constant power led emergency driver...led emergency driver lem-pxx-060-a-u-pt features 1. emergency...

12
McWong International, Inc. 1/12 1921 Arena Boulevard, Sacramento, California 95834 Tel: (916) 371-8080 Fax: (916) 371-6666 Email: [email protected] Web: www.mcwonginc.com CONSTANT POWER LED EMERGENCY DRIVER LEM-Pxx-060-A-U-PT FEATURES 1. Emergency operation of LED luminaires for factory installation 2. Perfectly compatible with most AC LED drivers 3. Constant emergency power output: Class 2 output voltage (10-60V), output current auto adjustable 4. One single driver model pairing with different battery packs 5. Field-replaceable NiMH battery pack with quick connect 6. Auto Test 7. Slim aluminum housing 8. Suitable for indoor, dry and damp applications E467188

Upload: others

Post on 15-Mar-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: CONSTANT POWER LED EMERGENCY DRIVER...LED EMERGENCY DRIVER LEM-Pxx-060-A-U-PT FEATURES 1. Emergency operation of LED luminaires for factory installation 2. Perfectly compatible with

McWong International, Inc.

1/12

1921 Arena Boulevard, Sacramento, California 95834 Tel: (916) 371-8080 Fax: (916) 371-6666 Email: [email protected]

Web: www.mcwonginc.com

CONSTANT POWER

LED EMERGENCY DRIVER

LEM-Pxx-060-A-U-PT

FEATURES

1. Emergency operation of LED luminaires for factory

installation

2. Perfectly compatible with most AC LED drivers

3. Constant emergency power output: Class 2 output voltage

(10-60V), output current auto adjustable

4. One single driver model pairing with different battery packs

5. Field-replaceable NiMH battery pack with quick connect

6. Auto Test

7. Slim aluminum housing

8. Suitable for indoor, dry and damp applications

E467188

Page 2: CONSTANT POWER LED EMERGENCY DRIVER...LED EMERGENCY DRIVER LEM-Pxx-060-A-U-PT FEATURES 1. Emergency operation of LED luminaires for factory installation 2. Perfectly compatible with

McWong International, Inc.

2/12

1921 Arena Boulevard, Sacramento, California 95834 Tel: (916) 371-8080 Fax: (916) 371-6666 Email: [email protected]

Web: www.mcwonginc.com

CHARACTERISTICS

LED Emergency Driver

Type LEM-P05-060-A-U-PT LEM-P09-060-A-U-PT LEM-P15-060-A-U-PT LEM-P25-060-A-U-PT

Rated voltage 120-277VAC 50/60Hz

Rated current 0.05A (Max.) 0.06A (Max.) 0.08A (Max.) 0.15A (Max.)

Rated power 3W (Max.) 4W (Max.) 5W (Max.) 7W (Max.)

Emergency output power 5.5W@1500mAh Battery 9W@2100mAh Battery 15.5W@3800mAh Battery 25.5W @4500mAh Battery

Output voltage 13-60VDC 14-60VDC 15-60VDC 25-60VDC

Output current 1 A (Max.)

Output current of AC driver 5 A (Max.)

Operation frequency 320kHz≥f≥50kHz

Power Factor 120V>0.4; 277V>0.3

Operation temperature 0-50℃

Efficiency 80%

Abnormal protection Over load, Inrush current limiting, over temperature, open circuit, short-circuit protection with auto-reset

Life time 5 years

EMC/FCC/IC standard EN 55015, EN 61547, EN 61000-3-2, EN 61000-3-3; FCC part 15, ICES-005

Safety standard EN 61347-1, EN 61347-2-7, UL924,CSA C.22.2 No. 141

Dimension mm[inch] L125 [4.92] x W65 [2.56] x H22 [0.87] Mounting Center: 117 [4.61]

