  • COMMERCIAL COOLING LOAD CALCULATION

    Project Bldg./Room Location CALAFONNIA Engrs. Calc. by Chk. By

    DB WB RH WF F % gr/lb Daily Range 33 F Ave. 84 F

    Outdoor 100 69 101 Day 21-JulRoom 78 50 66 Lat. 39N

    Conduction Dir. Color U A, ft2 CLTD, FGross Net Table Corr.

    Glass

    W 0.94 120 14 13 1466

    Wall

    Gro

    up E

    NSE DARKW 0.28 300 180 20 19 958

    Roof/Ceiling 0Floor 0Partition 0Door 0

    =

    RSH

    R =

    RSC

    L/R

    TCL

    =

    RSC

    L

    .

    1.1x

    (Tr-T

    sa)

    Solar Dir Sh. SHGF A SC CLF

    Glass

    W 216 120 0.81 0.72 15116

    Lights 2400 x W x 3.41 1.25 BF x CLF 10230Lights x W x 3.41 BF x CLF LCL

    People 250 SHG x 10 n x CLF 2500 BTU/hr200 LHG x 10 n 2000

    EquipmentEquipment

    Infiltration 1.1 x 150 CFM x 22 TC 36300.68 x 150 CFM x 40 gr/lb 4080

    SubtotalSA duct gain

    SA duct leakageTotal CL

    SA fan gain (draw through) BTU/hrRoom/Building Cooling Load, 39980

    SA fan gain (blow through)Infiltration 1.1 x CFM x TC

    0.68 x CFM x gr/lb

    RA duct gainRA fan gain Cooling Coil Load

    Refrigeration LoadPump gain

    SCL BTU/hr

    CFM

    sa =

  • COMMERCIAL COOLING LOAD CALCULATION

    Project Superb SuperMarket Bldg./Room Single Story Building with a BasementLocation Ohio, Clumbus Engrs. Haroon Sab Calc. by MA Javaid Chk. By Haroon Sab

    DB WB RH WF F % gr/lb Daily Range 19 F Ave. 81 F

    Outdoor 90 77 Day 21-JulRoom 76 Lat. 40

    Conduction Dir. Color U A, ft2 CLTD, FGross Net Table Corr.

    Glass

    W 1.01 - 830 13 11 9221W 1.01 - 42 13 11 467E 1.01 - 42 13 11 467

    Wall

    Gro

    up B

    W D 0.11 1260 388 17 15 640E D 0.11 - 1176 26 24 3105N D 0.11 - 840 11 9 832S D 0.11 - 840 17 16 1478

    Roof/Ceiling - D 0.09 - 5400 36 35 17010Floor - D 0.35 - 5400 - 9 17010Partition - - - - - - - -Door E D 0.39 - 42 - 24 393

    =

    RSH

    R =

    RSC

    L/R

    TCL

    =

    RSC

    L

    .

    1.1x

    (Tr-T

    sa)

    Solar Dir Sh. SHGF A SC CLF

    Glass

    W no 216 42 0.94 0.71 6055W no 216 830 0.69 0.71 87829E no 216 42 0.94 0.19 1620

    Lights 16200 x W x 3.41 1.2 BF x 1 CLF 66290Lights x W x 3.41 BF x CLF LCL

    People 250 SHG x 60 n x 1 CLF 15000 BTU/hr200 LHG x 60 n 12000

    EquipmentEquipment

    Infiltration 1.1 x CFM x TC0.68 x CFM x gr/lb

    SubtotalSA duct gain

    SA duct leakageTotal CL

    SA fan gain (draw through) BTU/hrRoom/Building Cooling Load,

    SA fan gain (blow through)Infiltration 1.1 x CFM x TC

    0.68 x CFM x gr/lb

    RA duct gainRA fan gain Cooling Coil Load

    Refrigeration LoadPump gain

    SCL BTU/hr

    CFM

    sa =

  • COMMERCIAL COOLING LOAD CALCULATION

    Project Peak Cooling Load Bldg./Room General OfficeLocation Sacramento, California Engrs. Haroon Sab Calc. by M.A Javaid

    DB WB RH WF F % gr/lb Daily Range

    Outdoor 83 Day Room 78 50 Lat.

    Conduction Dir. Color U A, ft2 CLTD, FGross Net Table Corr.

    Glass

    W - 0.81 - 120 9 7- - - - - - -- - - - - - -- - - - - - -

    Wall

    Gro

    up E

    W D 0.28 300 180 9 7E D 0.28 300 300 - 2- - - - - - -- - - - - - -

    Roof/Ceiling - - - - - - -Floor - - - - - - -Partition - - - - - - -Door - - - - - - -

    - - - - - - -- - - - - - -

    Solar Dir Sh. SHGF A SC CLF

    Glass

    W D 216 - 120 0.17- - - - - -- - - - - -- - - - - -- - - - - -

    Lights 2400 x W x 3.41 1.25 BF x 1 CLFLights x W x 3.41 BF x CLF

    People 250 SHG x 10 n x 1 CLF200 LHG x 10 n

    EquipmentEquipment

    Infiltration 1.1 x CFM x TC0.68 x CFM x gr/lb

    SubtotalSA duct gain

    SA duct leakage

    SA fan gain (draw through)Room/Building Cooling Load,

    SA fan gain (blow through)Infiltration 1.1 x CFM x TC

  • 0.68 x CFM x gr/lb

    RA duct gainRA fan gain Cooling Coil Load

    Refrigeration LoadPump gain

  • COMMERCIAL COOLING LOAD CALCULATION

    Chk. By Haroob Sab

    33 F Ave. 83 F7/21/2007, at 1200 hr

    39

    680

    353168

    =

    RSH

    R =

    RSC

    L/R

    TCL

    =

    RSC

    L

    .

    1.1x

    (Tr-T

    sa)

    4406

    10230LCL

    2500 BTU/hr2000

    Subtotal

    Total CLBTU/hr

    Room/Building Cooling Load,

    SCL BTU/hr

    CFM

    sa =

  • Cooling Coil Load

    Refrigeration Load

    ChartExample 6.17Problem 6.10