challenger 10-250kva serv man_ing

156
SERVICE MANUAL CHALLENGER SERIES 10 - 250 KVA

Upload: ermel-guaman

Post on 22-Nov-2015

99 views

Category:

Documents


37 download

TRANSCRIPT

  • SERVICE MANUALCHALLENGER SERIES

    10 - 250 KVA

  • AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    SERVICE MANUALCHALLENGER SERIES10-250 KVAAG-SD-36Document Y.No:1 Rev:0

  • AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    About The ManualThis manual is prepared for the users of Challenger 10-250 kVA.Companion ManualsFor more info about this device and its options, please visit www.makelsan.com.tr .Updates

    Please, visit www.makelsan.com.tr for updates. Always use the latest manuals.

  • CHALLENGER SERIES 10-250 KVA CONTENTS

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Contents1. SAFETY AND WARNINGS.......................................................................................................................81.1. Warnings ............................................................................................................................... 81.2. Clearance and Access .......................................................................................................... 91.3. Storage ................................................................................................................................... 91.4. Shipment ............................................................................................................................... 9

    2. PRODUCT DESCRIPTION.................................................................................................................... 102.1. General Information ......................................................................................................... 142.1.1. Static Transfer Switch............................................................................................... 142.1.2. Battery Temperature Regulation ........................................................................... 15

    2.2. UPSs Operation Modes..................................................................................................... 152.2.1. Normal (Online) Mode .............................................................................................. 152.2.2. Battery(stored) Mode ............................................................................................... 162.2.3. Bypass Mode ............................................................................................................... 162.2.4. Auto Restart Mode ..................................................................................................... 162.2.5. Maintenance Mode .................................................................................................... 17

    2.3. Battery Management......................................................................................................... 172.3.1. Normal Operation Mode........................................................................................... 172.3.2. Advanced Level Functions (Automatic Battery Test) ......................................... 18

    2.4. User Panel ........................................................................................................................... 182.4.1. Openning Screen ........................................................................................................ 212.4.2. Main Menu................................................................................................................... 212.4.3. Navigating Through the Menus............................................................................... 212.4.4. Password Protected Menus ..................................................................................... 222.4.5. Control Menu .............................................................................................................. 222.4.6. Status Menu................................................................................................................. 232.4.7. Setup Menu ................................................................................................................. 252.4.8 Logging Menu................................................................................................................... 28

    3. INSTALLATION ...................................................................................................................................... 293.1. Single Mode Installation................................................................................................... 293.1.1. Warnings ..................................................................................................................... 293.1.2. Pre-installation check up ......................................................................................... 29

  • CHALLENGER SERIES 10-250 KVA CONTENTS

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    3.1.3. Positioning .................................................................................................................. 303.1.3.1. Positioning of UPS.............................................................................................. 303.1.3.2. External Battery Configration ......................................................................... 30

    3.1.4 Transportation Type of Cabinets.................................................................................. 343.1.5 Main, Load and Battery Connections ........................................................................... 343.1.5.1 External Protection .................................................................................................. 353.1.5.2 Cable and Fuse Selection ......................................................................................... 353.1.5.3 Connecting the Cables.............................................................................................. 353.1.5.4 Battery Connections .......................................................................................... 40

    Battery Assembly for 28.............................................................................................................. 40

    Battery Assembly for 28x2......................................................................................................... 41

    Battery Assembly for 38.............................................................................................................. 41

    Battery Assembly for 38x2.......................................................................................................... 42

    Battery Assembly for 40............................................................................................................ 42

    3.1.5.4.1 External Battery Installation Procedure and Connection...................... 443.1.5.5. Menu Setup After Battery Installation........................................................... 473.1.5.6 Control and Communication Cable Connections ......................................... 47

    3.2 Parallel Installation .......................................................................................................... 474 OPERATION ............................................................................................................................................ 504.1 Operation Procedure ........................................................................................................ 504.1.1 Circuit Breakers ............................................................................................................... 504.1.2 First Start-Up .............................................................................................................. 514.1.3 Testing of Types of UPS Operation ......................................................................... 524.1.3.1 Switching from Online Mode to Battery Mode ............................................. 524.1.3.2 Switching from Online Mode to Static Bypass Mode................................... 524.1.3.3 Switching from Static Bypass Mode to Online.............................................. 534.1.3.4 Switching from Online Mode to Maintenance Bypass Mode ..................... 54

    4.1.4 Performing a Complete Shutdown ......................................................................... 554.1.5 EPO (Emergency Power Off) .................................................................................... 564.1.6 RS232 Serial Communication Installation and investigation ........................... 56

    Challenger Parallel Operation Guide..................................................................................................... 57A. Check if the devices can be used in parallel mode. .................................................................. 57B. Check the positioning of the devices. ............................................................................................ 57

  • CHALLENGER SERIES 10-250 KVA CONTENTS

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    C. Make the electrical connections ..................................................................................................... 57D. Set the software for parallel operation. ....................................................................................... 59E. Operation ................................................................................................................................................ 61Master/Slave configuration ...................................................................................................................... 61

    Parallel start-up........................................................................................................................... 61

    Switching to static bypass ........................................................................................................... 63

    Stopping/Removing a single UPS............................................................................................... 63

    Stopping all UPS.......................................................................................................................... 64

    Troubleshooting for Parallel Mode ........................................................................................................ 645 ELECTRONIC BOARDS ......................................................................................................................... 67

    Main Control Board........................................................................................................................ 67

    PFC Input Board D09-3.V1R1 ....................................................................................................... 71

    Battery Input Board........................................................................................................................ 75

    Fuse Board ....................................................................................................................................... 78

    Signal Flow Diagram........................................................................................................... 80

    HV DC TO DC SMPS..................................................................................................................... 81

    Signal Flow Diagram........................................................................................................... 85

    Main Board Power Supply ............................................................................................................. 86

    Front Panel Board ........................................................................................................................... 90

    IGBT Driver Board ......................................................................................................................... 95

    Signal Flow Diagram......................................................................................................... 101

    By-pass Board................................................................................................................................ 102

    IGBT Driver Connection Board................................................................................................... 109

    Contactors ...................................................................................................................................... 113

    Firmware Update for Challenger...........................................................................................................113DRY CONTACT R335...................................................................................................................................115

    Precautions..................................................................................................................................... 115

    Installation ..................................................................................................................................... 115

    Operation ....................................................................................................................................... 118

    Relay info................................................................................................................................ 118

    Isolated input info.................................................................................................................. 118

    Pin functionality ............................................................................................................................ 119

    Dry contact functions.......................................................................................................... 120Connection examples..................................................................................................................... 121

  • CHALLENGER SERIES 10-250 KVA CONTENTS

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    LED DEFINITIONS ................................................................................................................ 1226 EXPLANATIONS OF LOGGING .........................................................................................................133

    Fault Alarms ......................................................................................................................... 141SPARE PART LISTS............................................................................................................... 148

    7 TECHNICAL SPECIFICATIONS .........................................................................................................154Contact Information...................................................................................................................................156

  • CHALLENGER SERIES 10-250 KVA SAFETY AND WARNINGS

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    1.SAFETY AND WARNINGS1.1. WarningsThis manual must be read before installing the UPS. The device can be installed and started onlyby Makelsan staff.Installation or start-up by unauthorized personal may cause damage to the device and seriousinjury or death.The UPS is designed to be used in continuous vertical fixed position applications.

    Warning:

    THE UPS MUST BE USED WITH GROUND CONNECTION.Connect the ground cable before connecting the mains.Ground currents may be as high as 0.4ATHE UPS MUST BE DISCONNECTED FROM THE MAINS AND BATTERIES BEFORESERVICING. ALSO WAIT FOR AT LEAST 5 MINUTES FOR THE DC BUSCAPACITORS TO DISCHARGE AFTER POWER OFF.

    Service and MaintenanceAll servicing and maintenance is done internally. All parts in the device can be serviced andreplaced only by a trained technician.preventative maintenance is recommended at least once a year from the installation byauthorized technical staff. (This service will be provided for a fee by our authorizedMAKELSAN staff.)

    Battery Voltage may rise up to 700 V DC!

    Battery terminal voltages can be at hazardous levels (700Vdc). Nobody except trained staff shouldtouch batteries.Batteries certainly must not be thrown into fire. Regarding the topic of batteries which are deadand defected: The waste batteries must definitely not be thrown to nature. They must delivered toMAKELSAN authorized technicians or to the foundations which are authorized for collectingwaste batteries by the Ministry of Environment.

