These operating instructions only apply in conjunction with the operating instructions for the relevant CM Series control units. Correct use The CM Series coded magnetic safety switches are a series of technical safety devices for monitoring moveable separating safety guards. They ensure that: dangerous work on machines can only be carried out if the safety guards are closed. a stop command is triggered if a safety guard is opened while the machine is running. Before safety switches are used, a risk assessment must be performed on the machine in accordance with: EN 954-1, safety-related components of controls, Annex C EN 1050, machine safety, risk assessment. Correct use includes compliance with the relevant re- quirements for installation and operation, particularly: EN 954-1, safety-related components of controls EN 1088, interlocking devices in conjunction with moving safety guards EN 60204-1, electrical equipment of machines EN 60947-5-3 Requirements for proximity switches. Safety precautions It is only possible to ensure technical safety functionality when used as a complete system. If CM Series read heads and actuators are operated as technical safety components without the relevant CM Series control unit.., this is then the responsibility of the manufacturer of the plant / machine. Safety switches fullfill a personal protection function. Incorrect installation or manipulation can lead to severe injuries to personnel. Safety switches must not be bypassed (bridging of contacts), turned away, removed or otherwise rendered ineffective. The switching operation may only be triggered by actuators specifically supplied for this purpose which are permanently connected to the safety guard. A complete safety-oriented system generally consists of several signalling devices, sensors, evaluation units and concepts for safe shut-off operations. The manufacturer of a machine or installation is responsible for correct and safe overall function. Functioning The CM Series switch consists of a control unit, read head and actuator and is only functional in particular combinations (see combination options)! The read head connected to the control unit contains reed contacts which are activated by the coded magnetic actuators. The control unit converts this information and transfers the safety guard state to the control system via a safety output. Assembly Installation must be performed by authorized personnel only. Read heads and actuators must not be used as a mechanical stop. Read heads and actuators must not be used in an environment with strong magnetic fields. Read heads and actuators must be positively locked to the safety guard, e.g. by using the security screws supplied. The read head and actuator may be installed in any position. The alignment of the read head and the actuator must be kept in mind (see figure 1). Install read head and actuator so that: they are accessible for inspection work and the installation of spare parts when the safety guard is closed, the active read head and actuator area are exactly aligned (see figure 1) the actuator is located in the read head's response area when the safety guard is closed. a guide and an extra stop must be fitted to the moveable part of the safety guard. a stopping mechanism must be fitted to the protective doors for closed position. If the read head and actuator are fitted flush, the switching distance is reduced depending on the installation depth and the safety guard material. If the read head and actuator are fitted on ferromagnetic material, the read distance is reduced. If the approach speed between the read head and the actuator is low and the control unit CM-S4 is used, the approach direction z (see figure 1) should be avoided. Round actuators are torque-resistant. In order to ensure that the actuator cannot be rotated when secured to the protective doors, a 2 mm hole should be drilled for the safety lug during installation. Electrical connection Electrical connection must be performed by authorized personnel only. The connection cable for the read heads must not be extended. The read heads must be connected to the evaluation units in accordance with the wiring diagram (see operating instructions for control units). Service and inspection Remove iron swarf from the read head and actuator at regular intervals. Only use solvent-free detergents for cleaning the actuators and read heads! In order to ensure lasting, trouble-free operation, regular inspection of the following is required: correct switching function secure mounting of components loose connections. In the event of damage or wear and tear, the damaged system component must be replaced. Liability coverage is void under the following circumstances: if instructions are not followed non-compliance with safety regulations installation and electrical connection not performed by authorized personnel non-implementation of functional checks. Technical data Parameter Value Read heads Housing material reinforced PPS Ambient temperature -20 ... +60 °C Degree of protection IP 67 according to EN IEC 60529 Installation position Any, alignment with actuator should be kept in mind (markings) Connection type Molded cable with crimped ferrules Switching voltage 24 V Contact status indication (only CMS-A-AXR...) Switching voltage 24 V Switching current l e max. 0.01 A Method of operation Magnetic, reed contact Mech. life 100x10 6 operating cycles Vibration resistance 10 ... 55 Hz, amplitude 1 mm Shock resistance 30 g/11 ms EMC compliance acc. to EN 60947-5-3 Center offset m from actuator ± 2.5 mm at a distance of s = 3 mm Switch on distance S ao Switch off distance S ar See table listing Reset spacing S reset combination options Logic elements Actuator Housing material Reinforced PPS Ambient temperature -20 ... +60 °C Degree of protection IP 67 according to IEC 60529 Installation position Any, alignment with read head should be kept in mind (markings) Method of operation Magnetic Vibration resistance 10 ... 55 Hz, amplitude 1 mm Shock resistance 30 g/11 ms Center offset m from read head ± 2.5 mm at a distance of s = 3 mm Switch on distance S ao Switch off distance S ar See table listing Reset spacing S reset combination options X Y Z Direction of approach Alignment marking X Y Z Direction of approach Alignment marking CM-S1... CM-S2... CM-S3... Fig. 1: Alignment of read head and actuator X Y Z Alignment marking Direction of approach For use and operation as per the re- quirements, a power supply with the feature “for use in class 2 circuits” must be used. They are not tested as safety components in the context of the UL definition (e.g. for potentially explosive atmospheres). C US Not all faults are detected. An accumulation of undetected faults can lead to the loss of the safety function. With this application, therefore, it is necessary to ensure that only one safety gate (door) is open at a time or that the status of each safety gate is checked in suitable intervals. Switching current l e max. 0.5 A No responsibility whatever is accepted for the use of the technical safety functioning of the CM Series read heads or actuators without the relevant CM Series control units. Operating Instructions for CM Series Read Heads and Actuators CM Series Safety, Technology & Innovation

