civ100 wind and earthquake

Upload: pctingeniero

Post on 14-Apr-2018

219 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/27/2019 CIV100 Wind and Earthquake

    1/56

    Chevron Corporation 100-1 September 2000

    100 Wind and Earthquake

    Design Standards

    Abstract

    This section contains guidance for determining wind and earthquake loads on indus-

    trial structures and equipment. It also includes design methods for avoiding wind-

    induced vibration of steel stacks. It is based on ASCE 7-93 and the Uniform

    Building Code (1997). Wind and earthquake loads on tanks, buildings, and offshoreplatforms are beyond the scope of this document. The Tank Manualcovers wind and

    earthquake loads on tanks. Local building codes define lateral loads on buildings.

    Finally, API RP-2A should be used for the design of offshore platforms.

    Maps showing basic wind speeds and seismic zones for the United States are

    included in this section.

    Allowable stresses, foundation stability ratios, soil bearing pressures, and sample

    calculations are also included.

    This section can be used as a design guide for contractors responsible for seismic

    and wind design of new or existing Company facilities. Copies of this section can be

    obtained from CRTC Technical Standards Team. For additional guidance andrequirements, refer to Chevron Specification CIV-EG-5009-C, Structural Design

    Criteria. This document can also be obtained from the CRTC Technical Standards

    Team.

    Contents Page

    110 Design Standards 100-3

    111 Introduction

    112 General

    113 Wind Design

    114 Earthquake Design

    115 Allowable Stresses, Soil Bearing, and Stability Ratios

    120 Methods and Calculations 100-24

    121 Natural Period of Vibration

  • 7/27/2019 CIV100 Wind and Earthquake

    2/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-2 Chevron Corporation

    122 Wind-Induced Vibration of Steel Stacks and Columns

    123 Examples of Wind and Earthquake Load Calculations

    Example 1Two-Story Concrete Vessel Support Structure

    (Assume El Segundo, CA Location)

    Example 2Uniform Cylindrical Column(Assume El Segundo, CA Location)

    Example 3Column of Variable Cross Section

    (Assume Salt Lake City, UT Location)

    Example 4Braced-Column Spheres

    (Assume Richmond, California Location)

    Example 5Vertical Vessels with Unbraced Legs

    (Assume Richmond, CA Location)

    Example 6Stack Vibration and Ovalling

    Example 7Stack Vibration130 References 100-53

  • 7/27/2019 CIV100 Wind and Earthquake

    3/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-3 September 2000

    110 Design Standards

    111 Introduction

    It is important that a civil engineer be consulted whenever new facilities or existing

    structures are being evaluated for seismic and wind loads. This section is for civil

    engineers of all experience levels. Engineers from other disciplines might use this as

    a reference to follow a civil engineers calculations.

    This section gives the reader specific instructions for calculating wind and earth-

    quake loads on structures. It does not describe how to use the loads to calculate

    stresses and design/analyze a structure or piece of equipment. It does, however, give

    allowable stresses and foundation stability information that must be used in wind

    and earthquake design.

    This section includes formulas for natural period of vibration, example load calcula-

    tions, and a method of preventing wind-induced vibration of tall steel stacks.

    Section 110 may be used as a design specification.

    112 General

    These requirements provide the basic criteria for calculating wind and seismic loads

    for Company facilities. For further information and background material used in

    formulating these provisions, a list of references is provided in Section 130.

    For critical structures containing significant quantities of acutely hazardous mate-

    rial whose failure could result in off-site consequences, more stringent require-

    ments may be appropriate. Examples of critical structures are LNG tanks and

    ammonia spheres. The CRTC Civil/Structural Technical Service Team may be

    consulted in these cases.

    Use of Building Codes

    Where legal building code provisions are more stringent and more applicable to a

    particular structure than the guidelines and requirements presented here, then the

    more stringent provisions must necessarily govern the design.

    These provisions apply primarily to framed industrial structures other than build-

    ings and to industrial equipment.

    Load Combinations

    The basic principle of design for lateral forces involves determining the lateralforces due to wind and earthquake (not both at once) and designing for the most

    adverse conditions. Wind or earthquake loads should be combined with all other

    loads which may reasonably be expected to occur simultaneously with the design

    lateral loads. Vessels and other equipment and their supports should be analyzed for

    wind loads combined with gravity loads, both including and excluding the weight of

    the normal contents of the equipment. Earthquake loads need be combined only

  • 7/27/2019 CIV100 Wind and Earthquake

    4/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-4 Chevron Corporation

    with normal operating and gravity loads. Wind and earthquake loads need not be

    combined with hydrostatic test loads.

    Structures designed for wind and earthquake loads must also be capable of with-

    standing all other conditions of loading. Stresses from other loads must not exceed

    normal allowable stresses.

    Load Direction

    The wind or earthquake forces should be considered as acting in any direction, but

    for analysis they can be resolved into components in the directions of the principal

    axes of the structure.

    Dynamic Effects

    Both wind and earthquake effects are dynamic phenomena. However, for the design

    of structures covered by this document, the use of equivalent static forces is

    adequate. Wind design for some structures, e.g., for stacks or slender processing

    columns, must consider dynamic behavior. For earthquake design, dynamic

    behavior is considered to a limited extent in that the lateral force is based on thestructures natural period. For major structures or critical facilities, it may be desir-

    able to use dynamic procedures to supplement the basic static approach.

    Design Standard Basis

    The wind design provisions are based on ASCE 7-93 and the 1997 UBC.1

    The earthquake provisions are similar in form to those in Recommended Lateral

    Force Requirements and Commentary (1997 7th Edition), Structural Engineers

    Association of California, and to the 1997 Uniform Building Code.

    Locations outside the US must determine whether these standards or their own (e.g.,

    Canadas NBC) apply.

    113 Wind Design

    Design wind pressures are dependent on the Wind Speed Zone, which is defined for

    Company locations in Figure 100-1. Use Figure 100-2 to determine the Wind Speed

    Zone for other locations in the United States including Alaska and Hawaii. Increase

    the Wind Speed Zone if warranted by local conditions or anomalies.

    After determining the appropriate Wind Speed Zone, wind forces (Fw) on an

    exposed structure can be calculated:

    FW = (Shape Factor) (Basic Wind Pressure) (Projected Area) (Importance Factor)

    (Eq. 100-1)

    1. The wind load provisions of ASCE 7-95 were reviewed during this manual revision. ASCE 7-95 contains

    changes from previous editions and utilizes 3-second gust wind speeds instead of fastest-mile. However, the

    design wind forces using the ASCE 7-95 criteria are essentially the same as ASCE 7-93 and 1997 UBC criteria.

  • 7/27/2019 CIV100 Wind and Earthquake

    5/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-5 September 2000

    Shape factors for various elements are defined in Figure 100-3. The wind impor-

    tance factor IW shall be taken as 1.0 for normal non-critical oil industry structures.

    For critical structures or structures housing or supporting acutely hazardous mate-

    rials (AHMs) Iw shall be taken as 1.15.

    Fig. 100-1 Wind Speed Zone for Company Locations

    Location

    Wind Speed Zone

    (mph)

    California

    Bakersfield/Cymric/McKittrick/Kern River/Taft 70

    Carpinteria/Gaviota 70

    El Segundo 70

    Richmond 70

    Colorado

    Rangely 70

    Hawaii

    Barbers Point/Honolulu 80

    Louisiana

    Venice/Leeville/Oak Point/Morgan

    City/Cameron/St. James 100

    Mississippi

    Pascagoula 100

    Ohio

    Marietta 70

    Oregon

    Willbridge 75

    Texas

    El Paso 75

    Cedar Bayou/Houston/Mont Belvieu 90

    Orange 95

    Port Arthur 100

    Utah

    Salt Lake City 70

    Washington

    Kennewick 75

    Wyoming

    Evanston 75

    Rock Springs 80

  • 7/27/2019 CIV100 Wind and Earthquake

    6/56

    ChevronCorporation

    100-6

    September2000

    Fig. 100-2 Basic Wind Speeds for the United States (from 1997 Ed. UBC) Reproduced from the 1997 edition of

    1997, with the permission of the International Conference of Building Officials

  • 7/27/2019 CIV100 Wind and Earthquake

    7/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-7 September 2000

    Basic Wind Pressures are defined in Figure 100-4 and are a function of exposures.

    Exposure B has terrain which has buildings, forest or surface irregularities 20 feet or

    more in height covering at least 20 percent of the area, extending one mile or more

    from the site. Exposure C has terrain which is flat and generally open, extending

    one-half mile or more from the site in any full quadrant. Exposure D represents the

    most severe exposure in areas with basic wind speeds of 80 mph or greater and has

    terrain which is flat and unobstructed facing large bodies of water over one mile or

    Fig. 100-3 Shape Factors For Wind Load Calculation

    The shape factor shall be 1.3 for structures 40 feet or less in height and 1.4 for structures over 40 feet

    in height, except as specified below:

    Spheres 0.65

    Tanks, stacks (except for cooling towers or stacks with helical spoilers) andother cylindrical structures, excluding appendages

    0.8

    Induced draft cooling towers: 1.3 +(0.2N)

    N = number of cells in direction of wind loading

    Total design pressure shall not be less than 23 psf at any height.

    Cooling tower stacks 0.9

    Stacks with helical spoilers (projected area to include the spoilers, i.e., to

    outside

    diameter of spoilers)

    1.2

    Columns and vessels, including normal piping and platforms:

    Under 4-ft diameter 1.4

    4-ft to 8-ft diameter 1.7 (0.075D)

    Over 8-ft diameter 1.1

    D = Outside diameter, including insulation, ft

    Elements of structures:

    Applies to the projected framing area of the wind members on any elementexposed to the wind (i.e., consider both columns for a frame parallel to the

    wind).

    2.0

    (Forces on equipment and piping supported on the structure shall be added.)