Battery Packs

Model No. BCP-NiMH-9.6-1.5 BCP-NiMH-10.8-2.1 BCP-NiMH-10.8-3.8 BCP-NiMH-14.4-4.5

Nominal Voltage (V) 9.6 10.8 10.8 14.4

Pack Capacity (Ah) 1.5 2.1 3.8 4.5

Output Wattage (W) 5 9 15 25

Chemistry NiMH

Charging time 24 Hours

Discharge time >90Minutes

Charging current (A) 0.08 0.11 0.19 0.23

Charging cycles >500

Dimension mm[inch]

L100[3.94] x W57[2.24]

x H14[0.55], Mounting

Center: 115[4.53]

L150[5.91] x W51[2.01] x

H17[0.67], Mounting

Center: 165[6.50]

L213[8.39] x W56.4[2.22] x

H18.8[0.74], Mounting

Center: 230[9.06]

L196[7.72] x W76.5[3.01]

x H26[1.02], Mounting

Center: 211[8.31]

Page 3: CONSTANT POWER LED EMERGENCY DRIVER...LED EMERGENCY DRIVER LEM-Pxx-060-A-U-PT FEATURES 1. Emergency operation of LED luminaires for factory installation 2. Perfectly compatible with

McWong International, Inc.

3/12

1921 Arena Boulevard, Sacramento, California 95834 Tel: (916) 371-8080 Fax: (916) 371-6666 Email: [email protected]

Web: www.mcwonginc.com

WIRING CONFIGURATION

LEM-Pxx-060-A-U

Terminal block with external battery pack, choosing the different combination of the DIP switches

and the corresponding battery pack to have different emergency power output.

Page 4: CONSTANT POWER LED EMERGENCY DRIVER...LED EMERGENCY DRIVER LEM-Pxx-060-A-U-PT FEATURES 1. Emergency operation of LED luminaires for factory installation 2. Perfectly compatible with

McWong International, Inc.

4/12

1921 Arena Boulevard, Sacramento, California 95834 Tel: (916) 371-8080 Fax: (916) 371-6666 Email: [email protected]

Web: www.mcwonginc.com

DIMENSION

LED Emergency Driver

Item No. L

mm [inch]

M

mm [inch]

W

mm [inch]

H

mm [inch]

Total Weight

kg (lbs)

LEM-P05-060-A-U-PT

125 [4.92] 117 [4.61] 65 [2.56] 22 [0.87]

0.50 [1.10]

LEM-P09-060-A-U-PT 0.60 [1.32]

LEM-P15-060-A-U-PT 1.00 [2.20]

LEM-P25-060-A-U-PT 1.26 [2.78]

Notes:

1.Dimension unit: mm[inch]

2.Dimension tolerance: +/-1[0.04]

3. Total Weight includes LEM and corresponding battery pack

Page 5: CONSTANT POWER LED EMERGENCY DRIVER...LED EMERGENCY DRIVER LEM-Pxx-060-A-U-PT FEATURES 1. Emergency operation of LED luminaires for factory installation 2. Perfectly compatible with

McWong International, Inc.

5/12

1921 Arena Boulevard, Sacramento, California 95834 Tel: (916) 371-8080 Fax: (916) 371-6666 Email: [email protected]

Web: www.mcwonginc.com

DIMENSION

BATTERY PACK

Battery

Size

BCP-NiMH-9.6-1.5

mm [inch]

BCP-NiMH-10.8-2.1

mm [inch]

BCP-NiMH-10.8-3.8

mm [inch]

BCP-NiMH-14.4-4.5

mm [inch]

L 100 [3.94] ± 2 [0.08] 150 [5.91] ± 1.5 [0.06] 213 [8.39] ± 3 [0.12] 196 [7.72] ± 3 [0.12]

W 57 [2.24] ± 2 [0.08] 51 [2.01] ± 1.5 [0.06] 56.4 [2.22] ± 1 [0.04] 76.5 [3.01] ± 1.5 [0.06]

D ø14 [0.55] ± 1 [0.04] ø17 [0.67] ± 1 [0.04] ø18.8 [0.74] ± 0.5 [0.02] ø 26 [1.02] ± 0.5 [0.02]

Notes:

1.Dimension unit: mm [inch]

2.Dimension tolerance: +/-1[0.04]

Page 6: CONSTANT POWER LED EMERGENCY DRIVER...LED EMERGENCY DRIVER LEM-Pxx-060-A-U-PT FEATURES 1. Emergency operation of LED luminaires for factory installation 2. Perfectly compatible with

McWong International, Inc.

