    Chiller vs VRF system

    LG Electronics Inc.LGEHQ CAC Team

  • 5/28/2018 Chiller vs VRF

    2/26

    2/14

    Copyright 2008 All rights reserved LG Electronics Inc.

    1. Design Comparison

    VRF is very sim pl i f ied refr igerant pip ing system. More f lex ib le than w ater pip ing .

    Chiller

    MULTI V Plus VRF)hiller systemOutdoor unit (air-cooled type)

    Indoor unit

    Refrigerant piping

    Chiller

    FCU (Fan Coil Unit)

    AHU (Air Handling Unit)

    Systemcomposition

    FeatureCooling tower

    Water piping, Duct working

    Water pumps

    System concept

    Design CommissioningOperation MaintenanceInstallation Reliability

  • 5/28/2018 Chiller vs VRF

    3/26

    3/14

    Copyright 2008 All rights reserved LG Electronics Inc.

    Network

    Feature Chiller system

    Complicated wiring

    MULTI V Plus VRF)

    Simple wiring

    Design CommissioningOperation MaintenanceInstallation Reliability

    Easy network wir ing

    1. Design Comparison Network design

    ACP

  • 5/28/2018 Chiller vs VRF

    4/26

    4/14

    Copyright 2008 All rights reserved LG Electronics Inc.

    1. Design Comparison Total management

    Design CommissioningOperation MaintenanceInstallation Reliability

    [Manufacturer]

    VAV boxessupplier

    Controlsystem

    Feature Chiller system MULTI V Plus VRF)

    (For VRF) Manufactu rer prov ide al l equipment

    Simple control structure

    No additional control provider

    Central control and energy monitoring with

    low cost available

    Complicated control structure, additional

    control manager in the system needed,

    increasing cost

    Third part control provider needed,

    interconnectivity problems.

  • 5/28/2018 Chiller vs VRF

    5/26

    5/14

    Copyright 2008 All rights reserved LG Electronics Inc.

    Design Commissioning

    MULTI V Plus VRF)hiller systemThe systems condition only the

    necessary rooms with regardto user demands.

    The systems commonly condition the entire building

    at predetermined times, with no regard to user demands.very hot midnight, weekend, holiday etc)

    Capacitycontrol

    FeatureAfter of f ice hours operat ion, VRF could b e operated for the us er demands.

    Operating Area

    < Limited operation>

    Individual operation

    Operation MaintenanceInstallation Reliability

    2. Operation Comparison

  • 5/28/2018 Chiller vs VRF

    6/26

    6/14

    Copyright 2008 All rights reserved LG Electronics Inc.

    Temperature

    control

    Feature Chiller system

    Require

    1 or 2

    MULTI V Plus (VRF)

    Very precise

    0.5

    Precise temperature co ntro l

    30

    25

    20

    15

    10 20 30 40 50 60 70

    Cooling

    MIN.

    Chiller systemMULTI V system

    Ro

    omt

    emp.

    0.5 0 C from set point

    Design CommissioningOperation MaintenanceInstallation Reliability

    Temp. control2. Operation Comparison

  • 5/28/2018 Chiller vs VRF

    7/267/14 Copyright 2008 All rights reserved LG Electronics Inc.

    VRF system doesnt need a duct space.

    SpaceEfficiency

    Feature MULTI V Plus VRF)Small refrigerant space

    Chiller systemLarge duct space

    Design CommissioningOperation MaintenanceInstallation Reliability

    Space (Duct working)3. Installation Comparison

  • 5/28/2018 Chiller vs VRF

    8/268/14 Copyright 2008 All rights reserved LG Electronics Inc.

    Chiller

    Pump

    Boiler

    Coolingtower

    (On the rooftop)

    (Machine room drawing)

    OutdoorUnit

    (On the rooftop)

    (Rooftop drawing)

    VRF system is no need for a machine room .

    Installationspace

    Feature MULTI V Plus VRF)No need a machine room

    Chiller systemNeed a machine room

    Design CommissioningOperation MaintenanceInstallation Reliability

    Installation space3. Installation Comparison

  • 5/28/2018 Chiller vs VRF

    9/269/14 Copyright 2008 All rights reserved LG Electronics Inc.