    Flat or angular sections 1.3

    Cylindrical members (including piping):

    Two inches or less in diameter

    Over two inches in diameter

    1.0

    0.8

  • 7/27/2019 CIV100 Wind and Earthquake

    8/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-8 Chevron Corporation

    more in width. Exposure D extends inland from the shoreline .25 miles or 10 times

    building height, whichever is greater.

    Fig. 100-4 Basic Wind Pressures (psf) for Heights above Ground

    HeightWind Speed (MPH)

    Exposure

    70 75 80 85 90 95 100 110

    0-15 ft.

    20

    25

    30

    40

    60

    80

    100

    120

    160

    200

    300

    400

    8

    8

    9

    10

    11

    12

    13

    14

    15

    16

    18

    20

    22

    9

    10

    10

    11

    12

    14

    15

    16

    17

    19

    20

    23

    26

    10

    11

    12

    12

    14

    16

    17

    19

    20

    21

    23

    26

    29

    11

    12

    13

    14

    15

    18

    19

    21

    22

    24

    26

    30

    33

    13

    14

    15

    16

    17

    20

    21

    23

    25

    27

    29

    33

    37

    14

    15

    16

    17

    19

    22

    24

    26

    28

    30

    32

    37

    41

    16

    17

    18

    19

    21

    24

    26

    29

    31

    33

    36

    41

    46

    19

    21

    22

    23

    26

    29

    32

    35

    37

    40

    44

    50

    55

    B

    0-15 ft.

    20

    25

    30

    40

    60

    80

    100

    120

    160200

    300

    400

    13

    14

    15

    16

    16

    18

    19

    20

    21

    2223

    26

    28

    15

    16

    17

    18

    19

    21

    22

    23

    24

    2627

    30

    32

    17

    18

    19

    20

    21

    23

    25

    26

    27

    2931

    34

    36

    20

    21

    22

    23

    24

    26

    28

    30

    31

    3335

    38

    41

    22

    23

    25

    26

    27

    30

    32

    33

    35

    3739

    43

    46

    24

    26

    27

    29

    30

    33

    35

    37

    39

    4143

    47

    51

    27

    29

    30

    32

    33

    37

    39

    41

    43

    4648

    53

    56

    33

    35

    37

    38

    40

    44

    47

    50

    52

    5558

    64

    68

    C

  • 7/27/2019 CIV100 Wind and Earthquake

    9/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-9 September 2000

    The values of basic wind pressures in Figure 100-4 include: Structure Importance

    Factor for wind, Velocity Pressure Exposure Coefficient, and a Gust Response

    Factor per ASCE 7-93.

    Use the projected area of each element within each height zone for calculating the

    force. The total force on the structure is the sum of the forces on all the elements,

    including wind up-lift forces on the surfaces of horizontal projections. Apply all

    forces at the centroids of the projected areas. For example calculations, demon-

    strating wind design methodology, see Section 123, Examples of Wind and Earth-quake Load Calculations. Other wind design concerns include wind-induced

    vibration of stacks, above-grade pipelines, or any slender element which can be

    excited aerodynamically. See Section 122 for an analysis of this problem.

    114 Earthquake Design

    These requirements are intended only for use in designing ordinary industrial struc-

    tures. They are not intended to cover offshore platforms or buildings.

    These criteria are adequate for most conditions. However, specific sites may present

    special seismic hazards, such as soil liquefaction, landslide, surface rupture, and

    tsunami that require additional design considerations beyond the scope of this docu-ment.

    These provisions shall apply to the structure as a unit and also to the individual parts

    of a structure.

    0-15 ft.

    20

    25

    30

    40

    60

    80

    100

    120

    160

    200

    300

    400

    17

    18

    19

    19

    20

    22

    23

    24

    24

    25

    26

    28

    29

    20

    21

    22

    22

    23

    25

    26

    27

    28

    29

    30

    32

    34

    23

    24

    24

    25

    27

    28

    30

    31

    31

    33

    34

    36

    38

    26

    27

    28

    28

    30

    32

    33

    35

    36

    37

    39

    41

    43

    29

    30

    31

    32

    34

    36

    37

    39

    40

    42

    43

    46

    48

    32

    33

    35

    36

    37

    40

    42

    43

    44

    47

    48

    51

    54

    35

    37

    38

    39

    42

    44

    46

    48

    49

    52

    54

    57

    60

    43

    45

    46

    48

    50

    53

    56

    58

    59

    62

    65

    69

    72

    D

    Note For regions between the hurricane oceanline and 100 miles inland, the basic wind pressures shall be determined by

    linear interpolation. At the hurricane oceanline, the basic wind pressures shall be multiplied by 1.05. At 100 miles from

    the hurricane oceanline, the basic wind pressures shall be multiplied by 1.00. Hurricane oceanlines are the Atlantic and

    Gulf of Mexico coastal areas.

    Fig. 100-4 Basic Wind Pressures (psf) for Heights above Ground (Contd.)

    HeightWind Speed (MPH)

    Exposure

    70 75 80 85 90 95 100 110

  • 7/27/2019 CIV100 Wind and Earthquake

    10/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-10 Chevron Corporation

    Structural Systems Similar to Buildings (SSSB)

    A concentric braced frame is a braced frame in which the members are subjected

    primarily to axial forces.

    A shear wall is a wall designed to resist lateral forces parallel to the plane of the

    wall (sometimes referred to as a vertical diaphragm).

    A light-framed wall with shear panels is similar to a shear wall system except the

    vertical diaphragm is usually light gage metal, i.e., similar to a refinery box furnace.

    A moment-resisting space frame is a structural system in which the members and

    joints are capable of resisting lateral forces primarily by flexure. An ordinary

    moment-resisting space frame (OMRSF) is a moment-resisting space frame not

    meeting special detailing requirements for ductile behavior. An intermediate

    moment-resisting space frame (IMRSF) is a concrete space frame designed in

    conformance with UBC Section 1921.8. A special moment-resisting space frame

    (SMRSF) is a moment-resisting space frame specially detailed to provide ductile

    behavior and comply with the requirements given in UBC Section 1921 for concrete

    and UBC Chapter 22, Division IV or V for steel.

    An induced draft cooling tower is typically a timber structure with some type of

    internal brace system.

    Nonbuilding-Type Structures

    These structures include all self-supporting structures (equipment with integral

    supports) other than buildings which carry gravity loads and resist the effects of

    earthquake. Nonbuilding structures also include structures supporting equipment

    with structural systems similar to buildings (SSSB).

    Design Base Shear for Structures

    The determination of design base shear is directly related to the structures

    fundamental period of vibration, T. The fundamental period of a structure can be

    determined by rational methods as demonstrated in Section 121, Natural Period of

    Vibration. Structures with longer periods of vibration, such as stacks, frames, one-

    column pipe supports, and vertical vessels, will typically be governed by

    Equation 100-2 below. Rigid structures with a short period of vibration, such as

    short horizontal vessel supports or pump foundations, will typically be governed by

    Equation 100-6.

    It is important to note that the earthquake design forces specified by the 1997

    Uniform Building Code are based on strength design; whereas in past editions of the

    UBC the design forces were based on allowable stress design. Because this section

    is based on the 1997 UBC, the following equations will provide results which are

    strength design based. If one desires to use allowable stress design, the earthquake

    forces calculated using the following equations need to be divided by a factor of 1.4.

    For structure systems similar to buildings (such as those listed in sections I and II of

    Figure 100-11) the total design base shear in a given direction shall be:

  • 7/27/2019 CIV100 Wind and Earthquake

    11/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-11 September 2000

    (Eq. 100-2)

    With the conditions that:

    (Eq. 100-3)

    and

    (Eq. 100-4)

    In addition, for Seismic Zone 4,

    (Eq. 100-5)

    For nonbuilding structures (such as those listed in Sections III and IV of

    Figure 100-11) and having a period, T, less than 0.06 seconds, the total design base

    shear shall be:

    (Eq. 100-6)

    For flexible nonbuilding structures (such as those listed in sections III and IV of

    Figure 100-11), Equation 100-2 and Equation 100-3 shall apply, with the additional

    stipulations that:

    (Eq. 100-7)

    and additionally, for Seismic Zone 4,

    (Eq. 100-8)

    The coefficients used above are defined as follows:

    V = Total base shear

    Z = Seismic zone factor

    I = Occupancy importance factor

    Ca, Cv = Site-dependent seismic coefficients representing the ground

    motion

    Na, Nv = Near-source factors related to the proximity of the structure to

    known faults in seismic zone 4

    VCvI

    RT--------W=

    Vmax

    2.5CaI

    R---------------- W=

    Vmin 0.11CaIW=

    Vmin

    0.8ZNvI

    R--------------------W=

    V 0.7CaIW=

    Vmin 0.56CaIW=

    Vmin

    1.6ZNvI

    R--------------------W=

  • 7/27/2019 CIV100 Wind and Earthquake

    12/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-12 Chevron Corporation

    R = Structural system factor

    T = Fundamental period of vibration, in seconds, of the structure in

    the direction under consideration. See Section 121, Natural

    Period of Vibration

    W = Total seismic deadload plus operating weight

    The Seismic Zone Factor, Z, shall be as specified below for the earthquake zone in

    which the structure is located. The earthquake zone shall be as listed in Figure 100-5

    and shown on Figure 100-6.

    Seismic Zone

    Corresponding Seismic Zone

    Factor, Z

    0 0

    1 0.075

    2A 0.15

    2B 0.203 0.30

    4 0.40

    Fig. 100-5 Seismic Zone for Company Locations (1)

    Location

    Earthquake

    Zone Na Nv

    California

    Bakersfield/Cymric/McKittrick/Kern

    River/Taft 4 1.0 1.0

    Carpinteria 4 1.3 1.6

    El Segundo 4 1.1 1.33

    Gaviota 4 1.1 1.33

    Richmond 4 1.2 1.6

    Colorado

    Rangely 1

    Hawaii

    Barbers Point/Honolulu 2A

    Louisiana

    Venice/Leeville/Oak Point/Morgan

    City/Cameron/St. James 0

    Mississippi

    Pascagoula 0

    Ohio

    Marietta 1

  • 7/27/2019 CIV100 Wind and Earthquake

    13/56

    ChevronCorporation

    100-13

    September2000

    Oregon

    Willbridge 3

    Texas

    Cedar Bayou/Houston/Mont

    Belvieu/

    Orange/Port Arthur 0

    El Paso 1

    Utah

    Salt Lake City 3

    Washington

    Kennewick 2B

    Wyoming

    Evanston 2B

    Rock Springs 1

    (1) Near-source factors (Na and Nv) are given for Company locations found in Zone 4 only.

