A1 4-4

XC1005-A Extinguishing panel Comfort S54390-C3-A1 4-3

XCA1002-1 Display adapter S54390-B7-A1 12-5

XCA1002-2 Display adapter S54390-B8-A1 12-5

XCA1020 Accessory set for FDCIO A5Q00025158 4-5

XCA1030 Multi-zone extension module S54390-A5-A1 4-5

XCA1031 Common multi-zone module S54390-A6-A1 4-5

XCE1002 Trigger element A5Q00015659 4-5

XCH1001-A Cover set S54390-B9-A1 12-5

XCH1003-A Cover set S54390-B10-A1 12-5

XCH1005-A Cover set S54390-B11-A1 12-5

XCM1002 Main board S54390-A4-A1 12-5

XT1001-A1 Repeater display S54390-Z16-A1 4-7

XT1002-A1 Repeater display S54390-Z15-A1 4-7

Z3B171 Relay module with 1 contact BPZ:4843830001 1-9, 2-28, 3-7,

3-9, 3-13, 3-

17, 4-6,8-1, 8-3

Z3I410 Installation set BPZ:4837660001 9-27

ZS/AGN24.5 Adapter base BPZ:4242620001 8-1, 8-3

Page 244: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Order No. Index

1© Siemens Switzerland Ltd 2010

Order No. Description Type Page

A5Q00001603 Base attachment FDB291 5-30

A5Q00001643 Cover with key FDMK291 12-6

A5Q00001644 Protective cover FDMC291 5-9, 7-19

A5Q00001664 Detector base addressable FDB221 5-29

A5Q00001984 Input module FDCI222 5-37

A5Q00002122 Replacement glass FDMG291 12-6

A5Q00002217 Housing red with key FDMH291-R 5-8, 7-17

A5Q00002298 ASA Linear smoke detector unit FDL241-9 9-5–6

A5Q00002369 Input/output module FDCIO222 5-39

A5Q00002451 Switching unit with direct alarm actuation FDME221 5-8–9

A5Q00002621 Designation plate FDBZ291 5-6, 5-29–30,

5-32

A5Q00003006 ASA Infrared flame detector unit (3 sensors) FDF241-9 9-2–3

A5Q00003087 Switching unit with indirect alarm actuation FDME223 5-20, 5-22–24

A5Q00003310 Base for infrared flame detectors FDF2x1-9 FDFB291 9-2–3

A5Q00003855 Mounting feet for in-/output modules FDCM291 12-8

A5Q00003902 DA Infrared flame detector unit (1 sensor) FDF221-9 9-2

A5Q00003941 Base for linear smoke detector FDL241-9 FDLB291 9-5–6

A5Q00003945 Base attachment humid with seal FDB293 5-30

A5Q00004011 Line separator FDCL221 5-35

A5Q00004023 Housing red‚ with glass and key FDMH293-R 5-14, 5-20

A5Q00004117 Alarm sounder red FDS221-R 5-25

A5Q00004142 Lithium brownstone battery 9 V / 1 Ah A5Q00004142 9-21,10-8

A5Q00004397 Line tester FDUL221 10-8

A5Q00004470 Switching unit collective (double action) DMA1103D 7-20, 9-33

A5Q00004478 Screwed cable gland M20 x 1.5 A5Q00004478 2-20, 5-9, 5-12,5-16, 5-

18, 5-22, 5-24, 5-31, 5-

42, 7-7,7-12, 7-

16, 7-19, 7-23, 7-

25, 9-7,9-19, 9-

24, 9-26–27,

9-32, 9-35, 9-37

A5Q00004479 Back nut M20 A5Q00004479 2-21, 5-10, 5-12, 5-

42, 7-7,7-16, 7-

19, 9-24

A5Q00004905 Adjustment device set for linear smoke detector FDLU291 9-8, 10-6

Page 245: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Order No. Index

2 © Siemens Switzerland Ltd 2010

Order No. Description Type Page

A5Q00004908 Housing yellow‚ with glass and key FDMH293-Y 5-14–15,

5-20–21

A5Q00004909 Housing blue‚ with glass and key FDMH293-B 5-14–15,

5-20–21

A5Q00004911 Housing green‚ with glass and key FDMH293-G 5-14–15,

5-20–21

A5Q00004979 Housing yellow with key FDMH291-Y 5-8, 7-17–18

A5Q00004980 Housing blue with key FDMH291-B 5-8–9,7-

17–18

