connections and settings - caner62.com series/ios/23ba40_cs_en.… · sponding slot address in...

10
RTU560 product line Binary output 23BA40 Connections and settings Application, characteristics and technical data have to be taken from the hardware data sheet: 23BA40 Data sheet 1KGT 150 601 Operation The 23BA40 has sixteen output relays. Each relay has its own return. This allows to use individual process voltage levels for all channels. See "Fig. X: Logic block diagram"Figure 6 for a block diagram of the 23BA40. Processing function The I/O micro controller (EAP Ein- Ausgabe-Prozessor / Input- output processor) activates any output forced by the communi- cation unit (CMU) by a command output request. The EAP con- trols the time duration of a pulse output by the loaded pulse length time value. Output monitoring and supervision Any output is checked and monitored by the EAP by different tests and supervision functions: the output pattern is read back before the output is activat- ed the 24 V DC supply voltage to switch the output relays is supervised during an active output the pulse duration is controlled by the EAP any detected error is indicated by LED’s One or two pole outputs Figure Fig. 7 to Figure Fig. 9 show the different principle wirings for one or two pole command output. Settings On the 23BA40, only the rack address and the device address have to be set via the DIL- switch S1. To access S1, the top cover has to be removed. Figure 1 shows the position, Figure 2, Table 7 and Table 8 show the layout of the DIL-switch S1. Furthermore a terminating resistor of 1kΩ for the serial peripheral bus can be activated via DIL-switch S1. See Table 9. DANGER Hazardous voltage. Contact with live circuits will cause electric shock or burn. Verify that all terminals feeding dangerous contact voltages (supply voltage, input or output channels) is in secure OFF state before connecting or withdrawing the terminals. ADVICE Never remove top cover when process voltage is ap- plied! Danger! DIL-switch S1 may only be operated under off-circuit conditions (24 V supply removed) Take ESD-protective measures before removing the cov- er Signaling The board monitors and checks its functionality as well as the dialog via the peripheral bus. Detected errors are indicated and/ or transmitted by the board: by the red LED ”ST” by the red LED ”PST” by diagnostic messages LED ”ST” The „ST“ LED indicates board errors or peripheral bus errors. The „ST“ LED indicates: board runs initialization procedure board is doing a cold- or warm start board has detected a memory error (RAM or EPROM) micro controller faulty no dialog via the peripheral bus for at least 2 minutes. The board is not polled by the PBP of CMU.

Upload: trinhhuong

Post on 27-Jul-2018

284 views

Category:

Documents


10 download

TRANSCRIPT

RTU560 product line

Binary output 23BA40Connections and settings

Application, characteristics and technical data have to be takenfrom the hardware data sheet:

23BA40 Data sheet 1KGT 150 601

Operation

The 23BA40 has sixteen output relays. Each relay has its ownreturn. This allows to use individual process voltage levels for allchannels. See "Fig. X: Logic block diagram"Figure 6 for a blockdiagram of the 23BA40.

Processing function

The I/O micro controller (EAP Ein- Ausgabe-Prozessor / Input-output processor) activates any output forced by the communi-cation unit (CMU) by a command output request. The EAP con-trols the time duration of a pulse output by the loaded pulselength time value.

Output monitoring and supervision

Any output is checked and monitored by the EAP by differenttests and supervision functions:

• the output pattern is read back before the output is activat-ed

• the 24 V DC supply voltage to switch the output relays issupervised during an active output

• the pulse duration is controlled by the EAP• any detected error is indicated by LED’s

One or two pole outputs

Figure Fig. 7 to Figure Fig. 9 show the different principle wiringsfor one or two pole command output.

Settings

On the 23BA40, only the rack address and the device addresshave to be set via the DIL- switch S1. To access S1, the topcover has to be removed. Figure 1 shows the position, Figure

2, Table 7 and Table 8 show the layout of the DIL-switch S1.Furthermore a terminating resistor of 1kΩ for the serial peripheralbus can be activated via DIL-switch S1. See Table 9.

DANGER

Hazardous voltage.

Contact with live circuits will cause electric shock or burn.

Verify that all terminals feeding dangerous contact voltages(supply voltage, input or output channels) is in secure OFFstate before connecting or withdrawing the terminals.