    Fig. 100-5 Seismic Zone for Company Locations (Contd.)(1)

    Location

    Earthquake

    Zone Na Nv

  • 7/27/2019 CIV100 Wind and Earthquake

    14/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-14 Chevron Corporation

    The Occupancy Importance Factor, I, shall be taken as 1.0 for normal non-critical

    oil industry structures. For critical structures or structures housing or supporting

    acutely hazardous materials (AHMs), I shall be taken as 1.25. See Figure 100-12.

    The seismic coefficients, Ca

    and Cv, shall be determined using Figures 100-7 and

    100-8:

    Ca and Cv represent the ground motion, and are a function of the seismic zone (Z)

    and the soil profile type (given in 100-9). In seismic zone 4 only, Ca and Cv are also

    a function of the near source factors Na and Nv. Na and Nv factors are dependent on

    the distance of the structure to known active large magnitude faults. The Na and Nv

    factors for Company locations in seismic zone 4 are given in 100-5.

    Fig. 100-6 Seismic Zone Map of the United States (from 1997 ed. of UBC) Reproduced from the 1997

    edition of the Uniform Building Code 1997, with the permission of the International Confer-ence of Building Officials

  • 7/27/2019 CIV100 Wind and Earthquake

    15/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-15 September 2000

    A review of the Design Response Spectra (shown in Figure 100-10) helps to illus-

    trate how the seismic coefficients Ca and Cv define the seismic response throughout

    the spectral range. There are two basic regions to the response spectrum-short

    period

    (T < TS) and long period (T > TS). Equation 100-2 represents the curved (long

    period) portion of the response spectrum, while Equation 100-3 represents the flat(short period) portion of the spectrum.

    The Structural System Factor, R, reflects the expected earthquake resistance for

    different types of structures. It is a numerical coefficient which represents the

    inherent global energy absorbing capability or ductility and overstrength in a

    particular type of structural system. Values for R for a wide variety of structural

    systems are presented in Figure 100-11.

    Fig. 100-7 Seismic Coefficient Ca(Reproduced from the 1997 edition of the Uniform Building Code 1997, with the permission of the International Conference of Building Officials)

    Seismic Zone Factor, Z

    Soil Profile

    Type Z = 0.075 Z = 0.15 Z = 0.2 Z = 0.3 Z = 0.4

    SA 0.06 0.12 0.16 0.24 0.32Na

    SB 0.08 0.15 0.20 0.30 0.40Na

    SC 0.09 0.18 0.24 0.33 0.40Na

    SD 0.12 0.22 0.28 0.36 0.44Na

    SE 0.19 0.30 0.34 0.36 0.36Na

    SF See Footnote(1)

    (1) Site-specific geotechnical investigation and dynamic site response analysis shall be performed to determine seismic coeffi-

    cients for Soil Profile Type SF.

    Fig. 100-8 Seismic Coefficient Cv(Reproduced from the 1997 edition of the Uniform Building Code 1997, with the permission of the International Conference of Building Officials)

    Seismic Zone Factor, Z

    Soil Profile

    Type Z = 0.075 Z = 0.15 Z = 0.2 Z = 0.3 Z = 0.4

    SA 0.06 0.12 0.16 0.24 0.32Nv

    SB 0.08 0.15 0.20 0.30 0.40Nv

    SC 0.13 0.25 0.32 0.45 0.56Nv

    SD 0.18 0.32 0.40 0.54 0.64Nv

    SE 0.26 0.50 0.64 0.84 0.96Nv

    SF See Footnote(1)

    (1) Site-specific geotechnical investigation and dynamic site response analysis shall be performed to determine seismic coeffi-

    cients for Soil Profile Type SF.

  • 7/27/2019 CIV100 Wind and Earthquake

    16/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-16 Chevron Corporation

    Two major types of structural systems exist, e.g., structures similar to buildings, andnonbuilding-type structures, each having a different minimum design requirement.

    Fig. 100-9 Site Coefficients (Reproduced from the 1997 edition of the Uniform Building Code 1997,with the permission of the International Conference of Building Officials)

    Soil

    Profile

    Type

    Soil Profile

    Name/Generic Descrip-

    tion

    Shear Wave

    Velocity Vs

    feet/second

    (m/s)

    Standard Pene-

    tration Test, N

    [or NCH for cohe-

    sionless soil

    layers]

    (blows/foot)

    Undrained Shear

    Strength SU psf

    (kPa)

    SA Hard Rock > 5,000

    (1,500)

    --- ---SB Rock 2,500 to 5,000

    (760 to 1,500)

    SC Very Dense Soil and Soft

    Rock

    1,200 to 2,500

    (360 to 760)

    > 50 > 2,000

    (100)

    SD Stiff Soil Profile 600 to 1,200

    (130 to 360)

    15 to 50 1,000 to 2,000

    (50 to 100)

    SE(1) Soft Soil Profile < 600

    (180)

    < 15 < 1,000

    (50)

    SF Soil Requiring Site-specific Evaluation. See Section 1629.3.1.

    (1) Soil Profile Type SE also includes any soil profile with more than 10 feet (3048 mm) of soft clay defined as a soil with a

    plasticity index,

    PI> 20, wmc 40 percent and su < 500 psf (24 kPa). The Plasticity Index, PI, and the moisture content, wmc, shall bedetermined in accordance with approved national standards.

  • 7/27/2019 CIV100 Wind and Earthquake

    17/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-17 September 2000

    Fig. 100-10Design Response Spectra (Reproduced from the 1997 edition of the

    Uniform Building Code 1997, with the permission of the InternationalConference of Building Officials)

    Fig. 100-11Structural System Factors (R Factors) (1 of 2)

    Structural System Description

    I. STRUCTURAL SYSTEMS SIMILAR TO BUILDINGS (SSSB) Structural System Factor,R

    Steel Structures

    Special moment resisting frame 5.6

    Ordinary moment resisting frame 4.5

    Braced frame

    a. Eccentrically braced frame 5.6

    b. Concentrically braced frame 4.5

    Inverted pendulum type structure (cantilever column) 2.2

    Concrete StructuresSpecial moment resisting frame 5.6

    Intermediate moment resisting frame(1) 4.5

    Ordinary moment resisting frame(2) 3.5

    Shear wall 4.5

    Inverted pendulum type structure (cantilever pier/column) 2.2

  • 7/27/2019 CIV100 Wind and Earthquake

    18/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-18 Chevron Corporation

    II. PIPEWAYS

    Steel

    Special moment resisting frame 5.6

    Ordinary moment resisting frame 4.5

    Braced frame (CBF) 4.5

    Cantilever column 2.9

    Concrete

    Special moment resisting frame 5.6

    Intermediate moment resisting frame(1) 4.5

    Ordinary moment resisting frame(2) 3.5

    Cantilever column 2.9

    III. EQUIPMENT BEHAVING AS STRUCTURES WITH INTEGRAL SUPPORTS

    Vertical vessels/heaters, tanks, or spheres supported by:

    Steel skirts 2.9

    Steel skirt when tshell/tskirt > 1.5 2.2

    Steel braced legs 2.9

    Steel or concrete unbraced legs 2.2

    Horizontal vessels

    Flexible concrete support 2.2

    Boilers

    Light steel framed wall with shear panels 4.5

    Steel braced frame where bracing carries gravity load 4.5

    Steel ordinary moment frame 4.5

    Chimneys, stacks, or truss covers

    Steel guyed 2.9

    Steel cantilever 2.9

    Concrete 2.9

    IV. COOLING TOWERS

    Wood frame 5.6

    Concrete 3.6

    Notes: 1. Some R values are slightly different than those prescribed by the 1997 UBC. This is in accordance with the ASCE

    Publication Guidelines for Seismic Evaluation and Design of Petrochemical Facilities.

    2. For analysis of existing Moment-Resisting Frames, use R for an Ordinary Moment-Resisting Frame unless a different

    value can be justified.

    3. If assigning a value of R to a system not itemized in this table, in the absence of a detailed study, use R = 2.1. CRTCs

    Civil/Structural Team is available for counsel on this subject.

    (1) Prohibited in Seismic Zones 3 and 4, except as permitted in UBC Section 1634.2.

    (2) Prohibited in Seismic Zones 2A, 2B, 3, and 4.

    Fig. 100-11Structural System Factors (R Factors) (2 of 2)

  • 7/27/2019 CIV100 Wind and Earthquake

    19/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-19 September 2000

    Vertical Distribution of Base Shear Force for Free StandingStructures

    For structures having a natural period, T, greater than 0.7 sec., a portion of the total

    base shear force, V, shall be applied at the top of the structure, as determined by the

    following equation:

    Ft = 0.07 TV (Eq. 100-9)

    where:

    Ft = Portion of base shear applied at the top of the structure.

    T = Structure natural period of vibration, sec.

    V = Total base shear from appropriate equation (Equation 100-2

    through Equation 100-8)

    Ft need not exceed 0.25V (applies when T is equal to or greater than 3.57 sec.). If T

    is less than or equal to 0.7 sec., Ft shall be taken as zero.

    The remainder of the total base shear force shall be distributed and applied to thevarious masses in the structure in accordance with the following equation:

    (Eq. 100-10)

    where:

    Fx = Lateral force applied to a mass at level x.