Upload: others

Post on 02-Oct-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CM Series Read Heads and Actuators Instruction Sheetproducts.omron.us/Asset/CM_InstructionSheet_en_200801_C...Combination options 2.5 2.5 S a 0 78 ±0.1?5.5 9. 5 2 5 1 2 6 6 67.5 87.5

These operating instructions only apply inconjunction with the operating instructions forthe relevant CM Series control units.

Correct useThe CM Series coded magnetic safety switches are a series of technical safety devices for monitoringmoveable separating safety guards. They ensure that:

dangerous work on machines can only be carriedout if the safety guards are closed.a stop command is triggered if a safety guard isopened while the machine is running.

Before safety switches are used, a risk assessmentmust be performed on the machine in accordance with:

EN 954-1, safety-related components of controls,Annex CEN 1050, machine safety, risk assessment.

Correct use includes compliance with the relevant re-quirements for installation and operation, particularly:

EN 954-1, safety-related components of controlsEN 1088, interlocking devices in conjunction withmoving safety guardsEN 60204-1, electrical equipment of machinesEN 60947-5-3 Requirements for proximity switches.

Safety precautions

It is only possible to ensure technical safetyfunctionality when used as a complete system.If CM Series read heads and actuators are operated astechnical safety components without the relevantCM Series control unit.., this is then the responsibilityof the manufacturer of the plant / machine.Safety switches fullfill a personal protection function.Incorrect installation or manipulation can lead to severeinjuries to personnel.

Safety switches must not be bypassed (bridgingof contacts), turned away, removed or otherwiserendered ineffective.The switching operation may only be triggeredby actuators specifically supplied for this purposewhich are permanently connected to the safetyguard.

A complete safety-oriented system generallyconsists of several signalling devices, sensors,evaluation units and concepts for safe shut-offoperations. The manufacturer of a machine orinstallation is responsible for correct and safeoverall function.

FunctioningThe CM Series switch consists of a controlunit, read head and actuator and is only functionalin particular combinations (see combinationoptions)!The read head connected to the control unit containsreed contacts which are activated by the codedmagnetic actuators. The control unit converts thisinformation and transfers the safety guard state to thecontrol system via a safety output.

AssemblyInstallation must be performed by authorizedpersonnel only.Read heads and actuators must not be used as amechanical stop.Read heads and actuators must not be used inan environment with strong magnetic fields.Read heads and actuators must be positivelylocked to the safety guard, e.g. by using thesecurity screws supplied.

The read head and actuator may be installed in anyposition. The alignment of the read head and theactuator must be kept in mind (see figure 1).

Install read head and actuator so that:they are accessible for inspection work and theinstallation of spare partswhen the safety guard is closed, the active read headand actuator area are exactly aligned (see figure 1)the actuator is located in the read head's responsearea when the safety guard is closed.

a guide and an extra stop must be fitted to themoveable part of the safety guard.a stopping mechanism must be fitted to the protectivedoors for closed position.If the read head and actuator are fitted flush, theswitching distance is reduced depending on theinstallation depth and the safety guard material.If the read head and actuator are fitted onferromagnetic material, the read distance is reduced.If the approach speed between the read head andthe actuator is low and the control unit CM-S4 is used, the approach direction z (see figure 1) shouldbe avoided.Round actuators are torque-resistant. In order toensure that the actuator cannot be rotated whensecured to the protective doors, a ∅ 2 mm holeshould be drilled for the safety lug during installation.