    Eff ic ient use of space is pos sib le for VRF system

    Chiller systemSpace

    Efficiency

    Feature

    P P

    1/3

    CHILLER SYSTEM

    Large pipe shaft is needed for water piping

    MULTI V Plus VRF)

    VRF System

    Small pipe shaft is needed

    Design CommissioningOperation MaintenanceInstallation Reliability

    Space (Pipe shaft)3. Installation Comparison

  • 5/28/2018 Chiller vs VRF

    10/2610/14 Copyright 2008 All rights reserved LG Electronics Inc.

    VRF system exp ansion is very easy w ith extra outdoor & indoo r uni t .

    Chiller system

    SystemExpansion

    FeatureCapacity addition is difficult

    as additional mechanical room, pump, cooling tower,

    panel and piping is required.

    MULTI V Plus VRF)

    System Expansion is Easy

    +

    Design CommissioningOperation MaintenanceInstallation Reliability

    System expansion3. Installation Comparison

  • 5/28/2018 Chiller vs VRF

    11/2611/14 Copyright 2008 All rights reserved LG Electronics Inc.

    1 step Commiss ion ing6 steps Commiss ion ing

    MULTI V Plus VRF)hiller systemCommissioning

    FeatureThere are a lot of commiss ioning points fo r the chi l ler system

    6 Steps Commissioning 1 Step Commissioning

    Water cooled chiller (3)

    (4)

    Design CommissioningOperation MaintenanceInstallation Reliability

    NO. of commissioning point4. Commissioning Comparison

  • 5/28/2018 Chiller vs VRF

    12/2612/14 Copyright 2008 All rights reserved LG Electronics Inc.

    Maintenance

    FeatureMaintenance cos ts for a Mult i V is low er than chi l led water systems.

    Water cooled chiller (3)

    (4)

    MULTI V Plus VRF)Filter cleaning

    Heat exchanger cleaning

    Cycle check by notebook (LG MV)

    Chiller systemFilter cleaning

    Duct cleaning

    Water pipe maintenance

    Periodical oil change, overhaul

    Pump

    Water treatment

    Cooling tower cleaning

    Design CommissioningOperation MaintenanceInstallation Reliability

    Maintenance list5. Maintenance Comparison

  • 5/28/2018 Chiller vs VRF

    13/2613/14 Copyright 2008 All rights reserved LG Electronics Inc.

    (For Ch il ler Water treatment is required for c lean water)

    Watertreatment

    Feature Chiller systemWater treatment is required(deficient service can cause legionary disease in the system)

    MULTI V Plus VRF)

    No water treatment is needed

    Design CommissioningOperation MaintenanceInstallation Reliability

    Water treatment5. Maintenance Comparison

  • 5/28/2018 Chiller vs VRF

    14/2614/14 Copyright 2008 All rights reserved LG Electronics Inc.

    Scalecleaning

    Feature Chiller system MULTI V Plus VRF)

    < The system is consist of refrigerant pipes >

    No water pipes : No scale (use refrigerant) Need to clean the water pipes

    System efficiency drop & origin of germs

    After 2~3year After 5~6year After 7~8year10% 25~30% 35~40%

    thickness of scale

    E

    nergy

    Loss

    Unit : mm

    Unit : %

    (For Chi l ler) Maintenance & cleaning per iodical ly by exclu sive com pany

    Design CommissioningOperation MaintenanceInstallation Reliability

    Scale cleaning5. Maintenance Comparison

  • 5/28/2018 Chiller vs VRF

    15/2615/14 Copyright 2008 All rights reserved LG Electronics Inc.

    Maintenance Staff5. Maintenance Comparison

    Design CommissioningOperation MaintenanceInstallation Reliability

    MaintenanceStaff

    Feature Chiller system MULTI V Plus VRF)(For Ch il ler) Cert i f ied maintenan ce staff is needed

    No need special maintenance staff.

    Economic and easy maintenance

    The system requires certified maintenance

    staff not only for chillers but also pumps,

    boilers, cooling towers etc.

    More expensive maintenance cost.

