UPS TECHNOLOGY UPDATE
2
TYPES OF UPS TECHNOLOGIES
•STATIC, DOUBLE CONVERSION
•STATIC, LINE INTERACTIVE
•FLYWHEEL-BASED
•ROTARY
•OFF-LINE
Consult + Engineer + Commission
© All Rights Reserved
UPS TECHNOLOGY UPDATE
3
STATIC, DOUBLE CONVERSION UPS TOPOLOGY
•NORMAL POWER PATH: INPUT-RECTIFIER-DC BUS- INVERTER-OUTPUT
•BYPASS POWER PATH: INPUT-STATIC SWITCH-OUTPUT
•STORED POWER PATH: BATTERY/FLYWHEEL-DC BUS- INVERTER-OUTPUT
•MAJOR MANUFACTURERS: GE, LIEBERT, MGE, MITSUBISHI, POWERWARE, TOSHIBA
Consult + Engineer + Commission
© All Rights Reserved
UPS TECHNOLOGY UPDATE
4
Consult + Engineer + Commission
© All Rights Reserved
UPS TECHNOLOGY UPDATE
5
STATIC, DOUBLE CONVERSION UPS CHANGES FOR INCREASED OPERATING EFFICIENCY
•PWM IGBT RECTIFIERS INSTEAD OF SCRS•PWM IGBT INVERTERS•ELIMINATE INPUT AND OUTPUT TRANSFORMERS•USER-SELECTABLE OFFLINE OPERATION•USER-SELECTABLE CAPACITY CONTROL•DISTRIBUTED OR SYSTEM STATIC BYPASS SWITCH
Consult + Engineer + Commission
© All Rights Reserved 6
STATIC, DOUBLE CONVERSION UPS OPERATING EFFICIENCY
•TYPICALLY 91%-96% AT FULL LOAD AND 90%- 94% AT HALF LOAD
•USER-SELECTABLE OFFLINE 98%
•USER-SELECTABLE CAPACITY CONTROL CAN IMPROVE % AT LOW LOADS
UPS TECHNOLOGY UPDATE
Consult + Engineer + Commission
© All Rights Reserved
UPS TECHNOLOGY UPDATE
7
THE FLEAS THAT COME WITH THE DOG, PART 1
•ELIMINATING TRANSFORMERS REDUCES DC BUS SAFETY•INDUSTRY TREND IS TO ELIMINATE TRANSFORMERS•ELIMINATING THE OUTPUT TRANSFORMER MAY ELIMINATE A WYE-CONNECTED OUTPUT•INDUSTRY TREND IS TO PROVIDE DISTRIBUTED STATIC BYPASS SWITCHES•IN USER-SELECTABLE OFFLINE MODE, SOME TRANSIENTS COULD GET THROUGH BEFORE THE UPS CAN REACT
Consult + Engineer + Commission
© All Rights Reserved
UPS TECHNOLOGY UPDATE
8
STATIC, LINE-INTERACTIVE UPS TOPOLOGY
•NORMAL POWER PATH: INPUT-MAIN STATIC SWITCH-OUTPUT
•BYPASS POWER PATH: INPUT-ALTERNATE STATIC SWITCH-OUTPUT
•STORED POWER PATH: BATTERY-DC BUS-INVERTER- OUTPUT
•MANUFACTURER: APC (SYMMETRA MW)
Consult + Engineer + Commission
© All Rights Reserved
UPS TECHNOLOGY UPDATE
9
Consult + Engineer + Commission
© All Rights Reserved
UPS TECHNOLOGY UPDATE
10
STATIC, LINE INTERACTIVE UPS CHANGES FOR INCREASED OPERATING EFFICIENCY
•IMPROVED FIRMWARE CONTROL
STATIC, LINE INTERACTIVE UPS OPERATING EFFICIENCY
•TYPICALLY 97% AT FULL LOAD, 96% AT HALF LOAD AND 94% AT QUARTER LOAD
Consult + Engineer + Commission
© All Rights Reserved
UPS TECHNOLOGY UPDATE
11
THE FLEAS THAT COME WITH THE DOG, PART 2
•REDUCED DC BUS SAFETY
•SOME TRANSIENTS COULD GET THROUGH BEFORE THE UPS CAN REACT
Consult + Engineer + Commission
© All Rights Reserved
UPS TECHNOLOGY UPDATE
12
FLYWHEEL-BASED UPS TOPOLOGY
•NORMAL POWER PATH: INPUT-MAIN STATIC SWITCH-INDUCTOR-OUTPUT
•BYPASS POWER PATH: INPUT-ALTERNATE STATIC SWITCH-OUTPUT
•STORED POWER PATH: FLYWHEEL-CONVERTER- INDUCTOR-OUTPUT
•MANUFACTURER: ACTIVE POWER
Consult + Engineer + Commission
© All Rights Reserved
UPS TECHNOLOGY UPDATE
13
Consult + Engineer + Commission
© All Rights Reserved
UPS TECHNOLOGY UPDATE
14