A5Q00004981 Housing green with key FDMH291-G 5-8–9,7-

17–18

A5Q00004990 Adapter cable FDUD292-A 12-9

A5Q00004996 Telescope rod FDUM291 10-4

A5Q00004997 Telescope rod FDUM292 10-5

A5Q00005035 Detector locking device FDBZ293 5-28

A5Q00005327 RS232 module (isolated) FCA2001-A1 1-6, 2-21, 2-32

A5Q00005525 Housing red 'Heavy Duty' FDMH292-R 5-17, 5-23

A5Q00005545-R Periphery board (2-loop) FCI2002-A1 13-2

A5Q00005578 Switching unit collective (single action) DMA1101 7-17–18

A5Q00005925 Switching unit collective (single action) DMA1104D 7-19–20,

9-34

A5Q00006540 Adjustment device for FDLU291 FDLU291 12-9

A5Q00006711 Alarm sounder white FDS221-W 5-26

A5Q00006735 Locking plug M20 x 1.5 (1 hole) A5Q00006735 5-16, 5-22, 7-

23, 9-35

A5Q00008098 Manual call point complete FDM223 5-19

A5Q00008131 V-plug PA M20 x 1.5 A5Q00008131 5-18, 5-24

A5Q00008436 Line connection set FDUL221-A 12-10

A5Q00008437 Mains adapter set FDUL221-B 12-10

A5Q00008438 PC cable (RS232) FDUL221-C 12-10

A5Q00009392 Switching unit with direct alarm actuation FDME224 5-14, 5-16–18

A5Q00009786 Adapter with lever‚ screw and nut incl. attachment and bushing screw

A5Q00009786 12-9

A5Q00009787 Lever with screw and nut A5Q00009787 12-9

A5Q00009788 Small flap with screw and nut A5Q00009788 12-9

A5Q00009789 Large flap with screw and nut A5Q00009789 12-9

A5Q00009875 Line card (FDnet/C-NET) FCL2001-A1 2-18

A5Q00009923 RS485 module (isolated) FCA2002-A1 1-6, 2-21, 2-32

A5Q00009953-R Periphery board (4-loop) FCI2004-A1 13-2

A5Q00010055 Locking plug M20 x 1.5 (2 holes) A5Q00010055 5-17, 5-23, 7-

23, 9-35

Page 246: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Order No. Index

3© Siemens Switzerland Ltd 2010

Order No. Description Type Page

A5Q00010113 Key switch (Kaba) FTO2005-C1 1-9, 2-28, 2-

35, 5-45

A5Q00010126 Event printer FTO2001-A1 1-7, 2-19, 2-34

A5Q00010129 Key switch (Nordic) FTO2006-B1 1-9, 2-28, 2-35

A5Q00010136 Loop extension (FDnet/C-NET) FCI2003-A1 2-18

A5Q00010151 Mounting plate FHA2007-A1 2-19

A5Q00011687 Test gas can for smoke detectors REF8 10-2

A5Q00011688 Test gas can for smoke detectors REF8-S 10-2

A5Q00012020 Manual call point with resettable plastic element FDM225-RP 5-11

A5Q00012851 Network module (SAFEDLINK) FN2001-A1 2-26, 2-32

A5Q00012851-R Network module (SAFEDLINK) FN2001-A1 13-3

A5Q00013100 Fire brigade periphery module FCI2001-D1 2-19

A5Q00013279-R Fire terminal board FTI2001-A1 13-2

A5Q00013434 Manual call point with glass plate FDM225-RG 5-10

A5Q00013435 Manual call point with glass plate incl. housing base FDM226-RG 5-12

A5Q00013436 Manual call point with resettable plastic element incl. housing base

FDM226-RP 5-13

A5Q00013437 Back box FDMH295-R 5-11, 7-7, 7-16

A5Q00013438 Back box with 2 entries FDMH295-S 5-11, 7-7, 7-16

A5Q00013440 Protective cover FDMC295 5-12–13,7-8, 7-

17

A5Q00013442 Glass plate neutral FDMG295 12-6

A5Q00013445 Plastic element neutral FDMP295 12-6

A5Q00013448 Spare key FDMK295 12-7

A5Q00014104 Floor repeater terminal FT2010-A1 5-43

A5Q00014104-R Floor repeater terminal FT2010-A1 13-4

A5Q00014417 Mimic display driver FT2001-A1 5-46

A5Q00014486 Emergency stop button complete DM1103-S 7-22