    CHALLENGER SERIES 10-250 KVA SAFETY AND WARNINGS

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    1.SAFETY AND WARNINGS1.1. WarningsThis manual must be read before installing the UPS. The device can be installed and started onlyby Makelsan staff.Installation or start-up by unauthorized personal may cause damage to the device and seriousinjury or death.The UPS is designed to be used in continuous vertical fixed position applications.

    Warning:

    THE UPS MUST BE USED WITH GROUND CONNECTION.Connect the ground cable before connecting the mains.Ground currents may be as high as 0.4ATHE UPS MUST BE DISCONNECTED FROM THE MAINS AND BATTERIES BEFORESERVICING. ALSO WAIT FOR AT LEAST 5 MINUTES FOR THE DC BUSCAPACITORS TO DISCHARGE AFTER POWER OFF.

    Service and MaintenanceAll servicing and maintenance is done internally. All parts in the device can be serviced andreplaced only by a trained technician.preventative maintenance is recommended at least once a year from the installation byauthorized technical staff. (This service will be provided for a fee by our authorizedMAKELSAN staff.)

    Battery Voltage may rise up to 700 V DC!

    Battery terminal voltages can be at hazardous levels (700Vdc). Nobody except trained staff shouldtouch batteries.Batteries certainly must not be thrown into fire. Regarding the topic of batteries which are deadand defected: The waste batteries must definitely not be thrown to nature. They must delivered toMAKELSAN authorized technicians or to the foundations which are authorized for collectingwaste batteries by the Ministry of Environment.

    CHALLENGER SERIES 10-250 KVA SAFETY AND WARNINGS

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    1.SAFETY AND WARNINGS1.1. WarningsThis manual must be read before installing the UPS. The device can be installed and started onlyby Makelsan staff.Installation or start-up by unauthorized personal may cause damage to the device and seriousinjury or death.The UPS is designed to be used in continuous vertical fixed position applications.

    Warning:

    THE UPS MUST BE USED WITH GROUND CONNECTION.Connect the ground cable before connecting the mains.Ground currents may be as high as 0.4ATHE UPS MUST BE DISCONNECTED FROM THE MAINS AND BATTERIES BEFORESERVICING. ALSO WAIT FOR AT LEAST 5 MINUTES FOR THE DC BUSCAPACITORS TO DISCHARGE AFTER POWER OFF.

    Service and MaintenanceAll servicing and maintenance is done internally. All parts in the device can be serviced andreplaced only by a trained technician.preventative maintenance is recommended at least once a year from the installation byauthorized technical staff. (This service will be provided for a fee by our authorizedMAKELSAN staff.)

    Battery Voltage may rise up to 700 V DC!

    Battery terminal voltages can be at hazardous levels (700Vdc). Nobody except trained staff shouldtouch batteries.Batteries certainly must not be thrown into fire. Regarding the topic of batteries which are deadand defected: The waste batteries must definitely not be thrown to nature. They must delivered toMAKELSAN authorized technicians or to the foundations which are authorized for collectingwaste batteries by the Ministry of Environment.

  • CHALLENGER SERIES 10-250 KVA SAFETY AND WARNINGS

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Fire extinguishing equipment must be kept nearby the UPS.1.2. Clearance and Access

    ClearanceThere is no any air inlet or outlet grill on the left or right sides of our 10-250 kVA UPS. All air goesin to UPS from the front and is evacuated from the rear through fans. There must be spaces atleast 1 meter at the front side of UPS. Should not be permanent or temporary use within the limitsspecified. Otherwise, the UPS performance will decrease.AccessOperator reaches UPS via front panel on 10-250 kVA UPS. Therefore, enough area must be left foroperator.. There is no limit to the sides of the device.

    1.3. Storage

    UPS should be kept in a room or area where is protected from excessive moisture and heat beforecommissioning.WARNING:Unused batteries must be charged at regular intervals. This time interval is determined by thebattery supplier. Charging can be performed periodically by connecting to a proper mains for awhile.

    1.4. ShipmentCarrying vehicles must have enough features and characteristics to carry UPS.Be more careful of sudden movements, especially when batteries are inside of cabinet.Move the UPS as rarely as possible.

  • CHALLENGER SERIES 10-250 KVA PRODUCT DESCRIPTION

    AG-SD-36 Rev. No:0 Rev. Date:1511.2012 Publish No:1

    2. PRODUCT DESCRIPTIONFront Cover View ( 80-200kVA)

    1 RS232 Serial Interface for Inverter2 RS232 Serial Interface for Rectifier3 Input Circuit Breaker4 External Bypass Circuit Breaker5 Output Circuitr Breaker6 Optional Card Slots

    CH80120EN04R0

  • CHALLENGER SERIES 10-250 KVA PRODUCT DESCRIPTION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Rear view(10-60kVA)

    CH1060TR04R0

  • CHALLENGER SERIES 10-250 KVA PRODUCT DESCRIPTION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    1 Rectifier / Charger-Inverter Cooling Fans

    2 Winding Hot Air Evacuation Channel

    3 Mains (Input) Breaker

    4 Mains (Input) Connection Terminal

    5 Ground Connection

    6 Input-Output-Battery Cable Fixing Terminals

    7 Output Connection Terminals

    8Battery Rapid Fuses and Battery ConnectionTerminals

    9 Output Circuit Breaker

    10 External ( Maintanance) Bypass Breaker

    11 RS232 Terminal for Communication Socket of Rectifier

    12 RS232 Terminal for Communication Socket of Inverter

    13 Optional card slots14 Optional card slots15 Optional Parallel Port Terminal

  • CHALLENGER SERIES 10-250 KVA PRODUCT DESCRIPTION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Electrical Connection

  • CHALLENGER SERIES 10-250 KVA PRODUCT DESCRIPTION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    2.1. General InformationGeneral operation topology of Challenger Series UPS can be recognized as follows.

    The UPS is connected to the mains voltage through the CB1 breaker. As DC bus is ramped up, therectifier starts to operate and converts the AC mains to DC Voltage. When the mains voltage is notavailable, the DC/DC booster pumps the battery voltage to the necessary level. DC DC bus voltageis then converted to mains synchronized AC voltage by the inverter. This is a high quality voltage.Generated AC power is applied the loads after passed from static semi-conductor switches andoutput (load) breakers.2.1.1. Static Transfer SwitchSome blocks are named as static switches as can be seen above. These blocks consist of inverseparallel connected thyristors. These switches, which are under the control of the mainboardcontrol unit (DSP), provides controlling of supplying the loads through either mains or inverters.The loads are supplied through inverter during the normal operating mode. Therefore, Inverterstatic switches are active if there is no problem with the system.

    User can switch the UPS between mains and inverter by using front panel. While the loads are feddirectly by mains with the order of user, in case of either power off or mains values out oftolerances, the UPS will start to supply the loads through battery mode.If the user wants, can provide mains to feed load continuously by switching on the maintenancebypass without making adjustment on the front panel. Later on, the user can make the input andoutput switch fuses short circuit.If user wants, can provide mains to feed load continuously by switching on the maintenancebypass without making adjustment on the front panel. Later on, the user can make the input andoutput switch fuses short circuit.

  • CHALLENGER SERIES 10-250 KVA PRODUCT DESCRIPTION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    If Maintenance or repair are necessary, maintenance switch must be turned "ON" before the inputand output breakers are switched ON. After that, input and output of UPS are switched OFFrespectively.NOT: In the meantime, the loads are unprotected against the power-off, damage, twist etc.problems.

    2.1.2. Battery Temperature RegulationOptional temperature sensor is given with external battery cabinet. Battery temperature areperceived by mentioned temperature sensor. UPS adjusts battery charge parameters according tothe information of the perceived temperature. These parameters can easily be adjusted via LCD orTELNET interface by authorized staff of MAKELSAN.In this case, We recommend you to order "External Battery Temperature Measurement Kit" todetect the temperature.2.2. UPSs Operation ModesChallanger series UPS's on-line and has a double loop structure. Our products operate in thefollowing modes: Online Mode Battery Mode Bypass Mode Auto restart Mode Maintenance Mode

    2.2.1. Normal (Online) ModeIn this mode, UPS supplies the load through the inverters. Rectifier unit is supplied by the ACmains. Inverter and battery charger units are energized by the generated DC supply.

  • CHALLENGER SERIES 10-250 KVA PRODUCT DESCRIPTION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    2.2.2. Battery(stored) ModeUPS runs on battery mode when the mains voltage is bad.Battery Voltage is boosted for thesufficient Dc bus voltage.