    Wx = Weight of the mass at level x.

    hx = Height of level x above the base (normally the bottom of the base

    plate of the structure or portion of the structure being analyzed)

    V = Total base shear from appropriate equations (Eq. 100-2 through100-8)

    Wh = The sum of the products of Wx and hx for all the masses withinthe structure.

    Vertical Distribution of Base Shear Force for Guyed Structures

    Where guys are used to provide lateral force resistance, the total lateral force shall

    be distributed to the various masses in direct proportion to their weights and shall be

    applied at their centers of gravity. See Section 300, Industrial Structures, for more

    information on the design of guyed structures.

    Horizontal Distribution of Base Shear ForceThe total shear in any horizontal plane shall be distributed to the various resisting

    elements in proportion to their rigidities, considering the rigidity of the horizontal

    bracing system or diaphragm as well as the rigidities of the vertical resisting

    elements. Provision shall be made for the increase in shear resulting from the hori-

    zontal torsion due to an eccentricity between the center of mass and the center of

    rigidity. Negative torsional shears may be neglected. In addition, where the vertical

    Fx V Ft( )Wxhx

    Wh-------------=

  • 7/27/2019 CIV100 Wind and Earthquake

    20/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-20 Chevron Corporation

    resisting elements depend upon diaphragm action for shear distribution at any level,

    the shear resisting element shall be capable of resisting a torsional moment assumed

    to be equal to the shear at the level, acting with an eccentricity of not less than 5%

    of the maximum structure plan dimension at that level.

    Details of Earthquake Resistant DesignMuch of the damage sustained in past earthquakes could have been avoided through

    proper detailing of structural elements and connections. It is important in earth-

    quake-resistant design to give the structure the ability to absorb energy if loaded to

    levels above the minimum design. This quality is best achieved by detailing the

    structural frame, the members, and the connections so that overall structural defor-

    mation will be ductile rather than brittle. This flexibility is particularly desirable for

    reinforced concrete construction. Structures should also have a consistent stress

    level, or margin of reserve strength throughout.

    An increased force, Em, shall be used for the design of crucial structural

    components in the lateral force resisting system such as collector elements, steel

    connections, and elements supporting discontinuous systems. The symbol Em repre-sents the estimated maximum earthquake force that can be developed in a structure.

    It is a function of the base shear and the system overstrength, which takes into

    account factors such as material overstrengths, advantageous collapse mechanisms,

    and the type of lateral force resisting system. For more information on this topic,

    contact the CRTC Civil/Structural Team.

    The following general comments apply to structures and components of structures.

    1. Masonry StructuresAlways reinforce in accordance with Section 2106 of the

    Uniform Building Code.

    2. Reinforced Concrete StructuresConcrete frames in Seismic Zones 3 and 4

    shall be Special Moment Resisting Space Frames (SMRSF). Concrete frames inSeismic Zones 2A and 2B shall be, as a minimum, an Intermediate Moment

    Resisting Space Frame (IMRSF). Concrete shear walls, braced frames, or

    moment resisting frames used to resist earthquake forces shall be designed in

    accordance with Section 1921 of the Uniform Building Code.

    3. Steel StructuresPay special attention to connections. At connections and

    other points of high stress in rigid frame structures, follow the requirements of

    the AISC Specification for plastic design regarding width-thickness ratios,

    lateral bracing, web stiffening, and fabrication. Follow the provisions of

    Chapter 22, Divisions IV or V of the Uniform Building Code.

    4. Vessels, Columns and SpheresMinimize stress raisers and provide for conti-

    nuity of reinforcement around openings. Use bracing effective in tension and

    compression for braced legs of spheres and vertical vessels. Anchor bolts

    should be sized to resist the maximum predicted earthquake forces. Use the

    Standard Anchor Bolt Drawing (GD-Q68922) for bolt selection and spacing.

    This drawing was developed based on a ductile failure criteria. Do not oversize

    the anchor bolts as this will result in a non-ductile failure.

  • 7/27/2019 CIV100 Wind and Earthquake

    21/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-21 September 2000

    5. FoundationsProvide tie beams, reinforced concrete slabs, or other equivalent

    restraint interconnecting individual footings on piles when the surface soil does

    not provide adequate lateral restraint.

    See Sections 1626 through 1636 of the Uniform Building Code for general earth-

    quake regulations.

    Electrical and Mechanical Equipment

    All equipment and equipment anchorage to foundations or supporting structures

    shall be designed to resist a minimum lateral earthquake force acting at the center of

    mass of the equipment. This provision includes such items as switch gear, trans-

    formers, vessels supported in structures, control panels, etc.

    For equipment supported by a structure:

    (Eq. 100-11)

    With the condition that:

    (Eq. 100-12)

    (Eq. 100-13)

    where:

    For rigid equipment supported at grade (such as a transformer, switchgear, etc.):

    (Eq. 100-14)

    Fp = Design lateral earthquake force

    IP = Seismic importance factor (See Figure 100-12)

    Wp = Total operating weight of equipment

    ap = In-Structure Component Application Factor (from Figure 100-13)

    Rp = Component Response Modification Factor (from Figure 100-13)

    hx = element or component attachment elevation with respect to grade.

    hx shall not be less than 0.0

    hr = structure roof elevation with respect to grade

    Fig. 100-12Seismic Importance Factor

    Description I IP

    Equipment required for life safety systems 1.25 1.5

    Items containing sufficient quantities of acutely

    hazardous material whose failure could result in off-site

    consequences.

    1.25 1.5

    All other equipment or normal non-critical structures 1.0 1.0

    Critical structures 1.25 1.5

    Fp

    apCaIp

    Rp----------------- 1 3

    hx

    hr-----+

    Wp=

    Fpmin 0.7CaIpWp=

    Fpmax 4.0CaIpWp=

    Fp 0.7CaIpWp=

  • 7/27/2019 CIV100 Wind and Earthquake

    22/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-22 Chevron Corporation

    Direct anchorage through anchor bolts shall be provided where possible. For

    shallow expansion anchor bolts, use Rp = 1.5. For nonductile or adhesive anchor

    bolts, use Rp = 1.0. In situations where anchor bolt connections are impractical, a

    welded ductile connection between equipment and support may be provided. A

    ductile connection shall be defined as one that will undergo inelastic deformation

    through yielding before the connection fails. The direct welding of rigid equipment

    to a rigid foundation or support is not recommended.

    Appendix H, Determination of Base Shear for Selected Structures, indicates the

    appropriate base shear equations that should be used for many typical refinery struc-

    tures and types of equipment. Appropriate R values are also included.

    Displacement

    There is no specific code requirement which limits the lateral displacement/drift in

    industrial structures. However, it is recommended that the lateral displacement be

    limited to a displacement that can be tolerated by the equipment being supported,

    including the associated piping and other appurtenances.

    The Maximum Inelastic Response Displacement, M, corresponds to the maximumdeformations of a structure responding in the inelastic range. In order to calculateM, the design level displacement (S) is simplified to the inelastic level using thefollowing equation:

    (Eq. 100-15)

    where:

    M is as defined above

    S is the displacement corresponding to the code-level design seismic forces

    R is the structural system factor.

    The analysis used to determine the Maximum Inelastic Response Displacement

    (M) shall consider P effects. For guidance on this subject, contact the CRTCCivil/Structural Team.

    Earthquake Loads

    To design a structure, calculate the forces to be applied to each element of the

    structure. The earthquake load (E) on an element of a structure is a result of the

    Fig. 100-13Horizontal Force Factors (ap and Rp)

    Equipment Description ap Rp

    1. Vessels (including contents), and their support systems 1.0 3.0

    2. Electrical, mechanical, and plumbing equipment and associated conduit

    and ductwork and piping such as switchgears, transformers, pumps, andair-handling units.

    1.0 3.0

    NOTE:

    Refer to UBC Table 16-0 for a more extensive listing of horizontal force factors.

    M 0.7RS=

    http://civ.pdf/http://civ.pdf/http://civ.pdf/http://civ.pdf/
  • 7/27/2019 CIV100 Wind and Earthquake

    23/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-23 September 2000

    combination of the horizontal component (Eh) and the vertical component (Ev), and

    can be calculated using the following equation:

    (Eq. 100-16)

    where:

    = redundancy/reliability factor

    = 1.0 for nonbuilding structures and for structures in seismic zone

    0, 1, or 2

    1.0 for structural systems similar to buildings (SSSB) in seismiczone 3 or 4

    Eh = earthquake load due to either the base shear (V) or the design

    lateral force (Fp)

    Ev = the load effect resulting from the vertical component of the earth-

    quake ground motion

    = 0.5CaID for Strength Design

    = 0 for Allowable Stress Design

    The intent of the factor is to encourage the design of redundant lateral forceresisting structures by penalizing non-redundant structures. There are a number of

    important benefits to redundancy, one of the most evident being that the failure of

    any single element in a non-redundant structure can produce global structural

    collapse. Therefore, in order to obtain good seismic performance, the lateral resis-

    tance should be distributed throughout the structure so that failure of any single

    element will not result in collapse of the entire structure. The factor variesbetween 1.0 and 1.5, and takes into account the number of lateral force resisting

    elements, the plan area of the structure, and the distribution of the forces to thelateral force resisting elements. For a structure with an adequate level of redun-

    dancy, the factor would be equal to 1.0; whereas a structure with poor overallredundancy could have a factor of up to 1.5, resulting in design forces that are50% higher than otherwise required. Contact the CRTC Civil/Structural Team for

    guidance on this subject.

    Analysis of Existing Facilities

    These Design Standards are intended to apply to the design of new facilities. In

    general, structures and equipment properly designed in accordance with earlier

    codes need not be redesigned to meet the present Wind and Earthquake Design

    Standards. However, when any significant modification is made or weight is added

    to an existing structure, the design should be reviewed. If required, the structure

    should be modified to meet the requirements of the appropriate building code.

