Communication module CM DP

(6ES7545-5DA00-0AB0)

___________________

___________________

___________________

___________________

___________________

___________________

___________________

___________________

SIMATIC

ET 200SP Communication module CM DP (6ES7545-5DA00-0AB0)

Manual

12/2014 A5E33619758-AB

Preface

ET 200SP Documentation Guide

1

Product overview 2

Wiring 3

Programming 4

Diagnostics, error and system alarms

5

Technical specifications 6

Dimension drawing A

Page 3: Communication module CM DP (6ES7545-5DA00-0AB0)

Siemens AG Division Digital Factory Postfach 48 48 90026 NÜRNBERG GERMANY

A5E33619758-AB Ⓟ 12/2014 Subject to change

Copyright © Siemens AG 2014. All rights reserved

Legal information Warning notice system

This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.

DANGER indicates that death or severe personal injury will result if proper precautions are not taken.

WARNING indicates that death or severe personal injury may result if proper precautions are not taken.

CAUTION indicates that minor personal injury can result if proper precautions are not taken.

NOTICE indicates that property damage can result if proper precautions are not taken.

If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.

Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems.

Proper use of Siemens products Note the following:

WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed.

Trademarks All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.

Disclaimer of Liability We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.

Page 4: Communication module CM DP (6ES7545-5DA00-0AB0)

Communication module CM DP (6ES7545-5DA00-0AB0) 4 Manual, 12/2014, A5E33619758-AB

Preface

Purpose of the documentation This manual supplements the system manual ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293).

Functions that generally relate to the system are described in this system manual.

The information provided in this manual and in the system/function manuals supports you in commissioning the ET 200SP distributed I/O system.

Conventions STEP 7: In this documentation, "STEP 7" is used as a synonym for all versions of the configuration and programming software "STEP 7 (TIA Portal)".

Please also observe notes marked as follows:

Note

A note contains important information on the product described in the documentation, on the handling of the product or on the section of the documentation to which particular attention should be paid.

Security information Siemens provides products and solutions with industrial security functions that support the secure operation of plants, solutions, machines, equipment and/or networks. They are important components in a holistic industrial security concept. With this in mind, Siemens’ products and solutions undergo continuous development. Siemens recommends strongly that you regularly check for product updates.

For the secure operation of Siemens products and solutions, it is necessary to take suitable preventive action (e.g. cell protection concept) and integrate each component into a holistic, state-of-the-art industrial security concept. Third-party products that may be in use should also be considered. You can find more information about industrial security on the Internet (http://www.siemens.com/industrialsecurity).

To stay informed about product updates as they occur, sign up for a product-specific newsletter. You can find more information on the Internet (http://support.automation.siemens.com).

Page 5: Communication module CM DP (6ES7545-5DA00-0AB0)

Communication module CM DP (6ES7545-5DA00-0AB0) Manual, 12/2014, A5E33619758-AB 5

Table of contents

Preface ................................................................................................................................................... 4

1 ET 200SP Documentation Guide ............................................................................................................. 6

2 Product overview .................................................................................................................................... 8

2.1 Properties .................................................................................................................................. 8

2.2 Operating and display elements ............................................................................................. 11

3 Wiring ................................................................................................................................................... 12

3.1 Pin assignment ....................................................................................................................... 12

3.2 Block diagram ......................................................................................................................... 13

4 Programming ........................................................................................................................................ 14

5 Diagnostics, error and system alarms .................................................................................................... 16

5.1 Status and error displays ........................................................................................................ 16

5.2 DP slave diagnostics............................................................................................................... 18

5.3 Standard diagnostics .............................................................................................................. 20

5.4 Device-specific diagnostics with DP-V1 .................................................................................. 22

6 Technical specifications ........................................................................................................................ 25

6.1 Technical specifications .......................................................................................................... 25

A Dimension drawing ............................................................................................................................... 28

A.1 Dimension drawing of the CM DP communication module .................................................... 28

Page 6: Communication module CM DP (6ES7545-5DA00-0AB0)

Communication module CM DP (6ES7545-5DA00-0AB0) 6 Manual, 12/2014, A5E33619758-AB

ET 200SP Documentation Guide 1

The documentation for the SIMATIC ET 200SP distributed I/O system is arranged into three areas. This arrangement enables you to access the specific content you require.