    2.2.3. Bypass ModeIn an overload condition, or if there is a problem with the double conversion, the loads are fed bythe bypass line.UPS switches to AC supply from inverter for that by static switches. Inverter must besynchronized with the mains supply for these transitions to be seamless.This transitions mighttake 15 ms depending on the type of load if inverter output is not synchronized with the mains.

    2.2.4. Auto Restart ModeUPS supplies its critical loads up to end of discharge voltage level due to any mains failure. UPSfeeds critical loads untill end of battery discharge voltage level caused by any mains failure. Upswill operate until batteries charging process completing after that will be switched off. UPS canoperate by itself in specified time after mains turned back to normal mode. In this case, UPS keepsoperating proper as long as UPS voltage being in accordance criterias. For Challenger Series UPS,this feature is not activated as factory initial setups.

  • CHALLENGER SERIES 10-250 KVA PRODUCT DESCRIPTION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    2.2.5. Maintenance ModeIn maintenance mode, UPS equipped with a switch capable for not to be interrupted of the loads.This switch was choosen to meet the full load.

    2.3. Battery Management

    Lead Acid Batteries are used with UPSs as internal.2.3.1. Normal Operation Mode

    Constant Charge CurrentCurrent is limited to 0.1C untill the float reaches to charge voltage. (adjustable between 0.05C -0.25C.) The applied current can not exceed maximum charge power.Float ChargeDepending on the battery discharge current the third percent energy of the battery is charged atthis level. Thanks to this level, batteries are kept ready for use at the highest capacity. For lead-acid batteries, this voltage varies between values 2.2-2.35 V/cell This voltage may differ slightlywith temperature adaptation. Option of setting this coefficient is provided with our UPS. If thetemperature sensor is used, it is recommended to use.Deep Discharge ProtectionWhile the system operates on battery mode, if battery voltage has dropped below the dischargelevel UPS shuts down and stops absorbing energy from the batteries. This value varies between1.6-1.75 V/cell for Lead-Acid batteries, and for Ni-Cd batteries between 0.9-1.1 V / cell.Low Battery WarningWhile the system operates in battery (stored) mode, according to actual loads if the batterycapacity drops below its 40% value, it will give audible and visible alarms. This percentage valueis adjustable for user between 20%-70%.

  • CHALLENGER SERIES 10-250 KVA PRODUCT DESCRIPTION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    2.3.2. Advanced Level Functions (Automatic Battery Test)

    The auto battery test discharges 30% of the battery energy in a user defined period (default is 90days). This period can be adjusted between 30-360 days. Test reports the battery condition asgood or replace. Results of the latest test can be seen on the battery screen from the statusmenu.WARNING: If the test result is replace, then the batteries are completely drained during thetest. This situation may cause the load remained unpowered in case of mains voltage is out of thelimits or mains power off.This test can be started by command from front panel monitor, via TELNET interface, via RS232smart communication or via MAKNET (SNMP, see the options).It is checked that if the batteries can supply the minimum back-up time needed in case of the firstpower-off by using the results of all these tests. Checking the test results with a regular period isrecommended.

    2.4. User Panel

    User panel consists of mimic diagram, LCD screen, EPO button and menu keys. The UPS can becontrolled via this panel.

  • CHALLENGER SERIES 10-250 KVA PRODUCT DESCRIPTION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    1 Rectifier indicator LEDFlashes while the DC bus is ramping up. Illuminates when Rectifier works.2 AC/DC module (Rectifier)3 Boost mode indicator LEDIlluminates in battery mode. Flashes when UPS is started up through batteries.4 Battery charge indicator LEDIlluminates while the batteries are charging.5 Battery module6 DC/AC module (Inverter)7 Mains bypass indicator LEDIlluminates while the loads are fed through bypass line.8 Inverter static switch indicator LEDIlluminates when the load is fed by the inverter9 Alarm/Warning indicator LED10-13 Menu keys14 EPO (Emergency Power Off ) Button

  • CHALLENGER SERIES 10-250 KVA PRODUCT DESCRIPTION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Menu Flow Chart Control MenuStatus MenuSetup MenuLogging MenuService Menu

    CONTROLStartStopOutput BypassOutput UPSQuick Battery TestBattery Status TestStop Battery Test

    STATUSMainsOutputBypassBatteryTemperaturesInverterAlarmsDeviceInformation

    SETUPDate & TimeBattery Install DateAuto RestartAuto Battery TestScreenWarning BeepLanguageCommunication

    LOGGINGLog CodeDateTimeLog RecordsInformation

    MAINSVoltage(phase-neutral)FrequencyCurrentVoltage(phase-phase)Aktive PowerApparent PowerPower FactorPositive BusNegatif Bara

    WARNINGSActualAlarms

    BATTERYVoltageCurrentTemperatureCharge PercentageRemaining Back up(Autonomy) TimeLast Test ResultNext Test Date

    INVERTERVoltageCurrentActive Power

    TEMPERATURERectifierInverterAmbientBatteryBypassChoke

    BYPASSFrequencyCurrentVoltage (phase-neutral)Voltage (phase-phase)

    DEVICE INFORMATIONSoftware VersionsSerial NoAppearant PowerVoltageFrequencySerial Arm x BatteryQuantitiesBattery Capacity

    OUTPUTFrequencyCurrentVoltageActive PowerReactive PowerPower FactorApparent PowerLoad PercentageCrest Factor

    SERVICE**Detailedservicemenu can beobserved byonlyauthorisedstaff.

    Main ScreenManufacturer Device NameDate - TimeLoad Status as PercentBattery Charge Status as PercentRemaining Back up (Autonomy)TimeUPS Mode Actual AlarmsMain Menu Titles

  • CHALLENGER SERIES 10-250 KVA PRODUCT DESCRIPTION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    2.4.1. Openning Screen

    When the front panel monitor is turned on,firstly opening screen is observed.Manufacturer Device Name, Date Time,Load Status as Percent, Battery Charge Statusas Percent, Remaining Back up (Autonomy)Time, UPS Mode Actual Alarms, Main MenuTitles can be observed here.Last event (log) isshown at the bottom left and active alarmslist that appears 2,5 second intervals areshown at the bottom right. If no button ispressed for 5 minutes, system returns to theopening screen.2.4.2. Main MenuPress ENT button to switch to the main menu.

    2.4.3. Navigating Through the Menus Use UP and DOWN keys to move the cursor arrow.Press enter to open a sub- menu. Press ESC to goback to the previous menu. Control sub-menu isshown on left.Hold the UP or DOWN key to navigate between thesub- menus.

  • CHALLENGER SERIES 10-250 KVA PRODUCT DESCRIPTION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Some menus have changeable options likeON/OFF, durations or quantities. To changesome setups in such a menu, press ENTERto choose the variable, use up and downkeys. To change the value, press ENTER toset the new value, press ESC to cancel.2.4.4. Password Protected Menus Some menus such as the control menu arepassword protected.Press UP and DOWN toset eachdigit and press ENTER to confirm.

    User level password is: 0000 (zero-zero-zero-zero)

    2.4.5. Control Menu

    In the control menu, you can do one of the following: Start Start the UPS Stop Stop the UPS Switch to BYPASS Switch to static BYPASS mode Switch to UPS Switch to online mode Bat. Quick Test Start the quick battery test Bat. Capacity Test Start the deep battery test Stop Battery Test Stop the battery test

  • CHALLENGER SERIES 10-250 KVA PRODUCT DESCRIPTION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Battery status test, drains the 30% of battery energy and reports batteries which has morecapacity than 15-30% as Good, less capacity than 15% as Replace according to the testresults.After UPS is started and every 24 hours, it makes a quick battery test ,if test counter value is zero(0).Note: Batteries must have been fully charged and kept in floating situation for at least one hourbefore performing the quick battery test.Status on the System > Battery > Remaining Time can be seen.

    If Stop Battery Test is chosen from the menu, the UPS cancels the battery test and goes back tothe previous operating state.2.4.6. Status MenuMains Output, Bypass, Battery, Temperatures, inverter, Alarms and UPS information can be seenon this menu.