    Although current building codes do not require the upgrading of existing facilities,

    in keeping with Corporate Policy 530 for Safety, Fire, Health, and the Environment,

    it may be appropriate to review the design of facilities in critical service. A portion

    of that policy instructs management to conduct scientific hazard and risk assess-

    E Eh Ev+=

  • 7/27/2019 CIV100 Wind and Earthquake

    24/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-24 Chevron Corporation

    ments, as needed, to identify, characterize, and safely manage any present or future

    potential hazards of Company products and operations.

    A critical facility is defined as one for which a major failure would cause one of the

    following:

    1. Develop a condition which would result in serious injury or death.

    2. Result in damage to the environment significantly beyond that which the earth-

    quake would cause at the site.

    3. Result in appreciable loss of revenue.

    To evaluate the risk of a critical facility, the following steps are recommended:

    1. Determine the existing strength of the structures.

    2. Make a judgment as to whether the existing strength is acceptable in light of

    current conditions, including the types of risk factors previously noted.

    The judgments required to determine acceptability should include evaluation ofstructural redundancy and reserve strength. The assessment of existing facilities for

    earthquake capacity is not commodity engineering and should be done by qualified

    personnel.

    Since most assessments of existing facilities are voluntary efforts to mitigate

    potential business risks, it is not always necessary or even beneficial to measure a

    structures acceptability against the current building code requirements. CRTCs

    Civil/Structural Technical Service Team has performed many seismic assessments

    of Company owned facilities utilizing Proposed Guidance for Risk Management

    and Prevention Program (RMPP) Seismic Assessments. This document was

    developed in 1992 by a team of technical experts and industry professionals to aid

    in the assessment of seismic risk at existing industrial facilities. In 1998, thisdocument was revised and renamed Proposed Guidance for California Accidental

    Release Prevention (CalARP) Program Seismic Assessments.

    Proposed Guidance for CalARP Seismic Assessments evaluates the ultimate

    strength capacity of existing structures. The ultimate strength capacity of a structure

    is defined here as the ability of a structure to perform inelastically while avoiding

    failure. The ultimate strength must be compared to the expected structural demand

    resulting from the expected levels of ground shaking at the site. The CalARP guide-

    lines utilize the same level of acceptable risk as that defined in the current UBC, i.e.,

    the level of ground motion associated with a 10 percent chance of exceedance in 50 years.

    For facilities with unacceptably low strength, one of the following should be

    considered:

    1. Strengthen the facility

    2. De-rate the facility to lower the risk of failure. For example, reduce the safe

    operating height for tanks.

    CRTCs Civil/Structural Technical Service Team is available for counsel regarding

    these procedures and judgments.

  • 7/27/2019 CIV100 Wind and Earthquake

    25/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-25 September 2000

    115 Allowable Stresses, Soil Bearing, and Stability Ratios

    Allowable Stresses for Structural Members

    The allowable stresses for structural members for loading conditions including wind

    or earthquake loads shall be one-third greater than the stresses allowed for normal

    conditions of loading by applicable structural design codes.

    Stability Ratio

    The stability ratio of the resisting moments about the edge of a foundation to the

    overturning moment due to wind loads shall not be less than 1.5.

    The stability ratio for earthquake loads shall not be less than 1.0 and the force Ft, if

    applicable, may be omitted when determining the earthquake overturning moment

    to be resisted at the foundation-soil interface.

    Foundation Soil Bearing Pressures

    Foundation soil bearing pressures for loading conditions including wind or earth-quake loads should be based on sound engineering principles taking into account the

    nature of the subsoil and distribution of the load. In the absence of other criteria, the

    allowable soil bearing pressures may be increased by one-third when considering

    wind or earthquake forces acting alone or when combined with vertical loads.

    Allowable Stresses in Pressure Vessel Shells and Skirts

    See thePressure Vessel Manualfor allowable stresses in pressure vessels subject to

    wind or earthquake loads. Allowable stresses for loading conditions including wind

    or earthquake loads are typically higher than stresses allowed for normal conditions.

    120 Methods and Calculations

    121 Natural Period of Vibration

    In the design of flexible structures for earthquake loads and wind-induced vibra-

    tion, it is necessary to determine the first mode natural period of vibration of the

    structure. The following figures (Figures 100-14 through 100-20), and their accom-

    panying equations give the natural period of vibration for several types of industrial

    structures. Texts about dynamics of structures tell how to find the periods of more

    complex structures. Computer programs with dynamic structural analysis capabili-

    ties can also determine periods of structural vibration.

    The units used throughout the following formulas must be consistent except whereotherwise noted.

    Equation 100-23 in Figure 100-20 is an approximate formula which is sufficiently

    accurate for most non-uniform distillation columns and vertical vessels. If a vessel

    has a lower section several times the diameter of the upper portions, and the lower

    portion is short compared with the overall height (such as a vertical seal drum on

    which is mounted a self-supporting flare or vent stack), the period can be more

  • 7/27/2019 CIV100 Wind and Earthquake

    26/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-26 Chevron Corporation

    accurately determined by finding the period of the upper portion, assuming that

    displacement and rotation are fixed at its junction with the lower section. For

    vessels where the shell diameter or thickness is large in comparison with the

    supporting skirt, such as for high pressure reactors, the period calculated from

    Equation 100-23 may be overly conservative for earthquake design, and more accu-

    rate methods may be justified.

    The equations presented in this section ignore the effects of soil-structure inter-

    action. Soil-structure interaction can have a profound effect on the natural

    period of large vertical vessels on individual pile-supported foundations. All

    critical calculations for such vessels should consider this dynamic phenom-

    enon. The CRTC Civil/Structural Technical Service Team may be consulted in

    these cases.

    Figure 100-14 gives the general formula for determining the natural period of

    vibration, T, for a one mass structure.

    Figure 100-15 gives the equation for determining the natural period of vibra-

    tion for a one mass, Bending Type Structure.

    Figure 100-16 gives the equations for a one mass, rigid frame-type structure.

    Figure 100-17 gives the equation and parameters for determining the natural

    period of vibration for a two mass structure.

    Figure 100-18 gives the equation for a bending type structure of uniform

    weight distribution and constant cross section.

    Figure 100-19 gives the equation for the natural period of vibration for a

    uniform vertical cylindrical steel vessel.

    Figure 100-20 gives the equation for the natural period of vibration for a non-

    uniform vertical cylindrical vessel.

    Figure 100-21 lists the coefficients for determining the natural period of vibra-

    tion of free-standing cylindrical shells with varying cross sections and mass

    distribution.

    Fig. 100-14Natural Period of Vibration - One Mass Structure

    (Eq. 100-17)

    where:

    y = static deflection of mass resulting from a lateral load applied at the

    mass equal to its own weight.

    g = acceleration due to gravity.

    See Examples 4 and 5 for application.

    T 2 yg---

    0.5=

  • 7/27/2019 CIV100 Wind and Earthquake

    27/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-27 September 2000

    Fig. 100-15Natural Period of Vibration - One Mass, Bending Type Structure

    Fig. 100-16Natural Period of Vibration - One Mass, Rigid Frame Type Structure

    (Eq. 100-18)

    (Eq. 100-19)

  • 7/27/2019 CIV100 Wind and Earthquake

    28/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-28 Chevron Corporation

    Fig. 100-17Natural Period of Vibration - Two Mass Structure

    Fig. 100-18Natural Period of Vibration - Bending Type Structure, Uniform Weight Distribution and

    Constant Cross Section

    (Eq. 100-20)

    (Eq. 100-21)

  • 7/27/2019 CIV100 Wind and Earthquake

    29/56

    ChevronCorporation

    100-29

    September2000

    Fig. 100-19Natural Period of Vibration - Uniform Vertical Cylindrical Steel Vessel

    (Eq. 100-22)

  • 7/27/2019 CIV100 Wind and Earthquake

    30/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-30 Chevron Corporation

    Fig. 100-20Natural Period of Vibration - Non-uniform Vertical Cylindrical Vessel Courtesy of the James F.

    Lincoln Arc Welding Foundation

    (Eq. 100-23)

  • 7/27/2019 CIV100 Wind and Earthquake

    31/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-31 September 2000

    Fig. 100-21Coefficients for Determining Period of Vibration of Free-Standing Cylindrical Shells Having

    Varying Cross Sections and Mass Distribution Courtesy of the James F. Lincoln Arc Welding

    Foundation

  • 7/27/2019 CIV100 Wind and Earthquake

    32/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-32 Chevron Corporation

    122 Wind-Induced Vibration of Steel Stacks and Columns

    Introduction

    Welded steel stacks and other tall, cylindrical structures such as fractionating

    columns are susceptible to large-amplitude oscillations during steady winds of

    moderate velocity. These oscillations occur transverse to the mean wind direction

    and are driven by the vortices which form the downstream wake. The amplitude of

    the oscillations is inversely related to the mass and damping of the structure. Unac-

    ceptable oscillations are most likely to be encountered with lightly damped struc-

    tures, such as welded steel stacks on rigid foundations, and less likely with lined

    stacks, riveted structures, concrete stacks, or columns containing process fluids.

    The following is a method for design to avoid wind-induced oscillations for tall

    cylindrical structures, including guyed stacks. The method is based on a conserva-

    tive interpretation of available data, and will produce reliable results when used with

    realistic estimates of structural damping.

    Ovalling vibration of thin walled stacks must also be checked.

    Critical Wind Velocity

    The design objective is to have the Critical Wind Velocity (Uc) be greater than the

    Design Wind Velocity (Ud), thereby eliminating wind-induced vibration.

    The Critical Wind Velocity is the lowest velocity at which wind-induced oscilla-

    tions occur. It is computed as follows:

    1. Determine the natural fundamental period (T) of the structure (See Section 121,

    Natural Period of Vibration).

    2. Using the outside diameter of the stack (D), find the Critical Wind Velocity

    (Uc):

    (Eq. 100-24)

    3. Determine the Mean Steady Wind Velocity (Um) at the site, sustained for

    approximately 10 minutes. This wind velocity should be referenced to a

    particular height above grade (Z), which is 30 feet in most meteorological data.