6/12

1921 Arena Boulevard, Sacramento, California 95834 Tel: (916) 371-8080 Fax: (916) 371-6666 Email: [email protected]

Web: www.mcwonginc.com

DIMENSION

BATTERY MOUNTING BOX (OPTIONAL)

Battery Size

BCP-NiMH-9.6-1.5

mm [inch]

BCP-NiMH-10.8-2.1

mm [inch]

BCP-NiMH-10.8-3.8

mm [inch]

L 124 [4.88] 176 [6.93] 241 [9.49]

M 116 [4.57] 168 [6.61] 233 [9.17]

Notes:

1.Dimension unit: mm [inch]

2.Dimension tolerance: +/-1[0.04]

Page 7: CONSTANT POWER LED EMERGENCY DRIVER...LED EMERGENCY DRIVER LEM-Pxx-060-A-U-PT FEATURES 1. Emergency operation of LED luminaires for factory installation 2. Perfectly compatible with

McWong International, Inc.

7/12

1921 Arena Boulevard, Sacramento, California 95834 Tel: (916) 371-8080 Fax: (916) 371-6666 Email: [email protected]

Web: www.mcwonginc.com

DIMENSION

BATTERY MOUNTING BOX (OPTIONAL)

Battery Size

BCP-NiMH-14.4-4.5

mm [inch]

L 232 [9.13]

M 224 [8.82]

Notes:

1.Dimension unit: mm [inch]

2.Dimension tolerance: +/-1[0.04]

Page 8: CONSTANT POWER LED EMERGENCY DRIVER...LED EMERGENCY DRIVER LEM-Pxx-060-A-U-PT FEATURES 1. Emergency operation of LED luminaires for factory installation 2. Perfectly compatible with

McWong International, Inc.

8/12

1921 Arena Boulevard, Sacramento, California 95834 Tel: (916) 371-8080 Fax: (916) 371-6666 Email: [email protected]

Web: www.mcwonginc.com

DIMENSION

BATTERY: 9.6V 1500MAH

BATTERY:10.8V 2100MAH

Page 9: CONSTANT POWER LED EMERGENCY DRIVER...LED EMERGENCY DRIVER LEM-Pxx-060-A-U-PT FEATURES 1. Emergency operation of LED luminaires for factory installation 2. Perfectly compatible with

McWong International, Inc.

9/12

1921 Arena Boulevard, Sacramento, California 95834 Tel: (916) 371-8080 Fax: (916) 371-6666 Email: [email protected]

Web: www.mcwonginc.com

DIMENSION

BATTERY:10.8V 3800MAH

BATTERY:14.4V 4500MAH

BATTERY EXTENSION CORD

Page 10: CONSTANT POWER LED EMERGENCY DRIVER...LED EMERGENCY DRIVER LEM-Pxx-060-A-U-PT FEATURES 1. Emergency operation of LED luminaires for factory installation 2. Perfectly compatible with

McWong International, Inc.

10/12

1921 Arena Boulevard, Sacramento, California 95834 Tel: (916) 371-8080 Fax: (916) 371-6666 Email: [email protected]

Web: www.mcwonginc.com

WIRING DIAGRAM

LED TEST SWITCH

LEM-Pxx-060-A-U-PT

Page 11: CONSTANT POWER LED EMERGENCY DRIVER...LED EMERGENCY DRIVER LEM-Pxx-060-A-U-PT FEATURES 1. Emergency operation of LED luminaires for factory installation 2. Perfectly compatible with

McWong International, Inc.