  • CHALLENGER SERIES 10-250 KVA PRODUCT DESCRIPTION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    MainsUP, I, Hz Voltage (phase-neutral), current and frequency of each phase.UL, S, P Voltage(phase phase), reactive and active power of each phase.PF, U, D Power factor, positive DC bus and negative DC Bus of each phase.OutputUP, I, Hz Voltage(phase-neutral), current and frequency of each phase.UL, S, P Voltage(phase phase), reactive and active power of each phase.PF, L, CF Load percentage for each phase and crest factor.BypassUP, I, Hz Voltage(phase-neutral), current and frequency of each phase.UL Voltage of each phase (phase to phase).BatteryMode Battery Mode.U, I, T Battery Voltage, Charge Current and Temperature.Charge % Charge Percentage.Battery Time The estimated battery run time with current load.Last Test Result Test type, test number, test date and time. Battery capacity and condition.Next Test Time Next test dateTime Timer countdown for the next test availability.TemperatureC,C,C,C,C,C,C Rectifier, inverter, charger, ambient, battery and thyristor temperatures.InverterU, I, P Voltage, current and frequency of each phase.Alerts UPS alarms.

    UPS Information Software Version of inverter,rectifier,CPLDand front panel; UPS's apparent power(kVA),nominal output voltage (phase-neutral),nominal output frequency (Hz); number ofbatteries in parallel , serial and batterycapacity can be seen via version menu.

  • CHALLENGER SERIES 10-250 KVA PRODUCT DESCRIPTION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    2.4.7. Setup MenuThe following adjustments can made on setup menu:Date & Time To set date and time, use up and down keys tochoose the variable you want to set.

    Then use up and down keys to set the value,and press ENTER.

    Battery Replacement Date Set the date of battery installation through thismenu.

  • CHALLENGER SERIES 10-250 KVA PRODUCT DESCRIPTION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Auto Restart On the battery mode, UPS operates untilcharging process completed. the device turnsoffat the end of battery discharge process. Auto-restart can be used to restart the UPSautomatically when the mains comes back tolimits.Turn on auto-restart and set the time todefine when the device will be started afterthe mains is normal.Auto Battery Test This function can be turned on to startthe user independent battery tests.Time interval sets when the test will be repeated.

    Note: Auto Battery test is the equivalent ofbattery quick test.

    Screen Change the screen contrast to make it morevisible on different environmental conditions.

  • CHALLENGER SERIES 10-250 KVA PRODUCT DESCRIPTION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    BeepTurn the beeper sound on/off.

    LanguageSet the menu language.

    Communication Set the protocol for the RS232 connection. Theoptions are SEC, Megatech and TELNET.

  • CHALLENGER SERIES 10-250 KVA PRODUCT DESCRIPTION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Economy Mode Economy mode (ECO) and UPS switch to staticbypass mode at the specified days and hours.Use this menu to setup the days and hours.

    Service Menu Service menu is password secured, and cannot beaccessed with the user password.

    2.4.8 Logging Menu Last 500 events of the device can be seen in thismenu.When viewing an event, press enter to see detailedinfo about the UPS. Use up and down keys to seeolder/newer event logs.

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    3. INSTALLATION3.1. Single Mode InstallationIn this section, the warnings which must be obeyed and the checking which must be performedbefore starting-up the UPS are stated. Additionally, you can find informations about the points youmust pay attention during carrying the cabinets, positioning and connections.

    3.1.1. Warnings

    The UPS must be installed by a certified electrician.

    Do not energize the UPS before proper installation.Battery Hazard

    Battery terminal voltage reaches up to 450 Vdc during operation.Proper safety gear must be used to protect the skin and the eyes from electrical arcs.Check the batteries for leakage before using them.ESD-protected rubber gloves should be used.Battery ingredients are hazardous. In case of contact with battery ingredients, rinse the skin withwater, and consult a physician if irritation occurs.Remove any metal accessories (ring, watch, etc.) before working on the device.UPS, needs a feeding which has 3-phases and four-wire ( +earth) on the input. Feeding type issuitable for connection to IEC 60364-3. Optional 3-wire to 4-wire conversion transformers areavailable.If it is used in IT AC power distribution systems, a 4-pole circuit breaker must be used on theinput and refer to the relative IT Systems2 standart.Detail of the subject is explained in more detail on the standart named IEC 60364-3.3.1.2. Pre-installation check upBefore installing the device, the following checks should be carried , these are the first and mostimportant steps in the operation of the product correctly.

    Check if any damage was done to the device during transportation. Report any damages instantly. Make sure that the model power rating is right. Check the device label for the actual power rating.

    CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    3. INSTALLATION3.1. Single Mode InstallationIn this section, the warnings which must be obeyed and the checking which must be performedbefore starting-up the UPS are stated. Additionally, you can find informations about the points youmust pay attention during carrying the cabinets, positioning and connections.

    3.1.1. Warnings

    The UPS must be installed by a certified electrician.

    Do not energize the UPS before proper installation.Battery Hazard

    Battery terminal voltage reaches up to 450 Vdc during operation.Proper safety gear must be used to protect the skin and the eyes from electrical arcs.Check the batteries for leakage before using them.ESD-protected rubber gloves should be used.Battery ingredients are hazardous. In case of contact with battery ingredients, rinse the skin withwater, and consult a physician if irritation occurs.Remove any metal accessories (ring, watch, etc.) before working on the device.UPS, needs a feeding which has 3-phases and four-wire ( +earth) on the input. Feeding type issuitable for connection to IEC 60364-3. Optional 3-wire to 4-wire conversion transformers areavailable.If it is used in IT AC power distribution systems, a 4-pole circuit breaker must be used on theinput and refer to the relative IT Systems2 standart.Detail of the subject is explained in more detail on the standart named IEC 60364-3.3.1.2. Pre-installation check upBefore installing the device, the following checks should be carried , these are the first and mostimportant steps in the operation of the product correctly.

    Check if any damage was done to the device during transportation. Report any damages instantly. Make sure that the model power rating is right. Check the device label for the actual power rating.

    CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    3. INSTALLATION3.1. Single Mode InstallationIn this section, the warnings which must be obeyed and the checking which must be performedbefore starting-up the UPS are stated. Additionally, you can find informations about the points youmust pay attention during carrying the cabinets, positioning and connections.

    3.1.1. Warnings

    The UPS must be installed by a certified electrician.

    Do not energize the UPS before proper installation.Battery Hazard

    Battery terminal voltage reaches up to 450 Vdc during operation.Proper safety gear must be used to protect the skin and the eyes from electrical arcs.Check the batteries for leakage before using them.ESD-protected rubber gloves should be used.Battery ingredients are hazardous. In case of contact with battery ingredients, rinse the skin withwater, and consult a physician if irritation occurs.Remove any metal accessories (ring, watch, etc.) before working on the device.UPS, needs a feeding which has 3-phases and four-wire ( +earth) on the input. Feeding type issuitable for connection to IEC 60364-3. Optional 3-wire to 4-wire conversion transformers areavailable.If it is used in IT AC power distribution systems, a 4-pole circuit breaker must be used on theinput and refer to the relative IT Systems2 standart.Detail of the subject is explained in more detail on the standart named IEC 60364-3.3.1.2. Pre-installation check upBefore installing the device, the following checks should be carried , these are the first and mostimportant steps in the operation of the product correctly.

    Check if any damage was done to the device during transportation. Report any damages instantly. Make sure that the model power rating is right. Check the device label for the actual power rating.

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    3.1.3. PositioningUPS and batteries are designed for indoor use; UPS must be placed in a places where has cleanand easy air flow.3.1.3.1.Positioning of UPSIn Challenger 10-250 kVA series, air enters the device from the front side ventilation holes, goesout from the rear side of UPS through fans. Air inlet and outlet ports should never be covered. Itshould be positioned in a place where is far from the risk of liquid contact.If the area is dusty, Optional filters must be used on dusty environments.The using of these filters will be made according to the instructions on.UPS is an energy-loss system due to its nature. Energy losses emerges as heat. You can see whatkind of a forced air-cooling is needed in the following table. This table can be used to calculate thecapacity of air conditioning which must be used in UPS ambiance.