Basic information

The system manual describes in detail the configuration, installation, wiring and commissioning of the SIMATIC ET 200SP. distributed I/O system. The STEP 7 online help supports you in the configuration and programming.

Device information

Product manuals contain a compact description of the module-specific information, such as properties, terminal diagrams, characteristics and technical specifications.

General information

The function manuals contain detailed descriptions on general topics regarding the SIMATIC ET 200SP distributed I/O system, e.g. diagnostics, communication, Web server, designing interference-free controllers.

You can download the documentation free of charge from the Internet (http://w3.siemens.com/mcms/industrial-automation-systems-simatic/en/manual-overview/tech-doc-et200/Pages/Default.aspx).

Changes and supplements to the manuals are documented in a Product Information.

Page 7: Communication module CM DP (6ES7545-5DA00-0AB0)

ET 200SP Documentation Guide

Communication module CM DP (6ES7545-5DA00-0AB0) Manual, 12/2014, A5E33619758-AB 7

Manual Collection ET 200SP The Manual Collection contains the complete documentation on the SIMATIC ET 200SP distributed I/O system gathered together in one file.

You can find the Manual Collection on the Internet (http://support.automation.siemens.com/WW/view/en/84133942).

My Documentation Manager The My Documentation Manager is used to combine entire manuals or only parts of these to your own manual. You can export the manual as PDF file or in a format that can be edited later.

You can find the My Documentation Manager on the Internet (http://support.automation.siemens.com/WW/view/en/38715968).

Applications & Tools Applications & Tools supports you with various tools and examples for solving your automation tasks. Solutions are shown in interplay with multiple components in the system - separated from the focus in individual products.

You can find Applications & Tools on the Internet (http://support.automation.siemens.com/WW/view/en/20208582).

CAx Download Manager The CAx Download Manager is used to access the current product data for your CAx or CAe systems.

You configure your own download package with a few clicks.

In doing so you can select:

● Product images, 2D dimension drawings, 3D models, internal circuit diagrams, EPLAN macro files

● Manuals, characteristics, operating manuals, certificates

● Product master data

You can find the CAx Download Manager on the Internet (http://support.automation.siemens.com/WW/view/en/42455541).

TIA Selection Tool With the TIA Selection Tool, you can select, configure and order devices for Totally Integrated Automation (TIA). This tool is the successor of the SIMATIC Selection Tool and combines the known configurators for automation technology into one tool. With the TIA Selection Tool, you can generate a complete order list from your product selection or product configuration.

You can find the TIA Selection Tool on the Internet (http://w3.siemens.com/mcms/topics/en/simatic/tia-selection-tool).

Page 8: Communication module CM DP (6ES7545-5DA00-0AB0)

Communication module CM DP (6ES7545-5DA00-0AB0) 8 Manual, 12/2014, A5E33619758-AB

Product overview 2 2.1 Properties

Article number 6ES7545-5DA00-0AB0

View of the module

Figure 2-1 View of the CM DP communication module

Page 9: Communication module CM DP (6ES7545-5DA00-0AB0)

Product overview 2.1 Properties

Communication module CM DP (6ES7545-5DA00-0AB0) Manual, 12/2014, A5E33619758-AB 9

Properties The communication module CM DP can be used with the ET 200SP CPUs. You insert the communication module to the right next to the CPU.

The communication module has the following properties:

● Technical properties

– Connects the CPU of the ET 200SP distributed I/O system with PROFIBUS DP

– Bus connection via RS485 interface

● Supported functions

– Operation as DP master or DP slave

– Enable/disable DP slave

– Diagnostics requirements

– Identify the bus topology in a DP master system

– Identification data I&M 0

– Time-of-day synchronization

– Line diagnostics

– S7 services

Supported communication services The communication module supports the following communication services:

● PROFIBUS DP-Master, as of STEP 7 V13, Update 3

– PROFIBUS DP according to IEC 61158 and 61784 DPV1, DP master for DP slaves according to PROFIBUS DP and DPV1 standard

● PROFIBUS DP slave, as of STEP 7 V13, SP1

– PROFIBUS DP according to IEC 61158 and 61784 DPV1, DP slave and I-slave

Note DP master or DP slave

Note however: The CM DP only supports alternative operation as DP master or DP slave.