A5Q00014866 Sounder module FCA2005-A1 2-20

A5Q00015659 Trigger element XCE1002 4-5

A5Q00016005 Power supply kit (70 W) FP2003-A1 1-7, 2-25, 2-33

A5Q00016552 Rear (FT201x flat) FHA2013-A1 5-45

A5Q00017619 Thermo printer rolls for Custom Plus-S-0004 A5Q00017619 12-2

A5Q00017630 Manual release button complete DM1103-L 7-22

A5Q00017706 Floor repeater display FT2011-A1 5-45

A5Q00017706-R Floor repeater display FT2011-A1 13-4

A5Q00018689 Input/output module FDCIO224 5-40

A5Q00018779 Power supply kit (150 W‚ B) FP2005-A1 2-25

A5Q00018856 License key (L1) FCA2012-A1 1-6, 2-18, 2-32

A5Q00018857 License key (L2) FCA2013-A1 2-18, 2-32

A5Q00018923-R Operating unit FCM7201-Z3 13-1

A5Q00018925-R Operating unit (+LED ind.) FCM7202-Y3 13-1

A5Q00018933-R Operating unit (+EVAC term.) FCM7203-H3 13-1

A5Q00019353 Battery (12 V‚ 7 Ah‚ VDS) FA2003-A1 11-1

A5Q00019354 Battery (12 V‚ 12 Ah‚ VDS) FA2004-A1 11-1

Page 247: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Order No. Index

4 © Siemens Switzerland Ltd 2010

Order No. Description Type Page

A5Q00019356 Battery (12 V‚ 26 Ah‚ VDS) FA2006-A1 11-1

A5Q00019357 Battery (12 V‚ 65 Ah‚ VDS) FA2008-A1 11-2

A5Q00019677 Battery (12 V‚ 17 Ah‚ VDS) FA2005-A1 11-1

A5Q00020131 MCL USB adapter FDUZ221 10-9

A5Q00020179 19" mounting kit FHA2016-A1 1-9, 2-28, 2-35

A5Q00020241 Radio gateway FDCW221 9-16

A5Q00020825 Power supply kit (150 W‚ A) FP2004-A1 1-8, 2-25

A5Q00021362 Air sampling smoke detection kit FDBZ292 9-10

A5Q00021363 Air flow tube 0.6 m FDBZ292-AA 9-11

A5Q00021364 Air flow tube 1.5 m FDBZ292-AB 9-12

A5Q00021366 Air flow tube 2.8 m FDBZ292-AC 9-12

A5Q00021367 Sealing kit for air flow tubes FDBZ292-AD 9-12

A5Q00021369 Mounting bracket FDBZ292-AF 9-12

A5Q00022897 Battery (12 V‚ 45 Ah‚ VDS) FA2007-A1 11-1

A5Q00023027 Cable kit (communication) FCA2014-A1 1-9, 2-28, 2-35

A5Q00023092 Alarm sounder beacon‚ orange FDS229-A 5-28

A5Q00023093 Alarm sounder beacon‚ red FDS229-R 5-27

A5Q00023101 Battery (12 V‚ 100 Ah‚ VDS) FA2009-A1 11-2

A5Q00023962 Matrix printer external DL3750+ 1-10, 2-29, 2-36

A5Q00023963 Typewriter ribbon A5Q00023963 12-2

A5Q00025158 Accessory set for FDCIO XCA1020 4-5

A5Q00026302 RT Interface Set FCI2005-N1 2-19

A5Q00031729-R Periphery board (1-loop) FCI2010-A1 13-2

A6E60500015 12-zone conventional unit (Head removal monitoring) FC1012-B 3-14

A6E60500020 Line extension card 4-zones FCA1001 12-3

A6E60500021 Display unit FCA1002 3-12, 3-16

A6E60500022 Sounder control card FCA1003 3-12, 3-16

A6E60500024 RT-isolation card FCA1005-D 3-12, 3-16

A6E60500026 Key switch kit FCA1007 3-7, 3-9,3-13, 3-17, 4-6

A6E60500027 Add-on line card FCA1007-B 12-3

A6E60500031 EOL resistor 3.9 kT (set of 10 pcs.) FCE1001 12-3

A6E60500032 Termination element‚ control line FCE1002 12-3

A6E60500033 EOL element for head removal monitoring FCE1003-B 12-3

A6E60500035 Cover for the FC1002-A‚ -B‚ -C FCH1002 12-3

A6E60500036 Cover for the FC1004-A‚ -B‚ -C FCH1004 12-3

A6E60500037 Cover for the FC1004-E FCH1004-E 12-4

A6E60500038 Cover for the FC1008-A‚ -B‚ -C FCH1008 12-4

A6E60500039 Cover for the FC1008-D FCH1008-D 12-4