    UPS Amount of BTU /h forcoolingBridge Load 100% (Non-lineer) estimated

    BTU / h value for loadworking

    10KVA 2.663 3.19615KVA 3.790 4.54820KVA 3.892 4.67030KVA 7.785 9.34240KVA 8.058 9.67060KVA 12.975 15.57080 KVA 17500 21000100 KVA 21900 26300120 KVA 26300 31500160KVA 37000 44000200KVA 40000 48000250 KVA 54700 65600

    3.1.3.2.External Battery ConfigrationBatteries must be used in balanced and uniform temperature environments. temperature, is themost important factor that directly affect to battery capacity and usage lifes. in general, batterymanufacturers recommend the batteries to be used between 20-25 C. In addition, Batterymanufacturers give the performance of their products in this temperature range. If temperatureexceeds this specific limits, battery life will decrease. If the temperature drops below this range,the battery capacity is severely reduces. Therefore, the expected autonomy time will not besufficient during redundancy process. As a result, keep the batteries away from the points where aheat source and serious air flow are located. Please observe the following points on connectingexternal batteries by taking into account these issues:

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Keep batteries away from main heat sources. Keep batteries away from main air inlets. Keep batteries away from the humid places.Hereby batteries can be prevented from terminaloxidations and possible leakage currents. Please use aR or gR semi-conductor type fuse at the battery rooms and cabinets. If it is possible, please use breaker switch without fuse for the bateery cabinet. Keep battery cabinets and shelves high above the ground. UPS should be protected against floodsor liquid contacts. Battery rooms should be properly ventilated. Shelves will be accessible in touch if batteries are in battery room. Therefore please keeprestricted accessing to battery room. Use necessary safety writings and strips

    Espacially, for the external cabinet batteries system of UPS, fuses must definitely be used. Thesefuses must be mounted as close as possible to the batteries. This closeness will increase theelectrical operation safety.THE TABLE OF CHALLENGER EXTERNAL BATTERY USAGE

    Device Power (KVA) 10Total number of Batt. 28 32 36 38 42 46 50

    Ibat.max@ Vbat.max (A) 5,2 4,5 4,0 3,8 3,5 3,2 2,9Ibat.max@ Vcutoff (A) 31 27 24 23 21 19 17Recommended internal fuse (A) 40 32 32 32 25 25 20

    THE TABLE OF CHALLENGER EXTERNAL BATTERY USAGEDevice Power (KVA) 15Total number of Batt. 28 32 36 38 42 46 50

    Ibat.max@ Vbat.max (A) 7,8 6,8 6,0 5,7 5,2 4,7 4,3Ibat.max@ Vcutoff (A) 46 40 36 34 31 28 26Recommended internal fuse (A) 63 50 40 40 40 32 32

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    CHALLENGER SERS HARC AK KABN KONFGRASYONUDevice Power (KVA) 20 30Total number of Batt. 38 42 46 50 38 42 46 50

    Ibat.max@ Vbat.max (A) 7,6 6,9 6,3 5,8 11,4 10,4 9,5 8,7Ibat.max@ Vcutoff (A) 45 41 37 34 67 61 56 51Recommended internal fuse (A) 50 50 50 40 80 80 63 63

    Device Power (KVA) 40 60Total number of Batt. 48 50 50

    Ibat.max@ Vbat.max (A) 12,1 11,6 17.4Ibat.max@ Vcutoff (A) 71 68 102Recommended internal fuse (A) 80 80 125

    THE TABLE OF CHALLENGER EXTERNAL BATTERY USAGEDevice Power (KVA) 80 100 120 160 200 250Total number of Batt. 50 50 50 50 50 50

    Ibat.max@ Vbat.max (A) 18,6 23,2 27,8 37,1 46,4 58,0Ibat.max@ Vcutoff (A) 136 170 204 271 339 424Recommended internalfuse (A) 160 200 250 280 355 400

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    External battery cabinet and battery room applications are given below as an example.The method of application may vary according to the customer.

    Example Battery Chamber Application(80-250kVA)CH80120EN08R0

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    CH80120EN09R0

    External Battery Cabinet Application(80-250kVA)3.1.4 Transportation Type of CabinetsCarrying vehicles or handling accessories must have enough features and characteristics to carryUPSs weight.Cabinet is equipped with four-wheel. Thanks to this feature, it can be moved easily. These wheelsmust be used only on smooth surfaces.The front side wheels of UPS must be locked after positioning properly. The back side wheels arefixed. Be more careful of sudden movements, especially when batteries are inside of cabinet.Move the UPS as rarely as possible.3.1.5Main, Load and Battery ConnectionsMakelsan strictly recommends a distribution board for the UPS outputs. Proper fuses andbreakers must be used in such distribution board. A-B type fuses or magnetic breakers arerecommended if the load is suitable.

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    3.1.5.1 External ProtectionTo protect the AC inputs, thermal magnetic breakers or V type breakers must be installed on thedistribution board.Over current protecting must be installed on mains input distribution board and fuses must bechosen 135% higher rated than the ones given in the table below. Fuses must be C-type.Ground leakages flow to the ground through the EMI filters on the input and the output of the UPS.Makelsan recommends the use of 700mA rated relays for handling leakage currents.Leakage current relays that set at the input of UPS are shown below;

    Resistant to both positive and negative DC pulses, And not sensitive to transient currents. Must be sensitive to currents which is average between 0,3-1 A

    3.1.5.2 Cable and Fuse SelectionCable designs must be suitable to mentioned currents and voltages; additionally, local guidelineson this topic must be considered.UPSPower(KVA)

    Nominal Currents (A)Input currents@max chargecurrent (3P+N) Output Currents @100% Load(3P+N)380V 400V 415V 380V 400V 415V

    10 17,1 16,2 15,7 15,4 14,6 14,115 25,6 24,4 23,5 23,1 21,9 21,120 34,2 32,5 31,3 30,8 29,2 28,230 51,3 48,7 47 46,2 43,9 42,340 68,4 65 62,6 61,6 58,5 56,460 102 97 94 93 88 8580 137,6 128,0 127,0 123,2 116,8 112,8100 172,0 160,0 158,7 154,0 146,0 141,0120 206,4 192,0 190,5 184,8 175,2 169,2160 273,6 259,9 250,5 246,2 233,9 225,5200 342,0 324,9 313,1 307,8 292,4 281,8250 427,5 406,1 391,4 384,7 365,5 352,3

    Non-linear loads (computer-type loads) may affect design of cable cross-sectional. The Neutralcurrents may be bigger than the phase currents, even it may rise up to 1,5 times of phase current.Protection Ground cable must be connected to directly each cabinet and ground line easily.Typical ground line cable cross-sections for 80 kVA should be 50mm2, for 100 kVA should be70mm2 and for 120 kVA should be 95mm2.3.1.5.3 Connecting the CablesAll electrical connections of the UPS are made from the rear side of the device.

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    ATTENTION! 3 pole-circuit breakers (switch) are used for the input and output of UPS,Neutral line is not be interrupted.

    80-250kVA Cable Connection

    1 Input Terminals2 Output TerminalsCH80120EN10R0

    CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    ATTENTION! 3 pole-circuit breakers (switch) are used for the input and output of UPS,Neutral line is not be interrupted.

    80-250kVA Cable Connection

    1 Input Terminals2 Output TerminalsCH80120EN10R0

    CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    ATTENTION! 3 pole-circuit breakers (switch) are used for the input and output of UPS,Neutral line is not be interrupted.

    80-250kVA Cable Connection

    1 Input Terminals2 Output TerminalsCH80120EN10R0

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    10-60kVA Cable Connection

    1 Input Terminals2 Output Terminals

    1. Make sure that the network and loads areisolated through cables by turning off the allbreakers on the distrubution board.

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    2. Connect the ground cable.

    10-60kVA 80-250kVA3. Make sure that the circuit breakers are off. The use of these circuit breakers areexplained on the next sections.

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    4. Connect the input cables.; R to INPUT L1, S to INPUT L2, T to INPUT L3, N(Neutral) to INPUT N.

    80-250kVA

    10-60kVA5. Check the phase sequence.6. Repeat steps 4-5 for output cables.Use the cable clips to stabilize the cables when the connections are done.WARNING: Make sure that the loads are isolated from the UPS output if they are not ready to beconnected

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    WARNING: Make sure that the cables are connected properly before UPS is started. Additionaly,check if there is galvanic isolation transformers at input of UPS and consider the local directions.WARNING: Check the grounding before starting the UPS. Wrong works or grounding on UPS orother devices of installaton may be hazardous. Wrong works and grounding may damage UPS andanother system on the installation3.1.5.4 Battery ConnectionsYou can find explanations about installation procedures and connections of internal and externalbatteries in this section.

    Battery Hazard The battery terminal voltage can reach up to 700 Vdc. Preserve your eyes and skin against possible arcs. Check for leaks before connecting the batteries. Batteries have harmful content. In case of contact wash with plenty of water If irritation persists,consult a doctor.Remove the metal accessories such as ring ,watch before working with batteries

    Battery Assembly for 28

    CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    WARNING: Make sure that the cables are connected properly before UPS is started. Additionaly,check if there is galvanic isolation transformers at input of UPS and consider the local directions.WARNING: Check the grounding before starting the UPS. Wrong works or grounding on UPS orother devices of installaton may be hazardous. Wrong works and grounding may damage UPS andanother system on the installation3.1.5.4 Battery ConnectionsYou can find explanations about installation procedures and connections of internal and externalbatteries in this section.