    < Maintenance Staff>

  • 5/28/2018 Chiller vs VRF

    16/2616/14 Copyright 2008 All rights reserved LG Electronics Inc.

    Pipe Erosion6. Reliability Comparison

    Design CommissioningOperation MaintenanceInstallation Reliability

    PipeErosion

    Feature Chiller system MULTI V Plus VRF)(For Ch il ler) Cert i f ied maintenan ce staff is needed

    Refrigerant does not cause corrosion therefore

    no pipe damage occurred

    Pipe erosion can cause leakage.

    System capacity reduction.

    Brines use increase corrosion, anti corrosion

    additives needed

    < Water pipe leakage >

  • 5/28/2018 Chiller vs VRF

    17/2617/14 Copyright 2008 All rights reserved LG Electronics Inc.

    Category Product Initial Cost(USD) Initial Cost(USD)Total

    Water

    Cooled C

    hiller

    Chiller Price 355,484877,097AHU / Cooling Tower / Pump, Pr

    ice 148,065Installation 383,871

    VRV Multi V 874,498 1,109,660Installation 235,161

    April 2008

    Cooling Only

    Air Duct Included

    Initial Cost Running Cost Maintenance Cost Total cost

    Type of Building: Shopping Mall

    Total area 9,000 m2 : 6 storey Building :1,500 m2/floor

    Actual cooling area : 1,500 m2 * 80 % * 6 Floor = 7,200 m2

    Cooling Load (Tr) / m2 : 700 Tr *12000 Btu/Hr = 1,166 Btu/m2

    Equipment : Water cooled chiller /Multi V unit

    - Water Cooled Chiller :Trane Water cooled chiller

    350 Tr x 2 set =700 Tr + 300 Back up

    Pumps =400 Tr x 2 set

    AHU = 8000 CFM x 36 set

    Cooling Tower =1200 Gpm x 3 +3 Back up

    - VRF System :LG Multi V Plus II

    48 Hp x 19 set=912 Hp 726 Tr

    Air conditioning time : Operation

    - 13 hour a day (09:00 ~ 22:00)

    - 30 days a month

    - average load by month

    Equipments & Installation cost

    MULTI V vs Chiller7. Economic analysis

  • 5/28/2018 Chiller vs VRF

    18/2618/14 Copyright 2008 All rights reserved LG Electronics Inc.

    Multi V running cost is 65 % compare to chiller

    Category ProductRunning

    Cost

    (USD)TotalWater

    Cooled Chiller

    Chiller Price308,697AHU / Coolin

    g Tower / Pump, Price

    Multi V Price 200,158Based on KW data chiller/Multi V

    Based on, Thailand electrical standard

    ARI-Air conditioning & Refrigeration Institute

    $0k

    $100k

    $200k

    $300k

    $400k

    year

    2n

    d4th

    6th

    8th

    10th

    12th

    14th

    Chiller

    Multi V

    Running costSavings up to15thyr : 35%

    Chiller

    Multi V

    Electrical cost

    MULTI V vs Chiller7. Economic analysis

    Initial Cost Running Cost Maintenance Cost Total cost

  • 5/28/2018 Chiller vs VRF

    19/2619/14 Copyright 2008 All rights reserved LG Electronics Inc.

    Category Price MaintenanceCost(USD)Total

    Water

    Cooled Chiller

    Chiller Price32,177AHU / Cooling

    Tower / Pump,Price

    Multi V Price 11,468$0k

    $100k

    $200k

    $300k

    $400k

    year

    2nd 4th 6th 8th 10

    th12th

    14th

    Chiller

    Multi V

    Chiller

    Multi V

    MaintenanceCost savingsUp to 15thyr: 66%

    Maintenance breakdown

    Chiller system -31 USD / Rt / yr.- 6 times/yr

    Multi V- 48 USD / Indoor / yr.- 6 times/yr

    - 145 USD / Outdoor / yr.- 6 times/yr

    Multi V maintenance cost is 24 % compare to chiller

    Maintenance cost

    MULTI V vs Chiller7. Economic analysis

    Initial Cost Running Cost Maintenance Cost Total cost

  • 5/28/2018 Chiller vs VRF

    20/2620/14 Copyright 2008 All rights reserved LG Electronics Inc.