Page 10: Communication module CM DP (6ES7545-5DA00-0AB0)

Product overview 2.1 Properties

Communication module CM DP (6ES7545-5DA00-0AB0) 10 Manual, 12/2014, A5E33619758-AB

Maximum configuration as DP Master

Table 2- 1 General characteristics of DP mode

Feature Explanation/values Number of operable DP slaves 125 Max. size of the input area over all DP slaves 8 KB Max. size of the output area via all DP slaves 8 KB Maximum number of inputs per DP slave 244 bytes Maximum number of outputs per DP slave 244 bytes Max. size of the consistency area for a module 128 bytes

Note Setting the PROFIBUS DP address on the communication module CM DP

The communication module CM DP does not have a DIP switch. You set the PROFIBUS DP address via STEP 7 (TIA Portal). You can find more information on this topic in the STEP 7 online help.

Accessories A detailed list of the available accessories can be found in the system manual ET 200SP distributed I/O system (http://support.automation.siemens.com/WW/view/en/58649293).

Additional information You can obtain detailed information on the topic of PROFIBUS in the function manual PROFIBUS (http://support.automation.siemens.com/WW/view/de/59193579/0/en)

Page 11: Communication module CM DP (6ES7545-5DA00-0AB0)

Product overview 2.2 Operating and display elements

Communication module CM DP (6ES7545-5DA00-0AB0) Manual, 12/2014, A5E33619758-AB 11

2.2 Operating and display elements

Operating and connection elements The following figure shows the operating and connection elements of the CM DP communication module.

① Mounting rail release ② DIAG LED ③ DP interface

Figure 2-2 Operating and display elements of the communication module CM DP

Page 12: Communication module CM DP (6ES7545-5DA00-0AB0)

Communication module CM DP (6ES7545-5DA00-0AB0) 12 Manual, 12/2014, A5E33619758-AB

Wiring 3 3.1 Pin assignment

PROFIBUS DP with RS485 interface The following table shows the signal names and the designations of the pin assignment for the PROFIBUS DP interface.

Table 3- 1 Pin assignment PROFIBUS DP with RS485 interface

View Signal name Designation

1 - - 2 - - 3 RxD/TxD-P Data line B 4 RTS Request To Send 5 M5V2 DP data reference potential

(from station) 6 P5V2 Supply plus (from station) 7 - - 8 RxD/TxD-N Data line A 9 - -

Page 13: Communication module CM DP (6ES7545-5DA00-0AB0)

Wiring 3.2 Block diagram

Communication module CM DP (6ES7545-5DA00-0AB0) Manual, 12/2014, A5E33619758-AB 13

3.2 Block diagram The following figure shows the block diagram of the CM DP communication module.

① Backplane bus PB PROFIBUS interface ② ET 200SP PROFIBUS interface and backplane

bus transmission DIAG LED diagnostics (green/red)

③ Internal power supply

Figure 3-1 Block diagram of the CM DP

Page 14: Communication module CM DP (6ES7545-5DA00-0AB0)

Communication module CM DP (6ES7545-5DA00-0AB0) 14 Manual, 12/2014, A5E33619758-AB

Programming 4

Instructions Pre-written instructions are available as an interface in your STEP 7 user program for communication services.

Table 4- 1 Instructions for PROFIBUS DP

Instructions Meaning when used with CM DP

DP master DP slave (I-slave) DPSYC_FR Synchronize DP slaves/Freeze inputs

(SYNC/FREEZE instruction) -

DPNRM_DG Read diagnostics data of a DP slave - DP_TOPOL Determine topology for DP master system - WRREC Write data record of a DP slave - RDREC Read data record of a DP slave - GETIO Read process image of a DP standard slave Read process image SETIO Transfer process image of a DP standard slave Transfer process image GETIO_PART Read process image area of a DP standard

slave Read process image area

SETIO_PART Transfer process image area of a DP standard slave

Transfer process image area

D_ACT_DP Enable/disable DP slaves - DPRD_DAT Read consistent data of a module (user data) DPWR_DAT Write consistent data of a module RALRM Event-driven reading of alarm information

(diagnostics, pull/plug, hardware interrupt) as well as DPV1-specific interrupts (update, status, vendor-specific interrupt)

Event-driven reading of interrupt information (diagnostic interrupt)

Read the documentation for the instructions in the STEP 7 online help

Page 15: Communication module CM DP (6ES7545-5DA00-0AB0)

Programming

Communication module CM DP (6ES7545-5DA00-0AB0) Manual, 12/2014, A5E33619758-AB 15

Calling instructions for distributed I/O Multiple calls are required for the instructions of the distributed I/O.