    Battery Hazard The battery terminal voltage can reach up to 700 Vdc. Preserve your eyes and skin against possible arcs. Check for leaks before connecting the batteries. Batteries have harmful content. In case of contact wash with plenty of water If irritation persists,consult a doctor.Remove the metal accessories such as ring ,watch before working with batteries

    Battery Assembly for 28

    CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    WARNING: Make sure that the cables are connected properly before UPS is started. Additionaly,check if there is galvanic isolation transformers at input of UPS and consider the local directions.WARNING: Check the grounding before starting the UPS. Wrong works or grounding on UPS orother devices of installaton may be hazardous. Wrong works and grounding may damage UPS andanother system on the installation3.1.5.4 Battery ConnectionsYou can find explanations about installation procedures and connections of internal and externalbatteries in this section.

    Battery Hazard The battery terminal voltage can reach up to 700 Vdc. Preserve your eyes and skin against possible arcs. Check for leaks before connecting the batteries. Batteries have harmful content. In case of contact wash with plenty of water If irritation persists,consult a doctor.Remove the metal accessories such as ring ,watch before working with batteries

    Battery Assembly for 28

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Battery Assembly for 28x2

    Battery Assembly for 38

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Battery Assembly for 38x2

    Battery Assembly for 40

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Battery Assembly for 40x2

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    3.1.5.4.1 External Battery Installation Procedure and ConnectionYou can see detailed information about how to be positioned of external batteries under the titleof external batteries positioning above. In this section, Information about connecting batteries toUPS was givenAvoid short circuiting batteries .Exploding batteries can damage you andyour environment!Battery terminal may rise up to 700 Vdc1. If any switch breaker exist on the battery cabinet, switch Off them.2. Remove the battery fuse in the battery cabinet.3. Remove the battery fuse on the UPS.

    4. Make sure that the batteries are connected properly in series and parallel.5. Connect the negative battery terminal to BAT cable, also connect the positive battery terminal tothe +BAT cable in the UPS.6. Check the polarity of the battery connection once again.7. Replace the battery fuse on the UPS.

    8. Replace the battery fuse in the battery cabinet.9. Replace the battery fuse on the UPS10. If any switch breaker exist on the battery cabinet, switch ON them.11. Please check that whether there is appropriate battery voltage on the input terminals of thebattery of UPS by measurement tool.

    CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    3.1.5.4.1 External Battery Installation Procedure and ConnectionYou can see detailed information about how to be positioned of external batteries under the titleof external batteries positioning above. In this section, Information about connecting batteries toUPS was givenAvoid short circuiting batteries .Exploding batteries can damage you andyour environment!Battery terminal may rise up to 700 Vdc1. If any switch breaker exist on the battery cabinet, switch Off them.2. Remove the battery fuse in the battery cabinet.3. Remove the battery fuse on the UPS.

    4. Make sure that the batteries are connected properly in series and parallel.5. Connect the negative battery terminal to BAT cable, also connect the positive battery terminal tothe +BAT cable in the UPS.6. Check the polarity of the battery connection once again.7. Replace the battery fuse on the UPS.

    8. Replace the battery fuse in the battery cabinet.9. Replace the battery fuse on the UPS10. If any switch breaker exist on the battery cabinet, switch ON them.11. Please check that whether there is appropriate battery voltage on the input terminals of thebattery of UPS by measurement tool.

    CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    3.1.5.4.1 External Battery Installation Procedure and ConnectionYou can see detailed information about how to be positioned of external batteries under the titleof external batteries positioning above. In this section, Information about connecting batteries toUPS was givenAvoid short circuiting batteries .Exploding batteries can damage you andyour environment!Battery terminal may rise up to 700 Vdc1. If any switch breaker exist on the battery cabinet, switch Off them.2. Remove the battery fuse in the battery cabinet.3. Remove the battery fuse on the UPS.

    4. Make sure that the batteries are connected properly in series and parallel.5. Connect the negative battery terminal to BAT cable, also connect the positive battery terminal tothe +BAT cable in the UPS.6. Check the polarity of the battery connection once again.7. Replace the battery fuse on the UPS.

    8. Replace the battery fuse in the battery cabinet.9. Replace the battery fuse on the UPS10. If any switch breaker exist on the battery cabinet, switch ON them.11. Please check that whether there is appropriate battery voltage on the input terminals of thebattery of UPS by measurement tool.

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    The external battery cable selection is determined by the application. Recommended fuses aregiven for UPS and battery cabinet. The lowest diameter cable that can be connected to those fusesis recommended to be used. Please, refer to standard called EN 50525-2-31(VDE 0100-430) inthis subject. The selection should be such that the cable will allow at most 0,5 Vdc decreasing.External Battery Temperature Measurement Kit which is sold as optional is recommendedto purchase for optimization according to battery temperatures on the external battery cabinetsapplications. Otherwise, your batteries will not be optimized according to temperatures.80-250kVA External Battery Connection

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    10-60kVA External Battery Connection

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    3.1.5.5. Menu Setup After Battery InstallationMenu setup shall be adjusted in the following statements after installation is done.1. Turn on CB12. From the user panel, go to Service menu> Setup and adjust battery settings.Settings are: number of batteries in series, number of parallels and batterycapacity.

    3. Switch off CB1 and look at UPS operation conditions.3.1.5.6 Control and Communication Cable ConnectionsMAKELSAN UPS have standard or optional connections of advanced external battery cabinet,environmental monitoring, control panels and various intelligent monitoring.Connections on the side of UPS : One RS232 serial communication connector (RS232/Rectifier Service) One RS232 serial communication connector (RS232/Inverter Service) Two optional card slotConnections on the UPS:

    One paralleling connection connector3.2 Parallel InstallationThe product which you have bought can be operated in parallel; however, this feature is offered asan option. Please contact your dealer for parallel operation.

    Parallel application should be made by authorized personal of Makelsan !

    CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    3.1.5.5. Menu Setup After Battery InstallationMenu setup shall be adjusted in the following statements after installation is done.1. Turn on CB12. From the user panel, go to Service menu> Setup and adjust battery settings.Settings are: number of batteries in series, number of parallels and batterycapacity.

    3. Switch off CB1 and look at UPS operation conditions.3.1.5.6 Control and Communication Cable ConnectionsMAKELSAN UPS have standard or optional connections of advanced external battery cabinet,environmental monitoring, control panels and various intelligent monitoring.Connections on the side of UPS : One RS232 serial communication connector (RS232/Rectifier Service) One RS232 serial communication connector (RS232/Inverter Service) Two optional card slotConnections on the UPS:

    One paralleling connection connector3.2 Parallel InstallationThe product which you have bought can be operated in parallel; however, this feature is offered asan option. Please contact your dealer for parallel operation.

    Parallel application should be made by authorized personal of Makelsan !

    CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    3.1.5.5. Menu Setup After Battery InstallationMenu setup shall be adjusted in the following statements after installation is done.1. Turn on CB12. From the user panel, go to Service menu> Setup and adjust battery settings.Settings are: number of batteries in series, number of parallels and batterycapacity.

    3. Switch off CB1 and look at UPS operation conditions.3.1.5.6 Control and Communication Cable ConnectionsMAKELSAN UPS have standard or optional connections of advanced external battery cabinet,environmental monitoring, control panels and various intelligent monitoring.Connections on the side of UPS : One RS232 serial communication connector (RS232/Rectifier Service) One RS232 serial communication connector (RS232/Inverter Service) Two optional card slotConnections on the UPS:

    One paralleling connection connector3.2 Parallel InstallationThe product which you have bought can be operated in parallel; however, this feature is offered asan option. Please contact your dealer for parallel operation.

    Parallel application should be made by authorized personal of Makelsan !

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    In case of need for redundancy or more power, Challenger series UPS can be operated in parallelup to quantity 8 (eight). A schematic diagram which shows two UPS connected in parallel can beseen below.

    Inputs and outputs of more than one UPS are connected to each other; but definitely each batterygroup is different from another, batteries can not be used in common. The following points shouldbe considered while placement of UPS in parallel system and their electrical connections are made: UPSs connected in parallel must have the same power rating and must be the same series. Devices must be running on the same firmware, if not, old firmwares must be updated. Devices must be located as close as possible to each other (max. 6 x 110 cm paralleling cables.) Each device must have its own neutral cable . Each device must have its own ground connection. UPS must be connected in paralel on the distribution panel and phases must be connectedcorrectly. (U1-U2--UN), (V1-V2--VN), (W1-W2--WN). Each UPS must have their own battery set, batteries cannot be used for more than one device atthe same time. The length of all cables which are connected to distribution panel must be the same for the equalcurrent sharing.