A6E60500043 Cover for the FC1012-A‚ -B‚ -C FCH1012 12-4

A6E60500054 Power supply 3.5 A FCP1004-E 12-5

Page 248: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Order No. Index

5© Siemens Switzerland Ltd 2010

Order No. Description Type Page

A6E60500068 Universal accessory bag FCA1013 12-3

A6E60500069 Battery holder FCA1014 3-13, 4-5

BPZ:2473130001 Washer BPZ:2473130001 7-25, 9-37

BPZ:2785020001 Mallory buzzer AGS24.5 8-2

BPZ:3048160001 Insulating cap for alarm indicators BPZ:3048160001 7-25, 9-37, 12-8

BPZ:3169430001 Adapter frame for alarm indicator AI330 6-2, 7-9,7-24, 9-

36

BPZ:3496190001 Mounting bracket MVH1 7-26, 9-37

BPZ:3669510001 Test lamp for flame detectors LE3 9-4, 10-6

BPZ:3674840001 Ball and socket joint MWV1 9-4

BPZ:3679630001 Halogen lamp 12 V / 50 W BPZ:3679630001 12-10

BPZ:3680270001 Detector tester for heat detectors RE6T 10-3

BPZ:3680300001 Detector tester for smoke detectors RE6 10-2

BPZ:3685190001 Detector tester for linear smoke detectors RE10 9-8, 10-6

BPZ:3950450001 Mounting bracket MV1 9-3

BPZ:4242620001 Adapter base ZS/AGN24.5 8-1, 8-3

BPZ:4478380001 Bellow for RE6 DZZ1190 12-11

BPZ:4540830001 Base attachment for surface mounting DBZ1191 7-11, 9-29

BPZ:4585260001 Locking device DBZ1190 7-14, 9-18

BPZ:4588140001 Base attachment for humid environment DBZ1192 7-12, 9-19

BPZ:4588560001 Housing (empty) DCA1191 7-25, 9-25, 9-

27, 9-37

BPZ:4620910001 Test lamp for flame detectors 'Ex' StabexHF 9-32,10-6

BPZ:4677080001 Micro terminal 0.5 mm2‚ 4-pole DBZ1190-AA 5-7, 5-30, 5-33, 7-13, 9-

26–27,9-30

BPZ:4677110001 Protective cage DBZ1194 5-31, 7-12, 9-19

BPZ:4680660001 Detector base tester DZB1191 10-5

BPZ:4787710001 Reflector for long distance (prism) DLR1191 9-7

BPZ:4787840001 Reflector for short distance (foil) DLR1193 9-7

BPZ:4787970001 Detector heating DLH1191A 9-8

BPZ:4788490001 Reflector for middle distance (foil) DLR1192 9-7

BPZ:4837400001 Shunt Zener diode barrier SB3 9-27

BPZ:4837660001 Installation set Z3I410 9-27

BPZ:4843830001 Relay module with 1 contact Z3B171 1-9, 2-28, 3-7,

3-9, 3-13, 3-

17, 4-6,8-1, 8-3

BPZ:4851910001 Spare key DMZ1195 12-6

Page 249: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Order No. Index

6 © Siemens Switzerland Ltd 2010

Order No. Description Type Page

BPZ:4852140001 Heat detector collective 'Ex' DT1101A-Ex 9-28

BPZ:4852270001 Heat detector collective 'Ex' DT1102A-Ex 9-29

BPZ:4863650001 Base for collective detector series DB1101A 7-11, 9-11, 9-29

BPZ:4864330001 Detector designation plate DBZ1193A 5-31, 7-14, 9-19

BPZ:4926630001 Air flow tube for ASD-Duct DBZ1197-AA 9-11

BPZ:4930020001 Smoke detector‚ collective wide spectrum DO1101A 7-10

BPZ:4931090001 Alarm test filter (Absorption 77 %) TF04 9-9, 10-7

BPZ:4931700001 Heat detector DT1101A 7-10

BPZ:4931830001 Heat detector DT1102A 7-10

BPZ:4933030001 Filter for short distances (7... 10 m) DLF1191-AA 9-7

BPZ:4933160001 Filter for short distances (5... 8 m) DLF1191-AB 9-8

BPZ:4940140001 Acoustic base DBZ1195A 7-13

BPZ:4942050001 Spare glass neutral DMZ1196-AC 12-6

BPZ:4942340001 Connection terminal 2.5 mm2‚ 3-pole DBZ1190-AB 5-7, 5-12, 5-30, 5-33, 5-