Electrical connectionElectrical connection must be performed byauthorized personnel only.

The connection cable for the read heads must not beextended.The read heads must be connected to the evaluationunits in accordance with the wiring diagram (seeoperating instructions for control units).

Service and inspectionRemove iron swarf from the read head and actuatorat regular intervals.Only use solvent-free detergents for cleaning theactuators and read heads!In order to ensure lasting, trouble-free operation,regular inspection of the following is required:

correct switching functionsecure mounting of componentsloose connections.

In the event of damage or wear and tear, thedamaged system component must be replaced.

Liability coverage is void under the followingcircumstances:•

•••

••

••

if instructions are not followed• non-compliance with safety regulations•••

installation and electrical connection not performedby authorized personnelnon-implementation of functional checks.

Technical dataParameter ValueRead headsHousing material reinforced PPSAmbient temperature -20 ... +60 °CDegree of protection IP 67 according to EN IEC 60529Installation position Any, alignment with actuator should

be kept in mind (markings)Connection type Molded cable with crimped ferrulesSwitching voltage 24 V

Contact status indication (only CMS-A-AXR...)Switching voltage 24 VSwitching current le max. 0.01 A Method of operation Magnetic, reed contactMech. life 100x106 operating cyclesVibration resistance 10 ... 55 Hz, amplitude 1 mmShock resistance 30 g/11 msEMC compliance acc. to EN 60947-5-3Center offset m from actuator ± 2.5 mm at a distance of s = 3 mmSwitch on distance Sao

Switch off distance Sar See table listingReset spacing Sreset combination optionsLogic elementsActuatorHousing material Reinforced PPSAmbient temperature -20 ... +60 °CDegree of protection IP 67 according to IEC 60529Installation position Any, alignment with read head

should be kept in mind (markings)Method of operation MagneticVibration resistance 10 ... 55 Hz, amplitude 1 mmShock resistance 30 g/11 ms Center offset m from read head ± 2.5 mm at a distance of s = 3 mmSwitch on distance Sao

Switch off distance Sar

See table listing

Reset spacing Sreset

combination options

XY

Z

Directionof

approach

Alignmentmarking

XY

Z

Directionof

approachAlignmentmarking

CM-S1...

CM-S2...

CM-S3...

Fig. 1: Alignment of read head and actuator

XY

Z

Alignmentmarking

Directionof

approach

For use and operation as per the re-quirements, a power supply with the feature “for use in class 2 circuits” must be used. They are not tested as safety components in the context of the UL definition (e.g. for potentially explosive atmospheres).

R

C US

Not all faults are detected. An accumulation of undetected faults can lead to the loss of the safety function. With this application, therefore, it is necessary to ensure that only one safety gate (door) is open at a time or t ha t t he s t a t us o f each sa f e t y ga te i s checked in suitable intervals.

Switching current le max. 0.5 A

No responsibility whatever is accepted for the use of the technical safety functioning of the CM Series read heads or actuators without the relevant CM Series control units.

Operating Instructions for CM Series Read Heads and Actuators

CM Series

Safety, Technology & Innovation

lynn
1.08
Page 2: CM Series Read Heads and Actuators Instruction Sheetproducts.omron.us/Asset/CM_InstructionSheet_en_200801_C...Combination options 2.5 2.5 S a 0 78 ±0.1?5.5 9. 5 2 5 1 2 6 6 67.5 87.5

Combination options

2.5 2.5 Sa0

78 ±0.1

? 5.5

9.5

25 12

6

667.587.5

2.5

13

42

ca.Ø

5.8

0.34 mm2

Fig. 2: Dimensions for CM-S1 and CM-S2 Read Heads and Actuators

CM-S2 Read Head

Actuator

active area

Centre offset m at s = 3 mm

Fig. 3: Dimensions for CM-S3 Read Heads and Actuators

CM-S3 Actuator

2

? Ø30

32.6

90°

Son2.

52.

5

?5.

5 2.5

13

15active area

Read head

Cent

re o

ffset

mat

s =

3 m

m

M30

x1. 5

42

3620

Sao

2.5

2.5

8

ca.