The duration of the call processing is dependent on the load, bus cycle time and transmission rate. Timeouts may occur if these instructions are called in a loop within a cycle.

Exceptions:

● Only one call is necessary for the RALRM instruction "Receive interrupt".

Program blocks for DPV1 (according to PNO standard) 1):

● "Read data record from a DP slave" RDREC instruction is functionally equivalent to SFC59 (write record)

● "Write data record to a DP slave" WRREC instruction is functionally equivalent to SFC58 (read record)

● "Read interrupt information from a DP slave" RALRM instruction call is made within an interrupt OB

1) PNO: PROFIBUS user organization

Page 16: Communication module CM DP (6ES7545-5DA00-0AB0)

Communication module CM DP (6ES7545-5DA00-0AB0) 16 Manual, 12/2014, A5E33619758-AB

Diagnostics, error and system alarms 5 5.1 Status and error displays

Introduction Diagnostics by means of LEDs is an initial tool for error localization. In order to localize errors still further, you usually evaluate the display of the module status in STEP 7 or the diagnostics buffer of the CPU. The buffer contains plain text information on the error that has occurred. For example, you will find the number of the relevant error OB in the plain text information.

LED display The figure below shows the LED display on the CM DP communication module.

① DIAG (green/red)

Figure 5-1 LED display on the CM DP communication module

Page 17: Communication module CM DP (6ES7545-5DA00-0AB0)

Diagnostics, error and system alarms 5.1 Status and error displays

Communication module CM DP (6ES7545-5DA00-0AB0) Manual, 12/2014, A5E33619758-AB 17

Meaning of the DIAG LED display on the communication module The CM DP communication module has an LED for monitoring the diagnostics.

DIAG LED

Table 5- 1 DIAG LED fault display

DIAG LED Meaning

Flashes

Module parameters not assigned

On

Module parameters assigned and no diagnostics

Flashes

Diagnostics of subordinate modules (as of firmware version V1.7)

Additional information You can find more information on diagnostics in the Diagnostics function manual (http://support.automation.siemens.com/WW/view/de/59192926/0/en) for diagnostic options that are available for SIMATIC systems S7-1500, ET 200MP, ET 200SP and ET 200AL.

Page 18: Communication module CM DP (6ES7545-5DA00-0AB0)

Diagnostics, error and system alarms 5.2 DP slave diagnostics

Communication module CM DP (6ES7545-5DA00-0AB0) 18 Manual, 12/2014, A5E33619758-AB

5.2 DP slave diagnostics

DP V1 slave: Diagnostic interrupt Transmission of diagnostic data is made as a diagnostic interrupt. Diagnostic interrupts must be acknowledged by the DP master.

Supported diagnostic functions The CM DP supports the following blocks of the DP diagnostics:

● Standard diagnostics (6 bytes)

● Identifier-related diagnostics (2...17 bytes depending on the number of configured transfer areas)

● Module status (5...35 bytes depending on the number of configured transfer areas)

● Diagnostic interrupt (8 bytes, if any)

User program (DP master) The "DPNRM_DG" instruction is used to read the diagnostic data of a DP slave (DP single diagnostics) in the DP master.

The diagnostic interrupts for DP V1 slaves are periodically evaluated in the user program of the master via the "RALRM" instruction.

You can find the required parameter assignment for the instruction in the STEP 7 online help.

The following is a structural overview of the diagnostic data.