    Note: This is not the Wind Speed Zone used in Section 113 or the Base Shear

    Z used in Section 114.

    4. Determine the Mean Steady Wind Velocity (Ut) at the top of the stack (H):

    (Eq. 100-25)

    5. Calculate the Design Wind, (Ud):

    Ud = 3Ut (Eq. 100-26)

    If Uc > Ud, then the stack is not susceptible to wind-induced oscillation. If Uc < Ud,

    the following design check is required.

    Uc4.7D

    T------------=

    Ut Um HZ----

    0.28

    =

  • 7/27/2019 CIV100 Wind and Earthquake

    33/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-33 September 2000

    Design Check

    The design objective is to have the Design Damping Coefficient (Cd) be less than

    the Structural Damping Coefficient (Cs) so wind-induced vibration amplitudes will

    not exceed acceptable limits.

    The Design Damping Coefficient (Cd) and the Structural Damping Coefficient (Cs)are determined as follows.

    1. Select an allowable vibration amplitude, Ya, which represents the amplitude of

    vibrations that could be sustained indefinitely without fatigue damage to the

    stack. Use this method to find a good approximation for Ya.

    a. Define allowable stress range (Fr) for infinite life. For shells with butt

    welded circumferential joint, Fris 16 ksi. For shells with fillet welded

    circumferential joint, Fris 5 ksi. For other types of connections, refer to the

    tables in the AISC Manual of Steel Construction, Part 5, Appendix K4.

    b. Determine stress per unit-deflection (Fm) for the fundamental mode shape

    of the stack. This may be approximated by:

    Fm = 1.2 Fw / Yw (Eq. 100-27)

    where:

    Fw = the maximum change in stress from a static condition due to

    design wind load only.

    Yw = The maximum deflection from a static condition due to the design

    wind load only.

    c. Let:

    Ya = (Fr/2Fm) (Eq. 100-28)

    Note that allowable stress range is divided by two to get single amplitudeallowable stress.

    2. Compute Mr:

    (Eq. 100-29)

    w = Weight/unit length of the top one-third of the stack. If variable,

    average the weight over the top one-third of the stack.

    = Weight density of air times /4= 0.076 lb/ft3 x /4 = 0.06 lb/ft3

    D = Diameter of the top one-third of the stack. If variable, take thesquare root of the length-weighted average of the squared values

    of the diameters over the top one-third. For example, for two

    sections:

    (Eq. 100-30)

    Mrw

    D2----------=

    DD1

    2l1 D22l2+

    l1 l2+( )------------------------------

    0.5

    =

  • 7/27/2019 CIV100 Wind and Earthquake

    34/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-34 Chevron Corporation

    3. Compute Design Minimum Required Damping Coefficient (Cd):

    (Eq. 100-31)

    = A shape factor; use 1.3 for the fundamental mode of cantilever

    structures.

    4. Select a Structural Damping Coefficient (Cs) by adding the appropriate frac-

    tions listed below (other values for structural damping may be used if they can

    be substantiated):

    For example, a stack with refractory lining on a 2000 psf foundation would

    have:

    Cs = 0.003 + 0.002 + 0.002 = 0.007.

    5. If Cd < Cs, then wind-induced vibration amplitudes will not exceed acceptable

    limits. If Cd > Cs, then design alternatives must be considered.

    Design Alternatives

    1. Lower H/D or increase t, stack wall thickness (to raise Uc above Ud.)

    2. Increase t or refractory line stack (to increase Mrand Cs.)

    3. Attach helical spoilers to the top third of the stack. Conservative guidelines for

    spoiler design are:

    a. Spoilers shall consist of three helical strakes over the top third of the stack

    with a pitch of 5D and a height of 0.12D.

    b. A conservative estimate for Design Minimum Damping Fraction for a

    stack with spoilers is:

    (Eq. 100-32)

    Cd0.45

    Mr----------

    DYa-------- 1.0

    0.5=

    Factor Incremental Damping Fraction

    Basic Stack 0.003

    Refractory 0.002

    Basic Column

    Empty 0.008

    With Liquid Content 0.013Foundation soil strength:

    less than 1500 psf 0.006

    1500 psf to 3000 psf 0.002

    greater than 3000 psf 0.0

    Pile-supported stacks 0.0

    Stacks supported atop structures 0.0

    Cd0.30

    Mr----------=

  • 7/27/2019 CIV100 Wind and Earthquake

    35/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-35 September 2000

    Spoilers will be effective if Cs > Cd. A lower value of Cd may be used if it can

    be justified.

    Note that spoilers increase the effective area and shape factor for static wind

    load, which must be accounted for in the design.

    4. Attach a damping device to the stack. Several such devices have been used.Two proven alternatives are hydraulically tensioned guys, and chain impact

    dampers.

    If Design Minimum Damping is close to the required minimum, so that short dura-

    tions of wind-induced vibration will not result in damage, then a reasonable alterna-

    tive is to design an auxiliary damping system and provide attachments to the stack

    (i.e., padeyes), but defer fabrication and installation of the dampers until after the

    stack is erected and actual unacceptable vibration amplitudes have been observed.

    Ovalling Vibration of Thin-walled Stacks

    Thin-walled stacks are also susceptible to ovalling vibrations, i.e., oscillations

    where the stack cross-section vibrates as a ring. The same aeroelastic phenomenadescribed in the introduction to this section create this mode of vibration. Ovalling,

    however, can be directly prevented by the addition of circumferential stiffeners to

    the stack.

    Criteria for avoiding ovalling is:

    If (Eq. 100-33)

    where:

    t = stack wall thickness, inch

    R = stack radius, inch

    Ud = Design Wind (see Equation 100-26), fps

    If stiffeners are required:

    1. Choose a spacing of stiffeners, L, such that:

    (Eq. 100-34)

    2. Calculate the required moment of inertia, Ir(in4), of the added stiffener section

    about its center of gravity axis by

    (Eq. 100-35)

    where:

    E = modulus of elasticity at operating temperature in psi

    D = Diameter in feet

    R = Radius in inches

    t

    R---

    Ud

    10200--------------- stiffeners are required 0.003 R (Eq. 100-36)

    Example Calculations

    See Section 123, Examples 6 and 7, for a demonstration of the methodology for

    analyzing wind-induced vibration of steel stacks

    123 Examples of Wind and Earthquake Load Calculations

    Following are seven examples of wind and earthquake load calculations for several

    different structures and supports. These examples are:

    Note: Examples 1-5 are based on the 1997 edition of the UBC. The earthquake

    design forces specified by the 1997 UBC are based on strength design; whereas in

    past editions of UBC the design forces were based on allowable stress design.

    Therefore, in order to be consistent with the 1997 UBC, examples 1-5 are strength

    design based. If you want to use allowable stress design, the calculated earthquake

    forces should be divided by a factor of 1.4.

    Example 1Two-Story Concrete Vessel Support Structure(Assume El Segundo, CA Location)

    Earthquake Forces (Transverse directionLoads on one bent)

    W = 20 kips (includes structure weight)

    Deflections from 1 kip at A and B (calculations not shown):

    Caa = 0.0384 in., Cab = 0.0180 in., Cbb = 0.0157 in.

    Example 1 Two-Story Concrete Vessel Support Structure

    (Assume El Segundo, CA Location)

    Example 2 Uniform Cylindrical Column

    (Assume El Segundo, CA Location)

    Example 3 Column of Variable Cross Section

    (Assume Salt Lake City, UT Location)

    Example 4 Braced-Column Spheres

    (Assume Richmond, California, Location)

    Example 5 Vertical Vessels with Unbraced Legs

    (Assume Richmond, CA Location)

    Example 6 Stack Vibration and Ovalling

    Example 7 Stack Vibration

  • 7/27/2019 CIV100 Wind and Earthquake

    37/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-37 September 2000

    Use Equation 100-20

    (Eq. 100-2)

    Z = 0.40 (Seismic Zone 4)

    I = 1.0

    Assume Type Sc soil.

    For El Segundo, Na = 1.1 and Nv = 1.33 (Figure 100-5)

    Fig. 100-22Two-Story Concrete Vessel Support StructureSMRSF, EQ Zone 4, Wind Zone 70 MPH

    T 2 3.14( )12 0.0384( ) 8 0.0157( ) 12 0.0384( ) 8 0.0157( )[ ]

    24 12( ) 8( ) 0.0180( )

    2+[ ]

    0.5+ +

    2 386( )---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

    0.5

    =

    0.234 sec 0.06 sec>=

    Use VCvI

    RT--------W=

    Ca 0.40Na 0.40 1.1( ) 0.44 (Figure 100-7)= = =

    Cv 0.56Nv 0.56 1.33( ) 0.745= = = Figure 100-8( )

  • 7/27/2019 CIV100 Wind and Earthquake

    38/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-38 Chevron Corporation

    Check vs. Vmax:

    (Eq. 100-3)

    Note: If it is desired to use allowable stress design, the base shear value (V =

    3.93K) should be divided by 1.4.

    (Eq. 100-10)

    Base Moment, Mo = (2.95) (20) + (0.98) (10) = 68.2 k-ft.

    Wind Forces (Transverse directionLoads on one bent). Assume wind speedzone = 70, Exposure B.

    Shape Factors: Vessels = 1.4; Open Framework Structures = 1.3

    Base Overturning Moment = (0.64) (20) + (0.41) (10) = 16.9 k-ft

    Therefore, the Earthquake Moment controls the design.

    R 5.6 (Figure 100-11) Special Moment-Resisting Space Frame - Concrete=

    VCvI

    RT--------W

    0.745( ) 1.0( )5.6( ) 0.234( )

    ------------------------------- 20( ) 11.17 kip Total Base Shear= = =

    Vmax

    2.5CaI

    R---------------- W=

    2.5( ) 0.44( ) 1.0( )5.6

    ---------------------------------------- 20( )=

    3.93k

    =

    Vmax controls!