42, 7-4,7-7, 7-14, 7-16, 9-13, 9-

24, 9-30

BPZ:4995140001 Air flow tube for ASD-Duct DBZ1197-AC 9-12

BPZ:5008010001 Smoke detector‚ wide spectrum collective 'Ex' DO1101A-Ex 9-28

BPZ:5011270001 Base attachment flat for surface mounting DBZ1191A-AA 7-11

BPZ:5017870001 Relay base DBC1191A-AA 7-13

BPZ:5081200001 Electronic unit for DC1192 DCA1192A 9-25

BPZ:5081460001 Optical smoke detector OP320C 7-3

BPZ:5081590001 Heat detector (rate of rise and maximum) HI320C 7-3

BPZ:5084500001 Terminal base for DC1192 DCB1192A 9-25

BPZ:5085990001 Base for Synova 300 series detectors SO320 7-4

BPZ:5090190001 Housing green‚ with glass and key DMA1192-AD 7-19–21

BPZ:5090640001 Smoke detector‚ collective wide spectrum DO1104A 9-11

BPZ:5093100001 Detector locking device TP320 7-5

BPZ:5154140001 Flashing signal lamp 'orange' ALB24.1OR 8-3

BPZ:5154270001 Flashing signal lamp 'red' ALB24.1R 8-3

BPZ:5162220001 Line termination EOL22(Ex) 9-24, 9-26

BPZ:5165360001 Base for infrared flame detectors DF119x DFB1190 9-31–32

BPZ:5166750001 Infrared flame detector unit collective 'Ex' DF1101-Ex 9-31

BPZ:5166880001 Bellow for RE6 RG320 10-3,12-11

BPZ:5167850001 Detector heating DBZ1190A-AC 7-14

BPZ:5221480001 Filter against external light influences DLF1191-AC 9-8

BPZ:5222870001 Housing red‚ with glass and key DMA1192-AA 7-19–21,

9-33–34

Page 250: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Order No. Index

7© Siemens Switzerland Ltd 2010

Order No. Description Type Page

BPZ:5223550001 Protective cover DMZ1197-AC 5-16, 5-18, 5-22, 5-24, 7-

23, 9-35

BPZ:5291410001 LED flat cable 50-wire‚ with 24 red LEDs F50F410 5-46

BPZ:5302660001 Rain hood DFZ1190 9-3

BPZ:5302950001 Alarm indicator housing incl. washer DJZ1193 7-25, 9-37

BPZ:5316470001 Heat detector (maximum) HI322C 7-4

BPZ:5355590001 Base attachment for wet environment DBZ1192-AA 7-12

BPZ:5358340001 Base attachment for surface mounting SOA322 7-4

BPZ:5364190001 Smoke detector‚ conventional multi-sensor OH320C 7-3

BPZ:5371040001 Alarm device AGT24.1 8-1

BPZ:5371170001 Alarm device AGN24.6 8-1, 8-3

BPZ:5464120001 Housing yellow‚ with glass and key DMA1192-AC 7-19–21

BPZ:5464250001 Housing blue‚ with glass and key DMA1192-AB 7-19–21

BPZ:5470680001 Protection seal DMZ1197-AD 5-16, 5-18, 5-22, 5-24, 7-

23, 9-35

BPZ:5644230001 U-rail TS35/7.5/288 TS35_288 2-20, 5-36, 5-42

BPZ:5644780001 U-rail TS35/7.5/122 TS35_122 2-20, 5-36, 5-42

BPZ:5757970001 Alarm device for explosion-hazard areas of zones 1 and 2 DB3 9-38

BPZ:5762200001 Radio test set DZW1171 9-21

BPZ:9300100001 Fire control panel for connection to 12 VDC supply GEN2-es 3-3

BPZ:9300110001 Fire control panel for connection to 12 VDC supply GEN2-en 3-2

BPZ:9300120001 Fire control panel for connection to 12 VDC supply GEN2-it 3-2

BPZ:9300130001 Fire control panel for connection to 12 VDC supply GEN2-se 3-2

BPZ:9300150001 Fire control panel for connection to 12 VDC supply GEN2-de 3-2

BPZ:9300170001 Fire control panel PCB for all languages MGEN2 3-3

BPZ:9300180001 Fire control panel for connection to 12 VDC supply GEN2-fr 3-2

BPZ:9300190001 Fire control panel for connection to 12 VDC supply GEN2-nl 3-2

DC1192-I__ Input/output module for galvanic isolation DC1192-I__ 9-25

DF11Ex__ Infrared flame detector collective 'Ex' DF11Ex__ 9-31

DM1101__ Collective manual call point DM1101__ 7-17

DM1103(Ex)__ Collective manual call point (double action) for explosion-hazard areas

DM1103(Ex)__ 9-33

DM1103__ Collective manual call point DM1103__ 7-20

DM1104(Ex)__ Collective manual call point (single action) for explosion-hazard areas