Overview of standard diagnostics

Standard diagnostics Byte Meaning

0 Station status 1 1 Station status 2 2 Station status 3 3 Master address

4...5 Manufacturer ID of the slave

Page 19: Communication module CM DP (6ES7545-5DA00-0AB0)

Diagnostics, error and system alarms 5.2 DP slave diagnostics

Communication module CM DP (6ES7545-5DA00-0AB0) Manual, 12/2014, A5E33619758-AB 19

Overview of device-specific diagnostics The device-specific diagnostics data depends on the protocol variant in which the DP slave is operated:

● DP-V1 slave

Table 5- 2 Overview of device-specific diagnostics of the CM DP for DP V1 slaves

Device-specific diagnostics Byte Meaning

0 Header 1 Variant

Interrupt type Variant

Status type 2 Slot number 3 Variant

Interrupt specifier Variant

Status specifier 4...62 Module-specific diagnostic data

Page 20: Communication module CM DP (6ES7545-5DA00-0AB0)

Diagnostics, error and system alarms 5.3 Standard diagnostics

Communication module CM DP (6ES7545-5DA00-0AB0) 20 Manual, 12/2014, A5E33619758-AB

5.3 Standard diagnostics

Standard diagnostics The coding of the standard diagnostic bytes is explained below.

Byte 0: Station status 1

Table 5- 3 Structure of station status byte 1

Bit no. Name Explanation 7 Master_Lock The DP slave was configured by a different DP master. The DP slave can only be

accessed read-only by the DP master configured as productive. This bit is set by the DP master when its bus address does not match the configured address.

6 Parameter_Fault The most recently received parameter frame was corrupt or not permitted. This bit is set by the DP slave. Remedy: Check the parameter assignment with respect to invalid parameters.

5 Invalid_Slave_Response This bit is set by the DP master if an implausible response has been received by the DP slave.

4 Service_Not_Supported This bit is set by the DP master if a function is called by the master that is not supported by the DP slave. Remedy: Disable the parameter assignment of the required function at the master.

3 Ext_Diag This bit is set by the slave. • Bit =1: Diagnostic data is available in the diagnostic area specific to the slave.

The diagnostic data can be evaluated in the user program of the master. • Bit =0: A status message can be available in the diagnostic area specific to the

slave. The status message can be evaluated in the user program of the master.

2 Slave_Config_Check_Fault The configuration data sent by the DP master is rejected by the DP slave. Cause: Configuration error. Remedy: Change the configuration.

1 Station_Not_Ready The DP slave is not yet ready for productive data exchange. This is a temporary condition and cannot be influenced by the DP master.

0 Station_Non_Existent The DP slave is not responding on the bus. This bit is set by the DP master 1 (the slave permanently sets this bit to 0). If the bit is set, the diagnostic bits contain the status of the last diagnostic alarm or the initial value.

Page 21: Communication module CM DP (6ES7545-5DA00-0AB0)

Diagnostics, error and system alarms 5.3 Standard diagnostics

Communication module CM DP (6ES7545-5DA00-0AB0) Manual, 12/2014, A5E33619758-AB 21

Byte 1: Station status 2

Table 5- 4 Structure of station status byte 2

Bit no. Name Explanation 7 Deactivated The DP slave was shown as inactive in the local parameter set and will not be cyclically

queried. 6 Reserved - Reserved - 5 Sync_Mode The DP slave is in SYNC mode. The bit is set by the slave. 4 Freeze_Mode The DP slave is in FREEZE mode. The bit is set by the slave. 3 Watchdog_On The watchdog is activated on the DP slave. The bit is set by the slave. 2 Status_From_Slave Bit =1: The diagnostics comes from the DP slave. The bit is permanently set by the slave

to 1. 1 Static_Diag Static diagnostics

If the DP slave sets this bit, the DP master must fetch the diagnostic data from the DP slave until the DP slave resets this bit. The DP slave sets this bit, for example, if it cannot perform data transfer.

0 Parameter_Request The DP slave sets this bit when it has to be re-parameterized and configured. If bit 0 and bit 1 are both set, bit 0 has the higher priority.

Byte 2: Station status 3

Table 5- 5 Structure of station status byte 3

Bit no. Name Explanation 7 Ext_Data_Overflow If this bit is set, there is more diagnostic information than is specified in the diagnostics

data. This data cannot be viewed. 6...0 Reserved - Reserved -

Byte 3: Master address The address of the DP master that has configured this DP slave is entered in the "Master_Add" byte.