ADVICE

• Never remove top cover when process voltage is ap-plied! Danger!

• DIL-switch S1 may only be operated under off-circuitconditions (24 V supply removed)

• Take ESD-protective measures before removing the cov-er

Signaling

The board monitors and checks its functionality as well as thedialog via the peripheral bus. Detected errors are indicated and/or transmitted by the board:

• by the red LED ”ST”• by the red LED ”PST”• by diagnostic messages

LED ”ST”

The „ST“ LED indicates board errors or peripheral bus errors.

The „ST“ LED indicates:

• board runs initialization procedure• board is doing a cold- or warm start• board has detected a memory error (RAM or EPROM)• micro controller faulty• no dialog via the peripheral bus for at least 2 minutes. The

board is not polled by the PBP of CMU.

2 | 1KGT 150 602 V002 1 - Binary output 23BA40

LED ”PST”

The LED indicates an error at command output:

• 24 V DC for the output relays failed during command output• Time-out PBP during active output. Any active output is

stopped (switched off).

LED ”1...16”

The LED’s are dedicated to the output relays. The LED’s are ONthe time an output is active (pulse or persistent).

LED ”5V”

The LED indicates that the 5 V DC power is applied.

X 1

X 3

X 5X 6

S1

X 4Pin 3Pin 2Pin 1

Pin 3Pin 2Pin 1

Pin 1Pin 2Pin 3

Pin 1Pin 2Pin 3

X 2

Figure 1: Position of the indication-, connection- and control elements

Connection elements

Process connectors X1, X2: 16-pole pluggable screw-termi-nal: Phoenix ContactMVSTBR 2,5/16-STF-5,08

Power supply and /E-line X3,X4:

3-pole pluggable screw-termi-nal: Phoenix ContactMVSTBR 2,5/3-ST-5,08

Serial RTU peripheral busX5,X6:

3-pole pluggable screw-termi-nal: Phoenix ContactMVSTBR 2,5/3-ST-5,08

Several devices 23BA40 and 23BE40 can be mounted side byside on an EN-rail. The connectors X3, X4 and X5, X6 are suitablefor through-wiring. The internal wiring is designed for up to 8devices 23BA40 or 23BE40.

The Event-line (E) connects all devices of one string (up to 8). Nofurther connection to other devices is allowed. The cable shieldshall be grounded near the devices.

Pin assignment for X1

Pin Signal name

1 O1

2 O2

Pin Signal name

3 O3

4 O4

5 C1

6 C2

7 C3

8 C4

9 C5

10 C6

11 C7

12 C8

13 O5

14 O6

15 O7

16 O8

Pin assignment for X2

Pin Signal name

1 O16

2 O15

3 O14

4 O13

5 C16

6 C15

7 C14

8 C13

9 C12

10 C11

11 C10

12 C9

13 O12

14 O11

15 O10

16 O9

Pin assignment for X3

Pin Signal name

1 +24V

2 0V

3 E

Binary output 23BA40 - 1KGT 150 602 V002 1 | 3

Pin assignment for X4

Pin Signal name

1 E

2 0V

3 +24V

Pin assignment for X5

Pin Signal name

1 TA

2 TB

3 0V

Pin assignment for X6

Pin Signal name

1 0V

2 TB

3 TA

Figure 2: Assignment DIL-switch S1

DIL-switch S1: Slot/Device address

Slot/Device

address

S1/5 S1/6 S1/7 S1/8

1 0 0 0 0

2 0 0 0 1

3 0 0 1 0

4 0 0 1 1

5 0 1 0 0

6 0 1 0 1

7 0 1 1 0

8 0 1 1 1

ADVICE

For the RTU200/232 the configured Slot/Device address ofthe DIL-switch has to be incremented by one for the corre-sponding Slot address in RTUtil.

DIL-switch S1: Rack address

Rack

address

S1/2 S1/3 S1/4

0 not allowed

1 0 0 1

2 0 1 0

3 0 1 1

4 1 0 0

5 1 0 1

6 1 1 0

7 1 1 1

DIL-switch S1: Terminating resistor

Terminating resistor B S1/1

Open 0

Terminated 1

From the software point-of-view the module 23BA40 is treatedas a 23BA20 mounted in a dedicated rack on a dedicated slot(device address). This virtual rack has 8 different devices.