  • CHALLENGER SERIES 10-250 KVA INSTALLATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Parallel SettingsConnect the parallel cable as shown in figure below. Only use the cables provided by Makelsan. Software settings on the user panel should be made by authorized personel.

    80-250kVA Paralel Connection Socket

    10-60kVA Paralel Connection Socket

  • CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    4 OPERATION4.1 Operation Procedure

    You can find information about circuit breaker, first start-up, types of UPS operation tests, turningUPS off, EPO and RS232 serial communication system in this section.4.1.1 Circuit BreakersUPS has three circuit breakers that can be reached from the front panel, these are used for AC input,maintenance bypass and output connections respectively.Three-phase AC voltage is applied through CB1 to input of UPS.AC input voltage is applied directly to loads through CB2. In this way, maintenance purposedswitching is done properly. By auxiliary short circuit info located in CB3, mains makes the bypassstatic switches activated while UPS operates. The system will be switched to maintenance modesmoothly.

    CB3 is used to connect or separate AC voltage that comes from static switches to the loads on UPS.Active Breakers Operation Mode ExplanationCB1, CB3 Normal Mode UPS operates in normal mode..CB1, CB3 Static Bypass Mode UPS is overloaded, loads will be transferred tostatic bypass line temporarily.CB2 Test Mode UPS is ON, but loads will be fed throughmechanical bypass line.CB2 Maintenance Mode UPS is shut down for maintenance; loads will befed through mechanical bypass line.

  • CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    4.1.2 First Start-UpWARNING:Wait for at least 5 seconds between each step.1. Turn the Maintenance (CB2) bypass breaker ON2. Turn the input (CB1) breaker ON3. Start the UPS using the front panel.Main menu> Control > Password > Start

    4. Wait for the operation of the rectifier. Rectifier LED on the mimic diagram will flash for awhile, and then remain lit.

    5. Wait for the operation of the battery charge. Battery charge LED on the mimic diagram willbe lit continuously.

  • CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    6. Wait for the switching of UPS to static bypass mode. Static bypass LED on the mimicdiagram will light up.

    7. Check the UPS has switched to normal operation mode, via mimic diagram LEDs and LCDpanel. Verify that batteries are switched via front panel indicator and "Status > Battery" menu.8. Turn output circuit braker (CB3) ON.9. Turn the maintenance bypass braker (CB2) OFF.10. The loads which are connected to UPS can be turned on.After all these steps, check that load is fed through inverter static switches via mimic diagram. In acontrary situation, check UPS total and phase loads. The UPS gives audio alerts in an overloadcondition, without feeding critical AC loads.

    4.1.3 Testing of Types of UPS Operation

    After first start-up check device operation by switching between the following modes manually.4.1.3.1 Switching from Online Mode to Battery ModeTurn CB1 OFF. This action cuts off the mains voltage and the UPS starts operating on battery mode.Turn CB1 back ON again if everything is ok.4.1.3.2 Switching from Online Mode to Static Bypass Mode

  • CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Use the front panel to switch the device to static bypass mode. Check the mimic panel to make surethat the device has switched to bypass mode.Main menu> Control > Switch to Bypass

    NOTE: UPS will not switch to bypass mode if the inverter voltage is out of limits or there is andoverload or overtemperature situation.4.1.3.3 Switching from Static Bypass Mode to OnlineUse the front panel to switch the device to online mode. Check the mimic panel to make sure that thedevice has switched to online mode.

    Main menu > Control > Switch to UPS

  • CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    NOTE: The UPS will not switch to normal mode if the inverter voltage is out of limits, or there is andover load or over temperature situation.4.1.3.4 Switching from Online Mode to Maintenance Bypass Mode

    WARNING: Make sure that the inverter output is synchronous with the maintenance bypass linebefore switching to maintenance bypass mode. Otherwise there is a possibility of cutting off the loadpower for a short while.Use the front panel to switch the device to static bypass mode. Check the mimic panel to make surethat the device has switched to bypass mode.Main Menu > Control > Output BYPASS

    1. Turn CB2 ON.Stop the UPS by using front panel.

  • CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Main menu > Control > Stop

    2. Turn CB1 and CB3 OFF.WARNING:

    Wait at least 5 minutes before opening up the device after it is completely turnedoff for safety

    4.1.4 Performing a Complete Shutdown

    Turn off the loads connected to the device.Use the front panel to turn the device OFFMain Menu> Control> Password> Stop

    CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Main menu > Control > Stop

    2. Turn CB1 and CB3 OFF.WARNING:

    Wait at least 5 minutes before opening up the device after it is completely turnedoff for safety

    4.1.4 Performing a Complete Shutdown

    Turn off the loads connected to the device.Use the front panel to turn the device OFFMain Menu> Control> Password> Stop

    CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Main menu > Control > Stop

    2. Turn CB1 and CB3 OFF.WARNING:

    Wait at least 5 minutes before opening up the device after it is completely turnedoff for safety

    4.1.4 Performing a Complete Shutdown

    Turn off the loads connected to the device.Use the front panel to turn the device OFFMain Menu> Control> Password> Stop

  • CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    WARNING: Make sure that there are no critical loads on the UPS output before performing acomplete shutdown.

    4.1.5 EPO (Emergency Power Off)

    UPS turns off rectifier, amplifier and inverter respectively when the EPO button is pressed. UPS iscompletely separated from the system, if the shutdown option of output circuit breaker is setted.

    10-60kVA 80-250kVA

    4.1.6 RS232 Serial Communication Installation and investigationChallenger series has an RS-232 interface which supports SEC and TELNET protocol as standart.This interface is fully isolated and safe. UPS can be monitored remotely via a computer (PC) or SNMPby using this protocol. This connection works with all kinds of options.

    CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    WARNING: Make sure that there are no critical loads on the UPS output before performing acomplete shutdown.

    4.1.5 EPO (Emergency Power Off)

    UPS turns off rectifier, amplifier and inverter respectively when the EPO button is pressed. UPS iscompletely separated from the system, if the shutdown option of output circuit breaker is setted.

    10-60kVA 80-250kVA

    4.1.6 RS232 Serial Communication Installation and investigationChallenger series has an RS-232 interface which supports SEC and TELNET protocol as standart.This interface is fully isolated and safe. UPS can be monitored remotely via a computer (PC) or SNMPby using this protocol. This connection works with all kinds of options.

    CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    WARNING: Make sure that there are no critical loads on the UPS output before performing acomplete shutdown.

    4.1.5 EPO (Emergency Power Off)

    UPS turns off rectifier, amplifier and inverter respectively when the EPO button is pressed. UPS iscompletely separated from the system, if the shutdown option of output circuit breaker is setted.

    10-60kVA 80-250kVA

    4.1.6 RS232 Serial Communication Installation and investigationChallenger series has an RS-232 interface which supports SEC and TELNET protocol as standart.This interface is fully isolated and safe. UPS can be monitored remotely via a computer (PC) or SNMPby using this protocol. This connection works with all kinds of options.

  • CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Challenger Parallel Operation Guide

    Please read the following instructions before you use the devices in parallel mode.

    A. Check if the devices can be used in parallel mode.1. Be sure that all devices are from the same series and rated the same power.2. Go to the version screen using menu keys, and check if all devices have the same firmware.

    Main screen > Setup > Version

    B. Check the positioning of the devices.3. Keep the devices as close to each other as possible. The distance between must not exceed10 meters.C. Make the electrical connections

    4. Make sure that the devices are turned OFF and have been kept off for at least 5 minutesbefore you make any electrical connections.5. Connect the devices in parallel through the electrical panel. Refer to parallel connectionexample for detailed connection drawing.

  • CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    6. Connect each device to ground using seperate cables.7. Make sure that the phases are in the right order.(U1-U2--UN), (V1-V2--VN), (W1-W2--WN).Check the connections using a multimeter in diode mode;

    First turn the maintenance switch OFF and see if the inputs of the devices areconnected to each other.

    Then turn the maintenance switch ON and check the connection between the inputof the first device and the output of the second device.

  • CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    8. Use seperate sets of batteries for each device. Do NOT use the same set of batteries onmore than one device at the same time.9. Connect the communication cable and secure the connections.