11/12

1921 Arena Boulevard, Sacramento, California 95834 Tel: (916) 371-8080 Fax: (916) 371-6666 Email: [email protected]

Web: www.mcwonginc.com

OPERATION/TESTING/MAINTENANCE

OPERATION

When AC power is applied, the LED test switch is illuminated, indicating that the batteries are being charged.

When AC power fails, the LEM-Pxx-060-A-U-PT automatically switches to emergency (battery) power, which

can be maintained for >90 minutes, operating the LED load specified emergency power level. The LED test

switch (LTS) is switched off. When the AC power is restored the emergency module switches the system back

to normal mode and resumes battery charging. The charging time for the full discharged battery is 24 Hours.

TESTING AND MAINTENANCE

Periodic tests are recommended to ensure the system is functioning normally:

1. Visually inspect the LED test switch (LTS) monthly. It should be illuminated when AC power is applied.

2. Conduct a 30 second discharge test by switching off the mains power every month. The LTS is switched off

and LED loads should operate at reduced illumination.

3. Conduct a 90 minute discharge test once a year. The LED loads should operate at reduced illumination for

at least 90 minutes.

AUTO TEST

The LEM-Pxx-060-A-U-PT series has integrated Auto Test functions as follows.

1. Instant Auto Test

When the system is connected and powered on, the LEM-Pxx-060-A-U-PT model will Auto Test to verify proper

connection of LED load and connection/charging of battery pack. In case of LED load or Battery pack

problem, the LTS will Flash. When the abnormal condition is corrected, the LTS will stop flashing.

2. Preprogrammed Auto Tests

• The initial monthly Auto Test begins 24 hours to 7 days after Initial power up; monthly Auto Tests repeat

once every 30 days.

• Annual Auto Tests repeat every 52 weeks after Initial Power up.

- Monthly Auto Test

Monthly Auto Test is executed every 30 days, testing:

(a) Switching of normal to emergency mode, and the reverse;

(b) Emergency operation and battery charging and discharging;

Auto Test time is ~30 seconds.

Page 12: CONSTANT POWER LED EMERGENCY DRIVER...LED EMERGENCY DRIVER LEM-Pxx-060-A-U-PT FEATURES 1. Emergency operation of LED luminaires for factory installation 2. Perfectly compatible with

McWong International, Inc.

12/12

1921 Arena Boulevard, Sacramento, California 95834 Tel: (916) 371-8080 Fax: (916) 371-6666 Email: [email protected]

Web: www.mcwonginc.com

OPERATION/TESTING/MAINTENANCE

- Annual Auto Test

Annual Auto Test is executed every 52 weeks after 24 hours full charging, testing:

(a) battery voltage is equal or higher than 87.5% of initial voltage after 24 hours full charging;

(b) emergency operation meets 90 minutes minimum; And battery voltage after 90 minutes emergency

operation is equal or higher than 87.5% of initial voltage.

During Annual Auto Test, in case of power failure and cannot be on till the auto test completes, the Auto Test

will be executed again 24 hours after the power has been resumed.

If the emergency mode causes the battery discharged completely under the power-off condition, the Annual

Auto Test will be reset after power has been resumed.

MANUAL TEST

- Press LTS one time to simulate emergency mode.

- Press LTS 2 times within 5 seconds to initiate monthly test. Upon completion of this test, the Monthly

auto-test counter is set to repeat after 30 days.

- Press LTS 3 times within 5 seconds to initiate annual test. Upon completion of this test, the Annual

auto-test counter is set to repeat after 52 weeks.

- During the manual test, press and hold the LTS for longer than 3 seconds or press LTS 3 times to terminate

the test. (The next-occurring preprogrammed Auto Tests – Monthly and Annual -- will remain scheduled).

LED TEST SWITCH (LTS) INDICATION

- LTS slow flashing: In charging

- LTS on: Normal

- LTS off: Power failure

- LTS gradual change: In testing

- LTS quick flashing: Abnormal