DM1104(Ex)__ 9-34

DM1104__ Collective manual call point DM1104__ 7-19

FC1002.. 2-zone conventional unit FC1002.. 3-6

FC1004.. 4-zone conventional unit FC1004.. 3-8

FC1008.. 8-zone conventional unit FC1008.. 3-10

FC1012.. 12-zone conventional unit FC1012.. 3-14

FC721.. Fire control panel (1-loop) in housing (Eco) FC721.. 1-3

FC722.. Fire control panel (2-loop) in housing (Standard) FC722.. 2-4

FC724.. Fire control panel (4-loop) FC724.. 2-11

FC726.. Fire control panel (modular) FC726.. 2-16

Page 251: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Order No. Index

8 © Siemens Switzerland Ltd 2010

Order No. Description Type Page

FDF__ Infrared flame detector FDF__ 9-2

FDL__ ASA Linear smoke detector FDL__ 9-5

FDM221__ Manual call point FDM221__ 5-8

FDM223__ Manual call point FDM223__ 5-20

FDM223H__ Manual call point 'Heavy Duty' FDM223H__ 5-23

FDM224__ Manual call point FDM224__ 5-14

FDM224H__ Manual call point 'Heavy Duty' FDM224H__ 5-17

FT724.. Fire terminal FT724.. 2-30

GEN2.. Fire control panel for connection to 12 VDC supply GEN2.. 3-2

MM8000xxx MM8000 danger management station MM8000xxx 14-2

S24217-G34-A1 Key S24217-G34-A1 9-21

S24218-B102-A1 Input/output module 'Transponder' FDCIO223 5-41, 9-23

S24218-F316-A1 Base for radio smoke detector DBW1171 9-18

S24218-F62-A5 Radio smoke detector complete DOW1171/DBW1171 9-17

S24218-F62-A6 Radio smoke detector DOW1171 9-18

S24218-F72-A1 Radio base SMF6120 9-20

S24236-B2502-A1 Repeater (SAFEDLINK) FN2002-A1 2-26

S54310-F1-A1 Optical smoke detector OP720 5-3

S54310-F2-A1 Multi-sensor smoke detector OH720 5-3

S54310-F3-A1 Heat detector (static) HI722 5-4

S54310-F4-A1 Heat detector (static+RoR) HI720 5-4

S54311-F2-A1 Housing orange‚ with glass and key FDMH293-O 5-14–15,

5-20–21

S54312-F1-A1 Input module FDCI221 5-37

S54312-F2-A1 Input/output module FDCIO221 5-38

S54312-F3-A1 Housing for input/output modules FDCH221 2-20, 5-42, 9-23

S54312-F6-A1 Multi-line separator module FDCL221-M 5-36

S54319-F1-A1 Detector base flat‚ addressable FDB222 5-29

S54319-F10-A1 Sealing element FDBZ295 5-29

S54319-F11-A1 Detector base with loop contact DB721 5-5

S54319-F5-A1 Sounder base DBS720 5-6, 5-32

S54319-F6-A1 Detector exchanger DX791 10-2

S54319-F8-A1 Detector base seal RS720 5-6, 5-32

S54319-F9-A1 Detector locking device LP720 5-5

S54370-F10-A1 Addressable alarm indicator FDCAI221 6-2

S54370-F3-A1 Alarm indicator - Surface FDAI92 6-1, 7-24

S54370-F4-A1 Alarm indicator - Surface for explosion-hazard areas FDAI92-Ex 9-36

S54370-F5-A1 Alarm indicator - Flush FDAI93 6-1, 7-25

S54370-F6-A1 Alarm indicator - Flush FDAI93-Ex 9-36

S54370-F7-A1 Alarm indicator - Door frame AI91C 7-9

S54370-F8-A1 Alarm indicator - Surface AI92C 7-9

S54370-F9-A1 Alarm indicator - Door frame FDAI91 6-1, 7-24