    10. Check the termination resistors on the connection cable. Remove the UPS top panel and reach the main board. Find the J9 socket on the main board, and check the resistance between pin 2 andpin 3 using a multimeter. (60) Check the resistance between pin 4 and pin 5. (60) Close the replace the UPS top panel. Turn on the device.

    D. Set the software for parallel operation.In parallel operation, Challenger series UPS use the Master/Slave configuration. Masterauthorization is temporary for a UPS, one of the slaves may become the master depending onthe conditions.

  • CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    11. Go to the Servicemenu and enter the Parallel Operation screen.Main screen > Setup > Service Menu > Parallel Operation

    12. Change MODE to Parallel using the menu keys.

    13. Set a different ID number for each device and then authorize one of the devices asMASTER.

    14. Check the number of running devices (ACT) on the right lower side of the screen. If thenumber is not correct, make sure that each device has its own ID number.

    CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    11. Go to the Servicemenu and enter the Parallel Operation screen.Main screen > Setup > Service Menu > Parallel Operation

    12. Change MODE to Parallel using the menu keys.

    13. Set a different ID number for each device and then authorize one of the devices asMASTER.

    14. Check the number of running devices (ACT) on the right lower side of the screen. If thenumber is not correct, make sure that each device has its own ID number.

    CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    11. Go to the Servicemenu and enter the Parallel Operation screen.Main screen > Setup > Service Menu > Parallel Operation

    12. Change MODE to Parallel using the menu keys.

    13. Set a different ID number for each device and then authorize one of the devices asMASTER.

    14. Check the number of running devices (ACT) on the right lower side of the screen. If thenumber is not correct, make sure that each device has its own ID number.

  • CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    E. OperationMaster/Slave configurationOpen the status menu to see if any device is a master or a slave.

    Open the status menu to see if any device is a master or a slave. The letter on the lower leftcorner of the LCD screen is M or S in parallel mode.

    Parallel start-upRead the following to start the parallel system. Turn on the UPS breakers on the distribution board, then turn on the main inputbreaker.

    CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    E. OperationMaster/Slave configurationOpen the status menu to see if any device is a master or a slave.

    Open the status menu to see if any device is a master or a slave. The letter on the lower leftcorner of the LCD screen is M or S in parallel mode.

    Parallel start-upRead the following to start the parallel system. Turn on the UPS breakers on the distribution board, then turn on the main inputbreaker.

    CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    E. OperationMaster/Slave configurationOpen the status menu to see if any device is a master or a slave.

    Open the status menu to see if any device is a master or a slave. The letter on the lower leftcorner of the LCD screen is M or S in parallel mode.

    Parallel start-upRead the following to start the parallel system. Turn on the UPS breakers on the distribution board, then turn on the main inputbreaker.

  • CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Start one of the UPS using the front panel, and all the other UPS will start automatically.

    Turn on the output breakers on the distribution board, then turn on the main output breaker.

    The loads will be equally distributed on all devices.

    CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Start one of the UPS using the front panel, and all the other UPS will start automatically.

    Turn on the output breakers on the distribution board, then turn on the main output breaker.

    The loads will be equally distributed on all devices.

    CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Start one of the UPS using the front panel, and all the other UPS will start automatically.

    Turn on the output breakers on the distribution board, then turn on the main output breaker.

    The loads will be equally distributed on all devices.

  • CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Switching to static bypass If any one of the devices is manually switched to static bypass mode, the others will

    automatically switch to static bypass mode.

    To switch all the devices to online mode, select switch to UPS on any device.

    Stopping/Removing a single UPSIn a parallel Challenger system, any one of the devices can be removed off the system withoutaffecting the others. To remove a UPS off the parallel system for maintenance, follow the stepsbelow:

    Stop the desired UPS using the control menu.

    If the Master device is stopped, the UPS with the smallest ID no will become the newMaster device.

    Turn off the UPS input breaker (CB1)

    Turn off the UPS output breaker (CB3) and the maintenance breaker (CB2)

    Turn off the UPS breakers on the distribution board.

    CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Switching to static bypass If any one of the devices is manually switched to static bypass mode, the others will

    automatically switch to static bypass mode.

    To switch all the devices to online mode, select switch to UPS on any device.

    Stopping/Removing a single UPSIn a parallel Challenger system, any one of the devices can be removed off the system withoutaffecting the others. To remove a UPS off the parallel system for maintenance, follow the stepsbelow:

    Stop the desired UPS using the control menu.

    If the Master device is stopped, the UPS with the smallest ID no will become the newMaster device.

    Turn off the UPS input breaker (CB1)

    Turn off the UPS output breaker (CB3) and the maintenance breaker (CB2)

    Turn off the UPS breakers on the distribution board.

    CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Switching to static bypass If any one of the devices is manually switched to static bypass mode, the others will

    automatically switch to static bypass mode.

    To switch all the devices to online mode, select switch to UPS on any device.

    Stopping/Removing a single UPSIn a parallel Challenger system, any one of the devices can be removed off the system withoutaffecting the others. To remove a UPS off the parallel system for maintenance, follow the stepsbelow:

    Stop the desired UPS using the control menu.

    If the Master device is stopped, the UPS with the smallest ID no will become the newMaster device.

    Turn off the UPS input breaker (CB1)

    Turn off the UPS output breaker (CB3) and the maintenance breaker (CB2)

    Turn off the UPS breakers on the distribution board.

  • CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Stopping all UPSTo stop all the UPS in a parallel system, go to Setup >Service Menu >Control >Stop All UPS.

    Note: Pressing the EPO button on any UPS will stop all UPS

    Troubleshooting for Parallel ModePossible alarms regarding parallel mode, and their solutions are:

    Alarm Explanation Necessary Action

    Parl. ID CollisionTwo or more paralleldevices have been assignedto the same ID number.

    Check the parallel ID numbers and make surethat each device have their own unique ID.Main menu > setup > service menu > paralleloperation.

    No Parallel Comm.No parallel communicationbetween devices. Masterdevice is unavailable orcannot be reached.

    Make sure that one of the devices isauthorized as MASTER. Check the parallelconnection cable.

    CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Stopping all UPSTo stop all the UPS in a parallel system, go to Setup >Service Menu >Control >Stop All UPS.

    Note: Pressing the EPO button on any UPS will stop all UPS

    Troubleshooting for Parallel ModePossible alarms regarding parallel mode, and their solutions are:

    Alarm Explanation Necessary Action

    Parl. ID CollisionTwo or more paralleldevices have been assignedto the same ID number.

    Check the parallel ID numbers and make surethat each device have their own unique ID.Main menu > setup > service menu > paralleloperation.

    No Parallel Comm.No parallel communicationbetween devices. Masterdevice is unavailable orcannot be reached.

    Make sure that one of the devices isauthorized as MASTER. Check the parallelconnection cable.

    CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Stopping all UPSTo stop all the UPS in a parallel system, go to Setup >Service Menu >Control >Stop All UPS.

    Note: Pressing the EPO button on any UPS will stop all UPS

    Troubleshooting for Parallel ModePossible alarms regarding parallel mode, and their solutions are:

    Alarm Explanation Necessary Action

    Parl. ID CollisionTwo or more paralleldevices have been assignedto the same ID number.

    Check the parallel ID numbers and make surethat each device have their own unique ID.Main menu > setup > service menu > paralleloperation.

    No Parallel Comm.No parallel communicationbetween devices. Masterdevice is unavailable orcannot be reached.

    Make sure that one of the devices isauthorized as MASTER. Check the parallelconnection cable.

  • CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    Parl.Missing Dev.One or more devices cannotbe reached on parallelmode.

    Check the parallel connection cable. Check ifACT = NODE on parallel setup screen. If not,correct NODE.

    Par. CommunicationFE

    Parallel communicationframe error.

    Check the parallel connection cable andtermination resistors.

    Please contact MAKELSAN technical service for further questions.

  • CHALLENGER SERIES 10-250 KVA OPERATION

    AG-SD-36 Rev. No:0 Rev. Date:16.01.2014 Publish No:1

    CHALLENGER CARD MATRIX

    BOARDCODE BOARD EXPLANATIONS

    10KV

    A CHA

    LLENG

    ER15KV

    A CHA

    LLENG

    ER20KV

    A CHA

    LLENG

    ER30KV

    A CHA

    LLENG

    ER40KV

    A CHA

    LLENG

    ER60KV

    A CHA

    LLENG

    ER80KV

    A CHA

    LLENG

    ER100K

    VA CH

    ALLEN

    GER