FLYWHEEL-BASED UPS CHANGES FOR INCREASED OPERATING EFFICIENCY
•IMPROVED FIRMWARE CONTROL
STATIC, LINE INTERACTIVE UPS OPERATING EFFICIENCY
•TYPICALLY 98% AT FULL LOAD AND 96% AT HALF LOAD
Consult + Engineer + Commission
© All Rights Reserved
UPS TECHNOLOGY UPDATE
15
THE FLEAS THAT COME WITH THE DOG, PART 3
•LIMITED ENERGY STORAGE – 14 SECONDS
•SYSTEM CAPACITY LIMITED BY THE CAPACITY OF ONE STANDBY GENERATOR
Consult + Engineer + Commission
© All Rights Reserved
UPS TECHNOLOGY UPDATE
16
BASIC ROTARY UPS TOPOLOGY
•NORMAL POWER PATH: INPUT-RECTIFIER-INVERTER-SYNCHRONOUS MACHINE-OUTPUT
•BYPASS POWER PATH: INPUT-STATIC SWITCH - SYNCHRONOUS MACHINE –OUTPUT
•STORED POWER PATH: BATTERY-DC BUS-INVERTER- SYNCHRONOUS MACHINE-OUTPUT
•MANUFACTURER: PILLER
Consult + Engineer + Commission
© All Rights Reserved
UPS TECHNOLOGY UPDATE
17
Consult + Engineer + Commission
© All Rights Reserved
UPS TECHNOLOGY UPDATE
18
VARIATION ON ROTARY UPS TECHNOLOGY, AKA DYNAMIC ROTARY UPS (DRUPS)
•NORMAL POWER PATH: INPUT-RECTIFIER-COUPLING CHOKE-OUTPUT•BYPASS POWER PATH: INPUT-BYPASS SWITCH - OUTPUT•STORED POWER PATH: ENGINE-COUPLING-ENERGY ACCUMULATOR-SYNCHRONOUS MACHINE- COUPLING CHOKE-OUTPUT•CAN OPERATE AT LOW VOLTAGE OR MEDIUM VOLTAGE •MANUFACTURERS: EURO-DIESEL, HITEC, PILLER
Consult + Engineer + Commission
© All Rights Reserved
UPS TECHNOLOGY UPDATE
19
Consult + Engineer + Commission
© All Rights Reserved
UPS TECHNOLOGY UPDATE
20
ROTARY UPS CHANGES FOR INCREASED OPERATING EFFICIENCY
•IMPROVED FIRMWARE CONTROL•USER-SELECTABLE OFFLINE OPERATION
ROTARY UPS OPERATING EFFICIENCY
•TYPICALLY 92% AT FULL LOAD AND 88% AT HALF LOAD (BASIC)•TYPICALLY 96% AT FULL LOAD AND 48% AT HALF LOAD (VARIATION)
Consult + Engineer + Commission
© All Rights Reserved
UPS TECHNOLOGY UPDATE
21
THE FLEAS THAT COME WITH THE DOG, PART 4
•VARIATION IS THE MOST UPS CAPACITY/SQUARE FOOT OF BUILDING AREA
•VARIATION HAS CONSTANT LOSSES, REGARDLESS OF LOAD
•VARIATION CAN SUPPLY LARGE MEDIUM VOLTAGE SYSTEMS (VOLTAGE VARIES
BY MANUFACTURER)
Consult + Engineer + Commission
© All Rights Reserved
UPS TECHNOLOGY UPDATE
22
OFFLINE UPS TOPOLOGY
•NORMAL POWER PATH: INPUT-STATIC SWITCH- OUTPUT•BYPASS POWER PATH: INPUT-BYPASS SWITCH- OUTPUT•STORED POWER PATH: BATTERY-INVERTER-STEPUP TRANSFORMER-OUTPUT•CAN OPERATE AT LOW OR MEDIUM VOLTAGE (UP TO 25KV)•MANUFACTURER: S&C
Consult + Engineer + Commission
© All Rights Reserved 23
Consult + Engineer + Commission
© All Rights Reserved
UPS TECHNOLOGY UPDATE
24
OFFLINE UPS CHANGES FOR INCREASED OPERATING EFFICIENCY
•CAPACITY UP TO 16MW PER SYSTEM•IMPROVED FIRMWARE•CAN ACCOMMODATE WET CELL OR VRLA BATTERIES•CAN ACCOMMODATE UP TO 20 MINUTES BATTERY OPERATION AT FULL LOAD•CAN BE INSTALLED INDOORS OR OUT DOORS•CAN UTILIZE METAL-ENCLOSED OR METAL-CLAD SWITCHGEAR•DISTRIBUTED OR SYSTEM STATIC BYPASS SWITCH
Consult + Engineer + Commission
© All Rights Reserved 25
OFFLINE UPS OPERATING EFFICIENCY
•TYPICALLY 98%-99% AT ALL LOADS
THE FLEAS THAT COME WITH THE DOG, PART 5
•SOME TRANSIENTS COULD GET THROUGH BEFORE THE UPS CAN REACT