Ø5.

8?

0.34 mm2R1

SW40

SW15

Cent

re o

ffset

mat

s =

3 m

m

Actuator

active area

CM-S3 Read Head

Minimum Maximum Max.Read

Circuit diagramSwitch on Switch off Reset

Design headnot Actuator

distance distance dist.actuatedSao [mm]1) S Sresetar [mm] [mm]

CM-S2Read Head

CM-S2Actuator

CM-S3Actuator

6 13 30

CM-S3Read Head

6 13 16

1) There must be no ferromagnetic material in the vicinity of the read head or the actuator.All the data applies to the frontal direction of approach and a centre offset of m = 0.

2) The minimal switching distance S0mm between read head and actuator is 1 mm. If the distancefalls below 1 mm, the evaluation unit could go into fault condition.

CM

-S4

Con

trol

Uni

t

M30

2.5 2.5 Sao

19.2

26.2

22 736

13

5

8.5

4.5

42ca

5.8

?

0.34 mm2

CM-S1 Read Head

Actuatoractive area

Centre offset m at s = 3 mm

BNWH

YEGN

CM-S1Read Head

CM-S1Actuator 3 8 11

(2)

OMRON SCIENTIFIC TECHNOLOGIES, INC.6550 Dumbarton Circle, Fremont CA 94555-3605 USA

Tel: 1/510/608-3400 Fax: 1/510/744-1442E-mail: [email protected]

www.sti.com

European Tech SupportTel: +49 (0) 52 58 93 87 76Fax: +49 (0) 52 58 93 56 90

UK Sales OfficeTel: +44 (0) 1395-273-209Fax: +44 (0) 1395-276-183

©2007 Omron Scientific Tetchnologies, Inc. All rights reserved. Subject to technical modifications. Drawing Number 092580-04-09/07

Safety, Technology & Innovation

CM SeriesOperating Instructions for CM Series Read Heads and Actuators

Page 3: CM Series Read Heads and Actuators Instruction Sheetproducts.omron.us/Asset/CM_InstructionSheet_en_200801_C...Combination options 2.5 2.5 S a 0 78 ±0.1?5.5 9. 5 2 5 1 2 6 6 67.5 87.5

OMRON CANADA, INC. • HEAD OFFICEToronto, ON, Canada • 416.286.6465 • 866.986.6766 • www.omron247.com

OMRON ELECTRONICS DE MEXICO • HEAD OFFICEMéxico DF • 52.55.59.01.43.00 • 01-800-226-6766 • [email protected]

OMRON ELECTRONICS DE MEXICO • SALES OFFICEApodaca, N.L. • 52.81.11.56.99.20 • 01-800-226-6766 • [email protected]

OMRON ELETRÔNICA DO BRASIL LTDA • HEAD OFFICESão Paulo, SP, Brasil • 55.11.2101.6300 • www.omron.com.br

OMRON ARGENTINA • SALES OFFICECono Sur • 54.11.4783.5300

OMRON CHILE • SALES OFFICESantiago • 56.9.9917.3920

OTHER OMRON LATIN AMERICA SALES54.11.4783.5300

Authorized Distributor:

C278I-E-01 01/08 Note: Specifications are subject to change. © 2014 Omron Electronics LLC Printed in U.S.A.

Printed on recycled paper.

Automation Control Systems• Machine Automation Controllers (MAC) • Programmable Controllers (PLC) • Operator interfaces (HMI) • Distributed I/O • Software

Drives & Motion Controls • Servo & AC Drives • Motion Controllers & Encoders

Temperature & Process Controllers • Single and Multi-loop Controllers

Sensors & Vision• Proximity Sensors • Photoelectric Sensors • Fiber-Optic Sensors• Amplified Photomicrosensors • Measurement Sensors• Ultrasonic Sensors • Vision Sensors

Industrial Components • RFID/Code Readers • Relays • Pushbuttons & Indicators• Limit and Basic Switches • Timers • Counters • Metering Devices • Power Supplies

Safety • Laser Scanners • Safety Mats • Edges and Bumpers • Programmable Safety Controllers • Light Curtains • Safety Relays • Safety Interlock Switches

OMRON AUTOMATION AND SAFETY • THE AMERICAS HEADQUARTERS • Chicago, IL USA • 847.843.7900 • 800.556.6766 • www.omron247.com

OMRON EUROPE B.V. • Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands. • +31 (0) 23 568 13 00 • www.industrial.omron.eu