    Category Chiller system VRF system Remarks

    EconomicAnalysis

    Initial cost (USD) 877,097 927,057Running cost

    (USD) 308,698 200,158

    Shoppingmall6F,

    9,000

    Maintenace cost(USD) 32,177 11,468

    Total cost (USD) 1,217,972 1,138,683BEP - 1.7 years

    7. Economic analysis

    Initial Cost Running Cost Maintenance Cost Total cost

  • 5/28/2018 Chiller vs VRF

    21/26

    21/14 Copyright 2008 All rights reserved LG Electronics Inc.

    LCC (Life Cycle Cost for 15 years) : Chiller 5.99 M$ > Multi V 4.27 M$ (71%)

    BEP (Break Even Point) : 1.7 Years

    LCC (15 years) BEP

    1st year 2ndyear 3rd year 4th year

    - 20K$

    +10K$

    +40K$

    +70K$

    BEP :1.7 Years

    $0k

    $1000k

    $2000k

    $3000k

    $4000k

    $5000k

    $6000k

    $7000k

    year

    1st

    2nd

    3rd

    4th

    5th

    6th

    7th

    8th

    9th

    10th

    11th

    12th

    13th

    14th

    15th

    Chiller

    Multi V

    Cost savings: 29%

    BEP :1.7 Years

    8. LCC

    CC

  • 5/28/2018 Chiller vs VRF

    22/26

    22/14 Copyright 2008 All rights reserved LG Electronics Inc.

    Chiller Multi V

    1,228

    1,109

    877

    32

    308 20011

    1,3217%

    Product &

    Installation

    Maintenance

    Electrical Fee

    Chiller Multi V

    5,992

    23%15%8%

    77% 73%

    4%

    4,27435%

    Product &Installation

    Maintenance

    Electrical Fee

    Initial Cost (1styear)( K US$ )

    LCC (15 years)

    8. LCC

    A C t ti ti

  • 5/28/2018 Chiller vs VRF

    23/26

    23/14 Copyright 2008 All rights reserved LG Electronics Inc.

    Type of building : Shopping mall

    Water cooled Chiller :350 TR x 2 set=700 Tr + 300Tr (back up)VRF system:48 Hp x 19 set = 912 Hp (726TR)Commercial Building : (Shopping Mall - 9,000 Total Area) - 6 storey building:1500 per floorActual cooling area : 1,500 * 80 * 6F = 7,200Cooling load(TR) / : 700TR * 12,000Btu/h/TR 7,200 = 1167 Btu/

    Capacity Price EA Sub total (THB) Sub total (USD)350 RT 3,960,000 2 7,920,000 255,484

    300 RT 3,100,000 1 3,100,000 100,000

    400 RT 500,000 2 1,000,000 32,258

    400 RT 500,000 1 500,000 16,129

    1200 GPM 100,000 3 300,000 9,677

    840 GPM 90,000 3 270,000 8,710

    8,000 CFM 70,000 36 2,520,000 81,290

    15,610,000 57 503,548

    9,000,000 33% 290,323

    2,900,000 11% 93,548

    11,900,000 43 383,87127,510,000 100 887,419

    48 Hp 957,000 19 18,183,000 586,548

    Indoor unit ceiling duct 10 Hp 91,355 90 8,221,950 265,224

    2,915 90 262,350 8,463

    81,125 1 81,125 2,617

    141,570 1 141,570 4,567

    1,650 57 94,050 3,034

    3,300 38 125,400 4,045

    27,109,445 79 874,498

    Indoor unit ceiling duct

    36,000 90 3,240,000 104,516

    7,290,000 21 235,16134,399,445 100 1,109,660

    I lot

    back up cooling tower (open type)

    Duct working

    45,000

    back up chiller (screw type)

    Wired remote controller

    Centrol controller (ACP)

    Centrol control software (AC Manager)

    Sub totalTotal (Product + Installation)

    Pump (Evaporator) + 1 back up

    AHU

    Outdoor unit

    Sub total

    130,645

    Y branch

    ODU joint

    90 4,050,000

    VRF Sub total

    Sub total

    Outdoor unit

    Total (Product + Installation)

    Product

    Installation

    duct work

    piping & electrical work

    Water CooledChiller(Screwtype)

    Classification

    Pipe & Insulation

    Valve & Acc.