If the DP slave was not configured by a DP master, the DP slave sets address 255 in this byte.

Bytes 4 and 5: Manufacturer ID of the slave ("Ident_Number") The manufacturer ID ("Ident_Number") for the DP slave type is entered in the bytes 4 and 5. This identifier can be used to identify the slave.

The most significant part of the value is in byte 5.

Page 22: Communication module CM DP (6ES7545-5DA00-0AB0)

Diagnostics, error and system alarms 5.4 Device-specific diagnostics with DP-V1

Communication module CM DP (6ES7545-5DA00-0AB0) 22 Manual, 12/2014, A5E33619758-AB

5.4 Device-specific diagnostics with DP-V1

Device-specific diagnostics The device-specific diagnostics of DP V1 slaves is available in two variants:

● Interrupt type

● Status type

The two variants differ in the coding of byte 1, bit 7 of the device-specific diagnostic data. The distinction is component-specific.

Byte 0: Header The two most significant bits have the value 00. This identifies the "Module-specific diagnostic data" block as a whole (see bytes 4...62).

The remaining six bits indicate the length of the data block including byte 0.

Byte 1: "Interrupt type" variant

Table 5- 6 Structure of byte 1 of the device-specific diagnostics ("Interrupt type" variant)

Bit no. Meaning 7 Value Meaning

0 Interrupt 6...0 Alarm_Type

0 - Reserved - 1 Diagnostic interrupt 2 Process interrupt 3 Pull interrupt 4 Plug interrupt 5 Status interrupt 6 Update interrupt 7...31 - Reserved - 32...126 Manufacturer-specific 127 - Reserved -

Older status interrupts can be overwritten by newer ones when status interrupts occur in rapid succession.

Page 23: Communication module CM DP (6ES7545-5DA00-0AB0)

Diagnostics, error and system alarms 5.4 Device-specific diagnostics with DP-V1

Communication module CM DP (6ES7545-5DA00-0AB0) Manual, 12/2014, A5E33619758-AB 23

Byte 1: "Status type" variant

Table 5- 7 Structure of byte 1 of the device-specific diagnostics ("Status type" variant)

Bit no. Meaning 7 Value Meaning

1 Status message 6...0 Status_Type

0 - Reserved - 1 Status message 2 Module_Status (see also bytes 4...62) 3...31 - Reserved - 32...126 Vendor-specific 127 - Reserved -

Byte 2: Slot number Slot number (1...n) of the slave module

0 is the placeholder for the overall device.

Byte 3: "Interrupt specifier" variant

Table 5- 8 Structure of byte 3 of the device-specific diagnostics ("Interrupt specifier" variant)

Bit no. Meaning 7...3 Seq_No Unique identification of an alarm message 2 Add_Ack If this bit is set, the DP V1 master indicates that this interrupt

expects an acknowledgment in the form of a WRITE job. 1...0 Alarm_Specifier

0 No further distinction 1 Interrupt appears, slot is disrupted

The slot generates an interrupt due to an error. 2 Interrupt disappears, slot is OK

The slot generates an interrupt and indicates that there is no other error.

3 Interrupt disappears, slot is still disrupted The slot generates an interrupt and indicates that errors remain.

Page 24: Communication module CM DP (6ES7545-5DA00-0AB0)

Diagnostics, error and system alarms 5.4 Device-specific diagnostics with DP-V1

Communication module CM DP (6ES7545-5DA00-0AB0) 24 Manual, 12/2014, A5E33619758-AB

Byte 3: "Status specifier" variant

Table 5- 9 Structure of byte 3 of the device-specific diagnostics ("Status specifier" variant)

Bit no. Meaning 7...2 - Reserved - 1...0 Status_Specifier

0 No further distinction 1 Status appears 2 Status disappears 3 - Reserved -

Bytes 4...62: Module-specific diagnostic data: General coding This byte contains data with module-specific information that is described in the respective module documentation. The particular module is identified by the slot (byte 2).

Bytes 4...62: Module-specific diagnostics for "Status type" and "Modul_Status" In the case of the "Status type" variant of device-specific diagnostics from DP V1 slaves (see byte 1, bit 7) and the "Module_Status" setting (see byte 1, bits 0...6) two status bits are provided here for each slot (= module). Unneeded bits are set to 0.