    Use V 3.93k

    =

    T 0.7 sec., thereforeFt

    0.0=

    WA

    hA

    12 20( ) 240 WB

    hB

    ; 8 10( ) 80 Wh; 320= = = = =

    FA

    VW

    AhA

    Wh---------------- 3.93( )

    240

    320--------- 2.95 kip FB

    ;W

    BhB

    Wh---------------- 3.93

    80

    320--------- 0.98 kip= = = = = =

    FA

    1.4 9( ) 4 202------

    1.3 8( ) 1.5 112

    ------ 1.0 10

    2------

    ++

    1 000,-------------------------------------------------------------------------------------------------------------- 0.64 kip= =

    FB

    1.4 8( ) 2 152------

    1.3 8( ) 1.5 112

    ------ 1.0

    10

    2------ 10+

    ++

    1 000,-------------------------------------------------------------------------------------------------------------------------- 0.41 kip Total Shear 1.05 kip= = =

  • 7/27/2019 CIV100 Wind and Earthquake

    39/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-39 September 2000

    Example 2Uniform Cylindrical Column (Assume El Segundo,CA Location)

    In most columns of constant diameter, the entire mass can be assumed uniformly

    distributed over the height. Where there are large concentrations of mass or varia-

    tions in cross-section, the analysis should be made as shown in Example 3.

    Period of Vibration:

    (Eq. 100-22)

    Z = 0.4 (Zone 4); Importance Factor, I = 1.0

    Na = 1.1; Nv = 1.33 (From Figure 100-5).

    Assume Type Sc soil.

    Fig. 100-23Uniform Cylindrical Column: Earthquake Forces

    T7.78

    106----------

    100

    6---------

    2 12 600 60.25

    ------------------------------ 0.5 0.898 sec= =

    tvessel

    tsk ir t---------------

    0.625

    0.25------------- 2.5 and 2.5 1.5 therefore, useR 2.2= (from Figure 100-11),>= =

  • 7/27/2019 CIV100 Wind and Earthquake

    40/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-40 Chevron Corporation

    From Figures 100-7 and 100-8,

    Ca = 0.40Na = 0.40(1.1) = 0.44

    Cv = 0.56Nv = 0.56(1.33) = 0.745

    (Eq. 100-2)

    (Eq. 100-0)

    Check Vmin:

    (Eq. 100-7)

    Also, for Zone 4:

    (Eq. 100-8)

    Note If it is desired to use allowable stress design, the base shear value

    (V = 23.21k) should be divided by 1.4.)

    T > 0.7 sec, therefore Ft = 0.07 TV = 0.07(0.898)(23.21) = 1.46 kip (Eq. 100-9)

    V-Ft = 21.75 kip

    W wH 600 lb ft( ) 100 ft( ) 60 000 lb, 60 kip= = = =

    Base Shear, VCVI

    RT---------W

    0.745( ) 1.0( )2.2( ) 0.898( )

    ------------------------------- 60 kip( ) 22.63 kips= = =

    CheckVmax

    2.5CaI

    R---------------- W

    2.5( ) 0.44( ) 1.0( )2.2

    ---------------------------------------- 60( ) 30.0 kip= = =

    Vmin 0.56CaIW=

    0.56 0.44( ) 1.0( ) 60( )=

    14.78kips=

    Vmin

    1.6ZNVI

    R---------------------W=

    1.6 0.4( ) 1.33( ) 1.0( )2.2------------------------------------------------ 60( )=

    23.21kips=

    Vmin controls! Use V 23.21 kips=

  • 7/27/2019 CIV100 Wind and Earthquake

    41/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-41 September 2000

    When the weight is distributed uniformly along the height, the distribution of the

    lateral force V-Ft given by Equation 100-10 resolves to the triangular distribution

    shown in Figure 100-23.

    The moment at the top of the skirt, or at any other elevation, can be found bydrawing a free body diagram. For example, M15 = 1,243 k-ft.

    Wind Forces(Wind Zone = 70, Exposure C)

    Diam. = 6 ft.-0 in. + 2 (2 in) = 6.33 ft.

    Shape Factor = 1.7 - (0.075 D) = 1.7 - (0.075)(6.33) = 1.23

    Fig. 100-24Uniform Cylindrical Column: Wind Forces

    Base Moment,Mo FtH Fxhx+ 1.46 100( )2

    3--- 21.75( ) 100( )+ 1 596 k-ft,= = =

    Wind Base Shear, VW Wind Moment, MOW:

    F1 = 1.23(13)(6.33)(15) = 1,520 M01 = 1,520(7.5) = 11,400

    F2 = 1.23(14)(6.33)(5) = 550 M02 = 550(17.5) = 9,630

    F3 = 1.23(15)(6.33)(5) = 580 M03 = 580(22.5) = 13,050

    F4 = 1.23(16)(6.33)(15) = 1,870 M04 = 1,870(32.5) = 60,780

    F5 = 1.23(18)(6.33)(20) = 2,800 M05 = 2,800(50) = 140,000

    F6 = 1.23(19)(6.33)(20) = 2,960 M06 = 2,960(70) = 207,200

    F7 = 1.23(20)(6.33)(20) = 3,110 M07 = 3,110(90) = 279,900

    Vw = 13,390 lb Mow = 721,960 lb-ft = 722 k-ft

  • 7/27/2019 CIV100 Wind and Earthquake

    42/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-42 Chevron Corporation

    Moment at top of skirt:

    M15 = 1.23(14)(6.33)(5)(2.5) + 580(7.5)

    + 1,870(17.5) + 2,800(35)

    + 2,960(55) + 3110(75) = 532.5 k-ft.

    Therefore, Earthquake Moment controls the design.

    Wind and earthquake moments can be determined similarly at other sections.

    Combine the larger of wind or earthquake moment with corresponding gravity

    forces at each section and use allowable stresses to determine the required skirt and

    shell thickness.

    Example 3Column of Variable Cross Section (Assume SaltLake City, UT Location)

    Period of VibrationUse Equation 100-23 (see Figure 100-20.)

    Z = 0.30 (Zone 3); Occupancy Factor = 1.0

    Fig. 100-25Column of Variable Cross Section: Natural Period of Vibration

    1800

    (lb/ft)

    (lb)

    D

    3720 684.86

    1200

    8000

    900

    40

    3760

    1039.76

    672.47

    2397

    2397

  • 7/27/2019 CIV100 Wind and Earthquake

    43/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-43 September 2000

    Assume SD soil.

    Therefore, from Figures 100-7 and 100-8, Ca = 0.36, and Cv = 0.54

    W = 58.5(1.8) + 23.5(1.2) + 12(0.9) + 8.0 = 152.3 kips

    (Eq. 100-2)

    Check Vmin = 0.56CaIW = 0.56(0.36)(1.0)(152.3) = 30.7 kips (Eq. 100-7)

    Therefore, use V = 33.83 kips.

    Note If it is desired to use allowable stress design, the base shear value

    (V=33.83 kips) should be divided by 1.4.

    T > 0.7 sec; therefore Ft = 0.07TV = 0.07 (1.105) (33.83) = 2.62 kip (Eq. 100-9)

    V - Ft = 31.21 kips

    (Eq. 100-10)

    Shear and Moments: Divide column into segments not exceeding 20% of height.

    Base overturning moment, Mo = 2239.3 k-ft. See Figure 100-26.

    Wind Forces (Wind Speed Zone = 70, Exposure B)

    Base overturning moment, Mo = 499 k-ft. See Figure 100-27. The shape factor and

    projected area are based on the outside diameter including the insulation. M(Figure 100-27) is calculated for each section by multiplying average shear in

    section by height of section. (Area under shear diagram.) Therefore, M is theincremental moment at each section, while Mx is the total moment at each section.

    Therefore, Earthquake Moment controls the design.

    tvessel

    tsk ir t---------------

    0.625

    0.25------------- 2.5 and 2.5> 1.5, therefore, use R 2.2 (from Figure 100-11)= = =

    Base Shear, VCvI

    RT--------W

    0.54( ) 1.0( )2.2( ) 1.105( )

    ------------------------------- 152.3( ) 33.83 kips= = =

    Fx V Ft( )

    Wxhx

    Wh-------------31.21

    7672.7----------------Wxhx= =

  • 7/27/2019 CIV100 Wind and Earthquake

    44/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-44 Chevron Corporation

    Fig. 100-26Column of Variable Cross Section: Earthquake Forces

    Fig. 100-27Column of Variable Cross Section: Wind Forces

    62 62

    11.7

    11.7

    11.7

    11.7

    11.7

    21.06

    21.06

    21.06

    21.06

    21.06

    88.15

    76.45

    64.75

    53.05

    41.35

    1856.44

    1610.04

    1363.64

    1117.23

    870.83

    7.55

    6.55

    5.55

    4.54

    3.54

    10.17

    16.72

    22.27

    26.81

    30.35

    6.40

    13.45

    19.49

    24.54

    28.58

    74.83

    157.32

    228.08

    287.11

    334.42

    74.83

    232.15

    460.22

    747.34

    1081.76

    5.875

    5.875

    5.875

    7.05

    7.05

    7.05

    32.56

    26.69

    20.81

    229.57

    188.15

    146.73

    0.93

    0.77

    0.60

    31.29

    32.05

    32.65

    33.14

    33.57

    33.83

    30.82

    31.67

    32.35

    32.89

    33.35

    33.70

    181.07

    186.06

    190.07

    0.0

    195.94

    404.38

    1262.83

    1448.89

    1638.96

    1638.96

    1834.90

    2239.28

    5.875 7.05 14.94 105.31

    0.49

    0.43

    0.26

    60

    73

    106

    179

    192

    34

    226

    22248

    37285

    39

    32441

    365

    26391

    108

    499

  • 7/27/2019 CIV100 Wind and Earthquake

    45/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-45 September 2000

    Example 4Braced-Column Spheres (Assume Richmond, Cali-forniaLocation)

    The recommended bracing system for spheres consists of x-bracing connecting

    adjacent pairs of columns as illustrated in Figure 100-28. In accordance with Details

    of Earthquake Resistant Design in Section 114, the bracing for large spheres subjectto earthquake loads should be effective both in tension and compression to better

    resist the lateral forces. The lateral forces are transmitted into the shell by a

    balcony girder.