S54370-N4-A1 Solo719 Adapter for FDUM29x RE7T-A 10-4

S54370-N5-A1 Solo760 Battery for RE7T RE7T-B 12-11

S54370-N6-A1 Solo725 Charger for RE7T RE7T-C 12-11

S54370-S3-A1 Solo461 Heat detector tester kit RE7T 10-3

Page 252: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Order No. Index

9© Siemens Switzerland Ltd 2010

Order No. Description Type Page

S54371-F6-A1 Manual call point with glass plate FDM1101-RG 7-15

S54371-F6-A2 Manual call point with resettable plastic element FDM1101-RP 7-15

S54371-F6-A3 Manual call point with glass plate FDM1101A-RG 7-6

S54371-F6-A4 Manual call point with resettable plastic element FDM1101A-RP 7-6

S54380-B11-A1 EVAC module FCA1009-E 12-3

S54380-C1-A10 Main board for 8-zone units FCM1008 12-4

S54380-C1-A20 FCM1008-D Main board 8 zone CH FCM1008-D 12-4

S54380-C1-A30 FCM1008-E Main board 8 zone NL FCM1008-E 12-4

S54380-C2-A1 2-zone conventional unit (Standard) FC1002-A 3-6

S54380-C2-A10 2-zone conventional unit (Head removal monitoring) FC1002-B 3-6

S54380-C2-A20 2-zone conventional unit (Nordic) FC1002-C 3-6

S54380-C3-A1 4-zone conventional unit (Standard) FC1004-A 3-8

S54380-C3-A10 4-zone conventional unit (Head removal monitoring) FC1004-B 3-8

S54380-C3-A20 4-zone conventional unit (Nordic) FC1004-C 3-8

S54380-C3-A30 4-zone conventional unit (NL) FC1004-E 3-8

S54380-C4-A1 8-zone conventional unit (Standard) FC1008-A 3-10

S54380-C4-A10 8-zone conventional unit (Head removal monitoring) FC1008-B 3-10

S54380-C4-A20 8-zone conventional unit (Nordic) FC1008-C 3-11

S54380-C4-A30 8-zone conventional unit (CH) FC1008-D 3-11

S54380-C4-A40 8-zone conventional unit (Evacuation) FC1008-E 3-11

S54380-C5-A1 12-zone conventional unit (Standard) FC1012-A 3-14

S54380-C5-A10 12-zone conventional unit (Head removal monitoring) FC1012-B 3-14

S54380-C5-A20 12-zone conventional unit (Nordic) FC1012-C 3-15

S54380-C8-A1 Main board 2-zones FCM1002 12-4

S54380-C9-A1 Main board 4-zones FCM1004 12-4

S54380-C9-A10 FCM1004-E Main board 4 zone NL FCM1004-E 12-4

S54380-F10-A1 Cover for the FC1008-E FCH1008-E 12-4

S54390-A4-A1 Main board XCM1002 12-5

S54390-A5-A1 Multi-zone extension module XCA1030 4-5

S54390-A6-A1 Common multi-zone module XCA1031 4-5

S54390-B10-A1 Cover set XCH1003-A 12-5

S54390-B11-A1 Cover set XCH1005-A 12-5

S54390-B7-A1 Display adapter XCA1002-1 12-5

S54390-B8-A1 Display adapter XCA1002-2 12-5

S54390-B9-A1 Cover set XCH1001-A 12-5

S54390-C1-A1 Extinguishing panel Standard XC1001-A 4-2

S54390-C2-A1 Extinguishing panel Rack XC1003-A 4-4

S54390-C3-A1 Extinguishing panel Comfort XC1005-A 4-3

S54390-N12-A1 Transformer for 2/4-zone units FCP1002 12-4

S54390-Z15-A1 Repeater display XT1002-A1 4-7

S54390-Z16-A1 Repeater display XT1001-A1 4-7

S54400-A14-A1 Mimic display driver (EVAC) FT2003-N1 2-24

S54400-A15-A1 EVAC-NL connector board FTI2002-N1 2-24