Table 5- 10 Structure of the bytes for the module-specific diagnostic data

Byte Bit assignment Bit 7 6 5 4 3 2 1 0

4 Module status 4 Module status 3 Module status 2 Module status 1 5 Module status 8 Module status 7 Module status 6 Module status 5 ... ... ... ... ... 62 Module status 236 Module status 235 Module status 234 Module status 233

The respective status bits are coded as follows:

Table 5- 11 Meaning of the values of the status bits

Value Meaning 00 Data valid 01 Data invalid - error (e.g. short-circuit) 10 Data invalid - wrong module 11 Data invalid - no module plugged

Page 25: Communication module CM DP (6ES7545-5DA00-0AB0)

Communication module CM DP (6ES7545-5DA00-0AB0) Manual, 12/2014, A5E33619758-AB 25

Technical specifications 6 6.1 Technical specifications

Technical specifications of the CM DP (6ES7545-5DA00-0AB0) communication module

6ES7545-5DA00-0AB0 Product type designation ET 200SP, CM DP General information Hardware version FS01 HW functional status FS01 Engineering with STEP 7 TIA Portal can be configured/integrated as of version

V13 Update 3

Installation type/mounting Rack mounting possible No Rail mounting possible Yes; standard DIN rail Supply voltage Type of supply voltage 24 VDC Rated value (DC) 24 V Valid range low limit (DC) 19.2 V Valid range high limit (DC) 28.8 V Reverse polarity protection Yes Interfaces Number of interfaces PROFIBUS 1 1. interface Interface hardware • RS 485 Yes

Protocols • SIMATIC communication Yes

• PROFIBUS DP master Yes

• PROFIBUS DP slave Yes

Interface hardware RS 485 Transmission rate, max. 12 Mbps Max. cable length 100 m

Page 26: Communication module CM DP (6ES7545-5DA00-0AB0)

Technical specifications 6.1 Technical specifications

Communication module CM DP (6ES7545-5DA00-0AB0) 26 Manual, 12/2014, A5E33619758-AB

6ES7545-5DA00-0AB0 Protocols PROFIBUS DP master Services • PG/OP communication Yes

• S7 routing Yes

• Data record routing Yes

• Isochronous mode No

• Constant bus cycle time No

• Number of DP slaves 125

• Activation/deactivation of DP slaves Yes

PROFIBUS DP slave Transmission rate, max. 12 Mbps Automatic baud rate search Yes Address area, max. 120 User data per address area, max. 128 bytes Services • PG/OP communication Yes, only with active interface

• Routing Yes, only with active interface

• S7 communication Yes, only with active interface

• Direct data exchange (data exchange broadcast)

Yes, no subscriber possible - only passive publisher

• DPV1 Yes

Transfer memory • Inputs 244 bytes

• Outputs 244 bytes

Interrupts/diagnostics/status information Diagnostic alarms Diagnostics Yes Diagnostic indicator LED For module diagnostics Yes; green/red DIAG LED Electrical isolation Between backplane bus and interface Yes Ambient conditions Ambient temperature in operation Horizontal installation, min. 0 °C Horizontal installation, max. 60 °C Vertical installation, min. 0 °C Vertical installation, max. 50 °C

Page 27: Communication module CM DP (6ES7545-5DA00-0AB0)

Technical specifications 6.1 Technical specifications

Communication module CM DP (6ES7545-5DA00-0AB0) Manual, 12/2014, A5E33619758-AB 27

6ES7545-5DA00-0AB0 Dimensions Width 35 mm Height 117 mm Depth 75 mm Weights Weight, approx. 80 g

Page 28: Communication module CM DP (6ES7545-5DA00-0AB0)

Communication module CM DP (6ES7545-5DA00-0AB0) 28 Manual, 12/2014, A5E33619758-AB

Dimension drawing A A.1 Dimension drawing of the CM DP communication module

This section contains a dimension drawing of the module mounted on a mounting rail. Observe the dimensions when installing in cabinets, control rooms, etc.

Dimension drawing of the CM DP communication module

Figure A-1 Dimension drawing CM DP