HD HD HD HD Combined SPD- Type 1+2 Description Circuit diagram Dimension drawing Features Approval UL 94 V-0 TUV CE RoHS This SPD Combination consisting of: 4 x PE 760-25W1-10R 1 x Busbar 7P-4 No follow current Reliable thermo disconnect device High discharge capacity Capable of protecting terminal equipment Multifunctional terminals for connecting conductors and busbars Visual and remote status indication DIN rail installation DIN Rail, for use in a.c. system at combined Type 1&2 /Class I&II SPD boundaries from LPZ 0B-1 and higher. PTG CORPORATION Vibration and shock testing veried, EN60082-2 compliance Directly coordinated with Type 2 or 3 SPD without additional cable length, DIN CLC/TS 61643-12 compliance PE 760-25W1-10R PE 760-25W1-10R PE 760-25W1-10R PE 760-25W1-10R

Upload: others

Post on 10-Sep-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Combined SPD- Type 1+2 - canadiansolar.com.br€¦ · DIN CLC/TS 61643-12 compliance PE 760-25W1-10R PE 760-25W1-10R PE 760-25W1-10R PE 760-25W1-10R. 25 mm² stranded / exible Type

HDHD HD HD

Combined SPD- Type 1+2

Description

Circuit diagram

Dimension drawing

Features

Approval

UL 94 V-0

TUVCERoHS

This SPD Combination consisting of:

4 x PE 760-25W1-10R

1 x Busbar 7P-4

No follow currentReliable thermo disconnect deviceHigh discharge capacityCapable of protecting terminal equipment

Multifunctional terminals for connecting conductors and busbars

Visual and remote status indication

DIN rail installation

DIN Rail, for use in a.c. system at combined Type 1&2 /Class I&II SPD boundaries from LPZ 0B-1 and higher.

PTG CORPORATION

Vibration and shock testing veri�ed, EN60082-2 complianceDirectly coordinated with Type 2 or 3SPD without additional cable length, DIN CLC/TS 61643-12 compliance

PE 760-25W1-10R PE 760-25W1-10R PE 760-25W1-10R PE 760-25W1-10R

Page 2: Combined SPD- Type 1+2 - canadiansolar.com.br€¦ · DIN CLC/TS 61643-12 compliance PE 760-25W1-10R PE 760-25W1-10R PE 760-25W1-10R PE 760-25W1-10R. 25 mm² stranded / exible Type

2 mm² stranded / �exible5

Type 1 + Type 2

Withstand

≤ 100 ns

2.5 kV

3.5 kV

760 Vac

1

PE 760-25W1-40R-B

25 kArms

400/690 Vac

25 kA

156.25 kJ / ohms12.5 As

≤ 250 AgL / gG

Type

Part No.

Electrical

SPD according to IEC 61643-1/11

SPD according to EN 61643-11

Number of ports

Technology

Nominal Voltage (UN)

Max. continuous operating voltage (UC)

Nominal discharge current (8/20 µs) (In)

Lightning impulse current (10/350 µs) (limp)

Charge (Q)

Follow current extinguishing capability (If I)

Voltage protection level (UP)

Voltage protection level for 5 kA (UP)

Response time (tA)

Max. overcurrent protection

Short-circuit withstand capability

Temporary overvoltage (TOV) (UT)

TOV characteristic

3 N*m

10 mm

35 mm DIN rail

150 mm × 144 mm × 72 mm

Changeover contact

125 Vac / 1 A

1.5 mm ²

7 mm

0.2 N*m

IP 20

≤ 95%(max 40°C)

Indoor only

Thermoplastic, UL 94 V-0

≤ 4 km

Mechanical

Method of mounting

Enclosure dimensions (HxWxD)

Cross-sectional area (max.)

Cross-sectional area (min.)

Stripping length terminals

Torque contacts

Indication

Operating status/fault indication

Type of Changeover contact

Switching capacity

Cross-sectional area (max.)

Stripping length for indication terminals

Torque contacts for indication terminals

Environmental

Location category

Operation temperature range (TU)

Relative humidity

Operation altitude

Degree of protection according to IEC/EN 60529

Enclosure material

-40°C ... +80°C

SPD according to GB 18802.1 Class I + Class II

(ISCW)

25 kA

1.5 mm² stranded / �exible

PE 760-25W1-40R-B

Class I + Class II

Infinite

Spark Gap&MOV

Specific energy (W/R)

PTG CORPORATION PTG-DS-EN-V1901

1000 V / 5 s

Black / red

93 40 90

Page 3: Combined SPD- Type 1+2 - canadiansolar.com.br€¦ · DIN CLC/TS 61643-12 compliance PE 760-25W1-10R PE 760-25W1-10R PE 760-25W1-10R PE 760-25W1-10R. 25 mm² stranded / exible Type

Technical Data Connection Diagram Backup Fuse

Safety Instruction

The device may only be connected and installed by an electrically skilled person.National standards and safety regulations must be observed (see IEC 60364-5-53).The device must be checked for external damage before installation. The device must not beinstalled if any damage or other faults are detected in this check.Its use is only permitted within the limits shown and stated in these installation instructions. Thedevice and the equipment connected to it can be destroyed by loads exceeding the values stated.Opening or tampering with the device invalidates the warranty.

Maintenance info

INSTALLATION INSTRUCTION INS-E-760-25W1-40R-B-01A

@ COPYRIGHT 2018 PTG CORPORATION

CoordinationLPZ 0A LPZ 1 LPZ 2 LPZ 3

Class I + Class IIType 1 + Type 2PE XXX-XXW1-XXX

IEC 62305-4

IEC 61643-1/11EN 61643-11

F1

F2

F2 = 250 A gL / gG

F1 250 A gL / gG,

F2

F1 250 A gL / gG

IF

IF

max.

PE 760-25W1-40R-B

NC

COM

NO

Red ReplaceGreen OK;

max. 1.5 mm²6-7 mm

10-12 mm

Type934090No

Type of LV System TT,TNUo(UN)

LocationNumber of Ports

400/690 Vac(50/60 Hz)

1Indoor

Iimp(10/350 μs) 25 kA

T/H/A -40-85℃/<95%/4 kmA 3 NmB 35 mm DINrail (EN 60715)

L x H x W 150 mm x 144 mm x 72 mm

min. L, N, PEmax. L, N, PE

1.5 mm² 25 mm²

Fault Indication

Remote alarm terminalOnly for "R"

UN/IN 125 Vac/1 A;125 Vdc/0.2 A

In(8/20 μs)

Isccr/Ifi/IPE

25 kA

25 kA/-/-250 A gL/gG

min S1 16 mm² Cu

0.2 Nm

W/R 156.25 k J/ohms

F2

S1

MEB

F1L1L2L3NPE

ALARM

B

A

PTG CORPORATIONAddress: 3F, Mingdao Building, SGETechnology Park, #28 Cuibao Road, Long Gang District, Shenzhen, China

Tel: +86 755 2150 4406Fax: +86 755 2941 5700www.ptgcorporation.com