    The shear in each panel and the maximum panel shear may be found by the

    formulas:

    Fig. 100-28Recommended Bracing System for Spheres

  • 7/27/2019 CIV100 Wind and Earthquake

    46/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-46 Chevron Corporation

    (Eq. 100-37)

    (Eq. 100-38)

    where:

    Vp = panel shear

    Vpmax = maximum panel shear

    V = total lateral force

    n = number of panels (equal to number of columns)

    = angle between the plane of the panel and the direction of thelateral force.

    Earthquake ForcesPeriod of Vibration:

    The period of vibration is found using the general formula for one-mass structure in

    Section 121, Equation 100-17. The static deflection, y, is found by determining the

    change in length of the bracing resulting from a total lateral load equal to the weight

    of the sphere. Deformation of the columns and balcony girder are usually neglected

    for one-story structures.

    (Eq. 100-17)

    Z = 0.4, Zone 4; Occupancy Factor I = 1.0, R = 2.9 (Figure 100-11)

    From Figure 100-5, Na = 1.2 and Nv = 1.6.

    Assume SE Soil (site over Bay mud)

    Therefore, from Figures 100-7 and 100-8,

    Vp2V

    n------- cos=

    Vpmax2V

    n-------=

    P Maximum force in brace1

    2---

    2 15006

    --------------------- 36.0

    20.0----------

    450 kip= = =

    Change in length of brace PLEA------- 450( ) 36.0( ) 12( )

    29 000,( ) 8.0( )---------------------------------------- 0.838 in.= = = =

    y

    sin----------- 0.838( ) 36.0

    20----------

    1.51 in.= = =

    Period of Vibration, T 2 yg---

    0.5=

    T 2 1.5132.2 12( )---------------------

    0.5 0.393 sec= =

  • 7/27/2019 CIV100 Wind and Earthquake

    47/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-47 September 2000

    Ca= 0.36Na = 0.36(1.2) = 0.43

    Cv= 0.96Nv = 0.96(1.6) = 1.54

    (Eq. 100-2)

    Check Vmax:

    (Eq. 100-3)

    Note If it is desired to use allowable stress design, the base shear value (V = 556

    kips) should be divided by 1.4.

    Fig. 100-29Wind Forces for Braced-Column Spheres

    Wind Forces (Wind Speed Zone = 70, Exposure C)

    Description Projected Area ft2 Shap

    e

    factor

    Wind

    Pressure

    psf

    Force

    k

    Sphere Above 40 Elev. 246 0.65 18 2.9

    Sphere Between 30 and 40 Elev. 382 0.65 16 4.0

    Sphere Between 25 and 30 Elev. 198 0.65 16 2.1

    Sphere Between 20 and 25 Elev. 184 0.65 15 1.8

    Sphere Between 15 and 20 Elev. 154 0.65 14 1.4

    Sphere Below 15 Elev. 92 0.65 13 0.8

    Columns & Bracing Above 25 Elev. (1/6)[4(1)(30)+6(.5)(36

    )]=38

    2.0 16 1.2

    Columns & Bracing Between 20 and 25Elev. (1/6)[228]=38 2.0 15 1.1

    Columns & Bracing Between 15 and 20

    Elev.

    (1/6)[228]=38 2.0 14 1.1

    Columns & Bracing Below 15 Elev. (1/2)[228]=114 2.0 13 3.0

    Total Wind Force, VW = 19.4

    Note In computing the slenderness ratio of bracing in an x-braced frame, the effective length may be taken as one-half the

    total

    length about both axes of the member. Braces should be attached at their point of intersection.

    Base Shear, VC

    vI

    RT---------W

    1.54( ) 1.0( )2.9( ) 0.393( )

    ------------------------------- 1500( ) 2026.8 kips= = =

    Vmax

    2.5CaI

    R---------------- W=

    2.5 0.43( ) 1.0( )2.9

    ----------------------------------- 1500( )= 556.0 kips=

    Vmax controls.

    Use V 556.0 kips=

  • 7/27/2019 CIV100 Wind and Earthquake

    48/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-48 Chevron Corporation

    Therefore, earthquake forces control the design.

    Example 5Vertical Vessels with Unbraced Legs (Assume Rich-mond, CA Location)

    Vertical vessels are often supported with legs rather than skirts as represented in

    Figure 100-30. Where the legs are braced, earthquake and wind loads may be deter-mined as in Example 4. Small vessels are frequently supported on legs without

    bracing. Usually the legs are considered fixed at the vessel shell and pinned at their

    bases. For these cases, the shell must be adequate to resist the bending moments

    applied by the legs, or must be adequately stiffened.

    Earthquake Forces

    Period of Vibration:

    Since the stiffness of the shell is usually large compared with that of the legs, the

    period of vibration can be found using the general formula for a one-mass structure

    in Section 121 (Equation 100-17) assuming the deflection, y, equals the deflectionof the legs resulting from a total lateral force equal to the weight of the vessel. For a

    vessel supported on three or more legs symmetrically spaced about the center, y

    may be determined from the formula:

    (Eq. 100-39)

    where:

    N = number of legs

    Ix + Iy = sum of moments of inertia of one leg about the perpendicular axis

    L = length of legs from base to shell attachment

    For example shown:

    Period of Vibration:

    (Eq. 100-17)

    Zone 4; Z = 0.40, Occupancy Factor, I = 1.0; Assume SE soil

    From Figure 100-5, Na = 1.2; Nv = 1.6

    y2WL3

    3NE Ix Iy+( )-------------------------------=

    y2( ) 15.0( ) 5 12( )3

    3( ) 4( ) 29000( ) 2.45 2.45+( )-------------------------------------------------------------------- 3.80 in= =

    T 2 yg---

    0.5 2 3.8032.2 12( )---------------------

    0.5 0.623 sec= = =

  • 7/27/2019 CIV100 Wind and Earthquake

    49/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-49 September 2000

    Fig. 100-30Vertical Vessel with Unbraced Legs

  • 7/27/2019 CIV100 Wind and Earthquake

    50/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-50 Chevron Corporation

    (Eq. 100-2)

    Check Vmax:

    (Eq. 100-3)

    Vmax controls.

    Note If it is desired to use allowable stress design, the base shear value (V = 7.33

    kips) should be divided by 1.4.

    T < 0.7, therefore Ft = 0.0

    Considering the weight, W, uniformly distributed along the shell length, the force V-

    Ft given by Equation 100-10 resolves to a trapezoid, the extended non-parallel sides

    of which intersect at the base as shown in the sketch in Figure 100-30.

    Earthquake Base Overturning Moment:

    For the distribution noted above, the base overturning moment, Mo, can be deter-

    mined by the formula:

    (Eq. 100-40)

    for design example,

    Wind Forces (Wind Speed Zone = 70, Exposure B)

    Wind Base Moment Mo = 0.53(10) + 0.067(2.5) = 5.47 k-ft.

    Therefore, Earthquake Moment controls the design.

    R 2.2 (Figure 100-11)=

    From Figure 100-7, Ca 0.36Na 0.36 1.2( ) 0.43= = =

    From Figure 100-8, Cv

    0.96Nv

    0.96 1.6( ) 1.54= = =

    Base Shear, VC

    vIW

    RT--------------

    1.54( ) 1.0( ) 1.5( )2.2( ) 0.623( )

    ---------------------------------------- 16.85 kips= = =

    Vmax

    2.5CaI

    R---------------- W=

    2.5 0.43( ) 1.0( )

    2.2

    ----------------------------------- 15( )=

    7.33 kips=

    use V 7.33 k=

    M0 FtH2

    3--- V Ft( )

    H3 L3

    H2 L2-------------------+=

    M0

    2

    3--- 7.33( ) 15

    3 53( )

    152 52( )------------------------- 79.4 k-ft.= =

  • 7/27/2019 CIV100 Wind and Earthquake

    51/56

    Civil and Structural Manual 100 Wind and Earthquake Design Standards

    Chevron Corporation 100-51 September 2000

    The axial loads may be determined using the vessel weight and governing base

    overturning moment. The bending moment in the legs at the shell about each prin-

    cipal axis (axes of maximum and minimum moment of inertia) may be determined

    using the governing base shear.

    Example 6Stack Vibration and Ovalling

    Check the susceptibility to large-amplitude oscillation and also determine the

    required circumferential stiffener size and spacing for the following stack:

    H = 180 ft

    D = 15.0 ft

    t = 0.50 in.

    Um = 15 fps at elev. + 30 ft

    Use Figure 100-19, Uniform Vertical Cylindrical Steel Vessel, for determining

    period of vibration.

    (Eq. 100-22)

    (Eq. 100-24)

    (Eq. 100-25)

    (Eq. 100-26)

    Fig. 100-31Base Shear for Vertical Vessels with Unbraced Legs

    Item Projected Area (ft2) Shape Factor Wind Pressure

    Force

    (lb)

    Shell 5' 10' = 50 1.7-(0.0755) = 1.33 8 532

    Legs 5' 0.84' = 4.2 2.0 8 67Base Shear = 599 lb

    w4--- 180( )2 179( )2( )

    1

    144--------- 490 959 lb/ft.= =

    T7.78

    106----------

    180

    15---------

    2 12 959 150.50

    --------------------------------- 0.5 0.66 sec.= =

    Uc4.7D

    T------------

    4.7( ) 15( )0.66

    ----------------------- 106.8 fps= = =

    Ut UmH

    Z----

    0.28 15( ) 18030

    --------- 0.28 24.8 fps= = =

    Ud 3Ut 3( ) 24.8( ) 74.4 fps= = =

  • 7/27/2019 CIV100 Wind and Earthquake

    52/56

    100 Wind and Earthquake Design Standards Civil and Structural Manual

    September 2000 100-52 Chevron C