One power supply unit 560PSU40 is able to drive up to 8 mod-ules 23BA40.

The following configuration and wiring rules apply to 23BA40 and23BE40 as well:

• Not more than 8 modules per 560PSU40• Not more than 8 modules per rack• All modules with connected E-line must have the same rack

address• The E-line must be wired between 23BE40 and 23BA40

modules with same rack address, but need not to be con-nected to any other device

• Terminate only the last module within a bus segment

The following figures are examples for the possible connectionsof different modules:

4 | 1KGT 150 602 V002 1 - Binary output 23BA40

Figure 3: Connection principle of 23BE40 / 23BA 40

Figure 4: Wiring of two complete virtual racks with 8 ‘slots’ each

Binary output 23BA40 - 1KGT 150 602 V002 1 | 5

Figure 5: Wiring of different virtual racks, one or more bus segments

6 | 1KGT 150 602 V002 1 - Binary output 23BA40

Figure 6: Logic block diagram

Binary output 23BA40 - 1KGT 150 602 V002 1 | 7

Figure 7: Binary output 1 pole, same process voltage circuit for all outputs

8 | 1KGT 150 602 V002 1 - Binary output 23BA40

Figure 8: Binary output 1 pole. Different process voltage sources for k01 – k08 and k09 – k16

Binary output 23BA40 - 1KGT 150 602 V002 1 | 9

Figure 9: Binary output 2 pole. Same process voltage level for all outputs

10 | 1KGT 150 602 V002 1 - Binary output 23BA40

ABB AGPower Systems DivisionP.O. Box 10 03 5168128 Mannheim, Germany

www.abb.com/substationautomation

Note:

The specifications, data, design or other information contained in this document

(the “Brochure”) - together: the “Information” - shall only be for information pur-

poses and shall in no respect be binding. The Brochure does not claim to be ex-

haustive. Technical data in the Information are only approximate figures. We re-

serve the right at any time to make technical changes or modify the contents of

this document without prior notice. The user shall be solely responsible for the

use of any application example or information described within this document.

The described examples and solutions are examples only and do not represent

any comprehensive or complete solution. The user shall determine at its sole

discretion, or as the case may be, customize, program or add value to the ABB

products including software by creating solutions for the end customer and to

assess whether and to what extent the products are suitable and need to be ad-

justed or customized.

This product is designed to be connected to and to communicate information

and data via a network interface. It is the users sole responsibility to provide and

continuously ensure a secure connection between the product and users or end

customers network or any other network (as the case may be). The user shall es-

tablish and maintain any appropriate measures (such as but not limited to the in-

stallation of firewalls, application of authentication measures, encryption of da-

ta, installation of anti-virus programs, etc) to protect the product, the network, its

system and the interface against any kind of security breaches, unauthorized ac-

cess, interference, intrusion, leakage and/or theft of data or information. ABB AG

is not liable for any damages and/or losses related to such security breaches, any

unauthorized access, interference, intrusion, leakage and/or theft of data or infor-

mation.

ABB AG shall be under no warranty whatsoever whether express or implied and

assumes no responsibility for the information contained in this document or for

any errors that may appear in this document. ABB AG's liability under or in con-

nection with this Brochure or the files included within the Brochure, irrespective

of the legal ground towards any person or entity, to which the Brochure has been

made available, in view of any damages including costs or losses shall be exclud-

ed. In particular ABB AG shall in no event be liable for any indirect, consequen-

tial or special damages, such as – but not limited to – loss of profit, loss of pro-

duction, loss of revenue, loss of data, loss of use, loss of earnings, cost of cap-

ital or cost connected with an interruption of business or operation, third party

claims. The exclusion of liability shall not apply in the case of intention or gross

negligence. The present declaration shall be governed by and construed in ac-

cordance with the laws of Switzerland under exclusion of its conflict of laws rules

and of the Vienna Convention on the International Sale of Goods (CISG).

ABB AG reserves all rights in particular copyrights and other intellectual property

rights. Any reproduction, disclosure to third parties or utilization of its contents -

in whole or in part - is not permitted without the prior written consent of ABB AG.

© Copyright ABB 2015

All rights reserved