    Power & Control

    Product

    Installation

    Chiller (screw type)

    Cooling tower (open type)

    Pump (Condenser) + 1 back up

    App. Cost estimation

    A A t l i t

  • 5/28/2018 Chiller vs VRF

    24/26

    24/14 Copyright 2008 All rights reserved LG Electronics Inc.

    Energyconsumption

    / unitTotal

    energyconsumption

    kW) kW)271 2 542

    14.9 2 29.84 Load 100% 75% 50% 25%

    55.2 6 331.2 Chillier 542 179 84 47

    2.35 48 112.8 Others 474 474 474 474

    1015.84 Total 1016 653 558 521Outdoor Unit 48 HP-R410a 42 19 798

    Indoor Unit 10 HP CCD 0.8 90 72 Load 100% 75% 50% 25%

    870.0 VRF 870 609 287 16513

    30

    100% kW portion

    1% 100% 542 100% Used by Schedule 4.2.2 condition42% 75% 179.2 33% electrical charge in Thailand45% 50% 83.9 15% THB / month USD

    12% 25% 47.2 9% VRF 517,076 16,680

    Chiller 797,469 25,725

    Gap 280,393 9,045Operation

    hourskWh / day kWh / month

    Operation

    hourskWh / day kWh / month

    0.1 113.1 3,393.0 0.1 132.06 3,961.78

    5.5 3,325.1 99,754.2 5.5 3,565.60 106,967.95 VRF 200,158

    5.9 1,679.5 50,386.1 5.9 3,262.78 97,883.37 Chiller 308,698

    1.6 257.9 7,736.0 1.6 812.82 24,384.67

    13.0 5 375.6 161 269.3 13.0 7,773.3 233,197.8

    VRF system

    Cooling load portion IPLV100% cooling load

    VRF MULTI V system) Chiller system

    75% cooling load

    50% cooling load

    25% cooling load

    VRF

    AHU-10 tr

    Totaloperating time / day (hours)

    operating day / month

    ChillerPower consumption

    Load

    operating cost 1

    year

    hiller system

    Category EA

    Total

    Power consumption under partial loadWaterCooledChillerScrewtype)

    Chiller-350 Tr

    Cooling tower-1260 GPM

    Pump-50 Hp

    App. Actual running cost

    A M i t t

  • 5/28/2018 Chiller vs VRF

    25/26

    25/14 Copyright 2008 All rights reserved LG Electronics Inc.

    Cost Unit350 RT 105,000 Baht/unit 2 210,000

    400 RT 60,000 Baht/unit 2 120,000

    1200 GPM 15,600 Baht/unit 6 93,600

    15 RT 2,000 Baht/unit 70 140,000

    2 persons 20,000 Baht/unit 12 240,000

    803,600840 Hp 3,000 Baht/unit 90 270,000

    Outdoor unit 4,500 19 85,500

    355,500

    THB USD RemarksChiller 997,500 32,177 6 times / year

    270,000 6 times / year

    85,500 6 times / year355,500 11,468

    Pump

    TotalVRF

    1500 THB / indoor unit, year

    4500 THB / ODU module, ye

    950 THB / RT, year

    Control engineer

    Chiller(Screwtype)

    Chiller (Screw type)

    Cooling tower

    AHU

    Total

    TotalVRF

    Indoor unit

    A noteategory Capacity Maintenance cost EA Maintenancecost / year

    App. Maintenance cost

    A E ffi i (IPLV)

  • 5/28/2018 Chiller vs VRF

    26/26

    26/14

    ARI Released The New Standard in 2003

    Available throughthe ARI web site:WWW.ARI.ORG

    Portion by cooling load (%)

    IPLVOR

    APLV

    =

    0.01 + 0.42 + 0.45 + 0.12A B C D

    1

    kW / kW (ARI Part load weighting factors)

    1% 42% 45% 12%

    100% 75% 50% 25%

    WEIGHTED (%)

    ARI550/590-2003

    Cooling Load

    App. Energy efficiency (IPLV)