S54400-A6-A1 I/O card (programmable) FCI2008-A1 2-18

S54400-B70-A1 Housing (Standard) FH7202-Z3 1-7, 2-22

S54400-B71-A1 Housing (Comfort) FH7203-Z3 2-22–23

S54400-B72-A1 Housing (Eco) FH7201-Z3 1-6, 2-21, 2-33

S54400-B74-A1 Cover cap (without print) FHA7202-A3 12-1

S54400-B77-A1 Cover cap (Cerberus) FHA7201-A3 12-1

S54400-B79-A1 Mounting kit for housing (Comfort) FHA2029-A1 2-27

Page 253: Cerberus PRO Answers for infrastructure. Cerberus PRO ... · product catalog Cerberus PRO product catalog Fire safety products and accessories. Table of Contents ... Answers for infrastructure

Order No. Index

10 © Siemens Switzerland Ltd 2010

Order No. Description Type Page

S54400-B81-A1 Mounting kit for housing (Large Extension) FHA2030-A1 2-27

S54400-B86-A1 Housing (Large) FH7205-Z3 2-23

S54400-B89-A1 Housing (Large Extension) FH7204-Z3 2-23

S54400-B90-A1 Battery holder FCA1016 3-7, 3-9

S54400-C29-A1 Fire control panel (2-loop) in housing (Comfort) with 2 LED indi-cators

FC722-ZE 2-8

S54400-C29-A2 Fire control panel (2-loop) in housing (Comfort) FC722-ZA 2-7

S54400-C29-A3 Fire control panel (2-loop) in housing (Comfort) with EVAC oper-ating unit

FC722-HA 2-9

S54400-C29-A4 Fire control panel (2-loop) in housing (Standard) with 1 LED indi-cator

FC722-YZ 2-6

S54400-C29-A5 Fire control panel (2-loop) in housing (Standard) FC722-ZZ 2-5

S54400-C30-A1 Fire control panel (4-loop) with EVAC operating unit FC724-HA 2-14

S54400-C30-A2 Fire control panel (4-loop) FC724-ZA 2-12

S54400-C30-A3 Fire control panel (4-loop) with 2 LED indicators FC724-ZE 2-13

S54400-C31-A1 Fire terminal with EVAC operating unit FT724-HZ 2-31

S54400-C31-A2 Fire terminal FT724-ZZ 2-30

S54400-C32-A1 Fire control panel (1-loop) in housing (Eco) with EVAC operating unit

FC721-HZ 1-5

S54400-C32-A2 Fire control panel (1-loop) in housing (Eco) FC721-ZZ 1-4

S54400-C32-A3 Fire control panel (1-loop) in housing (Eco) with 1 LED indicator FC721-YZ 1-4

S54400-C87-A1 Fire control panel (modular) FC726-ZA 2-17

S54400-F34-A1 Floor repeater terminal FT2010-C1 5-44

S54400-F75-A1 Operating add-on (2xLED ind.) FCM7211-Y3 2-23–24,

2-33,12-1

S54400-F76-A1 Operating add-on FCM7210-Z3 12-1

S54400-F78-A1 Operating add-on (2xEVAC) FCM7221-H3 2-24

S54400-F88-A1 Operating add-on (4xLED ind.) FCM7212-Y3 2-24, 2-33, 12-2

S54400-F94-A1 Ethernet switch FN2008-A1 2-27

S54400-F95-A1 Security module FN2009-A1 2-27

SMF__ Manual call point SMF__ 9-20

V24069-Z112-A1 Lithium battery 3.6 V / 2.1 Ah V24069-Z112-A1 9-20

V24217-C1218-W100 Manual call point SMF121 9-20–21

V24217-C1218-W200 Manual call point SMF121 9-20–21

V24230-Z6-A4 Power supply (150 W) SV 24V-150W 12-1

VLF-250-SIE Aspirating smoke detector with display LaserFOCUS VLF-250 9-14

VLF-500-SIE Aspirating smoke detector with display LaserFOCUS VLF-500 9-15