led emergency driver installation instruction · led emergency driver model: veml20mv-1 input...

2
LED EMERGENCY DRIVER Model: VEML20MV-1 Input Voltage 120-277 VAC, 50/60 Hz Lamps Operated Other Class 2 LED lamp or module Output Voltage 12-50 VDC Operating Temperature 0°C/30°F - 50°C/122°F Battery 24-48 hr recharge, LiFePO4 options in 90 minutes: 5W, 10W, 15W and 20W Approval UL and cUL 924 Listed Technical Specifications IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS This guide contains important information regarding installation and operation. Please keep this guide for future reference. WARNING: READ AND FOLLOW ALL SAFETY INSTRUCTIONS. When using electrical equipment, basic safety precautions should always be followed including the following: 1. Do not use outdoors. 2. Do not mount near gas or electric heaters. 3. Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel. 4. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. 5.Do not use this equipment for other than its intended use. 6. This equipment has not been investigated for use in an air-handling fixture, it is not suitable in a heated air outlet. 7. Use with grounded, UL Listed, damp location rated fixtures and case should be connected to grounding. 8. The drivers are intended for ordinary locations and for permanent installation into one or more Listed emergency luminaires. Operation · Suitable for use in 0°C/30°F - 50°C/122°F · The charging indicator light would be on to indicate the battery is being charged when AC power is appied Installation · AC power has to be off before installation · Follow the wiring diagram to connect the LED emergency dirver to LED driver and lamp · Please ensure the electricity connections confirm to the National Electrical Code and local regulations · Do not connect to AC power until the battery connection is jointed · The battery needs to be charged for one hour in order to have short-term testing on the emergency function. Before having a long-term emergency function testing, the battery in the EM driver has to be charged for 24-48 hours according to battery charging rate Operates with Espen CoreTech type C LED lamp, VersaLinear LED module, or any other ESPEN Technology, Inc. 12257 Florence Ave Santa Fe Springs, CA 90670 Phone: (562) 529-2938 Fax: (562) 529-2978 Toll Free: (886) 933-7736 Email: [email protected] www.espentech.com Emergency Operation 90 mins Emergency mode rated power 90 min in 5W, 10W, 15W and 20W selectable Class 2 LED lamp or module 2’ - 4’ of Espen CoreTech type C LED lamp or VersaLinear LED module Installation Instruction

Upload: others

Post on 07-Aug-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: LED EMERGENCY DRIVER Installation Instruction · LED EMERGENCY DRIVER Model: VEML20MV-1 Input Voltage 120-277 VAC, 50/60 Hz Lamps Operated manufacturer may cause an unsafe condition

LEDEMERGENCY DRIVER

Model: VEML20MV-1

Input Voltage120-277 VAC, 50/60 Hz

Lamps Operated●

● Other Class 2 LED lamp or module

Output Voltage12-50 VDC

Operating Temperature0°C/30°F - 50°C/122°F

Battery24-48 hr recharge, LiFePO4options in 90 minutes: 5W, 10W,15W and 20W

ApprovalUL and cUL 924 Listed

Technical Specifications

IMPORTANT SAFEGUARDSREAD AND FOLLOW ALL SAFETY INSTRUCTIONS

This guide contains important information regarding installation and operation.Please keep this guide for future reference.

WARNING: READ AND FOLLOW ALL SAFETY INSTRUCTIONS.

When using electrical equipment, basic safety precautions should always be followed including the following:

1. Do not use outdoors.2. Do not mount near gas or electric heaters.3. Equipment should be mounted in locations and at heights where it will not be subjected to tampering by unauthorized personnel.4. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.5.Do not use this equipment for other than its intended use.6. This equipment has not been investigated for use in an air-handling fixture, it is not suitable in a heated air outlet.7. Use with grounded, UL Listed, damp location rated fixtures and case should be connected to grounding.8. The drivers are intended for ordinary locations and for permanent installation into one or more Listed emergency luminaires.

Operation · Suitable for use in 0°C/30°F - 50°C/122°F · The charging indicator light would be on to indicate the battery is being charged when AC power is appied

Installation · AC power has to be off before installation · Follow the wiring diagram to connect the LED emergency dirver to LED driver and lamp · Please ensure the electricity connections confirm to the National Electrical Code and local regulations · Do not connect to AC power until the battery connection is jointed · The battery needs to be charged for one hour in order to have short-term testing on the emergency function. Before having a long-term emergency function testing, the battery in the EM driver has to be charged for 24-48 hours according to battery charging rate

Operates with Espen CoreTech type C LED lamp, VersaLinear LED module, or any other

ESPEN Technology, Inc.12257 Florence Ave ● Santa Fe Springs, CA 90670

Phone: (562) 529-2938 ● Fax: (562) 529-2978 ● Toll Free: (886) 933-7736Email: [email protected] ● www.espentech.com

Emergency Operation90 mins

Emergency mode rated power90 min in 5W, 10W, 15W and 20Wselectable

Class 2 LED lamp or module

2’ - 4’ of Espen CoreTech type C LED lamp or VersaLinear LED module

Installation Instruction

Page 2: LED EMERGENCY DRIVER Installation Instruction · LED EMERGENCY DRIVER Model: VEML20MV-1 Input Voltage 120-277 VAC, 50/60 Hz Lamps Operated manufacturer may cause an unsafe condition

Wiring Diagram:

Specification data is based on tests performed in a controlled environment and represents relative performance. Actual performance can vary depending on operating conditions. Application and performance data subject to change without notice. All specifications are nominal unless noted otherwise.

ESPEN Technology, Inc.12257 Florence Ave ● Santa Fe Springs, CA 90670

Phone: (562) 529-2938 ● Fax: (562) 529-2978 ● Toll Free: (886) 933-7736Email: [email protected] ● www.espentech.com

BATTERY

YEL

RED/WHT

EmergencyDriverVEML20MV-1

Current adjustment (dip switch):

Driver (N)

WHT/BLK

Driver (L)

L

NBLACK

WHITE

Case must be grounded

Test Switch

RED (Driver +)

LED Driver

LED lamp/module+

_

BLUE (Driver -)

RED

Dip Switch SettingEmergency Mode

Output PowerBattery Charging

CurrentEmergency Mode

Output VoltageEmergency Mode

Output Current

5W

10W

15W

20W

12-50V

12-50V

12-50V

12-50V

416-100mA 60mA

1250-300mA

1400-400mA

830-200mA 100mA

160mA

210mA

12

31

23

12

31

23